CFM CX3000GS User Manual

CX3000GSCX3000GS Ducted Air PurifierDucted Air Purifier
Installation & Maintenance
Instructions
1
P
AGE
INSTALLATION INSTRUCTIONS
BEFORE INSTALLATION 2
INSTALLATION 2
TYPICAL HORIZONTAL SYSTEM 4
TYPICAL VERTICAL SYSTEM 4
WIRING DIAGRAM 5
OPERATION
AIR PURIFICATION 6
SAFETY INSTRUCTIONS 7
COST OF OPERATION 7
AIR CYCLES 7
PERFORMANCE DATA
AIRFLOW & RESISTANCE DATA 8
PARTICLE SIZE EFFICIENCY GRAPH 8
BACTERIA REDUCTION 9
PARTICULATE FILTRATION 9
PARTICLE REDUCTION 9
REMOVAL EFFICIENCY OF TYPICAL ALLERGENS 9
CARBON MONOXIDE REDUCTION 9
MAINTENANCE
SERVICE INTERVALS 10
REPLACING LAMPS 10
REPLACING FILTER 11
RESETTING SERVICE LIGHTS 11
PRODUCT SPECIFICATIONS
SPECIFICATIONS 12
REPLACEMENT PARTS 12
PARTS LIST 13
LIMITED WARRANTY
RREEAADD AANNDD SSAAVVEE TTHHEESSEE IINNSSTTRRUUCCTTIIOONNSS
TTAABBLLEE OOFF CCOONNTTEENNTTSSPPRROODDUUCCTT SSPPEECCIIFFIICCAATTIIOONNSS
IINNSSTTAALLLLAATTIIOONN IINNSSTTRRUUCCTTIIOONNSS
BBEEFFOORREE IINNSSTTAALLLLAATTIIOONN
1. Before installing the damage.
2. During handling and installation, take care to protect the honeycomb core of the photo-catalytic module. The titanium-aluminum core is very fragile and easily damaged.
3. Do not install insulation within 3 inches (75 mm) of the ultraviolet UVC lamps.
4. Access for service is required when mounting the or behind walls.
5. Do not install in such a manner that the interior photo-catalytic module may fall from an elevated position, and cause injury to people or equipment below.
1. Unscrew the two locking knobs and remove the inner module from the outer case.
2. Take care not to bend or distort the outer metal enclosure.
3. Ensure the unit is positioned so that the inlet, or return, air enters the side containing the MERV-11 electrostatic filter. (Fig. 1)
4. Mount the outer case to the support plenum. CAUTION: Use a screw length that will not penetrate the inside module containing the photo-catalytic mod­ule and MERV-11 electrostatic filter. There is only 1/2 inch of clearance between the outer case and inner module.
5. In the event the foot print of the air handler is larger or smaller than the outer metal enclosure of the fabricated from 18 ga. sheet metal. (Fig. 2)
6. Tape all seams between the air handler and the outlet side of the to ensure there can be no air bypassing the system.
7. Attach the air handler to the outlet side of the drilling sheet metal screws.
8. Slide the inner module into the outer case, and secure locking knobs finger tight only. Ensure the inner module can slide freely in and out of the outer case.
9. Plug the power cord into any 120 VAC outlet, and check both sight ports to ensure both lamps are illuminated. The ultraviolet lamps must remain on at all times.
10. Check the sequence for 15 seconds. The FILTER light should then turn flashing green, and the LAMP light a steady green.
11. Set the HVAC fan to operate for at least 30 minutes every hour. If air quality problems persist after one week, increase the fan operating time by 5 minute intervals, until suitable air quality is achieved.
CCXX33000000GGSS
CCXX33000000GGSS DDuucctteedd AAiirr PPuurriiffiieerr
IINNSSTTAALLLLAATTIIOONN
CCXX33000000GGSS
service panel. The LED service lights should flash in
unit, suitable metal transitions should be
, inspect for any signs of
CCXX33000000GGSS
CCXX33000000GGSS
above ceilings
with #10 x 3/8 self-
CCXX33000000GGSS
2
3
Filter Side Catalyst side
TTRRAANNSSIITTIIOONNSS FFOORR IINN--DDUUCCTT MMOOUUNNTTIINNGG
FFiigg.. 11
IINNSSTTAALLLLAATTIIOONN IINNSSTTRRUUCCTTIIOONNSS
AAIIRRFFLLOOWW
Airflow
FFiigg.. 22
20 Degree Expansion Per Side (4 in. Per Linear Foot)
Return Air Duct Clean Air Out
Tr ansition
CX3000GS
#10 Screws Not Longer Than 1/2 in.
