Chaffoteaux & Maury Britony combi 80, Britony combi 100 Maintenance And Service Manual

Page 1
-=G v
AA
Dimensions
MAINTENANCE AND
SERVICE GUIDE
combi 80 and 100
Fanned Flue Combination Boiler
CC
Edition et COMLEC 4/95
‘lue types: : 12 C 22 or C42: horizontal :32xx:
vertical concentric

Technical data

Heat input C/H & DHW Combi 80 :
Combi 100 :
Heat output C/H & DHW Combi 80 :
Combi 100 : Max. operating pressure C/H circuit : Expansion vessel net capacity Expansion vessel initial pressure Electrical consumption :
Voltage
Electrical protection index Fuses :
Nominal gas flow rate at 15°C and 1013 mbar
-Natural gas ( G 20) at 20 mbar
-Butane gas ( G 30 ) at 28 mbar
-Propane gas (G 31 ) at 37 mbar
: :
JKLMN I
Boiler outer case dimensions : I Safety valve outlet
11.73 to 28.70 kW
15.43 to 34.57 kW
9.5 to 23.25 kW
12.5 to 28 kW
2.5 bar
5.4 I
0.7 bar 15ow 230 v IP24 2Aand 1.25A
power 23.25 kW
Height : 850
- Boiler width : 440 (minimum space required 450)
- Depth : 380
DHW flow rate at @ 30°C Combi 80 : DHW flow rate at @ 35°C Combi 80 : Minimum DHW operating flow rate :
Minimum DHW working pressure Maximum DHW working pressure Gas category :
BRITONY Combi 80
Maximum
2.74 m3/h 1.22 m3/h
2.04 kg/h 0.91 kg/h
2.00 kg/h
Minimum
power 9.5 kW
0.89 kg/h
J Heating flow K D.H.W. flow L Gas supply M Cold water inlet N Heating return
Combi 100 : Combi 100 :
: 0.1 bar :
BRITONY Combi 100
Maximum
power 28.2 kW
3.34 m3/h
2.45 kg/h
2.42 kg/h
11.1 I/min
13.4 I/min
9.54 I/min
11.5 I/min
2 I/min
10 bar II 2E+ 3+
Minimum
power 12.5 kW
1.57 m3/h
1.17 kg/h
1.15 kg/h
Injectors and gas valves seat diameter
-Blue solenoid restrictor diameter
-Black solenoid restrictor diameter
-Manifold injectors (16)
BRITONY Combi 80
Natural qas
2.40 mm
4.25 mm 5.00 mm
1.23 mm
Butane or Propane
1.74 mm
0.72 mm
BRITONY Combi 100
Natural qas
2.80 mm
5.20 mm
1.26 mm
1 Butane or Propane
1.90 mm
3.80 mm
0.76 mm
Page 2

