Champion CRN25, CRN50, CRN35, CRN75, CRN100 Instruction Manual

Page 1
SERVICE DEPARTMENT: (724) 746-1100
CRN SERIES
REFRIGERATED
COMPRESSED
AIR DRYERS
INSTRUCTION MANUAL
7610.478.39/040103
INTERNAL USE ONLY
Models: CRN25, CRN35, CRN50,
CRN75, CRN100
®
CONTENTS
GENERAL SAFETY INFORMATION ............................2
RECEIVING, MOVING, UNPACKING ..........................2
1.0 INSTALLATION ...................................................3
2.0 OPERATION.......................................................4
3.0 MAINTENANCE .................................................6
SIZING ......................................................................6
ENGINEERING DATA.................................................7
ELECTRICAL SCHEMATICS ........................................8
DIMENSIONS / WEIGHTS..........................................9
TROUBLESHOOTING...............................................10
PARTS LIST............................................................. 11
WARRANTY............................................................12
Page 2
GENERAL SAFETY INFORMATION
RECEIVING, MOVING, AND UNPACKING
1. PRESSURIZED DEVICES:
This equipment is a pressure containing device.
Do not exceed maximum operating pressure as shown on equipment serial number tag.
Make sure equipment is depressurized before working on or disassembling it for service.
2. ELECTRICAL:
This equipment requires electricity to operate.
Install equipment in compliance with all applicable electrical codes.
Standard equipment is supplied with electrical enclosures not intended for installation in hazardous environments.
Disconnect power supply to equipment when performing any electrical service work.
3. BREATHING AIR:
Air treated by this equipment may not be suitable for breathing without further purification.
Refer to applicable standards and specifications for the requirements for breathing quality air.
A. RECEIVING
This shipment has been thoroughly checked, packed and inspected before leaving our plant. It was re­ceived in good condition by the carrier and was so acknowledged.
Check for Visible Loss or Damage. If this shipment shows evidence of loss or damage at time of delivery to you, insist that a notation of this loss or damage be made on the delivery receipt by the carrier’s agent.
B. UNPACKING
Check for Concealed Loss or Damage. When a ship­ment has been delivered to you in apparent good order, but concealed damage is found upon unpack­ing, notify the carrier immediately and insist on his agent inspecting the shipment. Concealed damage claims are not our responsibility as our terms are F.O.B. point of shipment.
C. MOVING
In moving or transporting dryer, do not tip dryer onto its side.
D. STORAGE/SHUT DOWN
Dryer should not be stored outside (either packed or unpacked) or exposed to the weather. Damage to electrical and control components may result.
IMPORTANT: Do not store dryer in temperatures above 130°F, 54.4°C.
2
Page 3
IMPORTANT:
READ PRIOR TO STARTING THIS EQUIPMENT
1.0 INSTALLATION
1.1 Location
A. For typical placement in a compressed air system, see
drawing.
B. Air compressor intake–Locate air compressor so that
contaminants potentially harmful to the dryer (e.g. ammonia) are not drawn into the air system.
C. Dryer should be installed in a moderately heated, well
ventilated area. Avoid locations immediately adjacent to cold exterior windows or walls, or adjacent to high temperature ovens or boilers.
D. Clearances: Minimum requirements for free air flow
and service access Flows 25 to 100 scfm:
Front 24 inches (610 mm) Back 24 inches (610 mm) Sides 12 inches (305 mm)
E. Standard units are designed to operate in ambients:
Air-cooled: 45 to 110°F (7 to 43°C). Water-cooled: 45 to 130°F (7 to 54°C).
F. Installations in altitudes above 4500 feet (1370
meters) – Dryer is adjusted to operate in altitudes up to 4500 feet (1370 meters). If dryer is installed in an altitude above this, and has not been preset at the factory for this altitude, contact manufacturer’s Service Department.
NOTE: Outdoor installation–Standard units are designed for indoor installation. Contact manufacturer if installing outdoors.
1.2 Mounting
Mount the dryer on a level solid surface. Holes are provided in the dryer base to permanently mount the dryer to the floor.
