CET PMC-340 User Manual

Page 1
PMC-340
Digital Three-Phase Energy Meter
User Manual
Version: V1.1A
May 8, 2018
Page 2
CET Inc.
2
This manual may not be reproduced in whole or in part by any means without the express written permission from CET Inc. (CET). The information contained in this manual is believed to be accurate at the time of publication; however, CET assumes no responsibility for any errors which may appear here and reserves the right to make changes without notice. Please consult CET or your local representative for the latest product specifications.
Standards Compliance
DANGER
This symbol indicates the presence of danger that may result in severe injury or death and permanent equipment damage if proper precautions are not taken during the installation, operation or maintenance of the device.
CAUTION
This symbol indicates the potential of personal injury or equipment damage if proper precautions are not taken during the installation, operation or maintenance of the device.
Page 3
CET Inc.
3
DANGER
Failure to observe the following instructions may result in severe injury or
death and/or equipment damage.
Installation, operation and maintenance of the meter should only be performed by qualified, competent personnel that have the appropriate training and experience with high voltage and current devices. The meter
must be installed in accordance with all local and national electrical codes.
Ensure that all incoming AC power and other power sources are turned OFF
before performing any work on the meter.
Before connecting the meter to the power source, check the label on top of the meter to ensure that it is equipped with the appropriate power supply, and
the correct voltage and current input specifications for your application.
During normal operation of the meter, hazardous voltages are present on its terminal strips and throughout the connected potential transformers (PT) and
current transformers (CT). PT and CT secondary circuits are capable of
generating lethal voltages and currents with their primary circuits energized. Follow standard safety precautions while performing any installation or service
work (i.e. removing PT fuses, shorting CT secondaries, …etc).
Do not use the meter for primary protection functions where failure of the device can cause fire, injury or death. The meter should only be used for
shadow protection if needed.
Under no circumstances should the meter be connected to a power source if
it is damaged.
To prevent potential fire or shock hazard, do not expose the meter to rain or
moisture.
Setup procedures must be performed only by qualified personnel familiar with
the instrument and its associated electrical equipment.
DO NOT open the instrument under any circumstances.
Page 4
CET Inc.
4
Limited warranty
CET offers the customer a minimum of 12-month functional warranty on the meter for faulty parts or workmanship from the date of dispatch from the
distributor. This warranty is on a return to factory for repair basis.
CET does not accept liability for any damage caused by meter malfunctions. CET accepts no responsibility for the suitability of the meter to the application for
which it was purchased.
Failure to install, set up or operate the meter according to the instructions herein
will void the warranty.
Only CET’s duly authorized representative may open your meter. The unit should only be opened in a fully anti-static environment. Failure to do so may
damage the electronic components and will void the warranty.
Page 5
CET Inc.
5
Table of Contents
Chapter 1 Introduction ........................................................................................................................ 8
1.1 Overview.............................................................................................................................. 8
1.2 Features ............................................................................................................................... 8
1.3 PMC-340’s application in Power and Energy Management Systems ............................... 10
1.4 Getting more information ................................................................................................. 11
Chapter 2 Installation ........................................................................................................................ 12
2.1 Appearance ....................................................................................................................... 12
2.2 Unit Dimensions ................................................................................................................ 12
2.3 Terminal Dimensions ......................................................................................................... 13
2.4 Mounting ........................................................................................................................... 13
2.5 Wiring Connections ........................................................................................................... 14
2.5.1 Direct Input Wiring ................................................................................................. 14
2.5.2 CT Input Wiring ...................................................................................................... 14
2.6 RS-485 Wiring .................................................................................................................... 15
2.7 Digital Input Wiring ........................................................................................................... 15
2.8 Pulse Output Wiring .......................................................................................................... 15
Chapter 3 Front Panel ....................................................................................................................... 16
3.1 LED Indicator ..................................................................................................................... 16
3.2 Buttons .............................................................................................................................. 16
3.3 LCD Display ........................................................................................................................ 17
3.4 LCD Testing ........................................................................................................................ 17
3.5 Default Display .................................................................................................................. 17
3.6 Setup Configuration .......................................................................................................... 18
3.6.1 Functions of buttons .............................................................................................. 18
3.6.2 Setup Menu ............................................................................................................ 20
3.6.3 Configuration .......................................................................................................... 20
Chapter 4 Applications ...................................................................................................................... 23
4.1 Inputs and Outputs ........................................................................................................... 23
4.1.1 Digital Inputs (PMC-340B Only) ............................................................................. 23
4.1.2 Energy Pulse Output .............................................................................................. 23
4.2 Power and Energy ............................................................................................................. 24
4.2.1 Basic Measurements .............................................................................................. 24
4.2.2 Energy Measurements ........................................................................................... 24
4.2.3 Demand Measurements ........................................................................................ 24
4.3 Power Quality .................................................................................................................... 25
4.3.1 Phase Angles .......................................................................................................... 25
4.3.2 Power Quality Parameters ..................................................................................... 25
4.3.3 Unbalance .............................................................................................................. 26
4.4 Logging .............................................................................................................................. 27
4.4.1 Max./Min. Log ........................................................................................................ 27
4.4.2 Monthly Energy Log ............................................................................................... 27
4.4.3 Peak Demand Log ................................................................................................... 28
Page 6
CET Inc.
6
4.4.4 SOE Log (PMC-340B Only) ...................................................................................... 28
4.4.5 Data Recorder Log (PMC-340B Only) ..................................................................... 28
4.5 Time of Use (TOU) ............................................................................................................. 29
Chapter 5 Modbus Register Map ....................................................................................................... 31
5.1 Basic Measurements ......................................................................................................... 31
5.2 Energy Measurements ...................................................................................................... 33
5.2.1 3-Phase Energy Measurements ............................................................................. 33
5.2.2 Phase A (L1) Energy Measurements ...................................................................... 34
5.2.3 Phase B (L2) Energy Measurements ...................................................................... 34
5.2.4 Phase C (L3) Energy Measurements ...................................................................... 35
5.3 DI Pulse Counter (PMC-340B Only) ................................................................................... 35
5.4 Harmonic Measurements ................................................................................................. 35
5.4.1 Power Quality Measurements ............................................................................... 35
5.4.2 Current Harmonic Measurements ......................................................................... 36
5.4.3 Voltage Harmonic Measurements ......................................................................... 36
5.5 Demands............................................................................................................................ 36
5.5.1 Present Demands ................................................................................................... 36
5.5.2 Peak Demand Log of This Month (Since Last Reset) ............................................. 37
5.5.3 Peak Demand Log of Last Month (Before Last Reset) ........................................... 37
5.6 Max./Min. Log ................................................................................................................... 38
5.6.1 Max. Log of This Month (Since Last Reset) ............................................................ 38
5.6.2 Min. Log of This Month (Since Last Reset)............................................................. 38
5.6.3 Max. Log of Last Month (Before Last Reset) .......................................................... 39
5.6.4 Min. Log of Last Month (Before Last Reset) .......................................................... 40
5.6.5 Max./Min. Log Structure ........................................................................................ 41
5.7 Monthly Energy Log .......................................................................................................... 41
5.8 SOE Log (PMC-340B Only) ................................................................................................. 42
5.9 Data Recorder Log (PMC-340B Only) ................................................................................ 43
5.10 Device Setup .................................................................................................................... 44
5.10.1 Basic Setup Parameters ........................................................................................ 44
5.10.2 I/O Setup .............................................................................................................. 45
5.10.3 Communication Setup Parameters ...................................................................... 45
5.11 Data Recorder Setup (PMC-340B Only) .......................................................................... 46
5.12 TOU Setup........................................................................................................................ 46
5.12.1 Basic...................................................................................................................... 46
5.12.2 Season .................................................................................................................. 47
5.12.3 Daily Profile .......................................................................................................... 48
5.12.4 Alternate Days ...................................................................................................... 49
5.13 Time ................................................................................................................................. 50
5.14 Clear/Reset Control ......................................................................................................... 51
5.15 Meter Information .......................................................................................................... 52
Appendix A Data Recorder Parameter List ......................................................................................... 53
Appendix B Technical Specifications .................................................................................................. 55
Appendix C Standards of Compliance ................................................................................................ 56
Page 7
CET Inc.
7
Appendix D Ordering Guide .............................................................................................................. 57
Contact us ......................................................................................................................................... 58
Page 8
CET Inc.
8
Chapter 1 Introduction
This manual explains how to use the PMC-340 Series Digital Three-Phase Energy Meter. Throughout the manual the term “meter” generally refers to all models.
This chapter provides an overview of the PMC-340 meter and summarizes many of its key features.
1.1 Overview
The PMC-340 Series Digital Three-Phase Energy Meter is CET’s latest offer for the low voltage power/energy metering market featuring DIN rail mount, high accuracy, multifunction measurements and a large, easy to read LCD display. The PMC-340 complies with the IEC 62053-21 Class 1 and IEC 62053-22 Class 0.5S kWh Accuracy Standards for 100A Direct Input and 5A CT Input, respectively. The PMC-340 comes standard with a LED as well as a Solid State Pulse Output for energy pulsing. The PMC-340 optionally provides 2MB memory for Data Recording and 3 Digital Inputs for status monitoring, Tariff switching or pulse counting for collecting WAGES (Water, Air, Gas, Electric and Steam) information. The standard RS-485 port and Modbus protocol support allows the PMC-340 to become a vital component of an intelligent, multifunction monitoring solution for any Power and Energy Management Systems.
You can setup the meter via our free PMC Setup software. The meter is also supported by our PecStar® Integrated Energy Management System.
The PMC-340 is available in two models: PMC-340A and PMC-340B. Following is a list of typical applications for the PMC-340:
DIN rail mount energy metering Industrial and commercial metering Substation, building and factory automation Sub-metering Power quality monitoring
1.2 Features
Ease of use
Easy to read LCD Two LED indicators for energy pulsing and communications activities Password-protected setup via front panel or free PMC Setup software Easy installation with DIN rail mounting, no tools required 3-phase power supply, no external control power required
Basic Measurements
Multifunction measurements
o Voltage, Current, kW, kvar, kVA, PF, Phase Angle and Frequency o Per phase kWh and kvarh Imp/Exp/Tot/Net and kVAh o 4-Quadrant kvarh o Device Operating Time (Running Hour) o Voltage/Current THD, THOD, THED, Individual harmonics up to 31
st
and Unbalance
o Current TDD, TDD Odd, TDD Even, K-factor and Crest Factor o kW/kvar/kVA Total Demands. Max. Demands and Max Demands per Tariff
Page 9
CET Inc.
9
o Per Phase Current Demands and Max. Demands o Max./Min. Log
Two TOU schedules, each providing
o 12 Seasons o 20 Daily Profiles, each with 12 Periods in 15-minute interval o 90 Holidays or Alternate Days o 4 Tariffs, each providing the following information
o kWh/kvarh Imp/Exp, kVAh o kW/kvar/kVA Max. Demands of This Month (Since Last Reset) and Last Month (Before
Last Reset)
12 monthly recording of kWh/kvarh Import/Export/Total/Net, kVAh, kvarh Q1-Q4 as well as
kWh/kvarh Import/Export and kVAh per Tariff
Front Panel & Communication Programming Counters (PMC-340B only)
SOE Log (PMC-340B only)
16 events time-stamped to ±1ms resolution Setup changes, Digital Input status changes
Data Recorder (PMC-340B only)
One Data Recorder Log of maximum 16 parameters Recording Interval from 1s to 40 days Configurable Depth and Recording Offset 2MB Log Memory
Digital Inputs (PMC-340B only)
3 channels for external status monitoring, pulse counting and Tariff switching Self-excited, internally wetted at 24VDC 1000Hz sampling
Energy Pulse Outputs
1 LED Pulse Output on the front panel for energy pulsing application 1 Solid State Digital Relay Output for energy pulsing application
Communications
Optically isolated RS-485 port, baud rate from 1,200 to 19,200 bps Modbus RTU protocol
Real-time Clock
Battery-backed real-time clock @ 6ppm Clock error ≤ 0.5s/day Can be set through front panel or communication
System Integration
Supported by our PecStar® iEMS and PMC Setup Easy integration into other Automation or SCADA systems via Modbus RTU protocol
Page 10
CET Inc.
10
Features and Options List
Features and Options
PMC-340 Models
A
B
Real-time Measurements
Uln/Ull per phase and Average
Current per phase and Average, In
kW/kvar/kVA per phase and Total
PF per phase and Total
Frequency
Demands and Peak Demands
Energy Measurements (per phase and 3-phase total)
kWh Imp, Exp, Net, Total
kvarh Imp, Exp, Net, Total
kVAh Total
4-Quadrant kvarh
TOU Energy (4 Tariffs)
Power Quality
Voltage and Current Unbalance
  THD, THOD, THED, K-Factor, Crest-Factor, TDD
Individual Harmonics (2nd to 31st)
Logging
Max./Min. & Peak Demand Recording
12 Monthly Energy Log
SOE Log
-
Data Recorder Log with 2MB Memory
-
Inputs and Outputs
DI
- 3 Energy Pulse Output (Solid State Relay)
1
1
LED Energy Pulse Output
1
1
Communications
RS-485 Port
1.3 PMC-340’s application in Power and Energy Management Systems
The PMC-340 series meter can be used to monitor Wye connected power system. Modbus communications allow real-time data and other information to be transmitted across a RS-485 network to an Integrated Energy Management System such as PecStar® iEMS.
Page 11
CET Inc.
11
1.4 Getting more information
Additional information is available from CET via the following sources:
Visit www.cet-global.com Contact your local representative Contact CET directly via email at support@cet-global.com
Page 12
CET Inc.
12
Chapter 2 Installation
2.1 Appearance
Figure 2-1 Appearance
2.2 Unit Dimensions
Front View Side View
Figure 2-2 Dimensions
Caution
Installation of the PMC-340 should only be performed by qualified, competent personnel that have the appropriate training and experience with high voltage and current devices.
The meter must be installed in accordance with all local and national electrical codes.
During the operation of the meter, hazardous voltages are present at the input terminals. Failure to observe precautions can result in serious or even fatal injury and equipment
damage.
Page 13
CET Inc.
13
2.3 Terminal Dimensions
Figure 2-3 Terminal Dimensions
Terminal
Terminal Dimension (mm)
Wire Size (mm2)
Max. Torque
1
L1, L2, L3, N
9.5 x 11.0
35.0
25.0 kgf.cm/M6
2
Voltage Inputs
2.5 x 2.8
1.5
4.5 kgf.cm/M2.5 (3.9 lb-in)
3
Pulse Outputs
4
Digital Inputs
5
RS-485
6
L1’, L2’, L3’, N
9.5 x 11.0
35.0
25.0 kgf.cm/M6
Table 2-1 Terminal Dimensions
2.4 Mounting
The PMC-340 should be installed in a dry environment with no dust and kept away from heat, radiation and electrical noise source. Installation steps:
Before installation, make sure that the DIN rail is already in place Move the installation clips at the back of the PMC-340 downward to the “unlock” position Align the top of the mounting channel at the back of the PMC-340 at an angle against the top of
the DIN rail as shown in Figure 2-4 below
Rotate the bottom of the PMC-340 towards the back while applying a slight pressure to make
sure that the device is completely and securely fixed on to the DIN rail
Push the installation clips upward to the “lock” position to secure the PMC-340 on to the DIN Rail
Figure 2-4 Installation
Page 14
CET Inc.
14
2.5 Wiring Connections
The PMC-340 supports 100A Direct Input or 5A CT Input. Please read this section carefully before installation and choose the correct wiring method for your power system.
2.5.1 Direct Input Wiring
1P3W
3P3W
3P4W
1P2W L-L*
1P2W L-N*
* The wiring modes 1P2W L-N and 1P2W L-L are not supported by PMC-340A.
