CentraLine MERLIN NX Series, RS4N, RL8N, RL2N, RS5N Installation & Commissioning Instructions

...
MERLIN NX Room Controller
Installation & Commissioning Instructions
GENERAL INFORMATION
Fig. 1. CLMERxxN (without optional covers)
(198 x 110 x 57.5
OS no.:
CLCM-…
RL4N 230 VAC 6 10 0 4 4 24 24-hr data retention
RL6N 24 VAC 6 10 0 4 4 24 24-hr data retention
mm)
RL8N 230 VAC 6 6(C 4(D 4 4 24
large housing
power
supply
AOs UIs BIs relays(A triacs(B
BEFORE INSTALLATION
IMPORTANT
It is recommended that the unit be kept at room temperature for at least 24 hours before applying power; this is to allow the evaporation of any condensation resulting from low shipping / storage temperatures.
US requirement, only: This device must be installed in a UL-listed enclosure offering adequate space to maintain the segregation of line voltage field wiring and Class 2 field wiring.
Table 1. Overview of models
CAUTION
To avoid electrical shock or equipment damage, you must switch OFF the power supply before attaching / removing connections to/from any terminals.
total no.
of I/Os
remarks
24-hr data retention; supports switch inputs with 24 V pull-up for connection of standard light switches; preferred model for light and blinds control
RS4N 230 VAC 4 4 0 4 2 14 24-hr data retention
mm)
small housing
(162 x 110 x 57.5
(A
See also section "Relay Current Limitations" on pg. 17.
(B
See also section "Triac Current Limitations" on pg. 17.
(C
Of this model's six UIs, only two UIs support NTC; this model is thus not suitable for the hardwiring of wall modules requiring
three UIs supporting NTC.
(D
This model's four binary-only inputs are labelled as UI1-UI4.
CPU: 32-bit MK24FN Freescale Kinetis Cortex M4
® U.S. Registered Trademark Copyright © 2019 Honeywell Inc. • All Rights Reserved EN1Z-1035GE51 R0319
RS5N 24 VAC 4 4 0 4 2 14 24-hr data retention
MERLIN NX ROOM CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
A
A
AO3A
A
A
A
A
A
A
DIMENSIONS AND MOUNTING
Housings
The controller is available in two housing sizes, both conforming to IP20:
▪ RLxN (large housing):
W x L x H = 110 x 198 x 59 mm and
▪ RSxN (small housing):
W x L x H = 110 x 162 x 59 mm
See also Fig. 2 and Fig. 3.
REMOVABLE
3.5
TERMINALS
59
53.5
52
57
C2+ GND2824V~
C2- WM130WM2
26
29
27
45
110
2N3
4
1
24V~7TN
24V0524V~624V0
L
230-V
MODELS
24-V
MODELS
Fig. 2. RLxN dimensions (in mm)
NOTE: In the case of the RL5N, all of the terminal blocks
are removable.
REMOVABLE
TERMINALS
57
198
O1
O2
O4
O5
O6
24V~46GND48UI250UI352GND54UI656UI758GND60UI10
3832
34
36
40
42
44
GND3524V~37GND3924V~41GND4324V~
31
33
8T~9
T0110TN11T0212T0313TN14T0415RC416RO417IN418RN19RN20IN121RO122IN223RO224IN325RO3
162
LED47UI149GND51UI453UI555GND57UI859UI961GND
45
C1+63C1- GND
62
64
BACnet MS/TP
SERVICE
59
59
10
10
198
IRM-RLC
(BULK PACK, 10 pcs.)
RLxNRLxN
54
Fig. 4. Large housing, with terminal protection covers,
dimensions (in mm)
162
54
IRM-RSC
(BULK PACK, 10 pcs.)
RSxNRSxN
59
54
58.32558.325
161.65
59
58.32558.325
161.65
10
WM1
WM2
3.5
59
53.5
52
24V~
O12724V~28GND
20
21
22
C2+23C2-
GND
26
25
24
45
110
1L2N3
230-V
MODELS
24V~424V05TN
24-V
MODELS
O2
O33124V~32GND
29
30
7
6T~10
T018TN9T02
UI136UI237UI339UI435GND38GND
O4
34
33
RO411IN412RN13RN14IN115RO116IN217RO218IN319RO3
C1-40C1+ GND
BACnet MS/TP
SERVICE
41
42
10
Fig. 3. RSxN dimensions (in mm)
The unit is suitable for mounting on a standard rail, on walls, as well as in wiring cabinets or fuse boxes.
Terminal Protection Covers for IP30
In the case of controllers mounted outside of a cabinet, before applying power to the device, Terminal Protection Covers (10­pc. bulk packs, order no.: IRM-RLC for large housings and IRM-RSC for small housings) must be mounted so as to provide IP30.
EN1Z-1035GE51 R0319 2
54
Fig. 5. Small housing, with terminal protection covers,
dimensions (in mm)
DIN Rail Mounting/Dismounting
MOUNTING DISMOUNTING
1.
2.
DIN EN 50022-35 x 7,5
Fig. 6. Mounting and dismounting
The unit can be mounted onto the DIN rail simply by snapping it into place. It is dismounted by gently pulling the stirrup(s) located at the base of the housing (see Fig. 6). When mounted vertically on a DIN rail, the unit must be secured in place with a stopper to prevent sliding.
1.
2.
RLxN: 2X RSxN: 1X
MERLIN NX ROOM CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
Wall Mounting/Dismounting
The unit can be mounted on floors, walls, and ceilings in any desired orientation. (See also section "Ambient Environmental Limits" on pg. 23 for temperature range restrictions with floor/ceiling mounting.)
The unit is mounted by inserting optional screws (recommended: DIN EN ISO 7049 – ST4,2x22 – C – H) through the corresponding screwing noses.
RLxN: 187.5
RSxN: 151.5
WM1
WM2
20
21
C2+23C2-
24
1L2N3
24V~
22
GND
25
AO12724V~28GND29AO230AO33124V~32GND33AO4
26
24V~424V05TN
7
6T~10
T018TN9T02
UI136UI237UI339UI435GND38GND
34
RO411IN412RN13RN14IN115RO116IN217RO218IN319RO3
C1-40C1+ GND
BACnet MS/TP
SERVICE
41
42
99.5
DIN EN ISO 7049 – ST4,2x22 – C – H
Fig. 7. Drilling template (view from above)
After mounting the unit onto the wall, snap the appropriate terminal protection covers (see Fig. 4 and Fig. 5 on pg. 2) into place onto the housing by hand.
NOTE: In the case of wall-mounting, optional terminal
protection covers (in the case of the RLxN [large housings]: IRM-RLC; in the case of the RSxN [small housings]: IRM-RSC) must be installed in order to comply with IP30.
The covers can be fixed into place using optional screws (recommended: DIN EN ISO 7049 – ST2,9x9,5 – C (F) – H). To remove a cover, place a screwdriver in the two leverage slots (marked with arrows) and pry it loose.
TERMINAL ASSIGNMENT
General
For a complete list of all terminals and a description of their functions, see Table 2 and Table 6.
NOTE: All terminal blocks capable of carrying either low
voltage or line voltage are orange-colored.
The delivery includes a plastic bag containing additional, removable terminal blocks for BACnet MS/TP and Sylk interfaces.
The controller is powered by 230 VAC, and is equipped with differing numbers of triac outputs, relay outputs, etc. capable of being configured in a variety of ways. See Table 1 on page
1. Every controller features a terminal assignment label on the
top of the housing.
Power Supply Terminals
▪ Power is supplied via an orange-colored fixed screw-type
terminal block (terminals 1+2).
See also section "Power Supply" on pg. 11.
Input / Output Terminals
The controller features rows of terminal blocks on the top and bottom.
▪ In the case of the RLxN (large housing), the controller has
double rows of analog outputs (AOs) and universal inputs (UIs) at the top and a single row of binary outputs (BOs) – triacs (TRs) and relay outputs (ROs) – at the bottom.
▪ In the case of the RSxN (small housing), the controller has
a single row of analog outputs (AOs) and universal inputs (UIs) at the top and a single row of binary outputs (BOs) – triacs (TRs) and relay outputs (ROs) – at the bottom.
NOTE: According to VDE guidelines, it is not allowed to mix
low-voltage and high-voltage signals on the relays and triacs.
See also section "I/O Terminals" on pg. 17.
Communication Interfaces
All models of the controller feature the following communi­cation interfaces:
▪ A Sylk Bus interface (removable plug; RSxN: terminals 20
and 21; RLxN: terminals 30 and 31), for connection to CLCMTR40x/42x Wall Modules;
▪ A BACnet MS/TP interface (removable plug; RSxN:
terminals 40, 41, and 42; RLxN: terminals 62, 63, and 64); ▪ A second RS485 interface for future use with Modbus; ▪ An RJ45 connector for connection of the BACnet WiFi
Adapter.
3 EN1Z-1035GE51 R0319
MERLIN NX ROOM CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
Table 2. RSxN Room Controller: Overview of terminals and functions
term. printing function RS4N RS5N
1, 2 "L", "N" 230-V power supply X --
3, 4 "24V~", "24V0"
3, 4 "24V~", "24V0" Aux. output voltage (24 VAC) for all triacs -- X
5 "TN" Aux. term. for triac neutral wiring (internally connected with terminal 8) X X
6 "T~" Triac input voltage (24 VAC / 230 VAC) for all triacs; triac-switched X X
7 "T01" Triac-switched output X X
8 "TN" Aux. term. for triac neutral wiring (internally connected with terminal 5) X X
9 "T02" Triac-switched output X X
10, 11 "RO4", "IN4" Output of Relay 4, Input for Relay 4 type 2 type 2
12, 13 "RN", "RN" Aux. terminals for relay neutral wiring X X
14, 15 "IN1", "RO1" Input for Relay 1, Output of Relay 1 type 1 type 1
16, 17 "IN2", "RO2" Input for Relay 2, Output of Relay 2 type 1 type 1
18, 19 "IN3", "RO3" Input for Relay 3, Output of Relay 3 type 1 type 1
20, 21 "WM1", "WM2" Removable interface for Sylk Bus X X
22, 23, 24, 25
26 "AO1" Analog Output 1 type 2 type 2
27 "24V~" 24 VAC power for field devices X X
28 "GND" Ground for AOs X X
29 "AO2" Analog Output 2 type 1 type 1
30 "AO3" Analog Output 3 type 1 type 1
31 "24V~" 24 VAC power for field devices X X
32 "GND" Ground for AOs X X
33 "AO4" Analog Output 4 type 1 type 1
34 "UI1" Universal Input 1 type 1 type 1
35 "GND" Ground for UIs X X
36 "UI2" Universal Input 2 type 1 type 1
37 "UI3" Universal Input 3 type 1 type 1
38 "GND" Ground for UIs X X
39 "UI4" Universal Input 4 type 1 type 1
40, 41, 42 "C1+", "C1-", "GND" Removable BACnet MS/TP interface and corresponding GND X X
Relay output types: See Table 3. Universal input types: See Table 4. Analog output types: See Table 5.
"24V~", "C2+", "C2-", "24V0"
type 1 (standard) type 2 (high in-rush current)
corresponding ROs of RSxN RO1, RO2, RO3 RO4
corresponding ROs of RLxN RO2, RO3 RO1, RO4
contact N.-O. N.-O.
min. load 5 VAC, 100 mA 24 VAC, 40 mA
switching voltage range 15 … 253 VAC 15 … 253 VAC
max. continuous load at 250 VAC (cos φ = 1) 4 A 10 A
max. continuous load at 250 VAC (cos φ = 0.6) 4 A 10 A
in-rush current (20 ms) -- 80 A
usage fan motor light switching and fan motor
NOTE: The max. sum load of all relay currents at the same time is 14 A.
Removable 24-V power supply input and aux. output voltage (24 VAC) for all triacs
Aux. power (24 VAC 20%, 50/60 Hz) + RS485 Modbus interface + corresp. GND
Table 3. Relay output types and characteristics
X --
-- --
EN1Z-1035GE51 R0319 4
MERLIN NX ROOM CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
Table 4. Universal input types and characteristics
type 1 type 2 type 3
dry contact (closed: res. <10 kΩ; open: res. > 20 kΩ; max. 0.2 Hz; pull-up voltage: 10 V)
dry contact (closed: res. <10 kΩ; open: res. > 20 kΩ; max. 0.2 Hz; pull-up voltage: 24 V)
fast binary (=counter) input (max. 30 Hz; pulse ON = min. 16 ms; pulse OFF = min. 16 ms; closed: voltage < 1 V; open: voltage > 5 V; pull-up voltage: 10 V)
fast binary (=counter) input (max. 30 Hz; pulse ON = min. 16 ms; pulse OFF = min. 16 ms; closed: voltage < 1 V; open: voltage > 5 V; pull-up voltage: 24 V)
0(2) … 10 V X X -­NTC20kΩ
SetPoint and FanSpdSW (from CLCM1T,2T,4T,5T,6T111) X -- -­NTC10kΩ
PT1000 + Ni1000TK5000 -- X --
Table 5. Analog output types and characteristics
type 1 type 2 type 3 type 4 type 5
output voltage 0…11 V output current 0…1 mA 0…5 mA 0…10 mA 0…20 mA -1…+1 mA min. accuracy ±150 mV max. ripple ±100 mV accuracy at zero point 0…200 mV ±150 mV
UI1, UI2, UI3,
UI4, UI5, UI6
X X --
-- -- X
X X --
-- -- X
X -- --
X -- --
UI7, UI8, UI9,
UI10
UI1, UI2, UI3,
UI4 (RL8N,
only)
5 EN1Z-1035GE51 R0319
MERLIN NX ROOM CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
Table 6. RLxN Room Controllers: Overview of terminals and functions (by model)
term. printing function RL4N RL6N RL8N
1, 2 "L", "N" 230-V power supply
3, 4 "24V~", "24V0" Removable 24-V power supply input
3, 4 "24V~", "24V0" Aux. output voltage (24 VAC) for all triacs
5, 6 "24V~", "24V0" Aux. output voltage (24 VAC) for all triacs
7 "TN"
8 "T~" Triac input voltage (24 VAC / 230 VAC) for all triacs; triac-switched
9 "T01" Triac-switched output
10 " TN"
11 "T02" Triac-switched output
12 "T03" Triac-switched output
13 " TN"
14 "T04" Triac-switched output
15 "RC 4" Not used.
