chaffotteaux Challenger 40 BF User guide

CHALLENGER
Balanced Flue Boilers
30 BF
(GCN"41.980.71)
40 BF
(GCN"41.980.75)
installation
and servicing instructions
(leave these instructions adjacent to the gas meter)
CHALLENGER
30 is rated between 4.35 kW (15,000
Btu/h) and 8.7 kW (30,000 Btu/h).
CHALLENGER
40 is rated between 5.8 kW (20,000 Btu/h)
and 11.6 kW (40,000 Btu/h). The boiler is designed for use on Natural Gas, unless
otherwise stated. It is suitable for open systems and sea­led systems.
The boiler is designed for fully pumped systems only with a number features incorporated.
- Fully adjustable electronic temperature regulation bet­ween 60 “C and 82 “C.
- Automatic alternation high flame/low flame.
- Pump overrun.
- Low resistance.
- High limit thermostat.
Guarantee
The manufacturer’s guarantee on the appliance is for 24 months from not installed in accordance with the recommendations made herein or in a manner approved by the manufacturer.

1.1 TECHNICAL DATA

return *; ~ Tflow
the date of
installation. The guarantee is voidable if it is
-
F
­A 6 C D
E
F G H
J K
L M N 0
LLENGEI
Cl
mm
610 24 330 270 10.6 350 224 8.8 120 5.0
200 7.8 215 8.5 300 12 660 26 260 10.25
80
30 45
R3
‘OBF
l-
13
13.77
1
ins
3.1
1.2
1.7
.
R4 LLENGEI
10 BF
mm
A
655 25.78
B
395
C
260
D
320
E
J
c
F G
H
J
K
L M N 0
225 8.9
120 5.00 250 9.8 200 210 300 12.00 700 260 10.23
35 1.37 50
ins
15.55
10.25
12.6
7.87
8.26
27.5
1.96
1
2
1.2
30 BF
OUTPUT
INPUT
BURNER PRESSURE (HOT)
GAS RATE
1.3
kW Btdh
Max
Min
40 BF
Max
Min
8.7
4.35
kW
11.6
5.8
30,000 15,000
OUTPUT
Btu/h
40,000 20,000
Max
Min
Max
Min
BalanceFlue ..___. Gas connection Waterconnection
kW Btu/h mbar ins.w.g. m3/h ft3/h
10.9 37,500 6.4
5.66 19,480 1.15
INPUT
kW
14.5 50,000 12.0
7.55 26,000 3.5
NB : For intermediate settings see graph page 13
Flue set requires a hole in the wall 205 mm highx305 mm wide (8 inxl2 in) 15 mm compression fitting 22 mm compression fittings
Minimum flow rate see 1.4
Maximum static head 30
m (98 ft)
Minimum static head 150
Electrical connection Weight
Watercapacity .._.......
Manifold Injector Size
240 V single phase 50 Hz supply fused 3 amp
30 BF - 18.18
0.5 lit. (0.11 gals.)
30 BF Pilot injector 0.3 Ignition
Electrode ..___......... ,.,.,
Boiler thermostat High Limit thermostat Thermocouple and thermoelectric valve
Continuous spark -spark generator ANSTOSS
Chaffoteaux - spark gap 5.0 mm
Electronic - Chaffoteaux Ltd
Ranco LM5
Chaffoteaux Ltd
2.56 1.02 36.26
0.45 0.53 18.83
BURNER PRESSURE (HOT)
Btu/h mbar ins.w.g. m3/h ft3/h
4.72 1.37 48.54
1.37 0.71 25.24
CLEARANCES
Sides
TOP
Bottom
Front
GAS RATE
mm ins
5 0.25
76 3
127 5
500 20
mm (6 ins) - See page 7.
kg (40 Ibs)
1.18 mm (0.046 ins.)
40
BF - 20
BF
kg (44 Ibs).
1.08 mm 0.042 ins
40
mm (0.011 ins.)
1.4
HYDRAULIC RESISTANCE
The hydraulic resistance of the boiler varies with the water flow. The graph (Fig. 2) indicates resistan­ce at various flow rates.
The minimum flow rate is equivalent to a tempera-
ture rise of 15” C :
30 BF
504
I/h
1.85 gpm
673
I/h
Minimum water flow rate
3
a
0.1
I I
100 300 500
200
water flow-gallons per minute
w I
400 600
I
700 900
water flow - litres per hour
I I
800
1000 1200 1400
1100
13bo
3
2:
1
z .c
f
9 B
.%?
1.5 Description of Operation
Pressing the ignitor (on) button disconnects the supply to the pump, opens the therm0 electric valve and causes a continuous pilot ignition spark to be generated and the pilot is lit.
If there is a demand the pump will start when the (( ON )) button is released. The burner will commence after a 30 second delay when the 50 % fixed gas valve opens. After 3 seconds the 2nd (variable output) valve opens.
Temperature control is by means of a temperature sen­sing thermistor and potentiometer. These signals are fed to a comparitor.
When the flow temperature approaches the set tempe­rature the main gas valve is closed and the bo’iler
ON n
continues to fire on 50 % fixed gas valve. When the set temperature is reached the boiler switches off. If flow temperature reduces the 50 % fixed gas valve opens fol­lowed by the variable valve.
At the end of an ‘on’ cycle under the control of a time
clock or programmer or when the cylinder and room thermostat are satisfied the boiler switches off but the pump continues to run for 15 seconds.
The high temperature cut out breaks the thermocouple circuit which extinguishes the Pilot and closes the gas supply to the burner. Manual re-setting is reauired. (See section 4.11)
FUNCTIONAL FLOW DIAGRAM
Fig. 1
I
L
THERM0 ELECTRIC
VALVE
THERMISTOR
FLOW SENSOR
POTENTIOMETER
TEMPERATURE
.2SI FPrl-m
. TIME DELAY PUMP
OVER RUN
L r
A
T
SPARK GENERATOR
HIGH LIMIT
THERMOSTAT
L r
1
I
COMPARITOR
L
I
r
1
L r
. r
PILOT
IGNITOR
THERMOCOUPLE
VARIABLE lDD%GAS SOLENOID
VALVE
rh
TIME DELAY
PUMP