Pump and expanssion vessel characteristics

Hauteurmanomemque m
5 1 3 2
1 0
100
200 300
1. CH Flow isolating valve
2. DHW outlet
3. Gas service tap
4. Water service tap
5. CH Return isolating valve
400 5OD 600
1 = by-pass closed
2 = by-pass open
Head available / flow
700 800 utl
Components location
DPbd
bar
13
I,7
13
I,3
1 ,I
03
0,7
20 50
Note : The system initial pressure should be over the following value :
System static height (in metre) + 0.7 = Initial pressure (in bar)
7. Pressure relief valve
8. Chassis
9. Connecting tails (x 5)
100 150 200 250 c (I)
10
10. Steel chassis complete with expansion Jesse1
11. Sealed chamber
12. Expansion vessel (not visible)
13. Overheat thermostat
14. Electrical box
15.Three position selector switch
16. User’s guide
17. Heating flow temperature adjustment
18. CH pressure gauge
20. Green indicator - Power ON
21. Orange indicator - Burner ON ?2. Red indicator - Lock out/flame failure ?3. Reset button
3 4 95
24. Multigas burner comprising:
-25. 16 burner head
-26. Manifold
-27. 2 Ignition electrode
-28. lonization electrode
29. Gas section comprising:
-30. Security valve (grey)
-31. l/3 gas stage (blue)
-32. 2/3 gas stage (black)
33. Right hydraulic assy
34. Left hydraulic assy
35. Single speed pump
36. Air separator
37. Heating thermistor
38. DHW thermistor
8
7
39. Combustion chamber made of aluminium coated steel with 4 cera­mic fibre panels to insure heat insu­lation
40. Copper main exchanger
41. Stainless steel secondary plate exchanger
42. Three way valve
43. connecting bracket
44. DHW flowstat
45. Heating flowstat
46. Flue hood
47. Adjustable by-pass
49. Air Pressure switch
50. 45” elbow comprising venturi
51. Fan
2
Page 3
WNCTIONING
gas service tap is opened at the gasmeter and
the
50
‘9 0 ‘3 0 x3
‘3 ‘3 0 ,3
‘3
pressure in central heating system is above 0.7
bar and below 2.5 bar with the pressure gauge0 (8).
3) Open the gas tap (3) by turning from right to left. 0
4) The boiler is now ready to use.
1) Turn selector switch (15) to position flf . The green “power on” indicator 0 (20) will light.
2) Turn on a hot water tap, the orange “burner on” indicator @ (21) will light and the water will become hot.
Heating and Hot Water
1) Turn selector switch (15) to position 2 ‘1111. The green “power on” indicator 0 will light (20).
3) If the room thermostat (if fitted), the boiler temperature control
‘1111 and the clock (if fitted) are all calling for heat, the orange
BRITONY COMBI FUNCTIONAL DIAGRAM
12
____A
35
Hot water mode
3
Page 4
“burner on” indicator 4 (21) will light and the heating will be on. When there is a need for hot water while heating control thermistor (37). This the heating is on, it is only necessary to turn tern anticipates the changes of temperatu- controlled by the central heating contra
on a hot tap. The heating will be momentarily while the hot water is being
delivered. The boiler will switch back auto­matically to heating when the tap is turned
Off.
Note: If the boiler has been turned off for some time the first attempt to light it may
result in a lockout @ (22) . If this happens press the reset button (23) and the boiler subsequent hot water demand. will light.
Domestic Hot Water Mode To be able to supply hot water, the selector switch 15 must be in either on ,:’ or
‘1111 2 the green indicator light 0 (20)
When a tap or shower is turned on, the flow of mains water, above 2 litres per min., will tor light 0 (20). activate the DHW flow switch (44) and allow the 3 way valve (42) to move to the DHW position. The pump can now circulate (either from the room thermostat or the primary water heated by the main heat clock) the pump starts. If the boiler tempe­exchanger through the secondary heat rature control is calling for heat and prima-
exchanger.
The first stage solenoid (31) (blue) and . security solenoid (30) (grey) open together to allow gas to the burner. The ignition sequence begins and a continuous high speed spark ignites the gas. As soon as a flame is detected the orange indicator bulb
h (21) will light and the second stage sole­noid (32) (black) opens to allow the full gas the orange indicator bulb b (21) will light. rate. If a flame is not detected, after 8 After 45 seconds the second stage sole­seconds, the security solenoid closes and noid (32) (black) opens to allow the full shuts bulb @ (22) will light. The domestic hot
position. This will be confirmed by
Off
the gas. The red lockout indicator
interrupted
water temperature is controlled by the hot shuts off the gas. The red lockout indicate water control thermistor 38 and the central bulb 0 22 will light.
SYS-
The central heating flow temperature i:
re in the secondary heat exchanger and thermistor (37). The boiler has been desi ensures accurate temperature regulation. gned to minimise cycling and will not attemp
to relight for at least 3 minutes after the boi When the tap is closed the burner is extin- ler thermostat has been satisfied. When the guished and the pump stops. The boiler room thermostat is satisfied the burner wil will now stay in the hot water mode for switch off and the pump will remain running three minutes to maintain temperature to for a further 3 minutes before it too stops. ensure a fast response in the event of a
NB
It is possible to override the 3 minute dela! Priority will be given to a demand for hot by pressing the RESET button (23). water. This will interrupt the central hea­ting for the duration of hot water delivery. Lock out procedure
Flame disappearance : Central Heating Mode To be able to supply heating, the selector switch (15) must be on This will be confirmed by the green indica-
When there is a demand for heating
ry flow rate over 4 Itr/min, the central ton (23). heating flow switch operates ailowing the Ignition sequence to begin. The first stage Overheat detection : solenoid (31) (blue) and security solenoid If an overheat is detected by the senso
(30) (grey) open together to allow gas to (13), the grey security solenoid (30) and the the burner. The ignition sequence begins and a continuous high speed spark ignites the gas. As soon as a flame is detected
gas
rate, lf a flame is not detected, after 8
seconds, the security solenoid closes and
‘Ill1
c? position.
When the ionisation electrode (28) does no detect flame presence. The orange indicate lamp (21) extinguishes. A lighting cyck starts. If a flame is not detected before f seconds, the grey security solenoid (30) ark the blue i/3 solenoid (31) will close. The lock out red indicator (22) lights, the pump
(35) runs and the 3 way valve (42) stays ir Its position. After a few seconds, it will become possibk to reset the boiler by pressing the reset but
blue i/3 (31) closes, the orange indicate lamp (21) extinguishes. The ignitor is energi sed for 8 seconds and the red lockout indi cator (22) ligths. If the burner cannot religh the boiler will go to lockout.

