This manual may not be reproduced in whole or in part by any means without the express
written permission from CET Electric Technology (CET).
The information contained in this manual is believed to be accurate at the time of publication;
however, CET assumes no responsibility for any errors which may appear here and reserves
the right to make changes without notice. Please consult CET or your local representative for
the latest product specifications.
DANGER
This symbol indicates the presence of danger that may result in severe injury or death and
permanent equipment damage if proper precautions are not taken during the installation,
operation or maintenance of the device.
CAUTION
This symbol indicates the potential of personal injury or equipment damage if proper
precautions are not taken during the installation, operation or maintenance of the device.
2
Page 3
Installation, operation and maintenance of the device should only be
performed by qualified, competent personnel that have the appropriate
training and experience with high voltage and current devices. The device must
Ensure that all incoming AC power and other power sources are turned OFF
Before connecting the device to the power source, check the label on top of
the device to ensure that it is equipped with the appropriate power supply, and
During normal operation of the device, hazardous voltages are present on its
terminal strips and throughout the connected potential transformers (PT) and
current transformers (CT). PT and CT secondary circuits are capable of
generating lethal voltages and currents with their primary circuits energized.
Follow standard safety precautions while performing any installation or service
Do not use the device for primary protection functions where failure of the
device can cause fire, injury or death. The device should only be used for
Under no circumstances should the device be connected to a power source if
To prevent potential fire or shock hazard, do not expose the device to rain or
Setup procedures must be performed only by qualified personnel familiar with
DANGER
Failure to observe the following instructions may result in severe injury or
death and/or equipment damage.
be installed in accordance with all local and national electrical codes.
before performing any work on the device.
the correct voltage and current input specifications for your application.
CET Inc.
work (i.e. removing PT fuses, shorting CT secondaries, …etc).
shadow protection if needed.
it is damaged.
moisture.
the instrument and its associated electrical equipment.
DO NOT open the instrument under any circumstances.
3
Page 4
CET Inc.
Limited warranty
CET offers the customer a minimum of 12-month functional warranty on the
device for faulty parts or workmanship from the date of dispatch from the
CET does not accept liability for any damage caused by device malfunctions. CET
accepts no responsibility for the suitability of the device to the application for
Failure to install, set up or operate the device according to the instructions herein
Only CET’s duly authorized representative may open your device. The unit should
only be opened in a fully anti-static environment. Failure to do so may damage
distributor. This warranty is on a return to factory for repair basis.
which it was purchased.
will void the warranty.
the electronic components and will void the warranty.
Appendix A Technical Specifications .................................................................................................. 31
Appendix B Standards of Compliance ................................................................................................ 32
Appendix C Ordering Guide ............................................................................................................... 33
Contact us ......................................................................................................................................... 34
6
Page 7
CET Inc.
Chapter 1 Introduction
This manual explains how to use the PMC-T402 Temperature & Iresidual Monitor.
This chapter provides an overview of the PMC-T402 and summarizes many of its key features.
1.1 Overview
The PMC-T402 is CET’s latest offer for the Temperature (RTD) and Residual Current monitoring for the
Commercial and Industrial markets. Housed in a compact form factor measuring only
72(L)×72(H)×87.8(D)mm, the PMC-T402 can be used as a stand-alone device that offers real-time
monitoring and alarming of Residual Current and Temperature with its LED display, Front Panel buttons,
1xDO for Alarm Output or General Purpose Control and a built-in Alarm Buzzer. With the standard RS485 port and Modbus RTU protocol support, the PMC-T402 becomes a vital component of an
intelligent, centralized Condition Monitoring.
Intelligent Electrical Fire and Condition Monitoring for Industrial or Commercial facilities
Industrial and Commercial Electrical Power System
AC Low Voltage Distribution System
Condition monitoring of electrical equipment
1.2 Features
Ease of use
Bright 2-line LED display with high visibility for Temperature and Residual Current measurements
LED Indicators for Run, Fault, Warning, Alarm, Comm. Activities, Measurement Channel and Unit
indicators
Built-in Alarm Buzzer
Password-protected setup via front panel or free PMC Setup software
Panel or DIN Rail (with adapter) Mount
Support Firmware Upgrade over Communications
Residual Current Measurement
4 channels Residual Current Input (CT not included)
Two Setpoint Alarm Levels between 20 and 1000mA
Temperature Measurement
4 channels RTD Input (PT100 sensor not included)
Two Setpoint Alarm levels between 45°C and 140°C
SOE Log
64 events time-stamped to ±1ms resolution
Setup changes, Setpoint Alarms, Power Reset …etc.