Compressor
Aftercooler
Separator
Dryer
Oil Removal
Filter
1.3 Piping connections
A. Air Inlet - Connect compressed air line from air
source to air inlet. (See callout drawing on page 3 for air in/outlet connection locations)
Refer to Serial Number Tag for maximum working pressure. Do not exceed dryer’s Maximum Working Pressure.
NOTE: Install dryer in air system at highest pressure possible (e.g. before pressure reducing valves).
NOTE: Install dryer at coolest compressed air temperature possible. Maximum inlet compressed air temperature: 110°F (43°C). If inlet air exceeds this temperature, precool the air with an aftercooler.
B. Air Outlet—Connect air outlet to downstream
air lines.
On/Off Switch
Power On-Light
Compressor On-Light
Dew point Temperature Indicator
Separator/Filter
Optional Cold Coalescing Filter
C. By-pass piping—
If servicing the dryer without interrupting the air supply is desired, piping should include inlet and outlet valves and an air by-pass valve.
Air Outlet
Air Inlet
Power Cord
Air Flow
Drain
3
Page 4
1.4 Electrical connections
......................39
.......................4
2.0 Operation
A. Dryer is designed to operate on the voltage, phase,
and frequency listed on the serial number tag.
B. If dryer is supplied with a cord and plug, install in a
receptacle of proper voltage.
NOTE: Refrigeration condensing unit is designed to run continu­ously and should NOT be wired to cycle on/off with the air compressor. Excessive cycling of the refrigeration system could lead to premature failure and void the warranty.
1.5 Moisture separator
A. Separator (and Oil Removal Filter where applicable) has
an internal drain which automatically discharges collected condensate. It may be desirable to pipe the condensate from the Automatic Drain outlet to a suitable drain.
NOTE: Discharge is at system pressure. Drain line should be anchored.
2.1 Minimum/Maximum operating conditions
A. Maximum inlet air pressure: refer to dryer serial
number tag B. Minimum inlet air pressure: 30 psig (2.1 kgf/cm C. Maximum inlet air temperature: 110°F (43°C) D. Maximum ambient temperature:
Air-cooled models: 110°F (43°C) Water-cooled models: 130°F (54°C)
E. Minimum ambient temperature: 45°F (7°C)
I - Controller Level 1 - Standard
On/Off Switch
Switch
Legend
Power On
Light
Compressor
On Light
33°F......................39°F
1°C.......................4°C
Dew point
Temperature
Indicator
2
)
NOTE: Condensate may contain oil. Comply with applicable laws concerning proper disposal.
B. I -Controller Level 1 ONLY:
Separator has a knurled fitting with flexible drain tubing attached. Be sure knurled fitting is tightened by turning it counter-clockwise before operating dryer.
TO CLOSE
TURN COUNTERCLOCKWISE
OptionaI Controller
On/Off Switch
Switch Legend
Power On
Light
Compressor On
Light
3333°F......................39
°F
°C
1°C.......................4
Dew point
Temperature
Indicator
Push-to-Test
Condensate
Drain
Draining
4
Page 5
2.2 Start-up
1. Confirm On/Off Switch is in the “Off” position.
2. Energize dryer. Green power-on light will illuminate.
1. For minimum inlet air pressures that fall between column values, the setting for the lower pressure is recommended. (i.e. select the 100 psi column values for 124 psi inlet pressure listed in Table 1.)
2.3 Timer Drain Option
(Only Models with I-Controller Level 2) Note: The Timer Drain LED level has been pre-pro-
grammed at the factory for your specific dryer. Programming is based upon a minimum of 100 psi saturated inlet air pressure and maximum energy effi­ciency. The drain open time is fixed at one second and a small amount of air will be exhausted with each cycle. Generally, no adjustment to the timer is required.
If water is present downstream of the dryer, always verify that any condensate drains installed upstream of the dryer are draining properly before attempting to readjust the LED setting.
