Certikin MBC100N, MBC100NW Installation, Service & User Instructions

Page 1
GC No. 47 555 02 and 47 555 17 WRc No. 95 110 46
0087
Certikin
100 & 100W Condensing
Pool Heaters
Note to the Installer: Natural gas Only
Installation,
Service & User
Instructions
Model: MBC100N MBC100NW Serial No:
Page 2
1
1. USER INSTRUCTIONS
1.1 Important Safety Notes
1.2 Connections
1.3 Quick Start
1.4 Summary of Controls
1.5 Re-Pressurising
1.6 Running the Pool Pump
1.7 Switching the Heater Off – temporarily
1.8 Switching off for the Winter
1.9 Maintenance
1.10 T roub le Shooting – Failure to Start
1.11 Service
1.12 Water Quality
2. INSTALLATION
2.1 Introduction
2.2 Standards & Regulations
2.3 If Combined with a Heating System
2.3 Standards & Regulations
2.4 Heater Controls
2.5 Gas Supply
3. FLUEING
3.1 Air Supply
3.2 Water Supply
3.3 Condensate Drain
3.4 Sealed Systems
3.5 Electricity Supply
4. INSTALLATION WIRING
4.1 Wiring
4.2 Installation of Heater
4.3 Fixing the Heater
4.4 Terminal
4.5 Twin Pipe Assembly
4.6 Plumbing
4.7 Gas Connection
4.8 Condensate Connection
5. SPACE HEATING
5.1 System Design
5.2 Electrical Connections
6. COMMISSIONING
6.1 General Information
6.2 Procedure
6.3 Setting up the Controls
6.4 Pump Pressure Switch
6.5 Responsibility
7. FAULT FINDING
7.1 Heater Control
7.11 Control F ault Diagnostics
7.2 Ignition Faults
8. SERVICING
8.1 Heater Servicing
8.2 Changing Components
8.2.1 Control Boards
8.2.2 Gas Valv e
8.2.3 Sequence Controller
8.2.4 CVI V alve and Full Pressure Set Up
8.2.5 Pressure Gauge
8.2.6 Pump
8.2.7 Diverter V alve
8.2.8 Safety V alve
8.2.9 Water to Water Heat Exchanger
8.2.10 Flow Regulator and Strainer
8.2.11 DHW T emperature Sensor
8.2.12 Removing the Case
8.2.13 Fan Assembly
8.2.14 Air Pressure Switch
8.2.15 Flue Thermostat
8.2.16 Pump Overrun Thermostat
8.2.17 Control Sensor
8.2.18 Overheat Cut-Off Device
8.2.19 Electrode and HT Lead
8.2.20 Pilot Assembly
8.2.21 Burner
8.2.22 Main Injector
8.2.23 Combustion Chamber Insulation
8.2.24 Primary Heat Exchanger
8.2.25 Secondary Heat Exchanger
9. PARTS
9.1 Spares
9.2 Electrical Components
1:4 Control Panel 1:5 The Filling Loop 2:3 Typical Circuits 3:4 Alternative Methods of
Filling a Sealed System
4:1 Installation Wiring
Diagram for Heater
Controller 4:3 Fixing Positions 4:5 T win Flue P ositions 4:8 Installation Dimensions
Service Access 5:2a Model 100 Schematic
Wiring 5:2b Model 100W Schematic
Wiring 5:1 Hydraulic Schematic 6:2 a Model 100 Gas V alve 6:2 b 100W Gas V alve 6:3 Control Display in Setup
Mode 6:4:a Adjustment Knob 6:4:b Heater Installation Limits 7:1 Control Display 7:2:a Indicator Lights, Model
100 Only 7:2:b Fault Finding Operation
Sequence, 100W 7:2:c Fault Finding Hot Water
Operation, 100W 7:2:d Fault Finding P ool or
Space Heating, 100W 8:2:2 Gas V alve Model 8:2:4 CVI V alve Modureg
Operator 9:2 Electrical Components 10:1 Major Components 10:2 Example Condensate
Disposal Methods 10:3 Condensate Drain Tap
CONTENTS
FIGURES
100 Gas Condensing Pool Heater
21/10/03
Page 3
1: USER INSTRUCTIONS 1:1 Important Safety Notes
T o obtain the best possib le performance and trouble free operation from your Heater , it is important that you read these instructions carefully . Your Pool Heater has built-in safety features, which are detailed in the relevant section of this manual.
If it is known or suspected that a fault exists on the Heater, it MUST NO T be used until the f ault has been corrected by a competent engineer (see Section 1:10, Trouble Shooting - Failure to Start)
It is essential that these instructions are strictly followed f or saf e and economic operation. F ailure to observe these instructions may invalidate your right to free breakdown cover during the guarantee period.
We recommend that you keep these instructions in a place near your Heater for easy reference.
1:2 Connections
Your Heater should be connected to an electrical supply complying with the Electrical Wiring Regula­tions (BS7671): as well as a gas supply complying with BS6891; and an appropriate flue system.
AL WAYS SWITCH OFF THE ELECTRICAL SUPPLY before removing any of the covers for cleaning.
If any part of the Heater or its flue is modified then the guarantee will be invalidated.
1:3 Quick Start
Check the Electricity and Gas supplies to the Heater are on. If the Pool Pump is not controlled by the Heater, turn it on. Turn on the Heater by turning the Pool Temperature Control Knob clockwise to show the required Pool temper ature, the Heater will fire. If the Heater fails to light see Section 1:10, T roub le Shooting - Failure to Start)
1:4 Summary of Controls (left to right)
Heater Pressure Gauge Normal - The needle should be in the area indicated as * * NORMAL * * , if low , re-pressurise, see Section 1:5 Flashing - The P ool Heating Demand is Met , the
pool is up to temperature.
Temperature is displayed after 3 seconds.
- Spa + - Setting for Spa Temperatures. Required temperature is displayed when setting, actual Spa T emper ature displayed after 3 seconds.
(NOTE: The Heater is delivered set to display in Fahren­heit. For a Centigrade display,
see 6:3
Commissioning Section of Installation Instructions)
Pool Temperature Mechanical Stop Stop – This can be used to obtain a repeatab le
setting and to limit maximum pool temperature. To set, loosen the screw , adjust as required and then re-tighten.
Pool T emperature Display Display - Normally shows the actual P ool Tempera-
ture, but also displa ys the Setting Temperature and a Setting Dot lit whilst being adjusted. The display is also used for commissioning and diagnostic pur­poses.
Heating Demand LED - GREEN
(Only in use when heating system connected)
Off - There is no Heating Demand , heating is
switched off. On - There is a Heating Demand , heating is on b ut not yet up to temperature. Flashing - The Heating Demand is met , heating is up to temperature.
Heating Temperature Control Knob (Only used when heating system connected) Off - There is no Heating Demand, heating is
switched off. Normal - Normal setting for heating, it can be adjusted lower if required.
(NOTE: Supplied set for Pool Priority. It will satisfy the Pool Temperature before supplying full Heating. To
change the priority,
see 6:3
Commissioning Section of
the Installation Instructions)
Filter LED - YELLO W On - Pool Filter Bloc k ed - Insufficient pressure,
possibly due to a blocked pool filter. The heater will not run. Flashing - Clean Pool Filter - The filter ma y require back washing. The heater will run. Can be reset by turning the Pool Temperature knob off and back on
again.
Pool Temperature Control Knob
16°C to 41°C (60°F to 106°F) Off - There is no P ool Heating Demand , pool heating is off. Pump - Runs Pool Pump only, if connected via heater. ‘P’ is indicated on P ool T emperature Displa y .
- Pool + - Setting f or pool temperatures. Requested temperature is displayed when setting, actual Pool
2
100 Gas Condensing Pool Heater01/06/02
Page 4
Heater Overheat LED - ORANGE On - Heater Ov erheat - This indicates that the
Heater has overheated and shut down. See Over­heat Reset instructions below.
Overheat Reset 100 Only
In the unlikely event of an Overheat it will neces­sary to obtain the assistance of a competent person to reset the thermostat. Turn the Mains supply off. Remov e the single fixing screw holding the Electrical Chassis and pull it out, hanging it on the back support. Remov e the Con­trols Cover and locate the Reset Switch on the side of the Control Chassis. Turn it off then back on again. Replace all the panels in reverse order . If the Heater repeated overheats a Service Engineer should be called to inspect the Heater.
Overheat Reset - 100W Model Only
In the unlikely event of an Overheat it will neces­sary to obtain the assistance of a competent person to reset the thermostat. The procedure is detailed in Section 8:2:18 If the Heater repeated overheats a Service Engineer should be called to inspect the Heater.
Automatic Frost Protection
The Heater will automatically run a Frost Protection routine if the temperature falls below 3°C (37°F). The Pool Temperature Display will show 0°C. This will include the use of the Pool Pump if it is connected to the Heater.
1:5 Re-Pressurising
Connect a Mains W ater supply then connect the free end of the braided flexible hose (the Filling Loop) (see Fig.1.5) to the incoming mains connec- tor.
Open the Valve to the supply , then, slo wly open the V alve on the Base P anel until the Pressure Gauge shows 1 Bar . Close both valves then disconnect the Filling Loop.
ON
bar
0 4
2
1 3
u
s
e
r
i
n
s
t
r
u
c
t
i
o
n
s
i
n
s
i
d
e
u
s
e
r
i
n
s
t
r
u
c
t
i
o
n
s
i
n
s
i
d
e
100
s
e
e
i
n
s
t
r
u
c
t
i
o
n
s
1:6 Running the Pool Pump
If this option has been installed the Heater can run the Pool Pump on its o wn. Turn the Pool Tempera­ture Control Knob to ‘Pump’, just ne xt to Off .
1:7 Switching the Heater Off -
temporarily
The Heater may be stopped by turning the Pool T emperature Control Knob and/or the Heating T emperature Control Knob to OFF on Control P anel.
1:8 Switching off for the Winter
T urn both T emper ature Control Knobs to Off. If the built in Frost Protection is required do not isolate the Heater from its electrical supply . If the Heater is to be shut off for the Winter, it is advisable to have it thoroughly serviced when first shut down. Thorough cleaning will minimise corro­sion during the idle period.
1:9 Maintenance
For normal cleaning of the outside casing, simply wipe with a dry cloth. To remove stubborn marks and stains, wipe with a damp cloth and finish off with a dry cloth. DO NO T use abrasive cleaning materials. A spr a y of WD40 or similar will also help to protect it. The Heater must be serviced every year by a qualified service engineer.
