Chaffoteaux & Maury Britony FIexiFIue Installation And Servicing Instrucnions

Page 1
Supplied By www.heating spares.co Tel. 0161 620 6677
Britony
Room Sealed Balanced Flue
MULTI POINT WATER HEAm
GAS SAFETY (INSTALLATION AND USE) REGUIATIONS.
It is the law that all gas appliances are installed by a competant person
(For use on natural gas only G20)
G.C. N” 52 980 22
from serial number 8942 16759-04
FIexiFIue
fastallatfon
and servicing instructfons
(leave these instructions with the aser)
The model number and serial number of this heater are on the data badge which is found inside rear case at lower IeA hand side. These numbers should be used when ordering replacement parts.
CONFORMSWIIHEUROPEANSTANDARDEN.26
Looking Good.Heating Better
Page 2
Supplied By www.heating spares.co Tel. 0161 620 6677
Page 3
Supplied By www.heating spares.co Tel. 0161 620 6677

CONTROL OF SUBSTANCES HARMFUL TO HEALTH

IMPORTANT To comply with the Control of Substances Harmful to Health Regulation 1988 we are required to provide infor-
mation on the following substance that is contained in this appliance. Description Combustion Chamber Lining Material Alumino Silicone Fibre Precadons During servicing, keep the dust generation to a minimum and avoid inhaling any dust and
contact with the skin and eyes. Normal handling and use wil not present any discomfort, although some people with a history of skin complaints may be susceptible to irritation., When disposing of the lining ensure that it is securely wrapped and wash hands after.
I
Page 4
Supplied By www.heating spares.co Tel. 0161 620 6677
L. GENERAL
The Britony Fle.xiFlue is a room sealed, fanned balanced ffue, multipoint water heater. The flue which is
100 mm (4”) diameter pipe, can be directed to the rear or to either side. The maximum recommended iIue
length is 3 metres for straight application and 1.6 metres total when using a bend.
The appliance is for connection to a mains cold water supply having a
A permanent electrical connection is required and should be provided by use of a fused spur. The external
electrical supply should be via a double pole switch having 3 mm. contact separation in both poles. If the appliance is installed in a bathroom the fused spur must be external to the bathroom.
When on pilot only the fan runs at “low speed” increasing to normal speed when there is a demand for hot water. Included is a pressure switch, which operates if the fan stalls or if the flues is obstructed and a low tem-
perature sensor which will turn off the fan when the appliance is running on pilot only (fan low speed) in the event of low air temperatures likely to cause freezing in the appliance.
Note : Gas Safety Installation and Use Reg 1984. It is the law that all gas appliances are installed by C.O.R.G.1 registered persons in accordande with the above regulations. Failure to install appliances correctly could lead to prosecution. It is in your own interest and that of safety to ensure compliance with the law.
minimum working pressure of 1 bar.
1.1 Guarantee
The guarantee on this appliance is void if it is not installed in accordance with the recommendations made herein or in a manner approved by the manufacturer.
1.2 Dimensions
3
mm
A
B C D
E F
G
H
J K
L M N
P
S
T
v
W
X
655 25.9 395 270 10.6
100 4.0
40 1.6 385 438 775 30.6 728 28.6
53
55 2.15
98 3.8 70
285
105
199
290
95 3.54
a70
Ins.
15.5
15.15
17.25
2.1
2.75
11.22
4.13
7.8
11.4
34.14
3
Page 5
Supplied By www.heating spares.co Tel. 0161 620 6677
. Technical Data
..
Heat input nomimaf Heat output nominal Gas rate (maximum) :
. Natural gas (G20) 35,9 MJ/ms - 20 mbar .....
with manifold restrictor..
Butane (G30) 45,6 MJ/Kg - . 28-30 mbar.. ....
Propane (G31) 46,4 MJ/Kg - 37 mbar
Main burner injectors :
G20 ..............................................................
. G30 - G31 .....................................................
Pilot injector marking G20..
Water flow rate - raised 50°C (90°F) .................
Water flow rate - raised 25°C (45°F) .................
Min. water pressure selector closed ..................
Min. water pressure selector open
Max. water pressure
Electrical supply
fused 3 A
..........................................
.........................................
...............................
.........
...............................
G30 - G31.......................
....................
.........................................
...............................................
25,2 kW 22,7 kW
2,67 msih
6,l mm diam.
1,99 kg/h 1,96 kg/h
1,28 mm diam.
0,74 mm diam.
26
15
3,2 to 6,5 Enin
6,5 to 13 Rnin
05 bar
1,0 bar
10 bar
240V-50Hz
85966 Btu/h
77452 Btu/h
94,29 fix/h
0,7 to 1,43 gpm
1,43 to 2,8 gpm
16,5 A (7,5 psi) 33,0 ft (15 psi)
150 psi.
The rninimum water pressure is for the correct operation of the appliance only. An additional aJlowance must be made for the resistance of pipework and fittings particularly where showers and washing machines are used. This should be equivalent to 2 m. (6,5 A) head.
Water inlet (Compression type fittings) Water outlet (Compression type fittings).
Gas (Compression type fittings) ........................
Height (iclud.ing ffue bend) ..............................
Width ................................................................
Depth ................................................................
Weight - Cartoned .............................................
Weight - Lift .......................................................
Minimum clearances - top (above flue)
- bottom (below case) .....
- sides. .............................
- front ..............................
Hole for the air inlet duct ..................................
The Britony FlexiFlue is supplied in one carton.
..............
...........
.............
Right hand connection
Left hand connection
Centre connection
778 mm 395 ml-n 270 mm
24,3 kg. 53,6 lbs.
15 kg. 33.1 lbs.
50 mm 2in
178 mm 7in
25 mm 1il-l
600 mm 24 in
102 mm diam.
15 mm Copper 15 mm Copper 15 mm Copper
30,6 in
15,5 in 10,6 in
4.2 in. diam.
Page 6
Supplied By www.heating spares.co Tel. 0161 620 6677
2. INSTALLATION REQUIREMENTS
2.1 Related Documents
The installation of the heater must be in accordance with the relevant requirements of the Gas Safety (Installation and Use) Regulations. Building Regulations and the current Byelaws of the local water undertaking. It should be in accordance with the current British Standard Codes of Practices Local Authority Building standard (Scotland) regulations, and the safety document 635, the electricity at work regulation. Detailed recommendations are contained in the following British Standard Codes of Practice :
BS6400:BS5546:BS5440:F't.l:andPQ:BS7671-BSOM2.
2.2 Location
The location chosen for the appliance must permit the provision of a satisfactory fIue termination The location must also permit adequate space for servi­cing and air circulation around the appliance.
The appliance may be installed in any room or inter­nal space although particular attention is drawn to the requirements of the current BS 7671 and, in Scotland, the electrical provisions of the Building
Standards applicable in Scotland, with respect to the installation of a heater i a room or internal space containing a bath or shower.
