Cellartec 1/8 Ton-SSL, 1/4 Ton-SSL, 1/3 Ton-SSL, 1/2 Ton-SSL Installation, Operation & Care Manual

Page 1
SSL Series Split System
Installation, Operation & Care Manual
CellarTec 1/8 Ton-SSL CellarTec 1/4 Ton-SSL CellarTec 1/3 Ton-SSL CellarTec 1/2 Ton-SSL
READ AND SAVE THESE INSTRUCTIONS
wwwwww..aappeexxwwiinneecceellllaarrss..ccoomm
m
wwwwww..cceellllaarrtteecc..ccoom
Page 2
TABLE OF CONTENTS
Important Safety Information…..........................................2
Features & Specifications…………………….….…………..3 Cellar Construction.…………………………….……………..7 Installer’s Instruction…………….…..….……..……………..8 Electrical Wiring…..…………….…..….……..……………..15 Temperature Control & Humidity Adjustment.………….20 Care Guide…………………………………………………….24 User’ Troubleshooting…….………………………………...25 Customer Support……………………………………………28 Warranty……………………………………………………….29
- 1 -
Page 3
Important Safety Information
WARNING:
DO NOT USE A GROUND FAULT INTERRUPTER (GFI).
A DEDICATED CIRCUIT IS REQUIRED, 15 AMP FOR 1/8-1/3 Ton-SSL
AND 20 AMP FOR 1/2 Ton-SSL.
- 2 -
Page 4
MODEL
CellarTec
1/8 TON-
SSL
CellarTec
1/4 TON-
SSL
CellarTec
1/3 TON-
SSL
CellarTec
1/2 TON-
SSL
Features and Specifications
CELLARTEC split cooling systems CellarTec 1/8-1/2 Ton-SSL are designed and used to provide a cold temperature between 50~65 properly insulated wine room at a normal environment.
The wine room will maintain humidity of 50~70% RH even when the environment becomes dry and humid. These temperatures and humilities are optimized for long term storage of wine.
SSL units consist of a condensing unit and an evaporator unit, and they are connected by a liquid line and an insulated suction line.
SSL condensing units can be located away from the evaporator units and wine cellars as far as 50 feet, which will bring you quiet operation.
SSL evaporator units provide low profile and whisper quiet operation. The evaporator units can be installed on the ceiling in a wine cabinet or room.
The dimensions and capacities are specified as follows:
EVAP UNIT
W”xD”xH”
WM-
15SFCL
16.75x14.5 x4.75
WM-
25SFCL
31.75x14.5 x4.75
WM-
45SFCL
40.25x14.5 x4.75
WM-
65SFCL
53.75x16.5 x6.75
COND UNIT
L”xD”xH”
WM-150SCU
18x12x14
WM-250SCU
18x12x14
WM-450SCU
18x12x14
WM-650SCU
24x18x17
Btu/h
CFM
°F)
(55/90
1500/180
2500/275
4500/460
6500/575
BOTTLE
CAPACITY
(55/75°F)
150
cu ft
250
cu ft
1000
cu ft
1500
cu ft
REFRIGERANT
R134a
R134a
R134a
R134a
ELECTRICAL
EVAP UNIT/ COND UNIT
115V-60HZ-
0.4A / 115V-
115V-60HZ-
0.4A / 115V-
115V-60HZ-
0.8A / 115V-
115V-60HZ-
0.8A / 115V-
Parts included:
Condensing Unit (pressure control, discharge and suction valves installed) + Filter + Sight Glass Evaporator Unit (liquid line solenoid valve and expansion valve installed) Temperature Controller + Air Sensor
CAUTION: LIQUID AND SUCTION LINES MAY DIFFER FROM WHAT ARE SHOWN HERE, PLEASE CHECK ON THE UNITS FOR PROPER INSTALLATION.