2. INSTALLATION REQUIREMENTS

2.1 General
The installation of the boiler must be in accordance with the Gas Safety Regulations, Building Regulations, I.E.E. Regulations and the Byelaws of the local Water Underta­king. It should be in accordance also with BS Codes of Practice and the British Gas Specifications for Domestic Wet Central Heating Systems and any relevant reauire­ments of the local Gas Region and Local Authority. Detailed recommendations are stated in the following British Standard Codes of Practice : CP 331:3, BS 5376:2,
BS 5546, BS 544011 and 2, BS 5449:l.
Note
: Gas safety (Installation and Use) regulations 1984 :
It is the law that all gas appliances are installed by com­petent persons in accordance with the above regula­tions Failure to install appliances correctly could lead to prosecution. It is in your own interest and that of safety to ensure compliance with the law.
2.2
Location
The position chosen for the boiler should permit the pro­vision of a satisfactory flue termination. The position should also provide adequate space for servicing and air circulation around the boiler. (See Section 4).
Where installation will be in an unusual position, special procedures may be necessary, and BS 5376:2 gives de­tailed guidance on this aspect.
A cupboard or compartment used to enclose the boiler must be designed and constructed specifically for this purpose. An existing cupboard or compartment may be used provided that it is modified for the purpose.
Details of essential features of cupboard/compartment design are given in BS 5376:2.
2.3
Water Circulation Systems
Open or sealed type central heating systems (see Section
5) should be in accordance with the relevant recommen­dations given in BS 5376:2, BS 5449:l (for smallbore or microbore systems) and the British Gas Specifications for Domestic Wet Central Heating Systems,
Hot water systems should be in accordance with the re­levant recommendations given in CP 34211 and the abo­ve mentioned British Gas publication and BS 5546.
2.5
Electrical Supply
This appliance must be earthed. All wiring must conform to the I.E.E. Regulations. The CHALLENGER 30 requires a
240 V, single phase, 50 Hz supply. A means of isolation
must be provided adjacent to the boiler, this should pre­ferably be an unswitched plug and socket. Alternatively, a double pole isolator having a contact separation of at
least 3 mm at both poles must be used. The fuse rating should be 3 amp The three core heat resisting cable.
supply
cord must be 0.75 mm2
2.4 Air supply - Balanced Flue Boiler
The room in which the boiler is installed does not require a purpose provided air vent.
If the boiler is installed in a cupboard or compartment permanent air vents are required in the cupboard and compartment, one at high level, and one at low level, ei­ther direct to the outside air or to a room. Both high and low level air vents must communicate with the same room or must both be on the same wall to outside air.
This free area may be halved if the ventilation is provi­ded directly from outside.
30 BF cupboard or compartment air supply
Position of Air from
air vents
40
BF
Position of
air vents
Air from
room
room
Air direct
from outside
Air direct
from outside
2.6
Gas Supply
The CHALLENGER 30 requires 1.1 m3/h (37 fts/h). CHAL-
LENGER 40 requires 1.4 m3/h (49 ft3/h) of natural gas. The meter and supply pipes must be capable of delive-
ring this quantity of gas in addition to the demand from any other appliances in the house. The complete installation must be tested for soundness as described in CP 331:3
2
7
.
Flueing
Detailed recommendations for flueing are given in BS 544O:l. The following notes are for general guidance only. The boiler must be installed so that the flue terminal dis­charges directly into the external air. Termination should be on a clear expanse of wall ; the terminal being preferably not less than 600 mm (2 ft) from a corner or recess. Where the terminal is less than 2 m (6.6. ft) above the le­vel of any ground, balcony, flat roof or place to which people have access, the terminal must be protected by a guard of suitable material. Where a terminal guard has not been supplied (optional extra) with the boiler, one may be obtained from Chaf­foteaux Limited or from Tower Flue Components Ltd. Tonbridge 351555. The air inlet/products outlet duct and the terminal should be no closer than 25 mm (I in) to combustible material. Detailed recommendations on protection of combustible material are given in BS 544O:l. The distance of any surface facing the terminal should be greater than 600 mm (24 ins). If the terminal is fitted within 850 mm of a plastic gutter
or within 450 mm of painted caves or a painted gutter, an aluminium shield at least 750 mm long should be fit­ted to the underside of the gutter or painted surface.
Fig. 2
SPLITTER
NOT TO EXTEND MORE THAN DEPTH OF TERMINAL
BALANCED FLUES
(Zft)
E PROJECTION
NE 1. TERMINALS MUST NOT BE FITTED
IN SHADED AREAS
2. IF LESSTHAN 1,606 mm l6ftl ABOVE GROUND LEVEL FIT TERMINAL GUARD
3. If 3OOmm (1 ft) BELOW EAVE FIT DEFLECTOR TO SOFFIT 600mm (2 h) ON EITHER SIDE OF TERMINAL & EXTENDING TO INCLUDE PLASTIC GUTTER
5
3.
3.1
3.2
3.3
3.4

