► When performing any work, all instructions given by the
manufacturer and in particular the safety instructions
provided in these Installation and Commissioning
Instructions are to be observed. Make sure that the local
standards and regulations are observed at all times.
► The EAGLE System (including the EAGLE Controller,
Panel Bus I/O modules, manual disconnect modules, and
auxiliary terminal packages) may be installed and mounted
only by authorized and trained personnel.
► If the controller housing is damaged or missing,
immediately disconnect it from any power.
► If the device is broken or defective, do not attempt to repair
it yourself; rather, return it to the manufacturer.
► Always check these Installation Instructions in order to
determine which relay terminals are suitable for 230 V.
Connect only suitable relay terminals to 230 V.
► It is recommended that devices be kept at room tem-
perature for at least 24 hours before applying power. This
is to allow any condensation resulting from low shipping /
storage temperatures to evaporate.
► The EAGLE System must be installed in such a manner
(e.g., in a lockable cabinet) as to ensure that uncertified
persons have no access to the terminals.
► In the case of vertical mounting on DIN rails, the EAGLE
controller should be secured in place using a
commercially-available stopper.
► If the EAGLE System is modified in any way, except by the
manufacturer, all warranties concerning operation and
safety are invalidated.
► Rules regarding electrostatic discharge should be followed.
► Use only accessory equipment which comes from or has
been approved by Honeywell.
Information as per EN 60730
Purpose
The purpose of the device is: OPERATING CONTROL. The
EAGLE Controller is a multifunctional non-safety control
device intended for HVAC in home (residential, commercial,
and light-industrial) environments.
Construction
The EAGLE Controller is an independently mounted
electronic control unit with fixed wiring.
Mounting Method
The EAGLE Controller is suitable for mounting as follows:
► in cabinets;
► in fuse boxes conforming with standard DIN43880, and
having a slot height of max. 45 mm;
► in cabinet front doors (using accessory MVC-80-AC2);
► on walls (using accessory MVC-80-AC1).
Table 1. Information as per EN 60730
Shock protection
Pollution degree
Installation
Rated impulse voltage
Automatic action
Software class
Ball-pressure test
temperature
Class II
2
Class 3
330 V for SELV, 2500 V for relay
outputs
Type 1.C (micro-interruption for
the relay outputs)
Class A
housing parts >75 °C
terminals >125 °C
WEEE Directive
WEEE: Waste Electrical and Electronic
Equipment Directive
At the end of the product life, dispose
of the packaging and product in an
appropriate recycling center.
Do not dispose of the device with the
usual domestic refuse.
Do not burn the device.
Standards, Approvals, etc.
Degree of Protection: IP20 (mounted on walls, with two
IP30 (mounted in cabinet doors, with
Device meets BTL, AMEV AS-A, EN 60730-1, EN 60730-29, UL60730, and UL916.
Refer to Code of Practice standards IEC 61000-5-1 and -2
for guidance.
The device complies with Ethernet Protocol versions IEEEC
802.3.
The device supports BACnet IP and BACnet MS/TP
communications as per ANSI / ASHRAE 135-2010.
accessory MVC-80-AC1 covers)
accessory MVC-80-AC2)
3RD-PARTY SOFTWARE LICENSES
This product contains software provided by third parties. See
also EAGLE Controller – Third-Party Software Licenses
(Product Literature No.: EN2Z-0991GE51).
Relay N.O. contact with one common; 3 A, 250 VAC, 30 VDC 400 m - - - - 3 3 - -
(1)
, or Modbus RTU
(1)
, or Modbus
(2)
1200 m 1 1 1 1 1 1 1 1
(2)
1200 m 1 1 1 1 1 1 1 1
bus
interfaces
RS485-1, isolated, BACnet MS/TP, Panel Bus
Master or Slave communication
RS485-2, non-isolated, BACnet MS/TP, Panel Bus
RTU Master or Slave communication
bus status LEDs (for isolated RS485-1 interface) -- 2 2 2 2 2 2 2 2
Socket for
CLEAHMI21
(1)
See also section "Restriction Applying to CLEA2014B21 and CLEA2014B31" on pg. 8.
(2)
Depending upon baud rate. For max. cable lengths, see section "RS485 Standard" on pg. 9. In the case of the Panel Bus, see also section
RJ45 socket for connection of CLEAHMI21 External HMI 5 m -- X -- X -- X -- X
"Panel Bus Considerations" on pg. 23. In the case of the BACnet MS/TP Bus, see also section "BACnet MS/TP Bus Considerations" on pg. 28.
In the case of the Modbus, see also section "Modbus Considerations" on pg. 31.
(3)
Depending upon baud rate. See also section "M-Bus Considerations" on pg. 33.
An EAGLE System consists of the EAGLE Controller and various Panel Bus I/O modules. The EAGLE Controller provides
interface connections, which allow connection to external systems (e.g., BACnet controllers). Via the IF-LON External Interface,
the EAGLE can also communicate with L
Auxiliary parts (see section "Extra Parts" on page 22) enable special features.
ONWORKS systems, including CentraLine LONWORKS I/O Modules.
► Do not touch any live parts in the cabinet!
► Disconnect the power supply before making connections
to or removing connections from terminals of the EAGLE
Controller or Panel Bus I/O modules.
► Do not reconnect the power supply until you have
completed installation.
► Due to the risk of short-circuiting (see Fig. 23), it is
strongly recommended that the EAGLE controller be
supplied with power from a dedicated transformer.
However, if the EAGLE controller is to be supplied by the
same transformer powering other controllers or devices
(e.g., the PW M-Bus Adapter), care must be taken to
ensure that correct polarity is observed.
► Observe the rules regarding electrostatic discharge.
2 USB 2.0 Host Interface (for connection to IF-LON)
3 Ethernet / RJ45 socket (for BACnet IP communication)
– all models except CLEA2014B21 and CLEA2014B31
4 RS485-1* (isolated; for BACnet MS/TP, Panel Bus, or
Modbus RTU Master communication)
5 RS485-2* (non-isolated; for BACnet MS/TP, Panel
Bus, or Modbus RTU Master communication)
6 LEDs
7 USB 2.0 Device Interface (for connection to CARE /
XW-Online and web browsers, CL-Touch, or other 3
party touch panels)
8 Three-position slide switch (for setting bias and ter-
mination resistance of RS485-1)
9 RJ45 socket for connection of CLEAHMI21 External
HMI – CLEA2000B31, CLEA2014B31, CLEA2014B32,
CLEA2026B31, only
* Modbus RTU Master communication is possible on either
one of the two RS485 interfaces, but not on both of them
concurrently.
NOTE:In the case of the CLEA2014B21 and
CLEA2014B31, at least one of the two RS485
interfaces must be assigned to BACnet MS/TP.
The other RS485 interface can then be assigned to
either Panel Bus, Modbus, or BACnet MS/TP.
WARNING
Risk of electric shock or equipment damage!
► It is prohibited to connect any of the RJ45 sockets of the
EAGLE Controller to a so-called PoE-enabled device
("Power over Ethernet").
Via its RS232 / RJ45 socket, the EAGLE Controller can be
connected (using an XW586 cable) to a PW M-Bus Adapter
and thus to M-Bus networks. See also section "M-Bus
Connection" on pg. 33.
J1J8
32 33 34 35 36 37 38 39 40
BI1
BI2
n.a.
BI3
BI4
GND
UI9
UI10
41 424344
UI1
UI2
UI3
UI4
UI5
45 46
UI6
UI7
47
UI8
RS232-RJ45 SOCKET
Fig. 5. RS232 / RJ45 socket
USB 2.0 Host Interface
Via its USB 2.0 Host interface, the EAGLE Controller can be
connected to, e.g., the IF-LON External Interface Adapter and
thus to L
ONWORKS networks. Max. 500 mA, high speed. See
also section "LonWorks Communications" on pg. 27.
J1J8
USB 2.0 Host Interface
Fig. 6. USB 2.0 Host interface
USB 2.0 Device Interface
All models of the EAGLE Controller are equipped with a USB
2.0 Device Interface at the front. This interface is for connection to CARE / XW-Online and web browsers, CL-Touch,
or other 3
rd
-party touch panels.
USB 2.0 Device Interface
Fig. 7. USB 2.0 Device Interface
A standard USB type-B connector can be inserted into this
USB 2.0 Device Interface. This USB 2.0 Device Interface is
the recommended interface for connection to CARE.
Ethernet / RJ45 Socket
All models of the EAGLE Controller (except CLEA2014B21
and CLEA2014B31) are equipped with an Ethernet / RJ45
socket featuring one LED.
J1J8
Ethernet / RJ45 socket
Fig. 8. Ethernet / RJ45 socket (CLEA2000Bxx,
CLEA2014Bx2, and CLEA2026Bxx, only)
This Ethernet / RJ45 socket is a 10/100-Mbaud Ethernet
interface permitting communication (as per IEEEC 802.3) on
BACnet IP networks.
grounded. For additional information on earth
grounding, see also "Appendix 1: Earth Grounding"
on pg. 36.