Figure 2-5 Direct Input connections
2.5.2 CT Input Wiring
1P3W with 2CTs
3P3W with 3CTs
3P3W with 2CTs
Page 15
CET Inc.
15
3P4W with 3CTs
1P2W L-L with 1CT*
1P2W L-N with 1CT*
* The wiring modes 1P2W L-N and 1P2W L-L are not supported by PMC-340A.
Figure 2-6 CT Input connections
2.6 RS-485 Wiring
The PMC-340 provides one standard RS-485 port that supports the Modbus RTU protocol. Up to 32 devices can be connected on a RS-485 bus. The overall length of the RS-485 cable connecting all devices should not exceed 1200m.
If the master station does not have a RS-485 communications port, a RS-232/RS-485 or USB/RS-485 converter with optically isolated outputs and surge protection should be used. The following figure illustrates the RS-485 connections on the PMC-340.
Figure 2-7 RS-485 Connections
2.7 Digital Input Wiring
The following figure illustrates the Digital Input connections on the PMC-340:
Figure 2-8 DI Connections
2.8 Pulse Output Wiring
The following figure illustrates the Pulse Output connections on the PMC-340:
Figure 2-9 Energy Pulse Output Connections
Page 16
CET Inc.
16
Chapter 3 Front Panel
The meter’s LCD display and two buttons are used for both data display and setup configuration purposes.
Figure 3-1 Front Panel Display
3.1 LED Indicator
There are two LED indicators on the PMC-340’s front panel as described below:
LED Indicator
Description
Pulse
LED Energy Pulse Output
Comm.
Communications Activities Indicator
Table 3-1 LED Indicators
3.2 Buttons
Buttons
Data Display Mode
Setup Configuration Mode
<>
The Default Display shows the kWh Import measurement under the Energy menu. Pressing this button scrolls through the available measurements in this menu (see Table 3-4 below).
While at a particular menu, pressing this button scrolls through the available measurements.
Before an item is selected, pressing this button scrolls to the next setup parameter. If the selected parameter is a numeric value, pressing this button increments the selected digit. If the selected parameter is an enumerated value, pressing this button scrolls through the selection list.
<>
Pressing this button at any time while in Data Display mode will jump to the next available menu item (see Table 3-4) depending on where the display is at the time.
For example, if the display currently shows Ib under the U/I menu, pressing <> now will immediately jump to the Power menu.
Pressing this button for two seconds toggles between Data Display mode and Setup
Configuration mode. Once inside the Setup Configuration mode, pressing this
button selects a parameter for modification. Once selected, the parameter value blinks while it’s being changed.
If the selected parameter is a numeric value, the cursor is at the right most digit by default. Pressing this button moves the cursor one position to the left. Once the cursor has reached the left most digit, pressing this button again will save the current numeric value into memory.
Table 3-2 Buttons Description
Page 17
CET Inc.
17
3.3 LCD Display
The PMC-340 comes standard with a large, easy to read LCD display.
Figure 3-2 LED Display
The following table shows the LCD display symbols:
Symbol
Description
Phase Indicator
Active Tariff Indicator where Tx indicates Tariff x
Quadrant Indicator
Total Harmonic Distortion/Demand/Unbalance Indicators
Communication Activities Indicator
Setpoint Alarm Indicator
DI status
DO status
Main Display Area for Measurements/Time/Version information
kxh Import/Export/Net/Total/Average Indicators
Max./Min. Indicators
Units
Table 3-3 LCD Display Symbols
Throughout this document, the phase-to-neutral notations of A/B/C and L1/L2/L3 as well as the phase­to-phase notations of AB/BC/CA and L12/L23/L31 may be used interchangeably for specifying a certain parameter to be a phase-to-neutral or phase-to-phase value, respectively.
3.4 LCD Testing
Pressing both the <> and the <> buttons simultaneously for 2 seconds enters the LCD Test mode. During testing, all LCD segments are illuminated and will blink on and off three times before returning to the display screen before entering the LCD Test mode.
3.5 Default Display
The PMC-340 has a Default Display that shows the kWh Imp parameter under the Energy menu as shown below. The user can use the <> and <> buttons to scroll and display other parameters. If there is no front panel activity for 3 Seconds or longer, the display will return to the Default Display. Please refer to Section 3.2 above for a complete description of the front panel and button operations.
Page 18
CET Inc.
18
Figure 3-3 Default Display
The following table illustrates the menu options and the available measurements under each menu. Depending on the Wiring Mode selected, certain measurements may not be available. For example, the per-phase Uln, Uln Average, In, per-phase kW, kvar, kVA and PF measurements are not available when the Wiring Mode is set to 3P3W or 1P2W L-L.
Menu
Measurements
U/I
(Voltage/Current)
Uan
Ubn
Ucn
Uln Average
Uab
Ubc
Uca
Ull Average
Ia
Ib
Ic
I Average
In
Frequency
Voltage
Unbalance
Current
Unbalance
PoWEr
(Power)
kWa
kWb
kWc
kW Total
kvara
kvarb
kvarc
kvar Total
kVAa
kVAb
kVAc
kVA Total
PFa
PFb
PFc
PF Total
EnErGy
(Energy)
kWh Import
kWh Export
kWh Net
kWh Total
kvarh Import
kvarh Export
kvarh Net
kvarh Total
kVAh Total
ToU EnEr6y
(TOU Energy)
T1 kWh Import
T1 kWh Export
T2 kWh Import
T2 kWh Export
T3 kWh Import
T3 kWh Export
T4 kWh Import
T4 kWh Export
rEAL dMd (Demand)
Ia Demand
Ib Demand
Ic Demand
kW Total Demand
kvar Total Demand
kVA Total Demand
ToU dMd
(TOU DMD)
T1 kW Demand
T1 kvar Demand
T1 kVA Demand
T2 kW Demand
T2 kvar Demand
T2 kVA Demand
T3 kW Demand
T3 kvar Demand
T3 kVA Demand
T4 kW Demand
T4 kvar Demand
T4 kVA Demand
MAx dMd
(Max. DMD)
Ia Max. Demand
Ib Max. Demand
Ic Max. Demand
kW Total Max. Demand
kvar Total Max. Demand
kVA Total Max. Demand
T1 kW Max. Demand
T1 kvar Max. Demand
T1 kVA Max. Demand
T2 kW Max. Demand
T2 kvar Max. Demand
T2 kVA Max. Demand
T3 kW Max. Demand
T3 kvar Max. Demand
T3 kVA Max. Demand
T4 kW Max. Demand
T4 kvar Max. Demand
T4 kVA Max. Demand
THd
(THD)
Uan/Uab1 THD
Ubn/Ubc1 THD
Ucn/Uca1 THD
Ia THD
Ib THD
Ic THD
dI CoUnTer
(DI Counter)
DI1
DI2
DI3
Table 3-4 PMC-340 Data Display Pages
Notes:
1) When the Wiring Mode is 3P3W or 1P2W L-L, the phase A/B/C Voltage THD/TOHD/TEHD/HDxx
is phase AB/BC/CA Voltage THD/TOHD/TEHD/HDxx.
3.6 Setup Configuration
3.6.1 Functions of buttons
The two front panel buttons take on different meanings in the Setup Configuration mode:
<>: Pressing this button for two seconds toggles between Data Display and Setup
Page 19
CET Inc.
19
Configuration. Once inside Setup Configuration, pressing <> either enters a sub-
menu or selects a parameter for modification. If inside a sub-menu, pressing <> for two seconds will return to the main menu. If a parameter is selected, its value will blink while it’s being changed. If the parameter is a numeric value, pressing <> will move the cursor one digit to the left. When the left most digit has been reached, pressing <> again will save the current value into memory.
<>: Once inside Setup Configuration, pressing <> scrolls to the next setup parameter or
sub-menu. If the selected parameter is a numeric value, pressing <> increments the current digit. If the selected parameter is an enumerated value, pressing <> scrolls to the next item in the enumerated list. When finished, press <> to save the current value into memory.
Making setup changes:
Press <> for two seconds to enter Setup Configuration, and the LCD displays PROGRAM. Press <> to advance to the Password page. A correct password must be entered before changes are allowed. The factory default
password is 0000 (zero). Press the <> button to select the parameter for modification. Use <> and <> to enter the correct password.
Use <> to scroll to the desired sub-menu or setup parameter. Press <> to enter a sub-menu or select a setup parameter for modification. Once a parameter has been selected, its value will blink. Use <> and <> to make modification to the selected parameter. Press <> for two seconds to return to the main menu Press <> for two seconds again to exit the Setup Configuration mode.
Also the Setup Configuration will be automatically exited if there is a period of inactivity of 3 minute or longer.
Page 20
CET Inc.
20
3.6.2 Setup Menu
Figure 3-4 Setup Menu
3.6.3 Configuration
The Setup Configuration mode provides access to the following setup parameters:
Label
Description
Range
Default
Menu
Main Sub
ProGrAM
Setup Configuration
/
/
PW
Enter Password
0 to 9999
0
SET PW
Set New Password
Enter New Password
0 to 9999
0
SyS SET
Basic Parameters
TyPE
Set Meter’s wiring connection1
DEMO/1P3W/3P3W/
3P4W/1P2W L-N/
1P2W L-L
3P4W
CT1
Set CT Primary Ratio2
1 to 30,000 5 CT2
Set CT Secondary Ratio2
1 to 5 5 I1 rEv
Reverse Phase A CT Polarity
YES/NO
NO
I2 rEv
Reverse Phase B CT Polarity
YES/NO
NO
I3 rEv
Reverse Phase C CT Polarity
YES/NO
NO
PF
Set PF Convention3
IEC/IEEE/-IEEE
IEC
kvA
Set kVA Calculation Method4
V=Vector, S=Scalar
V
CoM SET
Comm. Parameters
Id
Set Meter Address
1 to 247
100
bAUd
Set Baud Rate in Bits Per Second (bps)
1200/2400/4800/
9600
Page 21
CET Inc.
21
9600/19200/38400
CFG
Set Comm. Port Data Format
8N2/8O1/8E1/
8N1/8O2/8E2
8E1
dMd SET
Demand Parameters
PErIod
Set Demand Period
1 to 60 (min)
15
nUM
Set No. of Sliding Windows
1 to 15
15
PULS SET
Energy Pulse
LEd
Enable LED Energy Pulsing
OFF / P / Q
P
do
Enable DO Energy Pulsing
OFF / P IMP / P EXP /
P TOT / Q IMP / Q EXP /
Q TOT / PPS5 / DMD6 /
TOU
7
P IMP
CnST
Select Pulse Constant
8
1/10/100/1000/3200
100
CLr SET
Clear Data
CLr EnGY
Clear All Energy
9
YES/NO
NO
CLr dMd
Clear All Demand
10
YES/NO
NO
CLr Mn
Clear All Max./Min.
11
YES/NO
NO
CLr dI
Clear All DI Counters
YES/NO
NO
TIME SET
Date and Time
dAT
Enter the Current Date
YY-MM-DD
/
Clk
Enter the Current Time
HH:MM:SS
/
InFo
View Meter Information (Read Only)
FW
Firmware Version
For example, 1.00.00
means the firmware
version is V1.10.00.
/
Pro
Protocol Version
e.g. 10 means V1.0
/
-
Firmware Update Date
e.g. 20140915 / -
Meter Serial Number
e.g. 1409005094
/
FCnT
Counter for Important Setup Parameter
Changes via Front Panel
12
/ / CCnT
Counter for Important Setup Parameter
Changes via Communications
12
/
/
Table 3-3 Setup Parameters
Notes:
1) The wiring modes 1P2W L-N and 1P2W L-L are not supported by PMC-340A.
2) This screen only appears if the PMC-340 is equipped with CT Inputs.
3) Power Factor Convention
Page 22
CET Inc.
22
Figure 3-5 PF Convention
4) There are two ways to calculate kVA:
Mode V (Vector method):
2
2
totaltotal
kvarkWkVA
total
Mode S (Scalar method):
c
kVAkVAkVAkVA
ba
total
5) PPS: 1 Pulse Per Second.
6) DMD: 1 pulse is generated at the end of every Demand Interval.
7) Tariff Switch: 1 pulse is generated every time a Tariff Switch takes place based on TOU Schedule.
8) The Pulse Constant setup parameter can be configured as 1/10/100 pulses per kXh for 100A Direct
Input option and 1000/3200 pulses per kXh for 5A CT Input option, respectively, where kXh may be kWh or kvarh.
9) Select CLr EnGY to clear 3-Phase Total Energy registers, Phase A/B/C Energy registers, Monthly
Energy Log of the Present Month and the last 1 to 12 months.
10) Select CLr dMd to clear Present Demand, Peak Demand log of This Month (Since Last Reset) and
Peak Demand log of Last Month (Before Last Reset).
11) Select CLr Mn to clear all Max./Min. Log, including Max./Min. Log of This Month (Since Last Reset)
and Max./Min. Log of Last Month (Before Last Reset).
12) Please see Section 5.1 Basic Measurement Note 1) for more information.
Page 23
CET Inc.
23
Chapter 4 Applications
4.1 Inputs and Outputs
4.1.1 Digital Inputs (PMC-340B Only)
The PMC-340B comes standard with three self-excited Digital Inputs that are internally wetted at 24 VDC. Digital Inputs on the PMC-340B can be used in the following applications:
1) Digital Input The digital inputs are typically used for status monitoring which can help
prevent equipment damage, improve maintenance, and track security breaches. The real-time statuses of the Digital Inputs are available on the front panel LCD Display as well as through communications. Changes in Digital Input status are stored as events in the SOE Log in 1 ms resolution.
2) Pulse Counting Pulse counting is supported with programmable pulse weight and facilitates
WAGES (Water, Air, Gas, Electricity and Steam) information collection.
3) Tariff Switching Up to 2 Digital Inputs may be used to select to which of the 4 Tariffs the
energy consumption should be accumulated. The 2 Digital Inputs (DI1 and DI2) represent 2 binary digits where Tariff 1=00, Tariff 2=01, Tariff 3= 10 and Tariff 4=11 where the least significant digit represents DI1 and the most significant digit represents DI2. The DI1 Function setup register must first be programmed as a Tariff Switch before configuring DI2 with the same function. In other words, if DI1 is configured as a Digital Input or Energy Pulse Counter and DI2 is configured as a Tariff Switch, the TOU will continue to function based on the TOU Schedule. This feature is available in Firmware V1.00.01. Tariff switching as a result of DI changes will be stored as an event in the SOE Log.
The following table describes the DI setup parameters that can be programmed over communications:
Setup Parameter
Definition
Options
DIx Function
Each DI can be configured as a Status Input or Pulse Counter. Only DI1 and DI 2 can be set to Tariff Switch.
0=Status Input*
1=Pulse Counter
2=Tariff Switch
DIx Debounce
Specifies the minimum duration the DI must remain in the Active or Inactive state before a DI state change is considered to be valid.
1 to 1000 (ms)
(Default=20ms)
DIx Pulse Weight
Specifies the incremental value for each received pulse. This is only used when a DI is configured as a Pulse Counter.
1* to 1,000,000
*Default
Table 4-1 DI Setup Parameters
4.1.2 Energy Pulse Output
The PMC-340 comes standard with one front panel LED Pulse Output and one Solid State Relay Output for energy pulsing. Energy Pulse Output is typically used for accuracy testing. Energy Pulsing can be enabled from the front panel through the Energy Pulse setup parameter. The pulse constant can be configured through the Pulse Constant setup parameter as 1/10/100 pulses per kXh for the 100A Direct Input option and 1000/3200 pulses per kXh for the 5A CT Input option, respectively, where kXh may be kWh or kvarh.
Page 24
CET Inc.