1:10 Trouble Shooting - Failure to Start
If the Heater fails to start, adopt the following procedure:-
1. Check that the P ool pump is operating and that the Filter lamp is not illuminated.
2. Check that the Heater Control Thermostat is set high enough to be “ON” and that the Pool De­mand lamp is on.
Fig 1:4
3
100 Gas Condensing Pool Heater 20/10/03
Page 5
Fig 1:5
3. Check whether the Heater Overheat light on the control fascia is glowing, if so it indicates an overheat situation. (See Section 1:4) If the Heater repeatedly overheats a Service Engineer should be called to inspect the Heater.
1:11 Service
T o ensure efficient and reliable oper ation of the Heater it is essential that the Heater is serviced every year. The Manufacturer recommends this is prior to start­ing the Heater each season.
1:12 Water Quality
Chemical imbalance can cause severe damage to your Heater and associated equipment. Maintain the pool water pH between 7.4 and 7.6 and ensure that the free chlorine levels are within the range recommended by the chemicals manufacturer for your size of pool. Check the Filter regularly and keep the pool free of debris such as leaves and grass cuttings.
4
100 Gas Condensing Pool Heater20/10/03
Filling Loop
First Valv e
Second V alve
100
Filling Loop
Second V alve
100W
Page 6
2 INSTALLATION 2:1 Introduction
This Manual covers Operation, Installation, Com­missioning and Maintenance of the 100 and 100plus Condensing Pool Heater . The Pool Heater is :-
• Designed for heating pools and Spas by utilising
an internal water to water heat exchanger .
• Incorporates its own sealed system
components; pressure vessel, filling loop, safety valve, and pressure gauge.
• Can also be used for space heating.
• The 100 Plus also provides Instantaneous Hot
W ater.
• Supplied with a manual reset limit thermostat.
• Suitable for new installations and for replacing
existing Heaters.
• Includes an internal automatic bypass to
accomodate all likely Space Heating designs.
These Instructions are for a Gas Fired, Condensing Pool Heater which are room sealed and f an assisted on the flue side. The flue system available is Twin Pipe, horizontal total combined length of 22 metres or vertical, up to a total length of 30 metres. The ignition system is fully automatic. The 100 plus incorporates electronic gas modulation.
The Heater casing is of polyester powder coated enamelled zinc coated steel.
Includes all the components required for a sealed system including a pump and is designed for the connection of an optional Heating or Hot W ater system.
It includes a pump overrun device and an automatic bypass valve.
There is no requirement for a scale reducer to be fit­ted to the cold water mains supply to the 100 Plus.
The Heater contains integral frost protection, the Heater will fire if the temperature within it ap­proaches 4 to 5 degrees Centigrade. It will do this even when turned to Off, and can only be inhibited by removing the P ermanent Live supply to the Heater.
Adequate arrangements for completely draining the system, by provision of drain cocks MUST be provided.
2:2 Standards & Regulations Gas Safety (Installation and Use) Regulations, (as amended).
It is the law that all gas appliances are installed by a competent person (e.g. a CORGI registered operative) in accordance with the above Regula­tions. F ailure to install appliances correctly could lead to prosecution.
It is in your own interest, and that of safety, to ensure that the law is complied with. The installation of the Heater MUST also be in accordance with the current I.E.E.. Wiring Regulations, the Local Build­ing Regulations, Building Standards (Scotland), the Bye Laws of the Local Water Undertaking, any relevant requirements of the Local A uthority , and Health and Safety document No 635, “Electricity at Work Regulations”.
Detailed recommendations are contained in the following British Standard Codes of Practice.
Codes of Practice.
BS.6798 Installation of gas fired hot water Heaters of rated input not exceeding 70kW . BS.5449:1 Forced circulation hot water systems (small bore and microbore domestic central heating systems). BS.5546 Installation of gas hot water supplies for domestic purpose (2nd Family Gases). BS.5440: P art1. Flues (f or gas appliances of rated input not exceeding 60kW). BS 6891 Specification for installation of low pres­sure gas pipework. BS 7074:1 Application, selection and installation of expansion vessels and ancillary equipment for sealed water systems. Building Regulations Part L1.
IMPORTANT.
It is important that no external control devices are directly connected to this appliance ­unless covered by these ‘Installation and Servicing Instructions’ or otherwise recommended by the manufacturer . If in doubt, please enquire.
Any direct connection of a control device not recommended by the manufacturer could infringe the Gas Safety (Installation & Use) Regulations, the above regulations and the normal appliance war­ranty.
Manufacturer’ s notes must NO T be tak en, in any way, as overriding statutory obligations.
Location of Heater
The Heater MUST be installed vertical and securely fixed .
The Heater is not suitable for an external
installation
5
100 Gas Condensing Pool Heater 05/02/03
Page 7
Important Notice
If the Heater is to be fitted in a timber framed building it should be fitted in accordance with the British Gas publication ‘Guide f or Gas Installations in Timber F rame Housing’, ref erence DM2. If in doubt, advice must be sought from the Local Gas Region of British Gas.
The Heater may be installed in any room or internal space. Particular attention is drawn to the require­ments of the current I.E.E Wiring regulations and, in Scotland, the electrical provisions of the Building Regulations applicable to Scotland with respect to the installation of the Heater in a room or internal space containing a bath or shower .
Where a room sealed appliance is installed in a room containing a bath or shower then the appliance and any electrical switch or appliance control, utilising mains electricity should be so situated that it cannot be touched by a person using the bath or shower .
Where installation will be in an unusual location then special procedures may be necessary and BS.6798 gives detailed guidance on this aspect.
A compartment used to enclose the Heater MUST be designed and constructed specially for this purpose. An existing cupboard, or compartment, may be used provided it is modified for the purpose. Details of essential features of cupboard compart­ment design, including airing cupboard installations are given in BS.6798. In siting the Heater, the f ollowing limitations MUST be observed:
1.
The position selected for installation MUST allow adequate space for servicing in front of the Heater and for air circulation around the Heater .
2.
This position MUST also permit the provision of
a satisfactory balanced flue termination.
3.
This position MUST also permit the provision of
a satisfactory connection to the condensate drain.
2:3 If Combined With A Heating System
The Controls provide a water temperature control for use with a heating system, the Heating Demand Knob. It requires an switched live from the Heating controls to be connected to Heating Demand, as shown in the Wiring Diagram and a pipe circuit to be connected to the two rear tappings of the Heater in place of the Air V ent and Drain. It is essential that the size of the expansion vessel in the Heater is sufficient for the proposed system Depending upon the Priority set
(See commissioning Section 6:1)
the Pool or The
Heating will be brought up to temperature first. Typical circuits are as
Fig 2:3.
2:4 Heater Controls
This Heater uses a control specifically designed for it and it has the following features:
A highly accurate Pool Thermostat , 16°C to 41°C (60°F to 106°F) A Heater Thermostat. Fixed f or P ool, 84°C, variab le for Heating 60 - 82°C. A Frost Thermostat which runs the Internal and Pool Pump at 3°C or below but then fires the Heater alone if the temperature has not risen sufficiently. A Return Thermostat operating an internal bypass for condensation reduction.
Fig 2:3
Heater
Pump
Pump
Zone Valve
Non return valve
Pump
Non return valve
Second water 2 water
heat exchanger
with Aquastat or similar
Pool Plus Heating and Hot Water
Pool Plus Heating
Pool Plus Spa
3 Way Valve
Expansion vessel
Expansion vessel
Heater Expansion
Vessel
4 litres
Heater
Heater Expansion
Vessel
4 litres
Heater
Heater Expansion
Vessel
4 litres
NB: Extra Expansion Vessel only required for very large systems. See Section 3:4
6
100 Gas Condensing Pool Heater01/06/02
Page 8
Terminal Position Minimum
Below window or vent 300 mm Below gutter or pipes 75 mm Below eaves 200 mm Below balcony or roof 200 mm From a window 200 mm From vertical pipe 75 mm From corners 300 mm Above ground, roof or balcony 300 mm From f acing surf ace 600 mm From f acing terminal 1200 mm From opening under a car port 1200 mm V ertically from a terminal 1500 mm Horizontally from a terminal 300 mm
An Over T emperature Thermostat (Overheat). Internal Pump control with run on. Pool Pump control with run on and out-of-season
exercise. (Requires external contactor)
Pool Temperature and Setting display . Engineer
selectable °C or °F.
User Indicators for P ool, Heating, Overheat, and
Service. Engineer indicators of all switched outputs for simple diagnosis. Priority selection of Pool or Heating, engineer
selectable. Memory of: Filter occurrences. Sensor failure detection and indication. Control self checking with fault indication.
For more detail see the
Commissioning (6:1) an
Fault Finding (7:1) sections
.
2:5 Gas Supply
The Local Gas Region should be consulted, at the installation planning stage, in order to establish the availability of an adequate supply of gas.
An existing service pipe must NOT be used without prior consultation with the Local Gas Region, or by a local Gas region contractor. An e xisting meter should be checked preferably by the Gas region, to ensure that the meter is adequate to deal with the rate of gas supply required. Installation pipes should be fitted in accordance with BS.6891 Do NOT use pipes of a smaller size than the Heater inlet gas connection.
3 FLUEING
Detailed recommendations for flueing are given in BS.5440: 1. The f ollowing notes are intended for general guidance.
1.
Be aware of the plume from the flue and the wetting effect it has to adjacent property.
2.
The flue can be taken upwards, left, right or to the rear of the appliance.
3.
The Heater is supplied with a Twin Pipe flue suitable for terminating on an outside wall 1 metre away. More complex and length y flues are possible, please consult the Flue Application Guide for designs and the components.
4.
The Heater MUST be installed so that the terminal is exposed to external air.
5.
It is important that the terminal allows the free passage of air across it at all times.
T ab le 1.
IMPORTANT.
It is absolutely ESSENTIAL to ensure, in practice, that products of combustion discharging from the terminal cannot re-enter the building, or any other adjacent building, through ventilators, windows, doors, other sources of natural air infiltration or forced ventilation/air conditioning.
If this should occur, the appliance MUST be turned OFF IMMEDIA TELY and the Local Gas Region consulted.
6.
The acceptable spacing from the terminal to obstructions and ventilation openings are specified in Table 1.
7.
Because the flue gases and terminal are at very low temperature it is not necessary to fit a Terminal guard to protect against burns. If a guard is required for any other reason the following is recommended.
