Chaffoteaux & Maury Calydra 80, Calydra 100 Installation And Operation Instruction Manual

COMBINATION BOILER

Calydra 80
Calydra 100
Heating and lnstantane~us
eater with TSS@ Fanned Flue system
Domestic Hot
Installation and Operating instructions
These instructions are suitable for the following boilers :
Calydra 80 Calydra 100

CUSTOMER CARE

chaffoteallx~
Chaffoteaux et Maury Ltd , as a leading manufacturer of domestic and commercial water heating appliances, as well as domestic unvented direct and indirect storage cylinders, is committed to providing high quality products and a first class after sales service. If it is necessary to contact an engineer, then telephone your local Chaffoteaux Service Centre. The number can be obtained from the leaflet enclosed with your appliance or by telephoning the Chaffoteaux Customer Services Department at Telford
Advice on installation or servicing can also
CUSTOMER SERVICES DEPARTMENT
Tel 01952 222288 Fax 01952 260915
GUARANTEE The manufacturer’s guarantee against faulty manufacture or materials for the cylinder and secondary heat exchanger is 5 years, from the date of purchase. For the boiler, electrical components, thermal controls and safety valves it Is for 12 months. from the date ot purchase. The guarantee will be rnvalrdated if the factory frtted DHW pressure relief valve is tampered with or removed The Manufacturer or Distributors cannot be held responsible for any damage howsoever caused and which is a consequence of the removal or tampering The guarantee may also be invaltdated if the appkance is not installed by a competent person in accordance with the recommendations made herein, current standards, regulations or in a manner not approved by the manufacturer, modified in any way, subjected to frost, misuse or neglect and that factory fitted parts have had unauthorised repairs or replacemenfs carned out Evidence of purchase and the date ot supply must be made available at the time of any claim. The guarantee is only vakd for appkances installed in the UK To asstst us In providing you with an efficient after sales service, please return the guarantee registration card enclosed with the cylinder without delay.
STATUTORY REQUIREMENTS The mstallatton of this appliance must be carried out by a CORGI Registered person or other competent person and in accordance with the requirements of the Gas
Safely (Installatron and Use) Regulations. In addrtion, the installahon must also comply with the current byelaws of Local Water Undertakings, Building Regulations, IEE Wiring Regulations, Local Authority
Building Standards (Scotland) Regulations and the Safety Document 635 The Electricity at work Regulation, It should also be carried out in accordance with current editions of the following British Standards Codes of practice: BS 6891, BS 5440 parts I and 2, BS 5449 part 1, BS 7593, BS 6798, BS 5546, BS 4814, BS 7074 part 1 and 2, BS 7671 and BG DM2 If there is a possibility of the incoming mains water pressure exceeding 7 bar then a suitable pressure limiting valve must be fitted.
Precautions During servicing, keep the dust generation to a minimum and avoid inhaling any dust and contact with the skin and eyes, Normal handling and use will not present any discomfort, although some people with a history of skin complaints may be susceptible to irntation. When disposing of the lining, ensure that it is securely wrapped and wash hands after contact
be contacting the Chaffoteaux Customer
Services Department
q
--iA
Page
CUSTOMER CARE.. ....................................................................
Guarantee.. ..................................................................................
Statutory Requirements.. ............................................................. 3
Contents.. .....................................................................................
INTRODUCTION.. ........................................................................
DESCRIPTION.. ...........................................................................
LOCATION OF COMPONENTS
SPECIFICATIONS.. ......................................................................
DIMENSIONS.. ............................................................................. 10
OPERATION ...............................................................................
DOMESTIC HOT WATER MODE CENTRAL HEATING MODE..
INSTALLATION .......................................................................... .15
PLANNING ..................................................................................
LOCATION .................................................................................
INSTALLING THE CALYDRA
INSTALLATION ...........................................................................
POSITIONING THE BOILER ON THE WALL.. CONNECTING THE BOILER TO THE SYSTEM.. FITTING THE HORIZONTAL
MAKING THE ELECTRICAL CONNECTIONS ........................... .18
PRE-COMMISSIONING.. ............................................................ .20
Electrical Adjustments ........................................................... .20
1. Room thermostat options..
2. Pump Speed Adjustment.. ................................................ .20
3. Burner operating modes
COMMISSIONING.. .....................................................................
DHW.. ....................................................................................