LEDs
The EAGLE Controller features the following LEDs:
Fig. 10. EAGLE Controller LEDs
Table 4. EAGLE Controller LEDs
symbol
See also section "EAGLE Controller Troubleshooting" on
page 35 for a detailed description of the behaviors of the Tx
and Rx LEDs, the status LED, and the power LED and their
meanings.
color function, description
L1 yellow
L2 -- Not used.
Tx yellow
Rx yellow
!
red
green power LED
application-specific LED indicating status
information ("Cooling Mode", "Heating
Mode" "Service Interval" etc.)
RS485-1 status LED indicating transmission of communication signals.
RS485-1 status LED indicating reception
of communication signals.
status LED indicating hardware problems,
lack of application, sensor failure, or Panel
Bus failure
RS485 Interfaces
General
The EAGLE Controller features two RS485 interfaces:
RS485-1 (consisting of push-in terminals 24 [GND-1], 25,
and 26) is isolated and can be used for BACnet MS/TP
bus, Panel Bus, or Modbus RTU Master communication.
RS485-2 (consisting of push-in terminals 29, 30, and 31
[GND-2]) is non-isolated (i.e. GND-2 is internally connected with terminal 1 [24V~0] and terminals 19+37
[system ground]) and can be used for BACnet MS/TP bus,
Panel Bus, or Modbus RTU Master communication.
Restriction Applying to CLEA2014B21 and CLEA2014B31
In the case of the CLEA2014B21 and CLEA2014B31, CARE
automatically assigns a minimum of one of the two RS485
interfaces to BACnet MS/TP. Although the user has the
option of shifting this assignment from the automatically
assigned RS485 interface to the other, the user cannot alter
the fact that a minimum of one of the two RS485 interfaces
will be assigned to BACnet MS/TP. Thus, in the case of the
CLEA2014B21 and CLEA2014B31, the total max. no. of
Panel Bus I/O modules is reduced from 128 to only 64.
RS485-1 Bias and Termination Resistors
RS485-1 is equipped with a three-position slide switch which
can be used to switch its bias resistors OFF (position "MID" –
this is the default), ON (position "BIAS"), and ON with an
additional 150Ω termination resistor (position "END").
J1J8
END
BIAS
MID
RS485-1
3-POSITION SLIDE SWITCH
Fig. 11. RS485-1 three-position slide switch
The recommended slide switch setting depends upon the
location and usage of the given EAGLE – see Fig. 12 and
Table 5; it also depends upon the selected communication
protocol (BACnet MS/TP, Panel Bus, or Modbus RTU Master
communication, respectively).
Table 5. Recommended slide switch settings
settingremarks
END
BIAS
MID
Controllers located on either end of bus should have
this setting.
In small bus networks, a min. of one and a max. of
two controllers should have this setting.
All other controllers (not set to "END" or "BIAS") on
bus should have this setting (which is the default).
Fig. 14. RS485-1 three-position slide switch setting END
NOTE: All terminals are protected (up to 24 Vac) against
NOTE: According to BACnet standards, a minimum of one
RS485-2 Bias and Termination Resistors
The RS485-2 interface is not affected by the aforementioned
three-position slide switch. The 550Ω bias resistors and 130Ω
termination resistor of the RS485-2 are thus always ON.
short-circuiting and incorrect wiring – except when
the 3-position slide switch is set to "END," in which
case the terminals of the RS485-1 bus (24, 25, and
26) have no such protection. Higher voltages may
damage the device.
and a maximum of two BACnet devices must have
its/their bias resistors switched ON. In the case of
the RS485-1 interface of the EAGLE, setting its
slide switch to either "BIAS" or "END" fulfills this
requirement.
550 OHM
RS485-2 (+)
130 OHM
RS485-2 (-)
550 OHM
Fig. 15. RS485-2 bias and termination resistors
NOTE: GND-2 is internally connected with 24V-0
RS485 Standard
According to the RS485 standard (TIA/EIA-485: "Electrical
Characteristics of Generators and Receivers for Use in
Balanced Digital Multipoint Systems"), only one driver communicating via an RS485 interface may transmit data at a
time. Further, according to U.L. requirements, each RS485
interface may be loaded with a max. of 32 unit loads. E.g.,
CentraLine devices have as little as ¼ unit load each, so that
up to 128 devices can be connected.
BACnet MS/TP connections to the RS485 interfaces must
comply with the aforementioned RS485 standard. Thus, it is
recommended that each end of every connection be equipped
with one termination resistor having a resistance equal to the
cable impedance (120 Ω / 0.25 – 0.5 W).
RS485 systems frequently lack a separate signal ground wire.
However, the laws of physics still require that a solid ground
connection be provided for in order to ensure error-free
communication between drivers and receivers – unless all of
the devices are electrically isolated and no earth grounding
exists.
IMPORTANT
The cable length affects the baud rate. The following table
provides a few examples.
(terminal 1) and system GND (terminals 19+37)
In the case of new EAGLE controller installations, we
strongly recommend using a separate signal ground
wire. Doing otherwise may possibly lead to
unpredictable behavior if other electrically non-isolated
devices are connected and the potential difference is
too high.
In the case of the installation of EAGLE controllers in
already-existent RS485 two-wire systems (e.g., when
replacing PANTHER or LION controllers with EAGLE
controllers), not using a separate signal ground wire
will probably have no undesirable effects.
Table 6. Baud rate vs. max. cable length for RS485
Baud rate Max. cable length (L)
9.6 - 76.8 kbps 1200 m
*115.2 kbps 1000 m
* In the case of configuration of RS485-2 for Panel Bus, the
communication rate is set to 115.2 kbps.
For information on wire gauge, max. permissible cable length,
possible shielding and grounding requirements, and the max.
number of devices which can be connected to a bus, refer to
standard EIA-485.
Modbus Connection
The EAGLE controller can function as a Modbus Master.
In general, the RS485 wiring rules must be followed.
Wiring Topology
Only daisy-chain wiring topology is allowed.
MODBUS
MASTER
Other wiring topologies (e.g., star wiring, or mixed star wiring
and daisy chain wiring) are prohibited; this is to avoid communication problems of the physical layer.
See also section "EIA 485 Cable Specifications" on pg. 26.
Use shielded twisted pair cable J-Y-(St)-Y 2 x 2 x 0,8.
You must use three wires:
One wire for D1 = Modbus +
One wire for D0 = Modbus –
One wire for the signal common
When using one pair for D1 and D0 and one wire of another
pair for the signal common, CAT5 cable may also be used.
MODBUS
SLAVE
MODBUS
SLAVE
MODBUS
SLAVE
Fig. 16. Allowed Modbus wiring topology
MODBUS
SLAVE
MODBUS
SLAVE
MODBUS
SLAVE
MODBUS
SLAVE
MODBUS
SLAVE
MODBUS
SLAVE
For connection details, see section "Modbus Connection" on
pg. 31.
Shielding
Shielding is especially recommended when the Modbus cable
is installed in areas with expected or actual electromagnetic
noise. Avoiding such areas is to be preferred.
Use shielded twisted pair cable shielded twisted pair cable JY-(St)-Y 2 x 2 x 0,8 and connect the Modbus to a noise-free
earth ground – only once per Modbus connection.
RS485 Repeaters
RS485 repeaters are possible, but have not been tested by
Honeywell. Hence it is within responsibility of the
installing/commissioning person to ensure proper function.
NOTE:Each Modbus segment will require its own line
polarization and line termination.
Modbus Master Specifications
Modbus Compliance
As per the Modbus standard, the EAGLE controller is a conditionally compliant "regular" Modbus device.
The EAGLE controller differs from an unconditionally compliant "regular" Modbus device in that it does not support
communication rates of 1.2, 2.4, and 4.8 kBaud (because
these communication rates are not market-relevant).
Physical Layer
2-wire serial line RS485 (EIA-485) (with additional common)
Communication rates: 9.6, 19.2, 38.4, 57.6, 76.8, and
115.2 kBaud supported.
Max. number of devices: 32
Cable and wiring specifications: See section "Wiring and Set-
Up" on pg. 14.
Communication Mode
Modbus Master.
Transmission Mode
RTU (Remote Terminal Unit)
Address Range
Modbus slaves can have an address between 1 and 247.
Discrete Inputs, Coils, Input Registers and Holding Registers
Upon reception of any of the following exception codes,
datapoints of the EAGLE application will show "no response."
Table 8. Supported exception codes
exception code (hex) function
01 illegal function
02 illegal data address
03 illegal data value
04 slave device failure
05 acknowledge
06 slave device busy
Register Sizes
The following Register sizes are supported:
16-bit Registers for Discrete inputs, Coils, Input Registers,
and Holding Registers
32-bit Registers for Input Registers and Holding Registers.
Data Types
The following data types are supported:
Discrete Inputs:
- BOOL
Coils:
- BOOL
Input Registers:
- BOOL
- INT16, UINT16
- INT32, UINT32
- FLOAT
Holding Registers:
- BOOL
- INT16, UINT16
- INT32, UINT32
- FLOAT
- 32-bit floating points can be transmitted as two
consecutive 16-bit registers.