°F for a
60HZ-3.1A
60HZ-5.7A
60HZ-6.9A
60HZ-12A
WEIGHT(lb) EVAP UNIT/ COND UNIT
15/30
30/40
37/60
61/90
- 3 -
Page 5
Fig. 1 WM15-25SFCL Evaporator Unit
Fig. 2 WM45-65SFCL Evaporator Unit
NOTE: LEAVE MINIMUM 3” CLEARANCE FOR ELECTRICAL WIRING AND REFRIGERATION PIPING.
- 4 -
Page 6
Fig. 3 WM150-450SCU Condensing Unit
Fig. 4 WM-650SCU Condensing Unit
- 5 -
Page 7
Fig. 5 Liquid Filter
Fig. 6 Sight Glass
CAUTION: LOW AMBIENT TEMPERATURE KIT IS REQUIRED IF THE INSTALLATION AREA WILL BE BELOW 50°F.
- 6 -
Page 8
Cellar Construction
This is only a guide and shall be considered as minimum requirements. All interior walls and floors shall have a vapor barrier and a minimum of R11
insulation. All exterior walls and ceiling shall have a vapor barrier and a minimum of R19 insulation. The vapor barrier shall be installed on the warm side of the insulation. All joints, door frames, electrical outlets or switches and any pipes or vents that go through the enclosure shall be sealed to prevent air and moisture leakage into the room. Concrete, rock, and brick are not insulation or vapor barriers.
Doors shall be of a minimum size, insulated to at least R11 and tightly sealed with high quality weather stripping. Be sure to seal the bottom of the door and fill gap between the door’s frame and wall before installing the cap molding. In order to maintain 55 °F in the wine cellar, the ambient temperature surrounding the enclosure shall not exceed the temperature of the enclosure by more than 25 °F. No enclosure wall shall receive direct sun or strong wind.
Lighting shall be of low wattage, with a timer to insure lights are not left on when the enclosure is not occupied.
The cooling system will not be able to maintain the proper temperature if fresh moisture-laden air is constantly being introduced to the enclosure. Symptoms of this condition are; unit runs all the time with only a slight reduction in temperature and/or water overflows from the unit. Because of the temperature difference between the inside and outside, very small cracks can allow large amounts of outside air to enter into the enclosure. Please be aware that moisture can pass through solid concrete, paint and wood. Often a newly constructed room contains fresh wood, paint, concrete and other building materials. These materials contain large amounts of moisture. When placed into operation in this type of environment, the system will work harder to remove this extra moisture resulting in increased “run” time.
- 7 -
Page 9
Installer’s Instruction
Federal law requires that CELLARTEC split cooling systems be
installed by an EPA certified refrigeration technician.
CELLARTEC split system is shipped as components and is ready for use only after a certified refrigeration technician has properly installed, evacuated, charged and tested the system. Proper installation is critical. Apex can only warrant the quality of the components. The installation and proper operation of the system must be warranted by the installer. Installation of the system must be done in accordance with all state and local building and electrical codes. The condensing unit and evaporator unit are connected by a liquid line and an insulated suction line that are supplied by the installer. These lines must be properly sized for the distance between the two units. After the units and the lines are installed, the system must be pressure tested. If no leaks are found, evacuate and charge system. Refrigerant amount will vary depending on the length of line set.
Fig. 7 SSL Split System Installation
- 8 -
Page 10
1. Condensing Unit
Place the condensing units WM150-650SCU in a properly ventilated location. If it is not, heat exhausted by the condensing unit will build up and the cooling system will not operate properly.
Condensing unit shall be elevated to avoid possible flooding and shaded from direct sun. It shall not be exposed to temperatures higher than 110
°F or lower than 50 °F (optional low ambient kit available).
Leave minimum 5 feet clearance for the exhaust side and leave minimum 1 foot clearance for the fresh air intake side.
CAUTION: IF THE CONDENSING UNIT IS EQUIPPED WITH A LOW AMBIENT CONDITION KIT, DO NOT TURN ON THE COMPRESSOR UNTIL THE CONDENSING UNIT HAS BEEN POWERD FOR 24 HOURS.