Central Heating .....................................................................
.................................................. 6
............................................... .12
..................................................... .I4
.................................................... .15
............................ 15
FLUE.. .......................................... .17
...................... .18
.12
.15
..15
.15
................................................ .20
:. ................................................. .20
.22 .22 .22
LIGHTING THE BOILER
3
POST COMMISSIONING..
3
HANDING OVER TO SYSTEM GUIDANCE..
4
FLUE ........................................................................................... .24
5
VENTILATION.. ........................................................................... .25
6
GAS SUPPLY.. ............................................................................
ELECTRICAL SUPPLY..
8
FLUSHING AND WATER TREATMENT
SYSTEM CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
BY PASS AND PUMP EXPANSION VESSEL..
FILLING POINT.. .........................................................................
............................................................. .22
........................................................... 23
THE HOUSEHOLDER.. ............................ .23
................................................................ .24
............................................................. .25
................................................................. .27
............................................................... .28
...................................... 26
MAINTENANCE.. .........................................................................
USER’S INSTRUCTIONS
Control panel ...............................................................................
Isolating Taps ..............................................................................
SWITCHING ON.. ........................................................................ .30
Hot Water ....................................................................................
Heating and Hot Water.. ..............................................................
Heating Only.. To Turn Boiler Off Completely..
INSTRUCTIONS FOR SETTING THE BUILT IN CLOCK..
MECHANICAL TIMER.. ...............................................................
1. General Layout..
2. To Set the Time.. ..................................................................... .31
3. To Set the “On” and “Oft” Times.. ............................................ .31
4. To Select Function MODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
..............................................................................
........................................................... .29
................................................... .30
......................................................................
Page
.25
.28
28
.29 .29
.30 .30 .30
........ .31
.31 .31
By combining their modern highly efficient low water content fanned TSS@‘Temperature Stabilised System”, Chaffoteaux et Maury have
This unique combination is able to provide the user with hot water immediately at the outlet of the appliance temperatures at both extremely low flow rates or when several taps are opened together.
The TSS@ is a 5 litres, independently controlled mini unvented storage cylinder, powered by a 3 kW coil. It works in conjunction with the Chaffoteaux et Maury low pressure instantaneous domestic hot water system.
The CALYDRA, as well as providing hot water, provides central heating. The boiler is designed for sealed systems only. A two speed circulating pump, diverter valve, expansion vessel as well as a pressure gauge and safety valve are included within the boiler.
The CALYDRA provides the advantages of mains pressure hot water water supply the CALYDRA does not need a separate feed cistern or vent pipe in the loft space.
The CALYDRA has been tested and approved by the WRc as meeting
boiler has been tested and approved to carry the
The The CALYDRA can be installed with
arrangements. Adapters, bends and other accessories are available on request. The boiler is packed in TWO cartons:
1. The boiler.
2. The flue assembly and fixing kit.
the standard horizontal flue, raised horizontal,
CE mark.
flue combination boiler concept created a whole new concept.
CALYDRA
to taps and showers. Supplied directly
with the requirements of the water by-laws scheme.
