Channel Safety Systems Brook Mk2 Installation Instructions

LED Luminaire from Channel Safety Systems
Emergency Lighting Spacing Table
Luminaire Spacing (Centre to centre in metres) on emergency escape routes
Transverse distance
Mounting
height
2.5m 4.6 lux 5.6 4.0 2.6 16.1 10.4 7.7 14.7 10.1 7.6 13.7 10.0 8.9 5.3 3.8 2.9 6.1 9.7 8.5 3.7
4m 1.9 lux 6.5 4.5 2.6 17.8 11.4 7.9 17.2 11.2 8.0 18.4 11.0 8.3 6.1 4.1 2.7 4.5 10.7 10.4 4.2
6m 0.9 6.3 4.0 3.8 19.7 11.4 8.1 19.3 13.0 8.0 19.5 12.8 7.9 7.0 4.1 3.8 4.2 11.4 10.6 4.0
Lux level
directly
beneath
to wall for level of
0.2 0.5 1.0 0.2 0.5 1.0 0.2 0.5 1.0 0.2 0.5 1.0 0.2 0.5 1.0
Transverse to transverse
spacing for level of
Transverse to axial
spacing for level of
Axial to axial spacing
for level of illuminance
(lux)
Axial distance to wall
for level of illuminance
(lux)
Spacing (m) in Anti -
Panic Open Areas of 0.5
lux minimum (inc 0.5
border area)
Illuminance values based on maintenance factor of 0.9