Where a room sealed appliance is installed in a room containing a bath or shower, any electrical
switch or appliance control, utilising mains electrici­ty should be so situated that is cannot be touched by
a person using the bath or shower. Where the installation of the appliance will be in an
unusual location special procedures may be neces-
sary and BS 5546 gives detailed guidance on this
aspect. A compartment used to enclose the appliance must
be designed and constructed specifically for this pur­pose. An existing cupboard or compartment may be used provided that it is modified for the purpose.
Details of essential features of cupboardcompart­ment design are given in BS 5546.
2.3 Gas Supply
An adequately sized gas meter must be connected
to the service pipe. Where necessary the local Gas
Region of British Gas will arrange for the existing meter to be checked or for a suitable meter to be installed. On no account must any work be carried
out on the gas meter other than by BRITlSH GAS or
their specifically authorised contractor.
Installation pipes should be fitted in accordance with BS 689 1. Pipework from the meter must be of ade-
quate size. Pipes of a smaller size than the gas
connection should not be used. Gas supply pipes in
excess of 3 metres use 22 mm pipe. The complete installation must be tested for gas
soundness and purged in accordance with BS 689 1.
2.4 Siting the Flue Terminal
The ffue must be installed in accordance with BS 5440 : Pt. 1.
The following notes are intended to give general gui-
dance. The standard ffue set is suitable for walls having a
thickness of 75 mm (3 in.) to 612.5 mm (24 in.) for
rear outlet lluing or up to 500 mm (19,5 in.) for side
outlet ffuing. Other ffue options are available to a
maximum of 3 m (9 ft. 8 in.) to special order.
The appliance must be installed so that the ffue ter­minal exposed to external air. The appliance must NOT be installed so that the terminal discharges into another room space such as an outhouse or lean-to. It is important that the position of the terminal allows a free passage of an across it all times. The minimum acceptable spacings from the terminal to obstructions and ventilation openings are specified in the following chart. Also see Section 3.4.
-
-
A
Directly below an opening, windows etc or adjacent to an opening
B
Below gutters soil pipes or drain
C
Below eaves Below balconies or car port roof 200 mm*
D E
From a vertical drain pipe or soil pipe
F
From an internal or external comer
G
Above ground roof or balcony level
H
From a surface facing the terminal From an opening in the car port
J
(e.g. door or window) into dwelling 1200 mm Vertically from a terminal on the same
K
Wd
Horizontally from a terminal on the
L
same wall
-
* (107 mm) minimum clearance using kit N” 76216.00 (G.C. 264 833)
Termhl poshions
pipes
Mirn
clearances
300 mm
75 mm
200 mm*
75 mm
300 mm*
300 mm 600 mm
1500 rnm
Note - Where the terminal is fitted within 850 mm (34 in.) of a plastic or painted gutter or 450 mm (180 in.) of painted eaves an aluminium shield of at least 750 mm (30 in.) long should be fitted to the underside of the gutter or painted surface.
Where the lowest part of the terminal is less than 2 m.
(6.5 ft) above the level of any ground, balcony, flat roof or place to which any person has access and
which adjoins the wall in which the terminal is situa-
ted must be protected by a guard of durable mate­rial (a terminal guard is available from Quinnel Barrett & Quinnel. 0171 639.1357 (GC No 381.
782) The air inlet/products outlet duct and the terminal of
the appliance must not be closer than 25 mm (1 in.) to any combustible material. Detailed recommenda­tions on the protection of combustible material are given in BS 5440 Pt. 1.
IMPORTANT NOTICE : TIMBER FRAMED HOUSES. If the appliance is to be fitted in a timber framed building it should be fitted in accordance with the British Gas publication <<Guide for Gas
Installations in Timber Framed Housing, reference
DM2. If in doubt advice must be sought from British Gas.
2.5 Wall Mounting
The appliance should be installed on a flat non-com­bustible material which not reverberate. What ever the thickness of the wall a hole 107 mm (4.2 in.) in diameter will be required for the appliance ffue assembly. It is recommended that a core drill be used to form this hole.
For dimensions are clearances see sections 1.2 and 1.3.
Page 7
Supplied By www.heating spares.co Tel. 0161 620 6677
2.6 Flue Terminal Assembly
The flue may be fitted from inside or outside of the building. If fitting from inside the flue duct should be assembled into the air intlet duct and the assembly passed trough the hole in the wall. The outside dia­meter of the terminal is the same as outside diame­ter of the air inlet duct.
3. An un-switched socket outlet compling with BS 1363. The method of connecting the plug brown wire to
live (L) blue wire to neutral (N) and green/yellow to earth ( f ), see fig. 3.
A three core cable should be used and a heat resis­ting cable of 0.75 mm2 (24 x 0,2 mm) is considered suitable.
2.7 hir supply
The appliance does not require any purpose provi­ded ventilation unless installed in a compartment. A compartment enclosing an appliance requires high
I
and low level openings. These openings must either communicate with a room or internal space or be direct to outside air. The minimum FREE area of the opening must be :
Air from room or Internal space
i,,,,,,,,.~
2.8 Electrical Connections
The appliances must be earthed. The installation should be undertaken by a compe-
tent electrician and should be in accordance with the current edition of B.S 7671.
Particular attention should be paid to cross bonding. The appliance must be provided with a means of
isolation. If installed in a bathroom the means of iso­lation must be external to the bathroom o; a double pole cord switch fitted.
Acceptable methods of connection are :
1. A switched, double pole fused spur with 3 mm contact separation on all poles.
2. A double pole switch where the supply must be suitably fused 3 A.
The cable should be passed through the gland on the top of appliance and the clamp tightened to secure the cable. Ensure current carrying conductors become taught before earthing conductor should cable slip from the cord anchorage. Connection to the appliance should be made in accordance with diagram (see section 3, 8, 2).
2.9 Description of Operation
Read in conjunction with iigs 1,2 and 4). The controls on the Britony FlexiFlue comprise of a
range of thermal, electric and electronic switches. Broadly, the thermal controls are for the pilot flame supervision, the electrical controls are functional switching and the electronic controls act as a securi­ty for the functional controls.
The circuit is designed so that. under normal condi­tions, the fan r-t.& continuously at low speed and automatically changes to high speed when the gas valve opens. If, however, the incoming air tempera­ture approaches 0°C the integral frost protection thermostat interrupts the low fan speed signal. Under this condition, if there is a demand for hot water, then the fan recommences at high speed. There is an in-built delay circuit to prevent the safe­ty devices operating prematurely.
The pilot can only be established under the control
of the thermocouple ikrne failure circuit after the
mains electricity connection is made since it is
dependent upon the energisiig of relay-RLl .
If the air ffow is not proved on high speed the &me
supervision device will operate by interrupting the ther-
mocouple as a result of the de-energising relay-RLl .