For the T win Flue T erminal:
Model B (black plastic coated).
For the Single Flue T erminal:
Model H (black plastic coated).
All are available from:
Tower Flue Components Ltd.
Tower House.
Vale Rise.
Tonbridge
KENT
TN9 1TB
01732 351555
7
100 Gas Condensing Pool Heater 01/06/02
Page 9
3:4 Sealed Systems
The Pool Heater is supplied with an Expansion V essel (see Technical Data for details), a Pressure Gauge, a Safety Valve and Filling Loop following the guidelines given in the Code of Practice BS 7074 :1.
Please check that the supplied Expansion Vessel is adequate for the proposed system. The f ollowing procedure is suggested.
1.
Choose a vessel pressure by taking the static head of the system, adding 0.3 bar, and taking the nearest larger figure.
2.
Select the Vessel V olume from the tab le below by finding the System Volume and V essel Pressure.
3.
Choose that size or larger from the manufactur­ers’ range.
Vessel System Volume
Litres
Pressure 50 60 70 100 150
Bar
Vessel V olume
0.5
448812
1.0
8881218
1.5
8 12121824
T ab le 2.
A design as detailed below should be used for the filling connection, it utilises a BS 1010 stop valve, a double non-return valve and filling loop fitted at low level and should be installed with the approval of the local W ater Undertaking.
3:1 Air Supply
It is NOT necessary to have a purpose provided air vent in the room or internal space in which the Heater is installed.
Where the Heater is installed in a cupboard or compartment no air vents are required. How ever the User may wish to ensure that is ventilated to provide air circulation.
3:2 Water Supply
The central heating system should be in accord­ance with the relevant recommendations given in BS.6798, BS 7593:1992 and, in addition, for smallbore and microbore systems - BS.5449:1.
The domestic hot water system, if applicable, should be in accordance with the relevant recom­mendations of BS.5546.
Copper tubing to BS 2871:1 is recommended for water carrying pipework.
The Mains W ater supply should be clean and able to produce the required flow rate, see the T echnical Data. New pipework must be flushed through before con­necting.
The 100W incorporates a strainer and flow regulator set to 8.5 l/m on the Cold W ater Mains Inlet, this can be removed in countries with warm climates. The In­let pressure should not exceed 10 bar , a reducer should be fitted if it does.
Any hot water storage cylinder MUST be of the indirect type and should preferably be manufactured of copper.
The hot water cylinder, & ancillary pipework, not forming part of the useful heating surface should be lagged, to prevent heat loss and any possible freezing, particularly where pipes run through roof spaces and ventilated underfloor spaces.
Draining taps MUST be located in accessible positions, which permit the draining of the whole system, including Heater and hot water storage vessel. Draining taps should be at least ½ in. nominal size and be in accordance with BS.2879.
3:3 Condensate Drain
Refer to Fig. 1:5, 5:1, and 10:2
A condensate drain is provided on the Heater , this drain must be connected to the household drainage point, or soakaway on site. All pipework and fittings in the condensate drainage system MUST be made of plastic. Refer to British Gas publication “Guid­ance notes for installation of domestic condensing boilers”
The drain outlet on the Heater is :
Polypipe, 21.5mm pushfit overflow pipe.
ALTERNATIVE METHODS OF FILLING A SEALED SYSTEM
Method A
Method B
Hose Unions
Air Inlet
Valve
Temporary Hose
Mains
Water
Supply
Mains
Water
Supply
Test Cock
Stop Valve
Drain & Fill
Double Check Valve Assembly
Drain &
Fill
Cistern & Overflow
Pressure Pump & Reducing Valve If Required
Stop Valve
3:5 Electricity Supply
Wiring external to the appliance MUST be in ac­cordance with the current I.E.E. Wiring Regulations and any Local Regulations that apply .
The Heater is supplied for 230V ~ 50Hz. Single phase. Fuse rating is 3A.
Fig. 3:4
8
100 Gas Condensing Pool Heater
20/10/03
Page 10
The method of connection to the mains electricity supply MUST facilitate complete electrical isolation of the Heater, pref erably by the use of a fused doub le pole switch having a 3mm (1/8in.) contact separation in both poles and servicing only the Heater and sys­tem controls.
The point of connection to the mains should be read­ily accessible and adjacent to the Heater , except that, for shower room installations, the point of connection to the mains MUST be situated outside the bathroom.
Note. Where a room sealed appliance is installed in
a room containing a basin or shower , the appliance, any electrical switch or appliance control utilising mains electricity should be so situated that it
cannot be touched by a person using the bath or shower.
4. INSTALLATION WIRING 4:1 Wiring
The designs below are in order of preference, the Quick Fit P ool Control Panel (CCP02) being the easi­est, quickest and most comprehensive solution.
Design 4 is the least preferred as it does not utilise all the features of the Heater Control.
Heater Connections are shown prefaced with ‘HTR’ in the diagrams below .
Fig. 4:1
9
100 Gas Condensing Pool Heater 01/06/02
LNE
Certikin Mk2 Oil Pool Heater
Pool Pump
Up to 16 A
Lights
Up to 6 A
Pool Pump
Rated to suit pump
RELAY
T.S
> HTR, Permanent Live
> HTR, Pool Demand
< HTR, Pool Pump
Pool Pump
Up to 3 A
More than 3 A
Trip
L
N
N
T.S
> HTR, Permanent Live
> HTR, Pool Demand
Pool Pump
Trip
L
N
T.S
> HTR, Permanent Live
Pool Pump
Trip
L
N
> HTR, Pool Demand
DESIGN
#
NOTES
Takes full advantage of all the features of the Certikin
Oil Pool Heater.
Pool Pump control providing overrun and Frost Protection action.
Provides the fastest installation
Optional connections for Lights and Space Heating all provided.
1
2
3
4
Takes full advantage of all the features of the Certikin
Oil Pool Heater. Considerable installation time.
Pool Pump control providing overrun and Frost Protection action.
Optional Space Heating only available with more wiring.
Limited application of Certikin Oil Pool Heater.
Moderate installation time.
No Pool Pump control, Overrun or Frost Protection action.
Non-preferred application of Certikin Oil Pool Heater.
Moderate installation time.
No Pool Pump control, overrun or Frost Protection action.
Optional Lighting only available with more wiring.
Optional Space Heating only available with more wiring.
Optional Lighting only available with more wiring.
Utilising the CCP02 "Quick Fit" Oil Pool Heater Control
Optional Space Heating only available with more wiring.
Optional Lighting only available with more wiring.
T.S = Time switch
T.S = Time switch
T.S = Time switch
HTR = Oil Heater
HTR = Oil Heater
HTR = Oil Heater
CCP02
IMPORTANT: Remove link, Live to Pool Demand, in Oil Heater
IMPORTANT: Remove link, Live to Pool Demand, in Oil Heater
OR, Certikin Condensing 100 Pool Heater
OR, Certikin Condensing 100 Plus, Pool Heater
Page 11
4:2 Installation Of Heater
Suggested procedure:
1.
Position to suit system and terminal limitations.
2.
Mark & Drill Flue hole(s). (see Fig. 4:8).
3.
Remove the Electrical Tray and the Lower Case from Heater module.
4.
Plumb tails to pool, gas heating and hot water .
5.
Test for leaks.
6. Replace the Low er Case and Electrical tray.
Space Required for Installation and Service.
Right or Left 30 mm 1 in. Above 30mm 1 in. Below 25mm 1 in. In Front 450mm 18 in.
T able 3
4:3 Fixing the Heater
1.
Position to suit system and terminal limitations.
2. Secure the frame, vertical, to the wall or floor
with the bracets provided..
3.
Mark the wall or ceiling for the flue exit points and core drill the wall to give a 0 to 3 degree slope down towards the Heater . The recom­mended core drill is 90mm for the Twin Pipe.
4:4 Terminal
The terminal can be fixed vertical or horizontal. The flue pipe must always be connected to the extended outlet of the terminal. The spacing is 120mm and a core drill of 90mm is recommended.
See Fig. 4:8
4:5 Twin Pipe Assembly
All the Twin Pipe components for this appliance are lightweight plastic and utilise a push-fit system. V ery few f asteners are required and their use is detailed on the instructions provided with the components.
Important:
All Twin Pipe Installations must comply with the following.
1.
The Flue pipe must slope back to the Heater by three degrees (1 in 20) on all horizontal runs. The air pipe can be above or below horizontal.
2.
Flue Pipes must be supported every 1000mm, minimum.
3. All connections should be made with the Socket end furthest from the heater.
4. Use the supplied CentraCerin or Silicone Grease to ease the fitting of sections.
5.
The combined Equivalent Length of Air and Flue should not exceed 22m horizontal, or 30m vertical and including any terminal parts.
6.
The straight equivalent lengths of bends in a horizontal design are as follows:
45 degrees, 1.3m. 90 degrees, 4m.
For more complex designs please see the details provided with the components
It is recommended that:
1.
That 45 degree bends are always used with vertical flues and where possible used in prefer­ence to 90 degree bends in horizontal installa­tions.
2.
Straight Flue pieces may be reduced in length by cutting square. It will ease assembly if the cut edge is cleaned, chamfered and greased before insertion.
4:6 Plumbing
Prepare the flow and return pipe work on the base of the Heater. If the requirement f or Space Heating exceeds 50,000 Btu/h (15kW), the Flow and Return pipework from the Heater must be 28mm until the heat load allows smaller bore pipework.
New pipework must be flushed through before connecting.
4:7 Gas Connection
The 15mm gas connection point is provided. A minimum of 20mb. (8in. w.g.) must be availab le at the Heater inlet, with the Heater and other con­nected appliances firing. Check for gas soundness (B.S. 6891: 1988) in pipework to Heater using a manometer. Open the gas coc k. Gas soundness within the Heater should be checked using sense of smell and/or leak detection fluid. Check the burner bar pressure with a manometer connected to the control and adjust if required with the pressure regulator.
10
100 Gas Condensing Pool Heater
01/06/02
Page 12
FIXING POSITIONS
TWIN FLUE POSITIONS
Fig.4:5
Flue Duct
Air Duct
100mm
Condensate Drain Connection
(connects to drain point on Flue Spigot Adapter)
Flue Spigot Adapter
Drain Point
Twin Pipe Heater Mounting Box Assembly
Connects to condensate drain point on Condensate Drain Trap
11
100 Gas Condensing Pool Heater 01/06/02
PLAN VIEW
FRONT VIEW
Suggested fixings 3 into the floor OR 2 into the wall.
