C.E. Niehoff & Co. C627, C628, C631, C656, C657 Troubleshooting Guides

...
C627, C628, C631, C656, C657, C658, C671 and C680
Alternator Troubleshooting Guide
Hazard Denitions
These terms are used to bring attention to presence of hazards of various risk levels or to important information concerning product life. Indicates presence of hazards that
CAUTION
will or can cause minor personal injury or property damage.
Indicates special instructions on
NOTICE
installation, operation or mainte­ nance that are important but not related to personal injury hazards.
Table of Contents
Section A: Alternator Description and Operation . 2–3
Section B: Basic Troubleshooting ............................ 4
Section C: Comprehensive Troubleshooting ......... 5–7
Battery Conditions
Until temperatures of electrical
NOTICE
system components stabilize, these conditions may be observed during cold start voltage tests.
• Maintenance/low maintenance battery: — Immediately after engine starts, system volts are lower than regulator setpoint with medium amps. — 3-5 minutes into charge cycle, higher system volts and reduced amps. — 5-10 minutes into charge cycle, system volts are at, or nearly at, regulator setpoint, and amps are reduced to a minimum. — Low maintenance battery has same characteris­ tics with slightly longer recharge times.
• Maintenance-free battery: — Immediately after engine start, system volts are lower than regulator setpoint with low amps. — 15-30 minutes into charge cycle, still low volts and low amps. — 15-30 minutes into charge cycle, volts increase several tenths. Amps increase gradually, then quickly to medium to high amps. — 20-35 minutes into charge cycle, volts increase to setpoint and amps decrease.
• High-cycle maintenance-free battery: — These batteries respond better than standard maintenance-free. Charge acceptance of these batteries may display characteristics similar to maintenance batteries.
Charge Volt and Amp Values
The volt and amp levels are a function of the battery state of charge. If batteries are in a state of discharge, as after extended cranking time to start the engine, the system volts, when measured after the engine is started will be lower than the regulator set point and the system amps will be high. This is a normal condition for the charging system. The measured values of system
volts and amps will depend on the level of battery discharge. In other words, the greater the battery discharge level the lower the system volts and higher the system amps will be. The volt and amp readings will change, system volts reading will increase up to regula­tor set point and the system amps will decrease to low level (depending on other loads) as the batteries recover and become fully charged.
Low Amps: A minimum or lowest charging system
amp value required to maintain battery state of charge, obtained when testing the charging system with a fully charged battery and no other loads applied. This value will vary with battery type.
Medium Amps: A system amps value which can
cause the battery temperature to rise above the adequate charging temperature within 4-8 hours of charge time. To prevent battery damage the charge amps should be reduced when battery temperature rises. Check battery manufacturer’s recommenda­tions for proper rates of charge amps.
High Amps: A system amps value which can cause
the battery temperature to rise above adequate charging temperature within 2-3 hours. To prevent battery damage the charge amps should be reduced when the battery temperature rises. Check battery manufacturer’s recommendations for proper rates of charge amps.
Battery Voltage: Steady-state voltage value as meas-
ured with battery in open circuit with no battery load. This value relates to battery state of charge.
Charge Voltage: A voltage value obtained when the
charging system is operating. This value will be higher than battery voltage and must never exceed the regulator voltage set point.
B+ Voltage: A voltage value obtained when measur-
ing voltage at battery positive terminal or alternator B+ terminal.
Surface Charge: A higher than normal battery volt-
age occurring when the battery is removed from a battery charger. The surface charge must be removed to determine true battery voltage and state of charge.
Significant Magnetism: A change in the strength or
intensity of a magnetic field present in the alternator rotor shaft when the field coil is energized. The mag­netic field strength when the field coil is energized should feel stronger than when the field is not ener­gized.
Voltage Droop or Sag: A normal condition which
occurs when the load demand on the alternator is greater than rated alternator output at given rotor shaft RPM.
TG30G
Page 1
Section A: Alternator Description and Operation
CEN C656, C657, C658, C671, and C680 Alternator Description and Operation
C656, C657, C658, and C671 14 V (400 A) and C680 14 V (430 A) alternators are self-rectifying. All
windings and current-transmitting components are non-moving, so there are no brushes or slip rings to wear out.
When C656 is controlled by the A2-149 regulator, this alternator becomes self-energizing through inter­nal diode trios in the drive end housing. Residual magnetic field induces small voltage in stator and energizes field coil. Field coil continues receiving incremental voltage until full voltage is achieved. See Figure 1. AC is rectified into DC output through diodes. Regulator controls voltage output. A2-149 regulator has a D+ terminal to provide a signal to vehicle electrical system, confirming alternator operation, and an R terminal to provide an optional AC voltage tap.
When C656, C657, C658, and C680 are controlled by the A2-155 regulator, these alternators become exter- nally energized through the IGN terminal connected to a switched power source to turn on regulator. See Figure 2. A2-155 regulator has a P terminal to pro­vide an optional AC voltage tap.
Figure 1 — Alternator with A2-149 Regulator
REGUL ATOR
CEN C627, C628, and C631 Alternator Description and Operation
C627 14 V (340A), C628 14 V (290 A), and C631 14 V (350 A) alternators are self-rectifying. All windings and current-transmitting components are non-mov­ing, so there are no brushes or slip rings to wear out.
When C627, C628, and C631 are controlled by the A2-155 regulator, these alternators become externally energized through the IGN terminal connected to a switched power source to turn on regulator. See Figure 2. A2-155 regulator has a P terminal to provide an optional AC voltage tap. Regulator can be mounted on the drive end or anti-drive end housing.
Figure 2 — Alternator with A2-155 Regulator
Page 2
TG30G
Section A: Alternator Description and Operation (CONT’D)
A2-149: D+ terminal A2-155: IGN terminal
B+ terminal stud (on rear of control unit)
B– terminal stud
Figure 3 — C627/C628/C631/C656/C657
Alternator Terminals
IGN terminal
P terminal
A2-149: R terminal A2-155: P terminal
B+ terminal stud (on rear of control unit)
B+ terminal stud
Figure 5 — C671 Alternator Terminals
B+ terminal stud
P terminal
IGN terminal
B– terminal stud
IGN terminal
P terminal
B– terminal stud
Figure 4 — C658 Alternator Terminals
B– terminal stud
Figure 6 — C680 Alternator Terminals
TG30G
Page 3
Loading...
+ 4 hidden pages