ELECTRIC SUPPLY
MlC& SWITCH
+ RLZ
RELAY
h L v
FUNCTIONAL FLOW DIAGRRM
RELAY
RLl
_
THERM0
r m”pu -b ElJEclmc
b
,
THERM0
& VALVE
Page 8
Supplied By www.heating spares.co Tel. 0161 620 6677
CIRCUIT DIAGRAM
THERMOELECTRH
WIRING DIAGRAM
FU Fuse (2 A)
TC Thermocoupla BM Thermc4ectrlc Valva SW MIcromitch PR Pressure Switch Y-G Yellow - meen Br Bruwn BI Blue R Red W White 0 orange
Bk Black v vldet 0 Orey
P Pink
ELECTRICAL CONNECTION
fuse 3 A
switched fused spur
NB : IF APPLIANCE INSTALLED IN A BATHROOM
SPUR MUST BE EXTERNAL TO ROOM
-----I--------------
NB : IF APPLIANCE INSTALLED IN A BATHROOM
SWITCH TO BE OF PULL CORD TYPE
3 A. fuse
do;ble&e -
heater
heater
LFig. 2
Fig. 3
7
Page 9
Supplied By www.heating spares.co Tel. 0161 620 6677
OPERATIONAL DIAGRAM
..---_.i
‘E SWITCH
. ’ ii II
II
ii
ii
II II II
II II II II
II II II II
II
II II
IL--- --- IL--- ---
Pig. 4

INSTALLING THE APPLIANCE

3.
A vertical flat area is required for the appliance : 1006 mm high x 445 mm wide (39.6 in x 17.5 in). The surface on which the appliance is mounted must be of a non combustible material.
L
PRINTED CIRCUIT BOAI PRINTED CIRCUIT BOAI
------- -------
I I I I I I I I I
ka
2
RL. RL.
RD
.-_----11
-m-s----
I
II
THERMOCOUPLE
II
N
\
=
N
3.1 Packaging
The appliance is attached to the wall via the mounting bracket and two bottom screw fixings. The appliance is pac­ked in a single carton. Remove contents from carton and check against List.
1)
APPLIANCE
2) FLUE ASSEMBLY
3)
ACCESSORY BOX
- Assembled with trims. : a) Air inlet duct complete with terminal.
b) 2nd section flue duct (inside air inlet duct). c) Hue turret with 1st section flue duct fitted. d) Plastic turret cover.
- containing : -mounting bracket
- ffue locking ring and ‘0’ ring seal
- 2 gaskets
- 4
wall mounting screws
- 4 turret fixing screws
- 2 turret cover fixing screws
- 1 gas control knob
- 1 temperature selector knob
- gas service tap assy (not supplied with LPG models)
- water service tap assy
8
Page 10
Supplied By www.heating spares.co Tel. 0161 620 6677
3.2 Prepatig and fitting the appliance
197,s
mm minimum
I
3
i
it
Preparation :
- Remove the bottom trim by pulkng forwards.
- Slide the controls facla plate (P) upwards to disen­gage from retaining bracket.
- Release the front case by removing the four Exing screws and washers positioned at the top, bottom and centre of appliance.
- Remove the front case by lifting off the top locating lugs and pulling forward to clear the water section at the base of the appliance.
NOTE : A template is not supplied with this applian-
ce. Particular care is therefore necessary to ensure that the appliance mounting bracket is fitted level and positioned accurately. When using extended flues, a fall fo 5 mm per metre length should be provided. (From turret to terminal) (see Fig. 5).
- Refer to the drawings opposite for rear and side flue applications and/or to the dimensions given.
- Set out an drill hole 290 mm (11.4 in) accurately mark position for bracket.
- Drill and plug the wall.
- Fii bracket to wall using No. 12 screws provided, ensuring that the bracket is level. If necessary adjust bracket, tinally secure in position.
Pig. 5
3.3 Flue Length
Rear Outlet
Side Outlet
- Hang the appliance on the bracket, and recheck for level. Mark bottom iixing holes, removes applian­ce, drill and plug the wall to suit No 12 screws.
- Re-hang appliance and secure with screws provi­ded.
Minimum Wall Thickness 3 in (75 mm)
Wall thickness
Flue duct length = wall thickness + 25 mm
Air inlet duct length = wall thickness + 25 mm
EM up to
+DM 500 MM
Up to 612.5 mm
Delivered with Extension available
appliance
500 mm 1401 mm 2300 mm
to 1400 to 2300 to 2787
Deliv.
With
appliance
1 extern. 2 extern. 3 extern.
Pt No 2x 3x
62823 62823 62823
Over 612.5 mm
Pt No 62823
Pt No. 62623 = GC NO 264 469
EM = Wal thickness Flue duct length EM + DM + 130 mm DM = Distance from wall to case Air inlet duct length EM + DM + 130 mm
Ftg. 6
Page 11
Supplied By www.heating spares.co Tel. 0161 620 6677
3.4 Other ffue arrangements
1. Distance from Internal comer 300 mm without kit, 150 mm with kit no. 76216 (GC No. 264
833).
2. Distance below balconies or eaves 200 mm without kit, 150 mm with no. 76216. (GC No.
264 833).
l- Plan View
2- Side Elevation
Fig. 7
3.5 Fitting the he
Fig. 8
3. Appliance is nom&y supplied packed with stan-
dard 650 mm straight ffue section, Additional straight extention lengths of 1 metre. Part No 62833 (GC No 264 459), can be used up to a total straight length of 3 metres. It is also possible to incorporate one bend in the ffue using Part No. 65572 (GC No. 264 835). In this case the length Ll + L2 should not exceed 1,6 metres horizon­tally, (see iig. 7).
3- Plan View
- Measure the wall thickness and cut ffue duct and air inlet duct to required length, (see Section 1.4).
- Peel off protective paper from adhesive side of cork gasket (A) and place on mating side of ffue turret @) lining up screw holes and press down.
- Fit locking ring (C) and “0” ring over the air inlet duct, (see iig. 8).
- Fit flue duct and turret so that it engages into the terminal.
- Engage locking ring over lugs by turning in an anticlockwise direction viewed from behind tur­ret.
- Position square channeled rubber gasket (E) on the ffue hood outlet of the heater, channel facing downwards.
- Pass the assembled ffue through the wall.
- If long ffue sections are used (up to 3 metres) and di&ulty is found, these can be assembled whil­st being passed through the wall.
- Seat the turret onto the top of the appliance ensu­ring the gaskets are in position.
- Secure with 4 saews provided.
- Do not fit plastic turret cover or the front case until electrical connections have been made and the appliance tested for gas and water soundness
(see section 5.1).
- A sealing ring (D) is supplied which can be used to seal the air inlet duct to wall joint-extemally.
- Make good inside wall surface.
10
Page 12
Supplied By www.heating spares.co Tel. 0161 620 6677
3.6 Gas Connection
3.7 Water Connections
- Fit the gas service cock provided using the fine fit­ter/washer to seal the connection. Fit the nut and olive onto the 15 mm gas supply pipe and tigh­ten, (see fig. 9).
- Test the complete gas installation for soundness and purge.
- Remove the plastic covers protecting the water inlet and the water outlet connections.
- Fit the water service cock provided to the right hand connection at the bottom of the appliance using the coarse filter/washer to seal the connection, (see Sg.
10).
