CET PMC-T402 User Manual

Page 1
PMC-T402
Temperature & Iresidual Monitor
User Manual
Version: V1.0
November 09, 2017
Page 2
This manual may not be reproduced in whole or in part by any means without the express written permission from CET Electric Technology (CET). The information contained in this manual is believed to be accurate at the time of publication; however, CET assumes no responsibility for any errors which may appear here and reserves the right to make changes without notice. Please consult CET or your local representative for the latest product specifications.
DANGER
This symbol indicates the presence of danger that may result in severe injury or death and permanent equipment damage if proper precautions are not taken during the installation, operation or maintenance of the device.
CAUTION
This symbol indicates the potential of personal injury or equipment damage if proper precautions are not taken during the installation, operation or maintenance of the device.
2
Page 3
Installation, operation and maintenance of the device should only be performed by qualified, competent personnel that have the appropriate training and experience with high voltage and current devices. The device must
Ensure that all incoming AC power and other power sources are turned OFF
Before connecting the device to the power source, check the label on top of the device to ensure that it is equipped with the appropriate power supply, and
During normal operation of the device, hazardous voltages are present on its terminal strips and throughout the connected potential transformers (PT) and
current transformers (CT). PT and CT secondary circuits are capable of
generating lethal voltages and currents with their primary circuits energized. Follow standard safety precautions while performing any installation or service
Do not use the device for primary protection functions where failure of the device can cause fire, injury or death. The device should only be used for
Under no circumstances should the device be connected to a power source if
To prevent potential fire or shock hazard, do not expose the device to rain or
Setup procedures must be performed only by qualified personnel familiar with
DANGER
Failure to observe the following instructions may result in severe injury or
death and/or equipment damage.
be installed in accordance with all local and national electrical codes.
before performing any work on the device.
the correct voltage and current input specifications for your application.
work (i.e. removing PT fuses, shorting CT secondaries, …etc).
shadow protection if needed.
it is damaged.
moisture.
the instrument and its associated electrical equipment.
DO NOT open the instrument under any circumstances.
3
Page 4
Limited warranty
CET offers the customer a minimum of 12-month functional warranty on the device for faulty parts or workmanship from the date of dispatch from the
CET does not accept liability for any damage caused by device malfunctions. CET accepts no responsibility for the suitability of the device to the application for
Failure to install, set up or operate the device according to the instructions herein
Only CET’s duly authorized representative may open your device. The unit should only be opened in a fully anti-static environment. Failure to do so may damage
distributor. This warranty is on a return to factory for repair basis.
which it was purchased.
will void the warranty.
the electronic components and will void the warranty.
4
Page 5
Table of Contents
Chapter 1 Introduction ........................................................................................................................ 7
1.1 Overview............................................................................................................................... 7
1.2 Features ................................................................................................................................ 7
1.3 Getting more information ..................................................................................................... 8
Chapter 2 Installation .......................................................................................................................... 9
2.1 Appearance ........................................................................................................................... 9
2.2 Dimensions ......................................................................................................................... 10
2.2.1 Main Unit ................................................................................................................. 10
2.2.2 Terminal ................................................................................................................... 10
2.2.3 Residual Current CTs ................................................................................................ 11
2.2.4 PT100 ....................................................................................................................... 12
2.3 Mounting ............................................................................................................................ 12
2.4 RS-485 Wiring ..................................................................................................................... 14
2.5 Digital Output Wiring .......................................................................................................... 14
2.6 Residual Current Input Wiring ............................................................................................. 14
2.7 RTD Input Wiring ................................................................................................................. 15
2.8 Power Supply Wiring ........................................................................................................... 15
Chapter 3 Front Panel ....................................................................................................................... 16
3.1 LED Indicator ....................................................................................................................... 16
3.2 Buttons ............................................................................................................................... 16
3.3 LED Display ......................................................................................................................... 17
3.3.1 LED Display Symbols ................................................................................................. 17
3.3.2 LED Testing ............................................................................................................... 17
3.3.3 Default Display ......................................................................................................... 17
3.3.4 Data Display ............................................................................................................. 18
3.3.5 SOE Display .............................................................................................................. 18
3.4 Setup Configuration ............................................................................................................ 19
3.4.1 Making Setup Changes ............................................................................................. 19
3.4.2 Setup Menu ............................................................................................................. 20
3.4.3 Configuration ........................................................................................................... 21
Chapter 4 Applications ...................................................................................................................... 23
4.1 Condition Monitoring .......................................................................................................... 23
4.1.1 Residual Current Monitoring .................................................................................... 23
4.1.2 Temperature Alarm .................................................................................................. 23
4.2 Digital Output ..................................................................................................................... 25
4.3 SOE Log ............................................................................................................................... 25
Chapter 5 Modbus Register Map ....................................................................................................... 26
5.1 Basic Measurements ........................................................................................................... 26
5.2 SOE Log ............................................................................................................................... 27
5.3 Device Setup ....................................................................................................................... 28
5.4 Time .................................................................................................................................... 29
5.5 Remote Control ................................................................................................................... 30
5
Page 6
5.6 Device Information.............................................................................................................. 30
Appendix A Technical Specifications .................................................................................................. 31
Appendix B Standards of Compliance ................................................................................................ 32
Appendix C Ordering Guide ............................................................................................................... 33
Contact us ......................................................................................................................................... 34
6
Page 7
Chapter 1 Introduction
This manual explains how to use the PMC-T402 Temperature & Iresidual Monitor.
This chapter provides an overview of the PMC-T402 and summarizes many of its key features.
1.1 Overview
The PMC-T402 is CET’s latest offer for the Temperature (RTD) and Residual Current monitoring for the Commercial and Industrial markets. Housed in a compact form factor measuring only 72(L)×72(H)×87.8(D)mm, the PMC-T402 can be used as a stand-alone device that offers real-time monitoring and alarming of Residual Current and Temperature with its LED display, Front Panel buttons, 1xDO for Alarm Output or General Purpose Control and a built-in Alarm Buzzer. With the standard RS­485 port and Modbus RTU protocol support, the PMC-T402 becomes a vital component of an intelligent, centralized Condition Monitoring.