Fig.4:3
Page 13
4:8 Condensate Connection
The position of the plastic condensate drain pipe is shown in
Fig 5:1
Where possible an internal termination of the Condensate discharge pipework should be used.
Installation pipework must be in plastic to a suitable drain location with a gradient of 2.5° (45mm/ meter run) minimum. If connected to another drainage trap, an air break is required between the Heater drain and that trap. (
See Fig.10:2
). Internal runs must be in a minimum of 19mm pipe. External runs MUST be made in a minimum of 32mm pipe, starting inside the building, and if possible insulated to defer problems from freezing.
Whichever method is used it should be checked during commissioning to prove there is a leakfree working connection from the Heater to the drain. The simplest way to do this is to carefully pour some water into the Heater flue and check it emerges at the drain.
The British Gas booklet “Guidance for the installa­tion of Domestic Condensing Boilers” should also be referred to .
5 SPACE HEATING 5:1 Typical Radiator System Design
General Principals
No special requirements are need for the selection of radiators, normal sized radiators are acceptable.
The Manufacturer recommends using a programma­ble room thermostat, alternatively a separate room thermostat and timeswitch can be used.
The Heaters include a pump overrun device so it is essential that there is an open circuit for water to flow between the flow and return. An Automatic Bypass is incorporated in the appliance which should be sufficient for most system designs.
The Heater includes integral frost protection. If the temperature approaches freezing it will first try and use the heat in the pool by running the Pool Pump . If this does not raise the temperature it will run the Heater. It will do this even when turned to Off, and can only be inhibited by removing the P ermanent Live supply to the Heater .
Thermostatic radiator valves can be used. The Heater Pump is factory set at Speed 3 and
should not be alterered. The Heater waterside is completely copper so all
good corrosion inhibitors are suitable. Inhibitor is not required for Pool only applications .
The design temperature difference across the Heater for optimum operating efficiency is 20°C. If thermostatic valves or zone valves are used ensure the minimum flow shown in the T echnical Data on
page 1 is possible.
5:2 Electrical Connections WARNING: The appliance MUST be
earthed.
All wiring for the Heater and system controls MUST conform to I.E.E. Wiring Regulations, and work should be tested using a suitable meter, f or Earth Continuity, Polarity, Short Circuit and Resistance to Earth.
The supply must be through a common isolator, a double pole 3A fused isolating switch with a contact separation of 3mm minimum on both poles. The cable used should be no less than 0.75mm
2
to BS.6500 PVC, 3 core , and fixed ensuring the earth connection is longer than the Live and Neutral.
Access to the Heater connections is made by sliding out the bottom tray which is held by mag­nets, removing the single screw retaining the Electrical Tray then releasing the screws retaining the Chassis Cover . The Heater internal wiring is shown in
Fig.5:2a &
Fig. 5:2b
.
Connections are made by push fit connectors Connections are as follows :-
3 Way T erminal 4 Wa y T erminal
Earth Pool Pump Neutral Neutral Permanent Live Heating Demand
Pool Demand
A link is factory fitted between the Permanent Live and the Pool Demand and should be remov ed if a separate switched supply is provided f or P ool Heating.
For systems using an external programmer , the electrical wiring should follow the relevant control manufacturer’ s recommendations, with the s witched live from the controls returning to Pool Demand and/ or Heating Demand in the 4 way push-fit connector .
12
100 Gas Condensing Pool Heater 01/06/02
Page 14
INST ALLA TION DIMENSIONS
FLUE POSITIONS AND SERVICE ACCESS
Fig 4:8
13
100 Gas Condensing Pool Heater08/09/03
HEATER HYDRAULIC SCHEMATICS
Fig. 5:1
Safety Valve Drain
From Pool
Heating Flow
Heating Return
Fill & Drain
Condensate Drain
To Pool
Condensate Trap
Pump
Safety Valve
Diverter Valve
Auto Bypass
Valve
Expansion Vessel
Heat Exchanger
Pool Heat Exchanger
Auto
Air
Vent
Safety Valve Drain
From Pool
Heating Flow
Heating Return
Fill & Drain
Condensate Drain
To Pool
Condensate Trap
Pump
Safety Valve
Diverter Valve
Auto Bypass
Valve
CW Inlet
Three Way Valve
Water to Water
Heat Exchanger
Filling Loop
Pool Heat Exchanger
Heat Exchanger
Expansion Vessel
Auto
Air
Vent
HW Outlet
100W100
Front View
C
L
100
Rear Flue Side View
Twin pipe
Maximum 22m horizontal
90mm
90° bend = 4.0m
45° bend = 1.3m
Suggested core drill
Service Access
Front 450mm Above 30mm
Sides 30mm
Equivelant lengths: Minimum 200mm
Maximum 30m vertical
Side Flue
Flue
Air
390
110
500
1750
1850
1850
120
100
Page 15
SCHEMATIC WIRING
Fig.5:2a
14
100 Gas Condensing Pool Heater 14/03/03
100
SUPPLY
E
N
L
HT
N
Ls
L
Lp
COM
AIR
NOAIR
O/H
O/H
SENSOR
SENSOR
12 Way connector
GV1
GV2
N
4 Core to Gas Valve
Fan
4 way Molex
10 way Molex
GV1 GV2
1 Amp 20mm
IGNITION BOARD
Or
Or
Br
Br
R
W
BkGyBr
R
Bk
Br
B
G/Y
G/Y
G/Y
B
G/Y
V
Gy
Br
R
OrWBk
Gy
V
G/Y
B
Brown
Red
Orange
White
Black
Blue
Grey
Violet
Green & Yellow
B
L
N
Pressure
Switch
O/H
P
o
o
l
P
u
m
p
Heating Demand
P
o
o
l
D
e
m
a
n
d
PUMP
E
N
Lp
CONTROL BOARD
INTERNAL
G/Y
E
N
N
2
5
0
m
A
A
S
L
R
C
POOL DMD
HTG DMD
HTR PUMP
POOL PUMP
BURNER
P
r
e
s
s
u
r
e
S
w
i
t
c
h
B
u
r
n
e
r
S
e
n
s
o
r
P
o
o
l
S
e
n
s
o
r
C
o
m
m
o
n
R
R
B
Or
Y
Yellow
W
B
Br
B
Gy
V
Sensor
Pool
3 PORT VALVE
B
R
O
W
N
RESET
SWITCH
Or
Br
Lockout Neon
14/03/03
Air Pressure Switch
NO
NC
S
e
n
s
o
r
Flue Stat
O/H Stat
M4733
10k
B
Page 16
SCHEMATIC WIRING
15
100 Gas Condensing Pool Heater
21/10/03
Fig.5:2b
100W
DRIVER PCB
X1
X2
X3
X4
X5
X6
X7
X8X10
CH SET MAX
MODUREG
DHW
SENSOR
NC
NC
24V
FLOW SWITCHES
PUMP
CVI VALVE ASSEMBLY
1
8
NC
R
Y
W
R
V
G
y
Y
W
R
P
Br
B
HW SET MAX
R/B
Bk
G
y
/
B
k
NC
G
y
W
R
Or B
B Br
Br
B
Br
FAN
PRESSURE
OH STAT
LOCKOUT
NEON
FLUE STAT
W
W
OVERRUN
PUMP
230 V
CH
Bk
B
B
G/Y
G/Y
B
G/Y
Spark Electrode
230 V
Br
Or
Set Maximum CH Pressure
1
2
3
Fuse 315 mA
Fuse 2 A
P Pink
Set Minimum CH pressure
SWITCH
12 11 9 6
5
3
12
G/Y
8
Br
Cold
5
6
3
10k
10k
SUPPLY
E
N
L
R
Br
R
Or
W
Bk
Gy
V
G/Y
B
Brown
Red
Orange
White
Black
Blue
Grey
Violet
Green & Yellow
L
N
Pressure
Switch
O/H
P
o
o
l
P
u
m
p
H
e
a
t
i
n
g
D
e
m
a
n
d
P
o
o
l
D
e
m
a
n
d
CONTROL BOARD
G/Y
N
2
5
0
m
A
A
S
L
R
C
POOL DMD
HTG DMD
HTR PUMP
POOL PUMP
BURNER
P
r
e
s
s
u
r
e
S
w
i
t
c
h
B
u
r
n
e
r
S
e
n
s
o
r
P
o
o
l
S
e
n
s
o
r
C
o
m
m
o
n
R
R
B
Or
Y
Yellow
Y
W
B
Br
B
Gy
V
Sensors
Pool
Burner
Or
Br
Bk
3 PORT
E
N
L
VALVE
B
r
B
G/Y
01/06/02
Page 17
6. COMMISSIONING
6.1 General Information
For Systems with Space Heating
The elimination of air from systems is essential to minimise the occurrence of heat exchanger and general system noise.
Metal swarf and flux chemicals make a very ag­gressive mixture, the destructive nature of which can be drastically reduced by flushing. Conse­quently this is a mandatory step in the commission­ing procedure.
Low water content, fabricated Heaters are vulner­able to damage by air , particularly when the system water is ‘hard’. (Contains a lot of dissolved calcium salts). The result of this damage is evident in noisy Heaters and reduced service life.
Removal of air from a system mainly takes place when the water is stopping, starting or not moving at all. It is removed most easily when it is in large bubbles, but the action of the pump is to chop it up so that it becomes a foam, which is extremely difficult to remove.
Two or three second bursts on the pump at the initial stage will reduce the risk of foam formation.
Sloping the pipe runs towards the vent points will greatly aid air removal. Sloping pipes are not just a feature of gravity systems but can greatly aid the pumped system because air can move towards a vent when the pump stops.
Air is dissolved in water but is released when heated. Always run a system at maximum tempera­ture for at least 15 minutes to enable this potential problem to be removed during commissioning.
6.2 Procedure
MODEL 100 ONL Y :
If the Heater has just been filled with very cold water, the b uilt in F rost Thermostat could attempt to fire it, if it has a permanent live and no switched live, this is completely normal. It is recommended that the gas cock is turned off during this early stage.
Pool Only Systems
There is an Automatic Air Vent inside the Heater, ensure that the cap is open before filling with mains water through the Filling Loop. With the gas off, run the heater to circulate the water and remove the air . T urning the supply on and off will pulse the pump and help the air to rise to the Automatic Air Vent. When completely clear of air, re-pressurise and remove filling loop.