- Fit the nuts and olives onto the supply and deltvery HP=
- Connect the inlet supply to the water service cock and tighten.
Pig. 10
3.8 Electrical connections
- The water service cock supplied with the appltance incorporates a drain plug.
- Ensure that all water connections are fully tightened.
3.8.1 Pressure Switch
- Connect the wires at the top of the appliance to the pressure switch, (see fig. 11).
- The grey wire is connected to normally closed (NC
1) contact.
- The pink wire to the normally open (NO 2)
contact.
- The violet wire to the common (P) contact.
- Fit the flue turret cover passing the wire through
one fo the slots provided and secure with the screws provided.
- See figure.
3.8.2 Mains Connection
- Pass 0.75 mm2 heat resisting cable through cable
gland.
- The earth wire (open yellow) must be connected
to the earth pillar ( 4 > (see fig. 12).
- The live (brown) and neutral (blue) should be
- Check that component plugs are pushed home.
- Check for continuity, polarity and earthing.
11
connected as indicated into the tetial block.
Page 13
Supplied By www.heating spares.co Tel. 0161 620 6677
4. APPLICATIONS OF
pipe between the non-return valve combinations of
THE BRITONY FLEXIFLUE
The appliance is designed to serve a variety of hot water draw off points including washing machines and showers. The appliance can be connected to all hot water draw-off points in the installation. If more than one outlet is open simultaneously the total ffow of water cannot exceed that quoted in the Technical Data.
The appliance is comptatible with most current auto­matic washing machines but care should be taken to ensure that the machine is capable of accepting water at the design flow of the appliance. Hot and cold fill machines normally require a hot water tem­perature of 60” C (140 “F), the appliance producing approximately 6.5 Enin (1.44 gpm) at this tempera­ture. The advice of the washing machine manufactu­rers should be sought but generally it is only neces­sary to remove the water flow restrictor (if fitted) in the hot water inlet connection of the machine to obtain a satisfactory appliance operation.
...............
................
................
................
................
................
.................................
.................
.................
................
.................
................
................
................
................
................
.................
................
Britony FlexiFlue
.................
................
.................
................
................
................
.................
,:.:.:.:.:.:.i;:.~.:.:.:.:.:.:.:,
................
.~.~.~.~.‘.‘.~.‘.~.~.~.~.~.~.~.~
. . . . .1. ..... . . .
. . .... ... . .
...............................
Do not use the appliance with push on hand showers that fit over existing hot and cold water taps or with mixer tans unless both sunnlied come from the same source. Showers fo&g part of bath mixers
are not recommended for satisfactory operation of
the appliance.
4.1 Pipework
The following notes are for general guidance only.
(i) The appliance performance may be affected if the
installation has old pipework forming dead-legs
or air reservoirs. Always ensure that any old pipe-
work is either removed or capped off immediate-
ly adjacent to the pipework that will be in use.
(ii) The-size of the pipework between the
appliance and the various draw-off points should be sized to ensure an adequate ffow at draw-off points when used individually.
(iii) A check should be made of all stop cocks in the
incoming supply and it should be ensured that they are of the fixed jumper pattern. Loose jum­pers can be pinned or soldered into the position.
T
3
I
s
-3
8
Mixing Valve
8
HOT WATER
HOT
COLD
The appliance
SepaK3te SlIOWer ClraW-Off. lhe appliance
can
be used
d -- I. a **
to supply
hot
water to a
should
not
be used to supply more than one shower mixing
valve. The recommended pipework arrangement for
a single shower head is shown above and the hot supply to the mixing valve should be the first draw off. Suitable shower mixing valves are manufactured
by :
Caradon Mira Ltd Barking Grohe Cromwell Road, 1 River Road Cheltenham Gloucester GL52 5EP
Tel : 01242 27953 Tel : 0181-594-8898 Aqualisa Products Ltd
Horton’s Way
London Road Westerham Kent TN16 1 BT Tel : 01959 563 240
Meynell Valves LTD,
Shaw Road Bushburv Wolverhampton west Midlands WV10 9LB Ted: 01902-28621
Barking Essex IGl 1 OHD
New Team Ltd Brunell Road Earlstree Ind Estate, Corby Northants NN17 2L-F Tel : 01536 62822
COLD WATER
(ii) If the appliance is installed on a supply or distri­bution pipe containing a non-return valve, combina­tions of check valve, or any equipment containing such devices, then provision must be hade to acco­modate an expansion of at least 4 % of the volume of water contained within the installation.
(V) Expansion vessels must be fitted on the supply pipe between the non-return valve, combinations of check valve, or any equipment containing such devices and the appliance.
12
Page 14
Supplied By www.heating spares.co Tel. 0161 620 6677
5.1 Putting into Service
Pig.
14
5.1.1. Open the gas and water service cocks beneath the appliance, purge the gas supply (BS 689 1). Turn on an adjacent tap and purge the water side of the installation. Test for water soundess at all appliance and external pipework connections;
Switch on electrical supply, fan will run at low speed.
5.1.2. Remove Protective Fii from casing before use.
5.1.3. To fight the pilot temporality fit the gas control knob (A) and light the pilot by turning the knob 90” anti clockwise. It may be necessary to purge the pilot gas supply, it so, wait a few minutes, return the gas control knob to the OFF position and repeat. (The pilot supply will only purge when the gas control knob has been turned 90” anti-clockwi-
se), (see flg. 13).
5.1.4. When the
pilot is lit turn the control knob (A) fully anti-clockwise as shown in the dia­gram. Test for gas soundness using leak detec­tion ffuid on all gas connections (see fig. 14).
5.1.5. Check the operation of the flame supervision device by blowing out the pilot light, the flow of gas to the pilot will cease and the thermoelectric valve should drop out with an audible &i& within approximately 30 seconds.
5.1.8. Relight pilot and check gas pressures see Section 5.2.
5.1.7;
Remove gas control knob (A).
5.1.8. Switch off electrical supply.
5.1.9. Fit front case by locationg bottom iirst
and ensuring top of case locates over brac­ket. Secure with 4 screws and washers pre­viously removed.
- The centre screw and plastic washer retains the fascia mounting bracket.
- Replace the control fascia plate by sliding down onto the support bracket.
- Fit bottom trim by sliding onto rails.
- Fit the gas control knob (A) and the tempe­rature selector knob (B). The temperature selector knob should be pushed onto the spline until it locates. Turn fully clockwise to (+), reposition knob as required, so that indicator dot is opposite the (+) sign.
5.1.10.
Switch on electricial supply.
- Light the pilot and tum gas control knob (A) fully anticockwise to, the main gas posi-
tion.
. If the pilot is now extinguished for only rea-
son return the gas control knob to the OFF
position and wait approwimately 30
seconds for the safety interlock to reset before repeating.
5.1.11.
Perform operations as detailed in
sections 5.3 to 5.7.
5.2 Gas Pressures
Pig.
15
13
- Turn on an adjacent hot water draw off, the appliance will now light and the fan will change to high speed.
- Check burner setting pressure at test point A see Section 1.3 technical data (see fig. 15).
