Center EHE0200160 Installation Manual

42009085-013 R1
The Programmer should be mounted at a level where the display can be seen clearly and the ambient temperature is within the range of 0 to 45°C. The unit is for use in normal domestic environments.
To remove the unit from the wallplate, slacken the two securing screws and hinge the unit up to separate the two halves.
CAUTION: Isolate power supply and make safe before wiring the unit to prevent electric shock and equipment damage. Installation should be carried out by a qualified electrician or competent heating engineer.
Installation Guide
for EHE0200160 Programmer
Introduction
EHE0200160 is an Electronic Full Programmer providing accurate time control for central heating installations with separate programmes for heating and hot water. It can be used to program a heating schedule for weekdays (Monday – Friday) and weekends (Saturday and Sunday) independently.
Specification
Power Supply : 230V~, 50…60Hz, 8VA Switch Action : 2 x SPDT Switch Rating : 230V~, 50…60Hz, 3(3)A Timing Accuracy : ±1min./month Power Reserve : typically 4 days Approvals : CE marked
Mounting
Mounting Options
Heating
Hot Water
ON-OFF
OVERRIDE EXTRA HOUR
Mon
Tue Wed Thu Fri Sat Sun
ON-OFF ON-OFF
RECOMMENDED CLEARANCE DISTANCES:
ABOVE WALLPLATE: 40mm BELOW WALLPLATE: 100mm LEFT/RIGHT OF WALLPLATE: 10mm
b. Flush switchbox Fixing
holes are spaced to suit BS4662 requirements
c. Surface mounting with
surface wiring in mini trunking
a. Surface mounting
concealed wiring
Wiring
A switch, having contact separation of at least 3mm in all poles (formerly Class ‘A’), must be incorporated in the fixed wiring as a means of disconnecting the supply.
The unit is a Class II (double insulated) device. An earth terminal is provided for external earth continuity.
The system must be appropriately fused. A fuse rated at no more than 3 Amps should be installed.
The unit has 4 knockouts for surface wiring, care must be taken to ensure that the cable or mini-trunking completely fills the knockout hole without leaving any gaps.
ALL WIRING MUST BE IN ACCORDANCE WITH I.E.E. REGULATIONS. THIS UNIT IS FOR FIXED WIRING ONLY.
Replacing Other Manufacturers’ Time Controls
This Programmer will mount directly onto many existing manufacturers’ back-plates, without the need for re-wiring. However, it is also supplied complete with a wiring back-plate, should this not be the case.
Wiring Connections for EHE0200160 Programmer
Internal Wiring
Notes
1. The Programmer is a Class II (double insulated) device. An earth parking terminal is provided for earth wiring continuity, if required.
2. In the SUNDIAL S, W, and Y Plan wiring diagrams, connections are shown to basic boilers only. For wiring connections to Pump over-run boilers refer to Boiler manufacturers’ instructions.
3.
The Programmer is not suitable for basic gravity hot water control, unless using a C-Plan, because it incorporates independent heating and hot water switching.
Final Assembly
Clip the unit onto the hinges on the top of the wallplate and hinge down into position. Tighten the two securing screws using a screwdriver.
Switch on the power – the Programmer will now be operating according to the built-in programme. Refer to “USER GUIDE” for programming details.
If the display remains blank press the RESET button, located under the controls cover, with a blunt instrument (e.g. Pencil)
Y-Plan
C-Plan
S-Plan
W-Plan
ROOM STAT
2 3 1
CYL. STAT
2 1
C
MID-POSITION VALVE
BLUE
G/YELLOW
WHITE
GREY
ORANGE
3 AMPS
MAX
L N
230V~
50...60Hz
BOILER
PUMP
E N L
L N E
EHE0200160
*NOTE 1
N
L 1 2 3 4
1 2 3 4 5 6 7 8 9 10
ROOM STAT
2 3 1
CYL. STAT
2 1
C
2 PORT ZONE VALVE
HEATING
BLUE
G/YELLOW
BROWN
ORANGE
GREY
2 PORT ZONE VALVE
HOT WATER
BLUE
G/YELLOW
BROWN
ORANGE
GREY
3 AMPS
MAX
L N
230V~
50...60Hz
BOILER
PUMP
E N L
L N E
EHE0200160
*NOTE 1
1 2 3 4 5 6 7 8 9 10
N
L 1 2 3 4
2 PORT ZONE VALVE
BLUE
G/YELLOW
BROWN
WHITE
ORANGE
GREY
3 AMPS
MAX
L N
230V~
50...60Hz
BOILER
PUMP
E N L
L N E
EHE0200160
*NOTE 1
CYL. STAT
2 1
C
N
L 1 2 3 4
ROOM STAT
2 3 1
1 2 3 4 5 6 7 8 9 10
ROOM STAT
2 3 1
DIVERTING VALVE
G/YELLOW
BROWN
BLUE
CYL. STAT
2 1
C
3 AMPS
MAX
L N
230V~
50...60Hz
BOILER
PUMP
E N L
L N E
EHE0200160
*NOTE 1
N
L 1 2 3 4
1 2 3 4 5 6 7 8 9 10
Clock
N L 1 2 3 4
3 AMPS MAX
HW OFF
HW ON
CH OFF CH ON
N L
OFF ON OFF ON
230V~
50...60Hz
EHE0200160
Timed Outputs
Whilst every care has been taken to ensure that the information included in this document was accurate at the time of printing, we reserve the right to change specifications at any time. The photographs reproduced in this publication are within the constraints of the printing process and are NOT to be used for matching purposes. E&OE.
For further information telephone 0870 8506538