Certikin MBD 200 Operating, Installation And Servicing Instructions

Page 1
NG: GC No.
47 555 18
Corgi Work Code
1014356
LPG:
Corgi Work Code
0087
Note to the Installer: Please leave these Instructions adjacent to the meter.
Operating, Installation and
Servicing Instructions for
MBD200
Condensing
De-Humidifier Boiler
Serial No:
NG
LPG
Page 2
User Instructions
You are the owner of a High Efficiency Condensing Boiler and due to the way it works it will appear to produce a lot of steam from the terminal; this is harm­less, low temperaure water vapour and quite normal. The boiler requires a drain to be permanantly con­nected and this will have been done by your installer, it must not be disconnected or removed. In freezing conditions ensure this drain is kept free of ice. The Gas Safety (Installations and Use) Regulations makes it illegal for gas appliances to be installed or serviced by persons not Corgi Registered Operatives. All Corgi Registered Operatives carry a Corgi ID card and have a registration number. This can checked by calling Corgi on 01256 372300.
IMPORTANT: DO NOT DISTURB THE APPLIANCE CASE
The appliance must be connected to a 230V AC 50 Hz supply with a 5 Amp fuse rating and must be Earthed.
The Certikin MBD 200 appliance is made with two independant condensing boilers that can work together or separately. It is designed to work simply and auto­matically with your de-humidifier and heating controls. To operate it has to be connected to both gas and electricity, the Front Panel switches in an On position, and the De-Humidifier or Heating controls calling for heat.
Quick Start
Set the De-Humidifier or Heating Controls to On. Turn both Thermostat Knobs fully cockwise to Normal then select the required service.
Pool and Heating (A only), for periods of light de­mand, like during the Summer.
Pool Boost (A & B), for rapid pool only heating. Pool and Heating (A & B), during periods of heavy
demand, like during the Winter. The operation is now fully automatic.
Indicators (a set for each boiler)
Power: Off - Mains not connected. On - The boiler is connected to the Mains.
MBD200
1
14/02/04
Running: Off - There is no demand from the external controls. On - There is a call for a boiler to fire. Flashing - The boiler thermostat is off.
Fan, Pilot and Burner:
These are diagnostic indicators for fault finding.
Lockout:
The boiler has shut itself off. Wait for the boiler to cool and then reset by turning the boiler Thermostat Knob Off then On.
Selector Switch:
Pool and Heating (A only) - Only boiler A will be
working, heating Pool water, Air, and secondary Space Heating.
Pool Boost - Both boilers will be working for Pool water and Air heating.
Pool and Heating (A & B) - Both boilers are avail­able for heating the Pool water, Air, and secondary Space Heating.
To Turn Off for a Short Period
Turn the Thermostat Knobs fully anti-clockwise and set all external controls to Off. In this condition the boilers will protect themselves from freezing by firing if the temperature falls below about 4°C
To Turn Off for a Long Period
Turn the Thermostat Knobs fully anti-clockwise, set all external controls to Off and the switch off the Mains supply. Please note there is no boiler Frost Protection once the Mains supply is Off. If the appliance is going to be off during the Winter it is recommended that a Frost Thermostat is fitted, the system is drained or it is filled with a suitable anti­freeze.
Maintenance
There are no user servicable parts. To clean the case wipe with a damp cloth, do not use an abrasive cleaner. It is recommended that the appliance is serviced twice a year by a CORGI Registered Engineer.
Page 3
Contents
Section Page
User Instructions 1 Introduction 2 Boiler Location 3 Gas Supply 3 Flueing 3 Air Supply 4 Water Supply 4 Condensate Drain 4 Sealed Systems 4 Electricity Supply 5 Installation 5
Removing Case
5
Boiler Location
6
Flue and Air Duct
6
Terminals
6
Plumbing
6
Gas Connection
6
Condensate
6 Heating Design 7 Electrical Connections 7 Commissioning 7 Fault Finding 18 Servicing 20 Technical Data 21
List of Figures Page
Fig 1.
Gas Valve
10 Fig 2.
Installation Dimensions
11 Fig 3.
Schematic Wiring
13 Fig 4.
Physical Wiring
14 Fig 5.
Low Voltage Connections
15 Fig 6.
Boiler Panel Assembly
16 Fig 7.
Concentric Flue & Air duct
19
Positions
Fig 9.
Electrical Components
23 Fig 10.
Major Components
24 Fig 11.
Example Condensate Disposal
25 Fig 12.
Condensate Drain Trap
25
Introduction
These Instructions cover the MBD200, a frame mounted, gas fired, condensing boiler which is room sealed and fan assisted on the flue side. The flue systems are Concentric, left, right, or rear, up to 2 metres.
The appliance is two boilers mounted on the frame, which are plumbed to common pipework so that they can work together or independantly.
It is designed to work with a De-humidiifer and an optional sealed heating system. These systems must be pumped and use the pumps integral to the appli­ance. The boiler casing is powder coated mild steel.
The boilers include pump overrun devices so it is essential that there is an open circuit for water to flow between the flow and return. An automatic bypass is provided on the Heating circuit.
The boilers also contain integral frost protection, a boiler will fire if the temperature within it approaches 4 to 5 degrees Centigrade. It will do this even when turned to Off, and can only be inhibited by removing the Permanent Live supply to the boiler.
Adequate arrangements for completely draining the system, by provision of drain cocks MUST be pro­vided.
Gas Safety (Installation and Use) Regulations, (as amended).
It is the law that all gas appliances are installed by a competent person (e.g. a CORGI registered opera­tive) in accordance with the above Regulations. Failure to install appliances correctly could lead to prosecution.
It is in your own interest, and that of safety, to ensure that the law is complied with. The installation of the boiler MUST also be in accordance with the current I.E.E.. Wiring Regulations, the Local Building Regu­lations, Building Standards (Scotland), the Bye Laws of the Local Water Undertaking, any relevant re­quirements of the Local Authority, and Health and Safety document No 635, “Electricity at Work Regu­lations”.
Detailed recommendations are contained in the following British Standard Codes of Practice.
Codes of Practice.