- If the burner setting pressure is not correct, check that the pressure at the gas service cock, test point B is 20 mbar (8. in. w.g.) with the appliance operating. If the inlet pressure is not correct, check for any pos­sible blockage or restriction in the pipe­work to the appliance. If the inlet supply pressure cannot be corrected contact your local gas region. The heat input to the
appliance is pre-set and non-ajustable.
Page 15
Supplied By www.heating spares.co Tel. 0161 620 6677
5.3 Slow Ignition
- Check burner ignition which should be smooth and quiet (not explosive).
- If slow ignition requires adjustment proceed as in Section 6.1 to remove front case.
- Adjust slow ignition device A (see iig. 16) l/4 turn at a time. Reiit front case and recheck operation.
NOTE : Turning screw A clockwise delays ignition.
Pig. 16
5.4 Microswitch
NOTE : During Commisionning it is important that the correct operation of the microswitch on the side of the gas section is checked.
Whilst the miaoswitch is factory set, it may require adjustment. When the appliance is at rest the fan runs conti­nuously at low speed. Check operation as follows - set temperature selector to - then open draw-off. The fan should now come to high speed before the burner ignites. On cloising draw-off, the burner should extinguish before the fan resumes at low speed. If fanbumer operational sequence is NOT as described see Section 7.13.
5.5 The Pressure Switch
Check the operation of the pressure switch as follows : ner ignites. Close draw off,. burner extinguishes and when fan resumes at low speed listen for the “click” as the relay changes over.This should be followed within 15 seconds by a lighter “click” as the pressure switck changes over. If the time separation is greater than 15 seconds or if the pilot extinguishes it suggests that the pressure switch is incorrectly set. (See Section 7.11).
Open draw off, fan comes to high speed and the bur-
5.6 Thermoelectric Ckuit
The Thermoelectric Circuit is &ted with an interrupter so that if the air flow is not proved on high speed the cir­cuit is incomplete and the ffame supervision device will operate. In the case of intermittant pilot failure or per­manent pilot failure the termocouple circuit can be checked with a British Gas Multimeter or suitable Millivolt Meter to determine if the pilot failure is due to poor thermoucouple output, high resistance through Relay-l contact or faulty themnoelectric valve. (See Section 2.9, iig. 1).
The thermocouple output measured at the Printed Circuit Board terminals should be greater than 12 millivofts. The millivoltage drop through the relay (i.e. terminal to terminal) should not be greater than 4 millivolts.
5.7 Handing Over
Hand all instructions to the user or purchaser and instruct in the correct and safe operation of the appliance. Explain to the user or purchaser that if the appliance is not used for long periods it is recommended that the
appliance is drained, this is particulary important during the winter months (see servicing instructions for pro­cedure to drain appliance).
Finally, advice the user or purchaser that, for continued efiicient and safe operation of the appliance it is impor­tant that servicing is carried out annually to the-manufactures recomendations by a C.O.R.G.I. registered person.
14
Page 16
Supplied By www.heating spares.co Tel. 0161 620 6677

6. ROUTINE SERVICING

To ensure continued efficient and sale operation of the appliance it is recommended that it is checked and serviced
as necessary at regular intervals. The frequency of servicing will depend upon the particular installation, condition and usage, but in general once a year should be adequate.
It is the law that any service work must be carried out by a competant person, such as British Gas, other C.O.R.G.I. registered personnel or your local Chaffoteaux Service Centre in accordance with the Gas Safety (Installation and
Use Regulations). This routine service will normally be confined to :
1) Cleaning the burner.
2) Cleaning the heat exchanger.
3) Checking the gas controls.
4) Cleaning water kilter, and water governor.
5) Check diaphragm and replace every three years. The following schedules are recommended :
a) Check the function of appliance, burner pressure, gas ffow rate and soundness.
b) Observe flame picture and undertake combusion test.
c) Check clean or replace components as necessary.
6.1 Front Casing
To
remove
- Pull off gas control and temperature selector knobs.
- Remove controls facia plate by sliding upwards.
- Remove the four fixing saews which secure the front case (top, bottom and centre) taking care not to lose facia retaining bracket and washers.
- Remove to front case by lifting off the to locating lugs and pulling forward to clear the water section at the base of the appliance.
:
6.2 Burner
Pig. 17
6.3 Pilot
Pig. 18
B
A
- Remove the combustion chamber front panel as fol­lows.
- Remove two threaded saews which secure the front panel of the combustion chamber skirt to the ilue hood (A) Section 6.4.
- Remove three self-tapping saews on either side of combustion chamber skirt (B) Section 6.4.
- Unscrew the pilot tube clamping screw (A) and remo-
ve the clamp and saew and pilot tube.
- Remove the burner manifold by unscrewing the two
screws and washers (C) (see fig. 17).
- Withdraw the burner head assembly taking care not
to damage the pilot burner/electrode assembly or the ignition lead.
- The burner head should be turned upside down and
cleaned by brushing.
- Replace in reserve order making sure that the gasket
between the burner manifold and gas section is in place and is in good condition. If necessary replace gasket and ensure that the burner head assembly is correctly located on the two spigots at the rear.
- Remove combustion chamber front panel, burner
and pilot tube as in 6.2. if not already removed.
- Blow through the tube to remove any dust.
- Remove screw securing spark electrode. LiA out off
“D” slot and ease to one side.
- Unscrew the knurled pilot burner outer ring (A).
- Remove flame retention’gauze (see fig. 18).
- Unscrew the pilot body (B) with a 15 mm spanner.
Clean by brushing and blowing.
DO NOT CLEAN HOLES WITH A WIRE.
- Re-assemble in reverse order ensuring pilot body is
screwed down tightly.
15
Page 17
Supplied By www.heating spares.co Tel. 0161 620 6677
6.4 Heating Body
a) The heat exchanger can be examked in
(see fig. 19)
- Remove combustion chamber front panel as in Section 6.2. if not already removed. Prior to clea-
ning the heat exchanger adequate precaution
should be taken to protect the pilot burner/gas
valve assembly to prevent the ingress of dust etc.
- If extensive cleaning is necessary, the heat exchan-
ger will need to be removed as follows.
b) To remove heat exchanger
- Slide out combustion lining and retain.
- Disconnect the unions on either side of the heat exchanger.
- Remove two screws securing the combustion chamber/heating body assembly to the rear panel.
- Remove heat exchanger and combustion chamber.
- Remove two saews at the rear of the combustion
chamber securing the combustion chamber to the
heat exchanger to seperate the components.
position :
Rg. 19
Care should be taken when handling the heating exchanger to ensure t&t the Bns are not damaged.
- Replace in reserve order.
6.5 Descalhg
Periodically it may be necessary to remove scale deposits from the waterways of the appliance to ensure conti­nued and efficient operation.
The frequency will depend largely on the hardness of the water in each speciiic area. If this is necessary contact your local water authority for advice.
Advice with regard to descaling is available from Chaffoteaux et Maury Ltd.
