C.E. Niehoff & Co. C709, C725 Troubleshooting Guides

Page 1
C.E. Niehoff & Co.
C709 and C725 Alternators
Troubleshooting Guide
Hazard Definitions
These terms are used to bring attention to presence of hazards of various risk levels or to important information concerning product life. Indicates presence of hazard(s)
CAUTION
that will or can cause minor personal injury or property damage if ignored.
Indicates special instructions on
NOTICE
installation, operation or mainte­ nance that are important but not related to personal injury hazards.
Table of Contents
Section A: Wiring Diagram ......................................2
Section B: Basic Troubleshooting ............................3
Section C: Advanced Troubleshooting ................ 4 – 8
Battery Conditions
Until temperatures of electrical
NOTICE
system components stabilize, these conditions may be observed during cold-start voltage tests.
— Immediately after engine starts, system volts are lower than regulator setpoint, amps are medium. — 3–5 minutes into charge cycle, system volts increase, amps decrease. — 5–10 minutes into charge cycle, system volts increase to, or near, regulator setpoint and amps decrease to a minimum. — Low maintenance battery has same characteristics with slightly longer recharge times.
Maintenance-free Battery
— Immediately after engine starts, system volts are lower than regulator setpoint, low charging amps. — Once charge cycle begins, low volts and low amps are still present. — After alternator energizes, voltage will increase several tenths. Amps will increase gradually, then quickly, to medium to high amps. — F i n a l l y , v o l t s w i l l i n c r e a s e t o s e t p o i n t a n d a m p s w i l l decrease. The time it takes to reach optimum voltage and amper­age will vary with engine speed, load, and ambient temperature.
High-cycle Maintenance-free Battery
These batteries respond better than standard mainte­nance-free. Charge acceptance of these batteries may display characteristics similar to maintenance batteries.
AGM (Absorbed Glass Mat) Maintenance-free Battery
These dry-cell batteries respond better than standard maintenance-free. If battery state of charge drops to 75% or less, batteries should be recharged to 95% or higher separately from the engine’s charging system to avoid damaging charging system components and to provide best overall performance. Charge acceptance of these batteries may display maintenance batteries.
characteristics similar to
Battery Charge Volt and Amp Values
Volt and amp levels fluctuate depending on the battery state of charge. If batteries are in a state of discharge—as after extended cranking time to start the engine—system volts will measure lower than the regulator setpoint after the engine is restarted and system amps will measure higher. This is a normal condition for the charging system; the greater the battery discharge level, the lower the system volts and the higher the system amps. The volt and amp readings will change as batteries recover and become fully charged: system volts will increase to regulator setpoint and system amps will decrease to low level (depending on other loads).
Low Amps: Minimum or lowest charging system amp
value required to maintain battery state of charge, obtained when testing the charging system with a fully charged battery and no other loads applied. This value will vary with battery type.
Medium Amps: System amps value which can cause
the battery temperature to rise above adequate charging temperature within 4-8 hours of charge time. To pre­vent battery damage, the charge amps should be reduced when battery temperature rises. Check battery manufacturer’s recommendations for proper charge amp rates.
High Amps: System amps value which can cause
the battery temperature to rise above adequate charging temperature within 2-3 hours of charge time. To pre­vent battery damage, the charge amps should be reduced when battery temperature rises. Check battery manufacturer’s recommendations for proper charge amp rates.
Battery Voltage: Steady-state voltage value as mea-
sured with battery in open circuit with no battery load. This value relates to battery state of charge.
Charge Voltage: Voltage value obtained when the
charging system is operating. This value will be higher than battery voltage and must never exceed the regula­tor voltage setpoint.
B+ Voltage: Voltage value obtained when measuring
voltage at battery positive terminal or alternator B+ terminal.
Surface Charge: Higher than normal battery voltage
occurring when the battery is disconnected from battery charger. The surface charge must be removed to determine true battery voltage and state of charge.
Significant Magnetism: Change in strength or inten-
sity of a magnetic field present in alternator rotor shaft when the field coil is energized. The magnetic field strength when the field coil is energized should feel stronger than when the field is not energized.