Byte and Word Order Transmission
Most Significant Byte First (default)
Lower Significant Byte First
Most Significant Word first (default)
Lower Significant Word first
Bit Unpack
The EAGLE allows direct reading of single bits of an Input
Register or of a Holding Register into a data-point.
In typical situations in which several different status bits of a
Modbus slave’s Register need to be read and linked into the
EAGLE application, this allows for very efficient application
engineering.
Number of Stop Bits
One and two stop bits are supported.
Error Checking Mode
Parity checking: No parity, even parity, odd parity.
Frame checking: Cyclical redundancy checking (CRC).
Life Check of Modbus Slaves
The EAGLE checks the Modbus every 15 seconds for lost
Modbus slave devices.
Message Response Timeout
20 msec ... 5000 msec.
Modbus Slaves Scan Cycle
The measurement cycle of all addressable Modbus slaves
depends upon the number of connected Modbus slaves and
the total number of mapped datapoints. The minimum
measurement cycle is 500 msec. This cycle time is based
upon the read cycle of the datapoint manager in the firmware.
Modbus Communication Failure Indication
As soon as the EAGLE runs an application which includes
Modbus points, it will try to communicate with the Modbus
devices based on the Modbus to datapoint mapping of the
application.
If a Modbus slave does not respond to a message from the
EAGLE controller, the message will be repeated two times. If
the Modbus slave does not respond to the two message
repeats either, the EAGLE will stall the messaging to this
Modbus slave for 15 seconds. After these 15 seconds, the
Modbus slave will be again addressed with the same two
repeats, if necessary. This cycle will be repeated endlessly.
If the EAGLE does not receive any response for a duration of
six (6) seconds, the System Alarm "MODB COMM ERROR"
will be issued.
To allow the evaporation of any condensation resulting from low shipping / storage temperatures, keep the controller at
room temperature for at least 24 h before applying power.
US requirement, only: This device must be installed in a UL-listed enclosure offering adequate space to maintain the
segregation of line voltage field wiring and Class 2 field wiring.
In the case of vertical mounting on DIN rails, the EAGLE controller should be secured in place using a commercially-available
stopper.
See also the EAGLE Mounting Instructions (MU1Z-0970GE51).
Dimensions
215.5
57.5
49.5
25 262728 29 30 31 32 33 34 35 36 37 38 39 40
24
END
BIAS
RS232
RS485-1
MID
485-1-
485-1+
GND1
BI1
485-2-
485-2+
GND2
UI9
BI2
BI3
BI4
UI10
GND
41 424344
UI1
UI2
45 46
47
UI3
UI8
UI7
UI4
UI5
UI6
55.5
45
IN
24V~
24V-0
1
2
BO1
BO2
BO3
5 6 7 8 9 10 11 12 13 14 15 16 17 1819 20 21 22
Fig. 18. EAGLE Controller with built-in HMI, dimensions (in mm)
IN5
IN6
IN7
IN4
BO4
BO5
BO6
BO7
IN8
BO8
GND
AO1
AO2
AO3
AO4
23
215.5
52
57.5
110
49.5
25 262728 29 30 31 32 33 34 35 36 37 38 39 40
24
END
BIAS
J1 J8
RS485-1
MID
485-1+
GND1
485-1-
BO1
BO2
BO3
56789
RS232
24V~
24V-0
1
2
BI1
BI2
485-2-
485-2+
GND2
IN
IN5
IN4
BO5
BO4
10 11 12 13 14 15 16 17
BI3
BI4
UI9
UI10
GND
IN7
IN8
IN6
BO6
BO7
BO8
1819
41 424344
UI1
UI2
45 46
47
UI3
UI4
UI5
UI6
UI7
UI8
GND
20 21 22
AO1
AO2
AO3
5245
AO4
23
110
Fig. 19. EAGLE Controller with RJ45 socket for connection of CLEAHMI21 External HMI, dimensions (in mm)
All wiring must comply with applicable electrical codes and
ordinances, including VDE, National Electric Code (NEC)
or equivalent, and any local regulations must be observed.
Refer to job or manufacturer’s drawings for details. Local
wiring guidelines (e.g., IEC 364-6-61 or VDE 0100) may
take precedence over recommendations provided here.
Electrical work should be carried out by a qualified
electrician.
Electrical connections must be made at terminal blocks.
For Europe only: To comply with CE requirements, devices
with a voltage in the range of 50 ... 1000 VAC or 75 ...
1500 VDC which are not provided with a supply cord and
plug or with other means for disconnection from the supply
having a contact separation of at least 3 mm in all poles
must have the means for disconnection incorporated in the
fixed wiring.
WARNING
Risk of electric shock or equipment damage!
► Observe precautions for handling electrostatic sensitive
devices.
► Do not touch any live parts in the cabinet.
► Do not open the controller housing.
► Disconnect the power supply before making connections to
or removing connections from terminals of the EAGLE
Controller and devices wired to it.
► Do not use spare terminals as wiring support points.
► Mixing of different voltages (e.g., 24 V and 230 V) within
individual relay blocks of the EAGLE is not allowed.
► To prevent risk of injury due to electrical shock and/or
damage to the device due to short-circuiting, low-voltage
and high-voltage lines must be kept separate from one
another.
► All terminals are protected (up to 24 Vac) against short-
circuiting and incorrect wiring (unless the 3-position slide
switch is set to "END," in which case the terminals of the
RS485-1 bus [24, 25, and 26] have no such protection).
Higher voltages may damage the device.
► Do not reconnect the power supply until you have
completed the installation.
Fig. 22. Inserting/removing wires from push-in terminals
NOTE: With solid conductors, ferrules are prohibited.
NOTE: Use only one conductor per push-in terminal.
NOTE: If, nevertheless, two stranded wires are to be
connected to a single push-in terminal, twin wire
end ferrules must be used.
stranded conductor with wire end
ferrules (w/o plastic collar)
stripping length
Power Supply
Powering EAGLE
Power is supplied via a removable terminal plug (attached to
terminals 1 and 2). See also Fig. 25.
The power supply of the EAGLE Controller must conform to
Safety Class II. To reduce overall current consumption, the
EAGLE can be powered by a switch power supply (rather
than by a transformer). See also Table 2 on pg. 3.
Due to the risk of short-circuiting (see Fig. 23), it is strongly
recommended that the EAGLE controller be supplied with
power from a dedicated transformer. However, if the EAGLE
controller is to be supplied by the same transformer powering
other controllers or devices (e.g., the PW M-Bus Adapter),
care must be taken to ensure that correct polarity is observed
N, L
EARTH GROUND
SHORT-CIRCUITING!
PC 1PC 2
0.2 … 1.50 mm
0.2 … 1.50 mm
0.2 … 1.50 mm
0.2 … 1.50 mm
10.0 +1.0 mm
2
2
2
2
Fusing Specifications
System Fusing
We recommend that the user equip the system with an
external fuse.
Fusing of Active Field Devices
F2 (depends upon loads in use).
Wiring Terminals
The EAGLE is equipped with push-in terminal plugs.
1 24V-0 supply voltage (GND), internally connected with term. 31 and system GND (term. 19+37) X X X
2 24V~
3,4 - not used - - 5 BO1 Binary output 1. N.O. relay contact switching input power connected to terminal 8 - X -
6 BO2 Binary output 2. N.O. relay contact switching input power connected to terminal 8 - X 7 BO3 Binary output 3. N.O. relay contact switching input power connected to terminal 8 - X 8 IN1,2,3 Common relay contact for BO1, BO2, and BO3 - X 9 IN4 Relay contact for BO4 X X 10 BO4 Binary output 4. N.O. relay contact switching input power connected to terminal 9 X X 11 BO5 Binary output 5. N.O. relay contact switching input power connected to terminal 12 X X 12 IN5 Relay contact for BO5 X X 13 IN6 Relay contact for BO6 X X 14 BO6 Binary output 6. N.O. relay contact switching input power connected to terminal 13 X X 15 BO7 Binary output 7. N.O. relay contact switching input power connected to terminal 16 X X 16 IN7 Relay contact for BO7 X X 17 IN8 Relay contact for BO8 - X 18 BO8 Binary output 8. N.O. relay contact switching input power connected to terminal 17 - X -
19 GND Ground terminal (see NOTE below) X X 20 AO1 Analog output 1 X X -
21 AO2 Analog output 2 X X 22 AO3 Analog output 3 - X 23 AO4 Analog output 4 - X -
24 GND-1 ref. GND of RS485-1 (isolated) X X X
25 485-1+ "+" signal for RS485-1 (isolated) X X X
26 485-1- "-" signal for RS485-1 (isolated) X X X
27,28 not used - - 29 485-2+ "+" signal for RS485-2 (non-isolated) X X X
30 485-2- "-" signal for RS485-2 (non-isolated) X X X
31 GND-2 ref. GND of RS485-2, int. connected with 24V-0 (term. 1) and system GND (term. 19+37) X X X
32 - not used - - 33 BI1 Binary input 1 (static dry contact) / pulse counter (fast totalizer) X X -
34 BI2 Binary input 2 (static dry contact) / pulse counter (fast totalizer) X X 35 BI3 Binary input 3 (static dry contact) / pulse counter (fast totalizer) X X 36 BI4 Binary input 4 (static dry contact) / pulse counter (fast totalizer) X X -
37 GND Ground terminal (see NOTE below) X X 38 UI9 Universal input 9 (for NTC10kΩ / NTC20kΩ / 0..10V / slow BI) - X -
In Europe, if the EAGLE is powered by transformers, then
such transformers must be safety isolating transformers
conforming to IEC61558-2-6.