6.6 Main Gas Valve
To inspect and clean
- Remove the burner (see Section 6.2)
- Disconnect the thermocouple at the PCB and igni-
tor lead from the piezo unit.
- Remove the four saews and washers fastening the
top of the gas section to the base and the two
saews at the back holding it to the rear case.
- LiA the gas section top off the base, taking care not
to damage the cork gasket.
- Remove the hexagonal spring retainer (A) from the
top of the assembly (20 mm) (see fig. 20).
- Remove the spring and gas valve and clean the
valve seating (B).
- Renew facing rubber washer on the gas valve if
necessary.
- Grease spindle see Section 6.11.
- Replace in reverse order, ensuring that the hexago-
nal spring retaining nut is screwed fully down.
Fig.20
- Do not change the setting of the valve body.
16
Page 18
Supplied By www.heating spares.co Tel. 0161 620 6677
6.7 Water Governor
I
A
-
pg.21
To clean
- Turn off the cold water supply to the appliance and drain into receptable.
- Remove the governor situated in the base of the
water section (A) (see fig. 21).
- Clean the components with water and grease see Section 6.11.
- Check that the spring loaded piston moves freely.
- Replace in reverse oder.
6.8 Gas and Water Pihers
Gas and water Met filters a~ fitted between the
inlet service cocks and the appliance.
- To clean, turn off the gas supply at the meter and the service cocks, unsaew the union nuts atta­ching the cocks to the appliance and remove the tilters (see iig. 22).
- Clean the filters by blowing or washing in water, DO NOT USE ANY SOLVENTS.
- Replace ensuring that the coarse filter is fitted in the
water inlet and the fine iilter in the gas inlet.
- Turn on the gas supply and open both water and gas service cocks.
- Test for soundness.
6.9 Microswitch
The miaoswitch operating mechanism is factory set and if the miaoswitch requires replacement or adjustment see Section 5.4. and proceed as in Section 7.12 and 7.13.
6.10 Pressrrre switch
The pressure switch is factory set and it the pressure switch requires adjustment or replacement, see Section 5.5.
and proceed as in Section 7.10 and 7.11.
6.11 Greasing of Components
Care should be taken during the annual service of an appliance to grease the gas valve spindle (see Section 6.6)
water Governor (see Section 6.7) and the bearing plate spindle (see Section 7.5). Use silicone grease.
6.12 Heat Input
It is a requirement of the Gas Safety (Installation and Use) Regulations 1984 that the burner pressure and gas rate are checked each time an appliance is serviced, likewise the service engineer should satisfy himself with regard to gas soundness and the adequacy of combustion and ventilation air if this is appropriate.
The heat input is preset and non-adjustable. The heat input and burner pressure should be checked (see Section 1.3). If the heat input/burner pressure is not correct check the working pressure at the pressure test point on the gas
service cock. This should be 20 mbar (8 in wg). The gas installation should be examined for any possible blockage if the pressure is incorrect.
17
Page 19
Supplied By www.heating spares.co Tel. 0161 620 6677
Before commencing any work involving component replacement :
1. Isolate electrical supply.
2. Turn off gas at the gas service cock.
3. Turn off water at the water inlet cock.
4. Drain the appliance by opening hot water outlet tap and removing the drain plug in the water service cock.
5. Remove the front casing (see Section 6.1).
7.1 Thermocouple
Ftg. 23
7.2 Spark Electrode
Fig. 25
-
Ftg.
24
- Remove the burner (see Section 6.2).
- Remove the pilot (see Section 6.3).
- Trace the thermocouple and disconnect at the ter­minal on the PCB.
- Disconnect at thermoelectric valce by undoing nut (A) (see iig. 23).
- With a 7 mm boxspanner, unscrew the nut (B) holding the thermocouple into the gas section (see fig. 24).
- Thread the thermocouple and wire up through the gas section.
- Replace in reverse order.
- Remove the burner (see Section 6.2).
- “;“s;““” the electrode retaining screw (A) (see iig.
- Pull off the electrode cable from the piezo cartridge.
- Liil the electrode out of the gas section.
- Re-assemble in reverse order, and note that the slot
in the connector on the end of the electrode cable
is
vertical when pushed onto the cartridge.
NOTE : Spark gap is 3-5 mm..
7.3 ThermoeIectric vaIve
Fig.
26
7.4 Water Section Ventufi
Fig. 27
,
- To renew, remove the thermocouple conductor lead nut (A) (see fig 26).
- Unscrew cap (B) from the side of the gas section and withdraw the thermoelectric valve.
NOTE : This heater is fitted with a safety interlock.
When the pilot is turned off, the appliance cannot be
relit until the thermocouple cools down and the ligh­ting sequence is repeated.
- Disconnect the right hand heating body leg from the water section and remove the venturi (A) (see fig 27).
Clean or replace as necessary and the re-assemble
in reverse order.
18
Page 20
Supplied By www.heating spares.co Tel. 0161 620 6677
7.5 Diaphragm
Fig.28
- To renew ensure that the cold water supply and gas are turned off.
- Drain the appliance by removing the water gover­nor plug situated in the base of the water section
(see Section 6.7).
- Disconnect the two water connections at the water section.
- Unscrew the six screws (A) which hold the water
section to the gas section (see fig. 28).
- Remove the water section complete with the dia­phragm.
- Remove bearing plate and spindle and grease, (see
Section 6.11).
- Carefully remove and inspect the plastic water sec-
tion top cover.
- Re-assemble in reverse order.
NOTE : Fit the water governor last. It is easier if the cold water inlet connection is partially engaged befo­re iitting the screws and reconnecting the union nuts.
7.6 Piezo Unit Cartridge
7.7 Fan Assembly
EARTH
Yelbw - Green
- Disconnect the spark electrode lead from the piezo unit cartridge.
- Remove the screw holding the gas control cam and
remove the cam (A) (see iig. 29).
- Remove the two screws (B) holding the retaining
plate.
- Remove the piezo cartridge and renew.
- On reassembling ensure that the locating pins on
each end of the spring are correctly engaged in their location holes.
- Disconnect electrical connectors from assembly. Note positions.
- Remove the two screws and washers (A) securing the fan assembly to the ilue hood (see iig. 30).
- Release wiring loom from support clip.
- Gently ease the fan assembly away from the flue hood disengaging lug at rear of fan assembly.
- Re-assemble in reverse order.
Note : The dimension - back plate to front face of
impeller is : -57.5 mm +0.5 mm -0.0 mm.
Rg.30
UT
Red
19
Page 21
Supplied By www.heating spares.co Tel. 0161 620 6677
7.8 To Replace Fttse or PCB
Pig. 27
7.10 To replace pressure suhh
Isolate electrical supply :
(A) FUSE : - Pull out fuse holder (A) from board and
slide fuse out of holder (see fig. 31).
(W PcB
: - Remove connections (fan, microswitch,
pressure switch).
- Disconnect mains supply cable from ter-
Klil-ldS.
- Remove two nuts and washers (EQ retai­ning thermocouple and conductor lead.
- Remove fuse and ease board from plas­tic retaining clips.
- Remove four screws and remove PCB.