Table 1 Timed drain illuminated LED Settings
Inlet Pressure
75 100* 125 150 200 225
RNC25 4 5 5 5 6 6 RNC35 4 4 4 4 5 5 RNC50 3 3 4 4 4 4
FLOW (scfm)
RNC75 4 4 4 4 5 5
RNC100 3 3 4 4 4 4
* Recommended and pre-programmed factory settings for each dryer model. Assumes CAGI ADF100 inlet conditions with 100°F ambient and 10°F air-cooled aftercooler approach temperature.
Table 2 LED Legend
LED between
Illuminated Drain Cycles
st
1
nd
2
rd
3
th
4
th
5
th
6
th
7
th
8
th
9
Minutes
1 3
5 10 20 30 40 50 60
2. Where the dryer is consistently operating at less than maximum capacity, it may be possible to increase the LED set point to minimize air loss. Discretionary adjustments to the dryer should only be made on a hot, humid day when the maximum expected air load is flowing through the dryer. Failure to do so may prevent the condensate from draining completely when operating under peak load conditions.
2.4 Timer Drain Programming Mode
Dew point Temperature
Indicator
33°F......................39°F
1°C.......................4°C
(LED Illuminated indicates
drain cycle time)
Drain Interval Selector
Condensate draining LED (Flashes in programming mode)
Drain Interval Program
1. Press the “Drain Interval Program” button (the “Condensate Draining” LED will start to flash, and the illuminated LED on the “Dew Point Temperature Indicator” will identify the factory setting for “Minutes Between Drain Cycles.” (See Table 1)
2. Press and release the “Drain Interval Selector” button to sequence the “Minutes Between Drain Cycle LED’s” from left to right until reaching your selection. The “Red” LED is not used (Reference Table 2 for “Drain Cycle Intervals”)
3. To initiate the new setting, press the “Drain Interval Program” button (this will store the new setting and exit the program).
4. Exiting the Program will cause the Timer Drain to discharge and begin a new cycle.
Note: Failure to perform step 3 within 25 seconds of completing step 2 will cause the unit to revert back to the previous setting.
Note: In the event of a brief or extended period of power loss, the unit will retain the existing program setting and will begin a new cycle once power is reap­plied. Had drain been ready to drain before the loss of power, the drain bowl’s capacity would prevent down­stream flooding. Condensate will drain completely within a couple of cycles. (Manually pressing the “Push-to-Test” button would drain bowl immediately)
2.5 Operating check points
Check the following on a periodic basis: A. Green power on light is illuminated.
B. Dewpoint indicator is in green area. C. Condensate is discharging from drain.
5
Page 6
3.0 Maintenance Sizing
3.1 Condenser coil—
Clean off accumulated dust and dirt monthly or as
necessary in dirty environments.
3.2 Moisture separator/Filter and optional Oil Removal Filter—
Replace filter element when pressure drop across
dryer is excessive or annually.
3.3 Check separator daily to be sure automatic drain is discharging.
3.4 Replace or rebuild drain mechanism annually.
To facilitate service, maintenance kits are available. Please refer to page 11.
Separator Element or Optional Oil Removal Element
Determining dryer capacity at actual operating conditions
To determine the maximum inlet flow capacity of a dryer at various operating conditions, multiply the rated capacity from Table 1 by the multipliers shown in Table 2. Example: How many scfm can an air-cooled 100 scfm model handle when compressed air to be dried is at 80 psig and 90°F; ambient air temperature is 80°F; and a 38°F dew point temperature is desired?
Answer: 100 x 1.17 x 1.12 x 1.0 = 131 scfm.