24
4.2 Power and Energy
4.2.1 Basic Measurements
The PMC-340 provides the following basic measurements which can be retrieved via the Front panel or communication:
Parameter
Phase A
Phase B
Phase C
Total
Average
Uln ● - ● Ull ● - ● Current
- ●
kW ● - kvar ● - kVA ●
-
Power Factor
● ● ● ● -
Frequency
- - - -
Table 4-2 Basic Measurements
4.2.2 Energy Measurements
The PMC-340 provides Energy measurements for active energy (kWh), reactive energy (kvarh) and apparent energy (kVAh) with a resolution of 0.01 kxh and maximum value of 10,000,000.00. When the maximum value is reached, the energy registers will automatically roll over to zero. The energy can be reset manually through the front panel or communication.
The PMC-340 provides the following energy measurements:
3-Phase Energy
kWh Import/Export/Net/Total kWh Import/Export of Tariff 1/2/3/4
kvarh Import/Export/Net/Total kvarh Import/Export of Tariff 1/2/3/4 kvarh of Q1/Q2/Q3/Q4
kVAh Total
Per-Phase Energy
(Phase A/B/C):
kWh Import/Export/Net/Total kWh Import/Export of Tariff 1/2/3/4
kvarh Import/Export/Net/Total kvarh Import/Export of Tariff 1/2/3/4 kvarh of Q1/Q2/Q3/Q4
kVAh
Table 4-3 Energy Measurement
4.2.3 Demand Measurements
Demand is defined as the average power consumption over a fixed interval (usually 15 minutes) based on the sliding window method. The PMC-340 provides the following Demand and Peak Demand measurements:
Demands
Ia, Ib, Ic
kW Total, kvar Total, kVA Total
Peak Demands
Ia, Ib, Ic
kW Total, kvar Total, kVA Total
kW Total, kvar Total and kVA Total for each Tariff
Table 4-4 Demand Measurement
The PMC-340 provides the following Demand setup parameters:
Setup Parameter
Definition
Options
Demand Period
1 to 60 minutes. For example, if the # of Sliding Windows is set as 1 and the Demand Period is 15, the demand cycle will be 1×15=15min.
1 to 60 minutes Default=15
# of Sliding Windows
Number of Sliding Windows.
1 to 15 Default=1
Page 25
CET Inc.
25
Self-Read Time
The Self-Read Time allows the user to specify the time and day of the month for the Peak Demand Self-Read operation. The Self-Read Time supports three options:
A zero value means that the Self-Read will take place at
00:00 of the first day of each month.
A non-zero value means that the Self-Read will take place
at a specific time and day based on the formula: Self-Read Time = Day x 100 + Hour where 0 ≤ Hour ≤ 23 and 1 ≤ Day ≤ 28. For example, the value 1512 means that the Self­Read will take place at 12:00pm on the 15th day of each month.
A 0xFFFF value will disable the Self-Read operation and
replace it with manual operation. A manual reset will cause the Max. Demand of This Month to be transferred to the Max. Demand of Last Month and then reset. The terms This Month and Last Month will become Since Last Reset and Before Last Reset.
Default=0xFFFF
Table 4-5 Demand Setup
4.3 Power Quality
4.3.1 Phase Angles
Phase analysis is used to identify the angle relationship between 3-phase Voltages and Currents.
For WYE connected systems, the per phase difference of the Current and Voltage angles should correspond to the per phase PF. For example, if the PF is 0.5 Lag and the Voltage phase angles are
0.0°, 240.0° and 120.0°, the Current phase angles should have the values of -60.0°, 180.0° and 60.0°.
4.3.2 Power Quality Parameters
The PMC-340 provides the following PQ parameters:
4.3.2.1 Harmonics
The PMC-340 provides THD, TOHD, TEHD and individual harmonics up to the 31st order. All harmonic parameters are available through communication while THDs are available on the front panel display. In addition, the PMC-340 also provides TDD, K-factor and Crest-factor measurements for Current, which are only available through communication.
4.3.2.2 TDD
Total Demand Distortion (TDD) is defined as the ratio of the root mean square (RMS) of the harmonic
current to the root mean square value of the rated or maximum demand fundamental current, expressed as a percentage. TDD of the Current I is calculated by the formula below:
where
IL = maximum demand of fundamental current h = harmonic order I
h
= rms load current at the harmonic order h
4.3.2.3 K-Factor
Page 26
CET Inc.
26
K-Factor is defined as the weighted sum of the harmonic load currents according to their effects on
transformer heating, as derived from ANSI/IEEE C57.110. A K-Factor of 1.0 indicates a linear load (no harmonics). The higher the K-Factor, the greater the harmonic heating effects.
)(
)(
K
2
hh
1h
2
hh
1h
max
max
h
h
I
hI
Factor
where
Ih = hth Harmonic Current in RMS h
max
= Highest harmonic order
4.3.2.4 Crest Factor
Crest Factor is defined as the Peak to Average Ratio (PAR), and its calculation is illustrated below:
x
x
rms
peak
C
where
|X|
peak
= Peak amplitude of the waveform
X
rms
= RMS value
The following table illustrates the available Voltage and Current Harmonic measurements on the PMC-
340.
Phase A/AB
Phase B/BC
Phase C/CA
Harmonic-Voltage
THD
THD
THD
TEHD
TEHD
TEHD
TOHD
TOHD
TOHD
2
nd
Harmonics
2
nd
Harmonics
2nd Harmonics
31st Harmonic
31st Harmonic
31st Harmonic
Harmonic-Current
THD
THD
THD
TEHD
TEHD
TEHD
TOHD
TOHD
TOHD
TDD
TDD
TDD
TEDD
TEDD
TEDD
TODD
TODD
TODD
K-factor
K-factor
K-factor
Crest-factor
Crest-factor
Crest-factor
2
nd
Harmonics
2
nd
Harmonics
2nd Harmonics
31st Harmonic
31st Harmonic
31st Harmonic
Table 4-6 Harmonic Measurements
4.3.3 Unbalance
The PMC-340 provides Voltage and Current Unbalance measurements. The calculation method of Voltage and Current Unbalance are listed below:
Voltage Unbalance =
100%
V1
V2
Current Unbalance =
100%
I1
I2
Page 27
CET Inc.
27
where
V1, V2 are the Positive and Negative Sequence Components for Voltage, respectively.
and
I1, I2 are the Positive and Negative Sequence Components for Current, respectively.
4.4 Logging
4.4.1 Max./Min. Log
The PMC-340 records the Max. Log and Min. Log of This Month (Since Last Reset) and Last Month (Before Last Reset) with timestamp for 44 parameters. Each log includes the relevant parameter
value and its timestamp. The recorded data is stored in non-volatile memory and will not suffer any loss in the event of a power failure. The PMC-340’s Max./Min. Log records the following parameters:
Max./Min. Parameters
Ia
Ib
Ic
I avg
Uan
Ubn
Ucn
Uln avg
Uab
Ubc
Uca
Ull avg
kWa
kWb
kWc
kW Total
kvara
kvarb
kvarc
kvar Total
kVAa
kVAb
kVAc
kVAc
PFa
PFb
PFc
PF Total
Frequency
I4
Ia THD
Ib THD
Ic THD
Uan/Uab THD
Ubn/Ubc THD
Ucn/Uca THD
Ia K-Factor
Ib K-Factor
Ic K-Factor
Ia Crest-factor
Ib Crest-factor
Ic Crest-factor
U Unbal.
I Unbal.
Table 4-7 Max./Min. Measurements
The same Self-Read Time for the Peak Demand Log is used to specify the time and day of the month for the Max./Min. Self-Read operation. Please refer to Section 4.5 for a complete description of the Self-Read Time and its operation. The Max./Min. Log of This Month can be reset manually from the front panel or via communications.
4.4.2 Monthly Energy Log
The PMC-340 stores monthly energy data for the present month and the last 12 months. The Monthly Energy Log Self-read Time setup parameter allows the user to specify the time and day of the month for the Recorder’s Self-read operation via communications. The Monthly Energy Logs are stored in the meter’s non-volatile memory and will not suffer any loss in the event of power failure, and they are stored on a first-in-first-out basis where the newest log will overwrite the oldest.
The Monthly Energy Log Self-Read Time supports two options:
A zero value means that the Self-Read will take place at 00:00 of the first day of each month.
A non-zero value means that the Self-Read will take place at a specific time and day based on the
formula: Energy Self-Read Time = Day x 100 + Hour where 0 ≤ Hour ≤ 23 and 1 ≤ Day ≤ 28. For example, the value 1512 means that the Self-Read will take place at 12:00pm on the 15th day of each month.
The Monthly Energy Logs can be reset manually through the front panel or via communications. The PMC-330 provides the following energy data for the present month and the last 12 months:
Active Energy
kWh Import
kWh Export
kWh Net
kWh Total
T1 kWh Import
T2 kWh Import
T3 kWh Import
T4 kWh Import
T1 kWh Export
T2 kWh Export
T3 kWh Export
T4 kWh Export
Reactive Energy
kvarh Import
kvarh Export
kvarh Net
kvarh Total
T1 kvarh Import
T2 kvarh Import
T3 kvarh Import
T4 kvarh Import
T1 kvarh Export
T2 kvarh Export
T3 kvarh Export
T4 kvarh Export
kvarh Q1
kvarh Q2
kvarh Q3
kvarh Q4
Page 28
CET Inc.
28
Apparent Energy
kVAh
Table 4-8 Energy Measurements for each Monthly Energy Log Record
4.4.3 Peak Demand Log
The PMC-340 records the Peak Demand of This Month (Since Last Reset) and Last Month (Before Last Reset) with timestamp for Ia, Ib, Ic, kW Total, kvar Total and kVA Total as well as kW Total, kvar Total
and kVA Total for TOU Tariffs 1 to 4. All Peak Demand information can be accessed through the front panel as well as communications. Please refer to Section 4.5 for a complete description of the Self-
Read Time and its operation.
Peak Demand Logs of This Month (Since Last Reset) and Last Month (Before Last Reset)
Ia
Ib
Ic
kW Total
kvar Total
kVA Total
kW Total for TOU Tariffs 1 to 4
kvar Total for TOU Tariffs 1 to 4
kVA Total for TOU Tariffs 1 to 4
Table 4-9 Peak Demand
4.4.4 SOE Log (PMC-340B Only)
The PMC-340B’s SOE Log can store up to 16 events such as Power-On, Power-Off, Digital Input status changes and setup changes in its non-volatile memory. Each event record includes the event classification, its relevant parameter values and a timestamp in ±1 ms resolution.
All events can be retrieved via communications for display. If there are more than 16 events, the newest event will replace the oldest event on a first-in-first-out basis. The SOE Log can be reset from via communications.
4.4.5 Data Recorder Log (PMC-340B Only)
The PMC-340B comes equipped with 2MB of memory and provides one Data Recorder capable of recording a maximum of 16 parameters. The Data Recorder Log is stored in the device’s non-volatile memory and will not suffer any loss in the event of a power failure.
The programming of the Data Recorder is only supported over communication. The Data Recorder provides the following setup parameters:
Setup Parameters
Value/Option
Default
Trigger Mode
0=Disabled / 1=Triggered by Timer
1
Recording Mode
0=Stop-When-Full / 1=First-In-First-Out
1
Recording Depth
1 to 28,400 (entry)
28,400
Recording Interval
1 to 3,456,000 seconds
900 s
Offset Time
0 to 43,200 seconds, 0 indicates no offset.
0
Number of Parameters
0 to 16
14
Parameter 1 to 16
See Appendix A
See 5.11
Table 4-10 Setup Parameters for Data Recorder
The Data Recorder Log is only operational when the values of Trigger Mode, Recording Mode, Recording Depth, Recording Interval, and Number of Parameters are all non-zero.
The Recording Offset parameter can be used to delay the recording by a fixed time from the Recording Interval. For example, if the Recording Interval parameter is set to 3600 (hourly) and the Recording
Page 29
CET Inc.
29
Offset parameter is set to 300 (5 minutes), the recording will take place at 5 minutes after the hour
every hour, i.e. 00:05, 01:05, 02:05…etc. The value of the Recording Offset parameter should be less than the Recording Interval parameter.
4.5 Time of Use (TOU)
Time-Of-Use (TOU) is used for electricity pricing that varies depending on the time of day, day of week, and the season. The TOU system allows the user to configure an electricity price schedule inside the PMC-340 and accumulate energy consumption into different TOU rates based on the time of consumption. TOU programming is only supported through communications.
The TOU feature on PMC-340 supports two TOU schedules, which can be switched at a pre-defined time. Each TOU schedule supporting:
Up to 12 seasons 90 Holidays or Alternate Days and 3 Weekdays 20 Daily Profiles, each with 12 Periods in 15-minute interval 4 Tariffs
Instead of using the TOU schedule to switch between Tariffs, the PMC-340 supports Tariff switching based on the status of DI1 to DI2, which is supported in Firmware V1.00.01 or later.
The 2 Digital Inputs (DI1 and DI2) represent 2 binary digits where Tariff 1=00, Tariff 2=01, Tariff 3= 10, and Tariff 4=11 where D1 represents the least significant digit and D2 represents the most significant digit. As soon as DI1 and/or DI2 are configured as Tariff Switches, the current TOU Tariff will be determined by the status of the DIs, and the TOU Schedule will be ignored. The DI1 Function setup register must first be programmed as a Tariff Switch before configuring DI2 with the same function. In other words, if DI1 is configured as a Digital Input or Energy Pulse Counter and DI2 is configured as a Tariff Switch, the TOU will continue to function based on the TOU Schedule. The number of Tariffs supported depends on how many DIs are programmed as a Tariff Switch as indicated in the following table.
Tariff
DI Function
DI1 = Tariff Switch
DI1 & DI2 = Tariff Switch
T1
DI1 (0=T1)
DI2 + DI1 (00=T1)
T2
DI1 (1=T2)
DI2 + DI1 (01=T2)
T3
Not Available
DI2 + DI1 (10=T3)
T4
Not Available
DI2 + DI1 (11=T4)
Table 4-11 DIs and the Number of Tariff Setup
Each TOU schedule has the following setup parameters and can only be programmed via communications:
Setup Parameters
Definition
Options
Daily Profile #
Specify a daily rate schedule which can be divided into a maximum of 12 periods in 15-min intervals. Up to 20 Daily Profiles can be programmed for each TOU schedule.
1 to 20, the first period starts at 00:00 and the last period end at 24:00.
Season #
A year can be divided into a maximum of 12 seasons. Each season is specified with a Start Date and ends with the next season’s Start Date.
1 to 12, starts from January 1st
Alternate Days #
A day can be defined as an Alternate Day, such as May 1st. Each Alternate Day is assigned with a Daily Profile.
1 to 90.
Day Types
Specify the day type of the week. Each day of a week can be assigned a Day Type such as Weekday1, Weekday2, Weekday3 and Alternate Day. The
Weekday1, Weekday2, Weekday3 and
Page 30
CET Inc.
30
Alternate Day has the highest priority.
Alternate Days
Switch Time
Specify when to switch from one TOU schedule to another. Writing 0xFFFFFFFF to this parameter disables switching between TOU schedules.
Format: YYYYMMDDHH
Table 4-12 TOU Setup Parameters
For each of the 4 Tariff Rates, the PMC-340 provides the following information:
Energy: kWh Import/Export, kvarh Import/Export, kVAh – Per Phase and Total
Peak Demand: kW/kvar/kVA of This Month (Since Last Reset) and Last Month (Before Last Reset). TOU data is available through communications.
Page 31
CET Inc.