SYSTEM GUIDANCE

(Chaffoteaux Ltd. recommendations).
General
The CHALLENGER is a low water content boiler designed ONLY for use with fully pumped systems. It may be used with open or sealed systems, all safety controls exclu­ding the pressure relief valve being incorporated in the boiler. The thermostat is adjustable and, on its maximum setting, gives a nominal 82 “C (180 “F)i4 “C (7 “F).
Detailed recommendations for the water circulation are given in BS 5376.2 1976, BS 5449.1 1977 and BS 5546:1979.
Thermostatic control should be fitted to the cylinder and heating circuits.
Strainers
Where the CHALLENGER is used as a replacement for a
boiler on an existing system, ideally the system should
be flushed and cleaned using a suitable chemical cleaner following the manufacturer’s recommendations and fit­ted with a strainer similar to that manufactured by Ho-
neywell.
Control Schemes
The boiler is electrically controlled. See section 3.11.
Most normal pumped primary control schemes can be
used including thermostatic radiator When using motorised valves the controls should be so arranged to switch off the boiler when circuits are satis­fied.
Chaffoteaux can be consulted where technical assistan­ce is required.
and
cylinder valves.
Circulation Pump
The system circulating pump should be sized relative to the resistance of the connected load and the system de­sign selected. The water flow rate through the boiler should not be less than shown in section 1.4. The pump
must be installed between isolating valves. Most pump
manufacturers require a minimum static head on the
pump inlet to prevent cavitation. For boiler resistance see graph on page 3.
3.7 Cylinder
The domestic hot water cylinder used with the CHAL­LENGER must be of the indirect and high recovery type to BS 1566 Pt. 1. Single feed cylinders are not suitable for use with the appliance. Flow and return pipework to the cylinder should be in 22 mm pipe.
3.8 Feed and Expansion Tank
The feed and expansion tank should be adequately sized to accept the system water expansion, it should not be mounted closer than 9 in. to a ceiling to allow access to
the ball valve.
3.9
Inhibitors
Chaffoteaux Limited do not generally recommend the inclusion of an inhibitor with heating and hot water sys­tems, utilising CHAFFOTEAUX boilers. It is, however, ap­preciated that the use of a corrosion and limescale inhi­bitor may be desireable or specified.
The following are the appliance manufacturer recom­mendations :
Use only a British Gas or similar approved inhibitor from the Fernox range manufactured by Industrial (Anti-Corrosion) Services, Brittanica Works, Arkesdon Road, Clabering, Nr Saffron Waldron.
Use only the quantities specified by the inhibitor manufacturer.
Cleanse the system as may be required be the inhibi­tor manufacturer.
Add inhibitor only after flushing when finally refilling the system.
3.10 Add on devices
This appliance is approved by British Gas for safety and performance. It is important that no external control de­vices - eg. flue dampers, economisers etc. - be directly
connected to this appliance unless covered by these lns­tallation Instructions or agreed by the Manufacturer in writing.
Any direct connection of a control device not approved
by the manufacturer could invalidate British Gas appro­val and also infringe the Gas Safety Regulations.
3.5
3.6
Cold feeds and open vents
The cold feed and open vent should be so positioned that pumping over and sub-atmospheric pressures are avoided see recommendations for various layouts on
page 7.
Automatic Air Separator
Chaffoteaux Limited strongly recommend the inclusion of a British Gas accepted automatic air separator in the system as shown in fig. 9.
The open vent pipe should rise continuously from the system pipework.
It should not be entered horizontally into the system pi­pework. The use of an enlarged T to create a low velocity point is recommended. The preferred arrangement is shown in fig. 9.
6
Minimum Static Head
150mm
Static Head
-----
PREFERED
.
. . .
. . . . .
. . . . .
----.
_----
Static Head
Static Head Refer to
BS 5449 Part 1 1977
Air seperator or formed low velocity point
1. Cold feed 15 mm
2. Open vent 22 mm
3.11 Electrical Controls
(Chaffoteaux recommendations)
CHALLENGER can be used with most normal pumped pri­mary schemes including non-electrical heating and hot water controls.
It is not normally possible to use full programming facili­ties when using a mixture of electrical and non-electrical controls. However, some non-electrical controls are now available with an external microswitch and these controls are preferred.
Where the thermostatic radiator valves are used a sys­tem by pass will be necessary to maintain the minimum flow rate - See section 1.4.
Important:
must be in accordance with the current edition of the
I.E.E. wiring regulations
1. Fully pumped system independant control of central hea­ting and hot water using two spring return motorised val­ves.
All external wiring to and from the boiler
3. Drayton flow share valve system.
Fig. 12
4. Honeywell Sundial ‘Y’ plan.
PROGRAMMER
PUMP
BOILER TERMINALS
Fig. 10
2. Fully pumped systems independant control of central heating and hot water using two motorised valves.
PROGRAMMER PUSP BOXER TERMINALS
Fig. 11
PROGRAMMER PUMP
Fig. 13
5. Satchwell Duoflow system. TLX 2259
ROOM
STAT
PROGRAMMER
SA 2451 CYL STAT
Fig. 14
PUMP
BOILER TERMNILS
CM 361 C”OFLOW VALVE
BOILER TERMINALS
4.