TABLE 1
Rated capacity (scfm) and pressure drop @ 100 psig inlet pressure, 100°F inlet temperature, and 100°F ambient temperature
MODEL
Rated capacity of 60 Hz 25 35 50 75 100
air-cooled models (scfm) 50 Hz 21 29 42 63 84
25 35 50 75 100
Bowl O-Ring
Wave Spring
Pneumatic Pilot Operated Drain
Tube
Timer Drain Valve
(ONLY with I-Controller Level 2)
TABLE 2
Air capacity correction factors (Multipliers)
INLET INLET TEMPERATURES PRESSURES 80
psig kgf/cm
50 3.5 1.35 1.05 0.84 0.69
80 5.6 1.50 1.17 0.95 0.79 100 7.0 1.55 1.23 1.00 0.82 125 8.8 1.63 1.31 1.07 0.91 150 10.5 1.70 1.37 1.13 0.95 175 12.3 1.75 1.42 1.18 0.99 200 14.0 1.80 1.47 1.22 1.03
COOLING MEDIUM*
AMBIENT
TEMPERATURE MULTIPLIER
°F °C
80 27 1.12
90 32 1.06 100 38 1.00 110 43 0.94
*Air-cooled models
INLET COMPRESSED AIR CONDITIONS
°F90°F 100°F 110°F
2
27°C32°C38°C 43°C
OUTLET DEWPOINT DEW POINT TEMPERATURE MULTIPLIER
°F °C
38 3 1.0 40 4 1.1 45 7 1.2 50 10 1.3
6
Page 7
ENGINEERING DATA
Minimum – Maximum Operating Conditions 25 scfm 35 scfm 50 scfm 75 scfm 100 scfm
Min.-Max. Inlet Air Pressure (compressed air at inlet to dryer) 30 psig (2.1 kgf/cm2) - 232 psig (16.3 kgf/cm2) Max. Inlet Air Temp. (compressed air at inlet to dryer) 110°F Min.-Max. Ambient Temperature Air-cooled 45°F (7°C) - 110°F (43°C)
Refrigeration System Data
Compressor Type Hermetic - Resistance Start, Induction Run - Non-Cycling Refrigeration Compressor Horsepower 1/6 1/5 1/4 1/3 1/2 BTU/HR – Refrigeration Only @ 35°F Evaporator & 100°F Ambient 60 Hz / 50 Hz 1010 / 842 1380 / 1150 2160 / 1800 2780 / 2317 4430 / 3692 Refrigerant Type R-134a R-134a R-134a R-134a R-134a Refrigerant Charge See dryer serial number tag Suction Pressure Setting (controlled by hot gas by-pass valve) 31.5 psig 31.5 psig 31.5 psig 31.5 psig 31.5 psig Condenser Fan Switch Setting (in-out) (psig) NA NA NA NA NA Air Flow Across Condenser (cfm) 60 Hz / 50 Hz 105 / 98 235 / 196 275 / 229 220 / 183 350 / 292
Electrical
Nominal Voltages 115/1/60
Max.- Min. Voltage 127-104 127-104 127-104 127-104 127-104 Rated Load Amps 3.4 3.9 5.9 7.4 10.3 Locked Rotor Amps 18.0 22.0 28.0 35.0 48.0 Minimum Circuit Ampacity 4.0 4.7 7.3 9.1 12.4 Branch Circuit Fuse Size (amps) 15 15 15 15 20 Watts @ 35°F Evaporator & 100°F Ambient 280 290 465 600 815
Overload Thermal & Current (Auto reset)
Nominal Voltages 208-230/1/60
Max.-Min. Voltage 253-187 253-187 253-187 253-198 253-187 Rated Load Amps 1.8 2.1 3.0 4.1 5.1 Locked Rotor Amps 8.5 13.7 14.4 19.0 23.0 Minimum Circuit Ampacity 2.2 2.6 3.7 5.1 5.2 Branch Circuit Fuse Size (amps) 15 15 15 15 15 Watts @ 35°F Evaporator & 100°F Ambient 280 290 470 600 815 Overload Thermal & Current (Auto reset)
Nominal Voltages 220-240/1/50
Max.-Min. Voltage 264-198 264-198 264-198 264-198 264-198 Rated Load Amps 1.6 1.8 2.6 3.5 4.2 Locked Rotor Amps 8.7 10.7 14.5 15.2 21.0 Minimum Circuit Ampacity 2.0 2.2 3.2 4.4 5.2 Branch Circuit Fuse Size (amps) 15 15 15 15 15 Watts @ 35°F Evaporator & 100°F Ambient 223 257 395 507 669 Overload Thermal & Current (Auto reset)
7
Page 8
Electrical Schematic
Models 25, 35, 50, 75 - 115V/60 Hz
Model 75 - 208-230V/60 Hz; 220-240V/50 Hz
Model 50 - 208-230V/60Hz
Models 100 - All Voltages
Legend
SW - On/Off Switch OL - Overload TB - Terminal Block CAP - Start Capacitor SR - Start Relay DRN1 - Drain Solenoid (STD IC2) MTR - Compressor DRN2 - Drain Solenoid (IC2, Oil Coalescing Option) FM - Fan Motor TC1 - Temperature Sensor
8
Optional Notes:
