Chalmit lighting Micronex 70W HPS, Micronex 70W MBI Installation, Operation And Maintenance Instructions

I-MICN-01.doc Issue 06 Mar10 1
IOM – MICRONEX - ZONE 2 FLOODLIGHT (ATEX, Ex n)
Micronex - Floodlight Luminaires
ATEX, Ex n
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
Important:
Please read these instructions carefully before installing or maintaining this equipment. Good electrical practices should be followed at all times and this data should be used as a guide only.
Cha
lmit Ligh
ting
MI C
R
O N
E
SIMP LEX
CHA LMIT LIGH
TING LTD,
V
CE 600
388
HILLI NGT ON
ROA D,GL ASG OW,
UK
SITE
0990
_
S O
N/ TS
_
24
0 3
T
S
E R.
No
.9 8
W
P
6
6
_
S
U P
PL Y:-
LA M
P
70
W
-30 TO
+40° C
II 3
B A
S
98ATEX405
4
IS
O LA
TE
S U
P P
L
Y
B E
F
O R
E
O P
E NI
Ex
nR
II
Hz W
50
70
230
83
350
381
51
3 x 11mm DIA
Ch almi t Lig hting
I-MICN-01.doc Issue 06 Mar10 2
IOM – MICRONEX - ZONE 2 FLOODLIGHT (ATEX, Ex n)
Type(s) of Protection
Ex nR (Non-Sparking) (Restricted Breathing)
Protection Standard
EN 50021
Area of Application
Zone 2 areas to BS EN 60079-10 and installation to BS EN 60079-14
ATEX Equipment
Classification
Group II Category 3 G
Equipment Coding
II 3 G Ex nR II T3 Tamb 40ºC
Certificate
Type Examination EECS BAS98ATEX3054
Ingress Protection
IP66 and IP67 to BS EN 60529
CE Mark
Declaration of compliance with standards
The CE marking of this product applies to "The Electrical Equipment (Safety) Regulations 2006", "The Electromagnetic Compatibility Regulations 2004", the “Waste Electrical and Electronic Equipment Regulations 2006” and the "Equipment and Protective Systems intended for use in Explosive Atmospheres Regulations 1996".
[This legislation is the equivalent in UK law of EC directives 2006/95/EC, 2004/108/EC
and 2002/96/EC respectively].
The Equipment is declared to meet the provisions of the ATEX directive (94/9/EC) by reason of the EC Type Examination and compliance with the Essential Health and Safety Requirements. I MacLeod Technical Manager
SPECIAL CONDITIONS FOR SAFE USE
None
1.0
Introduction - Micronex Floodlight
The type of protection is Ex nR using a restricted breathing enclosure.
Note: The maximum ambient and surface temperature ratings are as indicated in TABLE 0.
2.0 Application
The luminaire is designed to be safe in normal operation. The luminaire should not be used in conditions where there are environmental, vibration or shock conditions above the normal expected levels for fixed installations. The gaskets should not be exposed to hydrocarbons in liquid or high concentration vapour states.
The body material is made from marine grade aluminium, copper free (BS1490 LM6), powder coated.
The luminaire is suitable for applications where Category 3 apparatus can be used. The application is for ignitable gas atmospheres. The type examination does not address suitability for dusts or portable applications.
Table 1 Maximum Ambient and Surface Temperature Rating
Wattage Lamp Ambient Temp T Rating Cable Rating Cable Rise
70W SON/TS, MBI/TS 40ºC T3
75oC 30oC
Table 2 Starting and Running Currents
Lamp Start A
Run A
PFC µF
70W HPS 0.55 0.40 10 70W MBI 0.55 0.40 10
I-MICN-01.doc Issue 06 Mar10 3
IOM – MICRONEX - ZONE 2 FLOODLIGHT (ATEX, Ex n)
Table 3 Fuse Ratings
Number of Lamps
Lamp Type
1 2 3 4 5 6
70W HPS 4A
4A 4A
6A 6A 10A
70W MBI 4A 4A 4A 6A 6A 10A
Table 4 Weight and Windage
Type Weight
Windage
MICRONEX HPS/MBI 5.1kg
0.08m
2
Power factor ≥ 0.85 EMC EN 55015 Terminals 6mm² as standard, through wiring and looping has current limit of 16A. Tamb Storage -40°C to +80°C Storage Luminaires should be stored in cool dry conditions preventing ingress of moisture and
condensation
Lamps Lamps suitable for RX7 lampholders in accordance with EN 60838 Fuse and Refer to tables 2 and 3 for starting and running currents and fuse ratings. Also refer to
section
MCB ratings 5 for information regarding inrush current.