16, 17 "RO4", "IN4" Output of Relay 4, Input for Relay 4
18 "RN" Aux. terminal for relay neutral wiring
19 "RN" Aux. terminal for relay neutral wiring
20, 21 "IN1", "RO1" Input for Relay 1, Output of Relay 1
22, 23 "IN2", "RO2" Input for Relay 2, Output of Relay 2
24, 25 "IN3", "RO3" Input for Relay 3, Output of Relay 3
26, 27, 28, 29 "C2+", "C2-", "24V0", "24V~" Not used.
30, 31 "WM1", "WM2" Removable interface f or Sylk Bus
32 "AO1" Analog Output 1
33 "GND" Ground for AOs
34 "AO2" Analog Output 2
35 "24 V~" 24 VAC power for fiel d devices
36 "AO3" Analog Output 3
37 "GND" Ground for AOs
38 "AO4" Analog Output 4
39 "24 V~" 24 VAC power for fiel d devices
40 "AO5" Analog Output 5
41 "GND" Ground for AOs
42 "AO6" Analog Output 6
43 "24 V~" 24 VAC power for fiel d devices
44 "24 V~" 24 VAC power for fiel d devices
45 "LED" Output to LED of CLCM4T,5T,6T111
46 "GND" Ground for UIs
47 "UI1" Universal Input 1
48 "UI2" Universal Input 2
49 "GND" Ground for UIs
50 "UI3" Universal Input 3
51 "UI4" Universal Input 4
52 "GND" Ground for UIs
53 "UI5" Universal Input 5
54 "UI6" Universal Input 6
55 "GND" Ground for UIs
56 "UI7" Universal Input 7
57 "UI8" Universal Input 8
58 "GND" Ground for UIs
59 "UI9" Universal Input 9
60 "UI10" Universal Input 10
61 "GND" Ground for UIs
62, 63, 64 "C1+", "C1-", "GND" Removable BACnet MS/TP interface and corresponding GND
Aux. terminal for triac neutral wiring (internally connected with terminals 10 + 13)
Aux. terminal for triac neutral wiring (internally connected with terminals 7 + 13)
Aux. terminal for triac neutral wiring (internally connected with terminals 7 + 10)
Relay output types: See Table 3. Universal input types: See Table 4. Analog output types: See Table 5.
X -- X
-- -- --
-- X --
X X X
X X X
X X X
X X X
X X X
X X X
X X X
X X X
X X X
-- -- --
type 2 type 2 type 2
X X X
X X X
type 2 type 2 type 2
type 1 type 1 type 1
type 1 type 1 type 1
-- -- --
X X X
type 3 type 3 type 4
X X X
type 3 type 3 type 3
X X X
-- type 1 type 5
-- X X
-- type 1 type 5
-- X X
-- type 1 type 1
-- X X
-- type 1 type 1
-- X X
X -- X
X -- X
X X X
type 1 type 1 type 3 (BI)
type 1 type 1 type 3 (BI)
X X X
type 1 type 1 type 3 (BI)
type 1 type 1 type 3 (BI)
X X X
type 1 type 1 type 1
type 1 type 1 type 1
X X X
-- type 2 type 2
-- type 2 type 2
-- X X
-- type 2 type 2
-- type 2 type 2
-- X X
X X X
EN1Z-1035GE51 R0319 6
MERLIN NX ROOM CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
*OPTIONAL FUSE (TO PROTECT CONTROLLER‘S INTERNAL TRANSFORMER, WHICH HAS ONLY A NON-RESETTABLE FUSE).
CLCMTR40x/TR42x
WAL L MOD ULE
22
20
WM121WM2
1L2
PROP.
PROP.
COOL
HEAT
°C
27
26
AO1
24V~
N
3
24V~424V0
28
24V0
29
AO230AO3
NL
31
24V~
5TN6
T~
N TIN RIN NN FIN
230 V
F1*
Fig. 8. RS4N example wiring (230-V model)
24V~
PROP.
0...10V
CLCMTR40x/TR42x
WALL MODULE
22
°C
GND
DAMPER
ACTUATOR
7
T01
THERM.
COOL
32
GND
8TN9
33
AO4
T02
THERM.
HEAT
34
35
UI1
GND
ELECTR.
REHEATER
UI237UI3
CLCM2T WALL MODULE
1
TEMP2SETP
OCCUPANCY CONTACT
36
10
RO4
38
GND
11
IN412RN13RN14IN1
L L
N N
LINE VOLTAGE
3
COM
OCCUPANCY CONTACT
workbench
39
UI4
15
RO1
Niagara
workbench
Niagara
16
IN2
3-SPEED
FAN
BACnet MS/TP
40
C1+41C1-42GND
17
RO218IN319RO3
242 5 26 27 28 29 30 31 3 2
END
BIAS
MID
RS232
RS485-1
485-1+
GND1
J1 J8
EAGLEHAWK NX
24V~
24V-0
1
2
BACnet WiFi
n.a.
n.a.
n.a.
485-1-
485-2-
485-2+
GND2
ADAPTER
87 6543 21
RJ45 INTERFACE
7 8
RJ45 PLUG
2,3, 5,6
4
20
WM121WM2
1L2
26
AO1
3
N
24V~424V0
24V~
28
27
GND
29
AO2
30
AO3
5
TN
NL
24V~
6
T~
32
31
GND
AO4
7
9
8
T01
T02
TN
THERM.
THERM.
COOL
HEAT
34
33
UI1
35
GND
ELECTR.
REHEATER
36
UI237UI3
10
RO4
IN4
39
38
UI4
GND
11
12RN13
15
14
RO1
IN1
RN
16
RO218IN319RO3
IN2
3-SPEED
FAN
40
C1+41C1-42GND
17
87 6543
21
RJ45 INTERFACE
2,3, 5,6
7 8
4
230 V
F1
BACnet MS/TP
24V~24V0
N L
LINE VOLTAGE
Fig. 9. RS4N example wiring (230-V model) (with actuator powered by extra transformer)
7 EN1Z-1035GE51 R0319
MERLIN NX ROOM CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
CLCM2T WALL MODULE
CLCMTR40x/TR42x
WALL MODULE
22
°C
PROP. COOL
PROP.
HEAT
1
TEMP2SETP
COM
3
Niagara
workbench
OCCUPANCY CONTACT
1
2526272829 30 31 32
24
END
BIAS
MID
RS232
RS485-1
n.a.
n.a.
n.a.
485-1-
485-2-
485-1+
485-2+
GND1
GND2
J1 J8
EAGLEHAWK NX
24V~
24V-0
2
20
WM121WM2
26
27
AO1
24V~
3
4
24V~
24V0
L
N
LI NE VOLTA GE
28
GND
29
AO230AO3
5
TN
N TIN
24V~
6
T~
32
GND
7
THERM.
COOL
33
AO4
9
8
T02
TN
THERM.
HEAT
31
T01
F1
UI1
34
35
GND
ELECTR.
REHEATER
36
UI237UI3
10
11
RO4
IN4
RIN NN FIN
38
GND
12RN13
RN
UI4
IN1
39
15
14
RO1
3-SPEED
17
16
RO218IN319RO3
IN2
FAN
40
C1+41C1-42GND
87 65 43 2 1
RJ45 INTERFACE
2,3, 5,6
7 8
4
N NL L
LINE VOLTAGE
Fig. 10. RS5N example wiring (24-V model)
2425 26 2728 29 30 31 32
END
BIAS
MID
RS232
RS485-1
n.a.
n.a.
n.a.
485-1-
485-2-
485-1+
485-2+
GND1
BACnet MS/TP
GND2
J1 J8
EAGLEHAWK NX
24V~
24V-0
1
2
BACnet MS/TP
40
C1+41C1-42GND
87 6543
21
RJ45 INTERFACE
2,3, 5,6
7 8
4
CLCMTR40x/TR42x
WALL MOD ULE
22
°C
20
WM121WM2
26
AO1
24V~
GND
PROPORT.
DAMPER
ACTUATOR
27
GND
24V~
28
0...10V
29
AO230AO3
31
24V~
32
GND
CLCM2T WALL MODULE
1
TEMP2SETP
34
33
AO4
UI1
35
GND
3
COM
OCCUPANCY CONTACT
36
UI237UI3
Niagara
workbench
39
38
UI4
GND
3
24V~
24V0
4
NL
7
5
6
8TN9
T01
TN
T~
THERM.
COOL
T02
THERM.
HEAT
LI NE V OLTAG E
F1
24V0
24V~
N L
LINE VOLTAGE
Fig. 11. RS5N example wiring (24-V model) (with actuator powered by extra transformer)
EN1Z-1035GE51 R0319 8
ELECTR.
REHEATER
10
RO411IN4
14
12RN13
IN115RO116IN217RO218IN319RO3
RN
3-SPEED
FAN
MERLIN NX ROOM CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
*OPTIONAL FUSE (TO PROTECT CONTROLLER‘S INTERNAL TRANSFORMER, WHICH HAS ONLY A NON-RESETTABLE FUSE).
CLCMTR40x/TR42x
WAL L MOD ULE
22
30
WM131WM2
1L2
230 V
PROP.
PROP.
COOL
°C
N
NL
HEAT
32
34
AO1
AO236AO338AO440AO542AO6
35
24V~
5
24V~624V0
OUTPUT
37
GND
24VAC
33
GND
39
41
GND
24V~
7
8T~9
TN
N TIN RIN NN FIN
F1*
Fig. 12. RL4N (230-V model) example wiring
24V~
CLCMTR40x/TR42x
WALL MODULE
22
°C
30
WM131WM2
PROPORT.
DAMPER
GND
ACTUATOR
32
34
AO1
AO236AO338AO440AO542AO6
33
GND
35
24V~
37
GND
0...10V
39
24V~
CLCM4T,5T,6T111 WALL MODULE
1
2
3
4
BYP
5
LED
ELECTR.
REHEATER
43
24V~
T01
THERM.
HEAT
41
GND
COM
44
24V~
10TN11
T0212T03
LED
SETP
TEMP
46
GND48UI250UI352GND54UI656UI758GND60UI10
47
45
UI149GND51UI453UI5
13TN14
T04
FLOATING
COOL
CLCM4T,5T,6T111 WALL MODULE
1
2
TEMP3SETP4BYP
COM
44
46
GND48UI250UI352GND54UI656UI758GND60UI10
24V~
43
24V~
47
45
UI149GND51UI453UI5
LED
7
6
NC
NC
Pt1000
55
GND57UI8
16
17
RO4
18RN19RN20
IN4
L L
N N
LINE VOLTAGE
6NC7
LED
5
NC
55
GND57UI8
Niagara
workbench
OCC. CONTACT
59
UI961GND
IN1
OCC. CONTACT
Pt1000
59
UI961GND
21
22
RO1
IN2
Niagara
workbench
BACnet WiFi
BACnet MS/TP
62
C1+63C1-64GND
23
RO224IN325RO3
3-SPEED
FAN
BACnet MS/TP
62
C1+63C1-64GND
ADAPTER
RJ45 PLUG
87 6543 21
RJ45 INTERFACE
7 8
BACnet WiFi
ADAPTER
RJ45 INTERFACE
7 8
RJ45 PLUG
87 6543
2,3, 5,6
4
21
2,3, 5,6
4
1L2
N
NL
5
24V~624V0
7
9
T01
THERM.
HEAT
10 TN
11
T0212T03
8
TN
T~
13
TN
FLOATING
COOL
T04
14
ELECTR.
REHEATER
16
RO4
IN4
21
18RN19
20
IN1
RN
17
RO1
23
22
RO224IN325RO3
IN2
3-SPEED
FAN
230 V
F1
24V~24V0
N L
LINE VOLTAGE
Fig. 13. RL4N (230-V model) example wiring (with actuator powered by extra transformer)
9 EN1Z-1035GE51 R0319
MERLIN NX ROOM CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
CLCMTR40x/TR42x
WALL MODULE
22
°C
30
WM131WM2
1L2
N
NL
230 V
CLCMTR40x/TR42x
WALL MODULE
22
°C
30
WM131WM2
PROP.
PROP.
COOL
HEAT
32
34
AO1
AO236AO338AO440AO542AO6
35
33
GND
PROP.
PROP.