1. IC1-Includes IC1 Instrument Panel and Pneumatic Pilot operated Drains.
2. IC2-Includes IC2 Instrument Panel and Timed Solenoid Drains.
3. DRN2-Optional Cold Coalescing Drain.
Page 9
DIMENSIONS/WEIGHTS
Dimensions
inches
Flow (scfm) 25 35 50 75 100
A 26 26 26 33-1/8 33-1/8 B 18-1/2 18-1/2 181/2 25-5/16 25-5/16 C 20-1/2 20-1/2 20-1/2 26 26 D 3-3/16 3-3/16 3-3/16 4-1/8 4-1/8 E 6 6 6 9-7/16 9-7/16 F 2 2 2 4-1/2 4-1/2 G 18-3/16 18-3/16 18-3/16 20-11/16 20-11/16 H 21-3/16 21-3/16 21-3/16 24-3/16 24-3/16
I 18-1/2 18-1/2 18-1/2 24 24
J 16-1/2 16-1/2 16-1/2 21-13/16 21-13/16
Inlet/Outlet
Connections 1/2 MPT 1/2 MPT 1/2 MPT 3/4 MPT 3/4 MPT
Weights lbs 142 146 152 209 228 Weights lbs
w/Oil Removal Filter 147 151 157 216 235
25 thru 50
C
E
D
B
I
TOP VIEW
75 thru 100
B
I
TOP VIEW FRONT VIEW LEFT SIDE VIEW
A
H
G
J
F
FRONT VIEW LEFT SIDE VIEW
C
A
J
F
E
D
H
G
9
Page 10
TROUBLESHOOTING GUIDE
SYMPTOM
A. Water downstream of dryer
POSSIBLE CAUSE(S)
1. Residual free moisture remaining in downstream pipelines
2. Air by-pass system is open
3. Inlet and Outlet connections are reversed
4. Temperatures surrounding air lines downstream of dryer have dropped below dryers dew point rating
5. Excessive free moisture (bulk liquid) at dryer inlet
6. Condensate not being automati­cally drained Drain mechanism is clogged or inoperative. Drain line is restricted or frozen. Electric drains–timer not set to allow for sufficient condensate removal
7. Dryer overloaded resulting in elevated dew point.
8. Refrigeration system not func­tioning properly resulting in elevated dew point.
CORRECTIVE ACTION
Blow out system with dry air Check valve positions
Check for correct connection Insulate or heat trace air lines exposed to
low ambients or dry air to lower dew point
Install separator ahead of dryer
Replace drain mechanism if inoperative Open drain line
Electric drains–reset time so that all liquid is discharged
Check inlet air temperature and pressure, flow rate (compressor capacity) and ambient air or water temperature. See D below
B. High pressure drop across
dryer
C. Dew point indicator in red
area
D. Refrigeration system not
functioning properly
1. Compressor on light off
2. Refrigerant compressor cycles on and off
1. Excessive air flow
2. Freezing of moisture in evapora­tor because of refrigeration system improperly functioning.
3. Separator or optional Oil Removal filter element clogged.
1. Dryer overloaded resulting in high air outlet temperature.
2. Refrigeration system not func­tioning properly resulting in high air outlet temperature.
3. Dryer is running with no load
a. Power failure b. Line disconnect switch open c. Blown fuses, open breaker d. Faulty wiring, loose terminals
a. High or low ambient conditions b. Air-cooled models–Dirty, clogged
condenser fins, obstructed air flow across condenser, or non functioning fan motor or fan control switch.
Check flow rate See D below
Replace filter element(s).