2. Discharge/Suction Valve Operation (Condensing unit)
Back Position: Normal operation, process and manometer port closed Front Position: Liquid/suction line connection closed Middle Position: All ports open for evacuation, charge and manometer reading
BACK POSITION FRONT POSITION MIDDLE POSITION
BACK POSITION FRONT POSITION MIDDLE POSITION
- 9 -
Fig. 8 ROTALOCK Valve Operation
Fig. 9 Base Valve Operation
Page 11
1 - Process & Manometer; 2 – Receiver Discharge)/Compressor Suction 3 – Liquid Line/Suction Line; 4 - Pressure Control
3. Evaporator Unit
The WM15-65SFCL evaporator units shall be installed for ceiling mount with the air supply towards horizontally and air return on the bottom.
Supply air flow shall be unobstructed for at least 12” for free installation or 2” for deflector installation and return air shall be unobstructed for 6”.
There is a gravity drain line and the unit shall be installed level or with a slight angle toward the drain connection. If rise-up is needed, a condensation pump must be used.
4. Thermostat and Air Sensor
CAUTION: USE 18 GAUGE THERMOSTAT WIRE.
The thermostat with a built-in air sensor can be installed in the wine room 5 ft above the floor in an area with good air circulation at average temp.
If the thermostat is mounted outside the wine room, a remote air sensor is required inside the wine room. The air sensor can be located in a well circulated or in the return air area, but not the supply air or air dead area.
5. Piping, Evacuating, Charging and Starting
CAUTION:
ALWAYS USE THE SUPERHEAT AND SUBCOOLING, PRESSURE
READINGS TO CHARGE REFRIGERANT PROPERLY, THE LISTED CHARGES ARE FOR REFERENCE ONLY.
CHARGE 15% MORE REFRIGERANT IN THE SUMMER IF THE UNIT IS
EQUIPPED WITH A LOW AMBIENT CONDITION KIT.
NOTES:
THE VALVE CONNECTION SIZES OF CONDENSING UNIT AND THE LINE
CONNECTION SIZES OF EVAPORATOR UNIT ARE NOT NECESSARY THE SAME AS THE ABOVE LISTED LINE SIZES.
IF THE CONDENSING UNIT IS INSTALLED ABOVE THE EVAPORATOR
UNIT, USE THE SUCTION LINE ONE LISTED SIZE SMALLER.
EXPANSION AND SOLENOID VALVES ARE INSTALLED ON LIQUID LINE.
The installation order starts from condensing unit (including the receiver,
discharge valve), liquid line filter-drier, moisture-liquid indicator/sight glass, liquid line, to evaporator unit (including liquid line connection, solenoid valve, expansion valve, and suction line connection), returning to insulated suction line, suction valve and then condensing unit.
- 10 -
Page 12
Charge the system after pipe brazing, leak testing and evacuating. Liquid must always be charged into the hide side.
Use inverted siphons to prevent liquid from flooding back to the compressor and aid oil returning to the compressor.
The subcooling at the condensing unit shall be around 10
°F. The charge
may be complete when there are no more bubbles forming in the sight glass.
Head pressure: 125-150 psig at 70-90
°F ambient temperatures.
The evaporator’s constant pressure expansion valve is set around 35­40°F at factory. This pressure setting gives a dew point to maintain the humidity for storing wine.
Suction pressure: adjust the AXV to 30-35 psig.
The temperature split across the evaporator shall be 8-10
°F at 55°F wine
room temperature.
The superheat at the evaporator unit shall be around 9-18
°F under low -
high heat load at normal ambient temperatures.
If the superheat is high, check the subcooling first to know if the refrigerant charge is sufficient. If the charge is not sufficient, add more refrigerant. If the charge is good, then increase the evaporator suction pressure by turning the hex nut (5/16”) clockwise.
If the superheat is low, then decrease the evaporator suction pressure by turning the hex nut (5/16”) counter-clockwise.
The line sizes and refrigerant charges are listed as follows.