Turn the gas back on. The Heater is ready f or use . The Heater is fitted with automatic ignition and will start when the gas cock is open, Mains is con­nected to the Heater and the controls are calling for heat.
For the Model 100 only:
It has a built in delay, and the Heater can be held off for 120 seconds. How­ever, for commissioning purposes, switching off using the System Isolating Switch will avoid the delay.
For Systems with Space Heating
It is strongly suggested that the following stages of commissioning are followed, and not an immediate connection of all services. This procedure pre vents substantial amounts of air being dispersed through the system as small bubbles. Carry out electrical tests as stated in Electrical Connections if not already done so.
With all radiator valves open, fill the system from the Filling Loop, but do not start the pump.
With the temporary hose connected, fill from the mains supply , then follo w the procedure below .
Check for water soundness and rectify where necessary.
DO NOT TURN ON GAS
Drain the system by opening all draincocks. This will flush the system of flux and swarf. Pour ¾ of the inhibitor in and fill the system with clean water and vent air from radiators and pipework.
Pour in all the inhibitor , and fill to required pressure plus 0.3 bar to allow for venting.
Switch on the electrical supply to the Heater and switch the programmer ON.
Switch OFF after about five seconds and vent all points again.
Repeat this for 5 minutes.
Re-pressurise if required. T urn on pump (do not turn on gas) and run for at
least 30 minutes. Stop pump at five minute intervals and vent until no
more air can be removed and air noises are no longer produced at the Heater. While the system is venting check again for water soundness.
16
100 Gas Condensing Pool Heater22/07/03
Page 18
Rating Table(1040 Btu/ft³) (38.8 MJ/m³
)
kW
Btu/h sec/ft³ m³/2 mins
22
75064 49.9 0.0680
24
81888 45.7 0.0742
26
88712 42.2 0.0804
TURN ON THE GAS
Check for gas soundness (BS 6891) in pipework to the Heater using a manometer.
Open the gas cock and after purging the system, the Heater will light automatically .
Run the system at maximum thermostat setting. Gas soundness within the Heater should be
checked using sense of smell and/or leak detection fluid.
Continue running for 15 minutes, venting every 5 minutes.
The Main V alv e gradually raises the pressure to the set point. Allow at least 60 seconds for the Model 100 and 100 seconds for the Model 100W for the final pressure to stabilise. NB The Pilot has no adjustment.
IMPORTANT. It is essential when setting the burner pressure that the inlet pressure is at least 20 mbar with the Heater and any other connected appliances running.
Check the burner pressure is correct by using a manometer connected to the control.
(See the Datatable inside the cover , the c hart below and Fig.6:2a & 6:2b)
The pump speed is set by the Manufacturer at £ and should not be changed.
Re-pressurise to required pressure.
With the system hot, check again for water sound­ness. Refit the case to the Heater . Add remainder of corrosion inhibitor. If there is a Space Heating system balance in the normal way to obtain even heating of all radiators.
If fitted, set the cylinder thermostat to 60oC, or lower if preferred.
Complete the Logbook and pass to the user when explaining and demonstrate the operation of the system. Their instructions are in the first pages of this Installation Instructions.
Note: The Heater is fitted with a syphon trap that in­cludes a blocked drain detection device. This is to safeguard the Heater and help defer the effects from the possible freezing of the condensate pipework in extreme weather . The user should be made aware of this feature and, that in the event of blocked condensate pipework, for example frozen condensate pipework, the Heater will automatically stop functioning. It will start again as soon as the blockage has cleared.
COMMISSION CHECK LIST (HYDRAULIC)
The key points which must be observed closely, are shown below .
* With radiator valves and vents open fill the
system. * Do not use pump. Do not light gas * Check for and rectify leaks. * Drain to flush system. * Refill system, adding ¾ of the inhibitor . * Do not light Heater . * V ent all radiator and air release points. * Run pump for 5-10 second bursts and revent. * Do not light Heater .
* Run pump for at least 30 minutes. * Stop at 5 minute intervals to vent. * Continue venting until no more air noise can be
heard. * Light Heater and run at max thermostat setting.
Continue for 15 minutes, venting every 5
minutes. * Add remainder of inhibitor .
T able 6:2
17
100 Gas Condensing Pool Heater 20/10/03
Page 19
GAS VALVE
Fig 6:2a
18
100 Gas Condensing Pool Heater
01/06/02
IN
OUT
GAS INLET
GAS OUTLET
INLET PRESSURE POINT
OUTLET PRESSURE POINT
GAS VALVE
Fig 6:2b
100W
100
Page 20
6.3 SETTING UP THE CONTROLS
It is recommended that you familiarise yourself with the functions of the Control. These are detailed in the
User Instructions Section
, and the
Heater
Control Section
.
There are two options that should be set to suit the user and it also recommended that the Fault Logs are cleared.
1. The display is factory set for Fahrenheit Centigrade, it can be altered to show Centigrade.
2. If the Heater is also providing Space Heat ing/DHW , the f actory setting of Pool priority may want to be changed to Heating priority . Priority means, whichever is chosen has to be up to temperature before it heats the other.
These settings can be altered, and other data viewed in ‘Setup Mode’
Setting Heating Knob On or Off Fascia Indicator
1 Heater temperature * Actual temperature Set temperature e.g 20 & 70
Factory setting Alternative
2 Display Units °F = Fahrenheit °C = Centigrade °C or °F 3 Priority P = Pool H = Heating P or H 4 Filter Pressure log # Number of Operations Resets to zero Yellow Filter LED On 5 Not used 6 Not used 7 Version Number __e.g. 010
* In this position with the Pool Temperature Control off, the Heater can be run for test purposes, if there is a Space
Heating demand, by turning On the Heating Temperature Control Knob.
# Reset the log by turning the Heating Temperature Control Knob On or Off.
T able 6:3. Contr ol Display in Setup Mode.
PROCEDURE T O ENTER SETUP MODE
T o enter Setup Mode turn both T emperature Control Knobs to OFF. The following must be carried out within 5 seconds.
1. Turn on the Mains supply to the Heater.
2. Turn the Pool Temperature Control Knob ON.
3. Turn the Heating T emperature Control Knob ON.
4. Turn the Pool Temperature Control Knob OFF.
5. Turn The Heating Temperature Control Knob OFF. The Control is now in ‘Setup Mode’ and displaying the Heater temperature. Additional data is displayed as the Pool Temperature Knob is rotated.
See Fig.
6:3 & T able 6:3
Settings that can be altered are changed by turning the Heating Temperature Control Knob On or Off.
To leave ‘Setup Mode’ and retain the new settings, turn off the Mains supply for a few seconds at any time.
Note: At power-up the Display is also used to show fault conditions. If an unexpected display is shown please check the Fault Finding Section 10:2.
Fig 6:3
ON
bar
0 4
2
1 3
u
s
e
r
i
n
s
t
r
u
c
t
i
o
n
s
i
n
s
i
d
e
u
s
e
r
i
n
s
t
r
u
c
t
i
o
n
s
i
n
s
i
d
e
100
s
e
e
i
n
s
t
r
u
c
t
i
o
n
s
2
3
4
5
6
7
1
Heater Temperature Actual & Setting
Setting Knob
Adjusting Knob
Display units °C or °F
Priority P = Pool H = Heating
Filter Log
Not Used
Ver sion Number
Overheat LED
Filter LED
19
100 Gas Condensing Pool Heater
01/06/02
Page 21
6.4 Pump Pressure Switch
The pressure switch, ensures that the heater operates only when the filter pump is in operation. It is factory set at 0.12 bar (1.75 PSI) for deck level installations. When the heater is located below the level of the spa or pool, it may be necessary to reset the pressure switch to compensate for the no-flow static head. If it is necessary to reset the pressure switch, we recommend the following procedure:
PUMP PRESSURE SWITCH ADJUSTMENT
1. With pump and heater on, turn adjustment knob clockwise until a click is heard from the gas valve.
2. Turn adjustment knob counter clockwise ¼ turn.
3. Turn pump off and on several times. Heater should shut off immediately. If it does not, repeat steps above until proper adjustments is made.
Adjustment Knob
NOTE:
If heater is installed outside of the limits shown below, a flow switch must be used in place of the pressure switch when mounted and wired adjacent to the heater.
TWO SPEED PUMPS
In some cases, the flow on the low speed is insufficient to operate the heater. This is apparent when the pressure switch cannot be further adjusted or if the heater makes banging noises. In these cases, the pump must be run at high speed when heating the water.
CAUTION:
Do not operate the heater without the functionof a properly adjusted pressure switch or flow switch.
6.5 Responsibility
It is the responsibility of the Installer to ensure that the Heater is properly commissioned. It is essential that the commissioning procedures detailed in this
manual are carried out by a qualified engineer.
Fig. 6:4a
Fig. 6:4b
1.5 m Max
1.5 m Max
20
100 Gas Condensing Pool Heater
01/06/02
Page 22
7:1:1 Control Fault Diagnostics
Before commencing a diagnosis it is recommended that you familiarise yourself with the functions of the Controls. These are detailed in the
Users
Instructions Section 1:4
and in
Heater Control,
Section 2:4
The Control will diagnose and display
most of its own faults.
Self Check
The Control does a full self check during power up. It also briefly lights all the LEDs and the Tempera­ture Display so they can be checked for operation.
Demand Inputs
The front panel LEDs for P ool Demand and Heating Demand are triggered from the Mains Inputs and the chosen Priority. If they are not lit check the supplied voltage, connections and Priority setting.
Relay Outputs
LEDs on the Control Board, beside the relays, are directly connected to the relay outputs and show if there is an output voltage to the Burner, Internal Pump or Pool Pump . If they are not lit check the output voltages, if correct replace the board. If lit,
check voltage at the component, replace if correct.
7: FAULT FINDING 7:1 Heater Control
If the Heater fails to start, make the following checks .
1. Is the mains electricity supply switched On?
2. Is there a Demand for Pool or Space Heating?
3. For Space Heating is the Heater Thermostat set to the desired temperature?
6. Check the fuses which should have been fitted to the mains electricity supply to the Timeswitch/Heater . If the fuse has blown. Replace it. If it blows again, call a Service Engineer.
7. Is the Filter LED lit? If it is, check Pool Pump is running and the Filter is not blocked.
8. Is the Overheat LED lit? If it is press the Reset on the Control Panel.
If the fault is not permanently corrected by one of these actions it is likely that a component is faulty and will need replacing. This should only be carried out by someone competent to do so.