Intelligent Electrical Fire and Condition Monitoring for Industrial or Commercial facilities Industrial and Commercial Electrical Power System AC Low Voltage Distribution System Condition monitoring of electrical equipment
1.2 Features
Ease of use
Bright 2-line LED display with high visibility for Temperature and Residual Current measurements LED Indicators for Run, Fault, Warning, Alarm, Comm. Activities, Measurement Channel and Unit
indicators
Built-in Alarm Buzzer Password-protected setup via front panel or free PMC Setup software Panel or DIN Rail (with adapter) Mount Support Firmware Upgrade over Communications
Residual Current Measurement
4 channels Residual Current Input (CT not included) Two Setpoint Alarm Levels between 20 and 1000mA
Temperature Measurement
4 channels RTD Input (PT100 sensor not included) Two Setpoint Alarm levels between 45°C and 140°C
SOE Log
64 events time-stamped to ±1ms resolution Setup changes, Setpoint Alarms, Power Reset …etc.
Digital Output
1 Form A mechanical DO (3A @ 250VAC or 30VDC) Can be used for Alarm Output or General Purpose Control
Communications
7
Page 8
1xRS-485 port @ 9600bps, 8E1 Modbus RTU protocol
1.3 Getting more information
Additional information is available from CET via the following sources:
Visit www.cet-global.com Contact your local representative Contact CET directly via email at support@cet-global.com
8
Page 9
Installation of the PMC-T402 should only be performed by qualified, competent personnel that have the appropriate training and experience with high voltage and current devices.
During the operation of the monitor, hazardous voltages are present at the input terminals. Failure to observe precautions can result in serious or even fatal injury and equipment
damage.
Chapter 2 Installation
Caution
The monitor must be installed in accordance with all local and national electrical codes.
2.1 Appearance
Figure 2-1 Appearance
9
Page 10
2.2 Dimensions
2.2.1 Main Unit
2.2.2 Terminal
Figure 2-2 Main Unit Dimensions
Figure 2-3 Terminal Dimensions
10
Page 11
Terminal
Terminal Dimension (mm)
Wire Size (mm2)
Max. Torque
1
DO & RS-485
2.5 x 2.8
1.5
4.5 kgf.cm/M2.5 (3.9 lb-in)
2
TCn
3
IRn
4
Power Supply
6.0 x 6.0
1.0mm2 - 2.5mm2
(14AWG - 22AWG)
6.0 kgf.cm/M3 (5.2 lb-in)
2.2.3 Residual Current CTs
PMC-MIR-46 (160A, Ø=46mm)
Table 2-1 Terminal Dimensions
Figure 2-4 PMC-MIR-46 Dimensions
PMC-MIR-80 (400A, Ø=80mm)
Figure 2-5 PMC-MIR-80 Dimensions
11
Page 12
PMC-MIR-120 (1000A, Ø=120mm)
Figure 2-6 PMC-MIR-120 Dimensions
PMC-MIR-220x50 (630A, 220x50mm)
Figure 2-7 PMC-MIR-220x50 Dimensions
2.2.4 PT100
Figure 2-8 PT100 Dimensions
2.3 Mounting
The PMC-T402 should be installed in a dry environment with no dust and kept away from heat, radiation and electrical noise source. The PMC-T402 supports two installation modes: Panel mount and DIN-Rail mount.
Panel Installation steps:
o Remove the installation clips from the PMC-T402 o Fit the PMC-T402 through a 68mm x 68mm cutout as shown in Figure 2-9 o Re-install the installation clips and push the clips tightly against the panel to secure the PMC-
T402
12
Page 13
Figure 2-9 Panel Installation
DIN-Rail Installation steps:
o Before installation, please make sure that the DIN rail and the adapter are already in place. o Remove the installation clips from the PMC-T402 o Fit the PMC-T402 through the adapter as shown in Figure 2-10 o Re-install the installation clips and push the clips tightly against the adapter to secure the
PMC-T402
Figure 2-10 DIN-Rail Installation
13
Page 14
2.4 RS-485 Wiring
The PMC-T402 provides a standard RS-485 port that supports the Modbus RTU protocol. Up to 32 devices can be connected on a RS-485 bus. The overall length of the RS-485 cable connecting all devices should not exceed 1200m.
If the master station does not have a RS-485 communications port, a RS-232/RS-485 or USB/RS-485 converter with optically isolated outputs and surge protection should be used. The following figure illustrates the RS-485 connections on the PMC-T402.
Figure 2-11 RS-485 Connections
2.5 Digital Output Wiring
The following figure illustrates the Digital Output connections on the PMC-T402:
Figure 2-12 DO Connections
2.6 Residual Current Input Wiring
The following figures illustrate the Residual Current Input connection on the PMC-T402 and typical wiring with a 3P4W system, respectively:
Figure 2-13 Residual Current Input Connections
Notes:
1) The Residual Current terminals (either IR11 or IR12) should be left open and should not be connected to ground if unused. Otherwise, doing so would damage the device.
14
Page 15
2) The alarming feature of the Residual Current measurement is disabled by default and can be enabled via the Front Panel or through communications.
3) Please ensure that the device power is OFF when connecting the Residual Current CT.
2.7 RTD Input Wiring
The following figure illustrates the Temperature Input connections on the PMC-T402:
Figure 2-14 Temperature Input Connections
Notes:
1) The alarming feature of the Temperature measurement is disabled by default and can be enabled via the Front Panel or through communications.
2) Please ensure that the device power is OFF when connecting the RTD.