In the U.S. and Canada, if the EAGLE is powered by transformers, then such transformers must be NEC Class-2
transformers.
Table 11. 1450 series transformers data
part #
1450 7287
-001 120 Vac 24 Vac, 50 VA
-002 120 Vac
-003 120 Vac
-004 240/220 Vac 24 Vac, 50 VA
-005 240/220 Vac
-006 240/220 Vac
transformer
CRT 2 230 Vac 2 A 500 mA
CRT 6 230 Vac 6 A 1300 mA
CRT 12 230 Vac 12 A 2500 mA
primary sidesecondary side
2 x 24 Vac, 40 VA, and 100 VA
from separate transformer
24 Vac, 100 VA, and 24 Vdc, 600
mA
2 x 24 Vac, 40 VA, and 100 VA
from separate transformer
24 Vac, 100 VA, and 24 Vdc,
600 mA
Table 12. Overview of CRT Series AC/DC current
primary
side
max. AC
current
max. DC
current
PRIMARY
SIDE
EAGLE
NOTE: Use a min. distance of 10 cm between power
cables and 0…10 V / sensor cables in order to
prevent signal disturbances on the 0…10 V /
sensor cables. See also section "Addressing Panel
Bus I/O Modules" on page 26.
Powering Field Devices and EAGLE via Separate Transformers
24 V actuator connected to separate transformer
Field device located max. 400 m from EAGLE
24 V0
230 V~
24 V~
F2
24V
~
GND
230 V~
24 V~
24 V0
2
1
EAGLE
20...23
Y (0...10 Vdc)
19
max. 400 m
Fig. 25. Power supply of EAGLE and field devices by
separate transformer
Powering Field Devices and Panel Bus I/O Module via Separate
Transformers
24 V actuator connected to, e.g., an analog output module
Field device located 100 … 400 m from the Panel Bus I/O
module
230 V~
24 V~
24 V0
F1
CLIOP822A
73
741...8
11...18
24 V0
24 V~
Y (0...10 Vdc)
230 V~
F2
24V
~
GND
230 Vac
120 Vac
24 V~
24 V0
2
1
NOT
RECOMMENDED
Fig. 24. Connection of EAGLE Controller
RIN-APU24
The RIN-APU24 Uninterruptable Power Supply can be
directly wired to an EAGLE Controller.
See RIN-APU24 Uninterruptable Power Supply – Mounting
Instructions (EN0B-0382GE51) for a detailed wiring diagram.
Powering Panel Bus I/O Modules and Field Devices
The EAGLE, Panel Bus I/O modules, and field devices can be
powered by either separate transformers (see Fig. 25, Fig. 26,
and Fig. 27) or by the same transformer (see Fig. 28 on pg.
17).
EN1Z-0970GE51 R0918 16
max. 400 m
Fig. 26. Power supply via a separate transformer
Powering Field Devices via Panel Bus I/O Module
24 V actuator connected to, e.g., an analog output module
Field device located max. 100 m from the Panel Bus I/O
module
F2
CLIOP822A
F1
24 V~
230 V~
24 V0
73
1...8
74
11...18
Y (0...10 Vdc)
max. 100 m
24V
GND
~
Fig. 27. Power supply via Panel Bus I/O Module
Lightning Protection
Please contact your local Honeywell representative for
information on lightning protection.
Risk of electric shock or equipment damage!
Low voltage and line voltage must not be wired
within the same block.
4
L
IN
BO2
BO3
A5
5
6 7
N
IN4
7
BO4
XS830
IN5
IN6
BO5
11 121314
B1 B2B3B4
1 2
FAN
1: 230V N
2: 230V~
IN7
BO6
BO7
15 161718
B5
5
3
4
14
FAN
1: 230V N
2: 230V~
IN8
B6 B7
BO8
6 7
15
GND
19
FAN
1: 230V N
2: 230V~
20
AO1
AO2
AO3
AO4
23
22
21
111222
MMM
Fig. 29. CLEA2026Bxx connection example (with two XS830 Auxiliary Terminal Packages)
The XS830 and XS831 Auxiliary Terminal Packages are optional accessories which can be mounted onto the top and/or bottom
of the EAGLE Controller in order to equip them with additional terminals for the connection of, e.g., shields, sensors, GND, N,
230 V, or 24 V (but not earth!).
NOTE:Use a min. distance of 10 cm between power cables and 0…10 V / sensor cables in order to prevent signal
The CLEA2000Bxx is not equipped with inputs or outputs.
The following sub-sections thus apply only to the
CLEA2026Bxx and CLEA2014Bxx.
Universal Inputs
The CLEA2026Bxx is equipped with ten (CLEA2014Bxx: four)
universal inputs (UIs) configurable (in CARE).
For information on the accuracy of the sensor inputs, their
differential measurement error, the characteristics (i.e., resistances and resultant voltages in dependence upon temperature) of the various different sensor types which can be
connected to them, and on the thresholds at which sensor
failures are recognized, see section "Appendix 2" on page 39.
Table 13. Specifications of UIs
criteria value
voltage input
current input
supported
sensor types
resolution
accuracy
protection
Fig. 30 Internal wiring of UI1-UI8 configured for voltage
UI1-UI10: 0 … 10 VDC with pull-up resistor
(default)
UI1-UI8: 0…10 VDC w/o pull-up resistor
UI1-UI8: 2…10 VDC w/o pull-up resistor
UI1-UI10: 0 … 10 VDC w/o pull-up resistor,
external 499Ω resistor required to measure
0…20 mA
UI1-UI8: 2…10 VDC w/o pull-up resistor,
external 499Ω resistor required to measure
4…20 mA
NTC10kΩ (-30…+100 °C)
NTC20kΩ (-50…+150 °C)
Slow binary input (static, dry-contact),
0.4 Hz
12-bit resolution
±75 mV (0 ... 10 V)
against short-circuiting, 24 VAC
200 k
V
i
GND
input (without pull-up resistor)
10 VDC
25 k
200 k
V
i
GND
Fig. 31. Internal wiring of UI1-UI10 configured for input
from NTC10kΩ / NTC20kΩ / voltage input (with pull-up
resistor)
Slow Binary Input Specifications
When configured as slow binary inputs, the universal inputs of
the EAGLE have the following specifications:
open contact ≥ 100 kΩ
closed contact ≤ 100 Ω
The polarity (normal = N.O. contact or reverse = N.C. contact)
configuration defines if a logical 1 or a logical 0 is detected for
a closed contact. This is done by selecting (in CARE) one of
the following options:
normal (default)
reverse
closed external contact → state=1
open external contact → state=0
closed external contact → state=0
open external contact → state=1
Pulse Counter Specifications
Using CARE, the universal inputs of the EAGLE can be configured as pulse counters (totalizers).
If the duty cycle is 50% / 50%, the pulse counter supports up
to 0.4 Hz. Counting is done on the rising edge.
Table 14. UIs of EAGLE configured as slow BIs
frequency
pulse ON
pulse OFF
bounce
max. 0.4 Hz
min. 1.25 s
min. 1.25 s
max. 50 ms
Analog Outputs
The CLEA2026Bxx is equipped with four (CLEA2014Bxx: two)
analog outputs (AOs).
In the event of an application stop (e.g., during application
download), the analog outputs assume the safety positions
configured in CARE.
The analog outputs can be configured in CARE as binary
outputs (with an output of 0 V or 10 V, as the case may be).
max. output range 0 … 11 VDC (1 mA)
min. resolution 8 bit
min. accuracy ± 150 mV
max. wire length 400 m
wire cross section See Table 9 on pg. 14.
protection against short-circuiting, 24 VAC
Binary Inputs / Pulse Counters
Both the CLEA2026Bxx and the CLEA2014Bxx are equipped
with four binary inputs (static dry-contact inputs) / pulse
counters (fast totalizers).
Table 16. Specifications of BIs
criteria value
input type
current rating
(closed input)
open contact
voltage
protection against short-circuiting, 24 VAC
Binary Input Specifications
The binary inputs of the EAGLE are static dry-contact inputs.
This reduces the wiring effort, as it is then not necessary to
distribute an auxiliary voltage signal.
open contact ≥ 3000 Ω (24 VDC on BI terminal)
closed contact ≤ 500 Ω (short-circuit current: 2.0 mA)
The polarity (normal = N.O. contact or reverse = N.C. contact)
configuration defines if a logical 1 or a logical 0 is detected for
a closed contact. This is done by selecting (in CARE) one of
the following options:
normal (default)
reverse
Pulse Counter Specifications
Using CARE, the binary inputs of the EAGLE can be configured as pulse counters (fast totalizers) for operation in
conjunction with devices equipped with an open collector
output.
If the duty cycle is 50% / 50%, the pulse counter supports up
to 15 Hz. Counting is done on the rising edge.
closed external contact → state=1
open external contact → state=0
closed external contact → state=0
open external contact → state=1
Table 17. BIs of EAGLE configured as fast totalizers
frequency
pulse ON
pulse OFF
bounce
max. 15 Hz
min. 25 ms
min. 25 ms
max. 5 ms
24V
BI
FAST
TOTALIZER
DRY CONTACT
COM
24 VDC =
0 V =
GND
open
closed
Fig. 32. Internal wiring of BI
Binary Outputs
The EAGLE features eight (CLEA2026Bxx) or four
(CLEA2014Bxx) binary outputs arranged in two blocks
(BO1…4 and BO5..8, respectively).
WARNING
Risk of electric shock or equipment damage!
Low voltage and line voltage must not be wired within
the same block.
In the event of an application stop (e.g., during application
download), the binary outputs assume the safety positions
configured in CARE.
The polarity (normal = N.O. contact or reverse = N.C. contact)
configuration defines if a relay is open or closed, depending
upon whether there is a logical 1 or a logical 0. This is done
by selecting (in CARE) one of the following options:
normal (default)
reverse
state=1 → relay contact is closed
state=0 → relay contact is opened
state=0 → relay contact is closed
state=1 → relay contact is opened
* typically 250,000 cycles; ** typically 50,000 cycles
NOTE:The total max. sum load for all binary outputs
(BO1…8) equals 14 A.
NOTE:Binary output 4 supports the switching of high in-
rush currents (e.g., motors, incandescent lights,
etc.). The max. allowed switch current is 80 A for a
duration of max. 20 ms.
block 1 block 2
BO1…3 BO4 BO5…8
5…253 V 5…253 V 5…253 V
5…30 V 20…30 V 5…30 V
3 A 10 A 3 A
0.3 A* 10 A 0.3 A*
2 A** 10 A 2 A**
3 A 7 A 3 A
100 mA /
5 Vdc
40 mA /
24 Vdc
100 mA /
5 Vdc
ENGINEERING, COMMISSIONING
Please refer also to CARE - User Guide (Product Literature
No.: EN2B-0182GE51) for detailed information.
Required Preparations
In order to access (with a laptop or PC) the EAGLE Controller
via Ethernet/IP for the first time, you may employ any one of
the following two options:
Option 1: USB 2.0 Device (recommended)
This USB 2.0 Device interface is the recommended interface
for downloading applications and firmware via CARE. An "AMale to B-Male" USB cable is required.
For access via USB, the EAGLE Controller has a permanent
default IP address 192.168.255.241. Your PC's IP address
must match the EAGLE Controller's default IP address subnet: We recommend using DHCP or "Obtain an automatic IP
address".
Option 2: Standard Ethernet Interface
The standard IP address can be set in CARE. For this
purpose, connect first with the USB interface. In any case,
your PC's IP address must match the EAGLE Controller's
default IP address subnet. We recommend using DHCP or
"Obtain an automatic IP address".
Behavior of Outputs during Download
Table 19. Behavior of outputs during firmware download /
application download
analog, binary, and
floating outputs
onboard outputs
of EAGLE, itself
outputs of Panel
I/O modules
(CLIOP82x)
outputs of
L
ONWORKS I/O
modules
(CLIOL82x)
NOTE:These behaviors were determined using a test
application with a cycle time of 10 seconds. A
value update was triggered every 10 seconds.
Removable terminal plugs, push-in type; complete set of 3 plugs (for
terminals 1, 2, 24-32); for the CLEA2000Bxx.
A1 A2A3A4
A1 B1 A2 B2
A5 A6A7A8 A9
A3 B3
B5 B6B7B8 B9
B1 B2B3B4
A5 B5 A6 B6
A4 B4 G1G2
A8 B8
A7 B7
TPU-45-01
Removable terminal plugs, push-in type; complete set of 9 plugs (for
terminals 1 - 47); for the CLEA2014Bxx and CLEA2026Bxx.
MVC-80-AC1
Terminal cover (color: RAL9011); package of 10; for EAGLE
Controllers.
MVC-80-AC2
Front door mounting accessory (color: RAL9011); package of 10; for
EAGLE Controllers.
MVC-40-AC3
Strain relief; package of ten; for EAGLE Controllers.
Set of ten terminals. Each Auxiliary Terminal Package consists of two
groups of nine internally connected push-in terminals, for distributing
XS830
XS831
signals / power. For the Mixed Panel Bus I/O Module and the EAGLE
Controller, only. Please refer to CentraLine I/O Modules - Installation &
Commissioning Instructions (EN1Z-0973GE51) for more information.
Set of ten terminals. Each Auxiliary Terminal Package consists of two
groups of four pairs of push-in terminals (each with a 499 Ω resistor),
for converting 0…20 mA signals into 0…10 VDC signals, and one
push-in ground terminal per group. For the Mixed Panel Bus I/O
Module and the EAGLE Controller, only. Please refer to CentraLine I/O
Modules - Installation & Commissioning Instructions (EN1Z-0973GE51)
for more information.
External HMI with LCD display which derives needed electrical energy
CLEAHMI21
from the EAGLE controller. Suitable for connection to the RJ45 socket
on the front of the CLEA2000B31, CLEA2014B31, CLEA2014B32, and
CLEA2026B31.
The EAGLE Controller features two RS485 interfaces to which Panel Bus modules can be connected: RS485-1 (consisting of
push-in terminals 24 [GND-1], 25, and 26) and/or RS485-2 (consisting of push-in terminals 29, 30, and 31 [GND-2]).
NOTE:GND-2 is internally connected with 24V-0 (terminal 1) and system GND (terminals 19+37)
Overview of Panel Bus I/O Modules
pluggable
ANALOG INPUT
pluggable
ANALOG OUTPUT
pluggable
BINARY INPUT
pluggable
RELAY OUTPUT
pluggable
FLOATING
OUTPUT
MIXED I/Os
(with integrated electronic m odule)
PANEL BUS I/O
ELECTRONIC
CLIOPR822A
CLIOPR824ACLIOPR825A
MODULES
CLIOP821A
EAGLE
CLIOP822ACLIOP823A
PANEL BUSPANEL BUSPANEL BUSPANEL BUS
XS821-22
XSU821-22
S823
XSU823
CLIOP824A
S824-25
SU824-25
Fig. 34. Overview of Panel Bus I/O Modules
Panel Bus Considerations
RS485-1 (isolated)
- Max. Panel Bus length:
o 40 meters. Any type of cabling and topology (including star and loop topology) possible. No additional end
termination permitted.
o 1200 meters (9.6 – 76.8 kbps) or 1000 meters (115.2 kbps) (see also section "RS485 Standard" on pg 9).
Mandatory twisted-pair or telephone cable and daisy chain topology. The EAGLE must be positioned at one end
of the Panel Bus, and an end termination (120 Ω) at the other end. Further, the three-position slide switch (see
Fig. 11 on pg. 8) must be set to "END."
RS485-2 (non-isolated)
- Max. Panel Bus length:
o 40 meters. Any type of cabling and topology (including star and loop topology) possible. No additional end
termination permitted.
o 1200 meters (9.6 – 76.8 kbps) or 1000 meters (115.2 kbps) (see also section "RS485 Standard" on pg 9).
Mandatory twisted-pair or telephone cable and daisy chain topology. The EAGLE Controller must be positioned at
one end of the Panel Bus, and an end termination (120 Ω) at the other end.
- Must not extend beyond a single building or building floor
Max. no. of Panel Bus I/O modules per RS485 interface
- Max. no. of Panel Bus I/O modules of a given model: 16
- Total max. no. of Panel Bus I/O modules: 64
Max. no. of Panel Bus I/O modules per EAGLE
- Max. no. of Panel Bus I/O modules of a given model: 32
- Total max. no. of Panel Bus I/O modules: 128 (see NOTE below)
Max. no. of hardware I/O points + NVs per EAGLE: 600
- Max. no. of mapped NVs allowed per EAGLE is thus 600 minus the no. of hardware I/O points.
NOTE:In the case of the CLEA2014B21 and CLEA2014B31, the total max. no. of Panel Bus I/O modules is reduced from
128 to only 64. See also section "Restriction Applying to CLEA2014B21 and CLEA2014B31" on pg. 8.
Refer to CentraLine I/O Modules - Installation & Commissioning Instructions (EN1Z-0973GE51) for more information about
connection, current requirements, power supply, overvoltage protection, cable specifications, fusing, effects of manual overrides,
etc. of Panel Bus I/O modules and field devices connected to them.
Connecting RS485-1 to Panel Buses
NOTE: When connecting RS485-1 of the EAGLE with Panel Bus I/O modules, it is recommended that the slide switch be set
RS485-1
GND-1
RS485-1
GND-1
ISO
550 OHM550 OHM150 OHM
RS485-1 (+) RS485-1 (-)
24V~
24~0
1 2
F1
24 V
230 V
to "END."