MODEL
CellarTec 1/8
TON-SSL
CellarTec 1/4
TON-SSL
CellarTec 1/3
TON-SSL
CellarTec 1/2
TON-SSL
REFRIGERATION
LINES
<= 50 FT 1/4" OD 3/8” OD 1/2” OD <= 50 FT 1/4" OD 3/8” OD 1/2” OD <= 50 FT 1/4" OD 1/2” OD 1/2” OD <= 50 FT 1/4" OD 1/2” OD 1/2” OD
- 11 -
Fig. 10 Expansion Valve
LIQUID
LINE
SUCTION
LINE
DRAIN
LINE
CHARGE
R134a/
15 OZ
R134a/
19 OZ
R134a/
26 OZ
R134a/
32 OZ
Page 13
6. Use of the adjustable pressure control (if applicable for pump-down)
Suction pressure setting: Cut out=5 psig; Cut in=25 psig; Differential=20 psig Head pressure setting: Cut out=230 psig; Cut in=150 psig; Differential=80 psig It may need to adjust the setting in the field to get the right cycle time.
A. Single Control
Fig. 11 Single Adjustable Pressure Control
B. Dual Control
Fig. 12 Dual Adjustable Pressure Control
7. Use of the encapsulated low pressure control (if applicable)
Fixed suction pressure setting: Cut in = 32 psig; Cut out = 10 psig
- 12 -
Page 14
Fig. 13 Fixed Pressure Control
8. Use of the condenser fan control (if applicable for low ambient kit)
Head pressure setting: Cut in=170 psig; Cut out=120 psig; Differential=50 psig It may need to adjust the setting in the field to avoid fan short cycle.
9. Use of the crankcase heater (if applicable for low ambient kit)
The crankcase heater is installed around the lower part of the compressor and shall be turned on all the time. The heater is self-regulated.
10. Pressure, Superheat and Subcooling Readings
CAUTION: THE VALVES MUST BE IN THE MIDDLE POSITIONS TO READ PROPERLY.
Complaint Possible Causes
a. High suction pressure and low head pressure b. High suction pressure and low head pressure Low superheat and low subcooling c. High suction pressure and high head pressure Low superheat and high subcooling d. High to normal suction pressure and high head pressure Low subcooling e. High suction pressure and high head pressure Low subcooling f. High suction pressure and high head pressure High superheat g. Low suction pressure and low head pressu re High superheat and low subcooling h. Low suction pressure and low to normal head pressure High superheat and high subcooling
i. Low suction pressure and low head pressure Low subcooling j. Low suction pressure and low head pressure Low superheat and low subcooling k. Low suction pressure and low to normal head pressure High superheat and normal to high subcooling
a. Compressor may be bad b. Expansion valve opened, too
much oil
c. Overcharge d. Non-condensable gas e. Air restricted, dirty condenser,
bad condenser fans
f. High room temperature, high
evaporator load
g. Undercharge h. Liquid line restricted after
receiver, solenoid valve restricted
i. Suction line restricted j. Air restricted at evaporator,
evaporator iced
k. Evaporator restricted
- 13 -
Page 15
l. Low suction pressure and normal head pressure High superheat and normal subcooling m. Low suction pressure and high head pressure High superheat and high subcooling n. Low suction pressure and high head pressure High superheat and high subcooling o. low to normal suction pressure and high head pressure High to normal superheat and high subcooling
11. Condensing Unit Troubleshooting
Unit not running
a. Incorrect power supply b. Incorrect or loose wirings c. Failed components
d. Liquid refrigerant in the compressor e. Low pressure switch shutting down the system
a. Check for proper voltage b. Check all wirings and connections c. Check start relay, start capacitor, overload
d. Call service for OEM information e. Check for system restriction or low
l. Expansion valve restricted m. Both evaporator and condenser
restricted
n. Liquid line restricted before
receiver
o. Condenser restricted
protector, compressor.
refrigerant
- 14 -
Page 16
Electrical Wiring
CAUTION:
USE 14 GAUGE WIRE FOR POWER LINE WIRING.
USE 18 GAUGE WIRE FOR THERMOSTAT AND SENSOR.
