C.E. Niehoff & Co. C726 Troubleshooting Guides

C726 Alternator
Troubleshooting Guide
These terms are used to bring attention to presence of hazards of various risk levels or to important information concerning product life. Indicates presence of hazards that
CAUTION
will or can cause minor personal injury or property damage.
Indicates special instructions on
NOTICE
installation, operation or mainte­ nance that are important but not related to personal injury hazards.
Table of Contents
Section A: Wiring Diagram ......................................2
Section B: Basic Troubleshooting ............................3
Section C: Advanced Troubleshooting ................ 4 – 5
Battery Conditions
Until temperatures of electrical
NOTICE
system components stabilize, these conditions may be observed during cold-start voltage tests.
Maintenance/Low Maintenance Battery — Immediately after engine starts, system volts are lower than regulator setpoint, amps are medium. — 3–5 minutes into charge cycle, system volts increase, amps decrease. — 5–10 minutes into charge cycle, system volts increase to, or near, regulator setpoint and amps decrease to a minimum. — Low maintenance battery has same characteristics with slightly longer recharge times.
Maintenance-free Battery — Immediately after engine starts, system volts are lower than regulator setpoint, low charging amps. — Once charge cycle begins, low volts and low amps are still present. — After alternator energizes, voltage will increase several tenths. Amps will increase gradually, then quickly, to medium to high amps. — F i n a l l y , v o l t s w i l l i n c r e a s e t o s e t p o i n t a n d a m p s w i l l decrease. The time it takes to reach optimum voltage and amper­age will vary with engine speed, load, and ambient temperature.
High-cycle Maintenance-free Battery These batteries respond better than standard mainte­nance-free. Charge acceptance of these batteries may display characteristics similar to maintenance batteries.
AGM (Absorbed Glass Mat) Maintenance-free Battery These dry-cell batteries respond better than standard maintenance-free. If battery state of charge drops to 75% or less, batteries should be recharged to 95% or higher separately from the engine’s charging system to avoid damaging charging system components and to provide best overall performance. Charge acceptance of these batteries may display maintenance batteries.
characteristics similar to
Battery Charge Volt and Amp Values
Volt and amp levels fluctuate depending on the battery state of charge. If batteries are in a state of discharge—as after extended cranking time to start the engine—system volts will measure lower than the regulator setpoint after the en­gine is restarted and system amps will measure higher. This is a normal condition for the charging system; the greater the battery discharge level, the lower the system volts and the higher the system amps. The volt and amp readings will change as batteries recover and become fully charged: system volts will increase to regulator setpoint and system amps will decrease to low level (depending on other loads).
Low Amps: Minimum or lowest charging system amp value required to maintain battery state of charge, obtained when testing the charging system with a fully charged battery and no other loads applied. This value will vary with battery type.
Medium Amps: System amps value which can cause the battery temperature to rise above adequate charging temperature within 4-8 hours of charge time. To pre­vent battery damage, the charge amps should be reduced when battery temperature rises. Check battery manufacturer’s recommendations for proper charge amp rates.
High Amps: System amps value which can cause the battery temperature to rise above adequate charging temperature within 2-3 hours of charge time. To pre­vent battery damage, the charge amps should be reduced when battery temperature rises. Check battery manufacturer’s recommendations for proper charge amp rates.
Battery Voltage: Steady-state voltage value as mea- sured with battery in open circuit with no battery load. This value relates to battery state of charge.
Charge Voltage: Voltage value obtained when the charging system is operating. This value will be higher than battery voltage and must never exceed the regula­tor voltage setpoint.
B+ Volta ge: Voltage value obtained when measuring voltage at battery positive terminal or alternator B+ terminal.
Surface Charge: Higher than normal battery voltage occurring when the battery is disconnected from battery charger. The surface charge must be removed to determine true battery voltage and state of charge.
Significant Magnetism: Change in strength or intensi- ty of a magnetic field present in alternator rotor shaft when the field coil is energized. The magnetic field strength when the field coil is energized should feel stronger than when the field is not energized.
Voltage Droop or Sag: Normal condition occurring when the load demand on alternator is greater than rated alternator output at given rotor shaft RPM.
TG69A
Page 1
Section A: Wiring Diagram
CEN C726 Alternator Description and Operation
C726 42 V 380 A alternator is internally rectified. All windings and current-conducting components are non-moving, so there are no brushes or slip rings to wear out.
After engine is running, A2-339 regulator receives energize signal. Regulator monitors alternator rota­tion and provides field current only when it detects alternator shaft rotating at or above idle speed.
After regulator detects alternator rotation, it gradual­ly applies field current, preventing an abrupt me­chanical load on accessory drive system. The soft start may take up to 20 seconds.
A2-339 regulator used with these units also
• is negative temperature compensated. Setpoint is
42.0 V at 72 F.
• provides overvoltage cutout (OVCO). Regulator will trip OVCO when system voltage rises above 46 volts for longer than 3 seconds. OVCO feature detects high voltage and reacts by opening alter­nator field circuit and turning off alternator. Removing and reapplying energize signal at IGN terminal will reset OVCO circuit.
• maintains alternator steady-state output voltage at regulated settings as vehicle electrical loads are switched on and off.
B– terminal
IGN terminal
B+ terminal
Figure 1 — C726 Alternator and
A2-339 Regulator Terminals
P terminal
Page 2
BR
R
R
BK
G
BR
W
G
Figure 2 — Wiring Diagram
H G
F
E
D
C B
A
TG69A
Loading...
+ 3 hidden pages