2.8 Power Supply Wiring
The following figure illustrates the Power Supply connections on the PMC-T402:
Figure 2-15 Power Supply Connections
15
Page 16
LED Indicator
Color
Description
Run
Green
Blinking when the system is running normally
IR1~IR4
TC1~TC4
Green
Lit if the corresponding IRn or TCn measurement or Alarm/Fault event is displayed
Warn
Red
Lit if any measurement has breached the Warning Setpoint Limit
Alarm
Red
Lit if any measurement has breached its Alarm Setpoint Limit
Mute
Green
Lit if the activated buzzer is muted (by pressing < /Mute> button)
Comm.
Green
Blinking when communicating
mA/°C/s
Green
Lit to display the present measurement unit
Buttons
Data Display Mode
Setup Configuration Mode
Alarm/Fault Mode
< /Diag.>
Pressing this button scrolls to the next available parameter or menu item.
If the selected parameters is a numeric value, pressing this button moves the cursor to the left by one position. Once the cursor has reached the left most digit, pressing this button returns to the first digit.
Pressing this button queries other Fault or Alarm events under the event display screen.
< /Mute>
Pressing this button scrolls to the previous available parameter or menu item.
If the selected parameter is
a numeric value, pressing this button increments the selected digit. Once the number reaches to 9, pressing this button again will become to 0.
If the selected parameter is
an enumerated value, pressing this button scrolls through the enumerated
When the buzzer is
active due to an Alarm or a Fault, pressing this button for one second mutes the sound.
Under an Alarm event
screen, pressing this button switches to the Fault event screen.
Chapter 3 Front Panel
The PMC-T402 has a bright 2-line LED display and 4 buttons for both data display and setup configuration purposes.
Figure 3-1 Front Panel Display
3.1 LED Indicator
There are 17 LED indicators on the PMC-T402’s front panel as described below:
Table 3-1 LED Indicators
3.2 Buttons
16
Page 17
list.
< /Enter>
This button is ignored in the Data Display mode.
Pressing this button for
three seconds toggles between Data Display mode and Setup Configuration Mode.
Once inside the Setup
Configuration mode, pressing this button selects a parameter for modification. After changing the parameter, pressing this button again saves the new setting into memory.
This button is ignored in the Alarm/Fault Mode.
< /Esc>
Pressing this button returns to the previous menu level.
Press this button to discard the changes or cancel the current operation.
Pressing this button for three seconds to reset the Alarm and Fault.
Label
Description
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
Y
0
1
2
3
4
5
6
7
8
9
Table 3-2 Buttons Description
3.3 LED Display
3.3.1 LED Display Symbols
The following table shows the special LED display symbols:
3.3.2 LED Testing
Pressing < /Diag.> button for one second enters the LED Testing mode. During testing, all LED segments and indicators are illuminated for 1 second. This cycle will repeat 6 times to allow for the detection of faulty LED segments or indicators. In addition, the Alarm Buzzer will sound for 3 seconds first and then short sound for 3 times during illumination LED segments and indicators. The LED will return to its normal display mode afterwards.
3.3.3 Default Display
The PMC-T402 has a Default Display that shows the IR1 and IR2 parameters as shown below. The user can use the < /Diag.> and < /Mute>> buttons to scroll and display other parameters. Please refer to Section 3.2 above for a complete description of the front panel and button operations.
Table 3-3 LED Display Segments
17
Page 18
Menu
Display screens
Measurements
IRn
Display 1
IR1
IR2
Display 2
IR3
IR4
TCn
Display 1
TC1
TC2
Display 2
TC3
TC4
DO
Display 1
DO Status
Figure 3-2 Default Display
3.3.4 Data Display
The following table illustrates the available measurements under the Data Display Mode.
Table 3-4 PMC-T402 Data Display Pages
3.3.5 SOE Display
The PMC-T402 can display Alarm/Fault events on its LED. The users can scroll the display screens by pressing < /Diag.> button. When there is an Alarm or a Fault event:
The Front Panel displays the Alarm/Fault channel and the detailed information The Alarm buzzer would sound The correspond IRn/TCn LED indicator and Alarm/Fault indicator would be lit
The Alarm event has a higher priority than the Fault event. Users can press < /Mute> button to switch to the Fault event screen. Once there is no more Alarm or Fault event, the display will return to the Default Display screen automatically. In addition, users can query other Fault or Alarm events by pressing < /Diag.> under an event screen.
Examples of Event Log Display:
IRn/TCn Alarm Events:
Figure 3-3 IRn/TCn Alarm Events
18
Page 19
IRn/TCn Fault Events:
Figure 3-4 IRn/TCn Fault Events
3.4 Setup Configuration
3.4.1 Making Setup Changes
1) Entering the Password: Press < /Enter> for three seconds to enter Setup Configuration mode, and the LED displays
PROG.
Press < /Diag.> to advance to the Password page. A correct password must be entered before changes are allowed. The factory default password is
“0000”.
Press< /Diag.> to shift the cursor to the left by one position and press < /Mute> to increment
the numeric value for the password.
When the password has been entered, pressing < /Diag.> or < /Mute> advances to the setup
menu if the password is correct.
2) Selecting a parameter to change:
Press < /Diag.>or < /Mute> to scroll to the desired sub-menu or parameter. Press < /Enter> to select the sub-menu or parameter. Once a parameter has been selected, its
value will blink.
3) Changing and saving a setup parameter:
For a Numeric parameter, press < /Diag.> to shift the cursor to the left by one position. Press <
/Mute> to increment the numeric value
For an Enumerated parameter, press < /Mute> to scroll through the enumerated list. After modification, press < /Enter> to save the change into memory or < /Esc> to exit the
currently selected parameter without change.
Repeat step 3) until all setup parameters have been changed.
4) Exiting the Setup Mode
Press < /Enter> for three seconds to return to the Display Mode. Also, the Setup Mode will be automatically exited if there is a period of inactivity of 5 minutes or
longer.