COOL
HEAT
32
34
AO1
AO236AO338AO440AO542AO6
33
GND
24V~
24V~624V0
35
24V~
5
37
GND
37
GND
CLCM4T,5T,6T111 WALL MODULE
6NC7
1
2
TEMP3SETP4BYP
COM
46
GND48UI250UI352GND54UI656UI758GND60UI10
39
24V~
43
41
GND
24V~
7
9
8
TN
N TIN RIN NN FIN
10
T01
T~
TN
THERM.
HEAT
47
UI149GND51UI453UI5
11
T0212T03
13 TN
FLOATING
COOL
14
T04
F1
5
LED
ELECTR.
REHEATER
NC
55
GND57UI8
16
17
RO4
IN4
LINE VOLTAGE
Fig. 14. RL4N (230-V model) example wiring
CLCM4T,5T,6T111 WALL MODULE
6NC7
LED
5
NC
55
GND57UI8
39
24V~
41
GND
43
24V~
1
2
TEMP3SETP4BYP
COM
46
GND48UI250UI352GND54UI656UI758GND60UI10
47
UI149GND51UI453UI5
Pt1000
18RN19
RN
N NL L
Pt1000
Niagara
workbench
OCC. CONTACT
59
UI961GND
21
20
22
RO1
IN1
IN2
Niagara
workbench
OCC. CONTACT
59
UI961GND
BACnet WiFi
BACnet MS/TP
62
C1+63C1-64GND
23
RO224IN325RO3
3-SPEED
FAN
BACnet WiFi
BACnet MS/TP
62
C1+63C1-64GND
ADAPTER
87 65 43 2 1
RJ45 INTERFACE
7 8
ADAPTER
87 65 43 2 1
RJ45 INTERFACE
7 8
RJ45
PLUG
RJ45
PLUG
2,3, 5,6
4
2,3, 5,6
4
5
4
3
24V0
24V~
NL
LI NE VOLTA GE
24V~
6
7
9
T01
THERM.
HEAT
10
TN
11
T0212T03
13 TN
FLOATING
COOL
8
TN
24V0
T~
N TIN RIN NN FIN
F1
Fig. 15. RL6N (24-V model) example wiring
EN1Z-1035GE51 R0319 10
14
T04
ELECTR.
REHEATER
16
17
IN4
18RN19
RN
N NL L
RO4
LINE VOLTAGE
IN1
21
RO1
23
22
RO224IN325RO3
IN2
3-SPEED
FAN
20
MERLIN NX ROOM CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
POWER SUPPLY
General Information
CAUTION
To prevent a risk of injury due to electrical shock and/or damage to device due to short-circuiting, low­voltage and high-voltage lines must be kept physically separate from one another. Further, to prevent a risk of short-circuiting and damage to your unit, do not reverse the polarity of the power connection cables, and avoid ground loops (i.e., avoid connecting one field device to several controllers).
NOTE: All wiring must comply with applicable electrical
NOTE: To comply with CE requirements, devices having a
Wiring
230-VAC Models
The 230-VAC models are powered via an orange fixed screw­type terminal block (terminals 1+2). See also Fig. 16. These terminals support 1 x 4 mm
24-VAC Terminals for Auxiliary or Field Devices
All 24-VAC auxiliary power supply terminals support 1 x 2.5 mm
24-VAC Models
The 24-VAC models are powered via a black removable terminal plug (terminals 3+4), thus allowing daisy chain wiring
codes and ordinances. Refer to job or manu­facturers’ drawings for details. Local wiring guide­lines (e.g., IEC 364-6-61 or VDE 0100) may take precedence over recommendations provided in these installation instructions.
voltage of 50...1000 VAC or 75...1500 Vdc but lacking a supply cord, plug, or other means for disconnecting from the power supply must have the means of disconnection (with a contact separation of at least 3 mm at all poles) incorporated in the fixed wiring.
2
or 2 x 2.5 mm2 wiring.
230-VAC MODEL #1 230-VAC MODEL #2
1
2
L
N
230 VAC
(-15% / +10%),
50 / 60 Hz
1
2
L
N
NL
Fig. 16. Multiple 230-VAC models connected to single
power supply
2
or 2 x 1.5 mm2 wiring.
of the power supply. See also Fig. 17. These terminals support 1 x 2.5 mm
24-VAC MODEL #1 24-VAC MODEL #2
3
24V~
24 VAC
(+/-20%)
2
or 2 x 1.5 mm2 wiring.
4
24V0
120 VAC
230 VAC
(-15% / +10%),
50 / 60 Hz
or
3
24V0
24V~
CAUTION
!
ALWAYS CONN ECT TERM. 4 (24VAC0) OF EVERY 24-VAC MODEL TO TERM. OF EVERY OTHER 24-VAC
.
MODEL FAILURE TO COMPLY WILL RESULT IN SHORT-CIRCUITING!
4
4 (24VAC0)
NL
Fig. 17. Multiple 24-VAC models connected to single
power supply
Communication / Signal Terminals
All other (i.e.: communication / signal) terminals (except for the Sylk Bus – see Table 12) support 1 x 2.5 mm
2
mm
wiring. Two wires with a total thickness of 2.5 mm2 (14 AWG) can be twisted together and connected using a wire nut (include a pigtail with this wire group and attach the pigtail to the individual terminal block). Deviations from this rule can result in improper electrical contact. Local wiring codes may take precedence over this recommendation.
2
or 2 x 1.5
Electrical Data
RL2N, RL8N, RS4N (230 VAC)
Power via terminals 1 + 2: 230 VAC +10% / -15%, 50/60 Hz. Max. power consumption (when unloaded): 8 W. Max. power consumption (when loaded): 18 W. The controller is "unloaded" when it has no external load.
Thus, the only load on the controller is the inherent load (8 W) of the electronics, themselves. The heat dissipation then amounts to 8 W. The controller is "loaded" when – besides the inherent load – an additional sum load resulting from max. 300 mA (irrespective as to whether it is supplied by the con­troller's internal transformer or by an external source) is applied to the 24 VAC output terminals. The max. unloaded output voltage at terminals 3 and 4 (RSxN) or terminals 5 and 6 (RLxN), respectively, is 33 VAC (typically: 29.5 VAC).
RL6N, RS5N (24 VAC)
Power via terminals 3+4: 24 VAC 20%, 50/60 Hz. Max. current consumption (when unloaded): 300 mA. Max. current consumption (when loaded): 900 mA. The controller is "loaded" when – besides the inherent load
(300 mA) – an additional sum load resulting from max. 600 mA is applied to the 24 VAC output terminals. The max. unloaded output voltage at terminals 3 and 4 (RSxN) or terminals 5 and 6 (RLxN) is identical with the output voltage of the external supplying transformer.
11 EN1Z-1035GE51 R0319
MERLIN NX ROOM CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
FREELY PROGRAMMABLE APPLICATIONS
All models can be used with freely programmable appli­cations. The application engineer performs this task on a PC on which Niagara has been installed (see also corresponding Technical Literature listed in Table 15 on pg. 23).
Supported Actuators
The application supports a variety of actuators.
• Analog 0(2)…10 V
• Floating
• PWM
• Staged actuators
• 6-way valve actuators
Supported Sensors
A variety of sensors (e.g., room temperature sensors, supply temperature sensors, condensation switch, window sensors, occupancy sensors, card readers, etc.) may be used to optimize control quality.
Applications
Applications requiring a fast (20 ms) reaction time can be implemented as event-based applications.
Blinds Function Block
The sunblinds may be used to control different devices:
• Blinds: Height and slat angle.
• Shutter: Height.
• Motorized drapes: Horizontal position of drape.
• Motorized windows: Window position.
Blinds
CurrentPosition
CurrentAngle
MovementStatus
Cause
EmergencyCmd
EmergencyPosition EmergencyAngle Cause
ManualOverrideCmd
ManualOverridePosition ManualOverrideAngle
ApplicationCmd
ApplicationPosition ApplicationAngle ApplicationCause
Other useful inputs for special cases
Device Type, Hw Terminals, Runtimes,
Fig. 18. Blinds function block
(highest prio)
(lowest prio)
--Parameters--
SlatSteps, LockTime, ...
M
Last wins
with wired
push buttons
Manual Blinds Positioning
The blinds can be positioned manually using directly-wired pushbutton inputs or by manual override commands con­nected as input to the function block as programmed in the Niagara wire sheet (e.g., manual commands received via BACnet MS/TP). In the event of a conflict, i.e., when com­mands are issued both by pushbutton and via BACnet MS/TP, the last command received has priority and will thus position the blinds.
Manual Blinds Positioning by Pushbutton
• Short press UP: Opens the slat angle by a configurable slat angle segment.
• Long press UP: Drives the blinds to the UP position. Movement may be stopped by briefly pressing any blinds pushbutton.
• Short press DOWN: Closes the slat angle by a con­figurable slat angle segment.
• Long press DOWN: Drives the blinds to the DOWN posi­tion. Movement may be stopped by briefly pressing any blinds pushbutton.
• Example:
- Configuration: Slat angle fully open = 80°, slat angle
fully closed = -80°, 4 slat angle steps (move the blinds by 40° per step)
- The slat angle is in the fully open position. The room
occupant positions the slats horizontally with two short press signals. This is far more accurate than watching the slats and releasing the pushbutton once the slats appear to have reached the proper angle.
Application Commands
Energy optimization per EN15232 or special behavior of the blinds can be achieved via the application input. The appli­cation engineer can create customer-specific applications to drive the blinds to the optimal position based on daylight level, occupancy, heat/cool demand in the room, etc. The appli­cation engineer may, e.g., create an application which drives the blinds DOWN if the sun shines into the room and there is a cooling demand for the room.
Application commands may be used by the supervisory station or the primary plant controller to, e.g., drive all of the blinds UP during the night.
The application engineer can program scenes for light, blinds, and HVAC.
NOTE: The application engineer has the option of blocking
application commands for a configurable time after the blinds have been manually set.
Emergency Command
The blinds function block has an emergency input which has the highest priority. Application commands and manual commands are blocked in case of an emergency command. The emergency input is used, e.g., in case of strong wind, fire, open window, or during window cleaning to block the blinds, e.g., in the upper position.
Feedback Information from the Blinds Function Block
The blinds provide a feedback for the position of the blind. In addition, they provide a cause for the actual position. The
EN1Z-1035GE51 R0319 12
MERLIN NX ROOM CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
"cause" information is of considerable assistance to the application engineer in clearly understanding the cause for the blinds' position (e.g., movement stopped due to open window).
Commissioning Parameters
• Device type, e.g. blinds, shutter, drape…
• Time to open the blinds.
• Time to close the blinds.
• Slat angle fully open.
• Slat angle fully closed.
• Slat time to close.
• Slat time to open.
• Slat angle position steps.
• Lock time after manual command.
• Assignment of two outputs (relay or triac) per set of blinds. It is recommended to use coupling relays in case triac outputs are used for sunblinds positioning.
• Assignment of two inputs per set of blinds for pushbutton UP/DOWN connection.
Time Delays for Motor Protection
• Direction change: 600 msec pause.
• Same direction: 300 msec pause for reactivation of the motor.
• Minimum switch-on time: 50 msec.
General Remark regarding Parallel Positioning of Blinds for a Building Facade
The position of the blinds is calculated based on runtimes for UP/DOWN and slat angle open/close. There is no position sensor and the runtimes may change over time as the blinds become dirty, etc. It is therefore not possible to exactly position all blinds at the same height and slat angle.
Hardware Recommendation
The RL8N is the preferred hardware model for light and blinds control. Special features of RL8N:
• Dimming of lights via 1…10V output requires that the analog output be able to operate as a current sink (-/+ 1mA on AO3 and AO4).
• High inrush current (80A inrush current and 10 A con­tinuous current on relay 1 and 4) for capacitive loads like LED lighting.
• Increased reliability for dry inputs (24V pull-up voltage for UI1 …4).
Light Function Block
The light function block supports different types of lights:
• ON/OFF light.
• Light dimming.
• Light ON/OFF with timer.
• Light ON/OFF with timer with dimming function.
• Stair case lighting.
• Pushbutton used to switch ON a light. A timer is started and the light is switched OFF once the configurable time is over.
• Staircase lighting with dimming function.
Light
OutManualAddressedCmdBits
EmergencyCmd
EmergencyCause
MotionBrightnessSensor
- Light ON if Occ and Dark
- Light ON and restart AutoOffTimer if Occ a nd Dark
- Light OFF if Unocc or Bright
- If Occ, do not switch OFF even if AutoOffTimer has expired
- If Occ, ignore ApplicationCmd to switch OFF (i.e., do not switch OFF at 7:00 p.m.)
ManualOverrideCmd
ManualAddressedCmdBits
Last wins with wired push buttons
ApplicationCmd
ApplicationCause
Other useful inputs for special cases
MaxOutputs, DimmingSpeed, LockTime, ...
--Parameters--
LightControlType, Hw Terminals, Min/
1 x BI 2 x BI
Fig. 19. Light function block
Manual Light ON / OFF / Dim
The light can be switched ON/OFF or dimmed manually using directly-wired pushbutton inputs or by manual override com­mands connected as input to the function block as programmed in the Niagara wire sheet (e.g., manual com­mands received via BACnet MS/TP). In the event of a conflict, i.e., when commands are issued both by pushbutton and via BACnet MS/TP, the last command received has priority and will thus set the light.
Manual Light ON / OFF / Dim by Pushbutton
• The light can be controlled using one or two pushbuttons.
