C.E. Niehoff & Co. C622 Troubleshooting Guides

600 Series Troubleshooting Guide
for C622 Alternators
Hazard Definitions
These terms are used to bring attention to presence of hazards of various risk levels or to important information concerning product life.
DANGER
death or substantial property damage if ignored.
CAUTION
personal injury or property damage if ignored.
NOTICE
maintenance that are important but not related to personal injury hazards.
Indicates presence of hazards that will cause severe personal inury,
Indicates presence of hazards that will or can cause minor
Indicates special instructions on installation, operation or
Table of Contents
Section 1: Wiring Diagram ...................................... 2
Section 2: Basic Troubleshooting ........................... 3
Section 3: Advanced Troubleshooting ................4 – 7
Battery Conditions
NOTICE
conditions may be observed during cold start voltage tests.
Maintenance/low maintenance battery: — Immediately after engine starts, system volts
are lower than regulator setpoint with medium amps.
— 3-5 minutes into charge cycle, higher system
volts and reduced amps.
— 5-10 minutes into charge cycle, system volts
are at, or nearly at, regulator setpoint, and amps are reduced to a minimum.
— Low maintenance battery has same charac-
teristics with slightly longer recharge times.
Maintenance-free battery: — Immediately after engine start, system volts
are lower than regulator setpoint with low charging amps.
— 15-30 minutes into charge cycle, still low volts
and low amps.
— 15-30 minutes into charge cycle, volts increase
several tenths. Amps increase gradually, then quickly to medium to high amps.
— 20-35 minutes into charge cycle, volts increase
to setpoint and amps decrease.
High-cycle maintenance-free battery: — These batteries respond better than standard
maintenance-free. Charge acceptance of these batteries may display characteristics similar to maintenance batteries.
Until temperatures of electrical system components stabilize, these
Charge Volt and Amp Values
The volt and amp levels are a function of the battery state of charge. If batteries are in a state of discharge, as after extended cranking time to start the engine, the system volts, when measured after the engine is started
will be lower than the regulator setpoint and the system amps will be high. This is a normal condition for the charging system. The measured values of system volts and amps will depend on the level of battery discharge. In other words, the greater the battery discharge level, the lower the system volts and higher the system amps will be. The volt and amp readings will change, system volts reading will increase up to regulator setpoint and the system amps will decrease to low level (depending on other loads) as the batteries recover and become fully charged.
Low Amps: A minimum or lowest charging system amp value required to maintain battery state of charge, obtained when testing the charging system with a fully charged battery and no other loads applied. This value will vary with battery type.
Medium Amps: A system amps value which can cause the battery temperature to rise above the adequate charging temperature within 4-8 hours of charge time. To prevent battery damage, the charge amps should be reduced when battery temperature rises. Check battery manufacturer’s recommenda­tions for proper rates of charge amps.
High Amps: A system amps value which can cause the battery temperature to rise above adequate charging temperature within 2-3 hours. To prevent battery damage the charge amps should be reduced when the battery temperature rises. Check battery manufacturer’s recommendations for proper rates of charge amps.
Battery Voltage: Steady-state voltage value as measured with battery in open circuit with no battery load. This value relates to battery state of charge.
Charge Voltage: A voltage value obtained when the charging system is operating. This value will be higher than battery voltage and must never exceed the regulator voltage setpoint.
B+ Voltage: A voltage value obtained when measur­ing voltage at battery positive terminal or alternator B+ terminal.
Surface Charge: A higher than normal battery voltage occurring when the battery is removed from a battery charger. The surface charge must be removed to determine true battery voltage and state of charge.
Significant Magnetism: A change in the strength or intensity of a magnetic field present in the alternator rotor shaft when the field coil is energized. The magnetic field strength when the field coil is ener­gized should feel stronger than when the field is not energized.
Voltage Droop or Sag: A normal condition which occurs when the load demand on the alternator is greater than rated alternator output at given rotor shaft RPM.
TG0011A
Page 1
Section 1: Wiring Diagram
CEN C622 Alternator Description and Operation
C622 28 V 100 A/84 V 50 A alternator is internally rectified. All windings and current-transmitting components are non-moving, so there are no brushes or slip rings to wear out. This unit is externally energized through an energize switch (commonly an oil pressure switch), which activates regulator. Field coil is then energized. 84 V system is not energized until 28 V system is energized. 84 V and 28 V circuit output currents are controlled by separate SCRs in the drive end housing. Alternator output current is self-limiting and will not exceed rated capacity of alternator.
