
PART NUMBERS, UNIT COMBINATIONS, OPTIONS, DIMENSIONS & WEIGHTS
PERFORMANCE DATA & AIR FLOW SOUND POWER AND SOUND
PRESSURE LEVELS
INSTALLATION: CONTENTS & PIPEWORK
ELECTRICAL: CONNECTIONS & FUSES
PIPEWORK: FITTING LOSSES, INTERCONNECTING PIPEWORK
& EVACUATING
1. TEV Ltd recommend that personnel working on this equipment be skilled and fully conversant with
the appropriate Air Conditioning, Refrigeration and Electrical practices and have sound knowledge
of current Industrial Safe Working practices.
2. CX(E)A models are electromechanical / Electronic control units that use R410A refrigerant; they
provide cooling within the range of 2.8 – 5.6 kW. These units are matched with CKA outdoor units
to complete a system.
3. These units contain live electrical components, moving parts and refrigerant under pressure.
Always site out of reach of children and protect from vandalism.
4. The data plate only gives information for the CX(E)A unit. For system details add input power and
current of indoor and outdoor unit, including any heater load.

Digital temperature display (CXA only) STD on CX(E)A
De-ice thermostat (CXA only) STD on CX(E)A

RATING CONDITIONS
(ROOM 12.7C / 10C) (AMBIENT 35C / 19C)
Sound Power Levels were obtained in full accordance with the direct method of BS EN ISO3174:2000. Levels are shown in dB
with a standard reference of 1 pW.
Sound Pressure Levels in dB(A) refer to semi-hemispherical radiation (wall or ceiling mounted) at a distance of 1.5m from the
front of the unit, with the fan operating at full speed.
OUTDOOR UNIT
Sound Power Levels were obtained in full accordance with the direct method of ISO 3741: 1988. Levels are shown in dB with a
standard reference of 1 pW.
Sound Pressure Levels in dB(A) refer to semi-hemispherical radiation (wall or floor mounted) at a distance of 3m from the front
of the unit, with the fan operating at full speed; (add 3dBA or 3NC for units at an intersection of a wall, add 1dBA or 1NC for high
level wall mounted units).
RATING CONDITIONS
(ROOM 12.7C / 10C) (AMBIENT 27C / 19C)
SOUND POWER AND SOUND PRESSURE LEVELS

Maximum Running Current A
UNIT ELECTRICAL LOADS [230V 50Hz 1Ph (A) or 400V 50Hz 3Ph (A/Ph)]
2 CORE + EARTH 1.5mm 3 CORE + EARTH 1.5mm
INTERCONNECTING INSTRUCTIONS FOR CX(E)A AND CKA SYSTEMS

(Wall mounted)
FRONT VIEW
(Wall mounted)
REAR VIEW
(Ceiling Mounted)
TOP VIEW
(Ceiling mounted)
SIDE VIEW
X
2Z
1Z
X
(Wall mounted)
SIDE VIEW
= Liquid / Expansion 2
Z
= Suction 1
Z
X = Interconnecting Wiring
20
483
FOR SIDE ACCESS
MIN. 500
96
320
120
888 (Fixing centers)
124
888
845
70
422.5
124 (Fixing centers)
39
39
60
17.5
17.5
MIN.
120
36
215
75
140
65 TYP.
35
96
CONDENSATE DRAIN 22mm OD

7/9
55908028-03
The unit may be mounted on a wall or solid ceiling using brackets supplied. It should be matched with the
appropriately sized outdoor unit; this instruction should be used in conjunction with the outdoor unit
installation instructions.
1. Fit all kits prior to installing the unit. (Heater kit is easier to fit when unit has been mounted).
2. Ensure that the mounting surface will support the operating weight of the unit (see table below).
3. Mark out the mounting positions and drill holes to suit 6mm rawlbolt shields or equivalent strength
fasteners (ensure that the unit is positioned
to give sufficient access (min 0.5m) to the
electrics access side).
4. Fix the mounting brackets to the unit in the
correct position for wall or ceiling mounting.
5. Raise the unit into position and secure the
fixings, ensuring that it is square and level.
6. Remove the drain tray then fit the drain stub,
nut & gasket (Fig.1). Refit the drain tray.
Fig.1
CX(E)A PIPEWORK
NITROGEN CHARGE
The unit contains a small charge of dry nitrogen, which should be discharged into the atmosphere. This is a
non-toxic, non-ozone depleting gas with no global warming potential.
PIPE CONNECTIONS
Pipework is terminated with 2 flare nuts & bonnets. Access is via the rear right hand side. Pipes exit the unit
through holes in the back panel.
CONDENSATE DRAIN
Push fit connections are widely available for the 7/8” (22mm) OD condensate drain and 3/4"(19mm) ID drain
stub adaptor. Alternatively 7/8” (22mm) bore plastic tubing may be fitted directly to the stub/adaptor with a
hose clamp. Take care not to over tighten hose clamps as this could damage the stub pipe.
Envelope containing operating instructions
and Declaration of Conformity
Pass to the end user
Drain Stub/Nut/Gasket
Convert to ¾" drain if required
Mounting brackets plus fixings
INTERCONNECTING PIPEWORK (Max 15 metres)
DRAIN TRAY
GASKET
NUT
DRAIN STUB