19
Page 20
3.4.2 Setup Menu
Figure 3-5 Setup Menu
20
Page 21
Label
Description
Range
Default
Menu
Main Sub
PROG
Setup Configuration
/
/
PASS
Enter Password
0 to 9999
0
COM1 Set Comm. Parameters
Yes/No Id
Set Unit ID
1 to 247
100
FP
Set Setpoint Parameters
Yes/No
IRn
Set IRn Alarm parameters (n=1, 2, 3, 4)
SEL
IRn Alarm Setpoint
0=OFF
1=DO Alarm
2=No DO Alarm
0
VAL
IRn Alarm Limit
20 to 1000 mA
500
dLY
IRn Alarm Time Delay
5s
PSEL
IRn Warning Setpoint
0=OFF
1=DO Warning
2=No DO Warning
0
rAIo
IRn Warning Level Ratio
0.1 to 0.8
0.6
PdLY
IRn Warning Time Delay
5s
TCn
Set TCn Alarm parameters (n=1, 2, 3, 4)
SEL
TCn Alarm Setpoint
0=OFF
1= DO Alarm
2=No DO Alarm
0
VAL
TCn Alarm Limit
45 to 140°C
100°C
dLY
TCn Alarm Time Delay
0s
PSEL
TCn Warning Setpoint
0=OFF
1=DO Warning
2=No DO Warning
0
rAIo
TCn Warning Level
0.1 to 0.8
0.6
PdLY
TCn Warning Time Delay
0s
DO
Set DO parameter
do
DO pulse width
0 to 6000 (x0.1) s
1.0s
RES FP
Set other Alarm parameters
TCCP
Enable RTD Compensation2
0=OFF
1=ON 1 TCTH
Temperature threshold3
0 to 45°C
0°C
IRTH
Residual Current threshold3
10 to 500mA
20mA
dT
Set Clock
D Enter the Current Date
YY-MM-DD / T
Enter the Current Time
HH:MM:SS
/
MT
PASS SET
Set New Password
nEW
Enter New Password
0 to 9999
0
SoE ALM SoE
Display Alarm events
FAIL SoE
Display Fault events
MT SoE
Display Maintenance events
Clr SoE
Clear SOE
Yes/No
InFo
View Device Information (Read Only)
Yes/No
V
Firmware Version
For example, 1.00.00
means the firmware
version is V1.10.00.
/
Pro
Protocol Version
e.g. 1.0 means V1.0 / d
Firmware Update Date
e.g. 20160915
/
3.4.3 Configuration
The Setup Configuration mode provides access to the following setup parameters:
Notes:
1) The PMC-T402 only supports the configuration of Unit ID for its Com port. The default settings
for Baud Rate and Data Format are 9600 bps and 8E1, respectively and cannot be changed from the Front Panel.
2) In general, the RTD sensor comes standard with a 3m wire, and the wiring resistance may lead to
a relatively large error, it is recommended that the RTD Sensor Compensation be used to reduce
Table 3-5 Setup Parameters
21
Page 22
the error if the length of the wire exceeds 3m.
3) When the measurements of the Residual Current or Temperature are less than the Residual
Current or Temperature Threshold, the measurements will be displayed as 0.
22
Page 23
Setup Parameter
Definition
Default
IRn Alarm Setpoint
OFF / DO Alarm / No DO Alarm
OFF
Alarm Limit
20 to 2000mA
500mA
Time Delay
0 to 20s
5s
Active Condition
I
residual
Alarm Limit
Inactive Condition
I
residual
< 0.9 * Alarm Limit
Alarm Trigger
SOE, Alarm Buzzer, LED and/or DO
Setup Parameter
Definition
Default
IRn Warning Setpoint
OFF / DO Warning / No DO Warning
OFF
Warning Level
0.1 ~ 0.8
0.6
Time Delay
0 to 20s
5s
Active Condition
I
residual
Alarm Limit * Warning Level
Inactive Condition
I
residual
< 0.9 * [Alarm Limit * Warning Level]
Warning Trigger
SOE, Alarm Buzzer, LED and/or DO
Chapter 4 Applications
4.1 Condition Monitoring
PMC-T402 provides intelligent condition monitoring of Residual Current and Temperature through external Residual CTs and PT100 Temperature Probes. It can determine if the sensors are working normally, the setpoint limits have been breached or if the wires of the sensors are broken. The device can be configured to generate an alarm using the on-board buzzer and activate the Digital Output for external control when a measurement exceeds the pre-set alarm limit. In addition, a SOE Event would be generated.
4.1.1 Residual Current Monitoring
The PMC-T402 supports up to four Residual Current Inputs and provides two Setpoint levels between 20 and 1000mA: Warning and Alarm. If the Residual Current measurements exceed the pre-set limits, the Residual Current Setpoint will become active. The monitoring of Residual Current provides an indication of the amount of Leakage Current existing in the electrical system as a result of degraded insulation or poor wiring and acts as an early warning system to alert users of potential safety hazards as well as the health of the electrical system.
The PMC-T402’s Residual Current inputs are required to be paired with CET’s PMC-MIR series of Residual CT. Please refer to Section 2.2.3 and Appendix A for their dimensions and specifications.
Residual Current Setpoint parameters can be programmed via the Front Panel or through communications:
Table 4-1 Residual Current Alarm Setpoint Parameters
Table 4-2 Residual Current Warning Setpoint Parameters
The following figures illustrate the logic diagrams of the Residual Current Alarm and Warning.
Figure 4-1 Residual Current Alarm Logic Diagram
23
Page 24
Setup Parameter
Definition
Default
TCn Alarm Setpoint
OFF / DO Alarm / No DO Alarm
OFF
Alarm Limit
45 to 140 °C
100 °C
Time Delay
5s
Active Condition
Temperature Alarm Limit
Inactive Condition
Temperature < 0.9 * Alarm Limit
Alarm Trigger
SOE, Alarm Buzzer, LED and/or DO
Setup Parameter
Definition
Default
TCn Warning Setpoint
OFF / DO Warning DO / No DO Warning
OFF
Warning Level
0.1 ~ 0.8
0.6
Time Delay
5s
Active Condition
Temperature Alarm Limit * Warning Level
Inactive Condition
Temperature < 0.9*[Alarm Limit * Warning Level]
Warning Trigger
SOE, Alarm Buzzer, LED and/or DO
Figure 4-2 Residual Current Warning Logic Diagram
Notes:
1) The IRn Alarm or Warning must return to Normal first before a new Alarm or Warning would be generated.
