On Line│Champ RM
1K/2K/3K
Features
•True double-conversion
•Microprocessor control optimizes reliability
•Input power factor correction
•Output power factor 0.9
•Wide input voltage (110V - 300V)
•Converter mode available
•ECO mode for energy saving(Only available for 1-3KVA
•Adjustable battery string numbers only available for 6K/10K modelz
•Adjustable charging current via LCD or software (1A~6A)
•Emergency power off function (EPO) only available for 6K/10K models
•Generator compatible
•Smart SNMP works well with either USB or RS-233 together
•Comprehensive LCD display allows easy monitoring and access of
UPS status
MODEL
PHASE
CAPACITY
INPUT
Nominal Voltage
Input Voltage Range
Frequency Range
Power Factor
OUTPUT
Output Voltage
Voltage Regulation
Frequency Range (Synchronized Range)
Frequency Range (Batt. Mode)
Current Crest Ratio
Harmonic Distortion
Transfer Time
Waveform (Batt. Mode)
EFFICIENCY
AC Mode
Battery Mode
BATTERY
Standard Model
Long-run Model
INDICATORS
LCD Panel
ALARM
Battery Mode
Low Battery
Overload
Fault
PHYSICAL
Standard Model
Long-run Model*
ENVIRONMENT
Humidity
Noise Level
MANAGEMENT
Smart RS-232 / USB
Optional SNMP
* 1K-3K: Derate to 80% of capacity in Frequency converter mode or when the output voltage is adjusted to 208Vac.
* Product specifications are subject to change without further notice
* Long-run model power factor: 0.8
AC Mode to Batt. Mode
Inverter to Bypass
Battery Type
Numbers
Typical Recharge Time
Charging Current (max.)
Charging Voltage
Battery Type
Numbers
Charging Current (max.)
Charging Voltage
Dimension, D x W x H (mm)
Net Weight (kgs)
Dimension, D x W x H (mm)
Net Weight (kgs)
Champ RM 1K(L)
1000VA / 900W
110 / 115 / 120 / 127Vac or 208 / 220 / 230 / 240Vac
110 / 115 / 120 / 127Vac or 208 / 220 / 230 / 240Vac
≦ 3% THD (Linear Load) / ≦ 6% THD (Non-linear Load)
88%
83%
12 V / 9 AH
2
27.4VDC ± 1%
2 3 6 84 8
27.4VDC ± 1% 41.0VDC ± 1% 82.1VDC ±1% 109.4VDC ±1%
Load level, Battery level, AC mode, Battery mode, Bypass mode and Fault indicators
310 x 438 x 88
12
310 x 438 x 88
9
Supports
Depending on the capacity of external batteries
®
Windows
Power management from SNMP manager and web browser
Champ RM 2K(L)
Single phase with ground
2000VA / 1800W
60-145Vac or 120-300Vac at 50% load
90-145Vac or 180-300Vac at 100% load
≧ 0.99 @ Nominal Voltage (100% load)
50Hz ± 0.25Hz or 60Hz ± 0.3Hz
4 hours recover to 90% capacity
54.7VDC ±1% 109.4VDC ±1%
20-90% RH @ 0- 40°C (non-condensing)
2000 / 2003 / XP / Vista / 2008 / 7 / 8, Linux, Unix and MAC
40~70Hz
47~53Hz or 57~63Hz
4 ms (Typical)
Pure Sinewave
12 V / 9 AH
54.7 VDC ±1%
1A / 2A / 4A / 6A (Adjustable)
82.1VDC ±1%
Sounding every 4 seconds
Sounding every second
Sounding twice every second
Continously sounding
410 x 438 x 88
410 x 438 x 88
Less than 50dBA @ 1 Meter
± 1%
3:1
Zero
89%
87%
4
1.0 A
6
19
12
Champ RM 3KL
3000VA / 2400W
90%
88%
12 V / 9 AH
6
82.1 VDC ±1%
630 x 438 x 88
29.3
410 x 438 x 88
14.2
16