concentric
and the brand new
and
stable
from the main
vertical, twin pipe flue or seduct
Location of components
1. Flue hood with fan
2. Sealed chamber
3. Gas valve assembly
4. Electrical box
5. Pump
6. Automatic air separator and automatic vent
7. Multi-gas burner assembly comprising ignition and ionisation electrodes
8. Combustion chamber
9. Main heat exchanger
10. Steel chassis complete with expansion VE
11. Air pressure switch
12. Overheat thermostat
13. TSS @J (mini cylinder)
14. Central heating control thermistor
15. Three way valve
16. Expansion vessel connecting tube
17. By pass adjustment screw
18. By pass
19. CH Flow isolating valve
20. Domestic hot water outlet
21. Gas service tap
22. Water service tap
23. CH Return isolating valve
25. Pressure relief valve
27. DHW pressure relief valve
28. TSS@ control thermistor
Fig.1
29. Location of heating filter (not visible)
30. DHW circuit flow switch
31. Heating circuit flow switch
32. Hot water control thermistor
33. Secondary heat exchanger
34. Four position selector switch
35. User’s instruction panel.
36. Domestic hot water temperature adjustment
37. Heating flow temperature adjustment
38. Green indicator - Power ON
39. Orange indicator - Burner ON
40. Red indicator - Lock out / flame failure
41. Reset button
42. Mechanical clock
43. Pressure gauge
SPEClFlCATloNS
CALYDRA
Appliance category Heat input C/H
Maximum
Heat output C/H 81 DHW Maximum
C/H circuit pressures Min operating
Max operating
DHW specific flow rates for 10 min
Q 30 deg C rise
Q 35 cieg C rise
DHW circuit pressures Min operating
Max operating
Flow limiter rate Compartment ventilation
& DHW
80 100 CALYDRA 80 100
Cat ii 2H 3+ Cat ii 2H 3+ Natural gas G20
25.9 kW 31.1 kW Maximum 2.74 m31h 3.29 m3/h 88392 Btuh 106138 Btu4-1 97 ft3lh 116ft31h
23.25 kW 28.0 kW Nominal 20 mbar 20 mbar 79347 Bhuh 95558 lBu4-1 8inwg 8inwg
0.7 bar 0.7 bar Nominal 11 mbar 12.8 mbar 10 lb/in2 10 lb/in2 4.4 in wg 5.12 in wg
2.5 bar
36.3 lb/in2 36.3 lb/in2 Natural gas G20 1.23 mm 1.28 mm
11.5 Vmin 13.9 Vmin Z3 restrictor 6.7 mm no restrictor
2.54 gal/min 3.06 gai/min
9.86 Umin 11.91 Umin PROPANE LPG G31
2.17 gallmin 2.62 gailmin Gas rate
0.1 bar 0.1 bar
1.45 lb/in2 1.45 lb/in2 inlet pressure
7 bar 7 bar
100 lb/in2 100 lb/in2
8 Vmin 10 Vmin not required
2.5 bar
Gas rate
inlet pressure
Burner pressure
Burner injector and restrictor diameter
l/3 restrictor 2.60 mm 2.9 mm
Maximum
Nominal
Burner pressure Nominal
2.00 kg/h 2.42 kg/h
4.41 lb/l-u 5.34 Ib/hr
37 mbar
14.8 in wg
35 mbar 14 in wg
37 mbar
14.8 in wg
30.4 mbar
12.16 in wg
CALYDRA BUTANE LPG G30
Gas rate Maximum
inlet pressure Nominal
11.2 in wg Burner pressure
Nominal
Burner injector and restrictor diameter Butane LPG G30 l/3 restrictor 213 restrictor
80
2.04 kg/h
4.50 lb/h
28 mbar
11.2 in wg
26.7 mbar
10.7 in wg
0.7 mm
1.75 mm
4.9 mm
100
2.45 kg/h
5.40 lb/h
28 mbar
24 mbar
9.6 in wg
0.76 mm
2.0 mm
6.7 mm
CALYDRA Safety discharge -
Heating
Safety discharge - DHW
Expansion vessel Pre-charge pressure
Net capacity at 2.5 bar Adjustable by-pass
Minimum flow rate
Maximum flow rate
80 100
2.5 bar 2.5 bar
36.25 iblin2 36.25 lb/in2
7 bar 100 lb/in2
7 bar
100 lb/in2
0.7 bar 0.7 bar
9.4 lb/in2 9.4 lb/in2
5.44 itr 5.44 itr
150 i/h 150 i/h
0.55 gai/min 0.55 gai/min 480 i/h 480 iih
1.76 gai/min 1.76 gal lmin
Electrical characteristics SUPPlY
Consumption Protection Fuse no 1 Fuse no 2 External controls
23fiv5oi-k 23Ov5OHz 155w 155w IP 44 iP44 2A 2A
1.25A 1.25A 24V 24V
With packaging :
-Calydra 80 : Calydra 100 : 49.5 kg
Without packaging :
-Calydra 80 :
-Calydra 100 :
49.0 kg
46.5 kg
47.0 kg
Liit weight :
Weights
-Calydra 80 :
-Calydra 100 :
41.5 kg 41 .O kg
Tails diameter
J Heating flow
022mm K D.H.W. flow 015mm L Gas supply 022mm M Cold water inlet N Heating return
015mm
022mm P Safety valve outlet 015mm
Outer case dimensions :
-Width :
- Height :
- Depth : 380
1po
a,:
I : ‘. ji --
-
. -
--_
i-
All dimensions in mm
Fig. 4
440 (minimum space required 450) 850
Safety valve center line
66