BS.6798 Installation of gas fired hot water boilers of rated input not exceeding 70kW. BS.5449:1 Forced circulation hot water systems (small bore and microbore domestic central heating systems). BS.5546 Installation of gas hot water supplies for domestic purpose (2nd Family Gases). BS.5440: Part1. Flues (for gas appliances of rated input not exceeding 60kW). BS 6891 Specification for installation of low pressure gas pipework. BS 7074:1 Application, selection and installation of expansion vessels and ancillary equipment for sealed water systems. BS5482:1 Code of practice for domestic butane & propane gas burning installations. Building Regulations Part L1.
MBD200
2
14/02/04
Page 4
IMPORTANT.
It is important that no external control devices are directly connected to this appliance - unless covered by these ‘Installation and Servicing Instructions’ or otherwise recom­mended by the manufacturer. If in doubt, please enquire.
A 12V DC circuit is provided for system control devices located in wet areas.
Any direct connection of a control device not recommended by the manufacturer could infringe the Gas Safety (Installation & Use) Regulations, the above regulations and the normal appliance war­ranty.
Manufacturer’s notes must NOT be taken, in any way, as overriding statutory obligations.
Location of Boiler
The boiler MUST be fixed to a floor or vertical non­combustible wall, capable of adequately supporting the weight of the boiler and any ancillary equip­ment.
THE BOILER IS NOT SUITABLE FOR EXTERNAL INSTALLATION.
IMPORTANT NOTICE.
If the boiler is to be fitted in a timber framed building it should be fitted in accordance with the British Gas publication ‘Guide for Gas Installations in Timber Frame Housing’, reference DM2. If in doubt, advice must be sought from the Local Gas Region of British Gas.
The boiler may be installed in any room or internal space. Particular attention is drawn to the require­ments of the current I.E.E Wiring regulations and, in Scotland, the electrical provisions of the Building Regulations applicable to Scotland with respect to the installation of the boiler in a room or internal space containing a bath or shower.
Where a room sealed appliance is installed in a room containing a bath or shower then the appli­ance and any electrical switch or appliance control, utilising mains electricity should be so situated that it cannot be touched by a person using the bath or shower.
Where installation will be in an unusual location then special procedures may be necessary and BS.6798 gives detailed guidance on this aspect.
A compartment used to enclose the boiler MUST be designed and constructed specially for this purpose. An existing cupboard, or compartment, may be used provided it is modified for the purpose. Details of essential features of cupboard compartment
design, including airing cupboard installations are given in BS.6798. In siting the boiler, the following limitations MUST be observed:
1. The position selected for installation MUST allow adequate space for servicing in front of the boiler and for air circulation around the boiler.
2. This position MUST also permit the provision of a satisfactory balanced flue termination.
3. This position MUST also permit the provision of a satisfactory connection to the condensate drain.
Gas Supply
An existing meter (NG) and pipework should be checked, preferably by the Gas region, to ensure that they are adequate to deal with the rate of gas supply required. Supply pipes should be sized to suit installation and obtain a working pressure of 20 mbar (NG) or 37 mbar (Propane). Installation pipes should be fitted in accordance with BS.6891. A Natural Gas appliance must be connected to a governed meter.
Conversion
The appliance can be converted from NG to LPG or vice versa by change of the Burner, Main and Pilot Injectors and re-setting the Gas Valve. Contact your supplier for the necessary parts.
Flueing
Only flue components provided by the Manufacturer should be used with these appliances. Detailed recommendations for flueing are given in BS.5440: 1. The following notes are intended for general guid­ance.
1. Be aware of the plume from the flue and the wetting effect it has to adjacent property.
2. The flues can be taken left, right or to the rear of the appliance.
3. The appliance is supplied with two standard flue sets. There are two lengths of Concentric Flue. Standard, that will reach 500mm, and Extended that will reach up to 2000mm. (Part No. M3838).
4. The boiler MUST be installed so that the termi nals are exposed to external air.
5. It is important that the terminals allow the free passage of air across them at all times.
6. The acceptable spacing from the terminal to obstructions and ventilation openings are specified in Table 1.
7. Because the flue gases and terminal are at very low temperature it is not necessary to fit a Terminal guard to protect against burns. If a guard is required for any other reason the following is recommended.
MBD200
3
14/02/04
Page 5
For the
Concentric
Terminal:
Model K3 6.5 x 11 (plastic coated) (GC No 393554)
All are available from:
Tower Flue Components Ltd.
Tower House.
Vale Rise. Tonbridge
KENT
TN9 1TB
01732 351555
Table 1
.
IMPORTANT.
It is absolutely ESSENTIAL to ensure, in practice, that products of combustion discharging from the terminal cannot re-enter the building, or any other adjacent building, through ventilators, windows, doors, other sources of natural air infiltration or forced ventilation/air conditioning.
If this should occur, the appliance MUST be turned OFF IMMEDIATELY and the Local Gas Region consulted.
Air Supply
It is NOT necessary to have a purpose provided air vent in the room or internal space in which the boiler is installed.
Where the boiler is installed in a cupboard or compartment no air vents are required. However the User may wish to ensure that is ventilated to provide air circulation.
Water Supply
Aheating system should be in accordance with the relevant recommendations given in BS.6798, BS 7593:1992 and, in addition, for smallbore and microbore systems - BS.5449:1.
The domestic hot water system, if applicable, should be in accordance with the relevant recommenda­tions of BS.5546.
Copper tubing to BS 2871:1 is recommended for water carrying pipework.
The hot water storage cylinder MUST be of the indirect type and should preferably be manufactured of copper.
The hot water cylinder, & ancillary pipework, not forming part of the useful heating surface should be lagged, to prevent heat loss and any possible freezing, particularly where pipes run through roof spaces and ventilated underfloor spaces.
A Drain Tap is provided and should be installed in an accessible position on an unused end of the Heating manifold. Any other installed Draining taps should be at least ½” nominal size and be in accord­ance with BS.2879
.
Condensate Drain
Refer to Fig. 2, and 12.
A condensate drain is provided on the boiler, this drain must be connected to the household drainage point, or soakaway on site. All pipework and fittings in the condensate drainage system MUST be made of plastic. Refer to British Gas publication “Guidance notes for installation of domestic condensing boil­ers”
No other materials may be used.
The drain outlet on the boiler is :
Polypipe, 21.5mm pushfit overflow pipe.