• Control using two pushbuttons:
- Short press UP: Light is switched ON.
- Long press UP: Light intensity is increased. Releasing the pushbutton stops the brightness change.
- Short press DOWN: Light is switched OFF.
- Long press DOWN: Light intensity is decreased. Releasing the pushbutton stops the brightness change.
• Control using one pushbutton:
- Short press: Toggles the light ON/OFF.
- Long press: Starts the dimming process. Increasing / decreasing the light level is toggled with every push­button press. Releasing the pushbutton stops the brightness change. Example: The light level is being increased by means of a long press. If you now instead wish to decrease the light level, release the pushbutton and perform another long press.
- It is possible to configure the pushbutton such that only light ON / light increase or light OFF / light decrease using the pushbutton is supported. Switching
OutFeedback
(highest prio)
Last wins with
wired push buttons
(lowest prio)
1 x BO - 1 x AO
OutCause
RAM
RAM
13 EN1Z-1035GE51 R0319
MERLIN NX ROOM CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
OFF can be done automatically with a configurable delay.
Application Commands
Energy optimization per EN15232 or special behavior of the light can be achieved via the application input. The application engineer can create customer-specific applications to, e.g., switch the light OFF if the daylight level reaches a con­figurable level.
The application engineer can program scenes for light, blinds, and HVAC.
Application commands may be used by the supervisory station or the primary plant controller to, e.g., switch OFF all lights during the night.
NOTE: The application engineer has the option of blocking
application commands for a configurable time after the light has been manually set.
Manual Address Command Bit Input
This input is used if the light is controlled by a manual command coming from another light function block. This functionality is used for grouping, e.g., using one pushbutton to switch ON/OFF all lights in a room.
Motion and/or Brightness Sensor
This input is used to connect a motion detector including a brightness sensor.
The input can be configured for:
• Light ON if occupancy detected on dark.
• Light ON and AutoOffTimer restarted if occupancy detected and the room is dark.
• Light OFF if the room is unoccupied or the room is bright.
• Do not switch the light OFF if the automatic OFF timer has expired and occupancy is detected.
• Do not switch the light OFF if the application wants to switch the light OFF but the room is still occupied.
Emergency Command
The light function block has an emergency input which has the highest priority. Application commands and manual commands are blocked in case of an emergency command. The emergency input is used, e.g., in case of fire to switch ON all lights permanently or it can be used to switch OFF certain light groups in case the building is running in generator mode.
Feedback Information from the Light Function Block
The light provides a feedback for the light level. In addition, it provides a cause for the actual light level. The "cause" information is of considerable assistance to the application engineer in clearly understanding the cause for the light level (e.g., light switched ON due to emergency or for lamp test).
The light function block can be configured to command other light function blocks. This is used for grouping of lights.
Commissioning Parameters
• Light type, e.g. ON/OFF, dimming, staircase, etc.
• Assignment of switching outputs (relay or triac). It is recommended to use coupling relays if triac outputs are
used for lighting. Please observe the relays' constant current and inrush current limitations. Coupling relays may be used if the internal relays cannot support the required current.
• Assignment of analog outputs for light dimming via 1…10V. NOTE: Only AO3 and AO4 of the RL8N support dimming.
• Assignment of inputs for pushbutton connection and one or two pushbutton control.
• Min/max level and speed for dimming.
• Auto OFF time delay.
• Optional switch OFF delay time in case of automatic OFF. The light blinks to inform the room occupant that the light will be switched OFF. The room occupant may manually switch ON the light in this case to avoid automatic switching OFF of the light.
Hardware Recommendation
The RL8N is the preferred hardware model for light and blinds control. Special features of the RL8N:
Dimming of lights via 1…10V output requires that the
analog output can operate as a current sink (-/+ 1mA on AO3 and AO4).
High inrush current (80A inrush current and 10 A
continuous current on relay 1 and 4) for capacitive loads like LED lighting
Increased reliability for dry inputs (24V pull-up
voltage for UI1 …4)
Wiring Example for Lights and Blinds
32
34
AO1
AO236AO338AO440AO542AO6
33
GND
24V~
39
35
37
GND
24V~
LIGHT DIM
GND
43
41
24V~
16
RO417IN418RN19RN20IN121RO122IN223RO224IN325RO3
LIGHT ON/OFFLIGHT GND
NL
LINE VOLTAGE
BLINDS UP
BLINDS NEUTRAL
BLINDS DOWNLIGHT NEUTRAL
SUNBLINDS
Fig. 20. Wiring example for lights and blinds (RL8N)
COMMISSIONING
Automatic MAC Addressing
In contrast to other MS/TP controllers, the RxxN Controller features automatic MAC addressing.
The MAC addresses which the individual RxxN controllers on the BACnet MS/TP bus assign to themselves are not assigned in sequential order.
They assign those numbers (MAC ID) between 1…62 currently not in use by another device on the BACnet MS/TP bus. All RxxN controllers are BACnet MS/TP masters. Every master performs periodic polling for the possible appearance of new masters. Each master "knows" the identity of the "next" master (i.e., that RxxN controller with the next-highest MAC ID) on the BACnet MS/TP bus and to which it must therefore pass the token. The polling process includes a search for new masters which might have MAC addresses lying between its own MAC address and that of the "next" master. The value of the property Max Master specifies the highest-allowable address for master nodes. Max Master is
EN1Z-1035GE51 R0319 14
MERLIN NX ROOM CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
set to 35 by default, thus guaranteeing that, on a BACnet MS/TP bus with, e.g., 62 RxxN controllers, all of the other RxxN controllers will be found. Both the property Max Master and the property MAC ID are writeable properties that can be changed. Specifically: "MAC ID" can be changed using Niagara, while "Max Master" can be changed using Niagara or any other BACnet-compatible engineering tools, e.g., with BACShark.
NOTE: It is not possible to configure a MAC ID outside the
range of 1…62.
BACnet MS/TP
PLANT
CONTROLLER
LEGEND:
NON-RxxN CONTROLLER (WITH MANUAL MAC ADDRESSING)
RxxN (WITH AUTOMATIC MAC ADDRESSING)
#1 #2 #60 #62 #61
Fig. 21. Automatic MAC addressing (scenario "A")
In scenario "A", 29 controllers with manually-assigned MAC addresses (#1, #2, #3…#59, #60, #62 – MAC address #61 has thus been deliberately skipped) are already up and running on the BACnet MS/TP bus. A single additional RxxN is then connected to the bus and powered on.
RESULT: The RxxN Controller requires approx. 28-31 sec to automatically assign itself a compatible MAC address (#61), and to complete various other firmware tasks before becoming fully operational.
Scenario "A" and additional scenarios ("B" through "F") are described in Table 7 below.
Table 7. Possible Auto MAC addressing scenarios
scenario time remarks
A: RxxN start-up time on single BACnet MS/TP bus after power-on (cold boot or reset).
B: Average start-up time for all RxxN controllers on single BACnet MS/TP bus.
C: Time to recognize con­flicting MAC address of added non-RxxN controller.
D: Time to recognize con­flicting MAC address of added non-RxxN controller while auto MAC still in progress.
E: Time for auto MAC when additional RxxN controllers are added in stages while auto MAC still in progress.
F: Time for restart of RxxN controllers and verification of auto MAC addresses after power-down.
28-31 sec
1 min. and 34 sec
21 sec
50 sec
30 sec
17 sec
61 non-RxxN controllers (with manual MAC addressing) are running; 1 RxxN is then added and powered on.
Like "A," but with 8 non­RxxN controllers; 54 RxxN controllers are then added and booted.
Like "B," but with 7 non­RxxN controllers and 54 RxxN controllers; an additional non-RxxN con­troller with a conflicting address is then added.
Like "C," but with the addi­tional non-RxxN controller having a conflicting MAC address added while auto MAC still in progress.
Like "B," but with RxxN con­trollers added in stages.
8 non-RxxN controllers and 54 RxxN controllers are running; then power-down and restart.
OPERATOR INTERFACES
LEDs
The controller features the following LEDs:
T2 R2 T1 R1
Fig. 22. Controller LEDs
Table 8. Description of LED behaviors
symbol color function, description
T2 yellow Not used
R2 yellow Not used
T1 yellow
R1 yellow
!
yellow
green
LED indicating transmission of communication signals via the BACnet MS/TP interface.
LED indicating reception of communication signals via the BACnet MS/TP interface.
Status LED indicating firmware problems, hardware problems, etc. (see Table 9).
Power LED indicating firmware problems, hardware problems, etc. (see Table 9).
Table 9. Status LED and power LED behaviors
# Mode Power LED (green)
1 Power failure Stays OFF Stays OFF
2 Device error* Stays ON Stays ON
3 No application ON/OFF (0.5 Hz) ON/OFF (0.25 Hz)
4 Broken sensor ON/OFF (0.25 Hz) Stays ON
5 Short-circuiting ON/OFF (0.5 Hz) Stays ON
6 Auto-MAC ON/OFF (1 Hz) ON/OFF (0.5 Hz)
Unacknowledged
8
alarm
9 Normal operation ON/OFF (0.5 Hz) Stays OFF
ON/OFF (2 Hz) ON/OFF (2 Hz)
*Please return the controller for repair.
Service Button
The Service Button is used to trigger dedicated events.
Table 10. Use of controller's Service Button
action result
Button pressed 0.01 to 2 sec. while controller running
Button pressed > 10 sec. while controller powering up
Button pressed 0.01 to 5 sec. while controller powering up
!
Status LED
(yellow)
Service Pin (UID) broadcast on the BACnet MS/TP bus.
Password is reset.
Auto MAC addressing procedure reinitiated.
15 EN1Z-1035GE51 R0319
MERLIN NX ROOM CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
A
COMMUNICATION INTERFACES
BACnet MS/TP Interface
The controller features an RS485 interface (RLxN: terminals 62, 63, and 64; RSxN: terminals 40, 41, and 42) suitable for BACnet MS/TP communication. The terminal block containing it is black. The cable length affects the baud rate. See Table
11.
Table 11. Baud rate vs. max. cable length
baud rate max. cable length (L)
9.6, 19.2, 38.4, 57.6, and 76.8 kbps 1200 m
115.2 kbps 800 m
For information on wire gauge, max. permissible cable length, possible shielding and grounding requirements, and the max. number of devices which can be connected to a bus, refer to standard EIA-485.
Connecting to BACnet MS/TP Buses
The controller communicates via its BACnet MS/TP interface with other BACnet MS/TP-capable devices (e.g., other room controllers or plant controllers like the EAGLE / Excel Web II). In doing so, the following considerations should be taken into account.
▪ Max. BACnet MS/TP bus length (L): See Table 11. ▪ Twisted-pair cable, e.g.:
- AWG 18;
- J-Y-(St)-Y 2 x 2 x 0,8;
- CAT 5,6,7 cable – use only one single pair for one bus;
- Belden 9842 or 9842NH);
and daisy-chain topology. ▪ Must conform to EIA-RS485 cabling guidelines and
ANSI/ASHRAE Standard 135-2010.
▪ Max. no. of BACnet MS/TP devices (including the Master)
per BACnet MS/TP channel: 31 (= "N" in Fig. 23).
L
NOTE 1
25 26 62 63 64
24
END
BI
MID
S
EAGLE / Excel Web II
PLANT CONTROLLER
BACnet MS/TP
DEVICE #1 (MASTER)
40
END
C1+
CLME-RSxN CLME-RLxN
BACnet MS/TP
DEVICE #2
41 42
C1-
GND
C1-
C1+
BACnet MS/TP
DEVICE #3
GND
RS485 -
RS485 +
BACnet MS/TP
DEVICE #4
GND
Fig. 23. Connection to a BACnet MS/TP Bus
NOTE 1: If any of the devices are electrically isolated, it is
recommended that those devices be connected to signal ground.
NOTE 2: The 120-Ohm termination resistor must be inserted
directly into the terminals of the final BACnet MS/TP device.
TWISTED PAIR
120
RS485 -
RS485 +
BACnet MS/TP
DEVICE #N
GND
NOTE 3: If shielding is used, the shielding of each individual
bus segment should be separately connected at one end to earth.
RJ45 Connector for BACnet WiFi Adapter
A BACnet WiFi Adapter can be connected to the controller's RJ45 connector in order to establish wireless communication with a PC with Niagara so that the application engineer can commission the controller.
NOTE: When the BACnet WiFi Adapter is connected to the
controller's RJ45 connection, it is powered by the controller. It is then prohibited to simultaneously power the BACnet WiFi Adapter via a wall adapter. When, on the other hand, the BACnet WiFi Adapter is instead connected to the controller's BACnet MS/TP interface, it is prohibited to simultaneously use an RJ45 plug; instead, the BACnet WiFi Adapter must then be powered by a wall adapter (standard 5­V USB wall adapter with micro USB connector).
See also corresponding Technical Literature listed in Table 15 on pg. 23.
BACnet WiFi
Niagara
ADAPTER
workbench
RJ45
PLUG
CLME-RLxN (CLME-RSxN)
BACnet MS/TP
62
(40)
C1+
INTERNAL
CONNECTIONS
(41)
C1-
63
64
(42)
GND
RJ45 CONNECTOR
8 7654 32 1
2,3,
5,6
7 8
4
1 = DETECT 2 = GND 3 = GND 4 = 24VAC 5 = GND 6 = GND 7 = C1+ 8 = C1-
Fig. 24. RJ45 interface and BACnet WiFi Adapter
CAUTION
It is permitted to connect only the BACnet WiFi Adapter to this RJ45 connector. Do not connect IP!