4.1.2 Temperature Alarm
The PMC-T402 supports up to four PT100 Temperature Inputs and provides two Setpoint levels between 45 and 140°C: Warning and Alarm. If the temperature measurements exceed the pre-set alarm limit, the Temperature Setpoint will become active. The PMC-T402’s Temperature inputs provide a way to monitor the temperature condition of a certain piece of equipment and acts as an early warning system to alert users of potential safety hazards as a result of over-heating.
The PMT-T402’s Temperature inputs are required to be pared with external 2-wire PT100 sensors, please refer to Section 2.2.4 and Appendix A for its dimensions and specifications.
The Temperature Setpoint parameters can be programmed via the Front Panel or through the communications:
Table 4-3 Temperature Alarm Setpoint Parameters
Table 4-4 Temperature Warning Setpoint Parameters
The following figures illustrate the logic diagrams of the Temperature Alarm and Warning.
Figure 4-3 Temperature Alarm Logic Diagram
24
Page 25
Figure 4-4 Temperature Warning Logic Diagram
Notes:
1) The TCn Alarm or Warning must return to Normal first before a new Alarm or Warning would be generate.
4.2 Digital Output
The PMC-T402 comes standard with one Form A mechanical DO (3A @ 250VAC or 30VDC). Digital Outputs are normally used for Alarm Output or Remote Control applications.
1) Alarm Output The Residual Current Alarm and Temperature Alarm Setpoint can
be configured to trigger DO actions in response to the Residual Current Alarm or Temperature Alarm becoming active. Please refer to Section 4.1.1 and 4.1.2 for a detailed description.
2) Remote Control Remotely operated over communications via our free PMC Setup
software or PecStar® iEMS Integrated Energy Management System.
The Remote Control has a higher priority than the Alarm Output, meaning that even if the DO has been configured to operate in response to an Alarm, it may still be overridden for remote control operation.
4.3 SOE Log
The PMC-T402 has a SOE Log that can store up to 64 events such as Power-On, Alarm, DO action and Setup changes …etc. in its non-volatile memory. Each event record includes an Event Classification, its relevant parameter values and a timestamp in ±1 ms resolution.
All events can be retrieved via the Front Panel or through communications. If there are more than 64 events, the newest event will replace the oldest event on a First-In-First-Out basis. The SOE Log can be reset from the Front Panel or via communications.
25
Page 26
Format
Description
UINT16/INT16
Unsigned/Signed 16-bit Integer
UINT32/INT32
Unsigned/Signed 32-bit Integer
Float
IEEE 754 32-bit
Single Precision Floating Point Number
Register
Property
Description
Format
Scale
Unit
40000
RO
SOE Pointer
1
UINT32
40002
RO
I
residual
Self-Diagnostic Status
2
UINT16
40003
RO
Temp. Self-Diagnostic Status
3
UINT16
40004
RO
I
residual
Alarm Status4
UINT16
40005
RO
I
residual
Warning Status
5
UINT16
40006
RO
Temp. Alarm Status
6
UINT16
40007
RO
Temp. Warning Status
7
UINT16
40008
RO
Reserved
UINT16
40009
RO
Reserved
UINT16
40010
RO
Global Fault/Alarm Status8
UINT16
40011
RO
DO Status9
UINT16
40012
RO
IR1 (RMS)10
UINT16
x10
mA
40013
RO
IR2 (RMS)10
UINT16
40014
RO
IR3 (RMS)10
UINT16
40015
RO
IR4 (RMS)10
UINT16
40016
RO
TC1
10
INT16
x10
°C
40017
RO
TC210
INT16
40018
RO
TC310
INT16
40019
RO
TC410
INT16
40020
RO
IR1 (Fundamental)
UINT16
x10
mA
40021
RO
IR2 (Fundamental)
UINT16
40022
RO
IR3 (Fundamental)
UINT16
40023
RO
IR4 (Fundamental)
UINT16
Chapter 5 Modbus Register Map
This chapter provides a complete description of the Modbus register map (Protocol Version 1.1) for the PMC-T402 to facilitate the development of 3rd party communications driver for accessing information on the PMC-T402. For a complete Modbus Protocol Specification, please visit http://www.modbus.org. The PMC-T402 supports the following Modbus functions:
1) Read Holding Registers (Function Code 0x03)
2) Force Single Coil (Function Code 0x05)
3) Preset Multiple Registers (Function Code 0x10)
The following table provides a description of the different data formats used for the Modbus registers:
5.1 Basic Measurements
Notes:
1) The range of the SOE Log Pointer is between 0 and 0xFFFFFFFF, and it is incremented by one for
every new log generated and will roll over to 0 if its current value is 0xFFFFFFFF. A value of zero indicates that the SOE does not contain any Log. If a Clear SOE Log is performed via the Front Panel or through communications, the SOE Log Pointer will be reset to zero.
Use the following equation to determine the latest log location:
Latest Log Location = Modulo [SOE Log Pointer / Log Depth]
2) For the I
residual
the external CT for IR1 to IR4, respectively, with “0” meaning Normal and “1” meaning Abnormal.
3) For the Temp. Self-Diagnostic Status register, the bit values of B0 to B3 represent the status of
the external Temperature Probe for TC1 to TC4, respectively, with “0” meaning Normal and “1” meaning Abnormal.