WIRING

rEiimiq
El
4
Plug for main power and Room
thermostat connection
1 2 3
1. Neutral
2. Phase
3. Room thermostat live
4. Accelerator resistor
5. Common for Accelerator and room
thermostat.
4
5
I
Page 5
ELECTRICAL WIRING continuation
I
U”
Designation
-Overheat sensor
13.
14.
-Electrical box
I4a.
-Regulation PCB
14b.
-Igniter Red, Black
I4c.
-Fuse 1.25 A
l4d.
-Fuse 2A
I4e.
-Power PCB
I4f.
-Room thermostat
149.
-Mains 230V 50 Hz
-Pressure switch
18.
27.
-Spark electrodes
28.
-Ionisation probe
-Security solenoid (grey) Grey
30.
-2/3 gas stage solenoid (black) Black
31.
-l/3 gas stage solenoid (blue) Blue
32.
-Pump
35.
-C/H thermistor Violet
37.
-DHW thermistor Green
38. $2.
-3 way valve
-DHW flow switch Brown
$4.
-C/H flow switch Red
$5.
-Fan Brown. Blue
51.
Wiring colours
Brown
2: Black P: Orange 1: White White White
White, Yellow, Orange
REGULATION
Temperature regulation for both C/H and DHW circuits are controlled by 2 thermis­tors. The C/H knob allows the adjustment Df temperature between 35 and 85°C. The DHW temperature is limited to 60°C. DHW and C/H thermistors are identical and interchangeable.
Resistance value are
-5000 Q at
-2631 Q at
-620 52 at
-255 Q at
25 “C 40°C 80°C 11o”c
FLOW SWITCHES
To ensure continued efficient operation of the appliance, it is recommended that it is checked and serviced as necessary at
regular intervals. The frequency of servi­cing will depend upon the particular ins­tallation condition and usage, but in
general, once a year should be adequate.
It is the law that any service work must be
carried out by a competent person such
as your local Chaffoteaux Service Centre,
British Gas or other CORGI registered
personnel in accordance with the current
Gas Safety (Installation and Use)
Regulations.
ADJUSTMENTS ON
The following adjustments are available on the regulation PCB. To gain access to them, pivot down electrical box, remove the rear cover and the rear panel of electrical box, unplug connectors from regulation PCB and pull it toward you.
Heating output limitation :
- Functioning without limitation
- Functioning at l/3 gas rate only Burner functioning:
- Regulation available 3/3, l/3, 0
- Functioning at full gas rate only
I
CONTROL
plug C on “P MAX” plug C on “P l/3”
plug D on “NOR” plug D on “TUR”
ROUTINE SERVICING
- Check that the fan blades are clean.
- Check, clean and replace components as necessary.
- Carry out combustion test utilising the tes points in the flue turret.
SUGGESTED SEQUENCE for SERVI­CING
Before disconnecting or removing any parts, isolate the gas and electricity sup­plies. Ensure that the appliance is cool.
(for detail please see section on Parts Removal and Replacement)
1
Flow in both D.H.W. and Heating circuits are detected by 2 flow switches. A piston with a magnet at the top operates a REED switch. The piston is lifted by flow rates listed below :
Flow rate threshold : D.H.W. C/H 250 I/h *20 I/h
120 I/h ?20 I/h
AIR PRESSURE SWITCH
The air flow rate is detected by a pressure differential created by a venturi located in the flue duct.
ON threshold OFF threshold
AP > 130 Pa AP < 100 Pa
The service schedule should include the following operations:
- Check the pressure in the system.
- Check the correct operation of the appliance.
- Check the correct operation of the gas controls.
- Check the functions of the safety controls.
- Check combustion chamber insulation panels for damage.
- Clean the burner.
- Clean the heat exchanger.
- Check the burner manifold injectors.
- Clean gas and water filters.
- Check expansion vessel charge pressu­re.
- Clean and check operation of safety valve.
Additional Procedures that may be necessary:
- Check burner pressure and gas flow rates.
Preliminary Checks
- Remove outer case
- Check the system pressure is at least
0.7 bar cold
- Check operation of l/3 and 2/3 solenoids
- Check that the burner is extinguished full:
when both solenoids are closed in both
DHW and C/H modes.
- Test ionisation functions and check that lockout occurs by turning off gas tap.
-Whilst boiler is operating, check operatior of primary flow switch by closing heating
flow valve and by pass screw (turn clockwi
se) noting the number of turns so that it may be reset correctly.
5
Page 6