31
Chapter 5 Modbus Register Map
This chapter provides a complete description of the Modbus register map (Protocol Version 1.0) for the PMC-340 to facilitate the development of 3rd party communications driver for accessing information on the PMC-340. For a complete Modbus Protocol Specification, please visit http://www.modbus.org. The PMC-340 supports the following Modbus functions:
1) Read Holding Registers (Function Code 0x03)
2) Preset Multiple Registers (Function Code 0x10)
The following table provides a description of the different data formats used for the Modbus registers:
Format
Description
UINT16/INT16
Unsigned/Signed 16-bit Integer
UINT32/INT32
Unsigned/Signed 32-bit Integer
Float
IEEE 754 32-bit
Single Precision Floating Point Number
5.1 Basic Measurements
Register
Property
Description
Format
Scale
Unit
Model
A B 0000
RO
Uan
Float
x1
V  
0002
RO
Ubn
Float
V  
0004
RO
Ucn
Float
V  
0006
RO
Uln Average
Float
V  
0008
RO
Uab
Float
V  
0010
RO
Ubc
Float
V  
0012
RO
Uca
Float
V  
0014
RO
Ull Average
Float
V  
0016
RO
Ia
Float
A  
0018
RO
Ib
Float
A  
0020
RO
Ic
Float
A  
0022
RO
I Average
Float
A  
0024
RO
kWa
Float
W  
0026
RO
kWb
Float
W  
0028
RO
kWc
Float
W  
0030
RO
kW Total
Float
W  
0032
RO
kvara
Float
var  
0034
RO
kvarb
Float
var  
0036
RO
kvarc
Float
var  
0038
RO
kvar Total
Float
var  
0040
RO
kVAa
Float
VA  
0042
RO
kVAb
Float
VA  
0044
RO
kVAc
Float
VA  
0046
RO
kVA Total
Float
VA  
0048
RO
PFa
Float
 
0050
RO
PFb
Float
 
0052
RO
PFc
Float
 
0054
RO
PF Total
Float
 
0056
RO
Frequency
Float
Hz  
0058
RO
Uan/Uab (3P3W) Angle
Float
0060
RO
Ubn/Ubc (3P3W) Angle
Float
0062
RO
Ucn/Uca (3P3W) Angle
Float
0064
RO
Ia Angle
Float
 
0066
RO
Ib Angle
Float
 
0068
RO
Ic Angle
Float
 
0070
RO
In (Calculated)
Float
A  
0072~0073
Reserved
0074
RO
Displacement PFa
Float
x1
-
0076
RO
Displacement PFb
Float
0078
RO
Displacement PFc
Float
0080~0093
Reserved
Page 32
CET Inc.
32
0092
RO
FP Counter
1
UINT16
x1
-
 0093
RO
Comm. Counter
1
UINT16
 0094
RO
SOE Log Pointer
2
UINT32 
0096
RO
Data Recorder Log Pointer
2
UINT32 
0098
Reserved
0099
RO
DI Status
3
Bitmap 
0100
Reserved
0101
RO
Wiring Diagnostic Status
4
Bitmap  
0102
Reserved
0104
RO
Device Operating Time
5
UINT32
x0.1
Hour
Table 5-1 Basic Measurements
Notes:
1) The FP Counter and Comm. Counter will be incremented every time some important setup
parameters, which may affect the accuracy of Energy registers and DI Pulse Counters or the way they are calculated, are changed via Front Panel or Communication, respectively. The FP Counter is incremented every time a relevant setup parameter is changed via the Front Panel, while the Comm. Counter is incremented every time a single packet is sent to change one or more relevant setup parameters through communications. The following actions may trigger these counters to increment:
Changing Setup Parameters:
o Wiring Mode, PT and CT ratios and I Polarities o DI setup parameters o Energy Pulse Constant o Preset Energy Value o Demand Period and No. of Sliding Windows o TOU setup registers o Manual Time Set (via Front Panel only)
Clear Actions via Front Panel:
o Clear All Energy o Clear All Demand o Clear All Max./Min. o Clear All DI Counters
Clear Actions via Communication:
o Clear Monthly Energy Log (Register 9600) o Clear Energy (Register 9601) o Clear Monthly Energy Log of Present Month (Register 9602) o Clear Peak Demand Log of This Month (Register 9603) o Clear All Demand Registers and Logs (Register 9604) o Clear Device Operating Time (Register 9607) o Clear All Data (Register 9608) o Clear DI1 Counter (Register 9609) (only when DI1 = Energy Pulse Counter) o Clear DI2 Counter (Register 9610) (only when DI2 = Energy Pulse Counter) o Clear DI3 Counter (Register 9611) (only when DI3 = Energy Pulse Counter)
2) The PMC-340 has one SOE Log and one DR Logs. Each of these logs has a Log Pointer that
indicates its current logging position. The range of the Log Pointer is between 0 and 0xFFFFFFFF, and it is incremented by one for every new log generated and will roll over to 0 if its current value is 0xFFFFFFFF. A value of zero indicates that the SOE or DR does not contain any Log. If a Clear Log is performed via communications, its Log Pointer will be reset to zero.
Use the following equation to determine the latest log location:
Latest Log Location = Modulo [Log Pointer / Log Depth] where Log Pointer may be the SOE Log Pointer or DR Log Pointer and Log Depth is as follows:
SOE Log Depth = 16 (fixed) DR Log Depth = DR Recording Depth (see Section 5.11 Data Recorder Setup)
3) For the DI Status register, the bit values of B0 to B2 represent the states of DI1 to DI3,
respectively, with “1” meaning active (closed) and “0” meaning inactive (open).
4) The following table illustrates the Wiring Diagnostic Status with 0 meaning Normal and 1 meaning
Page 33
CET Inc.
33
Abnormal:
Bit
Description
B00
Summary Bit (Set if any other bit is set)
B01
Frequency is out of range between 45 to 65Hz (3P4W and 3P3W)
B02
Any phase voltage < 10% of PT Primary (Register 6000) (3P4W only)
B03
Any phase current < 10% of CT Primary (Register 6004) (3P4W or 3P3W)
B04~B05
Reserved
B06
Voltage Phase Reversal (3P4W or 3P3W)
B07
Current Phase Reversal (3P4W or 3P3W)
B08
Negative kW Total may be abnormal (3P4W or 3P3W)
B09
Negative kWa is may be abnormal (3P4W only)
B10
Negative kWb may be abnormal (3P4W only)
B11
Negative kWc may be abnormal (3P4W only)
B12
CTa polarity may be reversed (3P4W only)
B13
CTb polarity may be reversed (3P4W only)
B14
CTc polarity may be reversed (3P4W only)
B15
Reserved
Table 5-2 Wiring Diagnostic Status Register
5) The Device Operating Time means the accumulated Operating Time whenever any per-phase
Current exceeds 2% of I
nominal
(5A), which is 100mA. The Device Operating Time data is stored
in non-volatile memory and will not suffer any loss in the event of a power failure.
5.2 Energy Measurements
The Energy registers have a maximum value of 1,000,000,000 and will roll over to zero automatically when it is reached. The actual energy value is 0.01 times of the register value.
5.2.1 3-Phase Energy Measurements
Register
Property
Description
Format
Scale
Unit
0500
RW
kWh Import
INT32
x0.01
kWh
0502
RW
kWh Export
INT32
0504
RO
kWh Net
INT32
0506
RO
kWh Total
INT32
0508
RW
kvarh Import
INT32
kvarh
0510
RW
kvarh Export
INT32
0512
RO
kvarh Net
INT32
0514
RO
kvarh Total
INT32
0516
RW
kVAh
INT32
kVAh
0518
RW
kvarh Q1
INT32
kvarh
0520
RW
kvarh Q2
INT32
0522
RW
kvarh Q3
INT32
0524
RW
kvarh Q4
INT32
0526
RW
kWh Import of T1
INT32
kWh
0528
RW
kWh Export of T1
INT32
0530
RW
kvarh Import of T1
INT32
kvarh
0532
RW
kvarh Export of T1
INT32
0534
RW
kVAh of T1
INT32
kVAh
0536
RW
kWh Import of T2
INT32
kWh
0538
RW
kWh Export of T2
INT32
0540
RW
kvarh Import of T2
INT32
kvarh
0542
RW
kvarh Export of T2
INT32
0544
RW
kVAh of T2
INT32
kVAh
0546
RW
kWh Import of T3
INT32
kWh
0548
RW
kWh Export of T3
INT32
0550
RW
kvarh Import of T3
INT32
kvarh
0552
RW
kvarh Export of T3
INT32
0554
RW
kVAh of T3
INT32
kVAh
0556
RW
kWh Import of T4
INT32
kWh
0558
RW
kWh Export of T4
INT32
0560
RW
kvarh Import of T4
INT32
kvarh
0562
RW
kvarh Export of T4
INT32
0564
RW
kVAh of T4
INT32
kVAh
Table 5-3 3-phase Energy Measurements
Page 34
CET Inc.
34
5.2.2 Phase A (L1) Energy Measurements
Register
Property
Description
Format
Scale
Unit
0620
RW
kWh Import
INT32
x0.01
kWh
0622
RW
kWh Export
INT32
0624
RO
kWh Net
INT32
0626
RO
kWh Total
INT32
0628
RW
kvarh Import
INT32
kvarh
0630
RW
kvarh Export
INT32
0632
RO
kvarh Net
INT32
0634
RO
kvarh Total
INT32
0636
RW
kVAh
INT32
kVAh
0638
RW
kvarh Q1
INT32
kvarh
0640
RW
kvarh Q2
INT32
0642
RW
kvarh Q3
INT32
0644
RW
kvarh Q4
INT32
0646
RW
kWh Import of T1
INT32
kWh
0648
RW
kWh Export of T1
INT32
0650
RW
kvarh Import of T1
INT32
kvarh
0652
RW
kvarh Export of T1
INT32
0654
RW
kVAh of T1
INT32
kVAh
0656
RW
kWh Import of T2
INT32
kWh
0658
RW
kWh Export of T2
INT32
0660
RW
kvarh Import of T2
INT32
kvarh
0662
RW
kvarh Export of T2
INT32
0664
RW
kVAh of T2
INT32
kVAh
0666
RW
kWh Import of T3
INT32
kWh
0668
RW
kWh Export of T3
INT32
0670
RW
kvarh Import of T3
INT32
kvarh
0672
RW
kvarh Export of T3
INT32
0674
RW
kVAh of T3
INT32
kVAh
0676
RW
kWh Import of T4
INT32
kWh
0678
RW
kWh Export of T4
INT32
0680
RW
kvarh Import of T4
INT32
kvarh
0682
RW
kvarh Export of T4
INT32
0684
RW
kVAh of T4
INT32
kVAh
Table 5-4 Phase A Energy Measurements
5.2.3 Phase B (L2) Energy Measurements
Register
Property
Description
Format
Scale
Unit
0740
RW
kWh Import
INT32
x0.01
kWh
0742
RW
kWh Export
INT32
0744
RO
kWh Net
INT32
0746
RO
kWh Total
INT32
0748
RW
kvarh Import
INT32
kvarh
0750
RW
kvarh Export
INT32
0752
RO
kvarh Net
INT32
0754
RO
kvarh Total
INT32
0756
RW
kVAh
INT32
kVAh
0758
RW
kvarh Q1
INT32
kvarh
0760
RW
kvarh Q2
INT32
0762
RW
kvarh Q3
INT32
0764
RW
kvarh Q4
INT32
0766
RW
kWh Import of T1
INT32
kWh
0768
RW
kWh Export of T1
INT32
0770
RW
kvarh Import of T1
INT32
kvarh
0772
RW
kvarh Export of T1
INT32
0774
RW
kVAh of T1
INT32
kVAh
0776
RW
kWh Import of T2
INT32
kWh
0778
RW
kWh Export of T2
INT32
0780
RW
kvarh Import of T2
INT32
kvarh
0782
RW
kvarh Export of T2
INT32
0784
RW
kVAh of T2
INT32
kVAh
0786
RW
kWh Import of T3
INT32
kWh
0788
RW
kWh Export of T3
INT32
Page 35
CET Inc.
35
0790
RW
kvarh Import of T3
INT32
kvarh
0792
RW
kvarh Export of T3
INT32
0794
RW
kVAh of T3
INT32
kVAh
0796
RW
kWh Import of T4
INT32
kWh
0798
RW
kWh Export of T4
INT32
0800
RW
kvarh Import of T4
INT32
kvarh
0802
RW
kvarh Export of T4
INT32
0804
RW
kVAh of T4
INT32
kVAh
Table 5-5 Phase B Energy Measurements
5.2.4 Phase C (L3) Energy Measurements
Register
Property
Description
Format
Scale
Unit
0860
RW
kWh Import
INT32
x0.01
kWh
0862
RW
kWh Export
INT32
0864
RO
kWh Net
INT32
0866
RO
kWh Total
INT32
0868
RW
kvarh Import
INT32
kvarh
0870
RW
kvarh Export
INT32
0872
RO
kvarh Net
INT32
0874
RO
kvarh Total
INT32
0876
RW
kVAh
INT32
kVAh
0878
RW
kvarh Q1
INT32
kvarh
0880
RW
kvarh Q2
INT32
0882
RW
kvarh Q3
INT32
0884
RW
kvarh Q4
INT32
0886
RW
kWh Import of T1
INT32
kWh
0888
RW
kWh Export of T1
INT32
0890
RW
kvarh Import of T1
INT32
kvarh
0892
RW
kvarh Export of T1
INT32
0894
RW
kVAh of T1
INT32
kVAh
0896
RW
kWh Import of T2
INT32
kWh
0898
RW
kWh Export of T2
INT32
0900
RW
kvarh Import of T2
INT32
kvarh
0902
RW
kvarh Export of T2
INT32
0904
RW
kVAh of T2
INT32
kVAh
0906
RW
kWh Import of T3
INT32
kWh
0908
RW
kWh Export of T3
INT32
0910
RW
kvarh Import of T3
INT32
kvarh
0912
RW
kvarh Export of T3
INT32
0914
RW
kVAh of T3
INT32
kVAh
0916
RW
kWh Import of T4
INT32
kWh
0918
RW
kWh Export of T4
INT32
0920
RW
kvarh Import of T4
INT32
kvarh
0922
RW
kvarh Export of T4
INT32
0924
RW
kVAh of T4
INT32
kVAh
Table 5-6 Phase C Energy Measurements
5.3 DI Pulse Counter (PMC-340B Only)
Register
Property
Description
Format
Range/Unit
1200
RW
DI1 Pulse Counter
INT32
0 to 999,99,999
DI Pulse Counter= Pulse Counter
x DI Pulse Weight
1202
RW
DI2 Pulse Counter
INT32
1204
RW
DI3 Pulse Counter
INT32
Table 5-7 DI Pulse Counter
5.4 Harmonic Measurements
5.4.1 Power Quality Measurements
Register
Property
Description
Format
Scale
Unit
1300
RO
Ia TDD
Float
x1
-
1302
RO
Ib TDD
Float
1304
RO
Ic TDD
Float
1306
RO
Ia TDD Odd
Float
Page 36
CET Inc.
36
1308
RO
Ib TDD Odd
Float
1310
RO
Ic TDD Odd
Float
1312
RO
Ia TDD Even
Float
1314
RO
Ib TDD Even
Float
1316
RO
Ic TDD Even
Float
1318
RO
Ia K-factor
Float
1320
RO
Ib K-factor
Float
1322
RO
Ic K-factor
Float
1324
RO
Ia Crest-factor
Float
1326
RO
Ib Crest-factor
Float
1328
RO
Ic Crest-factor
Float
1330
RO
Voltage Unbalance
Float
1332
RO
Current Unbalance
Float
Table 5-8 Power Quality Measurements
5.4.2 Current Harmonic Measurements
Register
Property
Description
Format
Scale
Unit
1400
RO
Ia THD
Float
x1
-
1402
RO
Ib THD
Float
1404
RO
Ic THD
Float
1406
RO
Ia TOHD
Float
1408
RO
Ib TOHD
Float
1410
RO
Ic TOHD
Float
1412
RO
Ia TEHD
Float
1414
RO
Ib TEHD
Float
1416
RO
Ic TEHD
Float
1418
RO
Ia HD02
Float
1420
RO
Ib HD02
Float
1422
RO
Ic HD02
Float
1424~1590
RO … Float
1592
RO
Ia HD31
Float
1594
RO
Ib HD31
Float
1596
RO
Ic HD31
Float
Table 5-9 Current Harmonic Measurements
5.4.3 Voltage Harmonic Measurements
Register
Property
Description
Format
Scale
Unit
1600
RO
Uan/Uab THD
Float
x1
-
1602
RO
Ubn/Ubc THD
Float
1604
RO
Ucn/Uca THD
Float
1606
RO
Uan/Uab TOHD
Float
1608
RO
Ubn/Ubc TOHD
Float
1610
RO
Ucn/Uca TOHD
Float
1612
RO
Uan/Uab TEHD
Float
1614
RO
Ubn/Ubc TEHD
Float
1616
RO
Ucn/Uca TEHD
Float
1618
RO
Uan/Uab HD02
Float
1620
RO
Ubn/Ubc HD02
Float
1622
RO
Ucn/Uca HD02
Float
1624~1790
RO … Float
1792
RO
Uan/Uab HD31
Float
1794
RO
Ubn/Ubc HD31
Float
1796
RO
Ucn/Uca HD31
Float
Table 5-10 Voltage Harmonic Measurements
Notes:
1) When the Wiring Mode is 3P3W or 1P2W L-L, the phase A/B/C voltage THD/TOHD/TEHD/HDxx
is phase AB/BC/CA voltage THD/TOHD/TEHD/HDxx.
5.5 Demands
5.5.1 Present Demands
Page 37
CET Inc.
37
Register
Property
Description
Format
Scale
Unit
3000
RO
Ia
Float
x1
A
3002
RO
Ib
Float
3004
RO
Ic
Float
3006
RO
kW Total
Float
W
3008
RO
kvar Total
Float
var
3010
RO
kVA Total
Float
VA
Table 5-11 Present Demand Measurements
5.5.2 Peak Demand Log of This Month (Since Last Reset)
Register
Property
Description
Format
Scale
Unit
3400~3405
RO
Ia
See
Table 5-15
Demand Data
Structure
x1
A
3406~3411
RO
Ib
3412~3417
RO
Ic
3418~3423
RO
kW Total
W
3424~3429
RO
kvar Total
var
3430~3435
RO
kVA Total
VA
3436~3441
RO
kW Total of T1
W
3442~3447
RO
kvar Total of T1
var
3448~3453
RO
kVA Total of T1
VA
3454~3459
RO
kW Total of T2
W
3460~3465
RO
kvar Total of T2
var
3466~3471
RO
kVA Total of T2
VA
3472~3477
RO
kW Total of T3
W
3478~3483
RO
kvar Total of T3
var
3484~3489
RO
kVA Total of T3
VA
3490~3495
RO
kW Total of T4
W
3496~3501
RO
kvar Total of T4
var
3502~3507
RO
kVA Total of T4
VA
Table 5-12 Peak Demand Log of This Month
5.5.3 Peak Demand Log of Last Month (Before Last Reset)
Table 5-13 Peak Demand Log of Last Month
Notes:
1) The following table illustrates Demand Data Structure:
Offset
Description
+0
High
Year - 2000
Low
Month
+1
High
Day
Low
Hour
+2
High
Minute
Low
Second
Register
Property
Description
Format
Scale
Unit
3600~3605
RO
Ia
See
Table 5-15
Demand Data
Structure
x1
A
3606~3611
RO
Ib
3612~3617
RO
Ic
3618~3623
RO
kW
W
3624~3629
RO
kvar
var
3630~3635
RO
kVA
VA
3636~3641
RO
kW Total
W
3642~3647
RO
Kvar Total
var
3648~3653
RO
kVA Total
VA
3654~3659
RO
kW Total of T1
W
3660~3665
RO
kvar Total of T1
var
3666~3671
RO
kVA Total of T1
VA
3672~3677
RO
kW Total of T2
W
3678~3683
RO
kvar Total of T2
var
3684~3689
RO
kVA Total of T2
VA
3690~3695
RO
kW Total of T3
W
3696~3701
RO
kvar Total of T3
var
3702~3707
RO
kVA Total of T3
VA
Page 38
CET Inc.
38
+3
-
Millisecond
+4~+5
-
Record Value
Table 5-14 Demand Data Structure
5.6 Max./Min. Log
5.6.1 Max. Log of This Month (Since Last Reset)
Register
Property
Description
Format
Scale
Unit
4000~4005
RO
Uan
See 5.6.5
Max./Min. Log
Structure
x1
V
4006~4011
RO
Ubn
4012~4017
RO
Ucn
4018~4023
RO
Uln Average
4024~4029
RO
Uab
4030~4035
RO
Ubc
4036~4041
RO
Uca
4042~4047
RO
Ull Average
4048~4053
RO
Ia
A
4054~4059
RO
Ib
4060~4065
RO
Ic
4066~4071
RO
I Average
4072~4077
RO
kWa
W
4078~4083
RO
kWb
4084~4089
RO
kWc
4090~4095
RO
kW Total
4096~4101
RO
kvara
var
4102~4107
RO
kvarb
4108~4113
RO
kvarc
4114~4119
RO
kvar Total
4120~4125
RO
kVAa
VA
4126~4131
RO
kVAb
4132~4137
RO
kVAc
4138~4143
RO
kVA Total
4144~4149
RO
PFa
-
4150~4155
RO
PFb
4156~4161
RO
PFc
4162~4167
RO
PF Total
4168~4173
RO
Frequency
Hz
4174~4179
RO
I4
A
4180~4185
RO
Uan/Uab THD
-
4186~4191
RO
Ubn/Ubc THD
4192~4197
RO
Ucn/Uca THD
4198~4203
RO
Ia THD
4204~4209
RO
Ib THD
4210~4215
RO
Ic THD
4216~4221
RO
Ia K-factor
4222~4227
RO
Ib K-factor
4228~4233
RO
Ic K-factor
4234~4239
RO
Ia Crest-factor
4240~4245
RO
Ib Crest-factor
4246~4251
RO
Ic Crest-factor
4252~4257
RO
Voltage Unbalance
4258~4263
RO
Current Unbalance
Table 5-15 Max. Log of This Month (Since Last Reset)
5.6.2 Min. Log of This Month (Since Last Reset)
Register
Property
Description
Format
Scale
Unit
4300~4305
RO
Uan
See 5.6.5
Max./Min. Log
Structure
x1
V
4306~4311
RO
Ubn
4312~4317
RO
Ucn
4318~4323
RO
Uln Average
4324~4329
RO
Uab
4330~4335
RO
Ubc
Page 39
CET Inc.
39
4336~4341
RO
Uca
4342~4347
RO
Ull Average
4348~4353
RO
Ia
A
4354~4359
RO
Ib
4360~4365
RO
Ic
4366~4371
RO
I Average
4372~4377
RO
kWa
W
4378~4383
RO
kWb
4384~4389
RO
kWc
4390~4395
RO
kW Total
4396~4401
RO
kvara
var
4402~4407
RO
kvarb
4408~4413
RO
kvarc
4414~4419
RO
kvar Total
4420~4425
RO
kVAa
VA
4426~4431
RO
kVAb
4432~4437
RO
kVAc
4438~4443
RO
kVA Total
4444~4449
RO
PFa
-
4450~4455
RO
PFb
4456~4461
RO
PFc
4462~4467
RO
PF Total
4468~4473
RO
Frequency
Hz
4474~4479
RO
I4
A
4480~4485
RO
Uan/Uab THD
-
4486~4491
RO
Ubn/Ubc THD
4492~4497
RO
Ucn/Uca THD
4498~4503
RO
Ia THD
4504~4509
RO
Ib THD
4510~4515
RO
Ic THD
4516~4521
RO
Ia K-factor
4522~4527
RO
Ib K-factor
4528~4533
RO
Ic K-factor
4534~4539
RO
Ia Crest-factor
4540~4545
RO
Ib Crest-factor
4546~4551
RO
Ic Crest-factor
4552~4557
RO
Voltage Unbalance
4558~4563
RO
Current Unbalance
Table 5-16 Min. Log of This Month (Since Last Reset)
5.6.3 Max. Log of Last Month (Before Last Reset)
Register
Property
Description
Format
Scale
Unit
4600~4605
RO
Uan
See 5.6.5
Max./Min. Log
Structure
x1
V
4606~4611
RO
Ubn
4612~4617
RO
Ucn
4618~4623
RO
Uln Average
4624~4629
RO
Uab
4630~4635
RO
Ubc
4636~4641
RO
Uca
4642~4647
RO
Ull Average
4648~4653
RO
Ia
A
4654~4659
RO
Ib
4660~4665
RO
Ic
4666~4671
RO
I Average
4672~4677
RO
kWa
W
4678~4683
RO
kWb
4684~4689
RO
kWc
4690~4695
RO
kW Total
4696~4701
RO
kvara
var
4702~4707
RO
kvarb
4708~4713
RO
kvarc
4714~4719
RO
kvar Total
4720~4725
RO
kVAa
VA
4726~4731
RO
kVAb
Page 40
CET Inc.
40
4732~4737
RO
kVAc
4738~4743
RO
kVA Total
4744~4749
RO
PFa
-
4750~4755
RO
PFb
4756~4761
RO
PFc
4762~4767
RO
PF Total
4768~4773
RO
Frequency
Hz
4774~4779
RO
I4
A
4780~4785
RO
Uan/Uab THD
-
4786~4791
RO
Ubn/Ubc THD
4792~4797
RO
Ucn/Uca THD
4798~4803
RO
Ia THD
4804~4809
RO
Ib THD
4810~4815
RO
Ic THD
4816~4821
RO
Ia K-factor
4822~4827
RO
Ib K-factor
4828~4833
RO
Ic K-factor
4834~4839
RO
Ia Crest-factor
4840~4845
RO
Ib Crest-factor
4846~4851
RO
Ic Crest-factor
4852~4857
RO
Voltage Unbalance
4858~4863
RO
Current Unbalance
Table 5-17 Max. Log of Last Month (Before Last Reset)
5.6.4 Min. Log of Last Month (Before Last Reset)
Register
Property
Description
Format
Scale
Unit
4900~4905
RO
Uan
See 5.6.5
Max./Min. Log
Structure
x1
V
4906~4911
RO
Ubn
4912~4917
RO
Ucn
4918~4923
RO
Uln Average
4924~4929
RO
Uab
4930~4935
RO
Ubc
4936~4941
RO
Uca
4942~4947
RO
Ull Average
4948~4953
RO
Ia
A
4954~4959
RO
Ib
4960~4965
RO
Ic
4966~4971
RO
I Average
4972~4977
RO
kWa
W
4978~4983
RO
kWb
4984~4989
RO
kWc
4990~4995
RO
kW Total
4996~5001
RO
kvara
var
5002~5007
RO
kvarb
5008~5013
RO
kvarc
5014~5019
RO
kvar Total
5020~5025
RO
kVAa
VA
5026~5031
RO
kVAb
5032~5037
RO
kVAc
5038~5043
RO
kVA Total
5044~5049
RO
PFa
-
5050~5055
RO
PFb
5056~5061
RO
PFc
5062~5067
RO
PF Total
5068~5073
RO
Frequency
Hz
5074~5079
RO
I4
A
5080~5085
RO
Uan/Uab THD
-
5086~5091
RO
Ubn/Ubc THD
5092~5097
RO
Ucn/Uca THD
5098~5103
RO
Ia THD
5104~5109
RO
Ib THD
5110~5115
RO
Ic THD
5116~5121
RO
Ia K-factor
5122~5127
RO
Ib K-factor
5128~5133
RO
Ic K-factor
Page 41
CET Inc.
41
5134~5139
RO
Ia Crest-factor
5140~5145
RO
Ib Crest-factor
5146~5151
RO
Ic Crest-factor
5152~5157
RO
Voltage Unbalance
5158~5163
RO
Current Unbalance
Table 5-18 Min. Log of Last Month (Before Last Reset)
5.6.5 Max./Min. Log Structure
Offset
Description
+0
High
Year - 2000
Low
Month
+1
High
Day
Low
Hour
+2
High
Minute
Low
Second
+3
-
Millisecond
+4~+5
-
Record Value
Table 5-19 Max./Min. Structure
5.7 Monthly Energy Log
Register
Property
Description
Format
Scale
Unit
0980
RW
Month
INT16
0* to 12
0981
RO
High-order Byte: Year (0-99)
Low-order Byte: Month (1-12)
INT16
Time Stamp
(20YY/MM/DD
HH:MM:SS)
0982
RO
High-order Byte: Day (1-31)
Low-order Byte: Hour (0-23)
INT16
0983
RO
High-order Byte: Minute (0-
59)
Low-order Byte: Second (0-59)
INT16
0984
RW
kWh Import
INT32
x0.01
kWh
0986
RW
kWh Export
INT32
0988
RO
kWh Net
INT32
0990
RO
kWh Total
INT32
0992
RW
kvarh Import
INT32
kvarh
0994
RW
kvarh Export
INT32
0996
RO
kvarh Net
INT32
0998
RO
kvarh Total
INT32
1000
RW
kVAh
INT32
kVAh
1002
RW
kvarh Q1
INT32
kvarh
1004
RW
kvarh Q2
INT32
1006
RW
kvarh Q3
INT32
1008
RW
kvarh Q4
INT32
1010
RW
kWh Import of T1
INT32
kWh
1012
RW
kWh Export of T1
INT32
1014
RW
kvarh Import of T1
INT32
kvarh
1016
RW
kvarh Export of T1
INT32
1018
RW
kVAh of T1
INT32
kVAh
1020
RW
kWh Import of T2
INT32
kWh
1022
RW
kWh Export of T2
INT32
1024
RW
kvarh Import of T2
INT32
kvarh
1026
RW
kvarh Export of T2
INT32
1028
RW
kVAh of T2
INT32
kVAh
1030
RW
kWh Import of T3
INT32
kWh
1032
RW
kWh Export of T3
INT32
1034
RW
kvarh Import of T3
INT32
kvarh
1036
RW
kvarh Export of T3
INT32
1038
RW
kVAh of T3
INT32
kVAh
1040
RW
kWh Import of T4
INT32
kWh
1042
RW
kWh Export of T4
INT32
1044
RW
kvarh Import of T4
INT32
kvarh
1046
RW
kvarh Export of T4
INT32
1048
RW
kVAh of T4
INT32
kVAh
Table 5-20 Monthly Energy Log
Page 42
CET Inc.
42
Notes:
1) This register represents the Month when it is read. To read the Monthly Energy Log, this
register must be first written to indicate to the PMC-340 which log to load from memory. The range of this register is from 0 to 12, which represents the Present Month and the Last 12 Months. For example, if the current month is 2016/10, “0” means 2016/10, “1” means 2016/09, “2” means 2016/08, ……”12” means “2015/10”.
2) For each Monthly Energy Log, the time stamp shows the exact self-read time (20YY/MM/DD
HH:MM:SS) when the log was recorded. For the Monthly Energy Log of the Present Month, the time stamp shows the current time of the meter because the present month is not yet over.
3) The Monthly Energy Log for the Present Month can be modified, but the Monthly Energy Logs
for the Last 12 Months are Read Only.