Digital Output
1 Form A mechanical DO (3A @ 250VAC or 30VDC)
Can be used for Alarm Output or General Purpose Control
Communications
7
Page 8
CET Inc.
1xRS-485 port @ 9600bps, 8E1
Modbus RTU protocol
1.3 Getting more information
Additional information is available from CET via the following sources:
Visit www.cet-global.com
Contact your local representative
Contact CET directly via email at support@cet-global.com
8
Page 9
CET Inc.
Installation of the PMC-T402 should only be performed by qualified, competent personnel
that have the appropriate training and experience with high voltage and current devices.
During the operation of the monitor, hazardous voltages are present at the input terminals.
Failure to observe precautions can result in serious or even fatal injury and equipment
damage.
Chapter 2 Installation
Caution
The monitor must be installed in accordance with all local and national electrical codes.
2.1 Appearance
Figure 2-1 Appearance
9
Page 10
2.2 Dimensions
2.2.1 Main Unit
CET Inc.
2.2.2 Terminal
Figure 2-2 Main Unit Dimensions
Figure 2-3 Terminal Dimensions
10
Page 11
Terminal
Terminal Dimension (mm)
Wire Size (mm2)
Max. Torque
1
DO & RS-485
2.5 x 2.8
1.5
4.5 kgf.cm/M2.5
(3.9 lb-in)
2
TCn
3
IRn
4
Power Supply
6.0 x 6.0
1.0mm2 - 2.5mm2
(14AWG - 22AWG)
6.0 kgf.cm/M3
(5.2 lb-in)
2.2.3Residual Current CTs
PMC-MIR-46 (160A, Ø=46mm)
CET Inc.
Table 2-1 Terminal Dimensions
Figure 2-4 PMC-MIR-46 Dimensions
PMC-MIR-80 (400A, Ø=80mm)
Figure 2-5 PMC-MIR-80 Dimensions
11
Page 12
PMC-MIR-120 (1000A, Ø=120mm)
CET Inc.
Figure 2-6 PMC-MIR-120 Dimensions
PMC-MIR-220x50 (630A, 220x50mm)
Figure 2-7 PMC-MIR-220x50 Dimensions
2.2.4PT100
Figure 2-8 PT100 Dimensions
2.3 Mounting
The PMC-T402 should be installed in a dry environment with no dust and kept away from heat,
radiation and electrical noise source. The PMC-T402 supports two installation modes: Panel mount
and DIN-Rail mount.
Panel Installation steps:
o Remove the installation clips from the PMC-T402
o Fit the PMC-T402 through a 68mm x 68mm cutout as shown in Figure 2-9
o Re-install the installation clips and push the clips tightly against the panel to secure the PMC-
T402
12
Page 13
CET Inc.
Figure 2-9 Panel Installation
DIN-Rail Installation steps:
o Before installation, please make sure that the DIN rail and the adapter are already in place.
o Remove the installation clips from the PMC-T402
o Fit the PMC-T402 through the adapter as shown in Figure 2-10
o Re-install the installation clips and push the clips tightly against the adapter to secure the
PMC-T402
Figure 2-10 DIN-Rail Installation
13
Page 14
CET Inc.
2.4 RS-485 Wiring
The PMC-T402 provides a standard RS-485 port that supports the Modbus RTU protocol. Up to 32
devices can be connected on a RS-485 bus. The overall length of the RS-485 cable connecting all
devices should not exceed 1200m.
If the master station does not have a RS-485 communications port, a RS-232/RS-485 or USB/RS-485
converter with optically isolated outputs and surge protection should be used. The following figure
illustrates the RS-485 connections on the PMC-T402.
Figure 2-11 RS-485 Connections
2.5 Digital Output Wiring
The following figure illustrates the Digital Output connections on the PMC-T402:
Figure 2-12 DO Connections
2.6 Residual Current Input Wiring
The following figures illustrate the Residual Current Input connection on the PMC-T402 and typical
wiring with a 3P4W system, respectively:
Figure 2-13 Residual Current Input Connections
Notes:
1) The Residual Current terminals (either IR11 or IR12) should be left open and should not be connected to ground if unused.
Otherwise, doing so would damage the device.
14
Page 15
CET Inc.
2) The alarming feature of the Residual Current measurement is disabled by default and can be enabled via the Front Panel or
through communications.
3) Please ensure that the device power is OFF when connecting the Residual Current CT.