REMOVAL AND REPLACEMENT OF PARTS

efore removing appliance case, isolate 5. Ignition Electrodes
e gas and electrical supplies. Isolate boi- Carry out steps 1 and 2 as above. Hinge r from the system and drain before remo- down electrical box by pressing retaining ng any component in the waterways. tabs P on either side. nsure that the appliance is cool.
Outer Case
t free. When replacing, carefully locate on gs (B) on top edge of chassis.
Remove wiring cover C. Disconnect leads
and
C
from spark generator. Loosen screws secu­ring the closure plate and remove. Remove grommet from base of sealed chamber.
Remove screw securing electrode bracket and lift clear easing spade connectors through the grommet. Reassemble in rever­se order, twisted together electrodes cable at least IO times to avoid electrical interfe­rence.
6. Burner Assembly Carry out steps 1,2, disconnect electrodes as mentionned in section 4 and 5. Remove two screws securing burner assembly to the back panel of the boiler. Lift right hand back corner first. Reassemble in reverse order.
7. Gas Solenoids Disconnect colour coded leads. Remove six screws. The solenoids are attached to their base plate. Lift clear taking care not to lose the three plungers and springs. Reassemble in reverse order replacing the cork gasket.
1
front panel as in steps 1 and 2. Disconnec three pressure switch cables noting the1
positions. 1 = white cable connected to NC
2 = black cable connected to NO
P = orange cable connected to C
Remove screw securing the switch bracks to the chassis. Disconnect the samplin! tubes again noting their positioning (+ an
-). Remove switch. Reassemble in revers
order.
11. Pressure Switch Venturi Carry out steps 1, 2 and 8, as above Disconnect the sampling tubes and rema ve the screw securing the venturi to thl flue outlet. Remove venturi by the botton of the 45” elbow. Reassemble in revels order.
12. Drain down 5 drain points are located on the boiler
Combustion Chamber iscrew four self tapping screws securing s sealed chamber front panel and lift er top corner locating lugs. Unscrew four If tapping screws to release combustion iamber front plate and lift clear. ?assemble in reverse order.
Burner Manifold lrry out steps 1 and 2 as above. Remove o screws securing the closure plate and ? remaining four screws to release the mifold. Lift clear. Replace the manifold sket. Reassemble in reverse order.
Ionisation Electrodes trry out steps 1 and 2 as above. Loosen rews securing the closure plate and nove. Disconnect the lead from the main ring loom. Remove screw securing elec­Ide to burner. Thread wire through grom­9 and lift clear. Reassemble in reverse der.
8. Fan Assembly Remove outer case and sealed chamber front panel (See Steps 1 and 2). Disconnect spade connectors noting positions. Remove two screws securing the front of the fan assembly and loosen screw on flue outlet. Twist fan assembly anticlockwise to disen­gage from flue outlet and lift clear. Re-assemble in the reverse order ensuring that the wiring is re-connected correctly and the screw on the flue outlet tightened.
9. Flue Hood Carry out steps 1 and 2 as above. Remove fan assembly as in step 8. Remove the three screws securing the angled top of the hood to the chassis. Lift and remove taking care not to snag the pressure switch cables. Re-assemble in the reverse order ensuring that the hood is located behind the combus­tion chamber rear panel.
10. Pressure Switch Remove outer case and sealed chamber
(air sebarator)
1 = DHW circuit drain point 2 = Heating circuit drain point
