CET PMC-680i User Manual

Page 1
PMC-680i
Advanced Power Quality Analyzer
User Manual
Version: V0.9A
October 15, 2015
This manual may not be reproduced in whole or in part by any means without the express
written permission from Ceiec Electric Technology (CET).
1
Page 2
Ceiec Electric Technology
The information contained in this Manual is believed to be accurate at the time of
publication; however, CET assumes no responsibility for any errors which may appear here
and reserves the right to make changes without notice. Please consult CET or your local
representative for latest product specifications.
Standards Compliance
DANGER
This symbol indicates the presence of danger that may result in severe injury or death and
permanent equipment damage if proper precautions are not taken during the installation,
operation or maintenance of the device.
CAUTION
This symbol indicates the potential of personal injury or equipment damage if proper precautions are not taken during the installation, operation or maintenance of the device.
2
Page 3
Ceiec Electric Technology
and the correct voltage and current input specifications for your application.
generating lethal voltages and currents with their primary circuits energized.
with the instrument and its associated electrical equipment.
DANGER
Failure to observe the following instructions may result in severe injury or
death and/or equipment damage.
Installation, operation and maintenance of the meter should only be
performed by qualified, competent personnel that have the appropriate
training and experience with high voltage and current devices. The meter
must be installed in accordance with all local and national electrical codes.
Ensure that all incoming AC power and other power sources are turned OFF
before performing any work on the meter.
Before connecting the meter to the power source, check the label on top of
the meter to ensure that it is equipped with the appropriate power supply,
During normal operation of the meter, hazardous voltages are present on its
terminal strips and throughout the connected potential transformers (PT)
and current transformers (CT). PT and CT secondary circuits are capable of
Follow standard safety precautions while performing any installation or
service work (i.e. removing PT fuses, shorting CT secondaries, etc.).
Do not use the meter for primary protection functions where failure of the
device can cause fire, injury or death. The meter should only be used for
shadow protection if needed.
Under no circumstances should the meter be connected to a power source if
it is damaged.
To prevent potential fire or shock hazard, do not expose the meter to rain or
moisture.
Setup procedures must be performed only by qualified personnel familiar
3
Page 4
Ceiec Electric Technology
Limited warranty
Ceiec Electric Technology (CET) offers the customer a minimum of 12-month
functional warranty on the meter for faulty parts or workmanship from the
date of dispatch from the distributor. This warranty is on a return to factory
for repair basis.
CET does not accept liability for any damage caused by meter malfunctions.
CET accepts no responsibility for the suitability of the meter to the application
for which it was purchased.
Failure to install, set up or operate the meter according to the instructions
herein will void the warranty.
Only CET’s duly authorized representative may open your meter. The unit
should only be opened in a fully anti-static environment. Failure to do so may
damage the electronic components and will void the warranty.
4
Page 5
Ceiec Electric Technology

Table of Contents

Table of Contents ............................................................................................................................... 5
Glossary ........................................................................................................................................... 10
Chapter 1 Introduction .................................................................................................................... 11
1.1 Overview .................................................................................................................................. 11
1.2 Features ................................................................................................................................... 12
1.3 PMC-680i’ application in Power and Energy Management and Analyzer Systems ................. 19
1.4 Getting more information ........................................................................................................ 20
Chapter 2 Installation ...................................................................................................................... 21
2.1 Appearance .............................................................................................................................. 21
2.2 Unit Dimensions ....................................................................................................................... 23
2.3 Mounting ................................................................................................................................. 23
2.4 Wiring Connections .................................................................................................................. 24
2.4.1 3-phase 4-wire Wye Direct Connection ....................................................................... 25
2.4.2 3-phase 4-wire Wye with 3PTs and 4CTs ..................................................................... 25
2.4.3 3-phase 3-wire Grounded Wye Direct Connection ...................................................... 26
2.4.4 3-phase 3-wire Grounded Wye with 3PTs and 3CTs .................................................... 26
2.4.5 3-phase 3-wire Grounded Delta Connection ............................................................... 27
2.4.6 3-phase 3-wire Delta with 2PTs and 3CTs .................................................................... 27
2.4.7 3-phase 3-wire Delta with 2PTs and 2CTs .................................................................... 28
2.5 Communications Wiring .......................................................................................................... 28
2.5.1 Ethernet Port (10/100BaseT) ....................................................................................... 28
2.5.2 RS485 Port .................................................................................................................... 29
2.6 Digital Input Wiring .................................................................................................................. 29
2.7 GPS 1PPS Input wiring .............................................................................................................. 30
2.8 Digital Output Wiring ............................................................................................................... 30
2.9 RO Wiring ................................................................................................................................. 30
2.10 Pulse Output Wiring ............................................................................................................... 31
Chapter 3 User Interface .................................................................................................................. 32
5
2.11 Power Supply Wiring .............................................................................................................. 31
2.12 Chassis Ground Wiring ........................................................................................................... 31
3.1 Front Panel Interface ............................................................................................................... 32
3.1.1 Display Hierarchy and Menu Tree ................................................................................ 32
3.1.2 Navigating the Front Panel User Interface ................................................................... 34
Page 6
Ceiec Electric Technology
3.2 Web Interface .......................................................................................................................... 44
3.2.1 Setting PC's IP Address ................................................................................................. 45
3.2.2 Configure PMC-680i's IP Addresses ............................................................................. 45
3.2.3 Enabling Java Scripting in Google Chrome ................................................................... 46
3.2.4 Web Interface .............................................................................................................. 47
Chapter 4 Applications ..................................................................................................................... 67
4.1 Inputs and Outputs .................................................................................................................. 67
4.1.1 Digital Inputs ................................................................................................................ 67
4.1.2 Relay Outputs and Digital Outputs............................................................................... 69
4.1.3 Energy Pulse Outputs ................................................................................................... 71
4.2 Power, Energy and Demand .................................................................................................... 72
4.2.1 Basic Measurements .................................................................................................... 72
4.2.2 Energy Measurements ................................................................................................. 73
4.2.3 Demands ...................................................................................................................... 73
4.2.4 Time of Use (TOU) ........................................................................................................ 76
4.3 Setpoints .................................................................................................................................. 78
4.4 Power Quality Parameters ....................................................................................................... 81
4.4.1 Power Frequency ......................................................................................................... 81
4.4.2 Magnitude of the Supply Voltage ................................................................................ 81
4.4.3 Flicker ........................................................................................................................... 81
4.4.4 Supply Voltage Dips/Swells and Interruption .............................................................. 82
4.4.5 Voltage Transients ....................................................................................................... 86
4.4.6 Supply Voltage Unbalance ........................................................................................... 86
4.4.7 Harmonics and Interharmonics .................................................................................... 87
4.4.8 Mains Signalling Voltage (MSV) ................................................................................... 89
4.4.9 Voltage Deviation ......................................................................................................... 90
4.4.10 Rapid Voltage Changes (RVC) ..................................................................................... 91
4.4.11 Inrush Current ............................................................................................................ 93
4.4.12 Flagging Concept ........................................................................................................ 96
6
4.4.13 Disturbance Direction Location .................................................................................. 97
4.4.14 EN50160 Compliance Report ..................................................................................... 97
4.4.15 Disturbance Waveform Recorder (DWR) ................................................................... 98
4.4.16 ITIC/SEMI F47 Curve ................................................................................................. 100
4.5 Data Logging .......................................................................................................................... 101
4.5.1 SOE Log and PQ Log ................................................................................................... 101
Page 7
Ceiec Electric Technology
4.5.2 Statistical Data Recorder (SDR) .................................................................................. 103
4.5.3 Data Recorder (DR) .................................................................................................... 103
4.5.4 Max./Min. Log ............................................................................................................ 104
4.5.5 Pst Log ........................................................................................................................ 105
4.5.6 Plt Log ......................................................................................................................... 105
4.5.7 Interval Energy Recorder (IER) ................................................................................... 105
4.5.8 Qualification Rate Log ................................................................................................ 107
4.5.9 Waveform Recorder (WFR) ........................................................................................ 107
4.5.10 SDR Trend ................................................................................................................. 108
4.5.11 PQDIF and COMTRADE Storage ............................................................................... 109
4.5.12 PQ Counters ............................................................................................................. 110
4.6 SMTP (Simple Mail Transfer Protocol) ................................................................................... 111
4.7 Time Synchronization ............................................................................................................ 114
4.7.1 PMC Setup .................................................................................................................. 114
4.7.2 PecStar iEMS .............................................................................................................. 115
4.7.3 SNTP (Simple Network Time Protocol)....................................................................... 115
4.7.4 Modbus ...................................................................................................................... 115
4.7.5 GPS with Time Sync Pulse .......................................................................................... 116
4.7.6 IRIG-B ......................................................................................................................... 116
4.7.7 DI with PPS ................................................................................................................. 117
Chapter 5 Modbus Register Map ................................................................................................... 118
5.1 Basic Measurements .............................................................................................................. 118
5.2 Energy Measurements ........................................................................................................... 125
5.3 DI Pulse Counter .................................................................................................................... 125
5.4 PQ Measurements ................................................................................................................. 126
5.5 Harmonics & Interharmonic Measurements ......................................................................... 129
5.5.1 Harmonic Distortion Measurements ......................................................................... 129
5.5.2 Harmonic Voltage & Current RMS ............................................................................. 131
5.5.3 Individual Total Harmonic .......................................................................................... 133
7
5.5.4 Harmonic Power ........................................................................................................ 134
5.5.5 Harmonic Angles ........................................................................................................ 135
5.5.6 Harmonic Energy ........................................................................................................ 136
5.5.7 Interharmonics Distortion (IHD) Measurements ....................................................... 137
5.5.8 Interharmonic Voltage & Current RMS ...................................................................... 139
5.6 Demand.................................................................................................................................. 141
Page 8
Ceiec Electric Technology
5.6.1 Present Demand ........................................................................................................ 141
5.6.2 Predicted Demand ..................................................................................................... 145
5.6.3 Max. Value per Demand Period ................................................................................. 147
5.6.4 Min. Value per Demand Period .................................................................................. 151
5.6.5 Present Max. .............................................................................................................. 156
5.6.6 Max. of Last Time ....................................................................................................... 156
5.7 Log Register ........................................................................................................................... 157
5.7.1 SOE Log Buffer ............................................................................................................ 157
5.7.2 PQ Log Buffer ............................................................................................................. 158
5.7.3 SDR Log ...................................................................................................................... 159
5.7.4 DR (Data Recorder) Log .............................................................................................. 161
5.7.5 MM Log (Max./Min. Log) ........................................................................................... 164
5.7.6 Pst/Plt Log .................................................................................................................. 165
5.7.7 IER (Interval Energy Recorder) Log............................................................................. 167
5.7.8 EN50160 Log .............................................................................................................. 168
5.7.9 QR (Qualification Rate) Log ........................................................................................ 180
5.7.10 TOU Log .................................................................................................................... 181
5.8 Real-time WFR Register ......................................................................................................... 183
5.9 Device Setup Parameters ....................................................................................................... 184
5.9.1 Communications Setup .............................................................................................. 184
5.9.2 Basic Setup Parameters ............................................................................................. 185
5.9.3 DI Setup ...................................................................................................................... 187
5.9.4 RO/DO Setup .............................................................................................................. 188
5.9.5 SMTP Setup ................................................................................................................ 189
5.9.6 PQ Log Setup .............................................................................................................. 190
5.9.7 PQDIF Setup ............................................................................................................... 193
5.9.8 Demand Setup............................................................................................................ 194
5.9.9 WFR Setup .................................................................................................................. 194
5.9.10 Energy Pulse Setup ................................................................................................... 195
8
5.9.11 Standard Setpoints Setup ........................................................................................ 196
5.9.12 HS (High-speed) Setpoints Setup ............................................................................. 199
5.9.13 SDR Setup ................................................................................................................. 200
5.9.14 Data Recorder (DR) Setup ........................................................................................ 241
5.9.15 High-speed (HS) DR Setup ........................................................................................ 253
5.9.16 Max./Min. Recorder (MMR) Setup .......................................................................... 257
Page 9
Ceiec Electric Technology
5.9.17 Interval Energy Recorder (IER) Setup ....................................................................... 260
5.9.18 EN50160 Setup ......................................................................................................... 261
5.9.19 QR (Qualification Rate) Log ...................................................................................... 263
5.9.20 Trend Log Setup ....................................................................................................... 264
5.9.21 TOU Setup ................................................................................................................ 264
5.9.22 System Setup............................................................................................................ 272
5.10 File Transfer Register ........................................................................................................... 274
5.10.1 File Name ................................................................................................................. 274
5.10.2 Reading File .............................................................................................................. 275
5.10.3 Register Address ...................................................................................................... 275
5.11 Control Setup ....................................................................................................................... 275
5.11.1 RO/DO Control ......................................................................................................... 275
5.11.2 Clear DI/DO .............................................................................................................. 277
5.11.3 Clear/Reset Control .................................................................................................. 278
5.12 Time Registers ...................................................................................................................... 281
5.13 Information .......................................................................................................................... 282
5.13.1 Meter Information ................................................................................................... 282
5.13.2 Device Tag Information ............................................................................................ 284
5.13.2 Circuit Tag Information ............................................................................................ 285
Appendix A - Data ID ...................................................................................................................... 286
DR and SDR Data ID ..................................................................................................................... 286
High-speed DR Data ID ................................................................................................................. 304
Demand Data ID ........................................................................................................................... 305
Appendix B – Event Classification .................................................................................................. 308
Appendix C - Technical Specifications ............................................................................................ 317
Appendix D - Accuracy Specifications ............................................................................................. 319
Appendix E - IEC61000-4-30 Class A Certificate .............................................................................. 320
Appendix F - Ordering Guide .......................................................................................................... 323
Contact us ...................................................................................................................................... 324
9
Page 10
Ceiec Electric Technology

Glossary

1PPS = 1 Pulse Per Second
CET = Ceiec Electric Technology
DI = Digital Input
DMD = Present Demand
DO = Digital Output
DR = Data Recorder
DWR = Disturbance Waveform Recorder
FIFO = First In First Out
Fund. = Fundamental
GB = Giga Byte
GPS = Global Positioning System
HS = High-Speed
Hn = nth order Harmonic, integer multiple (n) of the Fundamental Frequency (50Hz or 60Hz)
IHn = nth order Interharmonic represents all components between the (n-1)th and nth harmonic orders in
RMS
HDn = nth order Harmonic Distortion
IHDn = nth order Interharmonic Distortion
Hn = nth order Harmonic in RMS
IHn = nth order Interharmonic in RMS
LCD = Liquid Crystal Display
MB = Mega Byte
Pred_DMD = Predicted Demand
Plt = Long-term Flicker
Pst = Short-term Flicker
PQ = Power Quality
RO = Relay Output
RTC = Real Time Clock
SDR = Statistical Data Recorder
SOE = Sequence Of Events
SMTP = Simple Mail Transfer Protocol
SYNC DI = Demand Sync Input
TH = Total Harmonic in RMS, excluding Fundamental
THD = Total Harmonic Distortion
10
Page 11
Ceiec Electric Technology
TOHD = Total Odd Harmonic Distortion
TEHD = Total Even Harmonic Distortion
U0 / I0 = Zero Sequence Voltage / Current
U1 / I1 = Positive Sequence Voltage / Current
U2 / I2 = Negative Sequence Voltage /Current
U0 / I0 Unb = Zero Sequence Voltage / Current Unbalance
U2 / I2 Unb = Negative Sequence Voltage / Current Unbalance
I5 =Ground Current
WF = Waveform
WFR = Waveform Recorder
Dip = Used interchangbly with Sag
Sag = Used interchangbly with Dip
Swell = Temporary increases in RMS value of AC voltage
Transient =Unidirectional impulse of either polarity or a damped oscillatory wave with the first peak occurring in
either polarity
U
= Half-Cycle RMS Voltage
rms(1/2)
U
= Declared input voltage - Value obtained from the declared supply voltage by a transducer ratio
din
Usr = Sliding Reference Voltage
I
= Value of the RMS Current measured over each half period
half cycle rms
Dip Threshold = Voltage magnitude specified for the purpose of detecting the start and end of a voltage dip
Flagged data = For any measurement time interval in which interruptions, dips or swells occur, the measurement
results of all other parameters made during this time interval are flagged

Chapter 1 Introduction

This manual explains how to use the PMC-680i Advanced Power Quality Analyzer.
This chapter provides an overview of the PMC-680i Analyzer and summarizes many of its key features.

1.1 Overview

The PMC-680i is CET’s Advanced Utility PQ Analyzer designed for the compliance monitoring market
as it offers un-surpassed functionality by combining Class 0.2S accuracy and advanced PQ features in a
standard DIN 192 form factor with a high resolution, backlit, color TFT LCD display. The PMC-680i
complies with IEC 62053-22 Class 0.2S, IEC 61000-4-30 Class A, IEC 61000-4-7, IEC-61000-4-15 and
EN50160. Further, it offers a logging capacity with up to 8GB of on-board memory, extensive I/O
with 8xDIs, 4xRO and 4xDOs, GPS Time Sync., dual Ethernet and two RS-485 ports. These features
likely make the PMC-680i the most advanced PQ Analyzer for the Utility market today.
Typical Applications
PQ monitoring at HV, MV and LV Utility Substations
11
Page 12
Ceiec Electric Technology
Data Centers, Semiconductor Fabs, Heavy Industries
7x24 Automated Manufacturing Facilities
Dips/Swell, Transient, Flicker and Disturbance monitoring
Mains and critical feeder monitoring
Substation automation with IEC61850 protocol
Retrofit applications with Clamp-on CTs
The above are just a few of the many applications. Contact CET Technical Support should you
require further assistance with your application.

1.2 Features

Basic Features
Standard 512 samples/cycle sampling, optional 1024
4GB on-board log memory, optional 8GB
Industrial-grade, high-resolution Color TFT LCD @ 640x480
IEC 62053-22 Class 0.2S kWh metering with Multi-Tariff TOU
Time Synch. via IRIG-B, SNTP or GPS 1PPS output
256 setpoints and 16 HS (High-Speed) Setpoints
Dual 100Base T Ethernet and RS485 ports
Up to 12 months of daily backup of PQ recordings in PQDIF format
Power Quality Features
IEC 61000-4-30 Class A Certified by PSL
IEC 61000-4-7, IEC 61000-4-15 and EN50160 Reporting
Dips/Swells, Transient, Interruptions, Mains Signalling Voltage (MSV), Rapid Voltage Changes
(RVC) and In-rush Current monitoring
Disturbance Direction Indicator & Disturbance Waveform Recording
Harmonic analysis up to 63
rd
on-board and 511th via software
Fault Capture up to 2,000V peak to peak (400VAC Option)
Real-time Waveform (WF) Capture, Trending and Statistical Reporting
Waveform recording in PQDIF and COMTRADE file format that is compatible with the PQ View
software
12
Page 13
Ceiec Electric Technology
Front Panel Display
Real-time, Harmonic Power and Energy measurements
Real-time waveforms for 3-phase Voltages and Currents
Harmonic histogram
EN50160 Report
Statistical Trending
PQ Log with ITIC/SEMI F47 and waveform displays
SOE Log
I/O status
Device configuration
Diagnostics
Power Quality Metering
PQ Parameters as per IEC 61000-4-30
Power Frequency
Magnitude of the Supply Voltage
Flicker
Supply Voltage Dips and Swells
Voltage Interruptions
Transient Voltages
Supply Voltage Unbalance
Voltage Harmonics and Interharmonics
Mains Signalling Voltage (MSV) on the Supply Voltage
Rapid Voltage Changes (RVC)
Measurement of Underdeviation and Overdeviation parameters
Harmonic and Interharmonic measurements
K-Factor for Current, Crest Factor for Current and Voltage
U and I THD, TOHD, TEHD
U and I Phase and Magnitude (RMS and %HD
13
#
) from 2nd to 63rd
Page 14
Ceiec Electric Technology
U and I Interharmonics from 0 to 63
Harmonic kW, kvar, kVA and PF from 2
rd
nd
to 63rd
Fundamental U, I, kW, kvar, kVA and Displacement PF
Total harmonic kWh, kvarh Imp./Exp./Net/Total
Harmonic kWh, kvarh Imp./Exp. from 2
nd
to 63rd
Fundamental kWh, kvarh Imp./Exp./Net/Total
#
%HD can be configured as % of Fundamental, % of U/I nominal or % of RMS
Symmetrical Components and Unbalances
Zero, Positive and Negative Sequence Components
U and I Unbalance based on Zero and Negative Sequence Components
Transient and Dip/Swell Recording
Transient recording as short as 40us at 512 samples or 20us at 1024 samples @ 50Hz
Dip/Swell recording @ 10ms (½ cycle at 50Hz)
Transient triggers WFR and DWR
Dip/Swell trigger DO/RO, WFR, WDR, DR and HS DR
On-board analysis of ITIC/SEMI F47 plot and the captured waveforms
Rapid Voltage Changes
Programmable detection modes: voltage change between two steady-state or maximum voltage
change
In-rush Current Monitoring
Monitoring of the ½ cycle RMS Current and capturing of the Current waveforms associated with
events such as motor starting and transformer being energized
Disturbance Direction Indicator
Determine if a Dip Event is located upstream or downstream
Pinpoint if the cause of the event is external or internal
Disturbance Waveform Recorder (DWR)
Disturbance recording of all Voltage (Ua, Ub, Uc, U4 and U5) and Current (Ia, Ib, Ic, I4 and I5) Inputs
Initial Fault: Up to 35 cycles @ 512 samples/cycle
Extended Fault: 150 cycles @ 16 samples/cycle
14
Page 15
Ceiec Electric Technology
Steady State: 300 seconds of 1-cycle RMS recording @ 50Hz
Post Fault: Up to 15 cycles @ 512 samples/cycle
Waveform Capture (WFC) and Waveform Recorder (WFR)
Real-time WF Capture @ 128 samples/cycle via front panel display
WF Recorder with 128~ entries each
Simultaneous capture of 4-phase Voltage and 5-phase Current inputs
# of Cycles x Samples/Cycles with programmable # of pre-fault cycles
10x1024*, 20x512, 40x256
80x128, 160x64, 320x32, 640x16
Extended recording for a maximum of 7 consecutive captures
COMTRADE file format, downloadable from the on-board FTP Server
~256 entries with the 8GB option, * only available for the 1024 sampling option
PQ Event Counters
Transient, Dip, Swell, Interruption, Rapid Voltage Changes and Mains Signaling Voltage
Metering
Basic Measurements (1-second update)
3-phase Voltages (U1-U3) and U4
3-phase Currents (I1-I3), I4 and I5
3-phase Power, PF, Frequency and Phase Angles
kWh, kvarh Imp./Exp./Net/Total and kVAh Total
High-speed Measurements
3-phase Voltage and Current, U4, I4, I5 @ ½ cycle
Frequency @ 1 cycle
Demands
3-phase Voltage, Current, Power, PF, U4, I4, I5, Frequency
Demand synchronization with DI
Predicted Demands
Peak Demands for This Month and Last Month, or Before the Last Reset and Since the Last Reset
15
Page 16
Ceiec Electric Technology
Max./Min. per Demand Period
Multi-Tariff TOU capability
Two independent sets of TOU Schedules, each supporting
Up to 12 Seasons
90 Holidays or Alternate Days and 3 Weekdays
20 Daily Profiles, each with 12 Periods in 1-minute interval
8 Tariffs, each providing the following information
o kWh/kvarh Imp./Exp. and kVAh
o kW/kvar Imp./Exp. Peak Demands
o Register Rollover value at 99,999,999,999 kXh
Data, Waveform and Event Recording
Non-Volatile Log Memory
Standard 4GB, optional 8GB
Interval Energy Recorder
kWh, kvarh Imp./Exp. and kVAh Total
Support FIFO
Statistical Data Recorder
Recording of the Max., Min., Avg. and CP95 for real-time measurements including U, I, Freq.,
Flicker, Harmonics and Unbalances in 16 different recorders
Recording interval from 1 minute to 60 minutes
30 days @ 1-minute, 300 days @ 10-minute, 450-day @ 15-minute
On-board trending via Front Panel display
PQDIF file format, downloadable from the on-board FTP Server
Data Recorder and HS Data Recorder
8 Data Recorders of 32 parameters and 4 HS DR of 16 parameters
Recording interval from 1s to 40 days for Data Recorder
Recording interval from ½ cycle to 60 cycles for HS Data Recorder
Programmable sources
Recording depth fixed at 65535
16
Page 17
Ceiec Electric Technology
DR supports FIFO or Stop-When-Full mode and HS DR supports Stop-When-Full mode
Max./Min. Log
Logging of Max./Min. values for real-time measurements such as U, I, kW, kvar, kVA, PF, Freq.,
Unbalance, K-factor, THD
SOE Log
1024 FIFO events time-stamped to ±1ms resolution
Setup changes, System events, Setpoint events and I/O operations
PQ Log
1024 FIFO entries time-stamped to ±1ms resolution
Transient, Dip/Swell, Disturbance Location, Rapid Voltage Change, etc.
Record the time and characteristic data of the captured PQ event
Setpoints
PQ Setpoints
Transient trigger WFR or DWR
Dip/Swell, Rapid Voltage Changes, Inrush Current and Harmonics trigger DO/RO, DR, HS DR, WFR
or DWR
Control Setpoints
256 Control Setpoints and 16 HS Setpoints
Extensive monitoring sources
Configurable thresholds and time delays
Trigger DO, DR, HS DR, WFR or DWR
Digital Input Setpoints
Provides control output actions in response to changes in Digital Input status
Demand Synchronization
Trigger DO, DR, HS DR, WFR or DWR
Inputs and Outputs
Digital Inputs
8 channels, volts free dry contact, 24VDC internally wetted
1000Hz sampling
17
Page 18
Ceiec Electric Technology
External status monitoring with programmable debounce
Pulse counting with programmable weight for each channel for collecting WAGES (Water, Air,
Gas, Electricity, Steam) information
Demand Synchronization
Time-Sync via GPS's 1PPS output
Digital Outputs
8 channels for control, alarming and pulsing applications
RO1-RO2: Form A Mechanical Relay
RO3-RO4: Form C Mechanical Relay
DO1-DO4: Optically Isolated Solid State Relay
Communications
Ethernet Ports (P1, P2)
Dual 10/100BaseT TCP/IP Ethernet Ports with RJ45 connector
Maximum of 10 simultaneous IP connections
Optional 100BaseFX with ST connector
Protocols
Modbus TCP
HTTP, SNTP, SMTP, FTP
Ethernet Gateway
IEC61850
Firmware upgrade via Ethernet port
RS-485 (P3, P4)
Optically isolated RS485 port with baudrate from 1.2 to 115.2 kbps
Modbus RTU protocol
Time Sync. via GPS’s 1PPS or IRIG-B outputs
Time Synchronization
Battery-backed real-time clock @ 6ppm (≤ 0.5s/day)
Time Sync. via SNTP, GPS’s 1PPS or IRIG-B outputs
System Integration
18
Page 19
Ceiec Electric Technology
PecStar iEMS
The PMC-680i is supported by CET’s PecStar iEMS software. In addition, the PMC-680i can be easily
integrated into other 3rd party systems because of its support of multiple communications ports as
well as different industry standard protocols
PMC Setup
Free Setup configuration tool
Real-time and log display
Remote control
3rd Party System Integration
Easy integration into Substation Automation or Utility SCADA systems via Modbus RTU, Modbus
TCP or IEC61850
The on-board Web Server allows complete access to its data and supports the configuration for
most of the setup parameters via a web browser (Chrome) without the use of any proprietary
software
The on-board, password protected FTP Server allows logged data in PQDIF or COMTRADE format
to be downloaded without any special software
The downloaded files can be subsequently viewed using software that supports the industry
standard PQDIF and COMTRADE file formats