IMPORT ANT - E
LECTRICAL SAFETY
IT IS
ESSENTIONAL THAT BEFORE ANY P ANELS ON COMPONENTS
ARE
REMOVED FROM THE HEATER, THAT THE MAINS ISOLATOR IS
SWITCHED
OFF
.
Displayed Faults
The Control board detects and displays certain fault conditions. The display alternates between two codes.
Display Reason Action
Err / No
Control board fault.
Power Off then On again. If not corrected replace board.
Oc / thb
Boiler sensor
Check connections,
Open Circuit.
if correct, replace sensor.
Oc / thp
Pool sensor
Check connections,
Open Circuit.
if correct, replace sensor.
Sc / thb
Boiler sensor
Check connections,
Short Circuit.
if correct, replace sensor.
Sc / thp
Pool sensor
Check connections,
Short Circuit.
if correct, replace sensor.
Log
The Control keeps a log of the number of times the Pressure Switch operates. These can be e xamined and reset to zero in Setup Mode. The Temperature Display units and Priority can also be checked and
altered in this mode.
Setup Mode
T o enter Setup Mode turn both temperature control knobs to OFF.
The following must be carried out within 5 seconds.
T o enter Setup Mode turn both Temperature Control Knobs to OFF. The following must be carried out within 5 seconds.
1. Turn on the Mains supply to the Heater.
2. Turn the Pool Temperature Control Knob ON.
3. Turn the Heating T emperature Control Knob ON.
4. Turn the Pool Temperature Control Knob OFF.
5. Turn The Heating Temperature Control Knob OFF. The Control is now in ‘Setup Mode’ and displaying
the Heater temperature. The Display can now show additional data as the Pool Temperature Knob is rotated.
See Fig 7:1 and
Table 7:1
Settings that can be altered can be changed by turning the Heating T emperature Control Knob On or Off.
To leave ‘Setup Mode’ and retain the new settings, turn off the Mains supply for a few seconds at any time.
21
100 Gas Condensing Pool Heater
10/03/03
Page 23
TABLE 7:1
FIG 7:1
ON
bar
0 4
2
1 3
u
s
e
r
i
n
s
t
r
u
c
t
i
o
n
s
i
n
s
i
d
e
u
s
e
r
i
n
s
t
r
u
c
t
i
o
n
s
i
n
s
i
d
e
100
s
e
e
i
n
s
t
r
u
c
t
i
o
n
s
2
3
4
5
6
7
1
Heater Temperature Actual & Setting
Setting Knob
Adjusting Knob
Display units °C or °F
Priority P = Pool H = Heating
Filter Log
Not Used
Ver sion Number
Overheat LED
Filter LED
22
100 Gas Condensing Pool Heater 01/06/02
CONTROL DISPLAY IN SETUP MODE.
Setting Heating Knob On or Off Fascia Indicator
1 Heater temperature * Actual temperature Set temperature e.g 20 & 70
Factory setting Alternative
2 Display Units °F = Fahrenheit °C = Centigrade °C or °F 3 Priority P = Pool H = Heating P or H 4 Filter Pressure log # Number of Operations Resets to zero Yellow Filter LED On 5 Not used 6 Not used 7 Version Number __e.g. 010
* In this position with the Pool Temperature Control off, the Heater can be run for test purposes, if there is a Space
Heating demand, by turning On the Heating Temperature Control Knob.
# Reset the log by turning the Heating Temperature Control Knob On or Off.
Page 24
7.2 Ignition Faults Model 100 Only
WARNING: BEFORE COMMENCING OR COM-
PLETING ANY ELECTRICAL WORK ON THE APPLIANCE, IT IS RECOMMENDED THAT THE BASIC SAFETY CHECKS FOR EARTH CONTINU­ITY, SHORT CIRCUIT , POLARITY AND RESIST­ANCE T O EARTH ARE MADE. ALL WORK CARRIED OUT SHOULD FOLLOW GUIDELINES LAID DOWN BY THE I.E.E.
The Ignition sequence in the Heater is straight forward and faults can easily be traced if these simple steps are followed.
Demand to Heat Pool Thermostat closed Boiler Thermostat closed Ignition Control energised Flue Stat closed Overheat Stat closed T rap not b locked Pressure Switch open Fan energised. Pilot Ignition Main Burner Ignition
If there is a request to heat the Pool, or if con­nected, the Space Heating, a mains signal will appear at the POOL DEMAND or HTG DEMAND connector in the Heater.
For Pool Heating
If the Pool Thermostat Board finds the P ool is below the set temperature it will put mains on the BURNER connection of the Pool Thermostat Board.This is indicated by the LED on the Pool Thermostat Board. This is connected to the Ignition Board at its Ls, (Switched Live) connection and the boiler will then start its ignition process.
For Space Heating (if connected) If the Pool Thermostat Board finds the Pool is up to temperature or it has been set for Heating Priority , it will put mains on the BURNER and HTR PUMP connections. This is indicated by the LEDs on the Pool Thermostat Board. The BURNER signal is connected to the Ignition Board at its Ls, (Swiched Live) connection and the boiler will then start its ignition process. The HTR PUMP signal is used to move the 3 way valve to Heating.
Ignition
Both the 100 and the100W follow the same se­quence however there are indicators on the 100 to show these steps. The description below uses the 100 to describe the process.
Lamps on the edge of the Ignition Board indicate the stages in the ignition sequence. Please refer to the lable inside the Heater . Permanent live has to be connected to the L terminal then the Power lamp lights .
A call for heat powers the Ls terminal and the Running and Pump lamps light.
Provided the Flue Stat, Overheat Stat and Heater are cold, the fan starts up. The pressure switch detects the correct airflow and that the condensate drain is not blocked then, switches over. This is indicated by the Fan lamp illuminating.
The Pilot lamp illuminates, the pilot gas valve opens and the Ignition Control Board provides a spark at the pilot electrode.
(If the L and N supply are reversed the Heater will not progress beyond pilot ignition. This is indicated by the Phase Reversed neon behind the knob lighting.)
The pilot flame is detected and the Ignition Control Board stops sparking and then energises the main gas valve and the Burner lamp is illuminated.
The pilot flame lights the burner, and it stays alight until turned off by the control thermostat, system controls, or in the case of a fault condition a safety thermostat.
The flue thermostat will trip if the flue exceeds a pre-set temperature. The ov erheat thermostat will trip if the water flow rate is insufficient, both are indicated by the Lockout lamp illuminating.
NOTE: The Heater has a b uilt-in dela y timer . It is indicated by the Running lamp flashing.
For testing, switching the Mains Supply off for a few seconds, then back on again will reset the delay.
Fault Diagnosis
The fault Diagnosis chart shows the normal and fault sequences for the Ignition Board indicator lamps.
T o diagnose a f ault, use the following procedure.
• Turn off the system Mains supply.
• Set all thermostats and timers to a call for
heat position.
• Turn on the system Mains supply and watch
the Ignition Board indicator lamps.
Compare the lamps with the diagnosis chart oppo­site to determine the fault and cause.
23
100 Gas Condensing Pool Heater20/10/03
Page 25
INDICATOR LIGHTS
Fig 7:2a
24
100 Gas Condensing Pool Heater
01/06/02
100
Page 26
Fig. 7:2b
25
100 Gas Condensing Pool Heater20/10/03
By using the flow charts basic problems can be identified. If the particular fault cannot be immediately identified, follow the charts from beginning to end
Before commencing, always check that the Mains is ON and the system controls are calling for heat, the gas cock is open.
Test the electrical system for short circuit, polarity, and resistance before attempting any electrical fault finding.
BOILER ACTION
Ensure Mains is ON.
Hot Water
required.
required.
Turn on any
Hot Water tap.
Ensure Clock/Thermostat
is set to call for heat.
Demand for heat
Fan and Pump start.
For HW Diverter Valve moves
to demand position.
Air Pressure switch
detects air flow.
Burner lights on
low flame.
Gas Valve opens for pilot.
Spark at electrode.
DHW: Burner to full rate.
CH: Low flame for 100 secs
then increases to full rate.
Flame modulates with heat demand.
Cycles ON and OFF if demand very low.
Demand Satisfied
USER CONTROLS
Operation Sequence
FAULT FINDING
Fault causes excess
temperature
Overheat trips
'Lockout' neon illuminates
A 'Demand' LED illuminates
Burner & Fan stop
100W
Page 27
Fig 7:2c
26
100 Gas Condensing Pool Heater 20/10/03
Is 230V at L connection ?
Correct Mains Supply.
NO
Open any Hot mains tap.
Is the water flow rate OK ?
NO
YES
Remove, clean &
replace Flow Restrictor.
Check pressure and flow
rate of water supply.
Have the Diverter micro-
switches moved ?
Are Inlet & Outlet pipes crossed ?
Replace diverter Valve.
Is there 230V to the pump
on its PCB terminals ?
YES
NO
NO
NO
Is the 2A PCB fuse OK ?
NO
Replace 2A PCB fuse.
NO
Are the micro-switches
operating electrically.
YES
NO
Replace the micro-
switch assembly.
Replace the main PCB
YES
Does the Fan start ?
Is the Pump free to rotate ?
Free or replace Pump
NO
YES
Does the pump start ?
NO
YES
Is there a spark ?
Has the O/H cutout tripped ?
Is there 230V to the Fan ?
NO
NO
NO
Has the Flue Stat tripped ?
NO
YES
YES
Reset or replace.
Reset or replace.
YES
Replace Fan.
Is there 230V from the CVI
Replace CVI board.
NO
Are the HT Lead & Electrode OK ?
Has the Pressure
Switch operated.
NO
YES
YES
NO
NO
Is there a blockage in the Condensate Trap or tubes ?
Replace Electrode and Lead
Replace the CVI board.
NO
YES
Replace the Pressure Switch.
YES
YES
Does the Burner light ?
FAULT FINDING Hot Water Operation
NO
Is the Gas Inlet pressure 20 mb
NO
Provide adequate Gas Supply
Replace CVI board, problem solved ?
if not replace CVI Valve
YES
Does Spark stop after Ignition ?
NO
YES
YES
Are the HT Lead & Electrode OK ?
Replace Electrode and Lead
NO
YES
Replace CVI board.
Is polarity of Boiler supply OK ?
NO
YES
Correct
Does Burner Flame increase to Maximum ?
Does the Flame reduce with water Flow Rate ?
Does the Flame reduce with the DHW Thermostat ?
Does the Flame stop before the O/H trips ?
YES
YES
YES
YES
Is the Thermistor reading
correct to Table A. ?