Tr ansition
100
99 98 97 96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81 80
Particle Size - Microns
Particle Reduction - First Pass
PARTICULATE FILTRATION
WHOLE HOME
PARTICLE REDUCTION
BACTERIA REDUCTION
Te st Period In Hours
Hours of Operation
1 2 3 4 5 6 7 8 9 10 11 12
CARBON MONOXIDE
REDUCTION
REMOVAL EFFICIENCY
OF TYPICAL ALLERGENS
0 15 30 45 60
0
1
17
30
42
65
Te st Room
15’ L x 15 W x 8’ H
Micro-organism Plate Count
Percent Reduction
100
90
80
70
60
50
40
30
20
10
0
2,300 Sq. Foot
Home
5.0
3.0
1.0
.5
.3
77.8
93.4
94.1
95.1
Start
Finish
Time In Hours
Parts Per Million - CO
1 2 3 4 5 6 7 8
250
225
200
175
150
125
100
75
50
25
0
99.9%
99.7%
99.5%
99.3%
99.1%
98.9%
98.7%
98.5%
98.3%
98.1%
97.9%
97.7%
97.5%
97.3%
97.1%
96.9%
96.7%
96.5%
96.3%
96.1%
IINNSSTTAALLLLAATTIIOONN IINNSSTTRRUUCCTTIIOONNSS
TTYYPPIICCAALL HHOORRIIZZOONNTTAALL SSYYSSTTEEMM
Gas Burners
Transition As Needed
TTYYPPIICCAALL VVEERRTTIICCAALL SSYYSSTTEEMM
Plenum
Airflow
Fan Coil Unit
CX3000GS Ducted Air Purifier
4
5
IINNSSTTAALLLLAATTIIOONN IINNSSTTRRUUCCTTIIOONNSS
WWIIRRIINNGG DDIIAAGGRRAAMM
LAMP
LAMP
SERVICE PANEL
BALLAST
120/220 V
BALLAST
120/220 V
1 AMP
120 V
TRANSFORMER
WHITE
BLACK
WHITE
BLACK
BLUE
BLUE
WHITE
BLACK
RED
CORD
POWER
AGC2
2 AMP FUSE
NEUTRAL - WHITE
WHITE GROUND
RECEPTACLE
LINE - RED
OOPPEERRAATTIIOONN
AAIIRR PPUURRIIFFIICCAATTIIOONN
CCXX33000000GGSS DDuucctteedd AAiirr PPuurriiffiieerr
The conditioning system, up to five tons in size. It is rated for use at standard ambient air temperatures during heating and air-conditioning functions. It is not rated for operation at elevated air temperatures in excess of 125 F.
CCXX33000000GGSS
The
1. Electrostatic MERV-11 Filter - removes 0.3 micron allergens and dust
2. Reactive Catalyst - destroys VOC’s, toxic chemicals and odors
3. UVC Germicidal Light - kills germs, viruses and bacteria on contact
4. Negative Ions and Activated Oxygen - keep air fresh and clean
Air purification and sterilization occur whenever the HVAC system fan is operating. The ultraviolet UVC lamps are always on. They continuously clean and reactivate the catalyst by burning off surface impurities during periods of non-use, or no airflow.
Do not attempt to clean the photo-catalytic honeycomb core with cleaning solutions.
uses a four-stage process to purify indoor air:
is designed to operate with any heating or air-
It is recommended that the per day, to remove toxic materials from an indoor environment. For individuals who may be sensitive to mold spores, dust mites or chemicals, or have respiratory problems such as asthma, emphysema and chronic allergies, the operating time should be extended to 40 minutes or more per hour. The actual time of operation depends on many factors, including the level of ambient pollution or pollen levels, and individual sensitivity to allergens.
It is recommended that a programmable thermostat be used. These can be set to provide continuous air circulation, and thus air purification, even when the HVAC system is not calling for heating or cooling.
In the event an existing thermostat does not have the capability to operate the fan independently, it is recommended that an AirCycler be installed. An AirCycler is a device that is wired in parallel with existing thermostat wiring, and can be programmed to turn on the HVAC system fan for any desired time interval. A built­in memory chip tracks the time that a fan operates every hour, and energizes the fan only if normal requirements for heating and air conditioning have not cycled the fan unit long enough to meet pre-determined air purification requirements.