- Reassemble in reverse order.
- Isolate electrical supply.
- Remove two screws securing plastic turret cover.
- Pull off tag connectors from tem&ials.
- Remove low pressure tube from pressure switch.
- Remove two screws securing pressure switch to bracket.
- Lift off pressure switch dis-engaging it from the high pressure tube.
- Remove “0” ring from spiggot on the underside of the pressure switch.
- Replace in reverse order referring to colour coding label on top of appliance.
7.11 Adjustment of pressure switch
a) If a pilot extinction occurs within 10 seconds of turning the hot tap off, it is possible that the pressure switch iz
out of adjustment, if the pressure switch remains in the high ilow position in excess of 10 seconds after the far
switches to low speed interruption of the current to the thermoelectric valve occurs.
It is possible to adjust the pressure switch to ensure a rapid return from high to low ffow.
Adjrrstment Sequence :
- Adjusting the pressure switch.
- Ensure the front case is on.
- Isolate electrical supply.
- Remove two screws securing plastic turret cover and liA off cover.
- Remove terminal cover from pressure switch e.xpo­sing the adjusting screw (A) and remove securing
paint (see ftg.32).
- Set a multimeter to 240 V scale and connect it across the common and one other terminal of the switch.
- Re-establish electrical supply and ensure that gas is off at gas control.
- Turn on a hot tap to give high fan speed.
- Using a suitable screwdriver screw the adjusting screw (A) in until changeover of the pressure switch
contacts are observed.
- Screw out adjusting screw (A) 3 tums to achieve the
setting point.
Pig. 32
- Check operation of the presxne switch (see section 5.5.).
- Replace the plastic terminal cover on the pressure switch.
- Replace the plastic turret cover and king screws.
b) If main burner extinction occurs during hot water demand, it is possible that the pressure switch is out of
adjustment. Screw adjusting screw (A) out until ilush with top of moulding, then follow adjustment sequen­ce above.
20
Page 22
Supplied By www.heating spares.co Tel. 0161 620 6677
7.12 Replacement of Mkroswitch
- Isolate electrical supply.
- Part connector plug on leads to microswitch.
- Remove two lock nuts (4 mm) from microswitch retaining screws (C) (see fig. 33).
- Remove screws securing microswitch.
- Remove switch together with plastic insulating plate.
- Renew microswitch and replace in reverse order.
NOTE : Microswitch is not available on its own. Microswitch Assembly must be used therefore ins-
tructions not detail changing whole assembly.
7.13 Amstment of Mkroswhh operating mechanism
- Re-establish electrical supply - leave gas cock and hot water taps off.
- Temperature selector can be set in any position.
- Slacken locking screw (B) see diagram in 7-12 - using 1,5 mm hexagon key.
- Turn adjusting screw (A) anti-clockwise until high speed fan operation is obtained.
- The fan should now be at high speed.
- Turn adjusting screw clockwise slowly until low speed fan operation is obtained
- Continue turning adjusting screw clockwise for a further 1 turn
- Tighten looking screw.
- Check operation of microswitch (see section 5.4).
7.14 IO replace the Gas and Water Section
- Remove the burner (see Section 6.2).
- Disconnect microswitch by parting plug connector on leads.
- Remove the conductor lead at thermoelectric valve (see Section 7.3).
- Remove thermocouple lead at PCB.
- Remove spark electrode lead from piezo cartridge (see Section 7.6).
- Discqnnect the gas union at rear of gas section.
- Disconnect the water connections from the water section these are the mains inlet and water section to hea­ting body.
- Remove the two screws securing the burner base to the rear chassis.
- Reassemble in reverse order.
7.15 IO replace Ceramic Liners in Heating Body
- Remove the burner (see Section 6.2).
- Remove two threaded screws (A) (Section 6.4), which secure the top front panel of the heating body to the flue hood.
- Remove six self tapping screws (B) (Section 6.4), from front panel of heating body.
- Slide out front and side ceramic liners from locating channels.
- Ease heat exchanger forward to allow rear ceramic liner to be lit?ed clear of lower channel.
- Iii? panel and withdraw lower edge f+st.
- Reassemble in reverse order.
21
Page 23
Supplied By www.heating spares.co Tel. 0161 620 6677
FAULT FINDING CHART *OR BRITONY FLEXIFLUE
8.1.
8.2.
8.3.
8.4.
PROBLEM
Pilot does not light
Poor Pilot Flame
Pilot only
P1Iot will not stay alight I)
CAUSE
Gas service cock closed
1) II)
Air in pipe
III)
Pilot injector blocked
IV) No Ignition spark
Pilot injector dirty
1) II)
Wrong injector
III)
Pilot head blocked
IV) Faulty pilot tube
Pilot injector loose
w
Microswitch out of adjustment
1)
Pilot flame poor
II)
Faulty flue
III)
Thermocouple not working
IV) Thermoelectric valve faulty Q) Gas pressure low/variable VI) Terminal wrongly positioned VII) Badly assembled flue
IX) Pressure switch faulty
Plug loose on PCB
w XI) PCB faulty
REMEDY
Open service cock
Purge line
Clean or change Check electrode, lead and ignitor
Clean or change Change for correct diameter Clean Clean or replace
‘lighten
a) Check microswitch high speed operation, see Section 5.4
b) Adjust micro switch, see Section 7.1:
(See 8.2)
(See
8.3)
Above
Above a) Check connection clean and tighten as necessary b) Replace it output less than 8 mv. Replaced if drop out greater than 5 mv.
Check at inlet to appliance (see 5.2) Re-position (see 2.4) Refit check sealing a) Check operation (see 5.5) b) Adjust (see Section 7.11) Replace (see 7.10)
Secure Replace (see 7.8)
8.5.
8.6.
Main burner does not fight I)
Burner goes out on hot water demand
Gas service cock not open fully
II)
Gas pressure low
Open fully
Check at manifold and at inlet with the appliance running (see page 3 and 5.2)
III)
Water flow rate low
IV) Gas valve not opening
V) Diaphragm punctured
Check if water rate sufficient (see page 3
Check(V) Change diaphram (see Section 7.5)
VI) Venturi blocked or loose Check venturi
VII) Gas control tap faulty
VIII) Slow ignition device screwed fully home Adjust (see
Fan not switching to high speed
1)
Check opemtion of User’s gas control tap
5.3)
a) Check it is fully opened b) Adjust micro-switch (see 7.13) c) Micro-switch defective - replace
(see Section 7.12) d) Fan defective - replace (see 7.7)
II)
Pressure switch out of adjustment a) Check pressue switch operation (see 5.5
b) Adl pressure switch (see 7.11) c) PIESUE switch de&&e - replace (see 7.10:
III)
Low pressure tube detached
Refit or replace (see 7.10)
IV) High pressure tube blocked Check and clean (see 7.10)
V) Flue blocked
Check and clean, and ensure that the flue declines from appliance (see 3.2)
VI) PCB faulty
Replace (see 7.8)
22
Page 24
Supplied By www.heating spares.co Tel. 0161 620 6677
FAULT FINDING CHART FOR BRITONY FLEXIFLUE
8.7.