A2-307 regulator used with these units:
maintains alternator output voltage at regulated settings as vehicle electrical loads are switched on and off.
monitors 28 V and 84 V systems separately.
A2-604 battery charge equalizer and A9-069 harness used with these units:
equalizes six 12 V batteries connected in series.
turns on when charge voltage is above 78 volts.
84 V LED Indicator
28 V B+ Terminal
Tricolor diagnostic LEDs (2 side-by-side)
TT
T
TT
84 V 28 V
A2-307 Regulator LEDs
TT
T
TT
TT
TT
T
TT
T
TT
NEG 84 V terminal
28 V E Terminal
TT
T
TT
TT
T
TT
T
TT
TT
POS 84 V terminal
TT
T
TT
28 V LED Indicator
28 V B– Terminal (either side)
DANGER
system. Severe personal injury or death will result from contact.
HIGH VOLTAGE. Use extreme caution when working around 84 V
Figure 1 — C622 Alternator Terminals
Page 2
Figure 2 — C622 Alternator with Regulator
TG0011A
Section 2: Basic Troubleshooting
A. Tools and Equipment for Job
Digital Multimeter (DMM)
Ammeter (digital, inductive)
Jumper wires
B. Identification Record
List the following for proper troubleshooting:
Alternator model number _____________________
❏ ❏
Regulator model number _____________________
Setpoint listed on regulator ___________________
Battery charge equalizer model number _______
Harness model number ______________________
C. Preliminary Check-out
Check symptoms in Table 1 and correct if necessary.
TABLE 1 – System Conditions
SYMPTOM
Low Voltage Output
High Voltage Output
No Voltage Output
No 84 V Output
Check: loose drive belt; low
battery state of charge.
Check: current load on system
is greater than alternator can produce.
Check: defective wiring or poor
ground path; low regulator setpoint.
Check: defective alternator
and/or regulator. Check: wrong regulator. Check: high regulator setpoint. Check: defective regulator. Check: alternator. Check: presence of energize
signal. Check: battery voltage at alter-
nator output terminal. Check: defective alternator
and/or regulator.
Go to “Steady Amber” in
Table 2, page 4.
ACTION
D. Basic Troubleshooting
DANGER
system. Severe personal injury or death will result from contact.
1. Inspect charging system components Check connections at ground cables, positive cables, and regulator harness. Repair or replace any damaged component before troubleshooting.
2. Inspect battery charge equalizer connections Connections must be in proper sequence and clean and tight. See Figure 4, page 6.
3. Inspect connections of vehicle batteries Connections must be clean and tight.
4. Determine battery type, voltage and state
of charge
Batteries must be all the same type for system operation. If batteries are discharged, recharge or replace batteries as necessary. Electrical system cannot be properly tested unless batter­ies are charged 95% or higher. See page 1 for details.
5. Connect meters to alternator Connect red lead of DMM to alternator 28 V B+ terminal and black lead to alternator 28 V B– terminal. Clamp inductive ammeter on 28 V B+ cable.
6. Operate vehicle Observe charge voltage.
CAUTION
or 85 V for 84 V system, immediately shut down system. Electrical system damage may occur if charging system is allowed to operate at excessive voltage. Go to Table 1 at left.
If voltage is at or below regulator setpoint, let charging system operate for several minutes to normalize operating temperature.
7. Observe charge volts and amps in each circuit Charge voltage should increase and charge amps should decrease. If charge voltage does not in­crease within ten minutes, continue to next step.
8. Batteries are considered fully charged if charge voltage is at regulator setpoint and charge amps remain at lowest value for 10 minutes.
9. If charging system is not performing properly, go to Chart 3, page 7.
HIGH VOLTAGE. Use extreme caution when working around 84 V
If charge voltage is above 33 volts for 28 V system
TG0011A
Page 3
Section 3: Advanced Troubleshooting
A2-307 Regulator
DESCRIPTION AND OPERATION
A2-307 Regulator with OVCO is attached directly to the outside of alternator. Set point of temperature compensation regulator is 82.0 V.
Main diagnostic feature of A2-307 regulator consists of two tricolored (red, amber, green) LEDs located on the side of the regulator. One LED indicates 28 V system performance, the other LED indicates 84 V system performance. The two LEDs work indepen­dently of each other, not in combination with each other. See Table 2 for diagnostic features and LED explanations.