5.8 SOE Log (PMC-340B Only)
The SOE Log Pointer points to the register address within the SOE Log where the next event will be stored. The following formula is used to determine the register address of the most recent SOE event referenced by the SOE Log Pointer value:
Register Address = 10000 + Modulo(SOE Log Pointer-1/16)*8
Register
Property
Description
Format
10000~10007
RO
Event 1
See Table 5-22
SOE Log Data
Structure
10008~10015
RO
Event 2
10016~10023
RO
Event 3
10024~10031
RO
Event 4
10032~10039
RO
Event 5
10040~10047
RO
Event 6
10048~10055
RO
Event 7
……
10120~10127
RO
Event 16
Table 5-21 SOE Log
Notes:
1) SOE Log Data Structure
Offset
Property
Description
Unit
+0
RO
High-order Byte: Event Classification2
-
RO
Low-order Byte: Sub-Classification2
-
+1
RO
Record Time: Year
0-99 (Year-2000)
RO
Record Time: Month
1 to 12
+2
RO
Record Time: Day
1 to 31
RO
Record Time: Hour
0 to 23
+3
RO
Record Time: Minute
0 to 59
RO
Record Time: Second
0 to 59
+4
RO
Record Time: Millisecond
0 to 999
+5
RO
High-order Byte: Reserved
-
RO
Low-order Byte: Status2
-
+6 to +7
RO
Event Value2
-
Table 5-22 SOE Log Data Structure
2) SOE Classification
Event
Classification
Sub-
Classification
Status
Event Value
Description
1=DI Status
Changes
1
0=Inactive,
1=Active
1/0
DI1 Inactive / DI1 Active
2
1/0
DI2 Inactive / DI2 Active
3
1/0
DI3 Inactive / DI3 Active
5=Operations
1
None
0
Power On
2
None
0
Power Off
3
None
0
Setup Parameter Changes via
Communication
4
None
0
Setup Parameter Changes
via Front Panel
5
None
0
Clear Monthly Energy Log of the Last
12 Months via Communication
Page 43
CET Inc.
43
Table 5-23 SOE Classification
5.9 Data Recorder Log (PMC-340B Only)
Register
Property
Description
Format
Note
20000
RW
Data Recorder Log Number
1
UINT32
20002
RO
High-order Byte: Year
UINT16
1 to 99 (Year-2000)
Low-order Byte: Month
1 to 120
20003
RO
High-order Byte: Day
UINT16
1 to 28/29/30/31
Low-order Byte: Hour
0 to 23
20004
RO
High-order Byte: Minute
UINT16
0 to 59
Low-order Byte: Second
0 to 59
20005
RO
Millisecond
UINT16
20006~20007
RO
Parameter 1
Float
20008~20009
RO
Parameter 2
Float
20010~20011
RO
Parameter 3
Float
20012~20013
RO
Parameter 4
Float
20014~20015
RO
Parameter 5
Float
20016~20017
RO
Parameter 6
Float
20018~20019
RO
Parameter 7
Float
20020~20021
RO
Parameter 8
Float
20022~20023
RO
Parameter 9
Float
20024~20025
RO
Parameter 10
Float
20026~20027
RO
Parameter 11
Float
20028~20029
RO
Parameter 12
Float
20030~20031
RO
Parameter 13
Float
6
None
0
Clear 3-Phase Energy registers and
Phase A/B/C Energy registers via
Communication
7
None
0
Clear Monthly Energy Log of The
Preset Month via Communication
8
None
0
Clear 3-Phase Total Energy registers
and Phase A/B/C Energy Registers, Monthly Energy Log of the Last 12
Months and Monthly Energy Log of the
Present Month via Front Panel
9
None
0
Clear Peak Demand Logs of This Month
(Since Last Reset) via Communication
10
None
0
Clear all Peak Demand Logs and
Present Demand via Communication
11
None
0
Clear All Peak Demand Logs and Present Demand via Front Panel
12
None
0
Clear Max./Min. Log of This Month
(Since Last Reset) via Communication
13
None
0
Clear All Max./Min. Log
via Communication
14
None
0
Clear all Max./Min. Log
via Front Panel
15
None
0
Clear Device Operating Time via
Communication
16
None
0
Clear All Records via Communication,
including 3-Phase Total Energy and
Phase A/B/C Energy Registers, Monthly
Energy Log of the Last 12 Months,
Monthly Energy Log of the Present
Month, all Max./Min. Log, all Demand
Log, Device Operating Time, DIx Pulse
Counters, DR Log and SOE
17
None
0
Clear DI1 Pulse Counter
via Communication
18
None
0
Clear DI2 Pulse Counter
via Communication
19
None
0
Clear DI3 Pulse Counter
via Communication
20
None
0
Clear DR Logs via Communication
21
None
0
Clear SOE Logs via Communication
22
None
0
Clear All DI Counters via Front Panel
Page 44
CET Inc.
44
20032~20033
RO
Parameter 14
Float
20034~20035
RO
Parameter 15
Float
20036~20037
RO
Parameter 16
Float
Table 5-24 Data Recorder Log
Notes:
1) Writing a value n (where 1 ≤ n ≤ 28,400) to the Data Recorder Log Number register will load the
nth Log Record into the buffer from memory.
5.10 Device Setup
5.10.1 Basic Setup Parameters
Register
Property
Description
Format
Range, Default*
6000
RW
PT Primary
1
UINT32
1 to 1,000,000V, 380*
6002
RW
PT Secondary
UINT32
1 to 690V, 380*
6004
RW
CT Primary
UINT32
1 to 30,000A, 5*
6006
RW
CT Secondary
UINT32
1 to 5A, 5*
6008~6018
RW
Reserved
UINT32
-
6020
RW
Wiring Mode
UINT16
0=DEMO, 1=1P2W L-N
2=1P2W L-L, 3=1P3W
4=3P3W, 5=3P4W*
6021
RW
Power Factor Convention
UINT16
0=IEC*, 1=IEEE, 2=-IEEE
6022
RW
kVA Calculation
UINT16
0=Vector*, 1=Scalar
6023
RW
Ia Polarity
UINT16
0=Normal*, 1=Reverse
6024
RW
Ib Polarity
UINT16
6025
RW
Ic Polarity
UINT16
6026~6027
RW
Reserved
UINT16
-
6028
RW
THD Calculation
2
UINT16
0= THDf*, 1= THDr
6029
RW
Demand Period
UINT16
1 to 60 (minutes), 10*
6030
RW
No. of Sliding Windows
UINT16
1 to 15, 15*
6031~6032
RW
Reserved
UINT16
-
6033
RW
Self-Read Time3
UINT16
Default=0xFFFF
(Auto Self-Read Disabled)
6034
RW
Monthly Energy Log
Self-Read Time
4
UINT16
0*
6035
RW
Energy Pulse Constant
UINT16
0 to 4
0=1 imp/kxh,
1=10 imp/kxh 2=100 imp/kxh* 3=1000 imp/kxh 4=3200 imp/kxh
6036
RW
LED Energy Pulse
UINT16
0=Disabled*
1=kWh
2=kvarh
6037~6040
RW
Reserved
UINT16
-
6041
RW
Energy Pulse Width
UINT16
60 to 150ms, 80*
Table 5-25 Basic Setup Parameters
Notes:
1) The ratio between PT Primary and PT Secondary cannot exceed 10,000.
2) There are two ways to calculate THD:
THDf (based on Fundamental):
%100THD
1
2
2
I
I
n
n
where In represents the RMS value for the nth harmonic and I1 represents the RMS value of the Fundamental harmonic.
Page 45
CET Inc.
45
THDr (based on RMS):
%100THD
1
2
2
2
n
n
n
n
I
I
where In represents the RMS value for the nth harmonic
3) The Self-Read Time applies to both the Peak Demand Log as well as the Max./Min. Log and
supports the following three options:
A zero value means that the Self-Read will take place at 00:00 of the first day of each month. A non-zero value means that the Self-Read will take place at a specific time and day based on
the formula: Self-Read Time = Day x 100 + Hour where 0 ≤ Hour ≤ 23 and 1 ≤ Day ≤ 28. For example, the value 1512 means that the Self-Read will take place at 12:00pm on the 15th day of each month.
A 0xFFFF value means the automatic self-read operation is disabled and the log will be
transferred manually
4) The Monthly Energy Log Self-Read Time supports only two options:
A zero value means that the Self-Read will take place at 00:00 of the first day of each month. A non-zero value means that the Self-Read will take place at a specific time and day based on
the formula: Self-Read Time = Day * 100 + Hour where 0 ≤ Hour ≤ 23 and 1 ≤ Day ≤ 28. For example, the value 1512 means that the Self-Read will take place at 12:00pm on the 15th day of each month.
5.10.2 I/O Setup
Register
Property
Description
Format
Range, Default*
Model
A
B
6200
RW
DI1 Function
UINT16
0=Digital Input
1=Energy Pulse Counter*
2=Tariff Switch1
6201
RW
DI1 Debounce
UINT16
1 to 1000ms, 20ms*
 6202
RW
DI1 Pulse Weight
UINT32
1 to 1,000,000, 1*
 6204
RW
Reserved -
6205
RW
DI2 Function
UINT16
0=Digital Input
1=Energy Pulse Counter*
2=Tariff Switch1
6206
RW
DI2 Debounce
UINT16
1 to 1000ms, 20ms*
 6207
RW
DI2 Pulse Weight
UINT32
1 to 1,000,000, 1*
 6209
RW
Reserved
UINT16
-
6210
RW
DI3 Function
UINT16
0=Digital Input
1=Energy Pulse Counter*
6211
RW
DI3 Debounce
UINT16
1 to 1000ms, 20ms*
6212
RW
DI3 Pulse Weight
UINT32
1 to 1,000,000, 1*
 6214~6231
RW
Reserved -
6232
RW
DO Mode
UINT16
0= Disabled
1= kWh Import
2= kWh Export
3= kWh Total*
4= kvarh Import
5= kvarh Export
6= kvarh Total
7= PPS (PMC-340B Only)
2
8= DMD
3
9=TOU Period Switch
4
6233~6249
Reserved
Table 5-26 I/O Setup Parameters
Notes:
1) The Tariff Switch option is available in Firmware V1.00.01 or later.
2) PPS: 1 Pulse Per Second
3) DMD: 1 pulse is generated at the end of every Demand Interval
4) Tariff Switch: 1 pulse is generated every time a Tariff Switch takes place based on TOU Schedule.
5.10.3 Communication Setup Parameters
Page 46
CET Inc.
46
Register
Property
Description
Format
Range, Default*
6400
RW
Reserved
- 6401
RW
Unit ID
UINT16
1 to 247, 100*
6402
RW
Baud Rate
UINT16
0=1200, 1=2400, 2=4800,
3=9600*, 4=19200,
Others=Reserved
6403
RW
Comm. Config.
UINT16
0=8N2, 1=8O1, 2=8E1*
3=8N1, 4=8O2, 5=8E2
Table 5-27 Communication Setup
Notes:
1) If the Baud Rate is set to an invalid value, it will default to 9600bps automatically.
5.11 Data Recorder Setup (PMC-340B Only)
Register
Property
Description
Format
Range, Default*
6500
RW
Trigger Mode
UINT16
0=Disabled
1=Triggered by Timer*
6501
RW
Recording Mode1
UINT16
0=Stop-when-Full
1=First-In-First-Out*
6502
RW
Recording Depth1
UINT16
0 to 28,400*
6503
RW
Recording Interval1
UINT32
1 to 3456000s, 600s*
6505
RW
Offset Time
2
UINT16
0* to 43200s
6506
RW
Number of Parameters1
UINT16
0 to 16, 14*
6507
RW
Parameter #1
1,3
UINT16
100 (kWh Import)*
6508
RW
Parameter #2
1,3
UINT16
101 (kWh Export)*
6509
RW
Parameter #3
1,3
UINT16
104(kvarh Import)*
6510
RW
Parameter #4
1,3
UINT16
105 (kvarh Export)*
6511
RW
Parameter #5
1,3
UINT16
108 (kVAh)*
6512
RW
Parameter #6
1,3
UINT16
603 (kW Total Demand)*
6513
RW
Parameter #7
1,3
UINT16
604 (kvar Total Demand)*
6514
RW
Parameter #8
1,3
UINT16
605 (kVA Total Demand)*
6515
RW
Parameter #9
1,3
UINT16
600 (Ia Demand)*
6516
RW
Parameter #101
1,3
UINT16
601 (Ib Demand)*
6517
RW
Parameter #11
1,3
UINT16
602 (Ic Demand)*
6518
RW
Parameter #12
1,3
UINT16
109 (DI1 Pulse Counter)*
6519
RW
Parameter #13
1,3
UINT16
110 (DI2 Pulse Counter)*
6520
RW
Parameter #14
1,3
UINT16
111 (DI3 Pulse Counter)*
6521
RW
Parameter #15
1,3
UINT16
0 (Not Used)
6522
RW
Parameter #16
1,3
UINT16
0 (Not Used)
Table 5-28 Data Recorder Setup
Notes:
1) Changing any of these Data Recorder setup registers will reset the Data Recorder.
2) Recording Offset can be used to delay the recording by a fixed amount of time from the
Recording Interval. For example, if the Recording Interval is set to 3600 (hourly) and the Recording Offset is set to 300 (5 minutes), the recording will take place at 5 minutes after the
hour every hour, i.e. 00:05, 01:05, 02:05…etc. The value of the Recording Offset parameter should be less than the Recording Interval parameter.
3) Please refer to Appendix A for a complete list of Data Recorder Parameters.
5.12 TOU Setup
5.12.1 Basic
Register
Property
Description
Format
Range, Default*
7000
RO
Current Tariff
1
UINT16
0=T1, 1=T2 2=T3, 3=T4
7001
RO
Current Season
UINT16
0 to 11
(Season #1 to #12)
Page 47
CET Inc.
47
7002
RO
Current Period
UINT16
0 to 11
(Period #1 to #12)
7003
RO
Current Daily Profile
UINT16
0 to 19
(Daily Profile #1 to #20)
7004
RO
Current Day Type
UINT16
0=Weekday1 1=Weekday2 2=Weekday3
3=Alternate Day
7005
RO
Current TOU Schedule No
UINT16
0=TOU #1 1=TOU #2
7006
RW
TOU Switch Time2
UINT32
See Note 1)
7008
WO
Switch TOU Manually
UINT16
Write 0xFF00 to manually switch
the TOU schedule
7009
RW
Sunday Setup
UINT16
0*=Weekday1
1=Weekday2 2=Weekday3
7010
RW
Monday Setup
UINT16
7011
RW
Tuesday Setup
UINT16
7012
RW
Wednesday Setup
UINT16
7013
RW
Thursday Setup
UINT16
7014
RW
Friday Setup
UINT16
7015
RW
Saturday Setup
UINT16
Table 5-29 TOU Basic Setup
Notes:
1) If DI1 is not programmed as a Tariff Switch, the TOU will function based on the TOU Schedule. If
at least one DI (DI1) is programmed as a Tariff Switch, the TOU Schedule will no longer be used and the Tariff switching will be based on status of the DIs.
2) The following table illustrates the data structure for the TOU Switch Time. For example,
0x1003140C indicates a switch time of 12:00pm on March 20th, 2016. Writing 0xFFFFFFFF to this register disables the switching between TOU schedules.
Byte 3
Byte 2
Byte 1
Byte 0
Year-2000 (0-37)
Month (1-12)
Day (1-31)
Hour (00-23)
Table 5-30 TOU Switch Time Format
5.12.2 Season
The PMC-340 has two sets of Season setup parameters, one for each TOU. The Base Addresses for the two sets are 7100 and 8100, respectively, where the Register Address = Base Address + Offset. For example, the register address for TOU #1’s Season #2’s Start Date is 7100+4 = 7104.