1.3 PMC-680i application in Power and Energy Management and Analyzer Systems

The PMC-680i can be used to monitor Wye or Delta connected power system. Modbus
communications allow real-time data, events, DI status, Data Logs, Waveform and other information
to be transmitted to an Integrated Energy Management System such as PecStar® iEMS.
19
Page 20
Ceiec Electric Technology
Figure 1-1 Typical Application

1.4 Getting more information

Additional information is available from CET via the following sources:
Visit www.cet-global.com
Contact your local representative
Contact CET directly via email or telephone
20
Page 21
Ceiec Electric Technology

Chapter 2 Installation

Installation of the PMC-680i should only be performed by qualified, competent personnel that have
the appropriate training and experience with high voltage and current devices. The meter must
be installed in accordance with all local and national electrical codes.
Caution
During the operation of the meter, hazardous voltages are present at the input terminals. Failure to

2.1 Appearance

Figure 2-1 Appearance
21
Page 22
Ceiec Electric Technology
Figure 2-2 Rear Panel
22
Page 23
Ceiec Electric Technology
Front View
Side View

2.2 Unit Dimensions

Figure 2-3 Unit Dimensions

2.3 Mounting

The PMC-680i should be installed in a dry environment with no dust and kept away from heat,
radiation and electrical noise sources.
Installation steps:
Remove the mounting brackets from the meter
Fit the meter through a 186mmx186mm cutout as shown in Figure 2-4
Re-install and tighten the mounting brackets against the panel to secure the meter
23
Page 24
Ceiec Electric Technology
energized. CT shorting blocks should be installed to allow for easy maintenance.
Figure 2-4 Panel Cutout

2.4 Wiring Connections

PMC-680i can satisfy almost any three or four phase power systems. Please read this section
carefully before installation and choose the correct wiring method for your power system. The
following wiring modes are supported:
3-phase 4-wire Wye Direct Connection
3-phase 4-wire Wye with 3PTs and 4CTs
3-phase 3-wire Grounded Wye Direct Connection
3-phase 3-wire Grounded Wye with 3PTs and 3CTs
3-phase 3-wire Grounded Delta Direct Connection
3-phase 3-wire Delta with 2PTs and 2CTs
3-phase 3-wire Delta with 2PTs and 2CTs
Caution
Under no circumstances should the PT secondary be shorted.
Under no circumstances should the CT secondary be open when the CT primary is
24
Page 25
Ceiec Electric Technology

2.4.1 3-phase 4-wire Wye Direct Connection

Please consult the serial number label to ensure that the system phase voltage is less than or equal to
the meter’s voltage input specification. Set the Wiring Mode to Wye.
Figure 2-5 4-Wire Wye, no PTs, 4CTs

2.4.2 3-phase 4-wire Wye with 3PTs and 4CTs

Please consult the serial number label to ensure that the rated PT secondary voltage is less than or
equal to the meter’s voltage input specification.
Set the Wiring Mode to Wye.
25
Page 26
Ceiec Electric Technology
Figure 2-6 4-Wire Wye, 3PTs, 4CTs

2.4.3 3-phase 3-wire Grounded Wye Direct Connection

Please consult the serial number label to ensure that the system phase voltage is less than or equal to
the meter’s voltage input specification.
Set the Wiring Mode to Wye.
Figure 2-7 3-Wire Grounded Wye, Direct Connection

2.4.4 3-phase 3-wire Grounded Wye with 3PTs and 3CTs

Please consult the serial number label to ensure that the rated PT secondary voltage is less than or
equal to the meter’s voltage input specification.
Set the Wiring Mode to Wye.
26
Page 27
Ceiec Electric Technology
Figure 2-8 3-Wire Grounded Wye, 3PTs, 3CTs

2.4.5 3-phase 3-wire Grounded Delta Connection

Please consult the serial number label to ensure that the rated PT secondary voltage is less than or
equal to the meter’s voltage input specification.
Set the Wiring Mode to Delta.

2.4.6 3-phase 3-wire Delta with 2PTs and 3CTs

27
Figure 2-9 3-Wire Grounded Delta, no PTs, 4CTs
Page 28
Ceiec Electric Technology
Please consult the serial number label to ensure that the rated PT secondary voltage is less than or
equal to the meter’s voltage input specification.
Set the Wiring Mode to Delta.
Figure 2-10 3-Wire Delta, 2PTs, 3CTs

2.4.7 3-phase 3-wire Delta with 2PTs and 2CTs

Please consult the serial number label to ensure that the rated PT secondary voltage is less than or
equal to the meter’s voltage input specification.
Set the Wiring Mode to Delta.

2.5 Communications Wiring

2.5.1 Ethernet Port (10/100BaseT)

28
Figure 2-11 3-Wire Delta, 2PTs, 2CTs
Page 29
Ceiec Electric Technology
RJ45 Connector
Pin
Meaning
1
Transmit Data+
2
Transmit Data-
3
Receive Data+
4,5,7,8
NC 6 Receive Data-
Table 2-1 RJ45 Connector Pin Description for 10/100BaseT Applications

2.5.2 RS485 Port

The PMC-680i provides up to two RS485 ports and supports the Modbus RTU protocol. Up to 32
devices can be connected on a RS485 bus. The overall length of the RS485 cable connecting all
devices should not exceed 1200m.
If the master station does not have a RS485 communications port, a RS232/RS485 or USB/RS485
converter with optically isolated outputs and surge protection should be used.
The following figure illustrates the RS485 communications connections on the PMC-680i:
Figure 2-12 RS485 Communications Connections

2.6 Digital Input Wiring

The following figure illustrates the Digital Input connections on the PMC-680i:
29
Page 30
Ceiec Electric Technology
Figure 2-13 DI Connections

2.7 GPS 1PPS Input wiring

The Digital Input on the PMC-680i can be used for time synchronization with a GPS 1PPS output.
The following figure illustrates the wiring connections:
Figure 2-14 Time Sync. Connections

2.8 Digital Output Wiring

The following figure illustrates the Digital Output connections on the PMC-680i:
Figure 2-15 DO Connections

2.9 RO Wiring

The following figure illustrates the RO connections on the PMC-680i:
30
Page 31
Ceiec Electric Technology
Figure 2-16 Pulse Output Connections

2.10 Pulse Output Wiring

The following figure illustrates the Pulse Output connections on the PMC-680i:
Figure 2-17 Pulse Output Connections

2.11 Power Supply Wiring

For AC supply, connect the live wire to the L/+ terminal and the neutral wire to the N/- terminal. For
DC supply, connect the positive wire to the L/+ terminal and the negative wire to the N/- terminal.
Figure 2-18 Power Supply Connections

2.12 Chassis Ground Wiring

Connect the G terminal to earth ground.
Figure 2-19 Chassis Ground connection
31
Page 32
Ceiec Electric Technology
Category
Page
Topic
Status

Chapter 3 User Interface

3.1 Front Panel Interface

The PMC-680i is equipped with a stunning, 640x480, TFT Color, LCD Display. The following figure
illustrates PMC-680i's Main Display, which is the first screen shown upon device power up.
Figure 3-1 Main Display

3.1.1 Display Hierarchy and Menu Tree

Figure 3-2 Hierarchy of Menu
For the PMC-680i, the display of the measurements is organized in a hierarchy that consists of
Categories, Topics and Pages. There are 10 icons in the Main Display, and each icon represents a
Category. Each Category displays a specific type of information and may have one or more Topics.
Each Topic may provide one or more Pages of measurement information. The Status area indicates
if there are additional Pages of measurement under a particular Topic and how to get there.
The following figure illustrates menu tree of the Front Panel:
32
Page 33
Ceiec Electric Technology
Power On
Metering
Real Time
Fundamental
Power Quality
Phasors
Harmonics
Harmonic Distortion
Harmonic RMS
Harmonic P
Harmonic Q
Harmonic Phase Angle
Waveform
Energy
I/O
Events
Statistics
Setup
Diagnostics
SOE
PQ Log
EN 50160
Max.
Min.
Basic
COMM
PQ
RVC
WFR DWR
I/O
Clock Language
Password
Demand Energy
Device Information
Site Information
Interharmonic Distortion
Interharmonic RMS
Total Energy
Harmonic Energy
Demand
TOU
TOU Log
PQ Event Counter
SDR Trend
MSV
Clear
33
Figure 3-3 Menu Tree
Page 34
Ceiec Electric Technology
Buttons
Description
In the Main Display, the four arrow buttons are used to move the cursor between Categories,
which are represented by the different icons. The current cursor position is indicated by the
highlighted Category's description. While inside a Category and under a particular Topic, the
arrow buttons are used to navigate between Pages.
Use or to view more parameters, while use or to backward
or forward.
<Enter>
Enter a Category when pressed.
<Tab>
Move between Topics from left to right.
<Esc>
Return to the previous level.
<Fn>
Press <Fn> and <Enter> to capture current interface.
<Fn> + /
Press this key combination to jump to first or last page.
<Fn> + /
Press this key combination to backward or forward ten pages.

3.1.2 Navigating the Front Panel User Interface

Figure 3-4 Front Panel User Interface
The PMC-680i features a stunning, high resolution, color LCD display with an intuitive graphical user
interface that makes it extremely simple to operate. There are eight buttons located beneath the
LCD display on the front panel: <Enter>, <Tab>, <Fn>, , , , and <Esc>.
34
Table 3-1 Description of Button in Front Panel
Page 35
Ceiec Electric Technology
Category
Topics
Pages
Metering
Real Time
The following table gives a complete description of this information hierarchy.
35
Page 36
Ceiec Electric Technology
Fundamental
Power Quality
Phasors
-
Harmonics
Ua Distortion
Ia Distortion
36
Page 37
Ceiec Electric Technology
Ua RMS
Ia RMS
Harmonic Pa
Harmonic Qa
Ua Harmonic Phase
Angle
Ia Harmonic Phase
Angel
Ua Interharmonic
Distortion
Ia Interharmonic
Distortion
Ua Interharmonic
RMS
Ia Interharmonic
RMS
37
Page 38
Ceiec Electric Technology
Waveform
-
Energy
Total Energy
Harmonic Energy
Demand
38
Page 39
Ceiec Electric Technology
39
Page 40
Ceiec Electric Technology
TOU
TOU Log
40
Page 41
Ceiec Electric Technology
I/O
-
Events
SOE
PQ Log
PQ Event Counter
Statistics
EN50160
41
Page 42
Ceiec Electric Technology
42
Page 43
Ceiec Electric Technology
Max.
Min.
SDR Trend
Setup
Basic
COMM
PQ
43
Page 44
Ceiec Electric Technology
RVC
MSV
WFR/DWR
I/O
Clock/Language
Demand/Energy
Password
Clear
Diagnostics
Device Information
Site Information

3.2 Web Interface

The PMC-680i's web interface has been designed specifically to work with Google Chrome. Please
use this link (https://www.google.com/intl/en/chrome/browser/) to download and install Google
Chrome if it's not already installed on the PC.
44
Table 3-2 Description of each Hierarchy
Page 45
Ceiec Electric Technology
The default IP Addresses of the PMC-680i’s two Ethernet Ports are 192.168.0.100 for P1 and
192.168.1.100 for P2, respectively. Please make sure to configure the IP Addresses and Subnet
Masks for the PMC-680i and the PC so that they are in the same subnet.