An AirCycler may be purchased from the following sources:
Your local HVAC wholesaler or contractor
Shelter Supply, Lakeville, MN (1-800-762-8399)
www.AirCycler.com
CCXX33000000GGSS
operate at least 30 minutes per hour, 24 hours
6
7
1. Never look into a burning ultraviolet lamp without proper eye protection, as severe eye damage may result.
2. Always unplug the power cord from the unit when changing the filter or ultra­violet UVC lamps.
3. Do not attempt to clean the photo-catalytic honeycomb core with cleaning solutions. The catalyst is constantly radiated by short wave ultraviolet UVC light during operation, and is self-cleaning.
CCOOSSTT OOFF OOPPEERRAATTIIOONN
(Calculations are based on continuous operation, 24 hours per day,
and an energy consumption of 32.25 kw-hrs per month)
ELECTRICITY COST (per kw-hr) MONTHLY COST ANNUAL COST
$0.06 $1.93 $23.16
$0.08 $2.58 $30.96
$0.10 $3.22 $38.64
FAN OPERATING
PERIOD
AIR CYCLES
PER HOUR
AIR CYCLES
PER DAY
10 minutes per hour 0.9 21
20 minutes per hour 1.8 42
30 minutes per hour 2.7 63
40 minutes per hour 3.6 84
50 minutes per hour 4.5 105
60 minutes per hour 5.4 126
OOPPEERRAATTIIOONN
SSAAFFEETTYY IINNSSTTRRUUCCTTIIOONNSS
AAIIRR CCYYCCLLEESS
(Calculations are based on a floor area of 3,000 sq. ft.)
PPEERRFFOORRMMAANNCCEE DDAATTAA
AAIIRRFFLLOOWW && RREESSIISSTTAANNCCEE DDAATTAA
Airflow (cfm) Resistance (in. wg) Air Velocity (fpm)
1250 0.18 360
1500 0.20 432
1750 0.25 504
2000 0.35 576
2250 0.42 648
2500 0.55 720
PPAARRTTIICCLLEE SSIIZZEE EEFFFFIICCIIEENNCCYY GGRRAAPPHH
100
80
60
40
Removal Percentage
20
0
0.3u 0.5u
Percent Reduction - First Pass
0.7u
Particle Size - Microns
1.0u
8
5.0u
10u
100
99 98 97 96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81 80
Particle Size - Microns
Particle Reduction - First Pass
PARTICULATE FILTRATION
WHOLE HOME
PARTICLE REDUCTION
BACTERIA REDUCTION
Te st Period In Hours
Hours of Operation
1 2 3 4 5 6 7 8 9 10 11 12
CARBON MONOXIDE
REDUCTION
REMOVAL EFFICIENCY
OF TYPICAL ALLERGENS
0 15 30 45 60
0
1
17
30
42
65
Te st Room
15’ L x 15’ W x 8’ H
Micro-organism Plate Count
Percent Reduction
100
90
80
70
60
50
40
30
20
10
0
2,300 Sq. Foot
Home
5.0
3.0
1.0
.5
.3
77.8
93.4
94.1
95.1
Start
Finish
Time In Hours
Parts Per Million - CO
1 2 3 4 5 6 7 8
250
225
200
175
150
125
100
75
50
25
0
99.9%
99.7%
99.5%
99.3%
99.1%
98.9%
98.7%
98.5%
98.3%
98.1%
97.9%
97.7%
97.5%
97.3%
97.1%
96.9%
96.7%
96.5%
96.3%
96.1%
9
PPEERRFFOORRMMAANNCCEE DDAATTAA
MMAAIINNTTEENNAANNCCEE
SSEERRVVIICCEE IINNTTEERRVVAALLSS
CCXX33000000GGSS DDuucctteedd AAiirr PPuurriiffiieerr
The track of service intervals. LED service lights change color, 30 days in advance of required service, to indicate when the MERV-11 electrostatic filter or ultraviolet UVC lamps need replacement.
MERV-11 Electrostatic Filter
o Replace every 6 months o LED service light turns from green to yellow after 5 months, and to
red after 6 months
Ultraviolet UVC Lamps
o Replace every 12 months o LED service light turns from green to yellow after 11 months, and to
red after 12 months
has a built-in computer to automatically keep
RREEPPLLAACCIINNGG LLAAMMPPSS
1. Unplug the power cord from the
2. Unscrew the two locking knobs and remove the door. (Fig. 6)
3. Remove photo-catalytic module. (Fig. 3)
4. Unplug UVC lamps. (Fig. 4)
5. Loosen retaining knobs and remove old UVC lamps. (Fig. 5)
6. Install new UVC lamps, tightening only finger tight.
7. Tighten retaining knobs and reconnect plug ends.
8. Re-install photo-catalytic module and filter. Ensure that filter and photo-cat­alytic module are installed in proper airflow sequence.
