Channel Safety Systems SoHo Installation Instructions

SoHo
LED Luminaire from Channel Safety Systems
Emergency Lighting Spacing Table
Luminaire Spacing (Centre to centre in metres) on emergency escape routes
Transverse distance
Mounting
height
2.5m 11 lux 4.6 4.3 12.8 10.0 12.8 10.0 12.8 10.0 4.6 4.3 3.9 11.0 11.0 3.9
3m 7.5 lux 5.9 4.7 13.7 10.7 13.7 10.7 13.7 10.0 5.9 4.7 4.8 12.0 12.0 4.8
3.5m 5.6 lux 6.2 4.75 14.4 11.1 14.4 11.1 14.4 11.1 6.2 4.75 4.95 12.6 12.6 4.95
Illuminance values based on maintenance factor of 0.9
4m 4.3 lux 6.3 4.8 15.0 11.4 15.0 11.4 15.0 11.4 6.3 4.8 5.3 13.2 13.2 5.3
Illuminance values based on maintenance factor of 0.90