Offset
Property
Description
Format
Range/Note
0
RW
Season #1: Start Date¹
UINT16
0x0101
1
RW
Season #1: Weekday#1 Daily Profile
UINT16
0 to 19
2
RW
Season #1: Weekday#2 Daily Profile
UINT16
3
RW
Season #1: Weekday#3 Daily Profile
UINT16
4
RW
Season #2: Start Date
UINT16
High-order Byte: Month
Low-order Byte: Day
5
RW
Season #2: Weekday#1 Daily Profile
UINT16
0 to 19
6
RW
Season #2: Weekday#2 Daily Profile
UINT16
7
RW
Season #2: Weekday#3 Daily Profile
UINT16
8
RW
Season #3: Start Date
UINT16
See Season #2: Start Date
9
RW
Season #3: Weekday#1 Daily Profile
UINT16
0 to 19
10
RW
Season #3: Weekday#2 Daily Profile
UINT16
11
RW
Season #3: Weekday#3 Daily Profile
UINT16
12
RW
Season #4: Start Date
UINT16
See Season #2: Start Date
13
RW
Season #4: Weekday#1 Daily Profile
UINT16
0 to 19
14
RW
Season #4: Weekday#2 Daily Profile
UINT16
15
RW
Season #4: Weekday#3 Daily Profile
UINT16
16
RW
Season #5: Start Date
UINT16
See Season #2: Start Date
17
RW
Season #5: Weekday#1 Daily Profile
UINT16
0 to 19
18
RW
Season #5: Weekday#2 Daily Profile
UINT16
19
RW
Season #5: Weekday#3 Daily Profile
UINT16
20
RW
Season #6: Start Date
UINT16
See Season #2: Start Date
21
RW
Season #6: Weekday#1 Daily Profile
UINT16
0 to 19
22
RW
Season #6: Weekday#2 Daily Profile
UINT16
23
RW
Season #6: Weekday#3 Daily Profile
UINT16
Page 48
CET Inc.
48
24
RW
Season #7: Start Date
UINT16
See Season #2: Start Date
25
RW
Season #7: Weekday#1 Daily Profile
UINT16
0 to 19
26
RW
Season #7: Weekday#2 Daily Profile
UINT16
27
RW
Season #7: Weekday#3 Daily Profile
UINT16
28
RW
Season #8: Start Date
UINT16
See Season #2: Start Date
29
RW
Season #8: Weekday#1 Daily Profile
UINT16
0 to 19
30
RW
Season #8: Weekday#2 Daily Profile
UINT16
31
RW
Season #8: Weekday#3 Daily Profile
UINT16
32
RW
Season #9: Start Date
UINT16
See Season #2: Start Date
33
RW
Season #9: Weekday#1 Daily Profile
UINT16
0 to 19
34
RW
Season #9: Weekday#2 Daily Profile
UINT16
35
RW
Season #9: Weekday#3 Daily Profile
UINT16
36
RW
Season #10: Start Date
UINT16
See Season #2: Start Date
37
RW
Season #10: Weekday#1 Daily Profile
UINT16
0 to 19
38
RW
Season #10: Weekday#2 Daily Profile
UINT16
39
RW
Season #10: Weekday#3 Daily Profile
UINT16
40
RW
Season #11: Start Date
UINT16
See Season #2: Start Date
41
RW
Season #11: Weekday#1 Daily Profile
UINT16
0 to 19
42
RW
Season #11: Weekday#2 Daily Profile
UINT16
43
RW
Season #11: Weekday#3 Daily Profile
UINT16
44
RW
Season #12: Start Date
UINT16
See Season #2: Start Date
45
RW
Season #12: Weekday#1 Daily Profile
UINT16
0 to 19
46
RW
Season #12: Weekday#2 Daily Profile
UINT16
47
RW
Season #12: Weekday#3 Daily Profile
UINT16
Table 5-31 Season Setup
Notes:
1) Start Date for Season #1 is Jan. 1
st
and cannot be modified.
2) Setting a Season’s Start Date as 0xFFFF terminates the TOU’s Season settings. All subsequent
Seasons’ setup parameters will be ignored since the previous Season’s duration is from its Start Date to the end of the year.
3) The Start Date of a particular Season must be later than the previous Season’s.
5.12.3 Daily Profile
The PMC-340 has two sets of Daily Profile setup parameters, one for each TOU.
Register Address
Property
Description
Format
7200~7223
RW
Daily Profile #1
See Table 5-34
Daily Profile Data
Structure
7224~7247
RW
Daily Profile #2
7248~7271
RW
Daily Profile #3
7272~7295
RW
Daily Profile #4
7296~7319
RW
Daily Profile #5
7320~7343
RW
Daily Profile #6
7344~7367
RW
Daily Profile #7
7368~7391
RW
Daily Profile #8
7392~7415
RW
Daily Profile #9
7416~7439
RW
Daily Profile #10
7440~7463
RW
Daily Profile #11
7464~7487
RW
Daily Profile #12
7488~7511
RW
Daily Profile #13
7512~7535
RW
Daily Profile #14
7536~7559
RW
Daily Profile #15
7560~7583
RW
Daily Profile #16
7584~7607
RW
Daily Profile #17
7608~7631
RW
Daily Profile #18
7632~7655
RW
Daily Profile #19
7656~7679
RW
Daily Profile #20
Table 5-32 TOU #1’s Daily Profile Setup
Register Address
Property
Description
Format
8200~8223
RW
Daily Profile #1
See Table 5-34
Daily Profile Data Structure
8224~8247
RW
Daily Profile #2
8248~8271
RW
Daily Profile #3
8272~8295
RW
Daily Profile #4
8296~8319
RW
Daily Profile #5
Page 49
CET Inc.
49
8320~8343
RW
Daily Profile #6
8344~8367
RW
Daily Profile #7
8368~8391
RW
Daily Profile #8
8392~8415
RW
Daily Profile #9
8416~8439
RW
Daily Profile #10
8440~8463
RW
Daily Profile #11
8464~8487
RW
Daily Profile #12
8488~8511
RW
Daily Profile #13
8512~8535
RW
Daily Profile #14
8536~8559
RW
Daily Profile #15
8560~8583
RW
Daily Profile #16
8584~8607
RW
Daily Profile #17
8608~8631
RW
Daily Profile #18
8632~8655
RW
Daily Profile #19
8656~8679
RW
Daily Profile #20
Table 5-33 TOU #2’s Daily Profile Setup
Offset
Property
Description
Format
Note
+0
RW
Period #1 Start Time1
UINT16
0x0000
+1
RW
Period #1 Tariff
UINT16
0=T1, …, 3=T4
+2
RW
Period #2
Start Time
High-order Byte: Hour
UINT16
0 ≤ Hour < 24
Low-order Byte: Min
Min = 0, 15, 30, 45
+3
RW
Period #2 Tariff
UINT16
0=T1, …, 4=T4
+4
RW
Period #3 Start Time
UINT16
See Period #2 Start Time
+5
RW
Period #3 Tariff
UINT16
0=T1, …, 3=T4
+6
RW
Period #4 Start Time
UINT16
See Period #2 Start Time
+7
RW
Period #4 Tariff
UINT16
0=T1, …, 3=T4
+8
RW
Period #5 Start Time
UINT16
See Period #2 Start Time
+9
RW
Period #5 Tariff
UINT16
0=T1, …, 3=T4
+10
RW
Period #6 Start Time
UINT16
See Period #2 Start Time
+11
RW
Period #6 Tariff
UINT16
0=T1, …, 3=T4
+12
RW
Period #7 Start Time
UINT16
See Period #2 Start Time
+13
RW
Period #7 Tariff
UINT16
0=T1, …, 3=T4
+14
RW
Period #8 Start Time
UINT16
See Period #2 Start Time
+15
RW
Period #8 Tariff
UINT16
0=T1, …, 3=T4
+16
RW
Period #9 Start Time
UINT16
See Period #2 Start Time
+17
RW
Period #9 Tariff
UINT16
0=T1, …, 3=T4
+18
RW
Period #10 Start Time
UINT16
See Period #2 Start Time
+19
RW
Period #10 Tariff
UINT16
0=T1, …, 3=T4
+20
RW
Period #11 Start Time
UINT16
See Period #2 Start Time
+21
RW
Period #11 Tariff
UINT16
0=T1, …, 3=T4
+22
RW
Period #12 Start Time
UINT16
See Period #2 Start Time
+23
RW
Period #12 Tariff
UINT16
0=T1, …, 3=T4
Table 5-34 Daily Profile Data Structure
Notes:
1) Daily Profile #1’s Period #1 Start Time is always 00:00 and cannot be modified.
2) Setting a Period’s Start Time as 0xFFFF terminates the Daily Profile’s settings. All later Daily
Profilesetup parameters will be ignored, and the previous Period’s duration is from its Start Time to the end of the day.
3) The minimum interval of a period is 15 minutes.
4) The Start Time of a particular Period must be later than the previous Period’s.
5.12.4 Alternate Days
Each Alternate Day is assigned a Daily Profile and has a higher priority than Season. If a particular
date is set as an Alternate Day, its assigned Daily Profile will override the “normal” Daily Profile for this
day according the TOU settings.
The PMC-340 has two sets of Alternate Days setup parameters, one for each TOU. The Base Addresses for the two sets are 7700 and 8700, respectively, where the Register Address = Base Address + Offset. For example, the register address for TOU #2’s Alternative Day #2’s Date is 8700+3 = 8703.
Page 50
CET Inc.
50
Offset
Property
Description
Format
Note
0
RW
Alternate Day #1 Date¹
UINT32
Table 5-36
2
RW
Alternate Day #1 Daily Profile
UINT16
0 to 19
3
RW
Alternate Day #2 Date¹
UINT32
Table 5-36
5
RW
Alternate Day #2 Daily Profile
UINT16
0 to 19
6
RW
Alternate Day #3 Date¹
UINT32
Table 5-36
8
RW
Alternate Day #3 Daily Profile
UINT16
0 to 19
9
RW
Alternate Day #4 Date¹
UINT32
Table 5-36
11
RW
Alternate Day #4 Daily Profile
UINT16
0 to 19
12
RW
Alternate Day #5 Date¹
UINT32
Table 5-36
14
RW
Alternate Day #5 Daily Profile
UINT16
0 to 19
15
RW
Alternate Day #6 Date¹
UINT32
Table 5-36
17
RW
Alternate Day #6 Daily Profile
UINT16
0 to 19
18
RW
Alternate Day #7 Date¹
UINT32
Table 5-36
19
RW
Alternate Day #7 Daily Profile
UINT16
0 to 19
21
RW
Alternate Day #8 Date¹
UINT32
Table 5-36
22
RW
Alternate Day #8 Daily Profile
UINT16
0 to 19
24
RW
Alternate Day #9 Date¹
UINT32
Table 5-36
25
RW
Alternate Day #9 Daily Profile
UINT16
0 to 19
27
RW
Alternate Day #10 Date¹
UINT32
Table 5-36
29
RW
Alternate Day #10 Daily Profile
UINT16
0 to 19
… … …
… … 240
RW
Alternate Day #81 Date¹
UINT32
Table 5-36
162
RW
Alternate Day #81 Daily Profile
UINT16
0 to 19
243
RW
Alternate Day #82 Date¹
UINT32
Table 5-36
245
RW
Alternate Day #82 Daily Profile
UINT16
0 to 19
246
RW
Alternate Day #83 Date¹
UINT32
Table 5-36
248
RW
Alternate Day #83 Daily Profile
UINT16
0 to 19
249
RW
Alternate Day #84 Date¹
UINT32
Table 5-36
251
RW
Alternate Day #84 Daily Profile
UINT16
0 to 19
252
RW
Alternate Day #85 Date¹
UINT32
Table 5-36
254
RW
Alternate Day #85 Daily Profile
UINT16
0 to 19
255
RW
Alternate Day #86 Date¹
UINT32
Table 5-36
256
RW
Alternate Day #86 Daily Profile
UINT16
0 to 19
258
RW
Alternate Day #87 Date¹
UINT32
Table 5-36
260
RW
Alternate Day #87 Daily Profile
UINT16
0 to 19
261
RW
Alternate Day #88 Date¹
UINT32
Table 5-36
263
RW
Alternate Day #88 Daily Profile
UINT16
0 to 19
264
RW
Alternate Day #89 Date¹
UINT32
Table 5-36
266
RW
Alternate Day #89 Daily Profile
UINT16
0 to 19
267
RW
Alternate Day #90 Date¹
UINT32
Table 5-36
269
RW
Alternate Day #90 Daily Profile
UINT16
0 to 19
Table 5-35 Alternate Days Setup
Notes:
1) The following table illustrates the data structure for the Date register:
Byte 3
Byte 2
Byte 1
Byte 0
Reserved
Year-2000 (0-37)
Month (1-12)
Day (1-31)
Table 5-36 Date Format
When the Year and/or Month are set as 0xFF, it means the Alternate Day is repetitive by year and/or month, i.e. the same day of every year or every month is an Alternate Day.
5.13 Time
There are two sets of Time registers supported by the PMC-340 – Year / Month / Day / Hour / Minute / Second (Register # 60000 to 60002) and UNIX Time (Register # 60004). When sending time to the PMC-340 over Modbus communications, care should be taken to only write one of the two Time register sets. All registers within a Time register set must be written in a single transaction. If registers 60000 to 60004 are being written to at the same time, both Time register sets will be updated to reflect the new time specified in the UNIX Time register set (60004) and the time
Page 51
CET Inc.
51
specified in registers 60000-60002 will be ignored. Writing to the Millisecond register (60003) is optional during a Time Set operation. When broadcasting time, the function code must be set to 0x10 (Pre-set Multiple Registers). Incorrect date or time values will be rejected by the meter. In addition, attempting to write a Time value less than Jan 1, 2000 00:00:00 will be rejected.
Register
Property
Description
Format
Note
60000
9000
RW
High-order Byte: Year
UINT16
0-37 (Year-2000)
Low-order Byte: Month
1 to 12
60001
9001
RW
High-order Byte: Day
UINT16
1 to 31
Low-order Byte: Hour
0 to 23
60002
9002
RW
High-order Byte: Minute
UINT16
0 to 59
Low-order Byte: Second
0 to 59
60003
9003
RW
Millisecond
UINT16
0 to 999
60004
~
60005
9004
~
9005
RW
UNIX Time
UINT32
This time shows the
number of seconds since
00:00:00 January 1, 1970
Table 5-37 Time Registers
5.14 Clear/Reset Control
Register
Property
Description
Format
Note
Model
A B 9600
WO
Clear Monthly Energy Log
1
UINT16
Writing
“0xFF00”
to the
register
execute
the
described
action.
9601
WO
Clear Energy
2
9602
WO
Clear Monthly Energy Log of Present
Month
3
9603
WO
Clear Peak Demand Log of This Month
(Since Last Reset)
4
9604
WO
Clear All Demand Registers
5
9605
WO
Clear Max./Min. Log of This Month
(Since Last Reset)
6
9606
WO
Clear All Max./Min. Log
7
9607
WO
Clear Device Operating Time
9608
WO
Clear All Data8
9609
WO
Clear DI1 Pulse Counter
 9610
WO
Clear DI2 Pulse Counter
 9611
WO
Clear DI3 Pulse Counter
 9612
WO
Clear Data Recorder Logs
 9613
WO
Clear SOE
9614
WO
Clear Counters of Important Setup
Parameters Changes
9615~9618
WO
Reserved
Table 5-38 Clear Control
Notes:
1) Writing 0xFF00 to the Clear Monthly Energy Log register to clear the Monthly Energy Log of the
last 1 to 12 months, excluding the Monthly Energy Log for the Present Month.
2) Writing 0xFF00 to the Clear Energy register to clear the 3-Ø Total and Per-Phase energy registers.
3) Writing 0xFF00 to the Clear Monthly Energy Log of Present Month register to clear the Monthly
Energy Log of the Present Month.
4) Writing 0xFF00 to the Clear Peak Demand Log of This Month register to clear Peak Demand Log
of This Month (Since Last Reset) when the Self-Read Time register is set for automatic Self-Read operation. The Peak Demand of Last Month will not be cleared. If the Self-Read Time register is set for manual operation with a register value of 0xFFFF, the Peak Demand of This Month (Since Last Reset) will be transferred to the Peak Demand of Last Month (Before Last Reset) and then cleared.