NO
NO
NO
NO
Replace Thermistor
NO
YES
Replace Main Board.
BOILER OPERATION SATISFACTORY
Is there upto 165mA on yellow lead to coil ?
NO
Replace Modureg Coil, now OK ?
YES
Start with system and boiler cold, with the power ON and no Hot Water taps open. Then Use a hot tap to operate the boiler.
0
20
10
30
40
50
60
70
80
90
33118
20198
12676
8176
5406
3657
2526
1780
1277
931
Temp °C
Ohms
TABLE A
YES
Has the Pilot lit ?
Check Pilot Injector, clean or replace.
NO
YES
Replace CVI
( CVI = Combined Valve & Ignition )
100W
Page 28
Fig. 7:2d
27
100 Gas Condensing Pool Heater 20/10/03
100W
Is 230V at L connection ?
Correct Mains Supply.
NO
Is there 230V to the pump
on its PCB terminals ?
Is the 2A PCB fuse OK ?
NO
Replace 2A PCB fuse.
NO
Are the micro-switches
operating electrically.
YES
NO
Replace the micro-
switch assembly.
Replace the main PCB
YES
Does the Fan start ?
Is the Pump free to rotate ?
Free or replace Pump
NO
YES
Does the pump start ?
NO
YES
Has the O/H cutout tripped ?
Is there 230V to the Fan ?
NO
NO
NO
Has the Flue Stat tripped ?
NO
YES
YES
Reset or replace.
Reset or replace.
YES
Replace Fan.
Is there 230V from the CVI
Replace CVI board.
NO
YES
YES
Does the Burner light ?
FAULT FINDING Pool or Space Heating Operation
Is the Gas Inlet pressure 20 mb
NO
Provide adequate Gas Supply
Replace CVI board, problem solved ?
if not replace CVI Valve
YES
Does Spark stop after Ignition ?
NO
YES
YES
Are the HT Lead & Electrode OK ?
Replace Electrode and Lead
NO
YES
Replace CVI board.
Is polarity of Boiler supply OK ?
NO
YES
Correct
Does Burner Flame increase to Maximum ?
Does the Flame reduce as temperature rises to Maximum ?
Does the Flame reduce with the Boiler Thermostat ?
Does the Flame stop before the O/H trips ?
YES
YES
YES
YES
Is the Thermistor reading
correct to Table A. ?
NO
NO
NO
NO
Replace Thermistor
NO
YES
Replace Main Board.
BOILER OPERATION SATISFACTORY
Is there upto 165mA on yellow lead to coil ?
NO
Start with system and boiler cold, with the power ON and no Hot Water taps open.
Set the system controls to call for heat.
0
20
10
30
40
50
60
70
80
90
33118
20198
12676
8176
5406
3657
2526
1780
1277
931
Temp C
Ohms
TABLE A
YES
Is there a spark ?
Are the HT Lead & Electrode OK ?
Has the Pressure
Switch operated.
NO
NO
NO
Is there a blockage in the
Condensate Trap or tubes ?
Replace Electrode and Lead
Replace the CVI board.
NO
YES
Replace the Pressure Switch.
YES
YES
NO
Has the Pilot lit ?
Check Pilot Injector, clean or replace.
NO
YES
( CVI = Combined Valve & Ignition )
YES
Replace CVI
Replace Modulating Coil, now OK ?
Page 29
8. SER VICING
8.1 Heater Servicing
Health and Safety Statement :
This product contains no asbestos.
Routine
T o ensure continued efficient oper ation of the appliance it is recommended that it is checked and serviced at regular intervals. The frequency of servicing will depend upon the particular installation and usage but in general once per year should be adequate. It is law that any service work should be carried out by Corgi registered personnel.
1.
Clean burner and combustion chamber .
2.
Check pilot and burner gas supply .
3.
Check condition of ignition sensing probe.
4.
Check Heater pipework joints for leaks.
5.
Check the case seals.
6.
Check condensate pipework for leaks.
7.
Check heat exchangers, and the flue and air duct are clear of any obstruction, and not leaking.
8.
Check the F an and its seal.
9.
Check and clear the condensate exit on the secondary heat exchanger by removing the Condensate Outlet and the Inspection Covers
(Fig. 10:1).
10.
Check and clear the condensate syphon.
Follow the procedures given in Changing Components for parts removal in addition to the following notes.
Heat Exchangers
Remove the panel in front of the secondary heat exchanger to gain access to inner inspection panels on the secondary and to view the primary (the lowest inspection panel also gives a view of the primary). Also view from beneath the primary . Clean as required. If in doubt, drain the system and remove for inspection.
Condensate Syphon
With a suitable bowl to catch the water , unscre w the drain cap(s) on the underside of the Syphon T rap and dr ain the water. Remo ve any solids and replace the cap(s). (
See Fig 10:3
)
8.2 Changing Components
THERE ARE NO REP AIRABLE ITEMS, IF NO T WORKING AN ITEM MUST BE REPLACED .
The Heater is in two major sections, the Case, and the Electrical Chassis, The Major Components Diagram shows where the items are to be found. (pages 23-24)
Behind the Case
1. Fan.
2. Air Pressure Switch.
3. Flue Thermostat.
4. Control Sensor.
5. Overheat Cut-off Device.
6. HT Lead.
7. Pilot Assembly.
8. Burner.
9. Main Injector.
10. Combustion Chamber Insulation.
11. Primary Heat Exchanger.
12. Secondary Heat Exchanger.
For the 100W only
13. Pump Overrun Thermostat.
Servicing inside the Electrical Chassis
T o Remove the Electrical Chassis
• Disconnect the electrical supply from the Heater and system.
For the 100W only:
Remove the single fixing screw.
• Slide the Electrical Tray forward a short wa y, then lower onto the brack et if supprt required.
• Remove the cover over the components.
• If complete removal required, disconnect all the leads and remove the plastic nut holding the Presssure Gauge retainer.
DO NOT STRAIN THE CABLES, USE THE SUP­PORT PRO VIDED.
8.2.1 Control boards
• Lower the Electrical T r ay.
• Remove the screws that retains the inner cover. Dissconnect all the leads from the board to be changed.
Inside the Electrical Chassis
1 . Control Boards.
2. Gas Valve.
3. Pump
4. Safety Valv e
5. Pressure Gauge.
For the 100W only
6. Divertor Valve
7. Water to Water Heat Exchanger .
8. DHW Sensor.
9. Inlet Flow regulator and strainer.
28
100 Gas Condensing Pool Heater
20/10/03
Page 30
8.2.2 Gas V alve - 100 Model Onl y
• Lower the Electrical T r ay.
• Turn the Gas Cock off .
• Pull off the electrical connector from the Gas Valve.
• Release the pilot feed tube.
• Undo the four shoulder bolts at each end of the valve.
TAKE CARE TO SUPPORT THE VALVE AS IT IS
RELEASED.
• Replacement is the reverse.
• When secure, attach a manometer to the burner pressure tapping on the right hand side of the valve.
• The Pilot Adjuster is factory set.
Model 100W Only:
832.3 Sequence Controller
• Remove the Electrical Tray.
• Identify the CVI valve, the red pod beside it contains the Sequence Controller.
• Prise off the multiway connectors from the CVI Sequence Controller pod.
• Pull off the HT Lead from the Controller .
• Pull the pod awa y, and replace.
• Re-assembly is the reverse.
Fig 8:2.2
• Turn on gas and electrical supply .
• The gas valve slowly opens to its setting ensure it has fully opened before adjusting.
• Set burner gas pressure with the gov ernor. (see T echnical Data inside of cover .)
8.2.4 CVI V alve
• Remove the Electrical Tray.
• Turn the Gas Cock off.
• Pull off the red pod.
• Pull off the two leads from the Modureg solenoid.
• Release the pilot feed tube (8mm AF).
• Undo the two screws holding the valve lower retainer.
• Undo the gas cock.
• Undo the four shoulder bolts and remove the flange to the gas cock.
• Release the CVI outlet connector , and withdraw valve.
• Re-assembly is the reverse.
CVI Pressure Set Up
• Check Inlet pressure is at least 20 mbar when operating.
• Remove the g rey co ver.
• Remove one of the yellow leads from the Modureg and its grey plastic cov er .
• Attach a manometer to the outlet pressure tapping.
• Set to Hot Water Only, turn on a tap and check burner gas pressure is 1.8 mbar. Adjust the 9mm brass nut on the Modureg to correct.
• Replace the yellow lead and the boiler will go to high fire, 11.3 mbar . Adjust with the nylon 7mm nut on the Modureg whilst pressing down on its shaft.
• Replace the grey co ver .
• Ensure the system controls are calling for POOL demand and set a Pool temper ature to bring on the Heater. The Heater will fire at low rate for 100 seconds. Adjust the small potentiometer on the Driver board to 5.0 mbar.
• After 100 seconds the boiler will go to high fire, adjust the large potentiometer on the driver board to the desired maximum output, factory setting 11.3 mbar.
For the Pool Thermostat Onl y:
• Remove the Control Knobs.
•
For the 100 Control Board Only:
• Release the Overheat Reset Switch.
• Slide out the board to be changed.
• Re-assembly is the reverse. NOTE
Replace the rear restraint to the Pool Thermostat board before re-fitting the board connectors.
For the 100W Control Board Only:
• Adjust the burner pressures. See CVI PRESSURE SETUP in CVI Valve section
below .
29
100 Gas Condensing Pool Heater
20/10/03
IN
OUT
INLET PRESSURE POINT
OUTLET PRESSURE POINT
100W
100
Page 31
8.2.6 Pump
• Remove the Electrical Tray .
• Close the CH Flow and CH Return valves.
• Drain the boiler through the Fill and Drain Valve.
• Disconnect the cable at the Pump including those in the terminal strip opposite the capacitor.
• Remove the terminal strip from the old pump.
• Undo the Pump nuts and remove the Pump.
• Re-assembly is the reverse,
• Note a brown and blue have a black sleeve and these go to terminal 1 and 2 respectively. The black goes to 7.
• Ensure the fibre washers are in place.
8.2.7 Diverter V alve
• Remove the Electrical Tray .
• Close the CH Flow and CH Return valves.
• Close the DHW Cold In valve and open a Hot tap to drain the pipework.
• Drain the boiler through the Fill and Drain Valve.
• Remove the circlip on the Diverter V alv e to release the switching head.
• Undo the five water connections to the valve and remove.
8.2.12 Removing the Case
• Lower the Electrical T ra y.