Sealed Systems
The sealed system should follow the guidelines given in the Code of Practice BS 7074 :1. The appliance includes a 3 bar (45 lb/in²) safety valve to BS 6750 Pt 1. It should be installed on an unused end of the Return manifold and discharge through a pipe to a safe outlet.
A 10l expansion vessel, complying with BS 4814 is also fitted on the return side of the pumps. If addi­tional system pipework is added the size of the vessel should be checked using the table below. If the fitted unit is not large enough the following steps should be taken to determine the required size.
MBD200
4
14/02/04
Terminal Position Minimum
Below window or vent 300 mm
Below gutter or pipes 75 mm
Below eaves 200 mm
Below balcony or roof 200 mm
From a window 200 mm
From vertical pipe 75 mm
From corners 300 mm
Above ground, roof or balcony 300 mm
From facing surface 600 mm
From facing terminal 1200 mm
From opening under a car port 1200 mm
Vertically from a terminal 850mm
Horizontally from a terminal 300 mm
Page 6
1. Choose a vessel pressure by taking the static head of the system, adding 0.3 bar, and taking the nearest larger size.
2. Select the Vessel Volume from the table below by finding the system volume and vessel pres­sure.
3. Subtract 10 for the vessel in the appliance then, choose that size or larger from the manufacturers’ range.
Vessel System Volume
Litres
Pressure
50 60 70 100 150
Bar
Vessel Volume
0.5 4 4 8 8 12
1.0 8 8 8 12 18
1.5 8 12 12 18 24
A pressure gauge with a fill pressure indicator and a range of 0-4 bar is fitted on the appliance front panel.
A Filling Loop incorporating a BS 1010 stop valve, a double non-return valve is provided with the appli­ance. It should be installed on the unused end of the LPHW Flow manifold with the approval of the local Water Undertaking.
Electricity Supply
Refer to Figs. 3, 3a and 4.
Wiring external to the appliance MUST be in accord­ance with the current I.E.E. Wiring Regulations and any Local Regulations that apply.
The boiler is supplied for 230V ~ 50Hz. Single phase. Fuse rating is 5A.
The method of connection to the mains electricity supply MUST facilitate complete electrical isolation of the boiler, preferably by the use of a fused double pole switch having a 3mm (1/8in.) contact separation in both poles and servicing only the boiler and system controls. The point of connection to the mains should be
readily accessible and adjacent to the boiler, except that, for bathroom installations, the point of connec­tion to the mains MUST be situated outside the bathroom.
Note.
Where a room sealed appliance is installed in a room containing a Pool, Bath or Shower, the appliance, any electrical switch or appliance control utilising mains electricity should be so situated that it cannot be touched by a person using the bath or shower.
The appliance incorporates a 12V DC switching circuit for connection to system controls in wet areas. All such system controls MUST be voltage free.
Installation Of Boiler
Suggested procedure:
1. Site to suit system and terminal limitations.
2. Mark & Drill Flue holes. See
Fig. 2
3. Fix Boiler Frame to the wall and/or floor.
4. Remove the Electrical tray and the Cases from
boiler module.
5. Fit the flues.
6. Plumb to the system and gas.
7. Fit the Filling Loop provided to an unused end of
the LPHW manifold.
8. Fit the Drain Tap provided and unused end of the
Heating manifold.
9. Fit the Safety Valve provided to an unused end of
the Return manifold.
10.Test for leaks.
11.Wire Mains supply and System Controls.
12.Replace the Cases and Electrical tray.
Space Required for Installation and Service.
Right or Left 30 mm 1¼ in.
Above 30mm 1¼ in.
Below 25mm 1 in.
In Front 450mm 18 in.
Removal of the Case
Refer to Fig. 6
1. Remove the Lower Cover by pulling forward.
2. Remove the Electrical Cover. This is detached by
pulling the cover towards you and carefully lowering. Care should be taken to prevent strain on the cables and connections.
MBD200
5
14/02/04
ALTERNATIVE METHODS OF FILLING A SEALED SYSTEM
Method A
Method B
Hose Unions
Air Inlet
Valve
Temporary Hose
Mains
Water
Supply
Mains Water
Supply
Test Cock
Stop Valve
Drain & Fill
Double Check Valve Assembly
Drain &
Fill
Cistern & Overflow
Pressure Pump & Reducing Valve If Required
Stop Valve
Page 7
MBD200
6
14/02/04
3. Remove the case by unscrewing the two pozidrive screws located at the bottom and rear of the case, and lifting and pulling forward off the two pegs which are located at the top. The case should be kept vertical as it is removed. Examine the sealing strip for damage and replace if neces­sary.
IMPORTANT: FAILURE TO CORRECTLY LOCATE THE APPLIANCE CASE COULD RESULT IN LEAKAGE OF COMBUSTION PRODUCTS INTO THE ROOM.
Boiler Location
1. Site to suit system and terminal limitations.
2. Secure the frame to the wall and/or floor with the
brackets supplied.
Assembly Of Flue Pipe & Air Duct Pipe to the Boiler
The following is based on the flue tube being sup­plied with the straight and elbow connectors being pre-assembled, the one NOT required to be cut off during installation.
Right or Left Outlet
1. Secure the 50mm flue tube with ELBOW connec­tor on the saddle using the Velcro strap.
See Fig. 7
2. Measure carefully and saw off the 50mm tube to give required projection from wall.
See Fig. 7
3. Measure carefully and saw off the 110mm Air duct tube to give required projection from wall. The flue pipe must project more than the outer air duct when assembled.
See Fig. 7
Note:
It is acceptable to obtain this dimension by pulling the air duct away from the air duct stop, provided there is a minimum of 10mm (1/2 in.) insertion into the Boiler Mounting Box and that a satisfac­tory seal is achieved.
4. For extended flues, position the air duct support clips provided every 700mm.
Rear Outlet
Install as above but using the STRAIGHT connector in the Boiler Mounting Box. Follow the instructions under Right or Left Outlet, points 1,2,3 and 4.
Terminals
Fix to the outside wall with the ‘T’ cutout, towards the top face which contains no holes. If a guard is fitted, the terminal should be at its centre.
Plumbing
If the requirement for Heating exceeds 50,000 Btu/h (15kW), the Flow and Return pipework from the appliance must be 28mm until the heat load allows smaller bore pipework.