Sylk Bus
Sylk Bus-capable devices (e.g., the CLCMTR40x/T42x) can be connected to the controller's Sylk Interface (RSxN: ter­minals 20 and 21; RLxN: terminals 30 and 31). Specifically:
▪ A max. of one wall module can be connected. ▪ The Sylk Bus is single pair, and polarity-insensitive. ▪ Max. current provided at the Sylk Bus interface: 96 mA.
EN1Z-1035GE51 R0319 16
MERLIN NX ROOM CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
Table 12. Recommended max. distances from controller
to CLCMTR40x/T42x wall modules
single twisted pair, non-
no.
shielded, stranded or solidA)
0.33…0.82 mm2 (18…22 AWG)
2
A)
As a rule of thumb, single twisted pair (two wires per cable, only), thicker gauge, non-shielded cable yields the best results for longer runs.
B)
The 30 m (100 ft) distance for standard thermostat wire is con­servative, but is meant to reduce the impact of any sources of electrical noise (incl. but not limited to VFDs, electronic ballasts, etc.). Shielded cable recommended only if there is a need to reduce the effect of electrical noise.
C)
These distances apply also for shielded twisted pair.
150 m
(500 ft)
0.20 mm2
(24 AWG)
120 m
(400 ft)
standard non-twisted
thermostat wire, shielded or
non-shielded, stranded or
B), C)
solid
0.20…0.82 mm2 (18…24 AWG)
30 m (100 ft)
I/O TERMINALS
CAUTION
Failure to observe the following max. permissible current outputs of the power output terminals will result in damage to the device.
Max. Current Output of Power Output Terminals of 230 VAC Controllers
The 24 VAC power output terminals of the 230 VAC RLxN controllers are terminals 5, 6, 35, 39, 43, and 44 plus pin 4 of the controller's RJ45 interface. Two of these terminals (typically: 5 and 6) will be used to supply the triacs.
The 24 VAC power output terminals of the 230 VAC RSxN controllers are terminals 3, 4, 27, and 31 plus pin 4 of the controller's RJ45 interface. Two of these terminals (typically: 3 and 4) will be used to supply the triacs.
Regardless of whether the triacs are supplied by the con­troller's internal transformer or by an external source, the max. permissible combined current output of the afore­mentioned 24 VAC power output terminals is 300 mA (or 320 mA for max. 2 minutes).
Consequently, if only those two 24 VAC power output ter­minals used to supply the triacs already have the max. per­missible combined current output of 300 mA (or 320 mA for max. 2 minutes), then the current output of the remaining 24 VAC power output terminals must, of course, equal zero.
Max. Current Output of Power Output Terminals of 24 VAC Controllers
The 24 VAC power output terminals of the 24 VAC RLxN con­trollers are terminals 5, 6, 35, 39, 43, and 44 plus pin 4 of the controller's RJ45 interface.
The 24 VAC power output terminals of the 24 VAC RSxN con­trollers are terminals 3, 4, 22, 23, 24, 25, 27, and 31 plus pin 4 of the controller's RJ45 interface.
The max. permissible combined current output of these 24 VAC power output terminals is 300 mA.
Relay Outputs
CAUTION
Mixing of different voltages (e.g., 24 V and 230 V) within the relay block is not allowed.
The terminal blocks containing the controller's relay outputs are orange. Relay output types: See Table 3.
NOTE: If inductive components are to be connected to the
relays and if these relays switch more often than once every two minutes, these components must be prevented from causing harmful interference to radio or television reception (conformance with EN 45014).
Relay Current Limitations
If the triacs are supplied with current from an external source, then a maximum of two relays may be loaded with a max. of 4 A per relay – even if two triacs are each simultaneously loaded with max. 300 mA.
If the triacs are supplied with current from an internal source, a maximum of two relays may be loaded as follows: a max. load of 4 A for a relay serving a fan and a max. load of 10 A for a relay serving a reheat – even if one triac is simul­taneously loaded with 300 mA.
Triac Outputs
NOTE: Recommended fuse (F1): 1.25 A time-lag fuse (IEC).
User must consider the correct voltage and max. breaking capacity / interrupting rate (line voltage urgently requires high breaking capacity / interrupting rate).
The terminal blocks containing the controller's triac outputs are orange.
These triac outputs can be used for a variety of different functions, e.g., for connection to either a floating drive or to a thermal actuator. Once the triac outputs have been programmed, the corresponding devices can then be connected to them directly.
NOTE: The VC6983 actuator is intended for use at relay
outputs, only and must not be used at the controller's triac outputs.
Triac Current Limitations
The max. allowed current with which the ensemble of a con­troller's triacs may be loaded is dependent upon whether the given model is powered with 24 VAC or with 230 VAC (and, in the case of models powered with 230 VAC, upon whether the outputs are supplied by the controller's internal transformer or by an external current supply). Specifically:
▪ In the case of 24 VAC models, the ensemble of a con-
troller's triacs may be loaded with 600 mA.
▪ In the case of the 230 VAC models, if the triacs are
supplied with 24 VAC current by the controller's internal transformer, the ensemble of a controller's triacs may be loaded with 300 mA (or 320 mA for a max. of 2 minutes); when supplied by an external source, this value is doubled.
However, regardless of whether the triacs are supplied internally or externally, a single triac must never be loaded
17 EN1Z-1035GE51 R0319
MERLIN NX ROOM CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
with a current of more than 300 mA (320 mA for max. 2 minutes).
Nevertheless, the ensemble of triacs can be loaded for very short periods of time (on the order of milliseconds) with a current on the order of 2500 mA typically encountered when switching on multiple thermal actuators.
Universal Inputs
The terminal blocks containing the controller's universal inputs are blue. Universal input types: See Table 4.
The universal inputs are protected against voltages of max. 29 VAC and 30 VDC (due to, e.g., miswiring).
Bias Resistors
Each universal input is equipped with one bias resistor. See Fig. 25.
SENSOR
DOWN
UI
S2
ADC
S1
R
BIAS
R
SER
V
UP
GND
R
Fig. 25. Schematic of universal inputs and bias resistors
LEGEND: V
= 10 V (except for UI1-4 of RL8N, which have 24 V).
UP
R
= Bias resistor (with a resistance of 24.9 kΩ in the
R
R
BIAS
SER
DOWN
case of NTC10kΩ andNTC20kΩ sensor inputs, and 7.5 kΩ in the case of Pt1000 sensor inputs); can be switched OFF via software by S1 to support 0…10 V inputs without bias current ("high impedance") – except in the case of UI1-4 of RL8N, which have a resistance of 11.8 kΩ and cannot be switched OFF.
= Series resistor for voltage dividing and filtering
(with a resistance of 150 kΩ).
= An internal load resistor (with a resistance of
49 kΩ); depending upon the given type of con­nected sensor, the firmware may switch this resistor OFF.
Analog Outputs
The terminal blocks containing the controller's analog outputs are green. Analog output types: See Table 5.
The analog outputs of the RLxN controllers (large housing) are protected against voltages of max. 29 VAC and 30 VDC (due to, e.g., miswiring).
NOTE: Connecting 24 VAC to any analog output of the
RSxN controller (small housing) will damage the hardware.
Free I/O Option
The limitations – including model-dependent limitations – set forth in Table 2, Table 3, Table 4, Table 5 apply. Further limitations are explained below.
Free Universal Inputs
Max. 5 BACnet Analog Input Objects
Under the free I/O option, a maximum of five of the MERLIN NX controller's unused UIs are available for use as analog inputs by the plant controller. However, they cannot be used for receiving input from NI1000TK5000 sensors.
Max. 5 BACnet Binary Input Objects
Under the free I/O option, a maximum of five of the MERLIN NX Controller's unused UIs are available for use as binary inputs by the plant controller.
Max. 2 BACnet Accumulator Objects
Under the free I/O option, a maximum of two of the MERLIN NX Controller's unused UIs are available for use as accumulators by the plant controller.
These accumulators can have up to 30 Hz (pulse ON ≥ 16 ms; pulse OFF ≥ 16 ms; closed: voltage < 1 V; open: voltage > 5 V).
These accumulators can be used, e.g., for energy meters which create pulses when energy is consumed.
Free Outputs
Max. 4 BACnet Analog Output Objects
Under the free I/O option, a maximum of four of the MERLIN NX Controller's unused outputs (analog or binary outputs) may be used with BACnet Analog Output objects by the plant controller. Possible characteristics are as follows:
▪ analog output: 0(2)..10 V outputs; ▪ floating output: triac or relay outputs; ▪ PWM: triac outputs; ▪ 1-, 2-, 3-stage output: triac / relay outputs.
Max. 4 BACnet Binary Output Objects
Under the free I/O option, a maximum of four of the MERLIN NX Controller's unused relays and triacs are available for use as binary outputs by the plant controller. However, they can be used only as ON / OFF binary outputs.
Example:
The customer wants the plant controller to use some of the I/Os of the CLMERL2N not used by the application as free
EN1Z-1035GE51 R0319 18
MERLIN NX ROOM CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
I/Os, and therefore hardwires the free inputs/outputs as shown in the following example.
Table 13. Use of unused I/Os as free I/Os (example)
Input/output Use as
UI1, 2 0…10V inputs
UI3 NTC20k temperature input
UI4, 5 binary inputs
UI6 counter
AO1 0…10V output
AO2 0…10V output
Triac 1, 2 floating actuator outputs
Triac 3, 4 floating actuator outputs
Relay 1, 2, 3, 4 binary outputs
In the above example, the customer has used the maximum of four analog characteristics.
No further analog characteristic can be assigned; e.g. relays 1, 2 could not be used as multistate outputs.
19 EN1Z-1035GE51 R0319
MERLIN NX ROOM CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
WALL MODULES
The CLCM1T,2T,4T,5T,6T111 and CLCMTR40x/TR42x Wall Modules can be used in conjunction with the controller to per­form room temperature sensing, setpoint adjustment, fan speed manual override, and occupancy override.
NOTE: The CLCMTR42x Wall Module must be version
Further, the LED of the CLCM4T,5T,6T111 and the LCD of the CLCMTR42x can be configured to provide information about:
▪ any override of the controller by, e.g., pressing the
▪ the controller's effective occupancy mode (see section
NOTE: The intended use of the wall module's buttons must
A) Requires one UI supporting NTC.
NOTE: The CLMERL8N has ten UIs, only two of which
See also corresponding Technical Literature listed in Table 15 on pg. 23.
Configuration of Wall Module LED / LCD
The LED of a CLCM4T,5T,6T111 Wall Module can be con­figured (using Niagara) to provide information about, e.g., overrides or effective occupancy modes. The LCD of the CLCMTR42x can likewise be configured to display such information.
CLCM Configured to Display Info on Overrides
The LED of a CLCM4T,5T,6T111 Wall Module connected to the controller can be configured to indicate if an override has been activated because either the wall module's override button has been pressed or the controller has received a BACnet MS/TP network command. Specifically, the following modes are supported:
1.00.3 or higher.
"occupancy" button of the wall module or receipt by the controller of a BACnet MS/TP network command (see section "CLCM Configured to Display Info on Overrides" below);
"CLCM Configured to Display Info on Occupancy" below).
be configured using Niagara.
Table 14. Supported wall module functions
CLCM1T11N
(T7460A1001)
CLCM2T11N
(T7460B1009)
CLCM4T111
(T7460C1007)
CLCM5T111
(T7460E1002)
CLCM6T111
(T7460F1000)
A)
temp.
setpt.
sensor
adjustment
X -- -- -- --
X X -- -- --
X X X -- X
X X X auto-0-1 X
X X X auto-0-
A)
A)
bypass
fanspeed
1-2-3
A)
override
support NTC; this model is thus not suitable for the hardwiring of wall modules requiring three UIs supporting NTC.
LED
X
▪ NO OVERRIDE: If the wall module's LED is OFF, then no
override is currently in effect.
▪ OVERRIDE OCCUPANCY: If the wall module's LED is
ON continuously, then the wall module's override button or a BACnet MS/TP network command has placed the controller into the "occupied" or "override" mode (but if the override button is again pushed or if a cancellation net­work command is received or if the override time expires, the controller will return to its scheduled occupancy mode, and the wall module's LED will behave accordingly).
▪ OVERRIDE HOLIDAY: If the wall module's LED flashes 2
sec OFF and 1 sec ON, then the controller has received a network command and been placed in the "holiday" mode.
▪ OVERRIDE UNOCCUPIED: If the wall module's LED
flashes once per sec, then the wall module's override button or a network command has placed the controller into the "unoccupied" mode (however, if the override button is again pushed or if a cancellation BACnet MS/TP network command is received, the controller will return to its scheduled occupancy mode, and the wall module's LED will behave accordingly).
▪ If the wall module's LED flashes twice per sec, then a
BACnet MS/TP network command has placed the con­troller into either the "standby" or the "occupied" mode.
CLCM Configured to Display Info on Occupancy
The LED of a CLCM4T,5T,6T111 Wall Module connected to the controller can also be configured to indicate the con­troller's effective occupancy mode. Specifically, the following modes are supported:
▪ UNOCCUPIED: If the wall module's LED is OFF, then the
controller is in the "unoccupied" mode.