5) Writing 0xFF00 to the Clear All Demand Registers register to clear all Demand registers and logs,
including Real-time Present Demand, Peak Demand Log of This Month (Since Last Reset) and Last Month (Before Last Reset).
6) Writing 0xFF00 to the Clear Max./Min. Log of This Month register to clear the Max./Min. log of
This Month (Since Last Reset) when the Self-Read Time register is set for automatic Self-Read operation. The Max./Min. log of Last Month will not be cleared. If the Self-Read Time register is set for manual operation with a register value of 0xFFFF, the Max./Min. log of This Month (Since
Page 52
CET Inc.
52
Last Reset) will be transferred to the Max./Min. log of Last Month (Before Last Reset) and then cleared.
7) Writing 0xFF00 to the Clear All Max./Min. Log register to clear both the Max./Min Log of This
Month (Since Last Reset) and the Max./Min. Log of Last Month (Before Last Reset).
8) Writing 0xFF00 to the Clear All Data register to perform the Clear operation for the action
specified in registers # 9600 to 9607 and # 9609 to 9613.
5.15 Meter Information
Register
Property
Description
Format
Note
60200~60219
9800~9819
RO
Meter model1
UINT16
See Note 1
60220
9820
RO
Firmware Version
UINT16
e.g. 10000 shows the
version is V1.00.00
60221
9821
RO
Protocol Version
UINT16
e.g. 10 shows the version
is V1.0
60222
9822
RO
Firmware Update
Date: Year-2000
UINT16
e.g. 140110 means
January 10, 2014
60223
9823
RO
Firmware Update
Date: Month
UINT16
60224
9824
RO
Firmware Update
Date: Day
UINT16
60225
9825
RO
Serial Number
UINT32
60227
9827
RO
Reserved
UINT16
60228
9828
RO
Reserved
UINT16
60229
9829
RO
Feature Code
UINT16
Bit 0 to Bit 3: Reserved
B4: Current Type
· 0=100A Direct Input
· 1=5A CT Input
B5: Reserved
Table 5-39 Meter Information
Notes:
1) The Meter Model appears in registers 60200 to 60219 and contains the ASCII encoding of the
string “PMC-340” as shown in the following table.
Register
Value(Hex)
ASCII
60200
0x0050
P
60201
0x004D
M
60202
0x0043
C
60203
0x002D
-
60204
0x0033
3
60205
0x0034
4
60206
0x0030
0
60207-60219
0x2020
Null
Table 5-40 ASCII Encoding of “PMC-340
Page 53
CET Inc.
53
Appendix A Data Recorder Parameter List
ID
Parameters
Forma
t
ID
Parameters
Form
at
Basic and Energy Measurements
176
kvarh Total
INT32
1
Uan
Float
177
kVAh
INT32
2
Ubn
Float
178
kvarh Q1
INT32
3
Ucn
Float
179
kvarh Q2
INT32
4
Uln avg
Float
180
kvarh Q3
INT32
5
Uab
Float
181
kvarh Q4
INT32
6
Ubc
Float
182
kWh Import of T1
INT32
7
Uca
Float
183
kWh Export of T1
INT32 8 Ull avg
Float
184
kvarh Import of T1
INT32
9
Ia
Float
185
kvarh Export of T1
INT32
10
Ib
Float
186
kVAh of T1
INT32
11
Ic
Float
187
kWh Import of T2
INT32
12
I avg
Float
188
kWh Export of T2
INT32
13
I4
Float
189
kvarh Import of T2
INT32
14
kWa
Float
190
kvarh Export of T2
INT32
15
kWb
Float
191
kVAh of T2
INT32
16
kWc
Float
192
kWh Import of T3
INT32
17
kW Total
Float
193
kWh Export of T3
INT32
18
kvara
Float
194
kvarh Import of T3
INT32
19
kvarb
Float
195
kvarh Export of T3
INT32
20
kvarc
Float
196
kVAh of T3
INT32
21
kvar Total
Float
197
kWh Import of T4
INT32
22
kVAa
Float
198
kWh Export of T4
INT32
23
kVAb
Float
199
kvarh Import of T4
INT32
24
kVAc
Float
200
kvarh Export of T4
INT32
25
kVA Total
Float
201
kVAh of T4
INT32
26
PFa
Float
Phase C (L3) Energy Measurements
27
PFb
Float
202
kWh Import
INT32
28
PFc
Float
203
kWh Export
INT32
29
PF Total
Float
204
kWh Net
INT32
30
Frequency
Float
205
kWh Total
INT32
31
Uan/Uab (3P3W) Angle
Float
206
kvarh Import
INT32
32
Ubn/Ubc (3P3W) Angle
Float
207
kvarh Export
INT32
33
Ucn/Uca (3P3W) Angle
Float
208
kvarh Net
INT32
34
Ia Angle
Float
209
kvarh Total
INT32
35
Ib Angle
Float
210
kVAh
INT32
36
Ic Angle
Float
211
kvarh Q1
INT32
37
Fundamental PFa
Float
212
kvarh Q2
INT32
38
Fundamental PFb
Float
213
kvarh Q3
INT32
39
Fundamental PFc
Float
214
kvarh Q4
INT32
Basic Energy Measurements
215
kWh Import of T1
INT32
100
kWh Import
INT32
216
kWh Export of T1
INT32
101
kWh Export
INT32
217
kvarh Import of T1
INT32
102
kWh Net
INT32
218
kvarh Export of T1
INT32
103
kWh Total
INT32
219
kVAh of T1
INT32
104
kvarh Import
INT32
220
kWh Import of T2
INT32
105
kvarh Export
INT32
221
kWh Export of T2
INT32
106
kvarh Net
INT32
222
kvarh Import of T2
INT32
107
kvarh Total
INT32
223
kvarh Export of T2
INT32
108
kVAh
INT32
224
kVAh of T2
INT32
109
DI1 Pulse Counter
INT32
225
kWh Import of T3
INT32
110
DI2 Pulse Counter
INT32
226
kWh Export of T3
INT32
111
DI3 Pulse Counter
INT32
227
kvarh Import of T3
INT32
112
kvarh Q1
INT32
228
kvarh Export of T3
INT32
113
kvarh Q2
INT32
229
kVAh of T3
INT32
114
kvarh Q3
INT32
230
kWh Import of T4
INT32
115
kvarh Q4
INT32
231
kWh Export of T4
INT32
116
kWh Import of T1
INT32
232
kvarh Import of T4
INT32
117
kWh Export of T1
INT32
233
kvarh Export of T4
INT32
118
kvarh Import of T1
INT32
234
kVAh of T4
INT32
119
kvarh Export of T1
INT32
Power Quality Measurements
120
kVAh of T1
INT32
300
Ia TDD
Float
Page 54
CET Inc.
54
121
kWh Import of T2
INT32
301
Ib TDD
Float
122
kWh Export of T2
INT32
302
Ic TDD
Float
123
kvarh Import of T2
INT32
303
Ia TDD Odd
Float
124
kvarh Export of T2
INT32
304
Ib TDD Odd
Float
125
kVAh of T2
INT32
305
Ic TDD Odd
Float
126
kWh Import of T3
INT32
306
Ia TDD Even
Float
127
kWh Export of T3
INT32
307
Ib TDD Even
Float
128
kvarh Import of T3
INT32
308
Ic TDD Even
Float
129
kvarh Export of T3
INT32
309
Ia K-factor
Float
130
kVAh of T3
INT32
310
Ib K-factor
Float
131
kWh Import of T4
INT32
311
Ic K-factor
Float
132
kWh Export of T4
INT32
312
Ia C-factor
Float
133
kvarh Import of T4
INT32
313
Ib C-factor
Float
134
kvarh Export of T4
INT32
314
Ic C-factor
Float
135
kVAh of T4
INT32
315
Voltage Unbalance
Float
Phase A (L1) Energy Measurements
316
Current Unbalance
316
136
kWh Import
INT32
317
Uan/Uab THD
Float
137
kWh Export
INT32
318
Ubn/Ubc THD
Float
138
kWh Net
INT32
319
Ucn/Uca THD
Float
139
kWh Total
INT32
320
Uan/Uab TOHD
Float
140
kvarh Import
INT32
321
Ubn/Ubc TOHD
Float
141
kvarh Export
INT32
322
Ucn/Uca TOHD
Float
142
kvarh Net
INT32
323
Uan/Uab TEHD
Float
143
kvarh Total
INT32
324
Ubn/Ubc TEHD
Float
144
kVAh
INT32
325
Ucn/Uca TEHD
Float
145
kvarh Q1
INT32
326
Uan/Uab HD02
Float
146
kvarh Q2
INT32
327
Ubn/Ubc HD02
Float
147
kvarh Q3
INT32
328
Ucn/Uca HD02
Float
148
kvarh Q4
INT32
… Float
149
kWh Import of T1
INT32
413
Ia HD31
Float
150
kWh Export of T1
INT32
414
Ib HD31
Float
151
kvarh Import of T1
INT32
415
Ic HD31
Float
152
kvarh Export of T1
INT32
Demand
153
kVAh of T1
INT32
600
Ia Present Demand
Float
154
kWh Import of T2
INT32
601
Ib Present Demand
Float
155
kWh Export of T2
INT32
602
Ic Present Demand
Float
156
kvarh Import of T2
INT32
603
kW Present Demand
Float
157
kvarh Export of T2
INT32
604
kvar Present Demand
Float
158
kVAh of T2
INT32
605
kVA Present Demand
Float
159
kWh Import of T3
INT32
606
Ia Max. Demand
Float
160
kWh Export of T3
INT32
607
Ib Max. Demand
Float
161
kvarh Import of T3
INT32
608
Ic Max. Demand
Float
162
kvarh Export of T3
INT32
609
kW Max. Demand
Float
163
kVAh of T3
INT32
610
kvar Max. Demand
Float
164
kWh Import of T4
INT32
611
kVA Max. Demand
Float
165
kWh Export of T4
INT32
612
T1 kW Max. Demand
Float
166
kvarh Import of T4
INT32
613
T1 kvar Max. Demand
Float
167
kvarh Export of T4
INT32
614
T1 kVA Max. Demand
Float
168
kVAh of T4
INT32
615
T2 kW Max. Demand
Float
Phase B (L2) Energy Measurements
616
T2 kVA Max. Demand
408
169
kWh Import
INT32
617
T2 kVA Max. Demand
Float
170
kWh Export
INT32
618
T3 kW Max. Demand
Float
171
kWh Net
INT32
619
T3 kvar Max. Demand
Float
172
kWh Total
INT32
620
T3 kVA Max. Demand
Float
173
kvarh Import
INT32
621
T4 kW Max. Demand
Float
174
kvarh Export
INT32
622
T4 kvar Max. Demand
Float
175
kvarh Net
INT32
623
T4 kVA Max. Demand
Float
Page 55
CET Inc.
55
Appendix B Technical Specifications
Inputs (L1, L2, L3, N)
Voltage (Un) Range Burden
240VLN
0.7 to 1.1 Un <10VA/phase
Direct Input
Current (Ib/Imax) Range Starting Current Burden Wire Size Torque for terminals
CT Input
Current (In/Imax) Range Starting Current Burden
20A/100A
0.4% Ib to Imax
0.4% Ib <4VA/phase Maximum 35mm2 (3 AWG) Maximum 2.5 N.m
5A/6A (0.1%-120%) In
0.1% In <0.5VA/phase
Frequency
45Hz-65Hz
Solid State Energy Pulse Output (Selectable - kWh/kvarh)
Pulse Constant Isolation Max. Load Voltage Max. Forward Current Pulse Width
1/10/100/1000/3200 imp/kWh (imp/kvarh) Optical 80V 50mA 60-150ms
Communications
RS-485 Baudrate Maximum Wire Size Maximum Torque
Modbus RTU 1200/2400/4800/9600/19200 bps
1.5 mm2 (16 AWG)
0.45 N.m.
Environmental Conditions
Operating Temp. Storage Temp. Humidity Atmospheric pressure Pollution Degree
-25°C to +70°C
-40°C to +85°C 5% to 95% non-condensing 70kPa to 106kPa 2
Mechanical Characteristics
Mounting Unit Dimensions Shipping Weight Shipping Dimensions IP Rating
DIN Rail 126x90x65mm 165x140x110mm TBD 51 (Front), 30 (Body)
Accuracy
Parameters
Accuracy
Resolution
Voltage
±0.5%
0.01V
Current
±0.5%
0.001A
kW, kvar, kVA
±1%
0.01kW/kvar/kVA
kWh, kVAh
IEC 62053-21 Class 1 for Direct Input
0.01kxh
IEC 62053-22 Class 0.5S for 5A CT Input
kvarh
IEC 62053-23 Class 2
0.01kvarh
PF
±1%
0.001
Frequency
±0.02Hz
0.01Hz
Harmonics
IEC 61000-4-7 Class B
0.1%
TDD
IEC 61000-4-7 Class B
0.1%
Crest Factor
0.5%
-
K-Factor
5%
-
Page 56
CET Inc.
56
Appendix C Standards of Compliance
Safety Requirements
CE LVD 2014 / 35 / EU
EN 61010-1: 2010, EN 61010-2-030: 2010
Insulation
AC Voltage (Dielectric test) Impulse voltage
IEC 62052-11: 2003 NMI M6-1 (PMC-340-B) 4kV @ 1 minute 10kV, 1.2/50µs (NMI M-6)
Electrical safety in low voltage distribution systems up to 1000Vac and 1500 Vdc
IEC 61557-12: 2008 (PMD)
Electromagnetic Compatibility
CE EMC Directive 2014 / 30 / EU (EN 61326: 2013)
Immunity Tests
Electrostatic Discharge
EN 61000-4-2:2009
Radiated Fields
EN 61000-4-3:2006+A1:2008+A2:2010
Fast Transients
EN 61000-4-4:2012
Surges
EN 61000-4-5:2006
Conducted Disturbances
EN 61000-4-6:2009
Magnetic Fields
EN 61000-4-8:2010
V dips, Interruptions & Variations
EN 61000-4-11:2004
Oscillatory Waves
EN 61000-4-12:2006
Radio Disturbances
CISPR 22:2006, Level B
Emission Tests
Limits and methods of measurement of electromagnetic disturbance characteristics of industrial, scientific and medical (ISM) radio­frequency equipment
EN 55011: 2009+A1:2010 (CISPR 11)
Limits and methods of measurement of radio disturbance characteristics of information technology equipment
EN 55022: 2010+AC: 2011 (CISPR 22)
Limits for harmonic current emissions for equipment with rated current ≤16 A
EN 61000-3-2: 2014
Limitation of voltage fluctuations and flicker in low­voltage supply systems for equipment with rated current ≤16 A
EN 61000-3-3: 2013
Emission standard for residential, commercial and light-industrial environments
EN 61000-6-4: 2007+A1: 2011
Electromagnetic Emission Tests for Measuring Relays and Protection Equipment
EN 61000-4-12: 2006
Mechanical Tests
Spring Hammer Test
IEC 62052-11: 2003
Vibration Test
IEC 62052-11: 2003
Shock Test
IEC 62052-11: 2003
Revenue Metering Approval
NMI M-6 of Australia
Approval Mark: NMI 14/2/102 UL Ref. # R4787950540-1-DC & R4787950540-2-CT
Page 57
CET Inc.
57
Appendix D Ordering Guide
Page 58
CET Inc.
58
Contact us
CET Inc. 8/F, Westside, Building 201, Terra Industrial & Tradepark, Che Gong Miao, Shenzhen, Guangdong, P.R.China 518040 Tel: +86.755.8341.5187 Fax: +86.755.8341.0291 Email: support@cet-global.com Web: www.cet-global.com
Loading...