The appliance includes a pump overun devices and there must be a flow path in the system at all times. An automatic bypass has been provided in the Heating circuit for this reason.
New pipework must be flushed through before connecting.
Gas Connection
The 28m Copper gas connection is shown in
Fig.2
. A minimum of 20mb. (NG), 37mb (LPG) must be available at the boiler inlet, with the boiler and other connected appliances firing. Check for gas sound­ness (B.S. 6891) in pipework to boiler using a manometer. Open the gas cock. Gas soundness within the boilers should be checked using sense of smell and/or leak detection fluid. Check the burner bar pressures with a manometer connected to the control and adjust if required, with the pressure regulator on the Gas Valve.
Condensate Connection
The position of the plastic condensate drain pipe is shown in
Fig 2
. Where possible an internal termination of the Con­densate discharge pipework should be used.
Installation pipework must be in plastic to a suitable drain location with a gradient of 2.5° (45mm/ metre run) minimum. If connected to another drainage trap, an air break is required between the boiler drain and that trap. (
see Fig.11
). Internal runs must be in a minimum of 19mm pipe. External runs MUST be made in a minimum of 32mm pipe, starting inside the building, and if possible insulated to defer prob­lems from freezing.
Whichever method is used it should be checked during commissioning to prove there is a leakfree working connection from the boiler to the drain. The simplest way to do this is to carefully pour some water into the boiler flue and check it emerges at the drain.
The British Gas booklet “Guidance for the installation of Domestic Condensing Boilers” should also be referred to.
Page 8
MBD200
7
14/02/04
Heating Design
General principals
The system should be designed to conform with the latest requirements of the Building Regula- tions.
Condensing Boilers give their best performance when the system water temperature is as low as possible and still achieve the desired room tempera­tures. Oversized radiators make this easier to achieve but are not essential as, even in a standard designed installation, most of the boilers’ working hours are spent with the system producing much less than the designed output. This is because the outside temperature is often higher than the figure used for the design, typically -1 to -2º C.
The Manufacturer recommends the use of a voltage free, programable room thermostat, alternatively a separate timeswitch and room thermostat can be used.
The boilers include pump overrun devices so it is essential that there is an open circuit for water to flow between the LPHW flow and return. In some system designs this may require the addition of a bypass, an automatic bypass is reccommended.
They also contain integral frost protection, a boiler will fire if the temperature within it approaches freezing. It will do this even when turned to Off, and can only be inhibited by removing the Permanent Live supply to the boiler.
Thermostatic radiator valves can be used. An automatic bypass is incorcporated in the appliance for the heating circuit.
The boiler waterside is completely copper so all good corrosion inhibitors are suitable.
Designs
The following designs are all acceptable:
1. Sealed system to BS.6798 and BS.5449:1
2. Combined Feed and Vent systems.
3. Separate Cold Feed and Vent systems.
The pump is on the return, careful note of its posi­tion relative to the feed and vent MUST be made to avoid pumping over, or sucking in air. The design temperature difference across the boiler for opti­mum operating efficiency is 20ºC. If thermostatic valves or zone valves are used ensure the minimum flow shown in the
Technical Data on page 21
is
possible.
Electrical Connections
WARNING: The appliance MUST be earthed.
All wiring for the boiler and system controls MUST conform to I.E.E. Wiring Regulations, and work should be tested using a suitable meter, for Earth Continuity, Polarity, Short Circuit and Resistance to Earth.
The supply must be through a common isolator, a double pole 3A fused isolating switch with a contact separation of 3mm minimum on both poles. The cable used should be no less than 0.75mm2 to BS.6500 PVC, 3 core, and fixed ensuring the earth connection is longer than the Live and Neutral.
Access to the boiler connections is made by with­drawing the Electrical Tray then releasing the screw retaining the cover over the push fit screw terminals. The boiler internal wiring is shown in
Fig.3, Fig.4
and Fig.5.
Connections are as follows :-
Supply Connection
Earth N Mains Neutral L Permanent Live
Pump Connections
Earth N Pump Neutral Lp1 Pump No1 Live Lp2 Pump No2 Live
Controls
1 +12 V DC to External controls. 2 +12V DC from Dehumidifier 3 +12V DC from Heating control E Earth, 2 Port Valve N Neutral, 2 Port Valve 4 2 Port Valve, Br 5 2 Port Valve, Or 6 2 Port Valve, Gy
The appliances includes pump overrun and the Pumps have been factory connected to their respec­tive push-fit connectors. External controls
MUST BE
voltage free and con-
nected to terminals 1, 2 and 3.
Commissioning
General
The elimination of air from systems is essential to minimise the occurrence of heat exchanger and general system noise. It is particularly important for lightweight boilers.
Metal swarf and flux chemicals make a very aggres­sive mixture, the destructive nature of which can be drastically reduced by flushing. Consequently this is a mandatory step in the commissioning procedure.
Page 9
MBD200
8
14/02/04
Carry out electrical tests as stated in Electrical Connections if not already done so.
With all valves fully open, and the filling loop con­nected, fill from the mains supply, then follow the procedure below.
Check for water soundness and rectify where neces­sary.
Check that there is a leakfree working connection from the boiler to the drain. The simplest way to do this is to carefully pour some water into the boiler flue and check it emerges at the drain.
DO NOT TURN ON GAS
Drain the system by opening all draincocks. This will flush the system of flux and swarf.
Pour in all the inhibitor, and fill to required pressure plus 0.3 bar to allow for venting.
Switch on the electrical supply to the boiler and switch the Thermostat/Timeswitch ON.
Switch off after about five seconds and vent all points again.
Repeat this for 5 minutes.
Re-pressurise if required.
Turn on pump (do not turn on gas) and run for at least 30 minutes with all valves open.
Stop pump at five minute intervals and vent until no more air can be removed and air noises are no longer produced at the boiler. While the system is venting check again for water soundness.
TURN ON THE GAS
Check for gas soundness (BS 6891) in pipework to boiler using a manometer.
Select each boiler in turn, open the gas cock and after purging the system, the boiler will light auto­matically.
Run system at maximum thermostat setting.
Gas soundness within the boiler should be checked using sense of smell and/or leak detection fluid.
Continue running for 15 minutes, venting every 5 minutes.
The Pilot is factory set.
