C.E. Niehoff & Co. C520 Troubleshooting Guides

500 Series Troubleshooting Guide
for C520 Alternators
Hazard Defi nitions
These terms are used to bring attention to presence of hazards of various risk levels or to important information concerning product life.
Indicates presence of hazards that
CAUTION
will or can cause minor personal injury or property damage if ignored.
Indicates special instructions on
NOTICE
installation, operation or mainte­ nance that are important but not related to personal injury hazards.
Table of Contents
Section 1: Wiring .......................................................... 2
Section 2: CAN/J1939 Diagnostics ............................... 3
Section 3: Basic Troubleshooting ................................. 4
Section 4: Advanced Troubleshooting ....................... 5-6
Battery Conditions
NOTICE
system components stabilize, these conditions may be observed during cold start voltage tests.
• Maintenance or low maintenance battery: — Immediately after engine starts, system volts are lower than regulator setpoint with medium amps. — 3-5 Minutes into charge cycle, system volts are higher and amps are dropping. — 5-10 Minutes into charge cycle, system volts are at, or nearly at, regulator setpoint and amps are reduced to a minimum. — Low maintenance battery has same characteris­ tics with slightly longer recharge times.
• Maintenance-free battery: — Immediately after engine start, system volts are lower than regulator setpoint with low charging amps. — 15-30 minutes into charge cycle, volts and amps are still low. — 15-30 minutes into charge cycle, volts increase several tenths. Amps increase gradually, then quickly, to medium to high amps. — 20-35 minutes into charge cycle, volts increase to setpoint and amps decrease.
• High-cycle maintenance-free battery: — These batteries respond better than standard maintenance-free. Charge acceptance of these batteries may display characteristics similar to maintenance batteries.
Charge Volt and Amp Values
The volt and amp levels are a function of the battery state of charge. If batteries are in a state of discharge, as after extended cranking time to start the engine, the system volts, when measured after the engine is started will be
lower than the regulator setpoint and the system amps will be high. This is a normal condition for the charging system. The measured values of system volts and amps will depend on the level of battery discharge. In other words, the greater the battery discharge level, the lower the system volts and higher the system amps will be. The volt and amp readings will change, system volts reading will increase up to regulator setpoint and the system amps will decrease to low level (depending on other loads) as the batteries recover and become fully charged.
Low Amps: A minimum or lowest charging system
amp value required to maintain battery state of charge, obtained when testing the charging system with a fully charged battery and no other loads ap­plied. This value will vary with battery type.
Medium Amps: A system amps value which can
cause the battery temperature to rise above the ad­equate charging temperature within 4-8 hours of charge time. To prevent battery damage, the charge amps should be reduced when battery temperature rises. Check battery manufacturer’s recommenda­tions for proper rates of charge amps.
High Amps: A system amps value which can cause
the battery temperature to rise above adequate charg­ing temperature within 2-3 hours. To prevent battery damage, the charge amps should be reduced when the battery temperature rises. Check battery manu­facturer’s recommendations for proper rates of charge amps.
Battery Voltage: Steady-state voltage value as mea-
sured with battery in open circuit with no battery load. This value relates to battery state of charge.
Charge Voltage: A voltage value obtained when the
charging system is operating. This value will be high­er than battery voltage and must never exceed the regulator voltage setpoint.
B+ Voltage: A voltage value obtained when measur-
ing voltage at battery positive terminal or alternator B+ terminal.
Surface Charge: A higher than normal battery volt-
age occurring when the battery is removed from a battery charger. The surface charge must be removed to determine true battery voltage and state of charge.
Significant Magnetism: A change in the strength or
intensity of a magnetic field present in the alternator rotor shaft when the field coil is energized. The mag­netic field strength when the field coil is energized should feel stronger than when the field is not ener­gized.
Voltage Droop or Sag: A normal condition which
occurs when the load demand on the alternator is greater than rated alternator output at given rotor shaft RPM.
TG0048A
Page 1
Section 1: Wiring Diagram
CEN C520 Alternator Description and Operation
C520 14 V 300 A 3-phase alternator is internally rectified. All windings and current-conducting compo­nents are non-moving, so there are no brushes or slip rings to wear out.
After engine is running, regulator receives energize signal. Regulator monitors alternator rotation and provides field current only when it detects alternator shaft rotating at or above idle speed.
After regulator detects alternator rotation, it gradually applies field current, preventing an abrupt mechani­cal load on accessory drive system. The soft start may take up to 20 seconds.
A2-215 regulator used with some of these units is flat temperature compensated. A 15.5 V regulator setpoint is available for battery isolator applications.
A2-326 regulator used with some of these units in­cludes measurement of battery current, voltage, and temperature for adjustment of regulator setpoint.
IGN terminal
T
Figure 1 — C520 Alternator/A2-215 Regulator Features
J1939 receptacle
Regulator receptacle
IGN terminal
T
T
T
B– terminal
T
T
T
LED
T
B+ terminal
LED
Figure 2 — A2-326 Remote-Mounted Regulator Features
Page 2
Figure 3 — C520 Alternator with Regulator
TG0048A
Section 2: CAN/J1939 Diagnostics
CAN/J1939 Interface
DESCRIPTION AND OPERATION
The CEN A2-326 digital regulator is compatible with SAE J1939 communications standard for vehicle net­working.
CEN uses MIL-STD connector MS3112E12-10P to inter­face between the A2-326 and the vehicle J1939 databus. Mating connector is MS3116E12-10S or equivalent. If J1939 connection is not used, the 10-pin connector must be covered with connector cover MS3181-12CA or equivalent. Message content is shown in Table 2.
TABLE 2 – A2-326 Regulator/J1939 Readout Diagnostics (see Table 3)
Regulator Readout
Alternator Output Voltage 28 V System
Alternator Speed
Regulator Temperature
Alternator Output
Charging System Hours
Expected Reading
13–15 V
1200 to 8000 RPM
Less than 257 F/125ºC
0–100%
>0 hours
TABLE 1 – J1939 Connector
Circuit Identifi cation
Pin
A
B
C
D
E
F
G
H
J
K
Identifi cation
CANH
CANL
CAN SHIELD
Battery
Mfr use only
Mfr use only
Mfr use only
Temperature sensor
Voltage sensor
Current sensor
Figure 4 – J1939
Connector Pins
Action—If Expected Reading Not Present
See Chart 1, page 6.
Check drive belt and charging system connections.
Decrease load on alternator.
Varies with load.
Check drive belt and charging system connections.
TABLE 3 – Message Data
PGN Name PGN Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
ALT RPM
ALT VOLT
ALT TEMP
PROPRIETARY #1
PROPRIETARY #2
0xFED5 ALT RPM
0xFEF7 VOLT SETPOINT ALT VOLT REG IGN VOLT BATT VOLT
0xFEA7 REG TEMP BATT TEMP
0xFFC8 BATT
CURRENT
0xFFC9 Proprietary Content: For Manufacturer Test Only
SHUTDOWN
COUNT
BATT AGE HOUR METER MINUTES
(0-59)
ALT LOAD
TG0048A
Page 3
Loading...
+ 5 hidden pages