IF EQUIPPED WITH LOW AMBIENT CONDITION KIT, USE LOW AMBIENT
TEMPERATURE WIRING DIAGRAMS. TURN OFF THE COMPRESSOR
BEFORE POWER THE CONDENSING UNIT. ONLY TURN ON THE COMPRESSOR AFTER THE CONDENSING UNIT HAS BEEN POWERED FOR 24 HOURS.
Fig. 14 Thermostat Installation
- 15 -
Page 17
Fig. 15 CellarTec 1/8-1/3 Ton-SSL Wiring Diagram
- 16 -
Page 18
Fig. 16 CellarTec 1/2 Ton-SSL Electrical Wiring Diagram
- 17 -
Page 19
Fig. 17 Low Ambient Temperature
CellarTec 1/8-1/3 Ton-SSL Electrical Wiring Diagram
- 18 -
Page 20
Fig. 18 Low Ambient Temperature
CellarTec 1/2 Ton-SSL Electrical Wiring Diagram
- 19 -
Page 21
Temperature Control & Humidity Adjustment
1. Temperature Setting
Set the temperature at 55
On initial start-up, the time required to reach the desired temperature
will vary, depending on the quantity of bottles, temperature setting and surrounding temperature.
Allow 24 hours to stabilize the temperature for each new temperature setting operation
2. Use of the Programmable Thermostat
°F for the optimum aging of wine
Fig. 19 Touchscreen Programmable Thermostat
1) System Setup
1. Press and release the SYSTEM Key.
- 20 -
Page 22
2. Press and hold the two blank keys on either side of the center blank key for
approximately five seconds until screen matches the screen below.
3. Press UP/DOWN advance keys to select setup number; press UP/DOWN
change keys to change settings.
4. Press the DONE key to exit the Installer Setup screen.
- 21 -
Page 23
Factory Setup Menu
Setup
Number
0120 Date (Year Upper) Select first two digits of current calendar year 0130 Date (Year Lower) Select last two digits of current calendar year 0140 Date (Month) Select number for current calendar month 0150 Date (Day) Select number for current calendar date 0160 Schedule Options 0-nonprogrammable 0170 System Selection 6-cool only conventional 0220 Cycles Per Hour 2 0280 Continuous Backlight 0-not; 1-yes 0300 Changeover 0-manual 0320 Temperature Display 0-fahrenheit; 1-celsius 0330 Daylight Savings 0-off; 1-on
Setup Name Settings
0340 Remote Air Sensor 0-no; 3-indoor 0380 Indoor Dehumidification 0-no 0580 Min Compressor Off 5-five minutes off 0610 Min Cool Temp 0640 Clock Format 12-12 hour; 24-24 hour 0660 Extended Cool Fan On 0-0 seconds 0670 Keypad Lockout 0-unlocked; 2-fully locked 0690 Cool Temp Control 2-standard 0700 Temperature Offset 0-no
50
°F
NOTES:
The setup 0660 can be used to increase the humidity in the wine cellar. The higher the setting is, the higher the humidity will be.
2) System Test
1. Enter the system setup, and press DOWN key to select setup number. “TEST” appears at the end of the installer setup number.
2. Press the keys below to test.
- 22 -
Page 24
Fig. 20 System Test
Test Number Test Type Description
1 cooling 1-on; 0-off 2 fan 1-on; 0-off
3) Clock Setting
1. Enter the system setup and set 670 = 0 to unlock screen, then exit.
2. Press CLOCK key; press UP/DOWN keys to change clock.
3. Press DONE key to exit.
4. Enter the system setup and set 670 = 2 to lock screen, then exit.
4) Temperature Setting
1. Enter the system setup and set 670 = 0 to unlock screen, then exit.
2. Press UP/DOWN keys to modify temperature.
3. Enter the system setup and set 670 = 2 to lock screen, then exit.
5) Remote Air Sensor
Enter the system setup and set 340 = 3, then exit
6) Humidity Display
It only displays the humidity where the thermostat is installed. The humidity level is shown in the lower right corner of the screen.
- 23 -
Page 25
Care Guide
In general, always unplug system or disconnect power while doing care.