The Main Gas Valve, GV2, gradually raises the pressure to the set point. Allow at least 60 seconds for the final pressure to stabilise.
IMPORTANT. It is essential when setting the burner pressure that the inlet pressure is at least 20 mbar (NG), 37 mbar (LPG) with the boiler and any other connected appliances running.
Set the burner pressures to the correct pressure by using a manometer connected to the control and adjusting the regulator to the desired input. (see the charts below and Fig.1)
Low water content, fabricated boilers are vulnerable to damage by air, particularly when the system water is ‘hard’. (Contains a lot of dissolved calcium salts). The result of this damage is evident in noisy boilers and reduced service life.
Removal of air from a system mainly takes place when the water is stopping, starting or not moving at all. It is removed most easily when it is in large bubbles, but the action of the pump is to chop it up so that it becomes a foam, which is extremely difficult to remove.
Two or three second bursts on the pump at the initial stage will reduce the risk of foam formation.
Sloping the pipe runs towards the vent points will greatly aid air removal. Sloping pipes are not just a feature of gravity systems but can greatly aid the pumped system because air can move towards a vent when the pump stops.
Air is dissolved in water but is released when heated. Always run a system at maximum temperature for at least 15 minutes to enable this potential problem to be removed during commissioning.
Commissioning Procedure
The boiler is fitted with automatic ignition and will start when the gas cock is open, mains is connected to the boiler and the controls calling for heat.
NOTE:
If the boiler has just been filled with very cold water, the built in Frost Thermostat will attempt to fire it if it has a permanent live and no switched live, this is completely normal. It is recommended that the gas cock is turned off during this early stage. Because of a built in delay, the boiler is always held off for a minimum of 120 seconds. However, for commission­ing purposes, switch off using the System Isolating Switch will avoid the delay.
It is strongly suggested that the following stages of commissioning are followed, and not an immediate connection of all services. This procedure prevents substantial amounts of air being dispersed through the system as small bubbles.
Page 10
MBD200
9
14/02/04
Rating Table (1040 Btu/ft³) (38.8 MJ/m³)
kW Btu/h sec/ft³ m³/2 mins
20 68240 54.9 0.0619
22 75064 49.9 0.0680
24 81888 45.7 0.0742
26 88712 42.2 0.0804
Note: The boiler is fitted with a syphon trap that includes a blocked drain device. This is to safeguard the boiler and help defer the ef- fects from the possible freezing of the con- densate pipework in extreme weather.
The user should be made aware of this fea- ture and, that in the event of blocked con- densate pipework, for example frozen con- densate pipework, the boiler will automati- cally stop functioning. It will start again as soon as the blockage has cleared.
For designs with a heating system check the operation of the bypass with the system hot. The minimum flow rate through the boiler should be as shown in the Technical Data on Page 21.
Set the pump speed to the highest setting that does not provoke unreasonable operational noise within the system.
Re-pressurise to required pressure and set the
gauge indicator
With the system hot, check again for water sound­ness.
Refit the case to the boiler.
For designs with heating circuits, balance the system in the normal way to obtain even heating of all radiators.
If fitted set the cylinder thermostat to 60oC, or lower if preferred.
Commission Check List (hydraulic)
The key points which must be observed closely, are shown below.
With valves and vents open fill the system.
Do not use pump. Do not light gas
Check for and rectify leaks.
Drain to flush system.
Refill system, adding the inhibitor.
Do not light boiler.
Vent all radiator and air release points.
Run pump for 5-10 second bursts and revent.
Do not light boiler.
Run pump for at least 30 minutes.
Stop at 5 minute intervals to vent.
Continue venting until no more air noise can be
heard.
Light boiler and run at max thermostat setting.
Continue for 15 minutes, venting every 5 minutes.
Rating and Setting Pressures for each boiler
Input v Burner Pressure
18
20
22
24
26
9 10 11 12 13 14 15 16
mBar
Input (gross) kW
Page 11
MBD200
10
14/02/04
Fig.1
Page 12
Front View
C
L
Rear Flue
Side View
Left, Right or Rear
128 mm
Suggested core drill
Boiler service access
Front 450mm Above 30mm
Sides 30mm
F
lu
e
1
0
0
t
o
2
0
0
0
m
m
S
i
d
e
F
l
u
e
495
515
1760
Flue Pipes
Degrees
0 to +3
1
9
5
55 mm
1650
Degrees
0 to +3
C
L
7
8
8
85
165
375
475
L
P
H
W
F
lo
w
R
e
t
u
r
n
CH Flow
Gas
MBD200
11
13/01/05
Installation Dimensions and Service Access
Fig.2
Page 13
MBD200
12
14/02/04
35mm
28mm
Gas Manifold
Heating Flow Manifold
LPHW Flow Manifold
Return Manifold
Safety
Valve
V
a
lv
e
Bypass
Filling
Loop
Drain
Tap
3
5
m
m
2
8
m
m
2 Port
Valve
Condensate
Trap
Condensate
C
o
n
n
e
c
t
io
n
Fig.2a
Pipe Connections & Locations
Page 14
SUPPLY
PUMPS
E
E
N
N
Ls A
L
LpA
HT
N
Ls
L
Lp
COM
AIR
NOAIR
O/H
O/H
SENSOR
SENSOR
12 Way connector
GV1
GV2
N
4 Core to Gas Valve
NC
Flue Stat
O/H Stat
Air presssure switch
Fan
4 way Molex
10 way Molex
Sensor
GV1
GV2
1 Amp 20mm
CONTROL BOARD
Or
Or
Br
Br
R
W
Bk
GyBrR
Bk
Br
Gy
G/Y
G/Y
G/Y
B
G/Y
V
Gy
Br
R
Or
W
Bk
Gy
V
G/Y
B
Brown
Red
Orange
White
Black
Blue
Grey
Violet
Green & Yellow
B
NO
10/07/06
LpB
Control Board 'B'
CONTROLS
2 PORT
+12v DC
DEHUM
HEATING
Br
Or
Gy
VALVE
E
N
1
2
3
4
5 6
MBD200
13
14/2/04
Schematic Wiring (one boiler only)
Fig.3
Page 15
MBD200
14
14/02/04