Table 5-1 Basic Measurements
Where SOE Log Depth = 64 (fixed)
Self-Diagnostic Status register, the bit values of B0 to B3 represent the status of
26
Page 27
Bit3
Bit2
Bit1
Bit0
IRn Warning
IRn Alarm
RTD Probe Fault
Residual CT Fault
Bit15
Bit14
Bit13~Bit6
Bit5
Bit4
Global Alarm
Global Fault
Reserved
TCn Warning
TCn Alarm
Register
Property
Description
Format
52000~52007
RO
Event 1
See Table 5-4 SOE Log Data
Structure
52008~52015
RO
Event 2
52016~52023
RO
Event 3
52024~52031
RO
Event 4
52032~52039
RO
Event 5
52040~52047
RO
Event 6
52048~52055
RO
Event 7
52504~52511
RO
Event 64
Offset
Property
Description
Unit
+0
RO
Log Position
0 to 63
+1
RO
High-order Byte: Event Classification2
RO
Low-order Byte: Sub-Classification2
+2
RO
Record Time: Year
0-99 (Year-2000)
RO
Record Time: Month
1 to 12
+3
RO
Record Time: Day
1 to 31
RO
Record Time: Hour
0 to 23
+4
RO
Record Time: Minute
0 to 59
RO
Record Time: Second
0 to 59
+5
RO
Record Time: Millisecond
0 to 999
+6
RO
Event Value2-Low-order Byte
+7
RO
Event Value2-High-order Byte
-
4) For the I
Alarm Status register, the bit values of B0 to B3 represent the Alarm Status of IR1
residual
to IR4, respectively, with “1” meaning Active and “0” meaning Inactive.
5) For the I
Warning Status register, the bit values of B0 to B3 represent the Warning Status of
residual
IR1 to IR4, respectively, with “1” meaning Active and “0” meaning Inactive.
6) For the Temp. Alarm Status register, the bit values of B0 to B3 represent the Alarm Status of TC1
to TC4, respectively, with “1” meaning Active and “0” meaning Inactive.
7) For the Temp. Warning Status register, the bit values of B0 to B3 represent the Warning Status of
TC1 to TC4, respectively, with “1” meaning Active and “0” meaning Inactive.
8) The table below illustrates the bit values of the Global Fault/Alarm Status register, where “1”
means Active and “0” means Inactive.
Table 5-2 Global Fault/Alarm Status Register
Bit 0/Bit 1/Bit 2/Bit 3/Bit 4/Bit 5 = 1 if there is any Residual CT/RTD Probe Fault, IRn or TCn
Alarm/Warning. Bit14 (Global Fault) = 1 if there is either an I
or Temperature Fault.
residual
Bit 15 (Global Alarm) = 1 if there is either an IRn or TCn Alarm/Warning.
9) For the DO Status register, the bit value of B0 represents the status of DO, with “1” meaning
Active (Closed) and “0” meaning Inactive (Open).
10) If the Residual CT or RTD Probe is detected as Fault, the corresponding IRn RMS or TCn register’s
reading is 0x7FFF.
5.2 SOE Log
The SOE Log Pointer points to the register address within the SOE Log where the next event will be stored. The following formula is used to determine the register address of the most recent SOE event referenced by the SOE Log Pointer value:
Register Address = 52000 + Modulo(SOE Log Pointer-1/64)*8
Table 5-3 SOE Log
Notes:
1) SOE Log Data Structure
Table 5-4 SOE Log Data Structure
27
Page 28
2) SOE Classification
Register
Property
Description
Format
Range, Default*
51000
RW
Alarm Buzzer
UINT16
0 = Disabled
1 = Intermittent*
2 = Continuous
51001
RW
Fault Buzzer
UINT16
0 = Disabled
1 = Intermittent*
2 = Continuous
51002
RW
Alarm Reset Mode
UINT16
0 = Manual*, 1 = Auto
51003
RW
RTD Probe Compensation
UINT16
0 = Disabled, 1 = Enabled*
51004
RW
Temp. Threshold
UINT16
0 to 45°C, 0°C*
51005
RW
I
residual
Threshold
UINT16
10 to 500 mA, 20 mA*
51006
RW
DO Pulse Width
UINT16
0 to 6000 (0.1s), 1.0s*
0=Latch Mode
51007
RW
Reserved
UINT16
-
51008
RW
IRn Alarm Setpoint
UINT16
0 = IRn RMS*
1 = IRn Fundamental
51009
RW
Reserved
UINT16 - 51010
RW
IR1 Setpoint
UINT16
See Note 1), 0*
51011
RW
IR1 Alarm Limit
UINT16
20 to 1000 mA, 500 mA*
51012
RW
IR1 Alarm Time Delay
UINT16
0 to 20s, 5s*
51013
RW
IR1 Warning Level
UINT16
0.1 to 0.8, 0.6*
Event
Classification
Sub-
Classification
Event Value
Description
1 1
Reserved
2
Reserved
3
1/0
DO Operated/Released
2
1
Triggered
Value
TC1 Alarm
2
TC2 Alarm
3
TC3 Alarm
4
TC4 Alarm
5
IR1 Alarm
6
IR2 Alarm
7
IR3 Alarm
8
IR4 Alarm
9
Reserved