INSTALLING THE BOILER

A vertical flat area is required for the boiler as follows : CHALLENGER 30 BF 340 mm wide x 813 mm high (13.4 ins x 32.0 ins) CHALLENGER 40 BF 405 mm wide x 858 mm high (16.0 ins x 33.7 ins) The above dimensions include the necessary clearances around the boilers for case removal and for air movement,
The standard flue set supplied with the boiler is suitable for walls having a thickness of 75 mm to 355 mm (3 ins to 14 ins). Ex­tension sets are available for walls up to 610 mm (24 ins). This can be extended to 610 mm (24 ins) using an extension kit or alternatively a 610 mm (24 ins) complete assembly is available.
4.1
4.2
4.3.1
Preparing the wall (traditional constructions) a) Using dimension on page 2, or using boiler as templa-
c
IMPORTANT NOTICE : TIMBER FRAMED HOUSES If the appliance is to be fitted in a timber framed building it should be fitted in accordance with the British Gas Publica-
tion, “Guide for Gas Installations in Timber Framed Housing” reference DM2. If in doubt, advice must be sought from the local Gas Region of British Gas.
te, cut hole for air duct.
b) If the hole is cut accurately, there will be no necessity
to line the hole since the air duct will make a satisfac-
tory seal.
Assembling the balanced flue set
NB : For walls 355 mm (14”) or less use the air duct body and cover supplied with the appliance. For walls over 355 mm (14 ins) up to 600 mm (24 ins) a 24” flue assembly is available alternatively the flue extension kit may be used (See 4.3.2).
a) Remove air duct body (I) and cover (2) from car-
ton.
b) Measure and cut plain ends of air duct body and cover
to the wall thickness plus 5 mm (l/4 ins).
c) Place cover over body and engage tags. d) Turn down tags in direction of flange (3). e) Tape along length of joints with tape provided.
f) Using nut and bolt provided fit hooks (4) to air duct.
4.3.2
tape
For walls in excess of 350 mm (14 ins)
NB : Use either 600 mm (24 ins) assembly or flue exten-
sion kit. a) Proceed as a-f -4.3.1. b) Assemble air duct extension. c) Insert extention piece inside flanged section and ex-
tend to the wall thickness + 5 mm (l/4) leaving a mini-
mum of 50 mm (2 ins) overlap. d) Trim extension piece to length as necessary. e) Mark around inside of joint, f) Remove from wall and reassemble to mark in (e) and
tape around outside of joint with tape provided.
9
4.4.1
Fitting the balanced flue set walls in excess of 100 mm (4 ins)
a) Fit air duct into hole with the flanged end flush with
the internal wall surface.
b) Make good and seal air duct into hole internally and
externally.
c) Pass terminal through hole and secure with springs
and chains on the hooks on the air duct.
NB : It is recommended that a length of card or string is fixed to the terminal to prevent any risk of damage or danger to persons in or about the building.
4.4.2
4.5
46.1
Fitting the balanced flue terminal walls 75 mm (3 ins) to 100 mm (4 ins) a) Proceed as 4.4.1 a and b. b) Mount boiler see 4.5 and 4.6.
G) Transfer chains from the hooks to the slots in the flue
bend mounting bracket A.
d) Secure chain with nut and bolt B provided.
Preparing the boiler for fitting a) Remove front casing by removing two screws (A) at
top and bottom and two screws (B) front lower Part of boiler.
b) Remove the aluminium flue bend by removing screws
(C) on either side of bend.
c) Fit two brackets to top of boiler using screws provi-
ded A - 4.6.1.
d) Fit cable clamp bracket below boiler (A - 4.8) using
screws and paint cutting washers provided.
NB : Paint cutting washers must be used to maintain the earth bond.
Fitting the boiler a) Measure down from base of the air duct (page I) for
bottom fixing. Mark, drill, rawplug and fix bottom bracket.
b) Offer boiler to wall resting on bottom bracket and lo-
cating with air duct.
c) Mark, drill and rawplug wall. d) Attach foam gasket around the air inlet spigot(c) (pull
off protective paper whilst sticking down gasket).
e) Lift boiler into position with the air inlet spigot loca-
ting into the air duct.
f) Secure boiler to the wall with the screws and washers
provided.
g) Secure boiler screwing through bottom bracket.
30 BF
46.2
Fitting the boiler a) Offer boiler to the wall and mark top fixing bracket
and bottom fixing holes. b) Drill and rawplug wall. c) Attach foam gasket around the air inlet spigot (pull
off protective paper whilst sticking down gasket). d) Lift boiler into position with the air inlet spigot loca-
ting into the air duct.
e) Secure boiler to the wall with the screws and washers
provided.
10
40 BF
4.7
4.7-I Assembling the flue duct and bend (Walls 75 mm (3 ins1 to 100 mm (4 ins)
a) Cut flue duct to length, wall thickness plus 100 mm (4”). b) Slide flue duct through the air duct and fully engage it
in the terminal. c) Replace flue bend engaging the flue duct. d) Ensure that the flue bend sits evenly and securely on
the heat exchanger secure flue bend with the two
screws previousty removed. NB : It is advisable to reduce the tension from the termi-
nal securing chains before locating flue bend. Retension after fixing bend securing chain with the nut and bolt provided. See 4.4.2.
4.8
Overlap 50 mm (2 ins)
4.7.2
4.7.3
Assembling the flue duct and bend (walls 100 mm to 350 mm (4 ins to 14 ins)
a) The flue duct is telescopic and should be extended to a
length equal to tha wall thickness plus 100 mm (4 ins)
including an overlap of not less than 50 mm (2 ins).
b) Tape around the joint in flue duct.
c) Slide flue duct through the air duct and fully engage
in the terminal. d) Replace the flue bend engaging the flue duct. e) Ensure that the flue bend sits evenly and securely on
the heat exchanger, secure flue bend with the two
screws previously removed. Assembling the flue duct and bend (walls
355 mm to 600 mm 14 to 24 ins) - 14 ins flue as-
sembly plus extension kit. a) The flue duct is telescopic and comprises 3 pieces it
should be extended to a length equal to the wall
thickness plus 100 mm (4”) including two overlaps of
not less than 50 mm (2 ins).
b) Proceed as 4.7.2 b to e. NB : When a 24 ins flue assembly is supplied the flue
duct comprises 2 telescopic sections.
Making the gas connection a) Fit the gas service tap (B) together with the filter was-
her 0.
b) The gas supply pipe size should be sufficient to ensu-
re that there is 20 mbar (8 in.w.g.) pressure at the service tap, with the appliance working.
NB : The gas supply pipe size should not be less than the gas inlet to the appliance.
11
Making the water connections a) Remove sealing plugs.
b) Fit the nuts and olives supplied in the accessory box. c) Enter the FLOW pipe into the RIGHT hand connection
and the RETURN goes to the LEFT hand connections.
d) Tighten compression fitting holding connection on in-
side of boiler.
Making Electrical Connections (See section 2 for electrical supply requirements.)
a) Remove control box cover (see 8.10). b) Three core heat resisting supply cable is passed
through clamp and through slot in casing, and into
rear of electrical box and connected to terminals on connection block and the earth connection made to earth terminal.
c) Connect pump cable to terminals @I and the earth on
earth terminal.
d) Connect ancillary controls across terminals marked 5
and 6. See controls diagrams, Pages 8 and 12.
e) Clamp wires with cable clamp. f) Replace control box cover.
NOTE : The length of the earth wire between the cord anchorage and the terminal must be such that the live and neutral wires become taut before the earth wire if the supply cord is pulled.
4.11
Maik
Pump
Resetting high limit thermostat
El@ reset
a) If for any reason the high limit thermostat operates
the pilot will go off and the boiler will require manual
re-setting.
b) Re-establish the appliance by re-setting the high limit
thermostat by pressing the red buttom in hole on electrical panel.
c) Establish cause and rectify - see fault finding chart,
page 21.
L
In the event of an electrical fault after installation preliminary electrical system checks as described in the Multimeter Instruction book should be carried out.
Checks to ensure electrical safety should be carried out by a competent person, i.e. earth continuity, polarity and resis-
tance to earth
3 Wire clock
CHALLENGER -SIMPLE CONTROLS
Room thermostat only
4 Wire clock
Fig. 15
f f R~~~~~~~ @
N N
Room thermostat and time clock
Fig. 16
12
6
I
Frost thermostat
Fig. 17
5.
5.4