Physical Wiring Diagram (one boiler only)
Fig.4
Page 16
MBD200 15 3/05/05 4
Fig.5
Low Voltage System Connections
3/05/05
MBD200
Selector Switch
Selector Switch
500 mA
a b
c
a b
c
a b
c
230 V AC
12 V DC
12V AC
+
-
6
2Port Valve
Or
Gy
Br
B
N
E
G/Y
L
Clock
De-Humidifier
HTG
Thermostat
5
4
3
2
1
R
Bk
Or
Or
Y
Br
Br
V
R
Ls A Ls B
(Direct to Molex)
b: Pool Boost (A & B)
a: Pool & Heating (A only)
c: Pool & Heating (A & B)
Br
Gy
Br
Br
Y
N
7
(Delta/Variheat
terminals shown)
6
Models before Serial No 05017481
Page 17
10/07/06
MBD200
Selector Switch
Selector Switch
500 mA
a b
c
a b
c
a b
c
230 V AC
12 V DC
12V AC
+
-
2Port Valve
E
L
Clock
De-Humidifier
HTG
Thermostat
Bk
Or
Br
V
R
Ls A Ls B
(Direct to Molex)
b: Pool Boost (A & B)
a: Pool & Heating (A only)
c: Pool & Heating (A & B)
Br
Br
Br
Y
N
7
(Delta/Variheat
terminals shown)
6
N
Y
Or
R
Or
Gy
Br
B
G/Y
R
Br
R
Gy
6
5
4
3
2
1
MBD200
15
10/07/06
Low Voltage System Connections
Fig.5
Models after Serial No 05017481
Page 18
MBD200
16
14/02/04
Boiler Panel Assembly
Fig.6
Concentric Flue Boiler Mounting Box
Side Trim
Pressure Cover
Front Burner Baffle
Lower Burner Baffle
Electrical Cover
Lower Trim
Controls Chassis
Page 19
MDB200
17
14/02/04
Fault Diagnosis (one boiler shown)
Page 20
MBD200
18
14/02/04
Fault Finding (for boiler only)
The electrical sequence in the boiler is very straightforward and faults can easily be tracked down if this simple sequence is followed.
System Controls - - - - Flue Stat - - - - Overheat Stat - - - - Pressure Switch - - - - Control Board - - - - Ignition
The lamps on the front panel indicate several of the stages in the ignition sequence.
Firstly a Permanent live has to be connected to the L terminal then the power lamp lights.
When the system controls and the programmer are calling for heat, power is fed to the boiler initiating the following sequence.
A call for heat powers the Ls terminal and the running and pump lamps light. Provided the Flue Stat, Overheat Stat and boiler are cold, the fan starts up. The pressure switch detects the correct airflow and that the condensate drain is not blocked then, switches over. This is indicated by the fan lamp illuminating.
The pilot lamp illuminates, the pilot gas valve opens and the Control Board provides a spark at the pilot elec­trode. (If the L and N supply are reversed the boiler will not progress beyond pilot ignition. This is indicated by the phase reversed neon behind the knob lighting.) The pilot flame is detected and the control board stops sparking and then energises the main gas valve and the burner lamp is illuminated.
The pilot flame lights the burner, and it stays alight until turned off by the control thermostat, system controls, or in the case of a fault condition a safety thermostat. The flue thermostat will trip if the flue exceeds a pre-set temperature. The overheat thermostat will trip if the water flow rate is insufficient, both are indicated by the lockout lamp illuminating.
NOTE
: The boiler has a built-in delay timer. It is indicated by the running lamp flashing.
For testing, switching the Mains Supply off for a few seconds, then back on again will reset the delay.
WARNING
: BEFORE COMMENCING OR COMPLETING ANY ELECTRICAL WORK ON THE APPLIANCE, IT IS RECOMMENDED THAT THE BASIC SAFETY CHECKS FOR EARTH CONTINUITY, SHORT CIRCUIT, POLARITY AND RESISTANCE TO EARTH ARE MADE. ALL WORK CARRIED OUT SHOULD FOLLOW GUIDELINES LAID DOWN BY THE I.E.E.
Fault Diagnosis
The Fault Diagnosis chart shows the normal and fault sequences for the boiler indicator lamps. To diagnose a fault, use the following procedure.
· Turn off the system Mains supply.
· Set all thermostats and timers to a call for heat position.
· Turn on the system Mains supply and watch the boiler indicator lamps.
Compare the lamps with the diagnosis chart opposite to determine the fault and cause.
Page 21
MBD200
19
14/02/04
Concentric Flue, positions
Fig.7
78 mm (3.0")
OUTSIDE FACE OF WAL
L
OUTSIDE FACE OF WALL
10 mm (0.4")
F
L
U
E
A
IR
D
U
C
T
Fig. 7
Page 22
MBD200
20
14/02/04
Servicing
Health and Safety Statement :
This product contains no asbestos.
Routine
To ensure continued efficient operation of the appli­ance it is recommended that it is checked and serv­iced at regular intervals. The frequency of servicing will depend upon the particular installation and usage but in general twice a year will be adequate. It is law that any service work should be carried out by Corgi registered personnel.
1. Clean burners and combustion chambers.
2. Check pilots and burner gas supply.
3. Check condition of ignition sensing probes.
4. Check boiler pipework joints for leaks.
5. Check the case seals.
6. Check condensate pipework for leaks.
7. Check heat exchangers, and the flue and air ducts
are clear of any obstruction, and not leaking.
8. Check the Fans and thieir seals.
9. Check and clear the Condensate exit on the
secondary heat exchangers by removing the Condensate Outlets and the Inspection Cover (
Fig. 10
).
10. Check and clear the condensate syphon trap.
The following procedures are given for one boiler but apply to both.
1.Heat Exchangers
Remove the panel in front of the secondary heat exchanger to gain access to inner inspection panels on the secondary and to view the primary (the lowest inspection panel also gives a view of the primary). Also view from beneath the primary. Clean as re­quired. If in doubt, drain the system and remove for inspection.
2.Condensate Syphon
With a suitable bowl to catch the water, unscrew the drain-cap(s) on the underside of the Syphon trap and drain the water. Remove any solids and replace cap(s). (
Fig 12
)
CHANGING COMPONENTS
THERE ARE NO REPAIRABLE ITEMS, IF NOT WORKING AN ITEM MUST BE REPLACED.