10
TC1 Warning
11
TC2 Warning
12
TC3 Warning
13
TC4 Warning
14
IR1 Warning
15
IR2 Warning
16
IR3 Warning
17
IR4 Warning
18~19
Reserved
20 0 TC1 RTD Probe Fault
21 0 TC2 RTD Probe Fault
22 0 TC3 RTD Probe Fault
23 0 TC4 RTD Probe Fault
24 0 IR1 Residual CT Fault
25 0 IR2 Residual CT Fault
26 0 IR3 Residual CT Fault
27 0 IR4 Residual CT Fault
3 1 0 System Parameter Fault
2 0 Calibration Parameter Fault
3
0
Ferroelectric Fault
4
0
AD Fault
4
1 0 Setup Changed via Communication
2 0 Clear SOE via Communication
3
0
Power On
4 0 Setup Changed via Front Panel
5 0 Clear SOE via the Front Panel
Table 5-5 SOE Classification
5.3 Device Setup
28
Page 29
51014
RW
IR1 Warning Delay
UINT16
0 to 20s, 5s*
51015
RW
IR2 Setpoint
UINT16
See Note 1), 0*
51016
RW
IR2 Alarm Limit
UINT16
20 to 1000 mA, 500mA*
51017
RW
IR2 Alarm Time Delay
UINT16
0 to 20s, 5s*
51018
RW
IR2 Warning Level
UINT16
0.1 to 0.8, 0.6*
51019
RW
IR2 Warning Time Delay
UINT16
0 to 20s, 5s*
51020
RW
IR3 Setpoint
UINT16
See Note 1), 0*
51021
RW
IR3 Alarm Limit
UINT16
20 to 1000 mA, 500 mA*
51022
RW
IR3 Alarm Time Delay
UINT16
0 to 20s, 5s*
51023
RW
IR3 Warning Level
UINT16
0.1 to 0.8, 0.6*
51024
RW
IR3 Warning Time Delay
UINT16
0 to 20s, 5s*
51025
RW
IR4 Setpoint
UINT16
See Note 1), 0*
51026
RW
IR4 Alarm Limit
UINT16
20 to 1000 mA, 500 mA*
51027
RW
IR4 Alarm Time Delay
UINT16
0 to 20s, 5s*
51028
RW
IR4 Warning Level
UINT16
0.1 to 0.8, 0.6*
51029
RW
IR4 Warning Time Delay
UINT16
0 to 20s, 5s*
51030
RW
TC1 Setpoint
UINT16
See Note 1), 0*
51031
RW
TC1 Alarm Limit
UINT16
45 to 140 °C, 100°C*
51032
RW
TC1 Alarm Time Delay
UINT16
0 to 40s, 0s*
51033
RW
TC1 Warning Level
UINT16
0.1 to 0.8, 0.6*
51034
RW
TC1 Warning Time Delay
UINT16
0 to 40s, 0s*
51035
RW
TC2 Setpoint
UINT16
See Note 1), 0*
51036
RW
TC2 Alarm Limit
UINT16
45 to 140 °C, 100°C*
51037
RW
TC2 Alarm Time Delay
UINT16
0 to 40s, 0s*
51038
RW
TC2 Warning Level
UINT16
0.1 to 0.8, 0.6*
51039
RW
TC2 Warning Time Delay
UINT16
0 to 40s, 0s*
51040
RW
TC3 Setpoint
UINT16
See Note 1), 0*
51041
RW
TC3 Alarm Limit
UINT16
45 to 140 °C, 100°C*
51042
RW
TC3 Alarm Time Delay
UINT16
0 to 40s, 0s*
51043
RW
TC3 Warning Level
UINT16
0.1 to 0.8, 0.6*
51044
RW
TC3 Warning Time Delay
UINT16
0 to 40s, 0s*
51045
RW
TC4 Setpoint
UINT16
See Note 1), 0*
51046
RW
TC4 Alarm Limit
UINT16
45 to 140 °C, 100°C*
51047
RW
TC4 Alarm Time Delay
UINT16
0 to 40s, 0s*
51048
RW
TC4 Warning Level
UINT16
0.1 to 0.8, 0.6*
51049
RW
TC4 Warning Time Delay
UINT16
0 to 40s, 0s*
51050~51120
RW
Reserved
UINT16 51121
RW
Unit ID
UINT16
1 to 247, 100*
51122
RW
Baud Rate1
UINT16
0=9600*, 1=19200
51123
RW
Comm. Config.
UINT16
0=8N2, 1=8O1, 2=8E1*
3=8N1, 4=8O2, 5=8E2
Bit15~Bit4
Bit3~Bit2
Bit1~Bit0
Reserved
00: OFF
01: DO Warning
10: No DO Warning
00: OFF
01: DO Alarm
10: No DO Alarm
Register
Property
Description
Format
Note
60000
RW
High-order Byte: Year
UINT16
0-37 (Year-2000)
Low-order Byte: Month
1 to 12
60001
RW
High-order Byte: Day
UINT16
1 to 31
Table 5-5 Basic Setup Parameters
Notes:
1) The following table illustrates the IRn/TCn Setpoint Register:
Table 5-6 IRn/TCn Setpoint Register
5.4 Time
There is one set of Time registers supported by the PMC-T402 – Year / Month / Day / Hour / Minute / Second (Register # 60000 to 60002). All registers within a Time register set must be written in a single transaction. Writing to the Millisecond register (60003) is optional during a Time Set operation. When broadcasting time, the function code must be set to 0x10 (Pre-set Multiple Registers). Incorrect date or time values will be rejected by the device. In addition, attempting to write a Time value less than Jan 1, 2000 00:00:00 will be rejected.
29
Page 30
Low-order Byte: Hour
0 to 23
60002
RW
High-order Byte: Minute
UINT16
0 to 59
Low-order Byte: Second
0 to 59
60003
RW
Millisecond
UINT16
0 to 999
Register
Property
Description
Format
Note
60064
WO
Arm DO Close
UINT16
Writing “0xFF00”
to the register to
perform the
described action.