24
2526
EAGLE
GND-1+5V
END
END
BIAS
MID
CentraLine I/O Module
Com a
71
Com b
72
24V~
7377
24~0
74
R
T
120 Ohm
75
76
78
CentraLine I/O Module
Com a
71
Com b
72
24V~
7377
24~0
74
CentraLine I/O Module
Com a
71
Com b
72
24V~
7377
24~0
74
75
76
78
75
76
78
CentraLine I/O Module
71
72
7377
74
CentraLine I/O Module
71
72
7377
74
Fig. 35. Connecting RS485-1 of the EAGLE with Panel Bus I/O Modules (single transformer)
24
2526
EAGLE
CentraLine I/O Module
Com a
71
Com b
72
24V~
7377
24~0
74
75
76
78
CentraLine I/O Module
Com a
71
Com b
72
24V~
7377
24~0
74
75
76
78
CentraLine I/O Module
71
72
7377
74
Com a
Com b
24V~
24~0
Com a
Com b
24V~
24~0
Com a
Com b
24V~
24~0
75
76
78
75
76
78
75
76
78
ISO
+5V
550 OHM550 OHM150 OHM
RS485-1 (+) RS485-1 (-)
24V~
24~0
1 2
F1F1
24 V24 V
230 V230 V
END
MID
GND-1
CentraLine I/O Module
R
T
END
BIAS
120 Ohm
71
72
73
74
Fig. 36. Connecting RS485-1 of the EAGLE with Panel Bus I/O Modules (two transformers)
Each Panel Bus I/O Module must be addressed manually
using its HEX switch (S2). The HEX switch setting is defined
using the engineering tool.
PANEL BUS I/O MODULE
(EXAMPLE)
Fig. 39. Location of HEX switch on Panel Bus I/O Module
NOTE: A HEX switch setting of "0" corresponds to an
A max. of 16 Panel Bus I/O Modules of each type (AI, DO,
etc.) per RS485 interface (i.e., per Panel Bus) can be
assigned addresses. In doing so, no two modules of the same
type (e.g., no two Analog Input Modules, no two Digital Output
modules, etc.) per RS485 interface (i.e., per Panel Bus) may
be assigned the same address.
address in the engineering tool of "1," a setting of
"1" corresponds to an address of "2," and so on.
Cable Specifications
Panel Bus I/O Modules
When checking the length of the power supply cable, the
connection cables to all Panel Bus I/O Modules must be
taken into account.
Table 21. Power supply cable specifications
max. length
cross section
EIA 485 Cable Specifications
The following cable specification is valid for all EIA 485 buses
(e.g., Panel Bus and BACnet MS/TP).
Table 22. EIA 485 cable specifications
max. length
cable type
charac. impedance
distributed capacitance between
conductors
distributed capacitance between
conductors and shield
twisted pair, shielded (foil or
braided shields are acceptable)
100…130 Ω
Less than 100 pF per meter (30
pF per foot)
Less than 200 pF per meter (60
pF per foot)
(AWG 18)
The following cables fulfill this requirement:
AWG 18;
shielded, twisted pair cable J-Y-(St)-Y 2 x 2 x 0,8;
CAT 5,6,7 cable (use only one single pair for one bus);
Belden 9842 or 9842NH.
Field Devices
Depending on the distance from the controller, field devices
can be supplied with power by the same transformer used for
the Panel Bus I/O Modules, or by a separate transformer,
using cables as specified in Table 23.
Table 23. Power / communication cable specifications
cross-sectional area
type of signal
24 VAC power 1.5 mm2 (16 AWG)
0…10 V signals0.081 – 2.08 mm2 (28 – 14 AWG)
For wiring field devices, see section "Powering Panel Bus I/O
Modules and Field Devices" on page 16.
100 m (Fig. 27)
single transformer
400 m (Fig. 26)
sep. transformers
not allowed for
> 100 m (300 ft)
Routing Cables to Field Devices
Route low-voltage signal and output cables to field devices
separately from mains cables.
Table 24. Minimum distances to power mains cables
cable min. distance
shielded 10 mm (0.4 in.)
unshielded 100 mm (4 in.)
All low-voltage signal and output cables should be regarded
as communication circuits in accordance with VDE 0100 and
VDE 0800 (or NEC or other equivalent).
If the general guidelines for cable routing are observed, it
is not necessary to shield field device signal and power
supply cables.
If, for whatever reason, the routing guidelines cannot be
observed, the field device signal and power supply cables
must be shielded.
– Shielding of cables leading to field devices must be
grounded only at one end.
– Do not connect the shield to the EAGLE Controller.
The EAGLE can be connected to LONWORKS networks. This
requires the use of an IF-LON2 (see section "IF-LON2"
below), which is then plugged into to the EAGLE's USB 2.0
Host Interface (see also section "USB 2.0 Host Interface" on
pg. 7).
This permits individual EAGLE controllers to be connected /
disconnected from the L
the operation of other devices.
ONWORKS network is insensitive to polarity, eliminating
The L
the possibility of installation errors due to miswiring.
Different network configurations (daisy-chain, loop, and star
configurations, or any combination thereof) are possible (see
also Excel 50/500 L
Description, EN0B-0270GE51).
Connecting to the LONWORKS Network
IMPORTANT
Do not bundle wires carrying field device signals or
ONWORKS communications together with high-voltage
L
power supply or relay cables. Specifically, maintain a
min. separation of 3 inches (76 mm) between such
cables. Local wiring codes may take precedence over
this recommendation.
IMPORTANT
Try to avoid installing in areas of high electromagnetic
noise (EMI).
Cable Types
The unit must be wired to the LONWORKS network using either
When possible, use Honeywell AK3781, AK3782, AK3791, or
AK3792 cable (US part numbers). See Excel 50/5000
L
ONWORKS Mechanisms, EN0B-0270GE51, for details,
including maximum lengths.
Use wire with a minimum size of 20 AWG (0.5 mm
maximum size of 14 AWG (2.5 mm
IF-LON2
Optionally, communication with physical I/O modules, with
room and zone controllers, and with CentraLine PANTHER,
TIGER, and LION controllers can utilize LonTalk.
The IF-LON2 is equipped with a free-topology transceiver
(FTT10A) for communication (at a data transmission rate of
78 Kbaud) on L
protocol).
ONWORKS network is insensitive to polarity, eliminating
The L
the possibility of installation errors due to miswiring. Different
network configurations (daisy-chain, loop, and star configurations, or any combination thereof) are possible. See
Excel 50/5000 L
for details.
ONWORKS® networks (using the LonTalk
ONWORKS network without disturbing
ONWORKS Mechanisms Interface
2
2
).
ONWORKS Mechanisms (EN0B-0270GE51)
) and a
Fig. 40. IF-LON2
See also IF-LON2 – Mounting Instructions (MU1B0545GE51).
Depending upon the chosen network configuration, one or two
terminations may be required.
The following L
L
ONWORKS connection / termination module
ONWORKS termination module is available:
(mountable on DIN rails and in fuse boxes),
order no.: XAL-Term2
The EAGLE Controller features two RS485 interfaces to which BACnet MS/TP devices can be connected: RS485-1 (consisting
of push-in terminals 24 [GND-1], 25, and 26) and/or RS485-2 (consisting of push-in terminals 29, 30, and 31 [GND-2]).
NOTE:GND-2 is internally connected with 24V-0 (terminal 1) and system GND (terminals 19+37)
BACnet MS/TP Bus Considerations
RS485-1 (isolated)
˗ Max. BACnet MS/TP bus length: 1200 meters (9.6 – 76.8 kbps) or 1000 meters (115.2 kbps) (see also section "RS485
Standard" on pg 9).
˗ Use only shielded, twisted-pair cable and daisy-chain topology.
˗ Must conform to EIA-RS485 cabling guidelines.
RS485-2 (non-isolated)
˗ Max. BACnet MS/TP bus length: 1200 meters (9.6 – 76.8 kbps) or 1000 meters (115.2 kbps) (see also section "RS485
Standard" on pg 9).
˗ Use only shielded, twisted-pair cable and daisy-chain topology.
˗ Ground noise should not exceed the EIA-485 common mode voltage limit.
˗ Must conform to EIA-RS485 cabling guidelines.
˗ Should not extend beyond a single building.
Max. no. of BACnet MS/TP devices
˗ The max. number of BACnet MS/TP devices per RS485 interface depends on the given traffic. The current limit is 200
messages per minute. The max. number of room controllers is 20, assuming a typical traffic of 10 messages per minute.
In the case of non-room applications, the max. number of MS/TP devices can be up to 32 (including the EAGLE, itself) –
provided the traffic does not exceed 200 messages per minute. Following the same logic, the max. number of BACnet
MS/TP devices per EAGLE is 40 room controllers or 62 non-room MS/TP devices – provided the traffic does not exceed
200 messages per minute per RS485 interface.
Connecting RS485-1 to BACnet MS/TP Buses
With regards to Fig. 42 through Fig. 44, please note the following:
NOTE: Always power each EAGLE and the connected BACnet MS/TP modules via separate transformers.
NOTE: For "L," see section "RS485 Standard" on pg. 9.
NOTE: If any of the devices are electrically isolated, it is recommended that those devices be connected to signal ground.
Example 1: Single EAGLE Controller and Connected BACnet Modules (with inserted termination resistor)
GND-1
+5V
The termination resistor must be inserted directly into the terminals of the last BACnet MS/TP module.
See section "RS485 Standard" on pg. 9.
RS485-1
EAGLE
2425 26
ISO
550 OHM 150 OHM 550 OHM
RS485-1 (+) RS485-1 (-)
24V~
24~0
1 2
BACnet
Module #1
F1
24 V
230 V
MID
END
GND-1
END
BIAS
RS485 -
RS485 +
BACnet
Module #2
Fig. 42. Connection of RS485-1 to a BACnet MS/TP Bus
Example 2: Multiple EAGLE Controllers and Connected BACnet Modules
L
RS485-1RS485-1RS485-1RS485-1
EAGLEEAGLEEAGLEEAGLE
242425252626
GND-1GND-1
+5V
ISO
550 OHM550 OHM150 OHM150 OHM550 OHM550 OHM
RS485-1 (+)RS485-1 (+)RS485-1 (-)RS485-1 (-)
24V~
24~0
11112222
BACnet
Module #1
F1F1F1F1
24 V24 V24 V24 V
230 V230 V230 V230 V
GND-1GND-1
END
END
BIAS
MID
Module #2
RS485 -
RS485 +
BACnet
GND
242425252626
GND-1GND-1
+5V
ISO
47 kOHM47 kOHM
RS485-1 (+)RS485-1 (+)RS485-1 (-)RS485-1 (-)
24V~
24~0
BACnet
Module #3
47 kOHM
MID
MID
GND-1
END
BIAS
Module #4
*CONNECT GND, IF AVAILABLE.
RS485 -
RS485 +
BACnet
GND
+5V
ISO
24~0
24V~
BACnet
Module #N-1
47 kOHM
MID
MID
END
BIAS
GND-1
+5V
ISO
24V~
24~0
BACnet
Module #N
MID
END
END
BIAS
Fig. 43. Connection of RS485-1 to a BACnet MS/TP Bus
Example 3: Multiple EAGLE Controllers and Connected BACnet Modules (with inserted termination resistor)
L
R
T
120 Ohm
RS485-1RS485-1RS485-1RS485-1
EAGLEEAGLEEAGLEEAGLE
242425252626
GND-1GND-1
END
MID
GND-1
END
BIAS
Module #2
+5V
ISO
550 OHM550 OHM150 OHM 550 OHM
RS485-1 (+)RS485-1 (+)RS485-1 (-)RS485-1 (-)
24V~
24~0
11112222
BACnet
Module #1
F1F1F1F1
24 V24 V24 V24 V
230 V230 V230 V230 V
RS485 -
RS485 +
BACnet
GND
242425252626
GND-1GND-1
+5V
ISO
47 kOHM47 kOHM
RS485-1 (+)RS485-1 (+)RS485-1 (-)RS485-1 (-)
24V~
24~0
BACnet
Module #3
47 kOHM
MID
MID
GND-1
END
BIAS
*CONNECT GND, IF AVAILABLE.
Fig. 44. Connection of RS485-1 to a BACnet MS/TP Bus
The termination resistor must be inserted directly into the terminals of the last BACnet MS/TP module (in this example, that is
the rightmost EAGLE, the 3-position slide switch of which has been set to "BIAS.")
The EAGLE controller supports Modbus RTU Master functionality.
Modbus slaves can be connected to either of the two onboard RS485 interfaces (but not to both simultaneously): RS485-1
(consisting of push-in terminals 24 [GND-1], 25, and 26) or RS485-2 (consisting of push-in terminals 29, 30, 31 [GND-2]).
NOTE:GND-2 is internally connected with 24V-0 (terminal 1) and system GND (terminals 19+37)
Modbus Considerations
RS485-1 (isolated)
˗ Max. Modbus length: 1200 meters (9.6 – 76.8 kbps) or 1000 meters (115.2 kbps) (see also section "RS485 Standard" on
pg 9).
˗ Use only shielded, twisted-pair cable and daisy-chain topology.
˗ Must conform to EIA-RS485 cabling guidelines.
RS485-2 (non-isolated)
˗ Max. Modbus length: 1200 meters (9.6 – 76.8 kbps) or 1000 meters (115.2 kbps) (see also section "RS485 Standard" on
pg 9).
˗ Use only shielded, twisted-pair cable and daisy-chain topology.
˗ Ground noise should not exceed the EIA-485 common mode voltage limit.
˗ Must conform to EIA-RS485 cabling guidelines.
˗ Should not extend beyond a single building.
Max. no of Modbus devices per EAGLE: 32 (including the EAGLE, itself, which is counted twice)
Connecting RS485-1 to the Modbus
With regards to Fig. 47, please note the following:
NOTE: Always power each EAGLE and the connected Modbus slaves via separate transformers.
NOTE: For "L," see section "RS485 Standard" on pg. 9.
NOTE: If any of the devices are electrically isolated, it is recommended that those devices be connected to signal ground.
The EAGLE controller supports M-Bus Master functionality
via its onboard RS232 / RJ45 socket.
It uses standard PW3/PW20/PW60 converters to connect to
the M-Bus devices.
M-Bus Considerations
Max. no. of M-Bus devices per EAGLE: 60.
Bus Length
Max. M-Bus length: 350 meters from PW3 / PW20 /
PW60, at baud rates of 9.6 kbaud or slower with shielded,
twisted pair cable: J-Y-(St)-Y 2 x 2 x 0,8.
The M-Bus can be extended to 1,000 meters, depending
upon the baud rate, and provided that the following
electrical limitations are observed:
˗ Bus voltage must at no point fall below 12 VDC
˗ Maximum cable capacitance of 180 nF
For bus length extension, M-Bus repeaters can be used, but
have not been tested by Honeywell. Hence, it is the
responsibility of the installing / commissioning personnel to
ensure proper functioning.
Wiring Topology
M-Bus meters are connected to the bus cable in parallel.
SLAVE 1SLAVE 2SLAVE 3
EAGLE
Cabling EAGLE to PW3/PW20/PW60
Use the XW586 cable between the RS232 / RJ45 socket
of the EAGLE and the PW adapters.
The XW586 cable has a length of 1.8 m, and the pin-out
listed in Table 26.
In case a third-party cable is used instead of the XW586
cable, the third-party cable must have a max. length of
15 meters and a max. cable capacitance of 2,500 pF.
Fig. 51. XW586 power / communication cable details
Cabling PW3/PW20/PW60 to M-Bus
Use shielded, twisted pair cable J-Y-(St)-Y 2 x 2 x 0,8.
Shielding is especially recommended when the M-Bus
cable is installed in areas with expected or actual electromagnetic noise. Avoiding such areas is to be preferred.
Connect the shield to a noise-free earth ground – only
once per M-Bus connection.
Power the EAGLE controller and the PW M-Bus Adapter
with separate transformers – see WARNING below.
NOTE:If, alternatively, only a single transformer is avail-
able, when connecting a laptop, PC, web browser,
CL-Touch, or 3
rd
-party touch panel to the USB 2.0
Device Interface on the front of the EAGLE controller, use an optical isolator for the USB connection or substitute an M-Bus Mikro-Master USB
(Relay GmbH, D-33106 Paderborn) for the PW MBus Adapter.
1. Install the PW M-Bus Adapter on DIN rail. Insert a
screwdriver into the slot in the DIN rail clamp on the
underside of the PW and pry downward to loosen clamp
until the unit snaps onto the rail.
DIN RAIL
3
1
2
Fig. 52. Mounting of PW (PW3 shown here)
2. Connect the M-Bus devices to the PW M-Bus Adapter.
All M+ and M- terminals are connected in parallel in the
PW M-Bus Adapter.
INSERT
METER-BUS
WIRES
EAGLE
J1 J8
RS232 / RJ45
SOCKET
XW586
M-BUS
DEVICE
Fig. 54. Connecting the EAGLE to the PW M-Bus adapter
4. Connect 24 V power to the M-Bus Adapter.
WARNING
Risk of electric shock or equipment damage!
► Due to the risk of short-circuiting (see Fig. 23), it is strongly
recommended that the EAGLE controller be supplied with
power from a dedicated transformer. However, if the
EAGLE controller is to be supplied by the same transformer powering other controllers or devices (e.g., the PW
M-Bus Adapter), care must be taken to ensure that correct
polarity is observed.
CLEAxxxxxx
XW586
INSERT POWER
SUPPLY WIRES
Fig. 53. PW M-Bus adapter connections
3. Connect the PW M-Bus Adapter to the RS232 / RJ45
The following LEDs of the EAGLE Controller can be used for troubleshooting purposes:
Power LED (green)
Status LED (red)
Tx (sending data on RS485-1) and Rx (receiving data on RS485-1) LEDs
Power LED (green) of EAGLE
Table 27. EAGLE Controller power LED
case power LED meaning remedy
1 ON
2 OFF
Status LED (red) of EAGLE
case status LED meaning remedy
LED remains
1
OFF after
power-up
LED remains
2
ON
continuously
after power-up
Tx and Rx LEDs
case bus LEDs meaning remedy
1
Both Tx and Rx
are flashing
2
Both Tx and Rx
are OFF
3
Rx is flashing
and Tx is OFF
4
Tx is flashing
and Rx is OFF
Panel Bus I/O Module Troubleshooting
Please refer to CentraLine I/O Modules - Installation & Commissioning Instructions (EN1Z-0973GE51) for more information
about Panel Bus I/O module troubleshooting.