1. Coil Cleaning
Clean the condenser coil regularly. Coil may need to be cleaned at least every 6 months.
Unplug the system or disconnect power.
Use a vacuum cleaner with an extended attachment to clean the coil when it
is dusty or dirty.
Plug cooling system or reconnect power.
2. Moisture Removing
Remove the extra condensate if it is accumulated in the wine cellar at high ambient temperature and humidity.
- 24 -
Page 26
User’s Troubleshooting
This Troubleshooting Chart is not prepared to replace the training required for a professional refrigeration service person, not is it comprehensive
Troubleshooting Chart
Complaint Possible Causes Response
1.Unit not running
2.Displaying Temperature fluctuating
3.Temperature high, but displaying temperature low, unit stopping and starting with short running time
4.Temperature high, compressor stopping and starting but short running time
5.Not cooling or
a. No power b. Power cord unplugged c. Setting higher than ambient
temperature d. Defrost light blinking e. Compressor light blinking f. Incorrect or loose wirings. g. Low voltage.
a. Air sensor When using an air sensor, the wine
a. air sensor contacting the
evaporator b. Short circuit of air flow between
supply and return air c. Setting too high d. Failed temperature controller
and air sensor
a. Incorrect voltage b. Failed components
c. Improper condenser airflow d. Dirty condenser e. Overcharge of refrigerant f. Discharge or suction pressure
too high a. Improper room insulation & seal
b. Room too large
a. Check power at receptacle & fuses b. Check for power cord plug c. Lower temperature setting
d. Unit is under defrost mode e. Unit waits for anti-short cycle delay f. Check all wirings and connections g. Contact an authorized electrician
bottle temperature is mainly controlled by the average air temperature. If the
set-point is 55 the cooling unit turns on at 59 temperature and turns off at 55
temperature. The average air temperature is 57 temperature is around 57+/-0.5
air is light enough to change so quickly that it maintains relatively constant average temperature that would prevent wine bottle temperature from varying. a. Move the air sensor away from the
evaporator
b. Deflect the supply air down c. Lower setting
d. Call service for diagnosis
a. Check for voltage b. Check compressor windings, start
relay and overload protector. c. Check for condenser fan d. Clean condenser e. Call service for removing refrigerant f. Call service for OEM information
a. Check for insulation, gasket and
door opening b. Check for excessive size
°F with a differential 4 °F,
°F, and then the wine
°F of air
°F of air
°F. The
- 25 -
Page 27
temperature too high and running continually
6.Unit running
too long
7.Evaporator
freezing up
8.Water leak
9.Circuit
tripping
c. Ambient temperature too high d. Exhaust restricted
e. Malfunctioning fans f. Improper evaporator or
condenser airflow g. Dirty Condenser h. Iced evaporator i. Sealed system problem
j. Undercharge or overcharge
a. Improper room insulation & seal b. Exhaust restricted
c. Room too large d. Ambient temperature extremely
high
e. Dirty Condenser a. Evaporator air flow restriction
b. Unit not stopping due to air leak,
high ambient temperature or low
setting c. Low ambient temperature d. Bad thermostat or sensor e. Refrigerant low or leak f. Expansion valve blockage
a. Unit not level b. Drain line restricted c. Drip tray leak
d. Very high humidity e. Wine room air leak
a. Incorrect fuse or breaker b. Incorrect wirings c. Overcharge of refrigerant d. Condenser air restriction e. Failed components
c. Check for installation location d. Leave minimum 3 feet clearance for
e. Check for both evaporator and f. Check for air restrictions g. Clean condenser
h. Defrost and reset temperature i. Call service for checking loss of
j. Call service to add or remove
a. Check for insulation, gasket and door b. Leave minimum 3 feet clearance for
c. Check for excessive size d. Check for installation location or
e. Clean condenser a. Check for fans, CFM
b. Check for seal, door opening,
c. Defrost the unit d. Check for thermostat and sensor e. Check for sealed system leakage f. Check for low side pressure
a. Check for installation b. Check drain line c. Check for if water leak but no
d. Use dehumidifier e. Check for air leak and if
a. Check for proper fuse or breaker b. Check for wirings and connections c. Call service for removing refrigerant d. Check condenser fan e. Call service
the exhaust side and leave minimum 1 foot clearance for the fresh air intake side
condenser fans
refrigerant or restrictions refrigerant
opening the exhaust side and leave minimum
1 foot clearance for the fresh air intake side
increase setting
ambient temperature and setting
overflow
condensation on the cooling unit
- 26 -
Page 28
10.Noisy
operation
a. Mounting area not firm b. Loose parts
c. Compressor overloaded due to
high ambient temperatures or
airflow restriction d. Malfunctioning components
a. Add support to improve installation b. Check fans, cabinet washers, tubing
contact and loose screws.