The boiler is in two major sections, the Case, and the Electrical Tray, The Major Components Diagram shows where the items are to be found. (pages 23-24)
Behind the Electrical Tray
1. Control Boards.
2. Gas Valves.
3. Pumps.
4. Pressure Guage.
5. Safety Valve.
Behind the Cases
6. Fan.
7. Air Pressure Switch.
8. Flue Thermostat.
9. Control Sensor.
10. Overheat Cut-off Device.
11. HT Lead.
12. Pilot Assembly.
13. Burner.
14. Main Injector.
15. Combustion Chamber Insulation.
16. Primary Heat Exchanger.
17. Secondary Heat Exchanger.
Servicing behind the Electrical Tray
To Remove the Electrical tray
Disconnect the electrical supply from the boiler
and system.
Slide the Electrical Tray forward a short way,
then lower. Remove the cover over the compo­nents.
DO NOT STRAIN THE CABLES, USE THE SUP- PORT PROVIDED.
1. Control board
Remove the Control Knob.
Lower the Electrical Tray.
Remove the screw that retains the inner cover.
Pull off the HT Lead, Multipole plug, and the
Gas Valve lead, at the Valve.
Slide back the Electrical Chassis and remove.
Undo the Earthing screw and then pull off the 4
and 10 way Molex connectors.
Remove the bracket for the potentiometer.
Slide the Control Board out of the chassis.
Transfer the pcb support to the new board.
Replace the Control board.
Re-assembly is the reverse.
2. Gas Valve
Lower the Electrical Tray.
Turn the Gas Cock off.
Pull off the electrical connector from the Gas
Valve.
Release the pilot feed tube.
Undo the four shoulder bolts at each end of the
valve.
TAKE CARE TO SUPPORT THE VALVE AS IT IS RELEASED.
Replacement is the reverse.
When secure, attach a manometer to the burner
pressure tapping on the right hand side of the valve.
Page 23
MBD200
21
14/02/04
3. Pump
Lower the Electrical Tray.
Close off the all the Flow and Return Valves.
Drain the boiler through the Drain Tap.
Disconnect the cable at the Pump.
Undo the Set Screws holding the pump head to its
base and remove the head.
Re-assembly is the reverse.
4. Pressure Gauge
Lower the Electrical Tray.
Close off the all the Flow and Return Valves.
Release the pressure in the boiler.
Loosen the Plasic Nut that hold the Gauge retainer.
Unscrew the ssensor end from the Safety Valve, it
may need a temporary plug to avoid leaks.
Re-assembly is the reverse.
5. Safety Valve
Lower the Electrical Tray.
Close off the all the Flow and Return Valves.
Drain the boiler through the Drain Tap.
Remove the Pressure Gauge from the Safety Valve.
Undo the water connections to the Safety Valve and
remove.
Re-assembly is the reverse.
Removing the Case
Lower the Electrical Tray.
Undo the two M5 screws at the base of the Case.
Lift the Case straight up about half an inch (12mm).
Gently pull the Case straight forward off the hidden
studs at the top of the boiler. (The cover hangs on two studs in keyhole slots)
Examine the sealing strip for damage and replace if necessary.
Place the Case somewhere safe from damage
IMPORTANT: FAILURE TO CORRECTLY LOCATE THE APPLIANCE CASE COULD RESULT IN LEAKAGE OF COMBUSTION PRODUCTS INTO THE ROOM.
6. Fan Assembly
Lower the Electrical Tray.
Remove the Case.
Undo the wing nut holding the Fan Protection
Hoop.
Pull the electrical connectors off the Fan.
Gently pull the pressure tubing off the tappings on
the Flue Hood.
Undo the two screws holding the Flue Hood and slide forward and away.
Re-assembly is the reverse.
7. Air Pressure Switch
Lower the Electrical Tray.
Remove the Case.
Pull the electrical connectors off the Air Pressure
Switch.
Gently pull the pressure tubing off the both tap­pings on the switch.
Undo the M4 nut and wing nut holding the Air Pressure Switch to its bracket on to the Back Panel
Lift off its studs and rotate out of its bracket.
Re-assembly is the reverse.
8. Flue Thermostat
Lower the Electrical Tray.
Remove the Case.
Pull the electrical connectors off the Flue
Thermostat.
Re-assembly is the reverse.
9. Control Sensor
Lower the Electrical Tray.
Remove the Case.
Unclip the sensor.
Pull the electrical connectors off the Control
sensor.
Re-assembly is the reverse.
10. Overheat Cut-off Device
Lower the Electrical Tray.
Remove the Case.
Pull the electrical connectors off the Over-
heat Cut-off device.
Unscrew from its mounting.
Re-assembly is the reverse.
Lower the Electrical Tray.
11. Electrode and HT Lead
Lower the Electrical Tray.
Remove the Case
Pull off the HT lead from the Control board.
Undo the left and right screws holding the
Front Burner Baffle.
The Pilot Adjuster is factory set.
Turn on gas and electrical supply.
The gas valve slowly opens to its setting ensure it
has fully opened before adjusting.
Set burner gas pressure with the governor. (
see
Technical Data on page 1 for figure
)
Page 24
MBD200
22
14/02/04
15. Combustion Chamber Insulation
Lower the Electrical Tray.
Remove the Case.
Remove the Front Baffle, then undo the four M5
screws holding the lower baffle onto the Back Panel
Remove the Burner, as in 10.
Undo the four screws holding the Chamber to the
Back Panel and lower downwards and away.
Replace the Insulation Panels in the Chamber.
Re-assembly is the reverse.
Remove the front baffle.
Release the tube nut holding the electrode to the
Pilot Burner.
Carefully withdraw the Electrode and HT Lead.
Re-assembly is the reverse.
12. Pilot Assembly
Lower the Electrical Tray.
Remove the Case.
Undo the left and right screws holding the Front
Burner Baffle and remove. If access is restricted also remove the lower baffle.
Release the tube nut holding the electrode to the Pilot Burner.
Undo the Pilot tube from the Pilot Assembly and gently lever downwards away from the Pilot. It has to be removed and replaced with the injector clipped into position.
Undo the two screws retaining the Pilot Assembly.
Re-assembly is the reverse
NB The pilot is
not
adjustable.
13. Burner
Lower the Electrical Tray.
Remove the Case.
Remove the Front Baffle.