60065
WO
Execute DO Close
UINT16
60066
WO
Arm DO Open
UINT16
60067
WO
Execute DO Open
UINT16
60068~60124
WO
Reserved
UINT16
60125
WO
Buzzer Mute
UINT16
60126
WO
System Self-Diagnostic
UINT16
60127
WO
Clear SOE
UINT16
60128
WO
Arm Reset Alarm & Fault Register
UINT16
60129
WO
Execute Reset Alarm & Fault Register
UINT16
Register
Property
Description
Format
Note
60200~60219
RO
Device model1
UINT16
See Note 1
60220
RO
Firmware Version
UINT16
e.g. 10000 shows the
version is V1.00.00
60221
RO
Protocol Version
UINT16
e.g. 10 shows the
version is V1.0
60222
RO
Firmware Date: Year-2000
UINT16
e.g. 160110 means
January 10, 2016
60223
RO
Firmware Date: Month
UINT16
60224
RO
Firmware Date: Day
UINT16
60225
RO
Serial Number
UINT32
60227-60228
RO
Reserved
UINT16 60229
RO
Feature Code
UINT16
0: 4xIR+4xTC
Register
Value(Hex)
ASCII
60200
0x0050
P
60201
0x004D
M
60202
0x0043
C
60203
0x002D
-
60204
0x0054
T
60205
0x0034
4
60206
0x0030
0
60207
0x0032
2
60208-60219
0x20
Null
Table 5-8 Time Registers
5.5 Remote Control
Before executing an Open, Close or Reset command on a target register, it must be “Armed” first. This is achieved by writing the value 0xFF00 to the appropriate register to “Arm” a particular Open, Close
or Reset operation. The Open, Close or Reset will be “Disarmed” automatically if an “Execute” command is not received within 15 seconds after it has been “Armed”. If an “Execute” command is received without first having received an “Arm” command, the PMC-T402 ignores the “Execute” command and returns the 0x04 exception code.
Table 5-9 DO Control
5.6 Device Information
Table 5-10 Device Information
Notes:
1) The Device Model appears in registers 60200 to 60219 and contains the ASCII encoding of the
string “PMC-T402” as shown in the following table.
Table 5-11 ASCII Encoding of “PMC-T402
30
Page 31
Appendix A Technical Specifications
RTD Temperature Inputs (TC1, TC2, TC3, TC4)
RTD Type PT100 Alarm Range
2-Wire PT100 (sensor not included) 0-200°C 45-140°C
Residual Current Inputs (IR1, IR2, IR3, IR4)
Standard (In) Range
0.5mA 2-200% In
Power Supply (L/+, N/-, GND)
Standard Burden Frequency
95-250VAC/DC, ±10%, 47-440Hz <1.5W 50Hz/60Hz
Digital Output
Type Loading
Form A Mechanical Relay 3A @ 250VAC or 30VDC
Communications
Type Baud Rate Communication Format Protocol
RS-485 9600bps 8E1 (8 Data Bits, Even Parity, 1 Stop Bit) Modbus RTU
Setpoint Range
Residual Current Temperature
20-1000mA in 1mA resolution 45-140°C in 1°C resolution
Buzzer
Decibel
70dB (measured at 1m range)
Installation Torque
Power Supply Terminals
0.6 N.m
Other Terminals
0.4 N.m
Environmental conditions
Operating Temperature Storage Temperature Humidity Atmospheric Pressure Pollution Degree
-25°C to +70°C
-40°C to +85°C 5% to 95% non-condensing 70 kPa to 106 kPa II
Mechanical Characteristics
Mounting Unit Dimensions IP Rating
Panel or DIN Rail 72(L)×72(H)×87.8(D) mm 30
Residual Current CT (not included)
Load Current (Solid Core)
Load Current (Split Core)
Primary Input (Residual) Secondary Output Range Overload Accuracy Frequency Dielectric Strength Operating Temperature Storage Temperature
160A (PMC-MIR-46, Ø=46mm) 400A (PMC-MIR-80, Ø=80mm) 630A (PMC-MIR-220x50, 220x50mm) 1000A (PMC-MIR-120, Ø=120mm) 160A (CT553203, Ø=48mm) 225A (CT553303, Ø=68mm) 1A
0.5mA 2-200% 44A Class 0.5 (Solid Core), Class 3 (Split Core) 50 / 60Hz 3kV rms @ 1 minute
-25 ~ +70°C(Solid Core), -12 ~ +45°C(Split Core)
-40 ~ +85°C(Solid Core), -25 ~ +70°C(Split Core)
RTD Temperature Sensor (not included)
Type Range Accuracy Cable Length Protective Tube Length
2-Wire PT100
-50°C to 200°C IEC 60751 Class B 3m, 5m or 8m 300mm
Parameters
Measurement Range
Accuracy
Resolution
Residual Current
20 - 2000mA
±1%
0.1mA
Temperature
0 - 200°C
±1°C
0.1°C
Accuracy
31
Page 32
Appendix B Standards of Compliance
Safety Requirements
CE LVD 2014 / 35 / EU
EN 61010-1: 2010 EN 61010-2-030: 2010
Insulation Dielectric test Insulation resistance Impulse voltage
IEC 60255-5-2000 2kV @ 1 minute >100MΩ 5kV, 1.2/50µs
Electromagnetic Compatibility
Immunity Tests
Electrostatic Discharge
IEC 61000-4-2:2001 Level III
Radiated Fields
IEC 61000-4-3:2006 Level (10V/m)
Fast Transients
IEC 61000-4-4:2004 Level III
Surges
IEC 61000-4-5:2005 Level III
Conducted Disturbances
IEC 61000-4-6:1995 Level III
Magnetic Fields
IEC 61000-4-8:2001 Level IV
Oscillatory Waves
IEC 61000-4-12:1995 Level III
Mechanical Tests
Vibration Test Response
IEC 60255-21-1:1998 Level I
Endurance
IEC 60255-21-1:1998 Level I
Shock Test Response
IEC 60255-21-1:1998 Level I
Endurance
IEC 60255-21-1:1998 Level I
Bump Test
IEC 62052-11: 2003 Level I
32
Page 33
Appendix C Ordering Guide
33
Page 34
Contact us
CET Inc. 8/F, Westside, Building 201, Terra Industrial & Tradepark, Che Gong Miao, Shenzhen, Guangdong, P.R.China 518040 Tel: +86.755.8341.5187 Fax: +86.755.8341.0291 Email: support@cet-global.com Web: www.cet-global.com
34
Loading...