Voltage Droop or Sag: Normal condition occurring
when the load demand on alternator is greater than rated alternator output at given rotor shaft RPM.
TG64B
Page 1
Page 2
Section A: Description and Operation
CEN C709 and C725 Dual Voltage Alternators Description and Operation
C709 and C725 240 A (28 /14 V) dual voltage alterna­tors are internally rectified. All windings and current­conducting components are non-moving, so there are no brushes or slip rings to wear out. Energize switch (com­monly an oil pressure switch or ignition switch) acti­vates regulator. Field coil is then energized when rota­tion is detected. Upper voltage (28 V) is rectified with standard diodes. Lower voltage (14 V) circuit output cur­rent is controlled by SCRs. Alternator output current is self-limiting and will not exceed rated capacity of alter­nator.
A2-329 regulator used with these units also
• is flat temperature compensated. Setpoints are 28.0 ± 0.2 V and 14.0 ± 0.2 V.
• provides overvoltage cutout (OVCO). Regulator will trip above 32 V for 28 V system (16 V for 14 V system) longer than 2 seconds. OVCO feature detects high voltage and reacts by signaling relay in F– alternator circuit to open, turning off alternator. Restarting engine resets OVCO circuit. If vehicle is run in OVCO mode, OVCO will automatically reset when system charging voltages drop below 11 V for both 14 and 28 volt batteries. Regulator regains control of alternator below output voltage.
• maintains alternator output voltage at regulated settings as vehicle electrical loads are switched on and off.
28 V B+ terminal
14 V B+ terminal
B– terminal
E terminal
Figure 1 — C725 Alternator and
A2-329 Regulator Terminals
Page 2
Figure 2 — C709 and C725 Alternators with A2-329 Regulator
TG64B
Page 3
Section B: Basic Troubleshooting
Tools and Equipment for Job
• Digital Multimeter (DMM)
• Ammeter (digital, inductive)
• Jumper wires
Identification Record
List the following for proper troubleshooting:
Alternator model number _________________________
Regulator model number ________________________
Setpoint listed on regulator _______________________
Preliminary Check-out
Check symptoms in Table 1 and correct if necessary.
TABLE 1 – System Conditions
SYMPTOM
Low Voltage Output
High Voltage Output
No Voltage Output
No 14 V Output
Check: loose drive belt; low battery
state of charge.
Check: current load on system is
greater than alternator can produce.
Check: defective alternator or
regulator.
Check: wrong regulator.
Check: defective regulator.
Check: alternator.
Check: presence of energize signal.
Check: battery voltage at alternator
output terminal.
Check: defective alternator or
regulator.
Go to Chart 2, page 6.
ACTION
Basic Troubleshooting
1. Inspect charging system components
Check connections at ground cables, positive cables, and regulator harness. Repair or replace any damaged component before troubleshooting.
2. Inspect connections of vehicle batteries
Connections must be clean and tight.
3. Determine battery type, voltage and state
of charge Batteries must be all the same type for system
operation. If batteries are discharged, recharge or replace batteries as necessary. Electrical system cannot be properly tested unless batteries are charged 95% or higher. See page 1 for details. Nominal battery voltage for 28 V systems is 25.2 ±0.2 V; for 14 V systems is 12.6 ±0.2 V. Less than 25 V or 12.4 V indicates no charge condition when engine is running.
4. Connect meters to alternator Connect red lead of DMM to alternator 28 V B+ terminal and black lead to alternator B – terminal. Clamp inductive ammeter on 28 V B+ cable.
5. Operate vehicle Observe charge voltage at batteries with engine running (nom. 27-28 V or 13.5-14.0 V).
If charge voltage is above 32 V
for 28 V system or 16 V for 14 V system, immediately shut down system. Electrical system damage may occur if charging system is allowed to operate at excessive voltage. Go to Table 1 at left.
If voltage is at or below regulator setpoint, let
charging system operate for several minutes to normalize operating temperature.
6. Observe charge volts and amps in each circuit Charge voltage should increase and charge amps should decrease. If charge voltage does not in- crease within ten minutes, continue to next step.
7. Batteries are considered fully charged if charge voltage is at regulator setpoint and charge amps remain at lowest value for 10 minutes.
8. If charging system is not performing properly, go to Chart 1, page 5.
CAUTION
TG64B
Page 3
Page 4
Section C: Advanced Troubleshooting
A2-329 Regulator
DESCRIPTION AND OPERATION
A2-329 Regulator with OVCO is attached directly to the outside of alternator. Regulator setpoint has f lat temper­ature compensation. Voltage setpoint is 28.0 ±1.0 V and
14.0 ±0.5.
OVCO (overvoltage cutout) will trip at any of the following conditions:
• 14 V side trips at voltage higher than regulator
setpoint that exists longer than 3 seconds of reading voltage above 16 V. OVCO feature detects overvoltage and reacts by disabling the alternator field circuit. This turns off alternator. OVCO circuit will reset by either: — Restarting engine (regulator regains control of alternator output voltage) OR
— System voltage on both 14 and 28 volt batteries
falling below 11 V. OVCO will automatically reset.
• 28 V side trips at voltage higher than regulator
setpoint that exists longer than 3 seconds of reading voltage above 32 V. OVCO feature detects overvoltage and reacts by disabling the alternator field circuit. This turns off alternator. OVCO circuit will reset by either: — Restarting engine (regulator regains control of alternator output voltage) OR
— System voltage on both 14 and 28 volt batteries
falling below 11 V.
Trou ble sh oot ing
Shut down vehicle and restart engine. If alternator functions normally after restart, a “no output condition” was normal response of voltage regulator to overvoltage condition. Inspect condition of electrical system, includ­ing loose battery cables, both positive and negative. If battery disconnects from system, it could cause overvolt­age condition in electrical system, causing OVCO circuit to trip.
If you have reset alternator once, and electrical system returns to normal charge voltage condition, there may have been a one time, overvoltage spike that caused OVCO circuit to trip.
If OVCO circuit repeats cutout a second time in short succession and shuts off alternator field circuit, try third restart. If OVCO circuit repeats cutout a third time, go to Chart 3a or 3b, page 7.
Page 4
TG64B
Page 5
Section C: Advanced Troubleshooting (CONT’D)
Chart 1 – No 28V Alternator Output – Test Charging Circuit
STATIC TEST – KEY ON, ENGINE OFF
Shut down vehicle and restart engine. Does alternator function normally after restart?
Yes
Regulator responded to overvoltage condition. Go to Chart 3 on page 7 to troubleshoot OVCO.
Shut off engine. With key on, engine off: Test for battery voltage at alternator 28 V B+ terminal. Does battery voltage exist?
Yes
Jumper 28 V B+ terminal on alternator to E terminal on regulator. Run engine. Wait 10 seconds. Does alternator charge?
Yes
No energize signal is present. Repair wiring harness in vehicle energize circuit. Retest alternator.
No
No
Repair vehicle wiring or recharge/replace batteries as necessary. Continue test.
No
CAUTION
When performing the following test, connect jumper wire away from pin A or not at pin A. Spark may erode pin.
Turn off engine, leave key off. Remove alterna­tor-to-regulator 5-pin harness from regulator. Momentarily (1 second) connect jumper wire from pin A in regulator harness plug to B– terminal on alternator. Spark will occur. Touch steel tool to shaft to detect significant magnetism. Is shaft magnetized?
Yes
Regulator is defective.
PIN CONNECTIONS A F– B unused C B– D 28 V B+ E Phase
Figure 3 – Alternator-to-Regulator 5-Pin Harness Plug
No
Alternator is defective.
TG64B
Page 5
Page 6
Section C: Advanced Troubleshooting (CONT’D)
Chart 2 – No 14 V Alternator Output – Test Circuit
Before starting test:
1. Remove 14 V B+ cable at alternator. Insulate cable to prevent arcing.
2. Connect test light across 14V B+ terminal on alternator and B–terminal on alternator.
Connect jumper from pin C on alternator-to-regulator 3-socket harness plug to 28 V B+ terminal on alternator. Does test light glow brightly?
Yes
Alternator is defective.
Substitute a known good regulator. Run engine. Is regulator setpoint voltage present?
Yes
No
No
Original regulator was defective.
Alternator is defective.
SOCKET CONNECTIONS
A 14 V B+
A
C
B unused
B
C 14 V Control
Page 6
Figure 4 – Alternator-to-Regulator 3-Socket Harness Plug
TG64B
Page 7
Section C: Advanced Troubleshooting (CONT’D)
Chart 3 – OVCO Trip – Determine 28 V or 14 V
With meter red lead on 28 V B+ at battery and black lead on chassis ground, start engine.
Watch meter dial: Does meter read battery charge above 29 V?
Yes
28 V side tripped OVCO circuit. Go to Chart 3b.
Chart 3a – No 14 V Alternator Output – Test OVCO Circuit
Disconnect alternator-to-regulator 3-pin harness from regulator. At receptacle on regulator, connect red lead from
DMM to pin C. Connect black lead to B– terminal. Does resistance read OL (out of limits)?
Yes
14 V side tripped OVCO circuit. Go to Chart 3a.
Alternator is defective.
PIN CONNECTIONS
C
B
Figure 5 – Alternator-to-Regulator 3-Pin Harness Receptacle
A 14 V B+
A
B unused C 14 V Control
Chart 3b – No 28 V Alternator Output – Test OVCO Circuit
Replace regulator with known good regulator. Run engine. Does OVCO trip?
Yes
Alternator is defective.
No
No
No
Original regulator is defective.
Unplug alternator-to-regulator 5-pin harness from regulator. Connect red lead from DMM to pin A in plug. Connect black lead to pin D in plug. Does resistance read 1.0 ± 0.2 ohms?
Yes
No
Alternator is defective.
Set DMM to auto-ranging scale. Connect red lead from DMM to pin A in plug. Connect black lead to B– terminal. Does resistance read OL (out of limits)? Then connect red lead to pin D and black lead to B– terminal. Does resistance read OL (out of limits)?
Yes
Replace existing regulator with known good regulator. Run engine. Does OVCO trip?
Yes
Alternator is defective.
Original regulator is defective.
No
Alternator is defective.
Figure 6 – Alternator-to-Regulator 5-Pin Harness Plug
No
PIN CONNECTIONS A F– B unused C B– D 28 V B+ E Phase
TG64B
Page 7
Page 8
Section C: Advanced Troubleshooting (CONT’D)
14 V Functions
Normal Resistance
Lead Connections from DMM Reading Component Tested
red to pin C in 3-pin receptacle and black to socket C in 5-socket receptacle OL* 14 V control signal
red to socket C in 3-socket plug and SCR gate in black to socket A in 3-socket plug 7-13 anti-drive end housing
28 V Functions
Lead Connections from DMM Normal to 5-socket Receptacle Reading Component Tested
red to socket A and black to socket C OL* (resistance) Power transistor
Short tone on red to socket A and black to socket D Diode Checker* Supressor diode
* If readings register other than those shown, regulator is defective. ** If readings register other than those shown, anti-drive end housing is defective.
5-PIN CONNECTIONS A F– B unused C B– D 28 V B+ E Phase
Figure 7 – Alternator-to-Regulator 5-Pin Harness Plug Figure 8 – Alternator-to-Regulator 3-Socket
5-SOCKET CONNECTIONS A F– B unused C B– D 28 V B+ E Phase
Figure 9 – Alternator-to-Regulator Harness Connections at Regulator – 5-Socket Receptacle and 3-Pin Receptacle
A
B
E
C
D
C
A
C
B
A
B
A 14 V B+ B unused C 14 V Control
3-SOCKET CONNECTIONS A 14 V B+ B unused C 14 V Control
Harness Plug
3-PIN CONNECTIONS
If you have quest ions about your alternator or any of these test procedures, or if you need to locate a Factory Authorized Service Dealer, please contact us at:
C. E. Niehoff & Co. • 2021 Lee Street • Evanston, IL 60202 USA
TEL: 800.643.4633 USA and Canada • TEL: 847.866.6030 outside USA and Canada • FAX: 847.492.1242
E-mail us at service@CENiehoff.com
Page 8
TG64B
Loading...