Remove the Combustion Chamber front by releas-
ing the four screws.
Undo the Pilot tube from the Pilot Assembly and gently lever downwards away from the Pilot. It has to be removed and replaced with the injector clipped into position.
Pull off the HT lead.
Pull the Burner forward off the two studs at the rear.
Remove the Pilot Assembly.
Re-assembly is the reverse.
14. Main Injector
Lower the Electrical Tray.
Remove the Case.
Remove the Burner.
Undo the Main Injector from the manifold.
Re-assembly is the reverse.
16. Primary Heat Exchanger
Lower the Electrical Tray.
Remove the Case.
Remove the front baffle.
Remove or cover the Burner.
Remove the Combustion Chamber.
Unclip the Control sensor.
Pull off the wires to the Overheat Cut Out
device.
Drain the Boiler of water.
Undo the flow and return connections to the
Heat Exchanger and lower away.
Re-assembly is the reverse.
17. Secondary Heat Exchanger
Lower the Electrical Tray.
Remove the Case.
Remove the Flue Thermostat.
Remove the Fan Assembly.
Drain the Boiler of water.
Undo the flow and return connections to the
secondary Heat Exchanger.
Release the Condensate connection clamping plate.
Undo the four screws holding the Secondary Heat Exchanger to the Back Panel and lift away.
Re-assembly is the reverse.
Page 25
MBD200
23
27/10/05
Spares
Control Boards
Fig.9
1st Line Spares:
Item Part Number GC Number
Primary Heat Exchanger (24 kW) SPMBC049 Secondary Heat Exchanger (24 kW) SPMBC048 Burner (24 kW) NG SPMBC050 Burner (24 kW) Propane M5148 Ceramic Board Set (24 kW) SPMBC032 106 404 Fan Assembly (24 kW) SPMBD002 106 435 Control Board M3752 Gas Valve, Sigma 840 SPMBC022 Air Pressure Switch (Concentric Flues) SPMBC015 379 091 Main Injector (4.1mm) (24 kW, NG) M0919 106 386 Main Injector (2.6 mm) (24 kW, Propane) M5110 Overheat Thermostat SPMBC019 379 314 Pilot Injector SPMBC007 386 673 Pilot Injector (Propane) M5149 Electrode SPMBC005 386 744 Pilot Assembly SPMBC025 381 865 Flue Thermostat 7717 379 308 HT Lead Assembly M3895 Clip-on Sensor (22mm) SPMBC011 Condensate Trap SPMBC042 Transformer M5584 Relay M5585 Pump SPMBC031
Electrical Components
Transformer
Relays (2)
Page 26
MBD200
24
14/02/04
Major Components
Condensate Trap
Air Pressure Switch
Gas Valve
Gas Cock
Rubber O Ring
( 3 Places )
Flue Thermostat
Fan Assembly
Secondary Heat
Exchanger
Fibre Washer
( 2 Places )
Flow Pipe
Control Sensor
O/H Stat
Primary Heat
Exchanger
Gas Manifold
HT Lead
Pilot Assembly
Main Injector
Electrode
Pilot Injector
Ceramic Board
Set
Burner
Condensate Outlet
Inspection Cover
Flue Gas Sampling Point
Flue Hood Gasket
Fig.10
Page 27
MBD200
25
14/02/04
Example Condensate Disposal Methods
Fig.11
75mm Running Trap
Air Break
Strap-On Boss
1:20 Fall ( 2.5 Degrees )
Washing Machine
Trap
Air Gap
Air Gap
110mm Soil Pipe or Drain
Soakaway
Insulate against freezing
150mm Land Drain Filled with Gravel 750mm deep
Condensate Drain from Boiler
Air Pressure Switch
pipe connection
Vent
Syphon
Connect To Waste
Drain Cap
Bypass
Condensate Drain Trap
Note:
Internal - minimum 19mm pipe External - minimum 32mm pipe
Optional Condensate Drain for Twin Pipe Flue Applications
Fig.12
Page 28
Technical Data: MBD 200
Flue, Gas Type & Destination SEDBUK Rating Heat Input, NET Heat Input, GROSS Heat Output 80-60ºC Heat Output 50-30ºC Setting Pressure, NG (
Propane
)
Gas Consumption for CV
39.0 Mj/m³ after 10 minutes Main Burner (Aeromatic) Gas Control Burner Injector, NG (
Propane
)
Pilot Injector, NG (
Propane
) Gas Connection Installation Lift Weight Total Dry Weight Water Content MAXIMUM Water Pressure MINIMUM Static Water Head Boiler Thermostat range Recommended Water Flow MINIMUM Water Flow Flow & Return Connections Electrical Supply Internal Fuse Rating External Fuse Rating Dimensions
mm
Service Clearances
mm
Terminal Dimensions
mm
Flue Dimensions
mm
Flue Length, min-max,
mm
MBD200
21
14/02/04
Pressure Loss Each boiler
mbar
litres/min
400
300
200
100
0
0 5 10 15 20 25
C
12 C32 C52
, CAT II 2H3P, U.K. & I.E.
B
2 x (20.0-23.0 kW (68,250-78,400 Btu/h))
2 x (22.2-25.5 kW (75,750-87,000 Btu/h))
2 x (19.1-22.0 kW (65,200-74,800Btu/h))
2 x (20.6-23.5 kW (70,000-80,000Btu/h))
10.4 - 14.0 mb (28.4 - 35.8 mb)
2 x (2.08 - 2.4 m³/h)
2 x ((75.3 - 85.7 ft³/h))
Aeromatic AC13/ 122557
SIT. 840.026
Dia. 4.1(2.6 Propane)
SIT0.997.142/33 (0.977.150/23 Propane)
22 mm Copper
80 kg.
88 kg.
5 litres
3 bar
1 m
3000 - 82ºC
14 - 32 litres/m
7.5 litres/m
35mm Copper
230V~50Hz 40W
2 x (1 Amp (20mm))
5 Amp
1760 High, 515 Wide, 495 Deep
450 Front, 30 Above, 25 Below
30 Left & Right
2 X 160 High 160 Wide & 55 Deep,
110
100 - 2000, each
Page 29
M5278 14/02/04
Station Lane
Industrial Estate
Witney
Oxon.
Tel. 01993 778855
Fax. 01993 703407
Loading...