See A 7 See D below
Light will go out when air flow is estab­lished
Check power to unit Close disconnect switch Check for continuity Have electrician check electrical connections Check min./max. temperature ranges Clean condenser and check for free air flow, if problem persists contact qualified refrigeration repairman or manufacturer’s service department.
10
Page 11
PARTS LIST
PARTS DESCRIPTION 100/1/50
Condensing Unit (Air-cooled) C41301205 C41301208 C41301209 C413012111 C41301219 C41301219 C413012210 C413012211 C413012215 Compressor (Only) C413010834 C413010861 C413010835 C413010838 C413010839 C413010840 C413010841 C413010842 C413010843 Overload C59255702 C592557824 C59255703 C59255781 C59255782 C59255783 C59255784 C59255785 C59255785 Start Relay C59456555 C594568324 C59456556 C59456831 C59456832 C59456833 C59456834 C59456835 C59456835 Start Capacitor N/A N/A N/A N/A N/A N/A N/A C5910-103-23 N/A Fan Motor C61052391 C61052374 C61052374 C610523827 C610523828 C610523828 C610523829 C610523830 C610523830 Fan Blade C41402282 C41402282 C41402282 C414022717 C414022717 C414022717 C414022718 C414022718 C414022718 Hot Gas By-Pass Valve C98021 C98021 C98021 C98021 C98021 C98021 C98021 C98021 G98021 Condenser (Air Cooled) C413011026 C413011026 C413011026 C413011118 C413011118 C413011118 C413011119 C413011119 C413011119 Dryer C413016514 C413016514 C413016514 C413016514 C413016514 C413016514 C413016514 C413016514 C413016514 By-Pass Valve Strainer C41307018 C41307018 C41307018 C41307018 C41307018 C41307018 C41307018 C41307018 C41307018 On-Off Switch C611070613 C611070613 C611070613 C611070613 C611070613 C611070613 C611070613 C611070613 C611070613 High Temperature Sensor C61503332 C61503332 C61503332 C61503332 C61503332 C61503332 C61503332 C61503332 C61503332 Digital PC Board (IC 1-0) w/ high temp-sensor C59455767 C59455767 C59455767 C59455767 C59455767 C59455767 C59455767 C59455767 C59455767
PARTS DESCRIPTION 100/1/50 100/1/50
Condensing Unit (Air-cooled) C413012212 C413012213 C413012214 C413012312 C413012313 C413012314 Compressor (Only) C413010844 C413010845 C413010846 C413010847 C413010848 C413010849 Overload C59255787 C59255788 C59255789 C592557810 C592557811 C592557812 Start Relay C59456837 C59456838 C59456839 C594568310 C594568311 C594568312 Start Capacitor N/A C591010326 C591010327 C591010328 C591010329 C591010329 Fan Motor C610523831 C610523832 C610523832 C610523833 C610523834 C610523834 Fan Blade C414022719 C414022725 C414022725 C414022720 C414022720 C414022720 Hot Gas By-Pass Valve C98021 C98021 C98021 C98021 C98021 C98021 Condenser (Air Cooled) C413011120 C413011120 C413011120 C413011121 C413011121 C413011121 Dryer C413016514 C413016514 C413016514 C413016514 C413016514 C413016514 Fan Pressure Switch N/A N/A N/A N/A N/A N/A Contactor N/A N/A N/A N/A N/A N/A By-Pass Valve Strainer C41307018 C41307018 C41307018 C41307018 C41307018 C41307018 On-Off Switch C611070613 C611070613 C611070613 C611070613 C611070613 C611070613 High Temperature Sensor C61503332 C61503332 C61503332 C61503332 C61503332 C61503332 Digital PC Board (IC 1-0) w/ high temp-sensor C59455767 C59455767 C59455767 C59455767 C59455767 C59455767
115/1/60 208-230/1/60 220-240/1/50 115/1/60 208-230/1/60 220-240/1/50 115/1/60 208-230/1/60 220-240/1/50
115/1/60 208-230/1/60 220-240/1/50 115/1/60 208-230/1/60 220-240/1/50
25 35 50
100/1/50 100/1/50
75 100
Maintenance Kits
Flow (scfm) 25 35 50 75 100
Standard CRNMK2 CRNMK2 CRNMK3 CRNMK4 CRNMK4
With Optional Cold Coaleser CRNMK12 CRNMK12 CRNMK13 CRNMK14 CRNMK14
11
Page 12
WARRANTY
©
2004 Gardner Denver, Inc.
Litho in U.S.A.
