• Do not exceed maximum operating pressure as shown
on equipment serial number tag.
• Make certain equipment is depressurized before servicing.
2. Electrical
This equipment requires electricity to operate.
• Install equipment in compliance with national and local
electrical codes.
• Standard equipment is supplied with NEMA 1 electrical enclosures and is not intended for installation in
hazardous environments.
• Disconnect power supply to equipment before
servicing.
3.Breathing air
• Air treated by this equipment may not be suitable for
breathing without further purification. Refer to OSHA
standard 1910.134 for the requirements for breathing
quality air.
CRH SERIES
HIGH INLET
TEMPERATURE
REFRIGERATED
COMPRESSED
AIR DRYERS
Ambient Air Filter
1.0 INSTALLATION
24"
12"
wall
6"
36"
1.1 Location
A. Air compressor intake - Locate air compressor so that
contaminants potentially harmful to the dryer are not
drawn into the air system.
B. Free air flow - Do not block either side of the cabinet.
Observe minimum installation clearances as shown.
1.2 Mounting
Dryer is suitable for floor or shelf mounting.
2. Location in the compressed air system
A. Maximum working pressure - 250 psig,
17.6 kgf/cm2. Do not exceed unit’s Maximum Working
Pressure.
1) For maximum capacity, install unit in air system at
highest pressure possible (e.g. before pressure reducing valves)
2) For maximum capacity, install unit at coolest compressed air temperature possible. Maximum inlet
compressed air temperature: 180°F, 82°C. If inlet air
exceeds this temperature, precool the air by extending the piping between the compressor and the
dryer.
B. Air Outlet - Connect air outlet to downstream air lines.
C. By-pass piping - If servicing the unit without interrupting
the air supply is desired, piping should include inlet and
outlet isolation valves and an air by-pass valve.
D. Condensate drain - It is advisable to connect drain outlet
to the condensate drainage system.
NOTE: Drain discharge is at system pressure. Drain line
should be anchored to prevent whipping.
1.3 Piping connections
A. Air Inlet - Connect compressed
air line from air compressor to air
inlet using strainer supplied.
1. Install strainer (included in
shipping carton) prior to
dryer inlet using pipe nipple
supplied or other piping as
required.
NOTE: Observe flow direction arrows on strainer.
NOTE: Install strainer where it is easily accessible for cleaning.
NOTE: Use vibration dampener, if vibration exists in air line at
inlet to dryer.
Control
Panel
IO
Separator and
Integral Filter
Drain
Mechanism
Drain
Connection
Electrical
Connection
1.4 Electrical connections
A. Dryer is designed to operate on power supply (voltage)
listed on serial number tag located on the back of the
dryer.
B. Dryer is supplied with an electrical cord. Install in recep-
tacle of proper voltage.
NOTE: Models 50 and 75 (115v only) - Install plug
in receptacle rated for 20 amps. Units are supplied
with 20 amp plug.
Plug
NOTE: Refrigeration system is designed to run continuously
and should NOT be wired to cycle on/off with the air compressor.
Serial Number
Tag
Air Inlet
Connection
Strainer
(shipped
separately)
Pipe Nipple
Air Outlet
Connection
Serial
Number
Tag
2
Left SideFrontBackRight Side
2.0 OPERATION
I
O
On/Off Switch
Fault Light
NOTE: Installations above 6000 feet, 1825 meters
Unit is adjusted to operate in altitudes up to 6000 feet, 1825
meters. If unit is installed in an altitude above this, and has
not been preset at the factory for this altitude, contact
Manufacturer’s Service Department.
2.1 Start-up
Start refrigeration system by pushing the on/off switch to
the ON position (depress rocker switch on side marked “I”).
NOTE: The fault light may illuminate when unit is energized.
Light should go out approximately 5 minutes after start-up.
If light remains lit after 30 minutes or illuminates after going
out, refer to Troubleshooting Guide.
Control Panel
2.2 Operating check points
Check the following on a periodic basis:
A. Rocker switch is in the ON position.
B. Amber fault light is out.
C. Condensate is being regularly discharged.
2.3 Minimum/maximum operating conditions
A. Minimum/Maximum air pressure: 20/250 psig,
1.4/17.6 kgf/cm
B. Maximum inlet air temperature: 180°F, 82°C
C. Minimum/Maximum ambient temperature:
40/110°F, 4/43°C
2
D. Maximum flow capacity
1. For dryers without an aftercooler installed upstream
Flow capacity in scfm (m3/min) @ 180°F, 82°C inlet
temperature, 160°F, 71°C inlet pressure dew point,
95°F, 35°C ambient temperature, and less than
5 psi, 0.35 kgf / cm2 pressure drop.