OVCO (overvoltage cutout) will trip at any of the following conditions:
28 V side trips at voltage higher than regulator setpoint that exists longer than 2 seconds of reading voltage above 32 V. OVCO feature detects high voltage and reacts by signaling relay in F+ alternator circuit to open. This turns off alterna­tor (28 V LED is steady RED light). Restarting engine resets OVCO circuit. Regulator regains control of alternator output voltage.
84 V side trips at voltage higher than regulator setpoint that exists longer than 2 seconds of reading voltage above 85 V. OVCO feature detects high voltage and reacts by signaling relay in F+ alternator circuit to open. This turns off alterna­tor (84 V LED is steady RED light). Restarting engine resets OVCO circuit. Regulator regains control of alternator output voltage.
TROUBLESHOOTING
DANGER
system. Severe personal injury or death will result from contact.
HIGH VOLTAGE. Use extreme caution when working around 84 V
Shut down vehicle and restart engine. If alternator functions normally after restart, a “no output condi­tion” was normal response of voltage regulator to “high voltage” condition. Inspect condition of electri­cal system, including loose battery cables, both positive and negative. If battery disconnects from system, it could cause “high voltage” condition in electrical system, causing OVCO circuit to trip.
If you have reset alternator once, and electrical system returns to normal charge voltage condition, there may have been a one time, high voltage spike, causing OVCO circuit to trip.
If OVCO circuit repeats cutout a second time in short succession and shuts off alternator F+ circuit, try third restart. If OVCO circuit repeats cutout a third time, check color of LED while engine is running.
28 V RED LED - go to Chart 1, page 5.
84 V RED LED - go to Chart 2, page 5.
LED COLOR STATUS
OFF
FLASHING (once per second
for respective system voltage)
Green
Amber
Red
STEADY
Amber (84 V LED Only)
Red
FAST FLASHING RED
(at least two times per second for respective system voltage)
Page 4
TABLE 2 – A2-307 Regulator Diagnostics
Regulator is not energized. Measure E terminal voltage. If voltage above 21 V, regulator is defective.
Respective system voltage is at regulated setting and operating under control.
Respective system voltage is below regulated setting. Alernator is not producing power or circuit is overloaded.
Respective system voltage is above regulated setting. This may occur intermittently with voltage transients or with system faults.
Alternator is producing only 28 V output current. This will occur if 84 V batteries are discon­nected. Regulator remains in this mode until reset by restarting engine.
Alternator is shut down and is not producing power for either voltage. 28 V side trips after 2 seconds of reading voltage above 32 V. 84 V side trips after 2 seconds of reading voltage above 85 V. Regulator remains in this mode until reset by restarting engine.
Indicates regulator redundant control is lost. Service as soon as possible for alternator, regulator or wiring fault. High side voltage will continue to produce 84 V, but low voltage side will default to 26 V regulation to alert operator of control malfunction. Regulator remains in this mode until reset by restarting engine. See Chart 1, page 5.
TG0011A
Section 3: Advanced Troubleshooting
(CONT’D)
Chart 1 – 28 V RED LED On Steady – No Alternator Output – Test OVCO Circuit
Make sure batteries are properly charged before proceeding.
Disconnect ground cable from 28 V battery pack. Unplug alternator-to-regulator harness from regulator. Connect red lead from DMM to socket S in plug. Connect black lead to alternator 28 V B+ terminal. Does resistance read 2.2 ± 0.2 ohms?
Yes
TT
T
TT
Disconnect cable from alternator 28 V B+ terminal. Set DMM to ohms scale. Connect red lead from DMM to socket S in plug. Connect black lead to 28 V B– terminal. Does meter read OL (out of limits)?
Yes
Alternator is defective.
TT
T
TT
Reconnect cables. Replace existing regulator with known good regula­tor. Run engine. Does OVCO trip?
Yes
No
No
TT
T
TT
No
TT
T
TT
Alternator is defective.
TT
T
TT
Alternator is defective.
Chart 2 – 84 V RED LED On Steady – No Alternator Output – Test OVCO Circuit
Make sure batteries are properly charged before proceeding.
Replace regulator with known good regulator. Run engine. Does OVCO trip?
Alternator is defective.
TT
T
TT
Original regulator is defective.
DANGER
system. Severe personal injury or death will result from contact.
Yes
TT
T
TT
HIGH VOLTAGE . Use extreme caution when working around 84 V
No
TT
T
TT
Original regulator is defective.