13. Water filters ( DHW and Heating) The DHW filter ensures a seal between the connecting bracket and the pipe to the DHW flow switch. Drain the boiler as ir step 12. Unscrew the pipe nut and remove the clip on the hydraulic assy. Pull the pipe toward you and remove the water filter from its location. The C/H filter is located in the right hydrau lit assembly. Remove the return pipe a: described previously and withdraw the fit ter. Reassemble in reverse order.
Page 7
14. Flow switches Drain boiler as in step 12. Disconnect the electrical plug, turn the top cover anti­clockwise, remove the O-ring and the brass piston. Reassemble in reverse order.
15.3-Way valve Drain boiler as in step 12. Remove the 3 clips on the 3 way valve. Remove the clip on the exchanger flow pipe. Pull the pipe down then pull it out of the 3 way valve. Disconnect the plug from the motor. Unscrew the nut on the pipe between the connecting bracket and the 3 way valve
and pull it toward you. Rotate the 3 way valve body anti-clockwise to unclip it from the left hydraulic assembly.
16. Secondary heat exchanger
Drain both circuits of the boiler as in step
12. Unscrew the 2 fixing screws (D) and
remove the DHW exchanger from the front.
toward you to remove. Reassemble in rever-
se order.
18. Pump Drain boiler as in step 12. Pivot the electical box downwards. Open the electrical box cover removing the 2 screws. Remove the pump plug from the power board and earth plug from earth socket. Unscrew the nut (F) of the return pipe from the volute. Remove
the clip (G) on the pump volute and pull
pump toward you. Reassemble in reverse
order.
19. Pressure relief valve The pressure relief valve can be serviced from the front of the appliance. Drain the boi­ler first, undo the retaining screw and pull out the valve.Reassemble in reverse order.
H
22. Spark generator Carry out steps 1,2, and open the electrical
box cover as mentionned in step 5. Undo the 4 screws of the electrical rear panel and remove it. Unplug electrodes wires, remove the ignitor connector from the PCB, remove earth plug from earth socket. Hang out the ignitor. Reassemble in reverse order.
23. Power board Carry out steps 1, 2, and open the electrical box cover as mentionned in step 5. Undo the 4 screws of the electrical rear panel and remove it. Unplug all cables from the PCB, remove earth plug from earth socket. Hang out the power board. Reassemble in rever­se order.
24. Control board Pull out plastic knob from the front panel and proceed as step 23. Reassemble in reverse order.
Prior to reassembly, check that the 4 gas-
kets are correctly positioned. The heat exchanger is so designed that it cannot be remounted incorrectly.
17. Main heat exchanger Carry out steps 1 and 2 as above. Drain boiler as in step 12. Remove the 2 clips (E) located on return and flow pipes and pull
them downwards. Pull the main exchanger
20. Thermistors Drain the boiler as step 12. Disconnect the
plug, remove the retaining clip pull the ther­mistor out. Reassemble in reverse order. 38 = DHW thermistor 37 = Heating thermistor
38
37
21. Safety thermostat Remove the casing as step 1 and hinge down the electrical box as step 5. Disconnect the 2 cables, pull out the sensor
with the clip (13). Reassemble in reverse order.
25. Expansion vessel Remove the casing as step 1 and drain the boiler as step 12 above. Unscrew the connecting tails nuts and lift out the boiler from the wall. Place it on a side on the floor. Remove the expansion vessel bracket retaining screws, disconnect the pipe from the vessel Reassemble in reverse order.
and pull ti toward you.
7
Page 8
-Check mains electrical connection
.
-Check internal fuses
-Check connection between the 2 PCBS
No
Ok
Press the reset button
Yes
Does the red LED
- Ok