3.2.1 Setting PC's IP Address

To determine the PC's IP Address, go to Control Panel, and double-click on Network and Sharing
Center and the Network Connections folder appears.
Figure 3-5 Control Panel and Network Connections
Double-click on the Ethernet adapter to open its dialog box. Then double-click on Internet Protocol
Version 4 (TCP/IPv4) to show the PC's IP configuration.
Figure 3-6 Setting PCs IP Address

3.2.2 Configure PMC-680i's IP Addresses

To configure the PMC-680i's IP Addresses, move the cursor to the Setup category, hit <Enter> and
then the Basic Setup topic appears. Hit the <Tab> button to move from Basic Setup to COMM
Setup. The IP Addresses can be modified by hitting <Enter> and going inside the page. Please note
that P1 and P2 should not on the same network segment.
45
Page 46
Ceiec Electric Technology
Figure 3-7 Configure PMC-680is IP Address

3.2.3 Enabling Java Scripting in Google Chrome

1) Open Google Chrome with Java scripting enabled. To enable Java Scripting, move the mouse
pointer to the upper right-hand corner of the Google Chrome interface and then click on this
icon to open the Settings page.
Figure 3-8 Open Setting page of Google Chrome
2) Double-click on the link Show Advanced Settings located at the bottom of the page to show the
advanced settings.
46
Page 47
Ceiec Electric Technology
Figure 3-9 Advanced Setting page of Google Chrome
3) Double-click on the Content Settings and the following screen appears. Select the option Allow
all sites to run JavaScript (recommended).
Figure 3-10 Set Content Setting for Google Chrome

3.2.4 Web Interface

1) Enter the IP Address of the PMC-680i in the Address area of Google Chrome and then press
<Enter>.
2) The PMC-680i’s Web Interface appears. There are four main menu items on the left-hand pane
- Metering, Statistics, Setup and Diagnostics.
3.2.4.1 Metering
47
Figure 3-11 Web Interface
Page 48
Ceiec Electric Technology
Click on the down arrow icon on the right of Metering to expand its sub-menu, which includes
Phasors, Real Time, Power Quality, Harmonics, Interharmonics, Demand, Energy, TOU, Waveform
and I/O. The following sections provide a quick overview of the web pages available under
Metering.
3.2.4.1.1 Phasors
Click Phasors on the left-hand pane, the page displays following information:
Phase and magnitude of Ua (WYE)/Uab (Delta), Ub (WYE)/Ubc (Delta), Uc (WYE)/Uca (Delta), Ia,
Ib, Ic, U4, I4 and I5
U1, U2 and U0
I1, I2 and I0
Figure 3-12 Phasors Interface
3.2.4.1.2 Real Time
Click Real Time on the left-hand pane, the available outputs are Voltage, Current, U/I Phase Angle,
Power and Frequency.
48
Page 49
Ceiec Electric Technology
Figure 3-13 Real Time Interface
3.2.4.1.3 Power Quality
Click Power Quality on the left-hand pane, the available outputs are Voltage Deviation, Frequency
Deviation, Flicker, Symmetrical Components, Unbalance and PQ Event Counter.
3.2.4.1.4 Harmonics
Click on the drop-down box beside Harmonics on the right-hand pane to select which input to display.
The available inputs are Ua (WYE)/Uab (Delta), Ub (WYE)/Ubc (Delta), Uc (WYE)/Uca (Delta), U4, Ia, Ib,
Ic, I4 and I5. Click Harmonic Distortion (%), Harmonic RMS (V), Harmonic P (W), Harmonic Phase
Angle (°) and Harmonic Q (var) to view corresponding information.
49
Figure 3-14 Power Quality Interface
Page 50
Ceiec Electric Technology
Figure 3-15 Harmonics Interface
3.2.4.1.5 Interharmonics
Click on the drop-down box beside Inter-Harmonics on the right-hand pane to select which input to
display. The available inputs are Ua (WYE)/Uab (Delta), Ub (WYE)/Ubc (Delta), Uc (WYE)/Uca (Delta),
U4, Ia, Ib, Ic, I4 and I5. Click Interharmonic Distortion (%) and Interharmonic RMS (V) to view
corresponding information.
3.2.4.1.6 Demand
Click Demand on the left-hand pane, the Demand and Max. Demand will be shown on the right-hand
pane. Depending on the setting of the Self-Read Time setup register, the Max. Demand web page
may display the Max. Demand of This/Last Month or Max. Demand since/before Last Reset.
50
Figure 3-16 Interharmonics Interface
Page 51
Ceiec Electric Technology
Figure 3-17 Demand Interfaces
3.2.4.1.7 Energy
Click Energy on the left-hand pane, the Total Energy and Harmonic Energy will be shown on the right-
hand pane. Click Total Energy tab, the available outputs are Active/Reactive/Apparent Energy, while
Harmonic Energy displays H01 to H63 kWh Imp./Exp., H01 to H63 kvarh Imp./Exp. measurements.
Figure 3-18 Energy Interfaces
3.2.4.1.8 TOU
Click TOU on the left-hand pane, the right-hand page displays TOU Real Time and Log information.
Click Real Time to view present TOU schedule information, Energy and Max. Demand information.
Click Log to view TOU data which includes historical Energy and Max. Demand information.
51
Page 52
Ceiec Electric Technology
Figure 3-19 TOU Interfaces
3.2.4.1.9 Waveform
This web page displays the real-time waveform captured by the PMC-680i. A small fly-out comment
showing the channel name and the measurement value is displayed when the mouse pointer is
positioned to a particular point in a waveform.
Figure 3-20 Waveform Interface
3.2.4.1.10 I/O
Click I/O on the left-hand pane to display status of Digital Inputs, Relay Outputs and Digital Outputs.
3.2.4.2 Statistics
52
Figure 3-21 I/O Interface
Page 53
Ceiec Electric Technology
Click on the down arrow icon beside Statistics on the right to expand its sub-menu, which includes
Counters, SOE, PQ Log, Max./Min., SDR Trend, PQDIF, COMTRADE and EN50160. The following
sections provide a quick overview of the web pages available under Statistics.
3.2.4.2.1 Counters
This web page displays counters for SOE, PQ log, Pst, Plt, TOU, IER, EN50160, WFR, DWR, MSV, DR,
HSDR and SDR.
Figure 3-22 Counter Interface
3.2.4.2.2 SOE
This web page displays SOE Log starting with the most recent event (with a Start Index of 1). There
is a text box near the lower right-hand corner of the page. By entering a specific value in the text
box and the web page jump to particular page.
Also, you can query fixed period’s SOE by specifying Start Date and End Date. By selecting event
type from Type drop-down box to query specific type SOE. If a SOE has Waveform, the waveform
column would display download link. Click Detail to download file, please see figures below. In the
Waveform dialog box, click view to display waveform, while click .cfg or .dat to download waveform
file.
53
Page 54
Ceiec Electric Technology
Figure 3-23 SOE Interface and Download Waveform file
3.2.4.2.3 PQ Log
This web page displays PQ Log starting with the most recent event (with a Start Index of 1). There is
a text box near the lower right-hand corner of the page. By entering a specific value in the text box
and the web page jump to particular page.
Also, you can query fixed period’s PQ by specifying Start Date and End Date. By selecting event type
from Type drop-down box to query specific type PQ log. If a PQ Log has corresponding Waveform,
SEMI F47 or ITIC file, the waveform and Evaluate columns would display view link. Click Detail, SEMI
F47 or ITIC to view and download file, please see figures below.
Figure 3-24 PQ Log Interface
3.2.4.2.4 Max./Min. Log
Click Max./Min. on the left-hand pane and the following screens appear. This web page displays the
Max./Min. Log information of this month (since last reset) and last month (before last reset).
Period Displays the Max. and Min. information for a specific period, which consists of This
Period and Last Period.
Recorder Specifies one of four Groups of Max. and Min. information to display.
54
Figure 3-25 Max./Min. Interface
Page 55
Ceiec Electric Technology
3.2.4.2.5 SDR Trend
Click SDR Trend on the left-hand pane and the following screen appears on the right-hand pane.
This web page displays the Statistical Log in a trend curve. The available inputs are FREQ, Ua, Ub,
Uc, U4, Ia, Ib, Ic, I4, I5, Ua ANG, Ub ANG which can be configured via communication, please refer to
5.9.20 Trend Log Setup.
The color of the trend curve is highlighted and a small fly-out comment displayed showing the
parameter name and the measurement when the mouse pointer is positioned to a particular point on
a trend curve. Please note that the curve set log entries plot as horizontal axis and the page displays
latest 200 logs. Plea
Figure 3-26 SDR Trend Interface
3.2.4.2.6 PQDIF
Click on PQDIF on the left-hand pane and the following screen appears on the right-hand pane. This
web page displays the available PQDIF files in a Table format. Setting start date and end date allows
the user to search for the PQDIF files for a specific date. The Download button on the right side of
the Table allows the user to download a PQDIF file and store it locally on a PC where it can be viewed
using a PQDIF viewer.
55
Page 56
Ceiec Electric Technology
3.2.4.2.7 COMTRADE
Figure 3-27 PQDIF Interface
Click on COMTRADE on the left-hand pane and the following screen appears on the right-hand pane.
This web page displays the available COMTRADE files in a Table format. The view button below
Waveform column allows the user to view waveform of the COMTRADE file. The .cfg and .dat
button on the right side of the Table allows the user to download a COMTRADE file and store it locally
on a PC where it can then be viewed using a COMTRADE viewer.
Figure 3-28 COMTRADE Interface
3.2.4.2.8 EN50160
Click EN50160 on the left-hand pane and the following screen appears. This web page displays the
Summary of Results for EN50160 Compliance in a Table format and click hyperlink such as FAIL to
view detail information. Export button allows users to download EN50160 Compliance report, and
the box near the Export button page allows the user to search for the EN50160 Compliance Report for
a specific period.
56
Page 57
Ceiec Electric Technology
Figure 3-29 EN50160 Interface
Figure 3-30 Detail Information Example
3.2.4.3 Setup
Click Setup on the left-hand pane to expand and the sub-menus, which includes Basic Setup, PQ
Setup, Demand Setup, Record Setup, I/O Setup, COMM Setup, Clock Setup, Password Setup and
Clear. Then click Basic Setup and the following screen appears. This web page displays Basic
Setup information.
57
Page 58
Ceiec Electric Technology
Parameter
Range
Parameter
Range
Parameter
Range
Rated Parameters
U Primary
1 to 1000000V
I Primary
1 to 30000A
U4 Primary
1 to 1000000V
U Secondary
1 to 1500V
I Secondary
1 to 50A
U4 Secondary
1 to 1500V
I4 Primary
1 to 30000A
I5 Primary
1 to 30000A
Ull Nominal
1 to 1500V
I4 Secondary
1 to 50A
I5 Secondary
1 to 50A
I Nominal
1 to 20A
Wiring Mode
4W-WYE, 3W-WYE, DEMO, DELTA
CT Polarity
Figure 3-31 Setup Interface
In order to make changes, the user needs to first login to the web interface by clicking on the Login
icon at the upper right-hand corner of the page. The user then enter the password (default
password = 000000) at the Login dialog box. The user may now make the necessary setup changes
for the PMC-680i.
3.2.4.3.1 Basic Setup
Click Basic Setup on the left-hand pane and the following screen appears on the right-hand pane.
Figure 3-32 Basic Setup Interface
The following table illustrates the range for each parameter:
58
Page 59
Ceiec Electric Technology
Ia Reverse
Normal,
Reverse
Ib Reverse
Normal, Reverse
Ic Reverse
Normal, Reverse
I4 Reverse
I5 Reverse
Calculation
PF Convention
IEC, IEEE, -IEEE
kVA Calculation
Vector, Scalar
Others
Basic Agg.
50cyc, 150cyc, 10min, 2
Freq. Agg
1sec, 3sec, 10sec
PQ Plot
ITIC, SEMI F47
Phase A Color
Red*
Phase B Color
Yellow*
Phase C Color
Blue*
Phase N Color
Black*
GND Color
Green/Yellow striped*
*default
Table 3-3 Basic Setup Parameters Range
3.2.4.3.2 PQ Setup
Click PQ Setup on the left-hand pane and the following screen appears on the right-hand pane. Set
power quality parameters as you need which consist of below categories and please refer to 5.9.6 PQ
Setup for detailed range.
Harmonic
Flicker
Dip/Swell
Transient
RVC (Rapid Voltage Changes)
Inrush Current
MSV (Mains Signalling Voltage)
Discard Flagged Data
59
Page 60
Ceiec Electric Technology
3.2.4.3.3 Demand Setup
Click Demand Setup on the left-hand pane and the following screen appears. Set demand
parameters as you need, please refer to 5.9.8 Demand Setup.
60
Figure 3-33 PQ Setup Interface
Page 61
Ceiec Electric Technology
3.2.4.3.4 Energy Setup
Figure 3-34 Demand Setup Interface
Click Energy Setup on the left-hand pane and the following screen appears. Set energy parameters
as you need, please refer to 5.9.17 Interval Energy Recorder (IER) Setup and 5.9.10 Energy Pulse
Setup.
Figure 3-35 Energy Setup Interface
3.2.4.3.5 Recorder Setup
Click Recorder Setup on the left-hand pane and the following screen appears. Set various recorders’
parameters as you need, please refer to 5.9.9 WFR Setup.
61
Page 62
Ceiec Electric Technology
Figure 3-36 Record Setup Interface
3.2.4.3.6 I/O Setup
Click I/O Setup on the left-hand pane and the following screen appears. Set I/O parameters as you
need, please refer to 5.9.3 DI Setup and 5.9.4 RO/DO Setup.
3.2.4.3.7 COMM Setup
The PMC-680i comes standard with two Ethernet ports (P1&P2) which support Modbus TCP and two
RS-485 ports (P3&P4) which support Modbus RTU. In addition, PMC-680i support sending alarm
email via setting SMTP server. Click on COMM Setup on the left-hand pane and the following screen
appears. Set COMM parameters as you need, please refer to 5.9.1 Communications Setup. Please
note that P1 and P2 should not on the same network segment.
62
Figure 3-37 I/O Setup Interface
Page 63
Ceiec Electric Technology
Figure 3-38 COMM Setup Interface
3.2.4.3.8 Clock Setup
Click Clock Setup on the left-hand pane and the following screen appears. This web page shows four
areas: PC Clock, Device Clock, Clock and SNTP. There is a quick access button that can be used to
synchronize the PMC-680i's Clock to the PC Clock with just a simple click.
3.2.4.3.9 Password Setup
Click Password Setup on the left-hand pane and the following screen appears. This web page allows
the user to change the Login password for the PMC-680i. It's highly recommended for the user to
63
Figure 3-39 Clock Setup Interface
Page 64
Ceiec Electric Technology
Button
Function
Clear Max. Demand
Clear Max. demand of this month
Clear All Max./Min. Log
Clear all Max./Min. Log of This Period (This Month or Since the Last Reset)
Clear SOE Log
Clear SOE Log
Clear PQ Log
Clear PQ Log
Clear PQ Event Counters
Clear PQ Event Counters
Clear All DI Counters
Clear all DI Counters
Clear TOU Log
Clear all TOU Log, including real-time log and historical log
Clear Energy
Clear energy record
change the default Login password to something unique. After inputting passwords, click Save to
save change.
Figure 3-40 Password Setup Interface
3.2.4.3.10 Clear
Click Clear on the left-hand pane and the following screen appears. This web page allows the user to
perform the following Clear functions:
64
Table 3-4 Clear Items
Page 65
Ceiec Electric Technology
Figure 3-41 Clear Setup Interface
For example, if the user clicks on Clear Max. Demand, the following dialog box appears. Click OK to
confirm to delete.
Figure 3-42 Confirm Page
3.2.4.5 Diagnostics
Click Diagnostics on the left-hand pane to expand its sub-menu, which includes Diagnostics and
Maintenance.
3.2.4.5.1 Diagnostics
Click Diagnostics on the left-hand pane and the following screen appears. This web page displays
the PMC-680i's diagnostics information in a table format, which includes Version, Self Diagnostics,
Memory and Site Information.
65
Figure 3-43 Diagnostics Interface
Page 66
Ceiec Electric Technology
3.2.4.4.2 Maintenance
User login the PMC-680i Web with standard password, and click Maintenance on the left-hand pane
and the following screen appears.
Backup & Restore Save or restore all configuration to local
Alarm E-mail Test Test Alarm Email which configured via communication
Figure 3-44 Maintenance Interface
3.2.4.6 Customization
PMC-680i provides web page to distributor which can be used to execute some customized
information, such as Device Model, Web Page Banner, Logo on Front Panel and Logo on Web.
Besides, you can reset to factory defaults and caution should be exercised when taking this action.
Enter http://IP:Port/index.html#Customize in the Address area of Google Chrome and then press
<Enter>. Follow the guidelines on the web to customize information as you need.
66
Figure 3-45 Customize Interface
Page 67