TG0011A
Page 5
Section 3: Advanced Troubleshooting
(CONT’D)
A2-604 Battery Charge Equalizer and A9-069 Harness
DESCRIPTION AND OPERATION
A2-604 Battery Charge Equalizer is attached directly to the battery compartment.
Main diagnostic feature of A2-604 equalizer is an LED display located on the front of the equalizer. The equalizer measures battery charge voltage and “equalizes” battery voltage to prevent overcharge. See Table 3 for diagnostic features and LED display explanations.
TABLE 3 – A2-604 Battery Charge Equalizer Diagnostics
DISPLAY STATUS
0
1, 2, 3,
4, 5 or 6
in rotation
Flashing
one number
(not “0”)
C
(unlit)
DANGER
All batteries are equalized.
Number represents series location of battery that is at least 0.4 V higher than the others. Number will change frequently during operation.
Number represents series location of battery that is continuously overcharged. Perform battery tests to determine problem. Replace batteries as necessary.
Connections are in wrong position or at least one of the wires is disconnected.
Equalizer is off.
Do not allow batteries to overcharge. Battery can explode, resulting in severe personal injury, death or substantial property damage.
TABLE 4 – A9-069 Harness Plug
Pin Functions
Pin
A
B
C
D
E
F
G
Figure 3 – A9-069
Harness Plug
Function
12 V
24 V
36 V
48 V
60 V
72 V
0.0 V
Battery #
1
2
3
4
5
6
N/A
Page 6
DANGER
system. Severe personal injury or death will result from contact.
Figure 4 – A9-069 Harness Connections
HIGH VOLTAGE. Use extreme caution when working around 84 V
TG0011A
Section 3: Advanced Troubleshooting
Chart 3 – No Alternator Output – Test Charging Circuit
STATIC TEST – ENGINE OFF, BATTERY SWITCH ON, KEY ON
Test for battery voltage at alternator 28 V B+ terminal. Does battery voltage exist?
Ye s
Repair vehicle wiring as necessary. Continue test.
TT
T
TT
Jumper 28 V B+ terminal on alternator to E terminal on regulator. Touch shaft with steel tool to detect significant magnetism. Is shaft magnetized?
No
TT
T
TT
TT
T
TT
Yes
TT
T
TT
Go to energize switch on engine in E circuit. Test for battery voltage going into energize switch from battery. Does battery voltage exist?
Ye s
Repair vehicle circuit to energize switch. Continue test.
TT
T
TT
Make sure jumper wire from alternator 28 V B+ termi­nal to regulator E terminal is still attached.
Test for battery voltage at energize switch E terminal connection. Does battery voltage exist at energize switch?
Yes
TT
T
TT
E circuit from regulator to energize switch is good. Energize switch is defec­tive.
Repair vehicle circuit from E terminal on regulator to energize switch on engine.
No
TT
T
TT
TT
T
TT
No
TT
T
TT
No
TT
T
TT
Connect jumper wire from socket S in alter­nator-to-regulator harness plug to 28 V B– terminal on alternator. Spark will occur. Touch shaft with steel tool to detect signifi­cant magnetism. Is shaft magnetized?
Yes
TT
T
TT
Disconnect jumper wire. Connect DMM red lead to socket J in alternator-to-regulator harness plug. Connect black lead to socket H in same plug. Does battery voltage exist?
Yes
TT
T
TT
Regulator is defective.
No
TT
T
TT
Alternator is defective.
No
TT
T
TT
Alternator is defective.
TT
T
TT
Vehicle charging circuit test is complete. Remove jumper wire used in testing. Run engine and re-test charging circuit for operation.
TT
T
TT
TG0011A
SOCKET CONNECTIONS
Pin G, F, E 84 V Phase Pin R, Q, P 84 V SCR Gate Pin D 84 V NEG Pin C 84 V POS Pin S F – Pin J 28 V B+ Pin H 28 V B – Pin B, A, K 28 V Phase Pin M, L, T 28 V SCR Gate
Figure 5 – Alternator-to-Regulator Harness Plug
Page 7
Notes
If you have questions about your alternator or any of these test procedures, or if you need to locate a Factory Authorized Service Distributor, please contact us at:
TEL: 800.643.4633 USA and Canada • TEL: 847.866.6030 outside USA and Canada • FAX: 847.492.1242
Page 8
C. E. Niehoff & Co.• 2021 Lee Street • Evanston, IL 60202 USA
E-mail us at support@ceniehoff.com
TG0011A
Loading...