9. Secure door.
10. Reconnect power cord.
11. Check both sight ports to ensure that both lamps are illuminated.
FFiigg.. 33
CCXX33000000GGSS
FFiigg.. 44
unit.
FFiigg.. 55
10
11
1. Unplug the power cord from the
CCXX33000000GGSS
unit.
2. Unscrew the two locking knobs and remove the door. (Fig. 6)
3. Remove old filter and replace with new MERV-11 electrostatic filter. Ensure that airflow arrow on filter points to the inside of module. (Fig. 7)
RREESSEETTTTIINNGG SSEERRVVIICCEE LLIIGGHHTTSS
On the right side of the service panel, there are arrows pointing to two small holes marked ‘RESET’. (Fig. 8) One is for the FILTER service light, and the other is for the LAMP service light. The service lights may be reset by inserting the end of a paper clip into the corresponding hole, and pushing lightly until the service light returns to green.
FFiigg.. 66 FFiigg.. 77
SSEERRVVIICCEE PPAANNEELL
FFiigg.. 88
MMAAIINNTTEENNAANNCCEE
RREEPPLLAACCIINNGG FFIILLTTEERR
LAMP
FILTER
SERVICE
OK
SOON
RESET
SERVICE
NOW
RESET
SSPPEECCIIFFIICCAATTIIOONNSS
Manufacturer: Continental Fan Manufacturing Inc.
Model: CX3000GS Ducted Air Purifier
Dimensions: 21” W x 25” H x 10” D
Weight: 26 lbs
Max Airflow: 2,170 cfm
Max Air Velocity: 625 fpm
Power Consumption: 45 watts
Voltage: 120V/60 Hz
Current: 0.6 amps
Fuse: AGC-2
Capacity: 4.0 to 5.0 tons
UV Range: 254 nm (germicidal)
Lamps: CX3000-RLGS - ultraviolet UVC lamps (2)
Filter: CX3000-RFGS - MERV-11 electrostatic filter
Application: 3000 sq. ft.
Service Interval: Lamps - 1 year
Filter - 6 months
Catalyst: Metal oxides (70 sq. ft.)
RREEPPLLAACCEEMMEENNTT PPAARRTTSS
Replacement parts are available from the following sources:
Your local HVAC wholesaler or contractor
Continental Fan Manufacturing Inc., Buffalo, NY (1-800-779-4021)
www.continentalfan.com
12
13
DESCRIPTION
Photo-Catalytic Module (Honeycomb Core)
12 Volt Transformer
Electronic Lamp Ballast
MERV-11 Electrostatic Filter
Ultraviolet UVC Lamps (Set of 2)
1 Year Replacement Parts Kit, comprising:
(2) CX3000-RFGS
(1) CX3000-RLGS
PPRROODDUUCCTT SSPPEECCIIFFIICCAATTIIOONNSS
PPAARRTTSS LLIISSTT
PART NUMBER
AL006
BL007
BL014
CX3000-RFGS
CX3000-RLGS
CX3000-RFLGS
CX3000GSCX3000GS Ducted Air PurifierDucted Air Purifier
Installation & Maintenance
Instructions
LLIIMMIITTEEDD WWAARRRRAANNTTYY
Subject to the provisions of the clauses herein, Vendor agrees to correct any
defect or defects in workmanship or materials which may develop under
proper and normal use, by repair or by replacement of the defective part or
equipment, at Vendor’s option, FOB factory. Unless otherwise stated, the
warranty period shall be one (1) year from date of shipment. The exceptions
to this warranty period are:
CX Complete Air Purification Systems - Two (2) years
This warranty is provided to the original Buyer, and may not be transferred,
sold or bartered. Motors, drives, electrical controls and other components
manufactured for Vendor by others are not covered by these warranty provisions.
All warranty claims must be processed through point of purchase. All warran-
ty repair work must be performed either at the factory or by a factory certified
service center. For additional information regarding warranties, see Vendor
document: Limited Warranty-0909.
UUSSAA
CCoonnttiinneennttaall FFaann MMaannuuffaaccttuurriinngg IInncc.. 203 Eggert Road Buffalo, New York 14215 Tel: (800) 779 4021 Fax: (716) 842 0611
wwww..ccoonnttiinneennttaallffaann..ccoomm
CCaannaaddaa
AAeerroofflloo IInncc.. 12-205 Matheson Blvd. East Mississauga, Ontario L4Z 3E3 Tel: (905) 890 6192 Fax: (905) 890 6193
wwwwww..aaeerroofflloo..ccoomm
CX3000GS-I&M-1001
Loading...