8/9
55908028-03
Cables are routed to the terminal block via the cable cord grips at the rear of the unit and then through
the back of the electrics box (see page 2).
Cables MUST be size compatible with the recommended system fuse.
FUSES
Note: On 3 ph systems the supply must go to the CKA outdoor unit and then to the CX(E)A indoor unit.
MOUNTING
Whether floor or wall mounted, it is essential that the mounting surface is capable of supporting the unit
weight. Leave space around the unit for air circulation and access for installation and maintenance.
1. Individual pipe runs to a maximum of 15m, including 7.5m lift, are permissible.
Performance is based on 7.5m pipe runs. Correctly sized pipes for each installation will result in no
significant loss of capacity on extended pipe runs.
a) Pipe sizes are based on:-
Minimum of 3.8 m/s (750 fpm) suction gas velocity for horizontal or downflow.
Minimum of 7.6 m/s (1500 fpm) suction gas velocity for upflow.
Maximum of 15.2 m/s (3000 fpm) suction gas.
b) Where vertical risers exceed 3m, oil traps must be formed in the pipe. This will help ensure that oil
returns to the compressor. Typically fit an oil trap every 3m with a trap at the bottom of the riser.
2. In calculating equivalent lengths of pipe runs, the effect of bends and fittings must be taken into
account. The table below covers the fittings most likely to be encountered in this installation.
The equivalent lengths of all the fittings in a pipe run should be added together and the total added to
the actual pipe length in order to calculate the total equivalent length.
3. Use the shortest possible route, avoiding sharp bends.
4. Completely insulate the suction line, fully over the indoor unit drain tray.
1500 min air off
100 min
100 min
600 min
CX(E)A ELECTRICAL CONNECTIONS

9/9
55908028-03
FITTING LOSSES, in equivalent straight lengths of pipe (m).
To calculate the total equivalent
length, the equivalent lengths of all
fittings in a pipe run must be added to
the actual length of pipe in the run:
these are the fittings most likely to be
used.
R = Radius of bend
d = Diameter of tube
C = Centres of bend
A. SUCTION AND LIQUID/EXPANSION LINES:
The expansion capillary is located in the outdoor unit and the equivalent pipe run is 15m maximum, including
a maximum lift of 7.5m. Fully insulate the suction and liquid/expansion line. Ensure the suction pipe is
insulated well over the drain tray at the indoor unit. Liquid lines should be routed to avoid hot areas. This
prevents flash gas forming, which may result in erratic control of liquid refrigerant to the evaporator.
MAXIMUM EQUIVALENT
LENGTH OF SUCTION LINE
PIPE SIZES (m)
For systems with interconnecting pipework in excess of 7.5 metre add 20gms per metre on
CKA 35 & CKA 50, add 30gms per metre on CKA 70. No additional oil is required.
INTERCONNECTING PIPEWORK
1. Indoor and outdoor units have a low pressure charge of N2, which may be safely released into the
atmosphere before connection. The service valves on the outdoor unit should remain closed (IN, fully
clockwise) until pipework has been fitted, to avoid unnecessary moisture ingress.
2. Connecting the pipework
a. Remove the flare nuts from the suction and liquid service valves.
b. Ensure that the suction line is fully insulated: if an expansion line is used this should also be fully
insulated.
c. Place the flare nuts over the incoming pipework and flare the pipe ends. The use of a little
refrigeration oil on the flaring tool will help.
d. Connect the pipework between the units. Do not leave pipe ends, valves etc. open to the
atmosphere.
R410A is very hygroscopic, and will absorb damaging levels of moisture if left open.
Always use two spanners when tightening the flare nuts to avoid twisting the pipes. Use a small
amount of refrigerant oil on the mating surfaces.
e. Sight glasses and filter driers are not necessary, but if required should be fitted between the
outdoor unit liquid shut off valve and the expansion device.
EVACUATING
1. Release the nitrogen holding charge in the indoor and outdoor units to atmosphere. Open the valves
(hex drive fully out) using a 5mm Allen key. Connect a vacuum pump to the service ports on the
outdoor unit valves and evacuate the system to 1000 microns (1 Torr) or better and allow to be held
for a minimum of 15 minutes.
2. Replace the caps on the service ports, (torque to 25NM).
TEV LTD, ARMYTAGE ROAD, BRIGHOUSE, WEST YORKSHIRE, HD6 1QF. + 44 (0) 1484 405600 +44 (0) 1484 405620
sales@marstair.com www.marstair.com
TEL: FAX:
EMAIL: WEB: