
LED Luminaire from Channel Safety Systems
Emergency Lighting Spacing Table
Luminaire Spacing (Centre to centre in metres) on emergency escape routes
Transverse distance
Mounting
height
2.5m 2.7 lux 4.6 2.4 10.3 5.8 9.9 5.6 9.4 5.4 4.3 2.4 2.8 6.9 6.8 2.5
4m 1.0 lux 5.5 1.0 12.6 4.9 12.0 5.3 11.7 5.2 5.0 1.0 2.3 7.9 7.6 1.6
Lux level
directly
beneath
to wall for level of
illuminance (lux)
0.2 1.0 0.2 1.0 0.2 1.0 0.2 1.0 0.2 1.0
Transverse to transverse
spacing for level of
illuminance (lux)
Transverse to axial
spacing for level of
illuminance (lux)
Axial to axial spacing
for level of illuminance
(lux)
Axial distance to wall
for level of illuminance
(lux)
Spacing (m) in Anti -
Panic Open Areas of 0.5
lux minimum (inc 0.5
border area)
Illuminance values based on maintenance factor of 0.9
1/1 | www.channelsafety.co.uk 0845 884 7000 @ sales@channelsafety.co.uk