C.E. Niehoff & Co. N1335 Troubleshooting Guides

N1335 Alternator
Troubleshooting Guide
Hazard Defi nitions
These terms are used to bring attention to presence of hazards of various risk levels or to important information concerning product life.
Indicates presence of hazards that
CAUTION
will or can cause minor personal injury or property damage if ignored.
Indicates special instructions on
NOTICE
installation, operation or mainte­ nance that are important but not related to personal injury hazards.
Table of Contents
Section 1: Wiring .......................................................... 2
Section 2: CAN/J1939 Diagnostics ............................... 3
Section 3: Basic Troubleshooting ................................. 4
Section 4: Advanced Troubleshooting ..................... 5 - 6
Battery Conditions
Until temperatures of electrical
NOTICE
system components stabilize, these conditions may be observed during cold start voltage tests.
Maintenance/Low Maintenance Battery:
— Immediately after engine starts, system volts measure lower than regulator setpoint and system amps measure at a medium level. — 3-5 minutes into charge cycle, volts increase and amps decrease. — 5-10 minutes into charge cycle, volts reach regulator setpoint or very close, and amps decrease to a minimum. — Low maintenance battery has same characteris­ tics with slightly longer recharge times.
Maintenance-free Battery:
— Immediately after engine starts, system volts measure lower than regulator setpoint with low charging amps. — Once the charge cycle begins, low volts and low amps are still present. — After the alternator energizes, voltage will increase several tenths. Amps will increase gradually, then quickly, to medium to high amps. — Finally, volts will increase to setpoint and amps will decrease. The time it takes to reach optimum voltage and am­perage will vary with engine speed, load, and ambient temperature.
High-cycle Maintenance-free Battery:
— These batteries respond better than standard maintenance-free. Charge acceptance of these batteries may display characteristics similar to maintenance batteries.
Charge Volt and Amp Values
Volt and amp levels fluctuate depending on the battery state of charge. If batteries are in a state of discharge— as after extended cranking time to start the engine— system volts will measure lower than the regulator set­point after the engine is restarted and system amps will measure higher. This is a normal condition for the charging system; the greater the battery discharge level, the lower the system volts and the higher the system amps. The volt and amp readings will change as batter­ies recover and become fully charged: system volts will increase to regulator setpoint and system amps will decrease to low level (depending on other loads).
Low Amps: Minimum or lowest charging system
amp value required to maintain battery state of charge, obtained when testing the charging system with a fully charged battery and no other loads applied. This value will vary with battery type.
Medium Amps: System amps value which can cause
the battery temperature to rise above adequate charging temperature within 4-8 hours of charge time. To prevent battery damage, the charge amps should be reduced when battery temperature rises. Check battery manufacturer’s recommendations for proper charge amp rates.
High Amps: System amps value which can cause
the battery temperature to rise above adequate charging temperature within 2-3 hours of charge time. To prevent battery damage, the charge amps should be reduced when battery temperature rises. Check battery manufacturer’s recommendations for proper charge amp rates.
Battery Voltage: Steady-state voltage value as mea-
sured with battery in open circuit with no battery load. This value relates to battery state of charge.
Charge Voltage: Voltage value obtained when the
charging system is operating. This value will be higher than battery voltage and must never exceed the regulator voltage setpoint.
B+ Voltage: Voltage value obtained when measuring
voltage at battery positive terminal or alternator B+ terminal.
Surface Charge: Higher than normal battery voltage
occurring when the battery is disconnected from battery charger. The surface charge must be removed to determine true battery voltage and state of charge.
Significant Magnetism: Change in strength or
intensity of a magnetic field present in alternator rotor shaft when the field coil is energized. The magnetic field strength when the field coil is ener­gized should feel stronger than when the field is not energized.
Voltage Droop or Sag: Normal condition occurring
when the load demand on alternator is greater than rated alternator output at given rotor shaft RPM.
TG0052A
Page 1
Section 1: Wiring Diagram
CEN N1335 Alternators Description and Operation
N1335 28 V 300 A alternators are internally rectified. All windings and current-conducting components are non-moving, so there are no brushes or slip rings to wear out.
After engine is running, N3234 regulator receives ener­gize signal. Regulator monitors alternator rotation and provides field current only when it detects alternator shaft rotating at or above idle speed.
After regulator detects alternator rotation, it gradually applies field current, preventing an abrupt mechanical load on accessory drive system. The soft start may take up to 5 seconds.
N3234 regulator used with these units also
• is negative temperature compensated. Setpoint is
28.8 ± 0.5 V at 72 F when configured to operate with 6TMF type batteries.
• provides overvoltage cutout (OVCO). Regulator will trip OVCO when system voltage rises above setpoint by 3 V for longer than 3 seconds. OVCO feature detects high voltage and reacts by opening alternator field circuit and turning off alternator. Restarting engine or waiting until system voltage drops 5 V below setpoint will reset OVCO circuit.
• maintains alternator steady-state output voltage at regulated settings as vehicle electrical loads are switched on and off.
(next to regulator connector)
B+ terminal
T
T
B– terminal
Figure 1 — N1335 Alternator and
N3234 Regulator Terminals
E terminal
F- terminal
T
T
Page 2
Figure 2 — N1335 Alternators with N3234 Regulator
TG0052A
Loading...
+ 4 hidden pages