COMMISSIONING -OPEN VENTED SYSTEMS

5.1
5.2
Gas Installation
The whole of the gas installation, including the meter should be inspected and tested for soundness and pur­ged in accordance with the recommendations of CP 331 :3.
Water circulation system ­Open vented system only
The whole of the system should be filled and thoroughly
flushed out with cold water without the pump in posi-
tion. Ensure that all valves are open. With the pump fitted the system should be filled and air
locks cleared. Vent all radiators and check for water soundness.
Light the boiler as detailed in 5.3.
The water system should be heated to maximum wor-
king temperature and examined for water soundness. Both gas and water should then be turned off and the
water system rapidly drained while still hot. The system should again be filled, cleared of air locks and
examined for water soundness and inhibitor added to
the system if required in the specification (See section
3.9).
5.3 Lighting the boiler
a) Check that the gas service tap is open.
b) Switch controls to a demand mode, ensuring that
pump is running.
c) Push the button marked ‘on’ fully in and hold for 10
seconds. d) Check that pilot is alight and release button slowly. e) If the pilot extinguishes press red button and repeat
from (b). (The pilot should be about 13 mm (l/2”) long
and impinge on the tip of the thermocouple). f) If the pilot extinguishes, wait 3 minutes and repeat b)
above.
g) After 30 seconds the main burner will light. h) Check for gas soundness around the boiler gas corn-
ponents using sense of smell and leak detection fluid.
i) Check and adjust gas rate as detailled in 5.4.
5.4
Gas rate adjustment
fore adjusting by-pass.) NB : The boiler is supplied rated at the highest output.
The boiler is fitted with a gas rate adjuster. a) Switch boiler to off by pressing OFF button.
b) Remove the pressure test point screw C (8.5) and
connect a suitable pressure gauge.
c) Remove the hexagonal cap from gas volume adjuster,
D (7.5) exposing the adjustment screw. d) Turn boiler on by pressing ON button (see lighting boi-
ler 5.3).
e) Adjust pressure after boiler has been running for 10
minutes and then check the gas rate. Setting pressu­res are given in graph relative to required output. The pressure will be reduced by clockwise movement of
screw, increased by anti-clockwise movement. f) Turn boiler to OFF and refit pressure test point screw
and volume regulator cap. Test for gas leakage around pressure test point.
g) Mark the data badge to indicate output to which boi-
ler has been set.
h) Replace case. Particular attention must be given to
ensuring that the case seal is sound when the casing
is replaced.
(TO be carried out be-
5.5 Adjusting the by-pass
NB : The by-pass valve should be of the lock shield pat­tern.
Set the pump to achieve the system requirements but ensure that the minimum flow rate through the boiler is achieved (See 1.4 - page 3). This is equivalent to a temperature rise across the boi!er of 15” C. Set boiler thermostat to maximum.
Fit the boiler with the by-pass fully closed and the system on full load, i.e. central heating and domestic hot water (indicator valve fully open).
Adjust the system to minimum load. This will normally be central heating only with one radiator operating.
Open the by-pass gradually until the boiler operates quietly at all flow temperatures and the boiler ther­mostat turns off the gas.
6
6.1
SEALED SYSTEMS Safety valve
A safety valve shall be fitted close to the appliance on the flow pipe. Only safety valves set to operate at 3 bar shall be used ; they shall be so positioned or any dischar­ge pipe so arranged, that discharge of water or steam from the valve cannot create a hazard to occupants of the premises or cause damage to electrical components and wiring.
6.2 Pressure Gauge
A pressure gauge covering the range O-4 bar (O-60 Ib/in2) shall be fitted to the system adjacent to, and visible from, the filling point.
6.3 Expansion vessel
0) A diaphragm type expansion vessel shall be fitted by a connection to the inlet side of the circulating pump, in a manner laid down in the vessel makers’ instruc­tions (see page 14 for illustration of recommended system layouts). The expansion vessel shall be capable of accepting water up to at least 62.5 % of its volume without damage.
(ii) The nitrogen or air charge pressure of the expansion
vessel shall not be less than the hydro-static head (height of the top point of the system above the ex­pansion vessel).
(iii) The expansion vessel shall be sized in accordance with
the Table on page 14.
3
boil: output kW
9 ?
51 I I I I I I I I
5
I e
=,
30 BF
outputBtu/h
40 E.F
i
-6 t
5 B
m E
13
Safetvvalvesetting (bar) Vessel charge pressure (bar) Initial system pressure (bar) Total water content of svstem Expansion Vessel Volume (litres)
litres
25 50
75 100 125 150 175
200 250 300 350 400 450 500
For systems volumes other than those given above, multiply the system volume bv the factor across
3.0
0.5
0.5 1.0 1.5
2.1
4.2
6.3 10.5 19.4
8.3 14.0 25.9 55.1 10.9 19.0 41.2 15.6 33.1
10.4
12.5
14.6 24.5 45.3 96.4 19.1 33.2 72.1 27.3
16.7 28.0 51.8 110.2 21.8 38.0 82.4 31.2
20.8 35.0 64.7 137.7 27.2 47.5 103.0 39.0 82.7
25.0 42.0 77.7 165.3 32.7 57.0 123.6 46.8 99.3
29.1 49.0 90.6 192.8 38.1 66.5 144.2 54.6 115.8
33.3 56.0 103.6 220.4 43.6 76.0 164.8 62.4 132.4
37.5 63.0 116.5 247.9 49.0 85.5 185.4 70.2 148.9
41.6 70.0 125.9 275.5 54.5 95.0 206.0 78.0 165.5
0.0833 0.140 0.259 0.551 0.109
3.5 6.5
7.0
17.5
21.0
12.9 27.5 5.4 9.5 20.6
32.4
38.8 82.6 16.3 28.5 61.8 23.4
2.0 1.0
13.7 2.7 4.7 10.3
41.3
68.9
1.0
1.5 2.0 1.5 2.0
8.2 14.2 30.9 11.7 24.8
13.6 23.7 51.5
0.190 0.412 0.156 0.331
1.5
3.9 8.3
7.8
19.5 41.3
16.5
49.6
57.9
66.2
I
For the Challenger boilers the volume found from the above table shall be multiplied by 0.80
6.4 Hot Water storage Cylinder
The hot water cylinder shall be the indirect coil type which is suitable for the system pressure.
6.5 Make-up system
Provision shall be made for replacing water lost from the system either :
(0 From a make-up vessel or tank mounted in a position
higher than the top point of the system and connec­ted through a non-return valve to the system on the return side of the hot water cylinder or the return side of all heat emitters, or -
(ii) Where access to make up vessel would be difficult, by
pressurisation of the system.
6.6 Mains Connection
There shall be no connection to the mains supply or to the water storage tank supplying domestic water, even through a non-return valve, without the approval of the local Water Authority.
6.7 Filling Point
For filling system see BS 5376 Pt2 appendix A. A tempo-
Pump on the return Pump on the flow
6.8
rat-y hose connection is only permissable if acceptable to
the local Water Authority.
Pipework
Pipework should be of copper; small bore or microbore
with capillary or compression jointing to a high standard.
Leak sealant shall not be used in the system.
Where a vessel of the calculated size is not obtainable, the next available larger size should be used.
For the purpose of the above calculation, the volume of
the system shall be determined as accurately as possible
using manufacturers’ data as appropriate. Alternatively the volumes given below may be used to give a conser­vative estimate of the system volume :
Boiler 0.5 litres (0.11 gallons)
Small bore pipework 0.3 litres (0.07 gallons)
per 0.292 kW (1000 Btu/h) of system output Microbore pipework 7 litres (1.5 gallons) Steel panel radiators 2.3 litres (0.5 gallons)
per 0.292 kW (1000 Btu/h) of system outpu’ Hot water cyliner 2 litres (0.44 gallons)
If a system is extended, an expension vessel of increased
volume may be required unless previous provision has been made for the extension.
Diagrams showing System layout
14
1 - Expansion vessel 2 - Pressure gauge 3 - Filling point 4 - Drain cock 5 - Air release point 6 - Safety valve 7 - Top-up bottle 8 - Temporary hose connection
or pressurisation make up.
5.9
6.9
Commissioning Sealed System Only
The whole of the system should be filled and thoroughly flushed out with cold water without the circulating pump
in position. Ensure that all valves are open. (The system must be filled with water either from a sealed system fil­ler pump with a break tank, or by any other method ap­proved by the Local Water Undertaking).
With the circulating pump fitted the system should be filled and airlocks cleared until the pressure gauge regis­ters 1.5 bar (21.5 Ibf/in*).
Vent all radiators and check for water soundness.
Manually raise the water pressure to ensure that the sa-
fety valve lifts. This should occur within + 0.3 bar (t-
4.3 Ibf/in*) of the preset lift pressure, ie. 3 bar (43.5 Ibf/in*).
Release water from the system until the initial system design pressure is attained, taking into account any dif-
I
rectkier tld; a6ji
transformer
1
ference in height between the pressure gauge and the point at which the pressure vessel is connected.
Light the boiler as detailed in 5.3. The water system should be heated to maximum wor-
king temperature and examined for water soundness. Both gas and water should then be turned off and the
water system rapidly drained whilst still hot. The system should again be filled, and inhibitor added to
the system, if required in the specification (see 3.9). clea­red of air locks and adjusted to the initial design pressu­re. Any set pointer on the pressure gauge should be set to coincide with the indicating pointer. Examine for wa­ter soundness. Now adjust the gas rate and the system by-pass (See 5.4 and 5.5).
n.b.
The boiler is supplied rated at highest output. The boiler is fitted with a gas rate adjuster.
S6
F1
n
1
2 amp. fuse
,L
5
supply 24 V DC
I I
*mistor
.-..-A..-- 1 1 I 1 I I
comparltor
orange solenoid
I
variable
I
pump
I
50
Hz
Fig. 19
CHALLENGER TEST POINTS
Solenoid Valves
Earth
Orange and Blue
Printed Circuit Board (Temperature & Sequence Control)
External Controls
Fig. 20
Thermocouple
I I
Thermoelectric Valve
Electrode Solenoid valves
d/v b7l @!” I
4!22, Blue
I I-
White
* I :
B
Thermo- ’ ’ .
~elecrnc
I I/ UM/ ‘a
240V 50 Hz
White
/ I
I
Thermistor
temperature sensor
White
I I
I I
Ignition
JJ
Red
:rol box
Fig. 2
control
thermostst
1
16
7.

SERVICING

For efficient and trouble free operation it is important that the CHALLENGER receives regular maintenance. The following
schedules are recommended
Before commencing any work turn off the gas at the gas inlet service 4.8 tap (Page 4). Ensure that the electricity
disconnected. NB : Always test for a gas soundness after completing any servicing or exchange of gas carrying components
supply
is
7.1
7.2
Remove front casing a) Remove screws (A) at top and bottom of boiler.
b) Remove two screws from lower front of case (B). c) Remove case by pulling forward easing out bottom
first.
d) Replace in reverse order.
Remove combustion chamber front panel
a) Remove six screws securing front panel of combus-
tion chamber.
b) Remove panel by easing forward at bottom and di-
sengage from flue hood by pulling downwards.
Remove burner assembly
a) Remove screws securing burner manifold to gas sec-
tion (A). 30 BF and screws A and B (end of manifold in the 40 BF).
b) Remove c) Burner can now be removed.
To remove pilot a) Release thermocouple from bracket retaining screw
and securing clamp (A). Move thermocouple to the side.
b) Release the electrode by loosening screw (B) on right
hand side of assembly and rotating retaining clip.
c) Remove pilot gauze and filter by removing screw (0
securing gauze to assembly.
d) Remove pilot by unscrewing (nut size 8 mm AF) using
set or adjustable spanner.
e) The pilot injector can be cleaned and should be repla-
ced bright side uppermost.
f) Replace in reverse order.
manifold and gasket and
retain in a safe
17
Cleaning the parts a) The burner can be cleaned by inverting and brushing with a soft brush.
b) The heat exchanger matrix can be cleaned by brushing. It may be an advantage to remove flue hood see 4.7. If deposits
are too hard to remove by brushing, the matrix can be removed - see section 8.7 page 19 and washed with hot water and
detergent. c) The gas filter (see C 4.8) can be cleaned using water and detergent d) Replace all components in reverse order. NB : particular attention must be given to ensuring that the case seal is sound
when the casing is replaced.
- DO NOT USE SOLVENTS.
8.
8.1
8.2