FAULT FINDING CHART Part 1

1 No
Ihght ?
I
1 PLEASE CHECK THE FOLLOWING POINTS CAREFULLY BEFORE GOING
THROUGH THE FAULT FINDING CHART
-Gas
pressure
-Electric mains
-Minimum water pressure in the heating circuit (over 0.8 bar)
-All isolating valves have been opened
-Boiler air vented
-Minimum domestic hot water flow of 2 I/min
-Check that the heating filter is clear.
Check or replace the DWH flow
Replace DHW flow
1
switch
switch
Check DHW flow switch
operation
I
.I , ,
Does the pump run 1
Draw off Domestic Hot water
Does the pump run ?
Does the fan run ?
y&3& “--
switch continuity
between P and 2
& No
Replace Driver or control PCB I
I
I
Release pump rotor
Replace driver or control PCB
Check or replace main or secondary
heat exchangers They could be
11
-Id 1
fully scaled.
Replace heating thermistor
Lot
_..“-. ~ ..“.. ,,. .,,- -.iler
Check heating
thermistor
Ok
Replace pressure switch
Check air pressure
switch continuity
between P and 1
No
-Replace pressure swtch
\
Replace spark generator or ignition
electrods assembly a go~~~o~~~~o 1 1
Replace fan assembly
J
I
Page 9

FAULT FINDING CHART Part 2

Replace control PCB because orange
LED is deffective
Replace control or driver PCB
Check if an overheat occur or replace
overheat sensor
Replace driver PCB
Replace gas solenoids
Replace electrode
assembly
Does the orange LED
Does the red LED
Does overheat contact
Press the reset button
Do the gas solendids
Is there a gas pressure
Check the ionization
Replace driver PC6
I
light ?
light 1
close ?
energise 1
at manifold ?
electrode
No
Yes
Yes
Yes
Ok
temperature rise ?
Does the heating outlet
pipe temperature we ?
Replace the DHW heat exchanger
+Y
I
Does the DHW
No
F
Wait until the temperature
becomes stable.
I
Replace DHW thermistor
J
Does DHW temperature
rise over 7o”C?
Replace control PCB
Replace the 3 way valve
Replace control PCB
No
cvi
Stop water draw off
Does the orange LED
hot then rotate the heating control
knob anticlockwise to minimum
Does the orange LED
light ?
+
light ?
I
Yes
No
co
1
The boiler is OK
Page 10

SHORT LIST

104---B
411
572
505 811 39
805
607
938
532
615
560
627d 6294
(ey no Description
104 OVERHEAT THERMOSTAT 100°C
BRITONY COMBI 80
GC N”
2;7$83
Manf. Pt. N”
1010572
BRITONY COMBI 100 G.C. N” Manf. Pt. N” 277783 1010572
110 IGNITION ELECTRODE ASSY 277788 1002801 277788 1002801 111 IONIZATION ELECTRODE 277789 1002802 277789 1002802 113 HEAT EXCHANGER 277790 1010017 1011136 206 FAN ASSY 277804 1010212 1003011 216 PRESSURE SWITCH KIT 277808 81725 277808 81725 411 SOLENOID VALVE KIT 277812 81432 277812 81432 505 THREE-WAY VALVE 277833 1010000 277833 1010000 514 WATER/WATER HEAT EXCHANGER 277836 1002540 1011164 532 WATER THROTTLE HEAD ASSY 277846 81471 277846 81471 553 WATER FILTER 277854 1007727 277854 1007727 560 AIR SEPARATOR HEAD ASSY 277857 1002653 277857 1002653 572 PUMP 1 SPEED 240V 277862 1010774 277862 1010774 605 CONNECTOR 277872 1010349 277872 1010349 607 IGNITER 379075 1002105.20 379075 1002105.20 615 PRINTED CIRCUIT BOARD OF POWER 277880 1010592 277880 1010592 616 PRINTED CIRCUIT BOARD OF REGULATION 277881 1010047 277881 1010047 627 FUSE 250V 2A - TEMPORIZED 277883 1003456 277883 1003456 629 FUSE 250V 1.25A - TEMPORIZED 277884 1003635 277884 1003635 805 PRESSURE GAUGE 1012561 1012561 811 BLACK KNOB 1011699 1011699 922 TAP HEAD ASSY 366937 67704 366937 67704 938 PRESSURE RELIEF VALVE 277770 76584 277770 76584
Chaffoteaux et Maury are continuously improving their products and therefore reserve the right to change specifications without prior notice and accepts no liability for any errors or omission in the information contained in this document.
0 Chaffoteaux et Maury 1996 a:
Chaffoteaux et Maury Ltd Trench Lock Trench
Telford -7 Shropshire
TFI 4SZ : Tel: 01952 222727
Fax: 01952 243493
8 6
W iz
2
Q a
Ei
r:
Page 11
Page 12
ESP035
ESP035
Loading...