2.7 RTD Input Wiring
The following figure illustrates the Temperature Input connections on the PMC-T402:
Figure 2-14 Temperature Input Connections
Notes:
1) The alarming feature of the Temperature measurement is disabled by default and can be enabled via the Front Panel or
through communications.
2) Please ensure that the device power is OFF when connecting the RTD.
2.8 Power Supply Wiring
The following figure illustrates the Power Supply connections on the PMC-T402:
Figure 2-15 Power Supply Connections
15
Page 16
CET Inc.
LED Indicator
Color
Description
Run
Green
Blinking when the system is running normally
IR1~IR4
TC1~TC4
Green
Lit if the corresponding IRn or TCn measurement or Alarm/Fault event is
displayed
Warn
Red
Lit if any measurement has breached the Warning Setpoint Limit
Alarm
Red
Lit if any measurement has breached its Alarm Setpoint Limit
Mute
Green
Lit if the activated buzzer is muted (by pressing < /Mute> button)
Comm.
Green
Blinking when communicating
mA/°C/s
Green
Lit to display the present measurement unit
Buttons
Data Display Mode
Setup Configuration Mode
Alarm/Fault Mode
</Diag.>
Pressing this button
scrolls to the next
available parameter
or menu item.
If the selected parameters is a
numeric value, pressing this
button moves the cursor to
the left by one position. Once
the cursor has reached the
left most digit, pressing this
button returns to the first
digit.
Pressing this button
queries other Fault or
Alarm events under the
event display screen.
< /Mute>
Pressing this button
scrolls to the
previous available
parameter or menu
item.
If the selected parameter is
a numeric value, pressing
this button increments the
selected digit. Once the
number reaches to 9,
pressing this button again
will become to 0.
If the selected parameter is
an enumerated value,
pressing this button scrolls
through the enumerated
When the buzzer is
active due to an Alarm
or a Fault, pressing this
button for one second
mutes the sound.
Under an Alarm event
screen, pressing this
button switches to the
Fault event screen.
Chapter 3 Front Panel
The PMC-T402 has a bright 2-line LED display and 4 buttons for both data display and setup
configuration purposes.
Figure 3-1 Front Panel Display
3.1 LED Indicator
There are 17 LED indicators on the PMC-T402’s front panel as described below:
Table 3-1 LED Indicators
3.2 Buttons
16
Page 17
CET Inc.
list.
</Enter>
This button is
ignored in the Data
Display mode.
Pressing this button for
three seconds toggles
between Data Display mode
and Setup Configuration
Mode.
Once inside the Setup
Configuration mode,
pressing this button selects
a parameter for
modification. After
changing the parameter,
pressing this button again
saves the new setting into
memory.
This button is ignored in
the Alarm/Fault Mode.
</Esc>
Pressing this button
returns to the
previous menu
level.
Press this button to discard
the changes or cancel the
current operation.
Pressing this button for
three seconds to reset the
Alarm and Fault.
Label
Description
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
Y
0
1
2
3
4
5
6
7
8
9
Table 3-2 Buttons Description
3.3 LED Display
3.3.1 LED Display Symbols
The following table shows the special LED display symbols:
3.3.2 LED Testing
Pressing </Diag.> button for one second enters the LED Testing mode. During testing, all LED
segments and indicators are illuminated for 1 second. This cycle will repeat 6 times to allow for the
detection of faulty LED segments or indicators. In addition, the Alarm Buzzer will sound for 3 seconds
first and then short sound for 3 times during illumination LED segments and indicators. The LED will
return to its normal display mode afterwards.
3.3.3 Default Display
The PMC-T402 has a Default Display that shows the IR1 and IR2 parameters as shown below. The user
can use the </Diag.> and < /Mute>> buttons to scroll and display other parameters. Please refer
to Section 3.2 above for a complete description of the front panel and button operations.
Table 3-3 LED Display Segments
17
Page 18
CET Inc.
Menu
Display screens
Measurements
IRn
Display 1
IR1
IR2
Display 2
IR3
IR4
TCn
Display 1
TC1
TC2
Display 2
TC3
TC4
DO
Display 1
DO Status
Figure 3-2 Default Display
3.3.4 Data Display
The following table illustrates the available measurements under the Data Display Mode.
Table 3-4 PMC-T402 Data Display Pages
3.3.5 SOE Display
The PMC-T402 can display Alarm/Fault events on its LED. The users can scroll the display screens by
pressing </Diag.> button. When there is an Alarm or a Fault event:
The Front Panel displays the Alarm/Fault channel and the detailed information
The Alarm buzzer would sound
The correspond IRn/TCn LED indicator and Alarm/Fault indicator would be lit
The Alarm event has a higher priority than the Fault event. Users can press < /Mute> button to switch
to the Fault event screen. Once there is no more Alarm or Fault event, the display will return to the
Default Display screen automatically. In addition, users can query other Fault or Alarm events by
pressing </Diag.> under an event screen.
Examples of Event Log Display:
IRn/TCn Alarm Events:
Figure 3-3 IRn/TCn Alarm Events
18
Page 19
CET Inc.
IRn/TCn Fault Events:
Figure 3-4 IRn/TCn Fault Events
3.4 Setup Configuration
3.4.1 Making Setup Changes
1) Entering the Password: Press </Enter> for three seconds to enter Setup Configuration mode, and the LED displays
PROG.
Press </Diag.> to advance to the Password page.
A correct password must be entered before changes are allowed. The factory default password is
“0000”.
Press</Diag.> to shift the cursor to the left by one position and press < /Mute>to increment
the numeric value for the password.
When the password has been entered, pressing </Diag.>or < /Mute>advances to the setup
menu if the password is correct.
2) Selecting a parameter to change:
Press </Diag.>or < /Mute> to scroll to the desired sub-menu or parameter.
Press </Enter> to select the sub-menu or parameter. Once a parameter has been selected, its
value will blink.
3) Changing and saving a setup parameter:
For a Numeric parameter, press </Diag.> to shift the cursor to the left by one position. Press <
/Mute> to increment the numeric value
For an Enumerated parameter, press < /Mute> to scroll through the enumerated list.
After modification, press </Enter> to save the change into memory or </Esc> to exit the
currently selected parameter without change.
Repeat step 3) until all setup parameters have been changed.
4) Exiting the Setup Mode
Press </Enter> for three seconds to return to the Display Mode.
Also, the Setup Mode will be automatically exited if there is a period of inactivity of 5 minutes or
longer.
19
Page 20
3.4.2 Setup Menu
CET Inc.
Figure 3-5 Setup Menu
20
Page 21
CET Inc.
Label
Description
Range
Default
Menu
Main Sub
PROG
Setup Configuration
/
/
PASS
Enter Password
0 to 9999
0
COM1 Set Comm. Parameters
Yes/No Id
Set Unit ID
1 to 247
100
FP
Set Setpoint Parameters
Yes/No
IRn
Set IRn Alarm parameters (n=1, 2, 3, 4)
SEL
IRn Alarm Setpoint
0=OFF
1=DO Alarm
2=No DO Alarm
0
VAL
IRn Alarm Limit
20 to 1000 mA
500
dLY
IRn Alarm Time Delay
0 to 20s
5s
PSEL
IRn Warning Setpoint
0=OFF
1=DO Warning
2=No DO Warning
0
rAIo
IRn Warning Level Ratio
0.1 to 0.8
0.6
PdLY
IRn Warning Time Delay
0 to 20s
5s
TCn
Set TCn Alarm parameters (n=1, 2, 3, 4)
SEL
TCn Alarm Setpoint
0=OFF
1= DO Alarm
2=No DO Alarm
0
VAL
TCn Alarm Limit
45 to 140°C
100°C
dLY
TCn Alarm Time Delay
0 to 40s
0s
PSEL
TCn Warning Setpoint
0=OFF
1=DO Warning
2=No DO Warning
0
rAIo
TCn Warning Level
0.1 to 0.8
0.6
PdLY
TCn Warning Time Delay
0 to 40s
0s
DO
Set DO parameter
do
DO pulse width
0 to 6000 (x0.1) s
1.0s
RES FP
Set other Alarm parameters
TCCP
Enable RTD Compensation2
0=OFF
1=ON 1 TCTH
Temperature threshold3
0 to 45°C
0°C
IRTH
Residual Current threshold3
10 to 500mA
20mA
dT
Set Clock
D Enter the Current Date
YY-MM-DD / T
Enter the Current Time
HH:MM:SS
/
MT
PASS SET
Set New Password
nEW
Enter New Password
0 to 9999
0
SoE ALM SoE
Display Alarm events
FAIL SoE
Display Fault events
MT SoE
Display Maintenance events
Clr SoE
Clear SOE
Yes/No
InFo
View Device Information (Read Only)
Yes/No
V
Firmware Version
For example, 1.00.00
means the firmware
version is V1.10.00.
/
Pro
Protocol Version
e.g. 1.0 means V1.0 / d
Firmware Update Date
e.g. 20160915
/
3.4.3 Configuration
The Setup Configuration mode provides access to the following setup parameters:
Notes:
1) The PMC-T402 only supports the configuration of Unit ID for its Com port. The default settings
for Baud Rate and Data Format are 9600 bps and 8E1, respectively and cannot be changed from
the Front Panel.
2) In general, the RTD sensor comes standard with a 3m wire, and the wiring resistance may lead to
a relatively large error, it is recommended that the RTD Sensor Compensation be used to reduce
Table 3-5 Setup Parameters
21
Page 22
CET Inc.
the error if the length of the wire exceeds 3m.
3) When the measurements of the Residual Current or Temperature are less than the Residual
Current or Temperature Threshold, the measurements will be displayed as 0.
22
Page 23
CET Inc.
Setup Parameter
Definition
Default
IRn Alarm Setpoint
OFF / DO Alarm / No DO Alarm
OFF
Alarm Limit
20 to 2000mA
500mA
Time Delay
0 to 20s
5s
Active Condition
I
residual
≥ Alarm Limit
Inactive Condition
I
residual
< 0.9 * Alarm Limit
Alarm Trigger
SOE, Alarm Buzzer, LED and/or DO
Setup Parameter
Definition
Default
IRn Warning Setpoint
OFF / DO Warning / No DO Warning
OFF
Warning Level
0.1 ~ 0.8
0.6
Time Delay
0 to 20s
5s
Active Condition
I
residual
≥ Alarm Limit * Warning Level
Inactive Condition
I
residual
< 0.9 * [Alarm Limit * Warning Level]
Warning Trigger
SOE, Alarm Buzzer, LED and/or DO
Chapter 4 Applications
4.1 Condition Monitoring
PMC-T402 provides intelligent condition monitoring of Residual Current and Temperature through
external Residual CTs and PT100 Temperature Probes. It can determine if the sensors are working
normally, the setpoint limits have been breached or if the wires of the sensors are broken. The device
can be configured to generate an alarm using the on-board buzzer and activate the Digital Output for
external control when a measurement exceeds the pre-set alarm limit. In addition, a SOE Event would
be generated.
4.1.1 Residual Current Monitoring
The PMC-T402 supports up to four Residual Current Inputs and provides two Setpoint levels between
20 and 1000mA: Warning and Alarm. If the Residual Current measurements exceed the pre-set limits,
the Residual Current Setpoint will become active. The monitoring of Residual Current provides an
indication of the amount of Leakage Current existing in the electrical system as a result of degraded
insulation or poor wiring and acts as an early warning system to alert users of potential safety hazards
as well as the health of the electrical system.
The PMC-T402’s Residual Current inputs are required to be paired with CET’s PMC-MIR series of
Residual CT. Please refer to Section2.2.3 and Appendix A for their dimensions and specifications.
Residual Current Setpoint parameters can be programmed via the Front Panel or through
communications:
Table 4-1 Residual Current Alarm Setpoint Parameters
Table 4-2 Residual Current Warning Setpoint Parameters
The following figures illustrate the logic diagrams of the Residual Current Alarm and Warning.
Figure 4-1 Residual Current Alarm Logic Diagram
23
Page 24
CET Inc.
Setup Parameter
Definition
Default
TCn Alarm Setpoint
OFF / DO Alarm / No DO Alarm
OFF
Alarm Limit
45 to 140 °C
100 °C
Time Delay
0 to 40s
5s
Active Condition
Temperature≥ Alarm Limit
Inactive Condition
Temperature< 0.9 * Alarm Limit
Alarm Trigger
SOE, Alarm Buzzer, LED and/or DO
Setup Parameter
Definition
Default
TCn Warning Setpoint
OFF / DO Warning DO / No DO Warning
OFF
Warning Level
0.1 ~ 0.8
0.6
Time Delay
0 to 40s
5s
Active Condition
Temperature ≥ Alarm Limit * Warning Level
Inactive Condition
Temperature< 0.9*[Alarm Limit * Warning Level]
Warning Trigger
SOE, Alarm Buzzer, LED and/or DO
Figure 4-2 Residual Current Warning Logic Diagram
Notes:
1) The IRn Alarm or Warning must return to Normal first before a new Alarm or Warning would be generated.
4.1.2 Temperature Alarm
The PMC-T402 supports up to four PT100 Temperature Inputs and provides two Setpoint levels
between 45 and 140°C: Warning and Alarm. If the temperature measurements exceed the pre-set
alarm limit, the Temperature Setpoint will become active. The PMC-T402’s Temperature inputs provide
a way to monitor the temperature condition of a certain piece of equipment and acts as an early
warning system to alert users of potential safety hazards as a result of over-heating.
The PMT-T402’s Temperature inputs are required to be pared with external 2-wire PT100 sensors,
please refer to Section 2.2.4 and Appendix A for its dimensions and specifications.
The Temperature Setpoint parameters can be programmed via the Front Panel or through the
communications:
Table 4-3 Temperature Alarm Setpoint Parameters
Table 4-4 Temperature Warning Setpoint Parameters
The following figures illustrate the logic diagrams of the Temperature Alarm and Warning.
Figure 4-3 Temperature Alarm Logic Diagram
24
Page 25
CET Inc.
Figure 4-4 Temperature Warning Logic Diagram
Notes:
1) The TCn Alarm or Warning must return to Normal first before a new Alarm or Warning would be generate.
4.2 Digital Output
The PMC-T402 comes standard with one Form A mechanical DO (3A @ 250VAC or 30VDC). Digital
Outputs are normally used for Alarm Output or Remote Control applications.
1) Alarm Output The Residual Current Alarm and Temperature Alarm Setpoint can
be configured to trigger DO actions in response to the Residual
Current Alarm or Temperature Alarm becoming active. Please
refer to Section 4.1.1 and 4.1.2 for a detailed description.
2) Remote Control Remotely operated over communications via our free PMC Setup
software or PecStar® iEMS Integrated Energy Management
System.
The Remote Control has a higher priority than the Alarm Output, meaning that even if the DO has been
configured to operate in response to an Alarm, it may still be overridden for remote control operation.
4.3 SOE Log
The PMC-T402 has a SOE Log that can store up to 64 events such as Power-On, Alarm, DO action and
Setup changes …etc. in its non-volatile memory. Each event record includes an Event Classification, its
relevant parameter values and a timestamp in ±1 ms resolution.
All events can be retrieved via the Front Panel or through communications. If there are more than 64
events, the newest event will replace the oldest event on a First-In-First-Out basis. The SOE Log can be
reset from the Front Panel or via communications.
25
Page 26
CET Inc.
Format
Description
UINT16/INT16
Unsigned/Signed 16-bit Integer
UINT32/INT32
Unsigned/Signed 32-bit Integer
Float
IEEE 754 32-bit
Single Precision Floating Point Number
Register
Property
Description
Format
Scale
Unit
40000
RO
SOE Pointer
1
UINT32
40002
RO
I
residual
Self-Diagnostic Status
2
UINT16
40003
RO
Temp. Self-Diagnostic Status
3
UINT16
40004
RO
I
residual
Alarm Status4
UINT16
40005
RO
I
residual
Warning Status
5
UINT16
40006
RO
Temp. Alarm Status
6
UINT16
40007
RO
Temp. Warning Status
7
UINT16
40008
RO
Reserved
UINT16
40009
RO
Reserved
UINT16
40010
RO
Global Fault/Alarm Status8
UINT16
40011
RO
DO Status9
UINT16
40012
RO
IR1 (RMS)10
UINT16
x10
mA
40013
RO
IR2 (RMS)10
UINT16
40014
RO
IR3 (RMS)10
UINT16
40015
RO
IR4 (RMS)10
UINT16
40016
RO
TC1
10
INT16
x10
°C
40017
RO
TC210
INT16
40018
RO
TC310
INT16
40019
RO
TC410
INT16
40020
RO
IR1 (Fundamental)
UINT16
x10
mA
40021
RO
IR2 (Fundamental)
UINT16
40022
RO
IR3 (Fundamental)
UINT16
40023
RO
IR4 (Fundamental)
UINT16
Chapter 5 Modbus Register Map
This chapter provides a complete description of the Modbus register map (Protocol Version 1.1) for
the PMC-T402 to facilitate the development of 3rd party communications driver for accessing
information on the PMC-T402. For a complete Modbus Protocol Specification, please visit
http://www.modbus.org. The PMC-T402 supports the following Modbus functions:
1) Read Holding Registers (Function Code 0x03)
2) Force Single Coil (Function Code 0x05)
3) Preset Multiple Registers (Function Code 0x10)
The following table provides a description of the different data formats used for the Modbus registers:
5.1 Basic Measurements
Notes:
1) The range of the SOELog Pointer is between 0 and 0xFFFFFFFF, and it is incremented by one for
every new log generated and will roll over to 0 if its current value is 0xFFFFFFFF. A value of zero
indicates that the SOE does not contain any Log. If a Clear SOE Log is performed via the Front
Panel or through communications, the SOELog Pointer will be reset to zero.
Use the following equation to determine the latest log location:
the external CT for IR1 to IR4, respectively, with “0” meaning Normal and “1” meaning
Abnormal.
3) For the Temp. Self-Diagnostic Status register, the bit values of B0 to B3 represent the status of
the external Temperature Probe for TC1 to TC4, respectively, with “0” meaning Normal and “1”
meaning Abnormal.
Table 5-1 Basic Measurements
Where SOE Log Depth = 64 (fixed)
Self-Diagnostic Status register, the bit values of B0 to B3 represent the status of
26
Page 27
CET Inc.
Bit3
Bit2
Bit1
Bit0
IRn Warning
IRn Alarm
RTD Probe Fault
Residual CT Fault
Bit15
Bit14
Bit13~Bit6
Bit5
Bit4
Global Alarm
Global Fault
Reserved
TCn Warning
TCn Alarm
Register
Property
Description
Format
52000~52007
RO
Event 1
See Table 5-4
SOE Log Data
Structure
52008~52015
RO
Event 2
52016~52023
RO
Event 3
52024~52031
RO
Event 4
52032~52039
RO
Event 5
52040~52047
RO
Event 6
52048~52055
RO
Event 7
…
…
52504~52511
RO
Event 64
Offset
Property
Description
Unit
+0
RO
Log Position
0 to 63
+1
RO
High-order Byte: Event Classification2
RO
Low-order Byte: Sub-Classification2
+2
RO
Record Time: Year
0-99 (Year-2000)
RO
Record Time: Month
1 to 12
+3
RO
Record Time: Day
1 to 31
RO
Record Time: Hour
0 to 23
+4
RO
Record Time: Minute
0 to 59
RO
Record Time: Second
0 to 59
+5
RO
Record Time: Millisecond
0 to 999
+6
RO
Event Value2-Low-order Byte
+7
RO
Event Value2-High-order Byte
-
4) For the I
Alarm Status register, the bit values of B0 to B3 represent the Alarm Status of IR1
residual
to IR4, respectively, with “1” meaning Active and “0” meaning Inactive.
5) For the I
Warning Status register, the bit values of B0 to B3 represent the Warning Status of
residual
IR1 to IR4, respectively, with “1” meaning Active and “0” meaning Inactive.
6) For the Temp. Alarm Status register, the bit values of B0 to B3 represent the Alarm Status of TC1
to TC4, respectively, with “1” meaning Active and “0” meaning Inactive.
7) For the Temp. Warning Status register, the bit values of B0 to B3 represent the Warning Status of
TC1 to TC4, respectively, with “1” meaning Active and “0” meaning Inactive.
8) The table below illustrates the bit values of the GlobalFault/Alarm Status register, where “1”
means Active and “0” means Inactive.
Table 5-2 Global Fault/Alarm Status Register
Bit 0/Bit 1/Bit 2/Bit 3/Bit 4/Bit 5 = 1 if there is any Residual CT/RTD Probe Fault, IRn or TCn
Alarm/Warning.
Bit14 (Global Fault) = 1 if there is either an I
or Temperature Fault.
residual
Bit 15 (Global Alarm) = 1 if there is either an IRn or TCn Alarm/Warning.
9) For the DO Status register, the bit value of B0 represents the status of DO, with “1” meaning
Active (Closed) and “0” meaning Inactive (Open).
10) If the Residual CT or RTD Probe is detected as Fault, the corresponding IRn RMS or TCn register’s
reading is 0x7FFF.
5.2 SOE Log
The SOE Log Pointer points to the register address within the SOE Log where the next event will be
stored. The following formula is used to determine the register address of the most recent SOE event
referenced by the SOE Log Pointer value:
1) The following table illustrates the IRn/TCn Setpoint Register:
Table 5-6 IRn/TCn Setpoint Register
5.4 Time
There is one set of Time registers supported by the PMC-T402 – Year / Month / Day / Hour / Minute /
Second (Register # 60000 to 60002). All registers within a Time register set must be written in a single
transaction. Writing to the Millisecond register (60003) is optional during a Time Set operation. When
broadcasting time, the function code must be set to 0x10 (Pre-set Multiple Registers). Incorrect date
or time values will be rejected by the device. In addition, attempting to write a Time value less than
Jan 1, 2000 00:00:00 will be rejected.
29
Page 30
CET Inc.
Low-order Byte: Hour
0 to 23
60002
RW
High-order Byte: Minute
UINT16
0 to 59
Low-order Byte: Second
0 to 59
60003
RW
Millisecond
UINT16
0 to 999
Register
Property
Description
Format
Note
60064
WO
Arm DO Close
UINT16
Writing “0xFF00”
to the register to
perform the
described action.
60065
WO
Execute DO Close
UINT16
60066
WO
Arm DO Open
UINT16
60067
WO
Execute DO Open
UINT16
60068~60124
WO
Reserved
UINT16
60125
WO
Buzzer Mute
UINT16
60126
WO
System Self-Diagnostic
UINT16
60127
WO
Clear SOE
UINT16
60128
WO
Arm Reset Alarm & Fault Register
UINT16
60129
WO
Execute Reset Alarm & Fault Register
UINT16
Register
Property
Description
Format
Note
60200~60219
RO
Device model1
UINT16
See Note 1
60220
RO
Firmware Version
UINT16
e.g. 10000 shows the
version is V1.00.00
60221
RO
Protocol Version
UINT16
e.g. 10 shows the
version is V1.0
60222
RO
Firmware Date: Year-2000
UINT16
e.g. 160110 means
January 10, 2016
60223
RO
Firmware Date: Month
UINT16
60224
RO
Firmware Date: Day
UINT16
60225
RO
Serial Number
UINT32
60227-60228
RO
Reserved
UINT16 60229
RO
Feature Code
UINT16
0: 4xIR+4xTC
Register
Value(Hex)
ASCII
60200
0x0050
P
60201
0x004D
M
60202
0x0043
C
60203
0x002D
-
60204
0x0054
T
60205
0x0034
4
60206
0x0030
0
60207
0x0032
2
60208-60219
0x20
Null
Table 5-8 Time Registers
5.5 Remote Control
Before executing an Open, Close or Reset command on a target register, it must be “Armed” first. This
is achieved by writing the value 0xFF00 to the appropriate register to “Arm” a particular Open, Close
or Reset operation. The Open, Close or Reset will be “Disarmed” automatically if an “Execute”
command is not received within 15 seconds after it has been “Armed”. If an “Execute” command is received without first having received an “Arm” command, the PMC-T402 ignores the “Execute”
command and returns the 0x04 exception code.
Table 5-9 DO Control
5.6 Device Information
Table 5-10 Device Information
Notes:
1) The Device Model appears in registers 60200 to 60219 and contains the ASCII encoding of the
string “PMC-T402” as shown in the following table.
Table 5-11 ASCII Encoding of “PMC-T402”
30
Page 31
Appendix A Technical Specifications
RTD Temperature Inputs (TC1, TC2, TC3, TC4)
RTD Type
PT100
Alarm Range
2-Wire PT100 (sensor not included)
0-200°C
45-140°C
Residual Current Inputs (IR1, IR2, IR3, IR4)
Standard (In)
Range
0.5mA
2-200% In
Power Supply (L/+, N/-, GND)
Standard
Burden
Frequency
95-250VAC/DC, ±10%, 47-440Hz
<1.5W
50Hz/60Hz
Digital Output
Type
Loading
Form A Mechanical Relay
3A @ 250VAC or 30VDC
Communications
Type
Baud Rate
Communication Format
Protocol
RS-485
9600bps
8E1 (8 Data Bits, Even Parity, 1 Stop Bit)
Modbus RTU
Setpoint Range
Residual Current
Temperature
20-1000mA in 1mA resolution
45-140°C in 1°C resolution
Buzzer
Decibel
70dB (measured at 1m range)
Installation Torque
Power Supply Terminals
0.6 N.m
Other Terminals
0.4 N.m
Environmental conditions
Operating Temperature
Storage Temperature
Humidity
Atmospheric Pressure
Pollution Degree
-25°C to +70°C
-40°C to +85°C
5% to 95% non-condensing
70 kPa to 106 kPa
II
Mechanical Characteristics
Mounting
Unit Dimensions
IP Rating
Panel or DIN Rail
72(L)×72(H)×87.8(D) mm
30
Residual Current CT (not included)
Load Current (Solid Core)
Load Current (Split Core)
Primary Input (Residual)
Secondary Output
Range
Overload
Accuracy
Frequency
Dielectric Strength
Operating Temperature
Storage Temperature
CET Inc.
8/F, Westside, Building 201, Terra Industrial & Tradepark,
Che Gong Miao, Shenzhen, Guangdong, P.R.China 518040
Tel: +86.755.8341.5187
Fax: +86.755.8341.0291
Email: support@cet-global.com
Web: www.cet-global.com
34
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.