8.8.
8.9.
8.10.
PROBLEM CAUSE
Explosive Ignition
Gas control tap stff (User’s)
Pilot too small
1) II)
Slow ignition not adjusted Check and adjust (see 5.3)
Grease dried
1) II)
Operating mechanism replaced incorrectly Refit
Low Water Temperature I)
Water rate too high
II)
Insufficient gas flow
III)
Water governor sticking IV) Incorrect venturi V) Main burner injector dirty
Burner stays on
Air in pipework
1) II)
Gas valve stays open
III)
Dirt on gas valve facing
IV) Dirt or foreign matter in water
section Loose jumper on house stop tap
VI VI) Check-valve fitted on supply pipe
. VII)
Slow ignition device stock
REMEDY
Check pilot tube and injector
Clean and regrease
Check water governor Clean rate and it user’s tap is open Remove and clean or replace (see 6.7) Replace (3.65 mm) (see section 7.4) Clean or replace (see section 6.2)
Check for dead legs Clean and grease gas spindle Strip and clean gas valve (See Section 6.6)
Clean water section (See Section 4.1) Clean or replace (see Section 5.3)
8.11.
8.12.
8.13,
8.14.
8.15.
Yellow
Flames-
Soot Formed
Unstable Flame
Heating Body Noise
Fan Noisy
Instff&ient Water
Heating body tins blocked
1)
II)
Primary air supply restricted
III)
Wrong injectors
Fan not switching to high speed
1) II)
Water in gas line
III)
Faulty flue
IV) Fan assy not fitted correctly
V) Gaskets not fitted correctly
Scale
1)
Excessive gas
11)
III)
Insuficient water flow
Fan remaining at high speed
1) II)
Fan out of balance
Water service tap closed
1) II)
Blocked venturi
III)
Low water pressure
IV) Water governor faulty V) Water governor sticking VI) Foreign matter in water section
VII)
Water filter blocked
Remove heating body and clean (see 6.4: Check burner manifold and clean (see 6.2) Check injector sizes and gas rates (see Section 1.3) technical data
See Section 8.6 Drain and purge Check terminal position and ffue ducts (see Section 3.3) Fit fan assy correctly (see Section 7.7) Fit gaskets correctly (see Section 3.5)
Descale heating body Check gas pressure (see 1.3 and 5.2) See section 8.15
See Section 8.3 Replace (see 7.7)
Check it is fully opened (see 3.5) Remove and clean venturi (see 7.4) Check water pressure (see Section 1.3) Change governor Remove and clean or replace (see 6.7) Remove and clean (see Section 7.4) Remove and clean/replace (see 3.5)
23
Page 25
Supplied By www.heating spares.co Tel. 0161 620 6677
9. GAS CONVERSION
From natural gas to butane-propane and vice-
versa (see fig. 34, 35 and 36).
- Turn off gas at the gas service cock and remove the front casing (see section 6.1 front casing p. 15).
- Unscrew the screw (1) and remove pilot tube (2).
- Remove the burner manifold (4) by unscrewing the four screws (3).
- Disconnect at thermo-electric valve by undoing nut (5) and pull off the electrode cable (6).
- Unscrew the two screws securing the rear of bur­ner and pull burner forward to remove.
- Unscrew the four screws (8) and lift the gas sec­tion top off the base.
- Unscrew the spring retainer (9).
- Remove spring (10) and change the main gas
valve (11) (see Technical Data table page 4).
- Replace the spring (10) and screw fully down the spring retainer (9).
- Replace the gas section top on the base and screw the four screws (8).
- Replace the burner and screw the two screws at rear.
- Re-assemble the thermocouple nut (5) and elec­trode cable (6).
- Change the pilot gasket (12) change the pilot injector.
- Replace the new burner manifold with appropriate injectors and the manifold restrictor (if planned).
- Fasten the four screws (3).
- Replace the pilot tube (2) conform with the new
used gas and gently tighten the screw (1).
Check for gas soundness and test the function of appliance.
Stic the adhesive advice informing about the nature and pressure of the adjusted gas.
Replace front casing.
24
Page 26
Supplied By www.heating spares.co Tel. 0161 620 6677
Page 27
Supplied By www.heating spares.co Tel. 0161 620 6677
Page 28
Supplied By www.heating spares.co Tel. 0161 620 6677

SHORT LIST

1756
+1508
- 1509
rii
yj
1609
634 625
r------------------~
I
I
1
1038-@
j 1006---~ j 10364
I L----------------,-d
1001 ;
NAT i
I
/
i I I
1602
@&-
(& 905
i
e-1032
902
Key
N”
211
CERAMIC PANEL KIT..
502
THERMOCOUPLE..
503
ELECTRODE AND LEAD ASSEMBLY..
529 THERMOCOUPLE LEAD ...........................................
625
MICRO SWITCH MECHANISM.. ................................ 264862 '1001338.00
634
DIAPHRAGM 902
GAS CONTROL KNOB ............................................. 264506
905
TEMPERATURE SELECTOR KNOB.. 907
FRONT CASE TRIMS ............................................... 264888
920 BOlTOM TRIM
1001
GAS SERVICE TAP ASSY..
1006
OLIVE ..................................................................... 263800
1018
WATER SERVICE TAP
1019
WATER FILTER..
1031
WALL MOUNTING
1032
WOOD SCREW..
1036 NUT l/2 1038
GAS FILTER ............................................................ 263545 37309.00
1503
PWNTED CIRCUIT BaARD ........................................... 264875 79333.00
1508 1509 1602 FAN ASSEMBLY 1609 SCREW HS M6-15 1705 1756
1042 DRAIN PLUG ......................................................... 263617 41197.00
1043
FUSE HOLDER.. ...................................................... 264536 74995.00
FUSE 264903
PRESSURE SWITCH.. z .............................................. 264508 76565.00 .
SILICONE TUBE
"0" RING D: 7.2-1.9.. ................................................ 262806
Description
.............................................
..................................................
......................
...........................................................
.........................
........................................................ 264490
.......................................
ASSY
.................................... 263794
......................................................
BRACKET..
......................................................
..................................................................
......................................................................
.......................................................
................................................... 264454
...................................................... 264444
..................................
Type
NAT
G. C. NO.
264789 264336 57703.00 387252 264326 57704.00
263432 25809.30 264507
265158
263589 1007727.00 264305 366017 263801
366812
MANF. PT. NO.
BRI. FLEXIFLUE
79350.00
60703.00
74477.00
74478.00
81172.00
74473.00
81288.00
56489.00
81289.00
28967.06
25617.03
56490.00
44790.00
1009106.00
19316.03
81265.00
24164.12
% 8
m
R 7
8 6
.L 2
ti E
Chaffoteaux et Mauty Limited,
Trench Lock, Trench,Telford, Shropshire TFl 4SZ
Telephone :Telford (0952)222727 - Telefax :(0952)243493
Lodcing Good. Healing Better
ESP030
Loading...