▪ STANDBY: If the wall module's LED flashes once per sec,
then the controller has received a network command and been placed in the "standby" mode.
▪ OCCUPIED: If the wall module's LED is ON, then the con-
troller is in the "occupied" mode.
▪ BYPASS: If the wall module's LED is ON continuously,
then the controller has received a network command and been placed in the "bypass" mode.
▪ HOLIDAY: If the wall module's LED is OFF, then the con-
troller has received a network command and been placed in the "holiday" mode.
LCD of a TR42x Configured to Display Info on Occupancy
The LCD of a CLCMTR42x connected to the controller can be configured to display various texts and symbols to indicate the effective occupancy mode of the controller. See the following sections "Unoccupied Mode," "Standby Mode," and "Occupied Mode."
EN1Z-1035GE51 R0319 20
MERLIN NX ROOM CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
Unoccupied Mode
CLCMTR42xx CONFIGURED
TO DISPLAY ENGLISH
OFF
FAN
OVERRIDE
OVERRIDE
CANCEL
AUTO
FAN
OVERRIDE
CANCEL OVERRIDE
CANCEL
H/C
AUTO
2.0
OVERRIDE
H/C
AUTO
2.0
CANCEL OVR
DONE
DONE
°C
OVERRIDE
°C
CLCMTR42xx CONFIGURED
TO DISPLAY SYMBOLS
H/C
OFF
AUTO
°C
2.0
H/C
AUTO
AUTO
°C
2.0
Standby Mode
CLCMTR42xx CONFIGURED
TO DISPLAY ENGLISH
CANCEL
AUTO
CANCEL
H/C
OFF
AUTO
2.0
FAN
OVERRIDE
OVERRIDE
H/C
AUTO
2.0
FAN
CANCEL OVR
OVERRIDE
CANCEL OVERRIDE
°C
OVERRIDE
DONE
OVERRIDE
°C
DONE
CLCMTR42xx CONFIGURED
TO DISPLAY SYMBOLS
H/C
OFF
AUTO
°C
2.0
H/C
AUTO
AUTO
°C
2.0
Fig. 26. Example "unoccupied" screens
If
is displayed, the controller is in the "unoccupied"
mode. The user can override the "unoccupied" mode by touching the
upper right softkey. An intermediate screen will then flash for a few seconds, allowing the user to either cancel (upper left softkey) or confirm (upper right softkey). If the user neither cancels nor confirms, this will be considered a confirmation, and the controller will be placed in the "overridden to bypass" mode. If, on the other hand, the user cancels, the controller will revert to the "unoccupied" mode.
Fig. 27. Example "standby" screens
If
is displayed, the controller is in the "standby" mode.
The user can override the "standby" mode by touching the upper right softkey. An intermediate screen will then flash for a few seconds, allowing the user to either cancel (upper left softkey) or confirm (upper right softkey). If the user neither cancels nor confirms, this will be considered a confirmation, and the controller will be placed in the "overridden to bypass" mode. If, on the other hand, the user cancels, the controller will revert to the "standby" mode.
Occupied Mode
CLCMTR42xx CONFIGURED
TO DISPLAY ENGLISH
H/C
OFF OFF
AUTO
°C °C
2.0 2.0
FAN
Fig. 28. Example "occupied" screens
If
is displayed, the controller is in the "occupied" mode.
CLCMTR42xx CONFIGURED
TO DISPLAY SYMBOLS
H/C
AUTO
21 EN1Z-1035GE51 R0319
MERLIN NX ROOM CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
A
A
A
LCD of a TR42x Configured to Display Info on Fan
OFF
If
is displayed, the fan is switched OFF. Depending upon the given application configuration, the effective control mode for underfloor heating, radiator, ceiling heating, and ceiling cooling can then be switched OFF as well.
Configuring the TR42x for Heating / Cooling
With the TR42x, the user can select whether he wants to have:
▪ cooling (
▪ heating (
▪ cooling plus heating (auto) ( By doing so, inadvertent heating or cooling is prevented.
Selecting "auto" results in automatic switching between cooling and heating.
To make these selections, the user must enter the expanded menu (see section below).
Expanded Menu
The user can enter the expanded menu at any time (i.e., in any mode). This is done by touching both upper softkeys simultaneously (see Fig. 29). The "temperature" screen appears first. The user can scroll to further screens ("heating / cooling," "relative humidity," and "CO the left (
NOTE: The user can, at any time, exit the expanded menu
In the expanded menu, the current temperature, relative humidity, and CO
The user can change automatic heating / cooling by scrolling (arrow softkeys) to the "heating / cooling" screen and then touching the upper right softkey, (below the " the word "EDIT"). The actual setting will then flash at 1 Hz for approx. 7 seconds, during which time the user can either cancel the given setting (upper left softkey, below the " symbol or the word "CANCEL") or confirm it (upper right softkey, below the " action is taken within this time, the given setting is auto­matically confirmed.
C
),
), or
H/C
AUTO
).
concentration") using
2
) or right ( ) arrow softkey.
using the upper left softkey (below the "
" symbol or the word "HOME") – or by simply waiting approx. 60 seconds.
concentration can be displayed.
2
" symbol or
"
" symbol or the word "DONE"). If no
CLCMTR42xx CONFIGURED
TO DISPLAY SYMBOLS
H/C
OFF
UTO
°C
2.0
°C
25.5
CTUAL
C
H/C
UTO
41
CO
603
%
%
2
ppm
FLASHES 7 SEC!
C
H/C
AUTO
FLASHES 7 SEC!
C
FLASHES 7 SEC!
C
C
Fig. 29. Accessing the expanded menu
EN1Z-1035GE51 R0319 22
MERLIN NX ROOM CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
TROUBLESHOOTING
All units feature a Service Button, Status LED, Power LED, and two additional LEDs (T1 and R1) for commissioning and troubleshooting. See also Table 8 and Table 9 and section "Service Button".
Check if the Status LED's behavior is changed if you switch the power OFF/ON. Please contact Honeywell if this does not solve the problem.
Further, the test function of Niagara can also be used to carry out general application and wiring checks. Niagara also features a BACnet Object Browser which can prove very helpful in analyzing the controller's function and communication.
ACCESSORIES
Terminal Protection Cover; required for wall mounting. Bulk pack, set of ten covers.
▪ For large controllers, order no.: IRM-RLC ▪ For small controllers, order no.: IRM-RSC
APPROVALS, CERTIFICATIONS, ETC.
Approvals and Certifications
▪ UL 60730-1, Standard for Automatic Electric Controls for
Household and Similar Use, Part 1: General Requirements;
▪ CAN/CSA-E60730-1:02, Standard for Automatic Electrical
Controls for Household and Similar Use, Part 1: General
Requirements; ▪ Complementary listing for UL916, CSA C22.2 No. 205; ▪ BTL-listed, BACnet AAC profile; ▪ SASO-approved; ▪ CE-approved; ▪ FCC part 15B-compliant: This equipment has been tested
and found to comply with the limits for a Class B digital
device, pursuant to part 15 of the FCC Rules. These limits
are designed to provide reasonable protection against
harmful interference in a residential installation. This
equipment generates, uses, and can radiate radio-
frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful
interference to radio communications. However, there is
no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful
interference to radio or television reception, which can be
determined by turning the equipment off and on, the user
is encouraged to try to correct the interference by one or
more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
Classification according to EN 60730-1
EN 60730 sub part: EN 60730-2-9 Environmental conditions: For use in home (residential,
Construction: independently mounted control,
Action: type 1.C Rated impulse voltage: 2500 V at 230 V; 500 V at 24 V Pollution degree: 2 Protection against shock: Class 0 (without terminal covers)
Software class: Class A
commercial, and light-industrial) environments
for panel-mounting
Class II (with terminal covers)
Classification according to EN 60529
(Degree of protection provided by enclosures) IP20. In the case of controllers mounted outside of a cabinet,
before applying power to the device, Terminal Protection Covers (10-pc. bulk packs, order no.: IRM-RLC for large housings and IRM-RSC for small housings) must be mounted so as to provide IP30.
Ambient Environmental Limits
(5…90% r.H., non-condensing)
Operating temperature (floor/ceiling mounting): 0 … +40 °C
Operating temperature (wall/rail mounting): 0 … +50 °C
Storage temperature: -20 … +70 °C
RELATED TECHNICAL LITERATURE
Table 15. Related Technical Literature
Title
CLMERxxN Room Controller – Mount. Instr. MU1Z-1035GE51
CLMERxxN Room Controller – Data Sheet EN0Z-1035GE51
CLMERxxN Room Controller – Inst. & Comm. Instr.
CLCM1T,2T,4T,5T,6T – Product Data EN0Z-0901GE51
CLCM1T,2T,4T,5T,6T – Installation Instructions MU1Z-0901GE51
CLCMTR40x/TR42x – Specification Data EN0Z-0990GE51
Product
Literature no.
EN1Z-1035GE51
23 EN1Z-1035GE51 R0319
MERLIN NX ROOM CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
APPENDIX: SENSOR CHARACTERISTICS
Sensor Input Accuracy
The controller's internal sensor inputs support NTC10kΩ and NTC20kΩ sensors. The following table lists the typical minimum accuracies of the hardware and software for these temperature sensors.
Table 16. Accuracies of internal NTC10kΩ and NTC20kΩ sensor inputs of the Excel Web II
range measurement error (excluding sensor characteristics)
-50 … -20 °C (-58 … -4 °F) ≤ 5.0 K ≤ 5.0 K
-20 … 0 °C (-4 … +32 °F) ≤ 1.0 K ≤ 1.0 K 0 … 30 °C (32 … 86 °F) ≤ 0.5 K ≤ 0.3 K 30 … 70 °C (86 … 158 °F) ≤ 0.5 K ≤ 0.5 K 70 … 100 °C (158 … 212 °F) ≤ 1.0 K ≤ 1.0 K 100 … 130 °C (212 … 266 °F) -- ≤ 3.0 K 130 … 150 °C (266 … 302 °F) -- ≤ 5.5 K 150 … 400 °C (302 … 752 °F) -- --
(1
NTC10kΩ specified for -30 … +100 °C, only.
NOTE: This is the accuracy of the internal sensor input (hardware + software [linearization]), only. This table does not include
the characteristics of the sensors, themselves (see section “Sensor Characteristics” below). If a different sensor or sensor accuracy is required, one may instead use the inputs of, e.g., a connected Panel I/O module.
NTC10kΩ
Recognition of Sensor Failure of Sensor Inputs
The thresholds at which sensor failures – i.e., sensor breaks (SB) and short-circuits (SC) – are recognized depends upon the given sensor type. In the event of a recognized sensor failure, the sensor inputs assume the safety values configured in CARE. Table 17 lists the measurement ranges and the corresponding thresholds for the recognition of sensor failure for the various different sensor types:
Table 17. Thresholds for short-circuit (SC) and sensor-break (SB) recognition
I/O configuration measurement range recognition thresholds
2…10 V 2…10 V / 4…20 mA (without pull-up) SC: < 1.5 V / 3 mA; SB: no recognition NTC10kΩ -50 … +100 °C SC: < 20 Ω; SB: < -70 °C NTC20kΩ -50 … +150 °C SC: < 20 Ω; SB: < -70 °C PT1000 -30 … + 400 °C SC: < 775 Ω; SB: < -50 °C Ni1000TK5000 -70 … +130 °C SC: < 850 Ω; SB: < -30 °C
NOTE: In the case of temperatures lying outside the aforementioned ranges, the lowest/highest value within the range, instead,
will be communicated. Thus a temperature of -51 °C will be communicated as “-50 °C.”
Sensor Characteristics
The characteristics (resistance in relation to temperature) of the sensors and the resultant voltage are listed on the following pages. The stated values do not include failures due to: sensor failures; wiring resistance or wiring failures; misreadings due to a meter connected to measure resistance or voltage at the input.
(1
NTC20kΩ
EN1Z-1035GE51 R0319 24
MERLIN NX ROOM CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
NTC 10 k
Resistance
Temp.
[°C]
-30 177 7.904
-29 166.35 7.848
-28 156.413 7.790
-27 147.136 7.730
-26 138.47 7.666
-25 130.372 7.601
-24 122.8 7.534
-23 115.718 7.464
-22 109.089 7.392
-21 102.883 7.318
-20 97.073 7.241
-19 91.597 7.161
-18 86.471 7.080
-17 81.667 6.996
-16 77.161 6.910
-15 72.932 6.821
-14 68.962 6.731
-13 65.231 6.639
-12 61.723 6.545
-11 58.424 6.448
-10 55.321 6.351
-9 52.399 6.251
-8 49.648 6.150
-7 47.058 6.047
-6 44.617 5.943
-5 42.317 5.838
-4 40.15 5.732
-3 38.106 5.624
-2 36.18 5.516
-1 34.363 5.408
0 32.65 5.299
1 31.027 5.189
2 29.494 5.079
3 28.047 4.969
4 26.68 4.859
5 25.388 4.750
6 24.166 4.641
7 23.01 4.532
8 21.916 4.423
9 20.88 4.316
10 19.898 4.209
11 18.968 4.103
[k
Terminal
voltage [V]
Resistance
Temp.