REPLACEMENT OF PARTS

Replacing thermocouple a) Remove front case 7.1
b) Remove combustion chamber front panel 7.2 c) Remove burner 7.3 d) Release thermocouple from bracket securing clamp
(A).
e) Release at thermoelectric valve by unscrewing nut
10 mm.
f) Disconnect from overheat thermostat by pulling
connections apart.
g) Replace in reverse order (taking care to replace rub-
ber seating BF only).
Replace high limit thermostat a) Remove front case 7.1 and electrical control box 8.10.
b) Remove two screws (A) securing overheat assembly. c) Disconnect at pin connectors by pulling apart, d) Remove sensor from dry pocket first removing split
pin.
e) Replace in reverse order using a heat sink grease on
the sensing phial.
8.3
8.4
Replace spark electrode and lead a) Remove front case 7.1.
b) Remove combustion chamber front panel 7.2. c) Remove burner 7.3. d) Remove thermostat knob and six screws from front
of electrical control box.
e) Remove plugs from rear of electrical controls box. f) Slide PCB forward and remove spark terminal. g) Feed lead out through rear of control box.
h) Loosen screw securing clip - retain electrode and turn
clip through 90 ‘,
i) Withdraw electrode by sliding forward.
j) Replace in reverse order taking care to locate electro-
de in locating groove and to replace plugs in rear of
To replace thermoelectric valve a) Remove front cover.
b) Remove thermocouple connection, c) Remove nut securing thermoelectric d) Withdraw thermoelectric valve. e) Replace in reverse order.
valve (25 mm).
18
8.5
8.5
8.6
8.7
To replace solenoid valves al Remove front casing 7.1.
b) Remove electrical control box 8.10. cl Withdraw plug connections (A) (colour coded from so-
lenoid valves.
d) Remove four screws (B) securing solenoid valve
mounting plate.
e) Remove mounting plate and solenoids -
not to misplace springs.
f) Replace in reverse order.
To
replace microswitch
a) Remove front casing 7.1.
b) Remove electrical control box 8.10.
c) Remove plugs (A) from microswitch.
d) Remove two screws (B) retaining microswitch.
e) Replace in reverse order.
To
replace heat exchanger
take care
8.8
a) Drain system.
b) Remove front casing 7.1.
c) Remove combustion chamber front panel 7.2.
d) Remove burner manifold and burner 7.3.
e) Remove flue bend (A).
f) Remove overheat thermostat phial - left hand side
(B).
g) Withdraw thermostat temperature sensor - right
hand side 0. h) Unscrew nuts on flow and return connections. 0 Slacken four screws securing combustion to rear chas-
sis.
j) Drop assembly and withdraw forwards.
k) Remove two screws from rear of assembly retaining
heat exchanger to combustion chamber. I) Replace in reverse order.
To replace pilot injector a) Proceed as 7.4.
b) Replace injector ensuring it is fitted bright side
uppermost.
8.9
19
To
replace combustion chamber linings
a) Remove front casing 7.1. b) Remove combustion chamber front panel 7.2. c) Remove burner 7.3. Slide outside linings first followed by
rear lining which is removed by easing upwards and sli­ding out from bottom. Replace in reverse order taking care that front lining is correctly positioned.
8.10
Pump
To replace electrical control box a) Isolate electrical supply.
b) Remove front casing 7.1. c) Remove six screws retaining electrical control box co-
ver
8.7
- F. d) Withdraw plugs from rear of box. e) Disconnect to terminal strip. f) Slide PCB forward and disconnect spark electrode and
earth leads. g) Remove 2 screws securing control box to chassis. h) Replace in reverse order taking care to replace plugs
in rear of control box. NB : Care should be taken to ensure correct location of
the ON, OFF and reset buttons.
8.11
8.12
8.13
To replace thermostat
L
A
-
a) Isolate electrical supply. b) Remove front casing. c) Undo knurled ring (A) retaining thermostat phial and
remove phial. d) Unplug from rear of control box. e) Replace in reverse order using heat sink grease on the sensing phial.
To replace fuse a) Isolate electrical supply.
b) Remove front casing 7.1. c) Remove cover on electrical control box (8.10 c) d) Remove and replace fuse. e) Reassemble in reverse order.
To replace PCB a) Isolate electrical supply.
b) Remove front casing 7.1. c) Remove electrical control box cover (see 8.10 c). d) Remove plugs from rear of electrical control box. e) Ease forward PCB and remove spark electrode wire
and earth wire from spark generator. f) Slide board forward and remove. g) Replace in reverse order.
8.14
Testing of FFD Circuit Closed circuit
- Slide back insulation at plug in connection and attach
millivolt meter using crocodile clip connectors.
- Output should not be less than 3 mv.
Open circuit
- Disconnect round pin connectors.
- Attach millivolt meter using crocodile clips to the ther­mocouple side - male connectors.
Press and hold ignitor button.
- Output with pilot on should not be less than 14 mv.
NB : If closed circuit output is high and approaching the open circuit voltage obtained, then suspect faulty ther­moelectric valve.
20
I-
I
I

SHORT LIST

(@I 46 @j 31
78
n I
63a
w
Key No
5 7a 7b
17 19
20 21 30 31 33 38
41 42 43 44 45 46 47 49 63a
78 117 118 141 203 225
47
Description
Screw M6 front cover/control box securing ......................
Door assembly (30 BF) ........................................
Door assembly (40 BF) ........................................
Temperatureselectorknob
Screw front case/rear case securing ............................
Plasticwasher.. .............................................
Serratedwasher.. ...........................................
Nut3/4..BSP ................................................
Olive(22mm) ...............................................
Top fixing bracket ...........................................
Bottom bracket 30 BF only ....................................
Cableclampbracket ..........................................
Cableclamp.. ...............................................
ScrewscableclamtYbracket ...................................
Gasfilterwasher .............................................
Gasservicecock .............................................
Olive (15 mm)
Nut1/2”BSP ................................................
Fixing screw - Bracket to case
Thermistortemperaturesensor ...............................
Foam gasket-rearcase/airinletduct ...........................
Thermocouple assembly ......................................
Electrode and lead assembly
High limit thermostat assembly ................................
Printed circuit board
Fuse(2amp) ................................................
...............................................
...................................
.................................
...................................
.........................................
42
GC Number Part Number
366713 65622/01 366688 64143 366649 64150 366553 64051 402327 45817 407715 34377 366035 366558 366559 366250 40169/06
366
691 65485106 366564 65519106 366565 27834 366714 45654 263 545 366566 263800 56489 366642 56490/01 366 546 66207/03 366570 64154 366662 56511 366667 366593 63404 366636 65962 366614 63176 264446 44790
13183
47509
47508
37309 65960
65974
Chaffoteaux Ltd, Concord House, Brighton Road, Salfords, Redhill, Surrey RH15DX. Telephone: Horley (02934) 72744. Telex: 87378.
ESP023
Loading...