• Undo the two M5 screws at the base of the Case.
• Lift the Case straight up about half an inch (12mm).
• Gently pull the Case straight forward off the hidden studs at the top of the Heater. (Thecover hangs on two studs in keyhole slots)
8.2.5 Pressure Gauge
• Remove the Electrical Tray .
• Loosen the Plastic Nut that holds Gauge retainer.
• Squeeze the top and bottom latches on the gauge, and push out of its retainer.
• V alv e off the Flow and Return connections.
• Release the pressure in the boiler .
• Unscrew the pressure sensor , it ma y need a temporary plug to avoid leaks.
• Re-assembly is the reverse.
Fig 8:2.4
• Replace unit with new or factory exchange unit.
• Re-assembly is the reverse, ensure the fibre washers are in place.
8.2.8 Safety V alve
• Remove the Electrical Tray .
• Close the CH Flow and CH Return valves.
• Drain the boiler through the Fill and Drain Valve.
• Remove the Pressure Gauge from the Safety Valve.
• Undo the water connections to the Safety Valv e and remo ve.
• Re-assembly is the reverse, ensure the fibre washer is in place.
8.2.9 Water to W ater Heat Exchanger
• Remove the Electrical Tray .
• Close the CH Flow and CH Return valves.
• Close the DHW Cold In valve and open a Hot tap to drain the pipework.
• Drain the boiler through the Fill and Drain Valve.
• Remove pump and pipes for easy access.
• Undo the four water connections to the heat exchanger and pull clear .
• Re-assembly is the reverse, ensure the fibre washer is in place.
8.2.10 Flow Regulator and Strainer
• Remove the Electrical Tray .
• Close the Cold Water In valve.
• Open a Hot tap to drain the pipework.
• Remove the Mains Cold In V alv e.
• Carefully prise out the Flow Regulator and Strainer (boiler side).
• Clean Strainer and restrictor.
• Re-assembly is the reverse.
8.2.11 DHW T emperature Sensor
• Remove the Electrical Tray .
• Remove the electrical connection from the DHW Temperature Sensor and unclip from pipe.
• Re-assembly is the reverse.
30
100 Gas Condensing Pool Heater 01/06/02
Page 32
• Examine the sealing strip for damage and replace if necessary.
• Place the Case somewhere safe from damage
IMPORT ANT: F AILURE T O CORRECTL Y LOCA TE
THE APPLIANCE CASE COULD RESUL T IN LEAKAGE OF COMBUSTION PRODUCTS INTO THE ROOM.
8.2.13 Fan Assembly
• Lower the Electrical T ra y.
• Remove the Case.
• Undo the wing nut holding the Fan Protection Hoop.
• Pull the electrical connectors off the Fan.
• Gently pull the pressure tubing off the tappings on the Flue Hood.
• Undo the two screws holding the Flue Hood and slide forward and aw ay.
• Re-assembly is the reverse.
8.2.14 Air Pressure Switch
• Lower the Electrical T ra y.
• Remove the Case.
• Pull the electrical connectors off the Air Pressure Switch.
• Gently pull the pressure tubing off the both tappings on the switch.
• Undo the M4 nut and wing nut holding the Air Pressure Switch to its bracket on to the Back Panel
• Lift off its studs and rotate out of its bracket.
• Re-assembly is the reverse.
8.2.15 Flue Thermostat
• Lower the Electrical T ra y.
• Remove the Case.
• To replace pull the electrical connectors off the Flue Thermostat.
• To reset press Red Button.
• Re-assembly is the reverse.
8.2.16 Pump Overrun Thermostat
• Remove the Electrical Tray .
• Remove the Case.
• Note the three wire colours and positions.
• Pull the electrical connectors off the Pump Overrun Thermostat.
• Undo the two M4 screws holding the Thermostat.
• Re-assembly using Heat Sink Compound is in the reverse order .
8.2.17 Control Sensor
• Lower the Electrical Tray .
• Remove the Case.
• Unclip the sensor.
• Pull the electrical connectors off the Control sensor.
• Re-assembly is the reverse.
8.2.18 Overheat Cut-off Device
• Lower the Electrical Tray .
• Remove the Case.
(To Reset, Press Red Button)
• Pull the electrical connectors off the Over heat Cut-off device.
• Unscrew from its mounting.
• Re-assembly is the reverse.
• Lower the Electrical Tray .
8.2.19 Electrode and HT Lead
• Lower the Electrical T r ay.
• Remove the Case.
• To Replace pull off the HT lead from the Control Board/Sequence Controller.
• Undo the left and right screws holding the Front Burner Baffle.
• Remove the front baffle.
For the 100 Only:
• Release the tube nut holding the electrode to the Pilot Burner.
• Carefully withdraw the Electrode and HT Lead.
For the 100W Only:
• Push the Electrode towards the burner and pull down and clear.
• Re-assembly is the reverse.
8.2.20 Pilot Assembly
• Lower the Electrical T r ay.
• Remove the Case.
• Undo the left and right screws holding the Front Burner Baffle and remove . If access is restricted also remove the lower baffle.
• Release the tube nut holding the electrode to the Pilot Burner.
• Undo the Pilot tube from the Pilot Assembly and gently lever downwards away from the Pilot. It has to be removed and replaced with the injector clipped into position. Undo the two screws retaining the Pilot Assembly.
• Re-assembly is the reverse
NB The pilot is not adjustab le.
31
100 Gas Condensing Pool Heater
20/10/03
Page 33
8.2.24 Combustion Chamber Insulation
• Lower the Electrical T r ay.
• Remove the Case.
• Remove the Front Baffle, then undo the four M5 screws holding the lower baffle onto the Back Panel
• Remove the Burner, as in 10.
• Undo the four screws holding the Chamber to the Back P anel and lower downwards and away .
• Replace the Insulation Panels in the Chamber.
• Re-assembly is the reverse.
8.2.25 Primary Heat Exchanger
• Lower the Electrical T r ay.
• Remove the Case.
• Remove the front baffle.
• Remove or cover the Burner.
• Remove the Comb ustion Chamber.
• Unclip the Control sensor .
• Pull off the wires to the Overheat Cut Out device.
• Drain the Heater of water .
• Undo the flow and return connections to the Heat Exchanger and lower aw ay .
• Re-assembly is the reverse.
8.2.21 Burner
• Lower the Electrical T r ay.
• Remove the Case.
• Remove the Front Baffle.
• Remove the Combustion Chamber front by releasing the four screws.
• Undo the Pilot tube from the Pilot Assembly and gently lever downwards away from the Pilot. It has to be removed and replaced with the injector clipped into position.
• Pull off the HT lead.
• Pull the Burner forward off the two studs at the rear.
• Remove the Pilot Assembly.
• Re-assembly is the reverse.
8.2.22 Main Injector
• Lower the Electrical T r ay.
• Remove the Case.
• Remove the Burner .
• Undo the Main Injector from the manifold.
• Re-assembly is the reverse.
8.2.26 Secondary Heat Exchanger
• Lower the Electrical T r ay.
• Remove the Case.
• Remove the Flue Thermostat.
• Remove the Fan Assembly.
• Drain the Heater of water.
• Undo the flow and return connections to the secondary Heat Exchanger.
• Release the Condensate connection clamping plate.
• Undo the four screws holding the Secondary Heat Exchanger to the Back Panel and lift away .
• Re-assembly is the reverse.
32
100 Gas Condensing Pool Heater 01/06/02
Page 34
9. PARTS
9.1 Spares
Ke y Item Part Number GC Number
1 Primary Heat Exchanger M0593 2 Secondary Heat Exchanger (17 kW) M0797 3 Burner (Model 100) M3727 3 Burner (Model 100W) M3728 4 Ceramic Board Set M1089 106 404 5 Fan Assemb ly M0910 106 435 6 Ignition Board (Model 100) M4750 6 Driver Board (Model 100W) M0614 173072 8 Contol Board M4735 9 Pool or Heating Sensor SPCOH2/002 10 Sequence Controller M0672 173066 11 Gas V alve (Model 100) M3783 12 Gas V alve (Model 100W) M0671 13 Air Pressure Switch M4176
Main Injector (4.1mm) M0919 106 386 14 Overheat Thermostat (Model 100) M3781 379 314 15 Overheat Thermostat (Model 100W) M0868 173068
Pilot Injector (Model 100) 7709 386 673
Pilot Injector (Model 100W) M0663 381656
Electrode (Model 100) 7710 386 744 16 HT Lead Assembly (Model 100) M3895 17 Electrode & Lead (Model 100W) M0666
Pilot Assembly (Model 100) 7716 381 865
Pilot Assembly (Model 100W) M0662 106437 18 Flue Thermostat 7717 379 308 19 Clip-on Sensor (22mm) M3338 20 Clip-on Sensor (15mm) M3337 21 Condensate T rap M3805 22 Safety Valve M0480 379831 23 Three Way V alve M0608 173071 24 Pressure Gauge SPCOH2/003 25 Expansion Vessel M0610 26 Plate Water to W ater Heat Exchanger M0612 106436 27 Grundfos Pump M0623 383722 28 Pool Water to Water Heat Exchanger M4374 29 Pool Pump Pressure Switch 651284 30 Bypass Valve M1091 31 Diverter Valve M4531
33
100 Gas Condensing Pool Heater
20/10/03
Page 35
34
100 Gas Condensing Pool Heater 20/10/03
9:2 Electrical Components
100 & 100W
16
6
9
8
Page 36
10 DIAGRAMS 10:1 Major Components
Fig.10:1
35
100 Gas Condensing Pool Heater
01/06/02
14/15
30
28
31
29
22
13
27
11
24
2
1
18
5
19
Page 37
10:2 Example Condensate Disposal Methods
Fig.10:2
75mm Running Trap
Air Break
Strap-On Boss
1:20 Fall ( 2.5 Degrees )
Washing Machine
Trap
Air Gap
Air Gap
110mm Soil Pipe or Drain
Soakaway
Insulate against freezing
150mm Land Drain Filled with Gravel 750mm deep
Condensate Drain from Heater
Air Pressure Switch
pipe connection
Vent
Syphon
Connect To Waste
Drain Cap
Bypass
10.3 Condensate Drain Trap
Note: Internal - minimum 19mm pipe
External - minimum 32mm pipe
Condensate Drain for Twin Pipe Flue
Fig. 10:3
36
100 Gas Condensing Pool Heater 01/06/02
Page 38
M4728 20/10/03
Loading...