[°C]
[k
Terminal
voltage [V]
12 18.087 3.998
13 17.252 3.894
14 16.46 3.792
15 15.708 3.690
16 14.995 3.591
17 14.319 3.492
18 13.678 3.396
19 13.068 3.300
20 12.49 3.207
21 11.94 3.115
22 11.418 3.025
23 10.921 2.937
24 10.449 2.850
25 10 2.767
26 9.572 2.684
27 9.165 2.603
28 8.777 2.524
29 8.408 2.447
30 8.057 2.372
31 7.722 2.299
32 7.402 2.228
33 7.098 2.159
34 6.808 2.091
35 6.531 2.025
36 6.267 1.962
37 6.015 1.900
38 5.775 1.840
39 5.546 1.781
40 5.327 1.724
41 5.117 1.669
42 4.917 1.616
43 4.726 1.564
44 4.543 1.514
45 4.369 1.465
46 4.202 1.418
47 4.042 1.373
48 3.889 1.329
49 3.743 1.286
50 3.603 1.244
51 3.469 1.204
52 3.34 1.166
53 3.217 1.128
Resistance
Temp.
[°C]
[k
Terminal
voltage [V]
54 3.099 1.092
55 2.986 1.057
56 2.878 1.023
57 2.774 0.990
58 2.675 0.959
59 2.579 0.928
60 2.488 0.898
61 2.4 0.870
62 2.316 0.842
63 2.235 0.815
64 2.158 0.790
65 2.083 0.765
66 2.011 0.740
67 1.943 0.718
68 1.877 0.695
69 1.813 0.673
70 1.752 0.652
71 1.694 0.632
72 1.637 0.612
73 1.583 0.593
74 1.531 0.575
75 1.481 0.557
76 1.433 0.541
77 1.387 0.524
78 1.342 0.508
79 1.299 0.493
80 1.258 0.478
81 1.218 0.464
82 1.179 0.450
83 1.142 0.436
84 1.107 0.423
85 1.072 0.411
86 1.039 0.399
87 1.007 0.387
88 0.976 0.375
89 0.947 0.365
90 0.918 0.354
91 0.89 0.344
92 0.863 0.334
93 0.838 0.324
94 0.813 0.315
95 0.789 0.306
Resistance
Temp.
[°C]
[k
96 0.765 0.297
97 0.743 0.289
98 0.721 0.280
99 0.7 0.276
100 0.68 0.265
Terminal
voltage [V]
25 EN1Z-1035GE51 R0319
MERLIN NX ROOM CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
NTC 20 k
Temp.
Resistance
[°C]
[k
-50.0 1659 8.78
-49.0 1541 8.77
-48.0 1432 8.76
-47.0 1331 8.75
-46.0 1239 8.74
-45.0 1153 8.72
-44.0 1073 8.71
-43.0 1000 8.70
-42.0 932 8.69
-41.0 869 8.67
-40.0 811 8.66
-39.0 757 8.64
-38.0 706 8.62
-37.0 660 8.60
-36.0 617 8.58
-35.0 577 8.56
-34.0 539 8.54
-33.0 505 8.52
-32.0 473 8.49
-31.0 443 8.47
-30.0 415 8.44
-29.0 389 8.41
-28.0 364 8.38
-27.0 342 8.35
-26.0 321 8.32
-25.0 301 8.28
-24.0 283 8.25
-23.0 266 8.21
-22.0 250 8.17
-21.0 235 8.13
-20.0 221 8.08
-19.0 208 8.04
-18.0 196 7.99
-17.0 184 7.94
-16.0 174 7.89
-15.0 164 7.83
-14.0 154 7.78
-13.0 146 7.72
-12.0 137 7.66
-11.0 130 7.60
-10.0 122 7.53
-9.0 116 7.46
-8.0 109 7.39
-7.0 103 7.32
-6.0 97.6 7.25
-5.0 92.3 7.17
-4.0 87.3 7.09
-3.0 82.6 7.01
-2.0 78.2 6.93
-1.0 74.1 6.85
Termina l
voltage [V]
Temp.
[°C]
Resistance
[k
Terminal
voltage [V]
0.0 70.2 6.76
1.0 66.5 6.67
2.0 63.0 6.58
3.0 59.8 6.49
4.0 56.7 6.40
5.0 53.8 6.30
6.0 51.1 6.20
7.0 48.5 6.10
8.0 46.0 6.00
9.0 43.7 5.90
10.0 41.6 5.80
11.0 39.5 5.70
12.0 37.6 5.59
13.0 35.7 5.49
14.0 34.0 5.38
15.0 32.3 5.28
16.0 30.8 5.17
17.0 29.3 5.07
18.0 27.9 4.96
19.0 26.6 4.85
20.0 25.3 4.75
21.0 24.2 4.64
22.0 23.0 4.53
23.0 22.0 4.43
24.0 21.0 4.32
25.0 20.0 4.22
26.0 19.1 4.12
27.0 18.2 4.01
28.0 17.4 3.91
29.0 16.6 3.81
30.0 15.9 3.71
31.0 15.2 3.62
32.0 14.5 3.52
33.0 13.9 3.43
34.0 13.3 3.33
35.0 12.7 3.24
36.0 12.1 3.15
37.0 11.6 3.06
38.0 11.1 2.97
39.0 10.7 2.89
40.0 10.2 2.81
41.0 9.78 2.72
42.0 9.37 2.64
43.0 8.98 2.57
44.0 8.61 2.49
45.0 8.26 2.42
46.0 7.92 2.34
47.0 7.60 2.27
48.0 7.29 2.20
49.0 7.00 2.14
Temp.
[°C]
Resistance
[k
Termina l
voltage [V]
50.0 6.72 2.07
51.0 6.45 2.01
52.0 6.19 1.94
53.0 5.95 1.88
54.0 5.72 1.82
55.0 5.49 1.77
56.0 5.28 1.71
57.0 5.08 1.66
58.0 4.88 1.61
59.0 4.69 1.56
60.0 4.52 1.51
61.0 4.35 1.46
62.0 4.18 1.41
63.0 4.03 1.37
64.0 3.88 1.32
65.0 3.73 1.28
66.0 3.59 1.24
67.0 3.46 1.20
68.0 3.34 1.16
69.0 3.21 1.13
70.0 3.10 1.09
71.0 2.99 1.06
72.0 2.88 1.02
73.0 2.78 0.991
74.0 2.68 0.960
75.0 2.58 0.929
76.0 2.49 0.900
77.0 2.41 0.872
78.0 2.32 0.844
79.0 2.24 0.818
80.0 2.17 0.792
81.0 2.09 0.767
82.0 2.02 0.744
83.0 1.95 0.720
84.0 1.89 0.698
85.0 1.82 0.676
86.0 1.76 0.655
87.0 1.70 0.635
88.0 1.65 0.616
89.0 1.59 0.597
90.0 1.54 0.578
91.0 1.49 0.561
92.0 1.44 0.544
93.0 1.40 0.527
94.0 1.35 0.511
95.0 1.31 0.496
96.0 1.27 0.481
97.0 1.23 0.466
98.0 1.19 0.452
99.0 1.15 0.439
Temp.
100.0 1.11 0.425
101.0 1.08 0.413
102.0 1.05 0.401
103.0 1.01 0.389
104.0 0.98 0.378
105.0 0.95 0.367
106.0 0.92 0.356
107.0 0.90 0.346
108.0 0.87 0.336
109.0 0.84 0.326
110.0 0.82 0.317
111.0 0.79 0.308
112.0 0.77 0.299
113.0 0.75 0.290
114.0 0.73 0.282
115.0 0.70 0.274
116.0 0.68 0.266
117.0 0.66 0.259
118.0 0.64 0.252
119.0 0.63 0.245
120.0 0.61 0.238
121.0 0.59 0.231
122.0 0.57 0.225
123.0 0.56 0.219
124.0 0.54 0.213
125.0 0.53 0.207
126.0 0.51 0.201
127.0 0.50 0.196
128.0 0.49 0.191
129.0 0.47 0.186
130.0 0.46 0.181
131.0 0.45 0.176
132.0 0.43 0.171
133.0 0.42 0.167
134.0 0.41 0.162
135.0 0.40 0.158
136.0 0.39 0.154
137.0 0.38 0.150
138.0 0.37 0.146
139.0 0.36 0.142
140.0 0.35 0.139
141.0 0.34 0.135
142.0 0.33 0.132
143.0 0.32 0.128
144.0 0.32 0.125
145.0 0.31 0.122
146.0 0.30 0.119
147.0 0.29 0.116
148.0 0.29 0.113
149.0 0.28 0.110
150.0 0.27 0.107
[°C]
Resistance
[k
Terminal
voltage [V]
EN1Z-1035GE51 R0319 26
PT 1000
Temp.
Resistance
[°C]
-50.0 803 0.312
-49.0 807 0.314
-48.0 811 0.315
-47.0 815 0.317
-46.0 819 0.318
-45.0 823 0.320
-44.0 827 0.321
-43.0 831 0.323
-42.0 835 0.324
-41.0 839 0.326
-40.0 843 0.327
-39.0 847 0.329
-38.0 851 0.330
-37.0 855 0.332
-36.0 859 0.333
-35.0 862 0.335
-34.0 866 0.336
-33.0 870 0.338
-32.0 874 0.339
-31.0 878 0.341
-30.0 882 0.342
-29.0 886 0.344
-28.0 890 0.345
-27.0 894 0.347
-26.0 898 0.348
-25.0 902 0.350
-24.0 906 0.351
-23.0 910 0.353
-22.0 914 0.354
-21.0 918 0.356
-20.0 922 0.357
-19.0 926 0.359
-18.0 929 0.360
-17.0 933 0.361
-16.0 937 0.363
-15.0 941 0.364
-14.0 945 0.366
-13.0 949 0.367
-12.0 953 0.369
-11.0 957 0.370
-10.0 961 0.372
-9.0 965 0.373
-8.0 969 0.375
-7.0 973 0.376
-6.0 977 0.378
-5.0 980 0.379
-4.0 984 0.380
-3.0 988 0.382
-2.0 992 0.383
-1.0 996 0.385
0.0 1000 0.386
1.0 1004 0.388
2.0 1008 0.389
3.0 1012 0.391
4.0 1016 0.392
5.0 1020 0.394
6.0 1023 0.395
7.0 1027 0.396
8.0 1031 0.398
9.0 1035 0.399
[
MERLIN NX ROOM CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
Terminal
voltage [V]
Temp.
[°C]
Resistance
[
Terminal
voltage [V]
10.0 1039 0.401
11.0 1043 0.402
12.0 1047 0.404
13.0 1051 0.405
14.0 1055 0.406
15.0 1058 0.408
16.0 1062 0.409
17.0 1066 0.411
18.0 1070 0.412
19.0 1074 0.413
20.0 1078 0.415
21.0 1082 0.416
22.0 1086 0.418
23.0 1090 0.419
24.0 1093 0.420
25.0 1097 0.422
26.0 1101 0.423
27.0 1105 0.425
28.0 1109 0.426
29.0 1113 0.428
30.0 1117 0.429
31.0 1121 0.431
32.0 1124 0.432
33.0 1128 0.433
34.0 1132 0.435
35.0 1136 0.436
36.0 1140 0.438
37.0 1144 0.439
38.0 1148 0.441
39.0 1152 0.442
40.0 1155 0.443
41.0 1159 0.445
42.0 1163 0.446
43.0 1167 0.448
44.0 1171 0.449
45.0 1175 0.451
46.0 1179 0.452
47.0 1182 0.453
48.0 1186 0.455
49.0 1190 0.456
50.0 1194 0.458
51.0 1198 0.459
52.0 1202 0.461
53.0 1205 0.462
54.0 1209 0.463
55.0 1213 0.465
56.0 1217 0.466
57.0 1221 0.467
58.0 1225 0.469
59.0 1229 0.470
60.0 1232 0.471
61.0 1236 0.473
62.0 1240 0.474
63.0 1244 0.476
64.0 1248 0.477
65.0 1252 0.479
66.0 1255 0.480
67.0 1259 0.481
68.0 1263 0.483
69.0 1267 0.484
Temp.
[°C]
Resistance
Terminal
voltage [V]
[
70.0 1271 0.486
71.0 1275 0.487
72.0 1278 0.488
73.0 1282 0.490
74.0 1286 0.491
75.0 1290 0.493
76.0 1294 0.494
77.0 1297 0.495
78.0 1301 0.497
79.0 1305 0.498
80.0 1309 0.499
81.0 1313 0.501
82.0 1317 0.502
83.0 1320 0.503
84.0 1324 0.505
85.0 1328 0.506
86.0 1332 0.508
87.0 1336 0.509
88.0 1339 0.510
89.0 1343 0.512
90.0 1347 0.513
91.0 1351 0.515
92.0 1355 0.516
93.0 1358 0.517
94.0 1362 0.519
95.0 1366 0.520
96.0 1370 0.522
97.0 1374 0.523
98.0 1377 0.524
99.0 1381 0.525
100.0 1385 0.527
101.0 1389 0.528
102.0 1393 0.530
103.0 1396 0.531
104.0 1400 0.532
105.0 1404 0.534
106.0 1408 0.535
107.0 1412 0.537
108.0 1415 0.538
109.0 1419 0.539
110.0 1423 0.541
111.0 1427 0.542
112.0 1430 0.543
113.0 1434 0.545
114.0 1438 0.546
115.0 1442 0.547
116.0 1446 0.549
117.0 1449 0.550
118.0 1453 0.551
119.0 1457 0.553
120.0 1461 0.554
121.0 1464 0.555
122.0 1468 0.557
123.0 1472 0.558
124.0 1476 0.560
125.0 1479 0.561
126.0 1483 0.562
127.0 1487 0.564
128.0 1491 0.565
129.0 1494 0.566
Temp.