c. Check for airflow blockage
d. Call service for checking Internal
loose, inadequate lubrication and incorrect wirings
- 27 -
Page 29
Customer Support
If you still have problems, please contact us at:
Apex 17631 South Susana Road Rancho Dominguez, CA 90221 Tel: (310) 886-3332 Fax: (310) 886-3310 Email: info@groupapex.com
- 28 -
Page 30
Warranty
Thank you for choosing an Apex cooling unit.
Please enter the complete model and serial numbers in the space provided:
Model_________________________________________________________ Serial No.______________________________________________________
Attach your purchase receipt to this owner’s manual.
1. Limited Warranty
APEX warrants its products, parts only, to be free from defects due to workmanship or materials under normal use and service for twelve months after the initial sale. If the product is defective due to workmanship or materials, is removed within twelve months of the initial sale and is returned to APEX, in the original shipping carton, shipping prepaid, APEX will at its option, repair or replace the product free of charge.
This warranty constitutes the entire warranty of the APEX with respect to its products and is in lieu of all other warranties, express or implied, including any of fitness for a particular purpose. In no event shall APEX be responsible for any consequential damages what is so ever. Any modification of APEX products shall void this warranty.
Service under Warranty
This service is provided to customers within the continental UNITED STATES only. APEX cooling units are warranted to produce the stated number of BTU/H. While every effort has been made to provide accurate guidelines, APEX can not warranty its units to cool a particular enclosure.
In case of failure, APEX cooling units must be repaired by the factory or its authorized agent. Repairs or modifications made by anyone else will void the warranty.
Shall a APEX cooling unit fail, contact the dealer for instructions, do not return the unit to the factory without authorization from APEX. If the unit requires repair, re-pack it in the original shipping carton and return it to the factory, shipping prepaid. APEX will not accept COD shipments. If the unit is determined to be faulty and is within the twelve month warranty period APEX will, at its discretion,
- 29 -
Page 31
repair or replace the unit and return it free of charge to the original retail customer. If the unit is found to be in good working order, or beyond the initial twelve month period, it will be returned freight collect.
2. Limitation of Implied Warranty APEX’S SOLE LIABILITY FOR ANY DEFECTIVE PRODUCT IS LIMITED TO,
AT OUR OPTION, REPAIRING OR REPLACING OF UNIT. APEX SHALL NOT BE LIABLE FOR:
DAMAGE TO OTHER PROPERTY CAUSED BY ANY DEFECTS IN THE UNIT, DAMAGES BASED UPON INCONVENIENCE, LOSS OF USE OF THE UNIT, LOSS OF TIME OR COMMERCIAL LOSS, ANY OUTER DAMAGES, WHETHER INCIDENTAL, CONSEQUENTIAL OR OTHERWISE.
THIS WARRANTY IS EXCLUSIBE AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED OR INPLIED, INCLUDING BUT NOT LIMITED TO, IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.
While great effort has been made to provide accurate guidelines APEX cannot warrant its units to properly cool a particular enclosure. Customers are cautioned that enclosure construction, unit location and many other factors can affect the operation and performance of the unit. There for suitability of the unit for a specific enclosure or application must be determined by the customer and cannot be warranted by APEX.
- 30 -
Loading...