Chapter 4 Applications

Setup Parameter
Definition
Options
DIx Mode
Each DI can be configured as a Status Input, Pulse Counter Input.
Only one DI should be programmed as a Demand Sync Input.
If Clock Source is set to DI, DI8 is used by default for GPS 1PPS Time Sync.
0=Status Input*
1=Counter
2=DMD Sync
DIx Debounce
Specifies the minimum duration the DI must remain in the Active or Inactive
state before a DI state change is considered to be valid.
1 to 9999 (ms)
(Default=20ms)
DIx Setpoint Type
Specifies the valid transition type, whether it’s positive, negative or any, that a DI
Setpoint looks for before triggering its output. DI Setpoint can only be used
when a DI is configured as a Status Input.
0=Any Transition*
1= +ve Transition
2= -ve Transition
DIx Setpoint Trigger
Specifies what output action a DI Setpoint will take when it triggers. DI
Setpoint can only be used when a DI is configured as a Status Input.
See Table 5-92
DIx Pulse Weight
Specifies the incremental value for each received pulse. This is only used when
a DI is configured as a Pulse Counter Input.
1* to 1,000,000
Setup Parameter
Value
Description
DIx Mode 0 Status Input
DIx Debounce
20
Default
DIx Setpoint Type
0, 1, 2
0=Any Transition*
1= +ve Transition

4.1 Inputs and Outputs

4.1.1 Digital Inputs

The PMC-680i is equipped with 8 self-excited Digital Inputs (DIs) that are internally wetted at 24 VDC.
Each DI has the following setup parameters:
Table 4-1 Definition for DI Parameters
The PMC-680i's DIs can be used in the following applications:
1) DIs are typically used for monitoring external status which can help prevent equipment damage,
improve maintenance, and track security breaches. The real-time statuses of the DIs are
available on the Front Panel as well as through communications. Changes in DI status are
stored as events in the SOE Log in 1 ms resolution. The following table illustrates how to
program a particular DI for Status monitoring.
67
Page 68
Ceiec Electric Technology
2= -ve Transition
DIx Setpoint Trigger
See Table 5-92
See Table 5-92
DIx Pulse Weight
N/A
N/A
Setup Parameter
Value
Description
DIx Mode
1
Counter
DIx Debounce
20
Default
DIx Setpoint Type
N/A
N/A
DIx Setpoint Trigger
N/A
N/A
DIx Pulse Weight
1
Default
Table 4-2 DI Setup Parameters for Status Input
Figure 4-1 Program DI for Status Monitoring
2) A DI can be used for pulse counting to collect WAGES (Water, Air, Gas, Electricity and Steam)
information. The DI Pulse Counter information is available via the Front Panel Interface or
communications. The DI Pulse Counters can be reset from the front panel or via
communications. The following table illustrates how to program a DI for pulse counting.
Table 4-3 DI Setup Parameters for Pulse Counting
68
Figure 4-2 Pulse Counter Display on the Front Panel Interface
Page 69
Ceiec Electric Technology
Setup Parameter
Value
Description
DIx Mode 2 DMD Sync
DIx Debounce
20 (Default)
Default
DIx Setpoint Type
N/A
N/A
DIx Setpoint Trigger
N/A
N/A
DIx Pulse Weight
N/A
N/A
Setup Parameter
Definition
Options
RO / DO Alarm
Enable Flag
Specifies if RO / DO alarm function is enabled.
0*=Disabled
1 ~ 4=RO1 to RO4 Enabled
5 ~ 8=DO1 to DO4 Enabled
Execute without
Arm
Specifies if the relays needs to be armed before they can be operated on.
Therefore, the user must first arm the relay first before operating a relay
0*=Disabled
1=Enabled
3) One of the Dls can be programmed to receive the Demand Sync Pulse by setting DI Mode to DMD
Sync. The following table illustrates how to program a DI as a Demand Sync Input. Please
refer to Section 4.2.3 for a detailed description.
Table 4-4 DI Setup Parameters for Demand Sync Pulse
4) When the Clock Source parameter is set to DI, DI8 is used by default to receive the 1PPS GPS
Time Sync. Signal for synchronizing its internal RTC. All DI8 setup parameters are disregarded
except for the DI8 Debounce. Please refer to Section 4.7.3 for a detailed description.
Figure 4-3 Set DI as Clock Source

4.1.2 Relay Outputs and Digital Outputs

The PMC-680i comes standard with 2 Form A and 2 Form C Mechanical Relay Outputs (RO) as well as
4 Solid State Relay Outputs (DO). RO and DO are normally used for setpoint alarming, load control,
or remote control applications. RO and DO on the PMC-680i has the following setup parameters:
69
Page 70
Ceiec Electric Technology
RO / DO Delay
As to remote aggregate command, and if the delay time is 0, the RO / DO will immediately take action when received the command and remain closed status until the next command come. On the contrary, RO / DO will take action and return after a certain time delay (x 0.1s). For remote open command, the delay time has no meaning and RO / DO will immediately return after receive the command.
As to non-remote command, and it means that the RO / DO will return immediately after receive the return command when the time delay is 0; if the time value is not 0, RO / DO will return at a certain time delay (x 0.1s) after receive the return command.
0 to 6000 (x 0.1s), 10*
Application
Description
Front Panel Control
Manual operation from the Front Panel, mainly used for relay testing.
Remote Control
Remotely operated over communications via our free PMC Setup software or PecStar® iEMS.
Remote Control of RO and DO is not supported by the Web Interface.
Control Setpoint
Control Setpoints can be programmed to trigger RO/DO, WFR, DR, Alarm Email, etc, upon
becoming active. Please refer to Section 4.3 for detailed description.
Dip/Swell Setpoint
Dip/Swell Setpoint can be programmed to trigger RO/DO, WFR, DR, Alarm Email, etc, upon
becoming active. Please refer to Section 4.4.4 for detailed description.
Transient Setpoint
Transient setpoint can be programmed to trigger WFR and DWR, upon becoming active. Please
refer to Section 4.4.5 for detailed description.
RVC Setpoint
RVC setpoint can be programmed to trigger WFR and DWR, upon becoming active. Please refer
to Section 4.4.10 for detailed description.
Inrush Setpoint
Inrush Setpoint can be programmed to trigger RO/DO, WFR, DR, Alarm Email, etc. upon becoming
active. Please refer to Section 4.4.11 for a detailed description.
* Default
Table 4-5 DO/RO Setup Parameters
ROs and DOs on the PMC-680i can be used in the following applications:
Table 4-6 DO/RO Setup Applications
Figure 4-4 Manual Operation of RO/DO via the Front Panel Interface
Since there are so many ways to utilize the relay output on the PMC-680i, a prioritized scheme has
been developed to avoid conflicts between different applications. In general, Front Panel Control
70
Page 71
Ceiec Electric Technology
Setup Parameters
Definition
Options
kWh LED Energy Pulse
Source
Specify the source to which the energy pulse output
is proportional.
Disabled
Harmonic kWh
Fundamental kWh
Total kWh
kvarh LED Energy Pulse
Source
Disabled
Harmonic kvarh
Fundamental kvarh
Total kvarh
DO Energy Pulse Source
See Table 4-8 DO Energy Pulse Source
Energy Pulse Constant
Specify the rate of the energy pulse output.
For example, 1000 means 1000 Impulses per kWh or
1 Impulse per 1Wh.
1000, 3200, 5000, 6400 or 12800 Impulses
per kXh (imp/kXh)
Energy Pulse
Description
Energy Pulse
Description
Energy Pulse
Description
has the highest priority and can override the other applications. Remote Control, Control, Dip/Swell,
Transient, Inrush Current and RVC Setpoint share the same priority, meaning that they can all be
programmed to control the same relay output. This scheme is equivalent to having an implicit
Logical OR operation for the control of a Relay Output and may be useful in providing a generic alarm
output signal. However, the sharing of a Relay Output is not recommended if the user intends to
generate a control signal in response to a specific setpoint condition.

4.1.3 Energy Pulse Outputs

There are two common applications for Energy Pulsing:
Accuracy Testing
Providing energy consumption information to an external device such as a PLC or a Pulse Counter
The PMC-680i can be configured to generate kWh and/or kvarh energy pulsing via either the 2 Front
Panel LED Pulse Outputs (kWh and kvarh) or the 4 Digital Outputs in the back. Energy pulsing can be
enabled from the Front Panel or Web through the Demand Energy or Energy Setup screen.
Figure 4-5 Enable Energy Pulse in the Front Panel and Web
PMC-680i’s Energy Pulse Outputs have the following setup parameters:
Table 4-7 Setup Parameters for Energy Pulse Output
71
Page 72
Ceiec Electric Technology
Source
Source
Source
0
Disabled
7
kWh TH
14
kvarh Imp. H01
1
Real Time kWh Total
8
kWh Imp. TH
15
kvarh Exp. H01
2
kWh Imp.
9
kWh Exp. TH
16
kvarh TH
3
kWh Exp.
10
Real Time kvarh Total
17
kvarh Imp. TH
4
kWh Total Fundamental
11
kvarh Imp.
18
kvarh Exp. TH
5
kWh Imp. H01
12
kvarh Exp.
6
kWh Exp. H01
13
kvarh Total Fundamental
Z
Energy Pulse Constant
Default
Min. Interval
1000
1000/3200/5000/6400/12800
1000
160ms
2000
1000/3200/5000/6400
1000
2600
1000/3200/5000
1000
4000
1000/3200
1000
13000
1000
1000
Table 4-8 DO Energy Pulse Source
It's important to understand that energy pulsing is always based on the secondary ratings (e.g. 230V
and 5A) as it would be impossible to generate the required number or pulses based on the primary
ratings. The following table illustrates the recommended settings for the Energy Pulse Constant
based on Z = 2 x V
nominal
x I
nominal
, where V
nominal
and I
are the secondary voltage and current
nominal
nominal ratings. In general, one would use a higher Pulse Constant for a smaller Z value (i.e. a
smaller V
nominal
and I
) in an accuracy testing situation to reduce the test time.
nominal

4.2 Power, Energy and Demand

4.2.1 Basic Measurements

The PMC-680i provides the following basic measurements with 1 second update rate:
72
Table 4-9 Settings for Energy Pulse Constant
3-phase Voltages and Currents
3-phase Powers, PFs and dPF
U4, I4, I5 and Frequency
Bi-directional Energy measurements
Voltage and Current phase angles
Page 73
Ceiec Electric Technology
kWh
kvarh
kVAh
Imp. (Total RMS)
Imp. (Total RMS)
kVAh Total
Exp. (Total RMS)
Exp. (Total RMS)
Net (Total RMS)
Net (Total RMS)
Total (Total RMS)
Total (Total RMS)
Net Fundamental
Net Fundamental
Total Fundamental
Total Fundamental
Imp./Exp. TH
Imp./Exp. TH
Net TH
Net TH
Total TH
Total TH
Imp./Exp. H02 to H63
Imp./Exp. H02 to H63
Real-time status for DIs, ROs and DOs
Ia/Ib/Ic/I4/I5 K-Factor and Crest Factor, Ua/Ub/Uc/U4 Crest Factor
Figure 4-6 Displaying for Basic Measurements

4.2.2 Energy Measurements

The PMC-680i provides Energy measurements include fundamental energy as well as harmonic
energy. The energy has a maximum value of 99,999,999,999.999 and will roll over to zero when it is
reached. The energy can be reset manually or preset to user-defined values through the front panel
or via communications. The PMC-680i provides the following energy measurements:

4.2.3 Demands

Demand is defined as the average power consumption over a fixed interval (usually 15 minutes),
including present demand and predicted demand, and both of them have two calculations: SLD and DI
73
Table 4-10 Energy Measurements
Page 74
Ceiec Electric Technology
Setup Parameter
Definition
Options
Demand Sync. Mode
SLD - Internally synchronized to the meter clock
DI Sync - Externally synchronized to a DI that has been programmed as a Demand
Sync Input by setting the DI Mode setup parameter as DMD Sync.
0=SLD (default)
1=DI Sync
Demand Period
1 to 60 minutes. For example, if the # of Sliding Windows is set as 1 and the
Demand Period is 15, the demand cycle will be 1×15=15min.
1 to 60 minutes
Default=15
# of Sliding Windows
The number of Sliding Windows.
1 to 15
Default=1
Self-Read Time
The Self-Read Time allows the user to specify the time and day of the month for
the Demand Log Self-Read operation. The Self-Read Time supports three
options:
A zero value means that the Self-Read will take place at 24:00 of the last day
of each month.
A non-zero value means that the Self-Read will take place at a specific time
and day based on the formula: Self-Read Time = Day * 100 + Hour where 0 ≤
Hour ≤ 23 and 1 ≤ Day ≤ 28. For example, the value 1512 means that the Self-Read will take place at 12:00pm on the 15th day of each month.
A 0xFFFF value will disable the Self-Read operation and replace it with manual
operation. A manual reset will cause the Max./Min. Log of This Month to
be transferred to the Max./Min. Log of Last Month and then reset. The
terms This Month and Last Month will become Since Last Reset and Before
Last Reset.
Default=0xFFFF
Predicted Response
The Predicated Response shows the speed of the predicted demand output. A
value between 70 and 99 is recommended for a reasonably fast response.
Specify a higher value for higher sensitivity.
70 to 99
Default=70
Ua/Ub/Uc
ULN avg
Uab/Ubc/Uca
ULL avg
U4
Sync. The predicted demand is typically used for pre-alarm and helps users reducing power
consumption.
PMC-680i also provides recording of Max. Demand of this month and last month. The Max. Demand
of this month can be transferred to be as Max. Demand of last month at the end of month, and the
Max. Demand of this month will be reset.
The PMC-680i has the following setup parameters which can set via communication or through the
Front Panel:
The PMC-680i provides the following Present Demand and Predicted Demand parameters:
74
Table 4-11 Setup Parameters for Demand
Page 75
Ceiec Electric Technology
Present
Demand
Ia/Ib/Ic
I avg
I4
I5
∑kVA
kWa/kWb/kWc
Imp./Exp.
∑kW Imp./Exp.
kvara/kvarb/kvarc
Imp./Exp.
∑kvar Imp./Exp.
kVAa/kVAb/kVAc
P.F.a/P.F.b/P.F.c
∑P.F.
Frequency
Ua/Ub/Uc
Deviation
Uab/Ubc/Uca
Deviation
Ua/Ub/Uc Over
Deviation
Uab/Ubc/Uca Over
Deviation
Ua/Ub/Uc Under
Deviation
Uab/Ubc/Uca
Under Deviation
Freq Deviation
U2/U0 Unbalance
I2/I0 Unbalance
Ia/Ib/Ic K Factor
I4 K Factor
I5 K Factor
Ua/Uab THD
Ub/Ubc THD
Uc/Uca THD
U4 THD
Ia/Ib/Ic THD
I4 THD
I5 THD
Ua/Uab TOHD
Ub/Ubc TOHD
Uc/Uca TOHD
U4 TOHD
Ia/Ib/Ic TOHD
I4 TOHD
I5 TOHD
Ua/Uab TEHD
Ub/Ubc TEHD
Uc/Uca TEHD
U4 TEHD
Ia/Ib/Ic TEHD
I4 TEHD
I5 TEHD
Ia Fund.
Ib Fund.
Ic Fund.
I4 Fund.
I5 Fund.
Predicted
Demand
Ua/Ub/Uc
ULN avg
Uab/Ubc/Uca
ULL avg
U4
Ia/Ib/Ic
I avg
I4
I5
kWa/kWb/kWc
Imp./Exp.
∑kW Imp./Exp.
kvara/kvarb/kvarc
Imp./Exp.
∑kvar Imp./Exp.
kVAa/kVAb/kVAc
∑kVA
P.F.a/P.F.b/P.F.c
∑P.F.
Frequency
Max.
Demand
Ia/Ib/Ic
∑kW Imp./Exp.
∑kvar Imp./Exp.
∑kVA
The Max. Demand can be reset manually through the Front Panel or via communications.
75
Table 4-12 Demand Parameters
Figure 4-7 Display of Demand via Front Panel
Page 76
Ceiec Electric Technology
Alternate Days?
Get the current time
Start
Choose Alternate Day
rate schedule
Choose current daily
profile
Choose current rates
Statistic
Energy & Demand
End
Choose season
Choose corresponding
weekday rate schedule
Identify Weekday Type
Yes
No
Figure 4-8 Clear Max. Demand through the front panel and Web

4.2.4 Time of Use (TOU)

TOU is used for electricity pricing that varies depending on the time of day, day of week, and the
season. For power provider, TOU is typically used for billing application, as it consists of daily
profiles for seasons, holidays, weekdays and weekends. For power consumers, understanding TOU
may provide you with an opportunity to save money by using less electricity at times of peak demand.
The PMC-680i supports two TOU schedules, which can be switched at a pre-defined time. The
switching between the two schedules is stored in the SOE log as an event. Up to twelve seasons can
be applied and each season can be programmed with up to twenty daily profiles for alternative day,
weekday1, weekday2 or weekday3.
76
Figure 4-9 TOU Logic
Page 77
Ceiec Electric Technology
Setup Parameters
Definition
Options
Daily Profile #
Specify a daily rate schedule which can be divided into a maximum
of 12 periods in 1-min intervals.
Up to 20 Daily Profiles can be programmed for each TOU schedule.
1 to 20, the first period start at
00:00 and the last period end
at 24:00.
Season #
A year can be divided into a maximum of 12 seasons. Each season
is specified a start date and end with the next season’s start date.
1 to 12, , start from January 1st
Alternate Days #
A day can be defined as an alternate day, such as May 1st. Each
alternate day uses a daily profile.
1 to 90.
Day Types
Specify the day types of the week. Each day of a week can be
categorized as a day type which includes weekday1, weekday2,
weekday3 and alternate days. The alternate day has the highest
priority.
Weekday1, Weekday2, Wee
kday3 and alternate days
Switch Time
Specify when to switch from one TOU schedule to another.
Write 0xFFFFFFFF to this parameter (register 50107) if there is no
need to switch or only one TOU schedule.
Format: YYYYMMDDHH
Self-Read time
Specify the day and time of each month to transfer TOU recorders.
A non-zero value means that the Self-Read will take place at a
specific time and day based on the formula: Self-Read Time = Day
* 100 + Hour where 0 ≤ Hour ≤ 23 and 1 ≤ Day ≤ 28. For example,
the value 1512 means that the Self-Read will take place at 12:00pm
on the 15th day of each month.
Format: DDHH
Each TOU schedule has the following setup parameters and can only be programmed via
communications:
Table 4-13 TOU Setup Parameters
The TOU status and readings can be displayed through the Front Panel or via communications, see the
below captures.
Figure 4-10 TOU Status
For each Tariff, the PMC-680i provides the following real-time Energy and Demand information:
kWh/kvarh Imp./Exp., kVAh and kW/kvar Imp./Exp. Max. Demands. The register value will roll over
to zero automatically when it reaches 99,999,999,999.999 kWh.
77
Page 78
Ceiec Electric Technology
In addition, PMC-680i provides real-time datalog, historic datalog and transient datalog for TOU.
Each datalog contains energy and demand information. The real-time datalog triggered by fixed
time automatically and transient datalog triggered manually. The real-time datalog has a capacity of
3 entries organized in a FIFO basis, with the newest datalog replacing the oldest one. Historic
datalog calculate Monthly Average Power Factor in statistic time while recording interval energy. All
TOU datalogs can be retrieved or reset via the Front Panel or communications.

4.3 Setpoints

The PMC-680i comes standard with 272 user programmable setpoints which provide extensive
control by allowing a user to initiate an action in response to a specific condition. There are 256
Standard Setpoints and 16 High-Speed Setpoints. Typical setpoint applications include alarming,
fault detection and power quality monitoring.
78
Figure 4-11 Over Setpoints
Page 79
Ceiec Electric Technology
Setup Parameter
Definition
Options
Setpoint Type
Specify the monitoring condition -- Over Setpoint, Under Setpoint.
0*=Over Setpoint
1=Under Setpoint
Setpoint Parameter
Specify the parameter to be monitored.
See table 4-15
Setpoint Active Limit
Specify the value that the setpoint parameter must exceed for Over Setpoint
or go below for Under Setpoint for the setpoint to become active.
0*
Setpoint Inactive
Limit
Specify the value that the setpoint parameter must go below for Over
Setpoint or exceed for Under Setpoint for the setpoint to becomes inactive.
0*
Setpoint Active
Delay
Specify the minimum duration that the setpoint condition must be met before
the setpoint becomes active. An event will be generated and stored in the
SOE Log. The range of the Setpoint Active Delay is between 0 and 9999
seconds for Standard Setpoints and between 0 and 9999 cycles for High
Setpoints.
0* to 9999s
Setpoint Inactive
Delay
Specify the minimum duration that the setpoint return condition must be met
before the setpoint becomes inactive. An event will be generated and
0* to 9999
Figure 4-12 Under Setpoints
The Setpoints can be programmed over communications and have the following setup parameters:
79
Page 80
Ceiec Electric Technology
stored in the SOE Log. The range of the Setpoint Inactive Delay is between
0 and 9999 seconds for Standard Setpoints and between 0 and 9999 cycles for
High Setpoints.
Setpoint Trigger
Specify what action a setpoint can take when it becomes active. Please refer
to Table 4-16 below for a list of Setpoint Triggers.
0*
Setpoint Parameters
Real-time*
Demand
PQ
Harmonics & Interharmonics
ULN
kW Total DMD
U0 Unb
U_THD, I_THD
ULL
kvar Total DMD
U2 Unb
U_TOHD, I_TOHD
U4
No kVA Total DMD
I0 Unb
U_TEHD, I_TEHD
Ia / Ib /Ic
P.F. Total DMD
I2 Unb
U_TIHD, I_TIHD
I4
kW Total Pred_DMD
U Fund.
U_TIOHD, I_TIOHD
I5
kvar Total Pred_DMD
I Fund.
U_TIEHD, I_TIEHD
Frequency
P.F. Total Pred_DMD
Volt. Fluctuation
U_HD02 to U_HD63
kW Total Pst
U_IHD01 to U_IHD63
kvar Total Plt
I_H02_RMS to I_H63_RMS
P.F. Total
I_IH01_RMS to I_IH63_RMS
Bit
Action
Bit
Action
Bit
Action
Bit0
RO1 Closed
Bit8~Bit10
Reserved
Bit21
Standard DR #3
Bit1
RO2 Closed
Bit11
HS DR #1
Bit22
Standard DR #4
Bit2
RO3 Closed
Bit12
HS DR #2
Bit23
Standard DR #5
Bit3
RO4Closed
Bit13
HS DR #3
Bit24
Standard DR #6
Bit4
DO1 Closed
Bit14
HS DR #4
Bit25
Standard DR #7
Bit5
DO2 Closed
Bit15~Bit18
Reserved
Bit26
Standard DR #8
*Default
Table 4-14 Description for Setpoint Parameters
* High-Speed Setpoint Parameters
Table 4-15 Setpoint Parameters
80
Page 81
Ceiec Electric Technology
Bit6
DO3 Closed
Bit19
Standard DR #1
Bit27
DWR
Bit7
DO4 Closed
Bit20
Standard DR #2
Bit28
WFR
* Only can be triggered by DI and Standard Setpoints
Table 4-16 Setpoint Triggers

4.4 Power Quality Parameters

The PMC-680i has been certified as an IEC 61000-4-30 Class A performance instrument by PSL.
Therefore, the Measurement Aggregation Algorithm used for the derivation of all IEC 61000-4-30 PQ
parameters are in accordance to Section 4.5 of the IEC 61000-4-30 Standard. Please refer to
Appendix E for a copy of the IEC 61000-4-30 Class A Certificate of Conformity.

4.4.1 Power Frequency

The PMC-680i is capable of measuring Frequency accurate to ±0.005Hz or 0.01%. The measurement
range is ±15% of f
system.
, which is 42.5Hz to 57.5Hz for 50Hz system and 51 Hz to 69Hz for 60Hz
nominal
The measurement method of Frequency is in accordance with Section 5.1 of IEC 61000-4-30 Standard
for Class A performance. The PMC-680i also computes Freq. Deviation as per below:
Freq. Deviation = ((f - f
nominal
)/f
) x 100% where f
nominal
is the Nominal Frequency
nominal
Figure 4-13 Displaying for Frequency Deviation

4.4.2 Magnitude of the Supply Voltage

The measurement method of the Magnitude of the Supply Voltage parameters is in accordance with
Section 5.2 of IEC 61000-4-30 Standard for Class A performance. The measurement method is not
intended for the detection and measurement of disturbances such as Dips, Swells, Voltage
Interruptions and Transients. The RMS value includes voltage related measurements such as
Harmonics, Interharmonics, Mains Signaling, etc.

4.4.3 Flicker

The PMC-680i provides the Flicker measurements in accordance with the IEC 61000-4-15 (2010)
Standard for Class A performance using the recommended models for 120V and 230V, supporting
81
Page 82
Ceiec Electric Technology
Parameter
Definition
Residual Voltage
The lowest U
rms (1/2)
value measured on any channel during the Dip
both 50Hz and 60Hz for each model. Voltage Dips, Swells and Interruptions shall cause Pst and Plt
output values as well as "output 4 and 5 values" (see IEC 61000-4-15) to be flagged. Please refer to
Section 4.4.12 Flagging Concept for a detailed description.
The PMC-680i is capable of storing Flicker measurements for 1 year with the standard 4GB model and
2 years with the 8GB option.
Figure 4-14 Displaying for Flicker

4.4.4 Supply Voltage Dips/Swells and Interruption

The PMC-680i supports the detection of the Supply Voltage Dips/Swells and Interruption using a
method that is in accordance with Section 5.4 of IEC 61000-4-30 Standard for Class A performance.
The PMC-680i provides Dip/Swell and Interruption detection for voltage quality monitoring on a per
phase basis and records an event in the PQ Log, which includes the event timestamp event type,
event characteristics and ITIC/SEMI F47 curve. Moreover, Dip/Swell detection for each phase
voltage would trigger WFR, DWR, HS DR, DR and RO/DO Alarm.
4.4.4.1 Voltage Dip Evaluation
A Voltage Dip is characterized by a pair of data, the Residual Voltage (U
82
Figure 4-15 Displaying for Dip/Swell and Interruption
) or Depth and Duration:
res
Page 83
Ceiec Electric Technology
Depth
The difference between the Reference Voltage (either U
din
or Usr) and the Residual Voltage. It's
generally expressed in percentage of the Reference Voltage.
Duration
The time difference between the beginning and the end of the Voltage Dip.
Parameter
Definition
Max. Voltage Swell Magnitude
The largest U
rms (1/2)
value measured on any channel during the Swell.
Duration
The time difference between the beginning and the end of the Voltage Swell.
Parameter
Definition
Options/Value
Dip/Swell Reference Voltage
Udin / Usr
0*= U
din,
1= Usr
Dip/Swell Enable
Dip/Swell Enable.
0*=Disabled, 1=Enabled
Table 4-17 Dip Evaluation Parameter
4.4.4.2 Voltage Swell Evaluation
A Voltage Swell is characterized by a pair of data, the Maximum Swell Voltage Magnitude and
Duration:
Table 4-18 Swell Evaluation Parameter
4.4.4.3 Sliding Reference Voltage (Usr)
If a sliding reference is chosen for the detection of Voltage Dip or Swell, this shall be calculated using
a first order filter with a 1-min time constant. This filter is given by
U
= 0.9967 x U
sr(n)
+ 0.0033 x U
sr(n-1)
(10/12)rms
where
U
sr(n)
U
is the previous value of the Sliding Reference Voltage
sr(n-1)
U
(10/12)rms
is the present value of the Sliding Reference Voltage
is the most recent 10/12-cycle r.m.s. value
4.4.4.4 Dip/Swell Setpoint
As per IEC 41000-4-30:
Voltage Swell Detection
On polyphase systems a Swell begins when the Urms(1/2) voltage of one or more channels rises above the Swell Threshold and ends when the Urms(1/2) voltage on all measured channels is equal to or below the Swell Threshold minus the Hysteresis voltage.
Voltage Dip Detection
On polyphase systems a Dip begins when the Urms(1/2) voltage of one or more channels is below the Dip Threshold and ends when the Urms(1/2) voltage on all measured channels is equal to or above the Dip Threshold plus the Hysteresis voltage.
The Dip/Swell Threshold and the Hysteresis Voltage are both set by the user according to the actual
situation. The Dip/Swell Setpoint provides the following setup parameters which can be
programmed via the Front Panel or over communications:
83
Page 84
Ceiec Electric Technology
Swell Limit
Specify the limit of Swell.
101 to 200(%) of reference voltage, Default=110%
Dip Limit
Specify the limit of Dip.
1 to 99(%) of reference voltage, Default=90%
Dip Return
Specify the return value of Dips.
1 to 1000 (x0.001 Ue), Default=5
Swell Return
Specify the return value of Swells.
1 to 1000 (x0.001 Ue), Default=5
Dip/Swell Trigger
Specify what action a setpoint can take when Dip / Swell become active
DO/RO Closed / DR / HS DR / WFR* / DWR
*default
Table 4-19 Description for Dip/Swell Parameter
The Dip Limit, Swell Limit, Voltage Interruption Threshold and Dip/Swell Return values should be
configured to meet the following criteria:
a) The Voltage Interruption Threshold shall be set below Dip Limit.
b) The Swell Limit and Dip Limit should associate with Voltage Rapid Changes in the minimum
difference between the two steady-states. The absolute value of the difference between the
Dip /Swell Limits and 100% must always be greater than the Voltage Rapid Changes in the
minimum pressure difference between the two steady-states (actual percentage).
c) The Dip/Swell Return value should associate with Swell limit and Dip Limit, Dip/Swell return
value (actual value) must be less than the Dip/Swell limit (Dip, Swell of the absolute difference of
the minimum value and 100%).
d) Regardless of whether Dip/Swell is enabled, the conditions for a), b) and c) must always be met.
4.4.4.5 WFR of Dips/Swells Events
84
Figure 4-16 WFR of a Dip Event
Page 85
Ceiec Electric Technology
Parameter
Definition
Options/Value
Interruption Reference Voltage
Udin / Usr
0*= U
din,
1= Usr
Interruption Enable
Dip/Swell Enable.
0*=Disabled, 1=Enabled
Interruption Limit
Specify the limit of Interruption.
50 to 0(%) of reference voltage, Default=10%
Interruption Return
Specify the return value of Interruption.
1 to 1000 (x0.001 Ue), Default=5
Interruption Trigger
Specify what action a setpoint can take when Dip / Swell become active
DO/RO Closed / DR / HS-DR / WFR* / DWR
Figure 4-17 RMS Plot of the same Dip Event
4.4.4.6 Voltage Interruption Evaluation
On polyphase systems, a Voltage Interruption begins when the U
below the Interruption Threshold and ends when the U
voltage on any one channel is equal to,
rms (1/2)
voltages of all channels fall
rms (1/2)
or greater than, the Interruption Threshold plus the Hysteresis.
The Interruption Threshold and Hysteresis are both set by the user according to the use. The
Interruption Threshold shall not be set below the uncertainty of Residual Voltage measurement plus
the value of Hysteresis. Typically, Hysteresis is equal to 2% of U
can, for example, be set to 5% of U
din
.
. The Interruption Threshold
din
The Duration of a voltage interruption is the time difference between the beginning and the end of
the Voltage Interruption.
4.4.4.7 Voltage Interruption Setpoint
The Voltage Interruption Setpoint provides the following setup parameters which can be programmed
via the Front Panel or over communications:
*default
85
Table 4-20 Description for Interruption Setpoint Parameter
Page 86
Ceiec Electric Technology
Setup Parameter
Definition
Options
Transient Enable
Transient enable or disable.
Disabled* / Enabled
Transient Limit
Specify the limit of Transient
5% to 500% Ue, 35*
Transient Trigger
Specify what action a setpoint can take when Transient become active
WFR* / DWR
2
V2 Unbalance x100%
V V1
2
I2 Unbalance x100%
I I1

4.4.5 Voltage Transients

The PMC-680i provides the capability for detecting voltage transient disturbances using the sliding-
window method according to IEC 61000-4-30 with a maximum resolution of 40µs (@50Hz) for the
standard PMC-680i and 20µs (@50Hz) with the optional 1024 samples/cycle sampling. The PMC-
680i provides transient detection for voltage quality monitoring and records an event in the PQ Log,
which includes the event timestamp event type, and event characteristics. In addition, transient
would trigger WFR and DWR.
4.4.5.1 Transient Setpoint
The Transient Setpoint provides the following setup parameters which can be programmed via the
Front Panel or over communications:
*default
Table 4-21 Setup parameters for Transient Setpoint
4.4.5.2 WFR of Transient Events
Figure 4-18 WFR of a Transient Event at 512 samples/cycle

4.4.6 Supply Voltage Unbalance

The PMC-680i provides both the Zero Sequence and Negative Sequence Voltage and Current
Unbalance measurements using Symmetrical Components and in accordance with Section 5.7 of IEC
61000-4-30 Standard for Class A performance.
86
,
(Negative Sequence Unbalance)
Page 87
Ceiec Electric Technology
0
V0 Unbalance x100%
V V1
I0
I0 Unbalance x100%
I1
X100%
U
U
1
k
%100
I
I
1
k
X
X100%
U
U
2
K
1K
k
X100%
I
I
2
K
1K
k
X100%
nom
k
U
U
X100%
nom
k
I
I
,
where
V0, V1, V2 are the Zero, Positive and Negative Sequence Components for Voltage, respectively.
and
I0, I1, I2 are the Zero, Positive and Negative Sequence Components for Current, respectively.
(Zero Sequence Unbalance)

4.4.7 Harmonics and Interharmonics

The PMC-680i provides the Harmonics and Interharmonics measurements in accordance with
Sections 5.8 and 5.9 of IEC 61000-4-30 Standard for Class A performance using a 10/12 cycle gapless
centered harmonic sub-group measurement, denoted Cng for Harmonics and C
Interhamonics, as per IEC 61000-4-7:2002.
There are three methods to calculate the Harmonic Distortion (HD):
a) Fundamental Method:
Voltage Kth Harmonic/Interharmonic Distortion=
where U1 is the Fundamental Voltage
n-200-ms
for
Current Kth Harmonic/Interharmonic Distortion=
b) RMS Method:
Voltage Kth Harmonic /Interharmonic Distortion=
Current Kth Harmonic/Interharmonic Distortion=
c) Nominal Method:
Voltage Kth Harmonic /Interharmonic Distortion=
Current Kth Harmonic /Interharmonic Distortion=
where I1 is the Fundamental Current
where the denominator is the RMS
where the denominator is the RMS
where U
where I
is the Nominal Voltage
nom
is the Nominal Current
nom
The PMC-680i also provides, in addition to Voltage Harmonics, measurements for Current Harmonics,
K-Factor, Crest Factor, Power Harmonics and Energy Harmonics.
K-Factor and Crest Factor
87
Page 88
Ceiec Electric Technology
)(
)(
K
2
hh
1h
2
hh
1h
max
max
h
h
I
hI
Factor
x
x
rms
peak
C
Ua
Ub
Uc
U4
Ia
Ib
Ic
I4
I5
THD, TOHD, TEHD (%)
▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
HD01 to HD63 (%)
▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
TH, H01 to H63 (RMS)
▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
TOH/THE/DC rms
▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
Current K-Factor
--
--
--
-- ▪ ▪ ▪ ▪
Crest Factor
▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
IHD01 to IHD63 (%)
▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
IH01 to IH63 (RMS)
▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
TIHD, TOIHD, TEIHD (%)
▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
Phase Angle H01 to H63
▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪
Ua
Ub
Uc
U4
Ia
Ib
Ic
I4
I5
K-Factor is defined as the weighted sum of the harmonic load currents according to their effects on
transformer heating, as derived from ANSI/IEEE C57.110. A K-Factor of 1.0 indicates a linear load
(no harmonics). The higher the K-Factor, the greater the harmonic heating effects.
Ih = hth Harmonic Current in RMS
h
= Highest harmonic order
max
Crest Factor is defined as the Peak to Average Ratio (PAR), and its calculation is listed below:
|X|
= Peak amplitude of the waveform
peak
X
= RMS value
rms
4.3.8.1 Voltage and Current Harmonics and Interharmonics
The following table illustrates the Voltage and Current Harmonics and Interharmonics measurements
available on the PMC-680i:
4.4.8.2 Power Harmonics
The following table illustrates the Power Harmonic measurements available on the PMC-680i:
88
Table 4-22 Voltage and Current Harmonics and Interharmonics Measurements
Page 89
Ceiec Electric Technology
kW/kvar/kVA TH
-- ▪ ▪ ▪ --
--
PF TH
--
--
--
--
--
--
--
--
--
kW/kvar/kVA Fundamental
-- ▪ ▪ ▪ --
--
PF Fundamental
-- ▪ ▪ ▪ --
--
kW/kvar/kVA H02 to H63
-- ▪ ▪ ▪ --
--
PF H02 to H63
-- ▪ ▪ ▪ --
--
Setup Parameter
Definition
Options
Harmonics Calculation
Specifies the Harmonics calculation methods, please refer to above introduction.
0*=% of Fundamental
1=% of RMS
2=% of Nominal
Statistical Harmonic Calculation
Specifies the mode of calculating harmonic.
0*=Subgroup, 1=Group
Order of Harmonic Calculation
Specifies the order of harmonic statistic.
2 to 63 (Default=40)
Table 4-23 Power Harmonics Measurements
4.4.8.3 Harmonic Setup Parameters
The Harmonic provides the following setup parameters which can be programmed via the Front Panel
or over communications:
*default
Table 4-24 Setup parameters for Harmonic
4.4.8.4 Screen Captures of Harmonics Measurements
Figure 4-19 Harmonic Measurements on Front Panel Interface and Web Interface
Indicates the data is flagged and press Enter to select to refresh present page or select to
stop refreshing data.

4.4.8 Mains Signalling Voltage (MSV)

89
Page 90
Ceiec Electric Technology
Setup Parameter
Value
MSV #x Enable
0 = Enable, 1 = Disable, default=0
MSV #x Frequency
50 Hz: 600 to 30000 (x0.1Hz)
60 Hz: 700 to 30000 (x0.1Hz)
Default=10000
MSV #x Limit
3 to 1000 (x0.001Ue), default=50 (x0.001Ue)
MSV #x Emission Time
1 to 120s, default=60s
As per 5.10 of IEC 61000-4-30:
Mains Signaling Voltage is RMS voltage of mains signal.
Mains signaling voltage measurement shall be based on
Either the corresponding 10/12-cycle r.m.s. value interharmonic bin Or the r.m.s. of the four nearest 10/12-cycle r.m.s. value interharmonic bins
The beginning of a signaling emission shall be detected when the measured value of the concerned interharmonic exceeds a threshold. The measured values are recorded during a period of time specified by the user, in order to give the level and the sequence of the signal voltage.
The user must select a detection threshold above 0.1% U
as well as the length of the recording period up to 120s.
din
The PMC-680i provides 3 groups of waveform recorder for MSV with 128 entries in accordance with
Section 5.10 of IEC 61000-4-30 Standard for Class A performance. Each MSV WR will be recorded as
PQ Log, SOE Log and EN50160 report.
The MSV provides the following setup parameters which can be programmed through the Front
Panel, Web or communication:
Table 4-25 Mains Signal Voltage Setup Parameters
Table 4-20 Setup Mains Signal Voltage via Front Panel and Web

4.4.9 Voltage Deviation

As per Section 5.12 of IEC 61000-4-30:
The 10/12-cycle r.m.s value Urms can be used to assess the underdeviation and overdeviation parameters in per cent of Udin. The underdeviation Uunder and overdeviation Uover parameters are determined by the following equations. w:
Voltage Overdeviation (%)
90
Page 91
Ceiec Electric Technology
U
= 0 if U
over
U
over
= ((U
rms
- U
din
) / U
) x 100% if U
din
rms
rms
< U
U
din
din
Voltage Underdeviation (%)
U
= 0 if U
under
U
under
= ((U
din
- U
rms
) / U
) x 100% if U
din
rms
rms
> U
U
din
din
The PMC-680i is capable of measuring Voltage accurate to 0.1% and monitoring Voltage deviation on
line. In addition, the Voltage deviation can be set as setpoint. The following screen captures
illustrates the display of the Deviation parameters in the Front Panel and built-in Web Interface.
Figure 4-21 Voltage Deviation Display on Front Panel and Web

4.4.10 Rapid Voltage Changes (RVC)

As per IEC 61000-4-30:
A rapid voltage change is a quick transition in RMS voltage between two steady-state conditions.
To measure rapid voltage change, threshold must be defined for each of the following: the minimum rate of change, the minimum duration of the steady-state conditions, the minimum difference in voltage between the two steady-state conditions, and the steadiness of the steady-state conditions.
The voltage during a rapid voltage change must not exceed the voltage dip and/or the voltage swell threshold, as it would otherwise be considered as a voltage dip or swell.
The characteristic parameter of the rapid voltage change is the difference between the steady-state value reached after the change and the initial steady-state value.
The PMC-680i provides the ability to capture RVC in accordance with the IEC 61000-4-30 Standard
and records in PQ Log and High-speed Recording with event timestamp, event type, and event
characteristics.
4.4.10.1 RVC Setpoint
91
Page 92
Ceiec Electric Technology
Setup Parameters
Definition
Options
RVC Enable
Specifies if RVC Setpoint is enabled.
Disabled* / Enabled
Detection Mode
Specifies detection mode of the RVC.
0*= Steady-state Volt. Change
1= Maximum Volt. Change
RVC Voltage
Tolerance
Maximum allowable fluctuation between the maximum and minimum voltage values during the steady state condition. For example, the voltage tolerance is 0.5% that is the allowable fluctuation max voltage is 0.005Vll
nominal.
0.1% to 100% ULL
nominal
RVC SS Duration Min.
Minimum duration to reach the steady-state condition.
0.1 to 10 seconds
RVC VStep Min.
Minimum voltage step change between two steady-state conditions
0.1% to 100% ULL
nominal
RVC Rate Change Min.
Minimum rate of change between two steady-state conditions.
0.1%/second to 100%/second
RVC Trigger
Output Specify what action a setpoint can take when RVC become active.
WFR* / DWR
Figure 4-22 Rapid Voltage Changes
The RVC Setpoint provides the following setup parameters which can be programmed through the
Front Panel, web or over communications:
*default
To reach the steady-state condition, the voltage fluctuation (voltage difference in RMS between Max.
and Min.) must be less than RVC Voltage Tolerance for a period longer than RVC SS Duration Min.
For the RVC Setpoint to trigger, the following conditions must be met:
a) The voltage step change between two steady-state conditions is greater than RVC VStep Min.
b) The rate of change between two steady-state conditions is greater than RVC Rate Change Min.
c) The voltage during a rapid voltage change must not exceed the voltage dip and/or the voltage
swell threshold, as it would otherwise be considered as a voltage dip or swell.
92
Table 4-26 Setup Parameters for RVC Setpoint
Page 93
Ceiec Electric Technology
4.4.10.2 WFR of RVC Event
Figure 4-23 RVC Setup via Front Panel and Web

4.4.11 Inrush Current

Figure 4-24 WFR of a RVC Event
Figure 4-25 RMS Plot of the same RVC Event
As per IEC 61000-4-30:
93
Page 94
Ceiec Electric Technology
Setup Parameters
Definition
Options
Inrush Current Enable
Specifies if inrush current setpoint is enabled.
0*=Disabled, 1=Enabled
Inrush Current Threshold
Defines the range that current must exceed for the
Inrush Current becomes active.
100% to 500% (Default=120)
Inrush Current Hysteresis
Defines the limit, which is equal to Inrush Threshold
- Inrush Hysteresis, for the I
half cycle rms
current below
which the inrush transient end
1-1000(x0.1%)
(Default = 10)
Inrush Current Trigger
Specify what action a setpoint can take when Inrush
Current become active
DO/RO Closed / DR / HS-DR / WFR* /
DWR
The inrush current begins when the I equal to or below the Inrush Threshold minus a user-selected Inrush Hysteresis value.
The inrush current can be further characterized by
the time duration between the beginning and the end of the inrush current the maximum value of inrush current measured I the square root of the mean of the squared I
current rises above the Inrush Threshold, and ends when the I
half cycle rms
value
half cycle rms
half cycle rms
values measured during the inrush duration
half cycle rms
current is
Inrush current refers to the maximum instantaneous current drawn by an electrical device, often
several times their normal full-load current, when first energized such as the turning on of an AC
electric motor or the energization of a transformer or a capacitor bank. The higher than normal
inrush current typically only lasts for a few cycles before returning to their steady state condition.
Figure 4-26 Inrush Current
The PMC-680i provides the capability for detecting and the capturing of the inrush current transient
disturbance that is in accordance with the IEC 61000-4-30 Standard for Class A performance.
4.4.11.1 Inrush Current Setpoint
The PMC-680i provides following programmable parameters for Inrush Current Setpoint which can be
set via the Front Panel or though communication.
*default
94
Page 95
Ceiec Electric Technology
Table 4-27 Setup Parameters for Inrush Current Setpoint
Table 4-27 Setup Inrush Current Setpoint via Front Panel and Web
4.4.11.2 WFR of Inrush Current Event
Figure 4-28 WFR of an Inrush Current Event @ 128 samples/cycle
Figure 4-29 WFR of an Inrush Current Event @ 512 samples/cycle
95
Page 96
Ceiec Electric Technology
Bit 15~Bit 5
Bit 4
Bit 3
Bit 2
Bit1
Bit 0
Bit 0
Reserved
QR Log
EN50160
Min. Log
Max. Log
SDR Log
Disabled/Enabled
Bit
Description
Bit
Description
B0
Basic Measurement
Dip
B8
Pst.
Dip
B1
Swell
B9
Swell
B2
Interruption
B10
Interruption
B3
Over Current Limit
B11
Reserved
B4
Freq.
Dip
B12
Plt.
Dip
B5
Swell
B13
Swell
B6
Interruption
B14
Interruption
B7
Reserved
B15
Reserved

4.4.12 Flagging Concept

As per Section 4.7 of IEC 61000-4-30:
During a dip, swell, or interruption, the measurement algorithm for other parameters (for example, frequency measurement) might produce an unreliable value. The flagging concept therefore avoids counting a single event more than once in different parameters (for example, counting a single dip as both a dip and a frequency variation) and indicates that an aggregated value might be unreliable.
Flagging is only triggered by dips, swells and interruptions. The detection of dips and swells is dependent on the threshold selected by the user, and this selection will influence which data are "flagged".
The flagging concept is applicable for Class A measurement performance during measurement of power frequency, voltage magnitude, flicker, supply voltage unbalance, voltage harmonics, voltage interharmonics, mains signalling and measurement of underdeviation and overdeviation parameters.
If during a given time interval any value is flagged, the aggregate value indicating that value shall also be flagged. The flagged value shall be stored and also included in the aggregation process, for example, if during a given time interval any value is flagged the aggregated value that includes this value shall also be flagged and stored.
The PMC-680i is a certified IEC 61000-4-30 Class A device so it supports the Flagging Concept.
Flagging Setup The Flagging Setup register (40825) defines if Flagging is enabled for a particular
type of Statistical Log as illustrated in the following table, with a bit value of 1
meaning that Flagging is enabled for the corresponding Log type.
Table 4-28 Flagging Setup Register (40825)
Flagging Status This register indicates if a particular type of data has been flagged with a bit value
of 1 meaning flagged and 0 meaning not flagged. The following table illustrates
the details of the Flagging Status register for real-time data.
Statistical Log For any Statistical Log (such as SDR Log, Max. Log, Min. Log and/or EN50160 Log), its
96
Table 4-29 Flagging Status Register (0080)
log entry will be discarded and will not be included in the statistical evaluation if any
Page 97
Ceiec Electric Technology
Score
Level
0–29
Low
30–69
Medium
70–100
High
data within the log entry has been Flagged while the bit representing the particular
Log type in the Flagging Setup register is enabled (set to 1).
Real-time Data Real-time data via Modbus communications will only refresh after the Flagging
Status register has been read if Bit 15 of the Flagging Setup register is enabled (set
to 1) and if Flagging is active. Conversely, real-time data via Modbus
communications will automatically refresh if Bit 15 of the Flagging Setup register is
disabled (set to 0) so there is no need to read the Flagging Status register before
reading the real-time data.
Real-time data includes Frequency, Voltage, Current, Unbalance, Harmonics and
Interharmonics measurements.

4.4.13 Disturbance Direction Location

The PMC-680i has disturbance direction detection capabilities to enable you to determine the
location of a disturbance, whether it's upstream or downstream, from multiple meters in a power
monitoring system more quickly and accurately. When the Dip starts, the PMC-680i start detect
location automatically and provide confidence by calculating power characters, and the direction
information and the confidence level are recorded as PQ Log.
Table 4-30 Confidence Level
Figure 4-30 Disturbance Direction Location

4.4.14 EN50160 Compliance Report

The EN50160 Standard defines the Voltage Characteristics of Electricity Supplied by Public
Distribution Systems. It provides the limits within which any customer can expect voltage
97
Page 98
Ceiec Electric Technology
characteristics to remain. For a complete definition of the non-conformity level for each of the
following EN50160 parameters, please consult the EN50160 Standard document.
The PMC-680i can measure, summarize data and statistics relevant data in accordance with the
EN50160 standard. In addition, the device is capable of creating a report per week for the following
PQ parameters and the report can be stored for one year.
Power Frequency, including Maximum and Minimum Supply Voltage Variations, including Maximum and Minimum Flicker, including Max./Min. and CP95 Voltage Unbalance, including Max./Min. and CP95 Harmonic Voltage, including Max./Min., Avg. and CP95 Mains Signal Voltage, including Max./Min. and CP95 Rapid Voltage Changes Swell and Dips, statistic parameters classified according to characteristic voltage and duration Interruption, statistics parameters classified according to duration Transient
The programming of EN50160 Log only supports communications, please refer to section 5.9.18 to set
parameters for each item. EN50160 Report can be accessed through the Front Panel or via
communications. The PMC-680i can store up to 52 logs, if there are more than 52 logs, the newest
log will replace the oldest on a FIFO basis.
The following screen captures illustrate the PMC-680i’s EN50160 Compliance Report available on its
Front Panel and Web Interface.

4.4.15 Disturbance Waveform Recorder (DWR)

The PMC-680i provides disturbance waveform recording including Ua/Ub/Uc/U4 and Ia/Ib/Ic/I4/I5.
The disturbance waveform recording can be triggered by dip, swell, transient, rapid voltage changes,
setpoint event, DI status changes and communications. The Disturbance Waveform data is stored in
the device’s non-volatile memory with COMTRADE file format and will not suffer any loss in the event
98
Figure 4-31 EN50160 Report Display via Front Panel and Web
Page 99
Ceiec Electric Technology
A B C D E F
Initial Stage Ending StageSteady Stage
Stage
Description
Recording Length
Recording Frequency
A
Pre-Fault cycles for the Initial Stage
5 to 10 cycles
512 Samples/Cycle
B
Waveform Recording of the Initial Stage
25 to 35 cycles
512 Samples/Cycle
C
Waveform Recording during the Steady Stage
0 to 150 cycles
16 Samples/Cycle
D
RMS Recording during the Steady Stage
0 to 18,000 cycles
1 Sample/Cycle
E
Pre-Fault cycles of the Ending Stage
2 cycles
512 Samples/Cycle
F
Waveform Recording of the Ending Stage
13 cycles
512 Samples/Cycle
of power failure. The PMC-680i can store DWR logs up to 128 entries @4GB or 256 entries @8GB.
Each disturbance waveform recording consists of the following stages.
Figure 4-32 Disturbance Location
Table 4-31 Time frames of waveform
Notes:
1) For stages C and D:
If C < 150 cycles, the D would be 0.
If C = 150 cycles, the D stage data will be recorded.
If D = 18,000 cycles, the recording of D stage data end even if disturbance does not finish. After 10 minutes, the E and F stage data will be recorded.
3) The following figure shows an example of Disturbance Waveform Recording.
Figure 4-33 Disturbance Waveform Recorder
99
Page 100
Ceiec Electric Technology
Setup Parameters
Definition
Options
PQ Curve
Set display ITIC or SEMI F47 curve for PQ event.
SEMI F47 only for Dip event.
0=ITIC (default)
1=SEMI F47
Figure 4-34 DWR Setup via Front Panel and Web

4.4.16 ITIC/SEMI F47 Curve

The ITIC Curve describes an AC input voltage which typically can be tolerated (no interruption in
function) by most Information Technology Equipment (ITE), while SEMI F47 is specification for
Semiconductor Processing Equipment Voltage Dip Immunity, which specifies the required voltage Dip
tolerance for semiconductor fabrication equipment.
ITIC SEMI F47
Figure 4-35 ITIC and SEMI F47
PMC-680i’s Front Panel or Web can display ITIC or SEMI F47 curve for PQ Events. Display ITIC or
SEMI F47 can be set via the Web or communication.
Table 4-32 ITIC/SEMI F47 Curve Setup Parameter
100
Loading...