Resistance
[°C]
[
130.0 1498 0.567
131.0 1502 0.569
132.0 1506 0.570
133.0 1510 0.572
134.0 1513 0.573
135.0 1517 0.574
136.0 1521 0.576
137.0 1525 0.577
138.0 1528 0.578
139.0 1532 0.580
140.0 1536 0.581
141.0 1539 0.582
142.0 1543 0.584
143.0 1547 0.585
144.0 1551 0.586
145.0 1554 0.587
146.0 1558 0.589
147.0 1562 0.590
148.0 1566 0.592
149.0 1569 0.593
150.0 1573 0.594
151.0 1577 0.596
152.0 1581 0.597
153.0 1584 0.598
154.0 1588 0.600
155.0 1592 0.601
156.0 1596 0.602
157.0 1599 0.603
158.0 1603 0.605
159.0 1607 0.606
160.0 1610 0.607
161.0 1614 0.609
162.0 1618 0.610
163.0 1622 0.612
164.0 1625 0.613
165.0 1629 0.614
166.0 1633 0.615
167.0 1636 0.617
168.0 1640 0.618
169.0 1644 0.619
170.0 1648 0.621
171.0 1651 0.622
172.0 1655 0.623
173.0 1659 0.625
174.0 1662 0.626
175.0 1666 0.627
176.0 1670 0.629
177.0 1674 0.630
178.0 1677 0.631
179.0 1681 0.632
180.0 1685 0.634
181.0 1688 0.635
182.0 1692 0.636
183.0 1696 0.638
184.0 1699 0.639
185.0 1703 0.640
186.0 1707 0.642
187.0 1711 0.643
188.0 1714 0.644
189.0 1718 0.645
Terminal
voltage [V]
27 EN1Z-1035GE51 R0319
MERLIN NX ROOM CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
Temp.
Resistance
[°C]
190.0 1722 0.647
191.0 1725 0.648
192.0 1729 0.649
193.0 1733 0.651
194.0 1736 0.652
195.0 1740 0.653
196.0 1744 0.655
197.0 1747 0.656
198.0 1751 0.657
199.0 1755 0.658
200.0 1758 0.659
201.0 1762 0.661
202.0 1766 0.662
203.0 1769 0.663
204.0 1773 0.665
205.0 1777 0.666
206.0 1780 0.667
207.0 1784 0.669
208.0 1788 0.670
209.0 1791 0.671
210.0 1795 0.672
211.0 1799 0.674
212.0 1802 0.675
213.0 1806 0.676
214.0 1810 0.678
215.0 1813 0.679
216.0 1817 0.680
217.0 1821 0.681
218.0 1824 0.683
219.0 1828 0.684
220.0 1832 0.685
221.0 1835 0.686
222.0 1839 0.688
223.0 1843 0.689
224.0 1846 0.690
225.0 1850 0.692
226.0 1854 0.693
227.0 1857 0.694
228.0 1861 0.695
229.0 1865 0.697
230.0 1868 0.698
231.0 1872 0.699
232.0 1875 0.700
233.0 1879 0.702
234.0 1883 0.703
235.0 1886 0.704
236.0 1890 0.705
237.0 1894 0.707
238.0 1897 0.708
239.0 1901 0.709
240.0 1905 0.711
241.0 1908 0.712
242.0 1912 0.713
243.0 1915 0.714
244.0 1919 0.716
245.0 1923 0.717
246.0 1926 0.718
247.0 1930 0.719
248.0 1934 0.721
249.0 1937 0.722
[
Termina l
voltage [V]
Temp.
[°C]
Resistance
[
Terminal
voltage [V]
250.0 1941 0.723
251.0 1944 0.724
252.0 1948 0.726
253.0 1952 0.727
254.0 1955 0.728
255.0 1959 0.729
256.0 1962 0.730
257.0 1966 0.732
258.0 1970 0.733
259.0 1973 0.734
260.0 1977 0.736
261.0 1980 0.737
262.0 1984 0.738
263.0 1988 0.739
264.0 1991 0.740
265.0 1995 0.742
266.0 1998 0.743
267.0 2002 0.744
268.0 2006 0.746
269.0 2009 0.747
270.0 2013 0.748
271.0 2016 0.749
272.0 2020 0.750
273.0 2024 0.752
274.0 2027 0.753
275.0 2031 0.754
276.0 2034 0.755
277.0 2038 0.757
278.0 2042 0.758
279.0 2045 0.759
280.0 2049 0.760
281.0 2052 0.761
282.0 2056 0.763
283.0 2060 0.764
284.0 2063 0.765
285.0 2067 0.766
286.0 2070 0.768
287.0 2074 0.769
288.0 2077 0.770
289.0 2081 0.771
290.0 2085 0.773
291.0 2088 0.774
292.0 2092 0.775
293.0 2095 0.776
294.0 2099 0.777
295.0 2102 0.778
296.0 2106 0.780
297.0 2110 0.781
298.0 2113 0.782
299.0 2117 0.784
300.0 2120 0.785
301.0 2124 0.786
302.0 2127 0.787
303.0 2131 0.788
304.0 2134 0.789
305.0 2138 0.791
306.0 2142 0.792
307.0 2145 0.793
308.0 2149 0.794
309.0 2152 0.796
Temp.
[°C]
Resistance
[
Termina l
voltage [V]
310.0 2156 0.797
311.0 2159 0.798
312.0 2163 0.799
313.0 2166 0.800
314.0 2170 0.802
315.0 2173 0.803
316.0 2177 0.804
317.0 2181 0.805
318.0 2184 0.806
319.0 2188 0.808
320.0 2191 0.809
321.0 2195 0.810
322.0 2198 0.811
323.0 2202 0.812
324.0 2205 0.814
325.0 2209 0.815
326.0 2212 0.816
327.0 2216 0.817
328.0 2219 0.818
329.0 2223 0.820
330.0 2226 0.821
331.0 2230 0.822
332.0 2234 0.823
333.0 2237 0.824
334.0 2241 0.826
335.0 2244 0.827
336.0 2248 0.828
337.0 2251 0.829
338.0 2255 0.830
339.0 2258 0.831
340.0 2262 0.833
341.0 2265 0.834
342.0 2269 0.835
343.0 2272 0.836
344.0 2276 0.838
345.0 2279 0.839
346.0 2283 0.840
347.0 2286 0.841
348.0 2290 0.842
349.0 2293 0.843
350.0 2297 0.845
351.0 2300 0.846
352.0 2304 0.847
353.0 2307 0.848
354.0 2311 0.849
355.0 2314 0.850
356.0 2318 0.852
357.0 2321 0.853
358.0 2325 0.854
359.0 2328 0.855
360.0 2332 0.856
361.0 2335 0.857
362.0 2339 0.859
363.0 2342 0.860
364.0 2346 0.861
365.0 2349 0.862
366.0 2353 0.863
367.0 2356 0.864
368.0 2360 0.866
369.0 2363 0.867
Temp.
370.0 2367 0.868
371.0 2370 0.869
372.0 2373 0.870
373.0 2377 0.871
374.0 2380 0.872
375.0 2384 0.874
376.0 2387 0.875
377.0 2391 0.876
378.0 2394 0.877
379.0 2398 0.878
380.0 2401 0.879
381.0 2405 0.881
382.0 2408 0.882
383.0 2412 0.883
384.0 2415 0.884
385.0 2419 0.885
386.0 2422 0.886
387.0 2426 0.888
388.0 2429 0.889
389.0 2432 0.890
390.0 2436 0.891
391.0 2439 0.892
392.0 2443 0.893
393.0 2446 0.894
394.0 2450 0.896
395.0 2453 0.897
396.0 2457 0.898
397.0 2460 0.899
398.0 2463 0.900
399.0 2467 0.901
400.0 2470 0.902
[°C]
Resistance
[
Terminal
voltage [V]
EN1Z-1035GE51 R0319 28
NI1000TK5000
Temp.
Resistance
[°C]
-30 871.7 0.338
-29 875.8 0.340
-28 880 0.341
-27 884.1 0.343
-26 888.3 0.344
-25 892.5 0.346
-24 896.7 0.348
-23 900.8 0.349
-22 905.1 0.351
-21 909.3 0.352
-20 913.5 0.354
-19 917.7 0.355
-18 922 0.357
-17 926.2 0.359
-16 930.5 0.360
-15 934.7 0.362
-14 939 0.363
-13 943.3 0.365
-12 947.6 0.367
-11 951.9 0.368
-10 956.2 0.370
-9 960.6 0.371
-8 964.9 0.373
-7 969.3 0.375
-6 973.6 0.376
-5 978 0.378
-4 982.4 0.380
-3 986.7 0.381
-2 991.2 0.383
-1 995.6 0.384
0 1000 0.386
1 1004.4 0.388
2 1008.9 0.389
3 1013.3 0.391
4 1017.8 0.393
5 1022.3 0.394
6 1026.7 0.396
7 1031.2 0.398
8 1035.8 0.399
9 1040.3 0.401
10 1044.8 0.403
11 1049.3 0.404
12 1053.9 0.406
13 1058.4 0.408
14 1063 0.409
15 1067.6 0.411
16 1072.2 0.413
17 1076.8 0.415
[Ω]
MERLIN NX ROOM CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
Terminal
voltage [V]
Temp.
[°C]
Resistance
[Ω]
Termina l
voltage [V]
18 1081.4 0.416
19 1086 0.418
20 1090.7 0.420
21 1095.3 0.421
22 1100 0.423
23 1104.6 0.425
24 1109.3 0.427
25 1114 0.428
26 1118.7 0.430
27 1123.4 0.432
28 1128.1 0.433
29 1132.9 0.435
30 1137.6 0.437
31 1142.4 0.439
32 1147.1 0.440
33 1151.9 0.442
34 1156.7 0.444
35 1161.5 0.446
36 1166.3 0.447
37 1171.2 0.449
38 1176 0.451
39 1180.9 0.453
40 1185.7 0.455
41 1190.6 0.456
42 1195.5 0.458
43 1200.4 0.460
44 1205.3 0.462
45 1210.2 0.463
46 1215.1 0.465
47 1220.1 0.467
48 1225 0.469
49 1230 0.471
50 1235 0.473
51 1240 0.474
52 1245 0.476
53 1250 0.478
54 1255 0.480
55 1260.1 0.482
56 1265.1 0.484
57 1270.2 0.485
58 1275.3 0.487
59 1280.3 0.489
60 1285.4 0.491
61 1290.6 0.493
62 1295.7 0.495
63 1300.8 0.496
64 1306 0.498
65 1311.1 0.500
Temp.
[°C]
Resistance
[Ω]
Terminal
voltage [V]
66 1316.3 0.502
67 1321.5 0.504
68 1326.7 0.506
69 1331.9 0.508
70 1337.1 0.510
71 1342.4 0.512
72 1347.6 0.513
73 1352.9 0.515
74 1358.2 0.517
75 1363.5 0.519
76 1368.8 0.521
77 1374.1 0.523
78 1379.4 0.525
79 1384.8 0.527
80 1390.1 0.529
81 1395.5 0.531
82 1400.9 0.533
83 1406.3 0.535
84 1411.7 0.537
85 1417.1 0.538
86 1422.5 0.540
87 1428 0.542
88 1433.4 0.544
89 1438.9 0.546
90 1444.4 0.548
91 1449.9 0.550
92 1455.4 0.552
93 1460.9 0.554
94 1466.5 0.556
95 1472 0.558
96 1477.6 0.560
97 1483.2 0.562
98 1488.8 0.564
99 1494.4 0.566
100 1500 0.568
101 1505.6 0.570
102 1511.3 0.572
103 1517 0.574
104 1522.6 0.576
105 1528.3 0.578
106 1534 0.580
107 1539.7 0.582
108 1545.5 0.584
109 1551.2 0.586
110 1557 0.589
111 1562.8 0.591
112 1568.5 0.593
113 1574.4 0.595
Temp.
Resistance
[°C]
[Ω]
114 1580.2 0.597
115 1586 0.599
116 1591.8 0.601
117 1597.7 0.603
118 1603.6 0.605
119 1609.5 0.607
120 1615.4 0.609
121 1621.3 0.611
122 1627.2 0.613
123 1633.2 0.616
124 1639.1 0.618
125 1645.1 0.620
126 1651.1 0.622
127 1657.1 0.624
128 1663.1 0.626
129 1669.1 0.628
130 1675.2 0.630
voltage [V]
Termina l
29 EN1Z-1035GE51 R0319
MERLIN NX ROOM CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
Trademark Information
BACnetTM is a trademark of ASHRAE Inc.
ONWORKS, and Neuron are trademarks of Echelon
LON, L Corporation registered in the United States and other countries.
Manufactured for and on behalf of the Connected Building Division of Honeywell Products and Solutions SARL, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative:
CentraLine Honeywell GmbH Böblinger Strasse 17 71101 Schönaich, Germany Phone +49 (0) 7031 637 845 Fax +49 (0) 7031 637 740
info@centraline.com
www.centraline.com
Subject to change without notice EN1Z-1035GE51 R0319
Loading...