7610.721.73 1/04 CA18-2-645, 1st Ed.
®
www.championpneumatic.com
Champion 1301 North Euclid Avenue Princeton, Illinois 61356 USA Phone: 815/875-3321 Fax: 815/872-0421 E-mail: Champion@championpneumatic.com
Plants in Princeton, IL, and Manteca, CA
Due to Champion’s continuing product development program,specifications and materials are subject to change without notice or obligation.
The manufacturer warrants the product manufactured by it, when properly installed, operated, applied, and maintained in accordance with procedures and recommendations outlined in manufacturer’s instruction manuals, to be free from defects in material or workmanship for a period as specified below, provided such defect is discovered and brought to the manufacturer’s attention within the aforesaid warranty period.
The manufacturer will repair or replace any product or part determined to be defective by the manufacturer within the warranty period, provided such defect occurred in normal service and not as a result of misuse, abuse, neglect or accident. Normal maintenance items requiring routine replacement are not warranted. The warranty covers parts and labor for the warranty period unless otherwise specified. Repair or replacement shall be made at the factory or the installation site, at the sole option of the manufacturer. Any service performed on the product by anyone other than the manufacturer must first be authorized by the manufacturer.
Unauthorized service voids the warranty and any resulting charge or subsequent claim will not be paid. Products repaired or replaced under warranty shall be warranted for the unexpired portion of the warranty applying to the original product.
The foregoing is the exclusive remedy of any buyer of the manufacturer’s product. The maximum damages liability of the manufacturer is the original purchase price of the product or part.
THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES, WHETHER WRITTEN, ORAL, OR STATU­TORY, AND IS EXPRESSLY IN LIEU OF THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. THE MANUFACTURER SHALL NOT BE LIABLE FOR LOSS OR DAMAGE BY REASON OF STRICT LIABILITY IN TORT OR ITS NEGLIGENCE IN WHATEVER MANNER INCLUDING DESIGN, MANUFACTURE OR INSPECTION OF THE EQUIPMENT OR ITS FAILURE TO DISCOVER, REPORT, REPAIR, OR MODIFY LATENT DEFECTS INHERENT THEREIN.
THE MANUFACTURER, HIS REPRESENTATIVE OR DISTRIBUTOR SHALL NOT BE LIABLE FOR LOSS OF USE OF THE PRODUCT OR OTHER INCIDENTAL OR CONSEQUENTIAL COSTS, EXPENSES, OR DAMAGES INCURRED BY THE BUYER, WHETHER ARISING FROM BREACH OF WARRANTY , NEGLIGENCE OR STRICT LIABILITY IN TORT.
The manufacturer does not warrant any product, part, material, component, or accessory manufactured by others and sold or supplied in connection with the sale of manufacturer’s products.
Warranty Period
Parts and labor for two (2) years from the date of shipment from the factory; heat exchangers are covered (parts only) for an additional three (3) years (total of five [5]). Lifetime heat exchanger warranty (parts only) requires a CFF Series prefilter on the initial purchase and annual filter element replacements with genuine CFF Series elements.
On units that manufacturer requests be returned to the factory, a one time removal/reinstallation labor allowance as noted in the Service Warranty Policies and Procedures Handbook will apply. Freight to the factory from the installation site and to the installation site from the factory will be paid by the manufacturer; means of transportation to be specified by manufacturer.
AUTHORIZATION FROM THE SERVICE DEPARTMENT IS NECESSARY BEFORE MATERIAL IS
RETURNED TO THE FACTORY OR IN-WARRANTY REPAIRS ARE MADE.
SERVICE DEPARTMENT: (724) 746-1100
Loading...