Normal operation No action necessary.
Power supply not OK.
Table 28. EAGLE Controller status LED
Normal operation. No action necessary.
– No or invalid firmware, or
– No or corrupt application, or
– License invalid or feature missing, or
– I/O module not found or configuration
mismatch, or
– Communication error, or
– Sensor failure on internal inputs, or
– Hardware error detected, or
– USB memory stick error.
Table 29. EAGLE Controller bus LEDs Tx and Rx
Normal operation; RS485-1 is functioning
properly.
No communication on RS485-1.
Communication on RS485-1 has been
switched OFF, but the EAGLE is receiving
data from other controllers.
The EAGLE Controller is attempting to
establish communication on RS485-1, but
there is no answer.
► Check power supply voltage.
► Check wiring.
► If problem persists, replace hardware.
► Try powering down and then powering up the
EAGLE Controller.
► If problem persists, check and – if necessary –
reload the application.
► If problem still persists, replace hardware.
No action necessary.
► Switch ON communication on RS485-1. L1 should
then flash. Further handling like case 4 (below).
► Switch ON communication on RS485-1. If this
proves unsuccessful, the hardware may be
defective.
► The communication rate (Kbaud) on RS485-1 has
not been correctly set; other controllers on the bus
may have been incorrectly assigned the same
device number; wiring problem or hardware defect.
In order to avoid distribution of noise or earth ground
potential differences over networks or other connections, the
EAGLE Controller is designed to be in compliance with
SELV (Safety Extra-Low Voltage).
Furthermore, SELV offers the greatest possible safety
against electrical impact.
To support SELV, all Honeywell external (CRT series) or
internal transformers comply with standard EN60742.
Earth grounding is therefore not recommended.
EAGLE Systems and Standard EN60204-1
However, if compliance with EN60204-1 is required, note the
following:
General Information about EN60204-1
EN60204-1 defines electrical safety for a complete
application/machine including controllers, sensors, actuators
and any connected/controlled electrical device.
EN60204-1 requires controllers to be powered by PELV
(Protective Extra-Low Voltage) and earth grounding of the
secondary side of the used transformers or earth grounding
of the system ground.
Earth grounding is prescribed to prevent unexpected startup of connected rotating/moving machines due to an
insulation fault and double earth grounding somewhere in
the plant.
In order to fulfill PELV (if earth grounding is prohibited), the
use of an earth leakage monitor is also possible.
When is EN60204-1 Applicable to EAGLE Systems?
Safety against electrical impact
– EN60204-1 is not mandatory; this is because electrical
safety is provided by the use of SELV and
transformers according to standard EN60742.
Safety against unexpected start-up of
rotating/moving machines
– If the application/plant does not contain machines that
can be harmful to the operator due to an unexpected
start-up, the standard EN60204-1 is not applicable.
If such machines are encountered, then EN60204-1 must be
followed. Grounding is required.
The following explains how to connect and earth multiple
CPUs (e.g., multiple EAGLEs, PANTHERs, TIGERs, LIONs,
etc. or any combination thereof) earth-grounded as per
EN60204-1.
NOTE: Use a noise-free earth ground inside the cabinet.
NOTE: If a field device that prohibits earth grounding is
► Connect earth ground to the respective terminal of the
supplied with electricity from its own dedicated
transformer.
connected to the system ground, an isolation
monitoring device must be used instead of earth
grounding.
CPU, see Fig. 57.
24V~24V~0
CPU 1
21
RS485-2 + RS485-2 -
29 30
I/O MODULEI/O MODULE
COM
COM
24V~24V~24V~024V~0
B
A
7474727273737171
COM
COM
B
A
► If system protective earth grounding is planned, use a
cable as short as possible for grounding:
min. 1.5 mm² (16 AWG).
► For connection details, refer to the following examples.
When connecting multiple CPUs to a single transformer, it is
imperative that the polarity of the power supply terminals of
the CPUs and the polarity of the transformer always correspond (namely: 24V-0 of the transformer must always be
connected to 24V-0 of the CPU, and 24V~ of the transformer must always be connected with 24V~ of the CPU).
Depending upon the individual CPU, the numbering of the
corresponding two terminals may possibly deviate from the
norm (which is usually "terminal 1 = 24V-0" and "terminal 2 =
24V~"). In the following example, CPU 3 has a deviating
numbering and must be connected accordingly.
NOTE: When using a single transformer for several
NOTE: If the field device transformer is physically far
NOTE: Use one star-point to split power for multiple
► Connect earth ground to the proper terminal of the CPU.
CPUs, each CPU ground must wired separately
to the star-point.
away from the CPUs, earth grounding must still
be performed for the controller.
The internal sensor inputs of the EAGLE Controller support both NTC10kΩ and NTC20kΩ sensors (see also section "Universal
Inputs" on page 19). The following table lists the typical minimum accuracies of the hardware and software for temperature
sensors.
Table 30. Accuracies of internal NTC20kΩ sensor inputs of the EAGLE
range measurement error (excl. sensor characteristics)
-50 … -20 °C (-58 … -4 °F) ≤ 5.0 K ≤ 5.0 K
-20 … 0 °C (-4 … +32 °F) ≤ 1.0 K ≤ 1.0 K
0 … 30 °C (32 … 86 °F) ≤ 0.5 K ≤ 0.3 K
30 … 70 °C (86 … 158 °F) ≤ 0.5 K ≤ 0.5 K
70 … 100 °C (158 … 212 °F) ≤ 1.0 K ≤ 1.0 K
100 … 130 °C (212 … 266 °F) -- ≤ 3.0 K
130 … 150 °C (266 … 302 °F) -- ≤ 5.5 K
150 … 400 °C (302 … 752 °F) -- --
(1
NTC10kΩ specified for -30 … +100 °C, only.
NOTE:This is the accuracy of the internal sensor input (hardware + software [linearization]), only. This table does not include
the characteristics of the sensors, themselves (see section "Sensor Characteristics" below). If a different sensor or
sensor accuracy is required, one may instead use the inputs of, e.g., a connected Panel I/O module.
NTC10kΩ sensors
Recognition of Sensor Failure of Sensor Inputs
The thresholds at which sensor failures – i.e., sensor breaks (SB) and short-circuits (SC) – are recognized depends upon the
given sensor type. In the event of a recognized sensor failure, the sensor inputs assume the safety values configured in CARE.
Table 31 lists the measurement ranges and the corresponding thresholds for the recognition of sensor failure for the various
different sensor types:
Table 31. Thresholds for short-circuit (SC) and sensor-break (SB) recognition
I/O configuration measurement range recognition thresholds
2…10 V 2…10 V / 4…20 mA (without pull-up) SC: < 1.5 V / 3 mA; SB: no recognition
NTC10kΩ -30 … +100 °C SC: < 20 Ω; SB: < -70 °C
NTC20kΩ -50 … +150 °C SC: < 20 Ω; SB: < -70 °C
NOTE:In the case of temperatures lying outside the aforementioned ranges, the lowest/highest value within the range,
instead, will be communicated. Thus a temperature of -51 °C will be communicated as "-50 °C."
Sensor Characteristics
The characteristics (resistance in relation to temperature) of the sensors and the resultant voltage are listed on the following
pages. The stated values do not include failures due to: sensor failures; wiring resistance or wiring failures; misreadings due to a
meter connected to measure resistance or voltage at the input.
connection, 10, 31
via RS485-1, 4, 6, 8, 31
via RS485-2, 4, 6, 8, 32
Panel Bus
connection, 23
multiple rails, single transformer, 24, 25
via RS485-1, 4, 8
via RS485-2, 4, 8
power supply
failure indication, 35
power supply (field devices)
cable specifications, 26
via EAGLE, 16
via I/O module, 16
via I/O module via EAGLE, 16
power supply (Panel Bus I/Os)
cable specifications, 26
RS232 / RJ45 socket, 6, 7
safety
electrical safety as per EN60204-1, 36
general safety information, 2, 14
PELV, 36
SELV, 36
safety values/positions
safety positions of AOs, 19
safety positions of relays, 20
safety values of sensor inputs, 39
sensor characteristics
NTC 20 kOhm, 40
sensor input accuracies, 19, 39
AOs, 20
UIs, 19
USB
USB 2.0 Device Interface, 4, 6
details, 7
initially accessing EAGLE via Ethernet/IP, 21
USB 2.0 Host Interface, 4, 6
details, 7
XS830 Auxiliary Terminal Package
connection example, 18
XW-Online, 6, 7
Manufactured for and on behalf of the Environmental & Energy Solutions Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative: