CellarCool copyrights this manual, the product design, and the design concepts, with all rights reserved. Your rights with
regard to the hardware and manual are subject to the restrictions and limitations imposed by the copyright laws of the
USA. Under copyright laws, this manual may not be copied, reproduced, translated, transmitted, or reduced to any printed
or electronic medium or to any machine-readable form, for any purpose, in whole or in part, without the written consent
of CellarCool.
Every effort has been made to ensure that the information in this manual is accurate. CellarCool is not responsible for
printing or clerical errors.
CellarCool reserves the right to make corrections or improvements to the information provided and to the related
hardware at any time, without notice.
Vinothèque and CellarCool are registered trademarks, and ECE is a trademark of CellarCool. All rights reserved.
Mention of third-party products is for informational purposes only and constitutes neither an endorsement nor a
recommendation. CellarCool assumes no liability with regard to the performance or use of these products.
Installation Terms and Conditions ......................................... 43
INTRODUCTION
Customer Service
Thank you for purchasing a CellarCool cooling system. We strive to provide the highest-quality products and the best possible
customer service. If you have any questions about your system, please call us at 1-800-343-9463 or visit cellarcool.com.
Using the Manual
This owner’s manual is intended to assist in the proper maintenance of the cooling system. In order to ensure the longevity of
your cooling unit, the equipment should be installed as outlined in the technician’s manual. It is also vital to establish a proper
care and maintenance schedule. Please read and review this manual carefully and keep it for future reference.
What is the CellarCool Cooling System?
The CellarCool cooling system is a specialized refrigeration system designed for one purpose only: to maintain the optimal
temperature and humidity levels conducive to the proper storage and aging of ne wines. This system produces minimal in-cellar
noise and has the most lenient exhaust requirements. An exterior housing is required for outdoor condensing unit installations.
How Does the Cooling System Work?
Similar to the air conditioning systems used for homes, the evaporator unit (fan coil unit) and condensing units are installed
in separate locations and are connected by a refrigerant line set. The evaporator portion is commonly installed in the wine
cellar, with the condensing unit is located either outside or in a remote indoor location that is ventilated. An exterior housing is
required for outdoor condensing unit installations.
Temperature Setting
The system is designed to maintain a cellar temperature of 55°F as long as the ambient temperature does not exceed 110°F.
WARRANTY REGISTRATION
In order to activate the warranty of your system, the verication and operational
documentation must be completed by the certied refrigeration technician
installing your system and submitted via mail, fax, or e-mail.
Mail to:
CellarCool
ATTN: Warranty Registration
1738 E. Alpine Avenue
Stockton, CA 95205-2505
USA
Fax to:
209-466-4606
Scan and email to:
warranty@cellarcool.com
Page 2 1-855-235-5271
WM&FD 051019
WM & FD SERIES
QUICK START GUIDE*
Pump Down Cycle
CellarCool’s split systems operate on a pump down cycle dierent from traditional air conditioners. As such, there is no wiring
between the condensing unit and evaporator unit.
CellarCool units utilize a solenoid valve on the liquid line and a low-pressure switch on the suction line. When the thermostat calls
for cooling, the solenoid valve opens, permitting the ow of refrigerant. The low-pressure switch then signals the compressor to
cycle on.
When the cellar reaches the desired temperature and the thermostat is satised, the solenoid will close, stopping the liquid
refrigerant ow to the TXV valve. The compressor will continue to operate until most of the refrigerant on the low side boils o
and is pumped through the compressor into the condenser coil and receiver. As the suction pressure falls below the pressure
control setting, the low-pressure switch will signal the compressor to cycle o. Most of the refrigerant is now stored between the
condensing unit and receiver.
…………………………………………………………………………………………………
WARNING: Do not utilize a ground fault interrupter, as it will prevent
the unit from drawing the necessary amperage to start the unit.
TXV Adjustments
A. A TXV adjustment may be necessary based on ambient temperatures in the cellar and at the condensing unit.
B. Adjust the TXV until the total superheat measured at the suction line service valve is 20-30°F.
C. Under normal operation, with the wine cellar at 55°F and the ambient temperature at 85°F, the low side pressure should be
between 28-32 PSI and the high side should be between 145-155 PSI.
TXV
The TXV is preadjusted at the factory. If the superheat is not within
20-30° at the service valve, the TXV will need to be adjusted.
ADJUSTING THE TXV
Use a ⁄” hex key to remove the cap from the TXV superheat
adjustment port. With the cap removed, insert the hex key into
the superheat adjustment port. Increase superheat by turning the
hex key clockwise. Decrease superheat by turning the hex key
counterclockwise.
Liquid Line King Valve
This location is used to charge the system with liquid refrigerant
and identify the high side pressure of the system.
Calculating Subcooling
To determine the subcooling of the system, calculate the dierence
between the high side pressure of the system (converted to
temperature) and the temperature of the liquid line. The temperature
of the liquid line will be taken at the outlet of the receiver.
*Saturation temp — liquid line temp
4-6°F SUBCOOLING REQUIRED FOR WARRANTY APPROVAL
*Further system operation information is available on page 32.
www.cellarcool.com | Page 3
BEFORE YOU START
1. Inspect all components prior to installation. If damage is found, please contact your distributor or CellarCool Customer
Service at 1-800-343-9463.
2. The evaporator unit requires a dedicated 115V, 15-amp circuit. The 3500 condensing unit requires a dedicated 115V, 15-
amp circuit. The 5000 condensing unit requires a dedicated 115V, 20-amp circuit. Use a surge protector with the unit. Do
not use a GFI (ground fault interrupter) line.
3. No communication cable is required between the evaporator and condensing unit.
4. You are REQUIRED to install a drain line to remove condensation from the evaporator unit.
5. The warranty is not active until a warranty checklist has been received, reviewed, and approved.
6. The system is intended for use in properly designed and constructed wine cellars. Hire a professional wine storage
consultant with a valid contractor’s license to build your wine cellar.
7. CellarCool requires that all split systems be installed by a certified HVAC-R technician only. NATE or equivalent is recommended.
If you encounter a problem with your CellarCool system, please refer to the Troubleshooting Guide. If you have any further
questions or concerns, or need assistance, please contact CellarCool’s Customer Service at 1-800-343-9463. Please be sure all
testing has been completed prior to contacting Customer Service. Please have your results ready for your representative.
1-800-343-9463
Page 4 1-855-235-5271
WM&FD 051019
WM & FD SERIES
RECEIVING & INSPECTING THE SYSTEM
• Use caution when lifting and check package for damage.
• Lift only at the designated hand-hold locations on the shipping container, or fully support the unit from underneath. A
shipment may include one or more boxes containing accessories.
• Before opening the container, inspect the packaging for any obvious signs of damage or mishandling.
• Write any discrepancy or visual damage on the bill of lading before signing.
• Allow the condensing unit to sit for 24 hours prior to start-up. The condensing unit can be placed in the installation
location, piped, and evacuated during this time.
NOTE: CellarCool units are manufactured in the USA and tested prior to shipment.
• Review the packing slip to verify contents.
• Check the model number to ensure it is correct.
• Check that all factory options ordered are listed.
If any items listed on the packing slip do not match your order information,
contact CellarCool Customer Service immediately.
Check all shipped boxes for the following contents:
Main Evaporator Box
(1) WM/FD evaporator unit
Documentation bag:
• WM/FD Version 3 owner’s manual
• WM/FD Version 3 technician’s manual
• R-134a split system warranty checklist
Evaporator installation hardware bag:
• (2) ½” x ½” nylon barbed tting
• (1) ½” barbed tee
• (1) Double-D strain relief
• (4) ¾” adhesive cable tie mounts
• (2) Small cable ties
• (4) #8 x 1¾” hex-head screws
Wall-Mounted Accessory Kit
Ducted Accessory Kit
Main Condensing Unit Box
(1) Condensing unit
Condensing unit accessory kit:
• (1) Filter drier
• (1) Sight glass
(1) Filter grille
(1) Duct plenum
(1) WM/FD Evaporator Wall-Mounting Template
Please leave the unit in its original box until you are ready for installation. This will allow you to move the product safely without
damaging it. When you are ready to remove the product from the box, refer to the installation instructions.
TIP: Save your box and all packaging materials. They provide the only safe means of transporting/shipping the unit.
www.cellarcool.com | Page 5
Front / Side View
QUICK REFERENCE GUIDE
Evaporator unit
Rear / Side View
Filter grille
Mounting keyholes (4)
THROUGH THE WALL
Option 1
Knockout for wiring
Line set knockout
Knockout for drain line
Thermostat wire routing for
optional 24-volt thermostat
(NOT INCLUDED)
Page 6 1-855-235-5271
Line set knockout
INSIDE CELLAR
Option 2
Knockout for drain line
Knockout for wiring
WM&FD 051019
Evaporator unit (fan coil unit)
Filter grille
WM & FD SERIES
WALL-MOUNTED UNIT SPECIFICATIONS
Model
Cellar SizeApprox. 1000 cu. ft., provided cellar is fully insulated and sealed with proper vapor barrier*
BTU/h w/85°F air
entering condenser coil
Dimensions16.1”L x 20.5”W x 15.5”H16.08”L x 16.23”W x 12.61”H
RefrigerantR-134a
HP1/3
Voltage Rating115V (15-amp dedicated circuit required)115V (15-amp dedicated circuit required)
Line SetLiquid line: ¼" ; suction line: ½" (less than 50 ft.), ⁄" (greater than 50 ft.)
Duct Size8" supply, 10" return
Drain Line½” ID clear plastic tubing (not provided)
Installation
Evaporator can be installed up to 25 duct feet away from cellar. Condensing unit can be installed up to
100 line feet from evaporator unit.
5000 Evaporator
(Fan Coil Unit)
(Air-Cooled Condensing Unit)
3788
5000 Condenser
ThermostatAftermarket (24V thermostat not included)
Temp. DeltaCan maintain a 55°F temperature dierential with up to 110°F condenser air intake temperature
WarrantyTwo-year limited warranty (parts and labor)
*Each cellar is unique and has specic cooling requirements. Heat load calculations should always be performed prior to selecting a cooling unit.
Page 10 1-855-235-5271
WM&FD 051019
WM & FD SERIES
SPLIT SYSTEM CHECK LIST
In order to activate the warranty for this product, the information here must be complete and accurate. Any
incorrect or omitted information will result in a return trip by the installing technician at their cost.
DATA RECORDINGS
NOTE: All readings need to be taken while the compressor is running.
Line Set Information
A. Line set length:
B. Suction line OD:
C. Liquid Line OD:
Charging the System
A. Fill system until bubbles dissipate from sight glass.
NOTE: Be careful not to overcharge the system.
Temperature Dierential at the Evaporator
A. Measure return air and supply air temperatures at the evaporator to ensure adequate cooling of air in cellar.
Sub Cooling
A. Measure head pressure at liquid line king valve. Convert pressure to temp using conversion chart.
B. Temp of liquid line at king valve:
C. Complete sub cooling calculation: A – B =
Superheat
A. Measure suction pressure at the suction line service valve, convert to temp.
B. Measure the temperature of the suction line at the outlet of the evaporator.
C. Complete superheat calculation: A – B =
NOTE: There may be a need to adjust the TXV to get the correct superheat levels.
Compressor Temperature
A. Measure temperature at bottom of compressor.
NOTE: Cool temp may indicate liquid in the compressor.
Voltage and Amp Draw
A. Measure voltage to compressor and amp draw.
Condensation Drain Test
A. Pour water into the drain pan to assure it drains properly.
www.cellarcool.com | Page 11
24V THERMOSTAT CONVERSION KIT WIRING INSTRUCTIONS
The 24V Thermostat Conversion Kit requires a standard 18-5 thermostat wire to be run from the evaporator unit to the
thermostat. The white wire will not be used, as there is no heating function. (Some thermostats need a common wire and some
do not; the unit is equipped with a common wire if needed.)
If the system is equipped with the Cold Weather Start Kit a standard 18-2 thermostat wire must be run between the evaporator
unit and the condensing unit.
24V Wiring Connections (Evaporator)
1. Route a standard 18-5 thermostat wire into the evaporator unit.
2. Locate the wire thermostat connection cable inside of the evaporator unit.
3. Connect the wires according to color (yellow to yellow, red to red, green to green, and blue to blue).
4. If the system is equipped with a Cold Weather Start Kit, connect one wire from the 18-2 thermostat wire to the low-voltage
yellow wires (2). Then connect the other 18-2 wire to the blue low-voltage wires (2).
Thermostat Wiring Connections
Follow the thermostat installation instructions. NOTE: The white wire will not be used, as there is no heating function.
Thermostat
R/RC
Y
G
C
NOTE: To ensure correct system operation, the
24V thermostat must be placed inside the
wine cellar, preferably in a central location
away from any airow.
Cold Weather Start Kit Wiring Connections
If the system is equipped with a cold weather start
kit, connect one of the 18-2 thermostat wires to the
purple #12 wire. Connect the other 18-2 wire to the
grey #13 wire.
Evaporator Unit
Grey (13)
Purple (12)
Condensing Unit
Page 12 1-855-235-5271
WM&FD 051019
PREPARING THE EVAPORATOR (FAN COIL) UNIT
Required Tools:
WM & FD SERIES
• Drill
• ⁄” drill bit
• ¼” socket drill bit
• ¼” wrench
• Phillips-head screwdriver
• Tape measure
• Brazing torch
• Drywall saw
• Ladder
• Level
• Pliers
• Pencil
Drain Pan
Power
3/8” Suction
1/4” Liquid
Unit
Panel
Thermostat
Wire
Strain
Relief
Drain
Thermostat wire routing for 24V thermostat
(NOT INCLUDED)
1. Remove the knockouts for the drain line, line set, and
electrical on the bottom or rear of the unit, depending
on your installation preference.
2. Remove the insulation from the knockout holes.
3. For ease of installation, remove the nine (9) screws
securing the top and remove the top.
4. Install strain relief around thermostat wires if routed
through the circular connector hole in the bottom
corner (see illustration).
www.cellarcool.com | Page 13
INSTALLING THE WALL-MOUNTED EVAPORATOR UNIT
Refer to the Wall-Mounted Evaporator Unit Installation Template for more information about mounting the wall-mounted
evaporator unit.
1. Locate two (2) wall studs in the desired mounting location spaced 16” on center.
2. Mark vertical lines on each stud 16” apart.
3. Mark an intersecting horizontal line at the desired height of the unit.
4. Make a mark on each stud 13½” down from the intersection of the horizontal and vertical lines.
NOTE: The top of the unit must be installed a minimum of 6” and a
maximum of 18” from the ceiling.
1/8”
WALL
STUD
5. Install the four (4) supplied 1¾” hex head
screws into the studs at the locations marked
leaving ⁄” between the wall surface and
screw head.
6. If routing through a wall, cut out an access
hole for the line set, drain line, and power wires.
7. Raise the evaporator to the installation location. Align the rear key
holes with the mounting screws and mount the unit.
8. Using a ¼” wrench or socket, tighten the top mounting screws.
9. Using ¼” and ½” copper tubing, route the liquid and suction lines
through the knockouts in the housing. Be sure to extend the
tubing far enough outside of the housing to extend through the
wall if necessary. NOTE: ½” copper tubing will slip over the ⁄”
suction line on the evaporator for an easy connection.
10. Remove the solenoid coil and wrap the solenoid valve in a wet rag
to prevent overheating.
11. To prevent oxidation, purge the system with nitrogen.
12. Braze the copper tubing to the connections on the evaporator
unit.
Page 14 1-855-235-5271
WM&FD 051019
WM & FD SERIES
13. Insulate the suction line using Armaex or similar insulation.
14. Using the cable ties and cable tie mounts provided, secure the drain line to the bottom of the housing to ensure a downward
slope.
15. Route the power wires into the unit through the knockout.
16. Following the supplied wiring diagram on page 12, connect thermostat wires.
17. Connect the green wire to the green wire, the black wire to the black wire, and the white wire to the white wire.
18. Install the supplied black strain relief to secure the power wires in the housing.
19. Secure all wiring neatly and as close to the left wall as possible in order to minimize airow obstruction.
www.cellarcool.com | Page 15
DRAIN LINE
Condensation Drain Line (not provided, but required)
The condensation drain line tube moves excess condensation from the evaporator unit to a proper discharge
location. It is important for the drain line tube to be properly connected in order to prevent leakage and other problems associ-
ated with excess condensation.
Failure to use the condensation drain line tube will void the warranty on the unit.
Drain Line
All systems come with a drain line connection tee and two 90-degree fittings. The unit is equipped with a ½” OD barbed fitting
coming from the drip tray. (NOTE: ½” ID clear PVC tubing will need to be purchased and installed by the installing technician.)
Installation of the drain line is mandatory, whether it leads through the wall and out of the cellar or remains inside the cellar.
During operation, the cooling system will strip excess water from the air in order to maintain the proper level of humidity within
the cellar. However, in extreme humidity, additional condensate will be removed; thus the drain line will prevent overflow and
leakage by discharging the excess condensate.
Routing the tubing out of the unit:
Cut a small piece of ½” tubing and connect one
end to the drip tray port and the other to a
90-degree fitting. (This will direct the tubing
toward the back of the unit where the tube will
exit the unit.) Be sure to extend the tubing far
enough outside the housing to extend through
the wall if necessary.
If routing out of the rear: Cut a piece of tubing
long enough to protrude out of the knockout on
the back side of the unit.
If routing out of the bottom: Cut a piece of
tubing long enough to reach the knockout in
the bottom of the unit and install the supplied
90-degree fitting. (This will direct the tubing out
of the bottom of the unit without the risk of
kinking the tubing.) DO NOT USE TEE WHEN
ROUTING OUT OF THE BOTTOM.
Routing to discharge location if routed out
of the bottom:
Connect the drain line directly to the second
90-degree barb fitting previously installed. Route
the drain line to an appropriate drain location.
No tee is required if draining through the
bottom of the unit.
Routing to discharge location if routed out of the rear:
Insert the middle barb of the barbed tee fitting into the end of the drain
line coming from the evaporator. Rotate fitting so tee is in the orientation
shown in the diagram below. Connect a 3-inch piece of ½” drain line to
the barb on top. Connect the remaining “long” piece of drain tubing to
the bottom barb of the tee. Route the drain line to an appropriate drain
location.
NOTE: The fitting should be placed
vertically with the 3” cutout facing
up.
Failure to install the drain line
voids the warranty.
To prevent mold from growing,
allow the drain line to hang
above the water line.
WRONG: Drain line is under water.
Page 16 1-855-235-5271
WM&FD 051019
WM & FD SERIES
PREPARING THE FULLY DUCTED EVAPORATOR UNIT
1. Remove the knockouts for the drain line,
line set, and electrical on the bottom
Power
Line set
Drain line
Thermostat
Wire
or rear of the unit (depending on your
installation location).
2. Remove the insulation from the knockout
holes.
3. Install strain relief around thermostat wires
if routed through the circular connector
hole in the bottom corner of the housing.
Thermostat wire routing for optional
24V thermostat conversion kit
(THERMOSTAT NOT INCLUDED)
Strain
Relief
Unit
Panel
www.cellarcool.com | Page 17
INSTALLING THE FULLY DUCTED EVAPORATOR
1. Using ¼” and ½” copper tubing, route the liquid and suction lines through the knockouts in the housing. Be sure to extend
the tubing far enough outside of the housing to extend through the wall if necessary. NOTE: ½” copper tubing will slip over
the ⁄” suction line on the evaporator for an easy connection.
2. Remove the solenoid coil and wrap the solenoid valve in a wet rag to prevent overheating.
3. To prevent oxidation, purge the system with nitrogen.
4. Braze the copper tubing to the connections on the evaporator unit.
5. Insulate the suction line using Armaex or similar insulation.
6. Using the cable ties and cable tie mounts provided, secure the drain line to the bottom of the housing to ensure a
downward slope.
7. Route the power wires into the unit through the knockout.
8. Remove the wire nuts from the black, white, and green wires located in the lower left corner of the evaporator unit.
9. Following the supplied wiring diagram on page 12, connect thermostat wires.
10. Connect the green wire to the green wire, the black wire to the black wire, and the white wire to the white wire.
11. Install the supplied black strain relief to secure the power supply wires in the housing.
12. Secure all wiring neatly and as close to the left wall as possible in order to minimize airow obstruction.
Page 18 1-855-235-5271
WM&FD 051019
WM/FD EVAPORATOR WITH
PS-WM/FD with
24V Thermostat Conversion Kit
24V CONVERSION KIT WIRING DIAGRAM
White
24v
Transformer
24V Common
Blue
Blue
Black
Black
Black
Yellow
24V Hot
WM & FD SERIES
Blue
115V Line
115V Neutral
Ground
Black
White
Green
Blue
Black
Black
White
Fan
Neutral
Line
14
14
Solenoid
Blue
6
1
Blue
Green
Yellow
Red
Solenoid
Ref.
Green
Solenoid
Relay
4
0
Blue
6
1
Bare End
Relay
Fan
4
0
Thermostat
C
G
Y
R
RC
LEGEND
Field Installed
Factory Installed
Units equipped with a factory installed CWSK Option, must
have an 18-2 Thermostat wire run from the evaporator to the
condensing unit. Connect the yellow wire to the purple #12 wire,
and connect the blue wire to the grey #13 wire.
Black
White
White
White
14
14
Green
Green
Black
White
FV-30VQ3
www.cellarcool.com | Page 19
3500/5000 CONDENSING UNIT WIRING DIAGRAM
Page 20 1-855-235-5271
WM&FD 051019
WM & FD SERIES
COPELAND COLD WEATHER START KIT WIRING DIAGRAM
For systems manufactured after October 31, 2018
COPELAND CWSK
N
1234
5
H
1234
Black
Black
HEATER
5
TS
www.cellarcool.com | Page 21
PREPARING THE CONDENSING UNIT
Electrical Needs
The 3500 condensing unit requires a dedicated 115V, 15-amp circuit. The 5000 condensing unit requires a 115V, 20-amp
circuit. The unit draws a large inrush current for about 1 second the instant the compressor starts. With a dedicated circuit and
circuit breaker, the condensing unit will have sucient power for eective operation. (The compressor is controlled by a lowpressure transducer mounted on the condensing unit. This feature eliminates the need for wiring between the evaporator unit/
fan coil unit and the condensing unit.)
• Ensure the voltage supplied matches the rating specied on the unit spec label.
• Provide a non-GFI dedicated circuit and an appropriate outlet for the evaporator unit.
• Provide a dedicated circuit and circuit breaker for the condensing unit.
• Provide a weatherproof disconnect for the condensing unit if it is located outside.
Power surges and spikes can damage sensitive electrical equipment. CellarCool recommends plugging the unit into a surge
protector or power conditioner in order to protect your system. As outlined in our terms and conditions, power surges and spikes
are not covered under warranty.
Page 22 1-855-235-5271
WM&FD 051019
WM & FD SERIES
INSTALLING THE CONDENSING UNIT
The condensing unit can be installed inside a well-ventilated area of the home, but is typically installed outside. Exterior
applications will require the use of a protective housing. The amount of sun exposure should be considered when selecting
the placement of the condensing unit .The 3500 condensing unit requires a dedicated 15-amp circuit (non-GFI). The 5000
condensing unit requires a 20-amp circuit (non-GFI). Make sure there is a minimum of three (3) feet of horizontal clearance in
every direction around the unit (ve feet is ideal). The unit may either be hard-wired or plug-in, depending on local electrical
codes.
Indoor condensing unit installations: Inside installations require special consideration, as there must be adequate
ventilation to remove the heat created during normal operations. An exhaust port with fan may need to be installed to
ensure that heat is eectively removed from the utility room. There must be a return grille or provision for 500 - 600 CFM
of cool air to enter the room to replace the exhausted air. Unobstructed airow to and from the unit is a critical factor in
the unit’s overall performance. Make sure there is a minimum of three (3) feet of horizontal clearance in every direction
around the unit (ve feet is ideal). This will assure that the unit can move the air around the room in an ecient manner.
Outdoor condensing unit installations: You must utilize the exterior condensing unit housing for outdoor installations.
Place the condensing unit on a solid foundation in a location with adequate ventilation. Make sure there is a minimum
of three (3) feet of horizontal clearance in every direction around the unit (ve feet is ideal). The unit should be
elevated 18 inches in order to avoid any possible ooding or damage by animals, and should be clear of leaves, dirt, and
other debris.
www.cellarcool.com | Page 23
WM/FD SERIES WIRING PROCEDURES
1. Locate or install an electrical outlet near the condensing unit.
2. Follow the instructions listed below to wire the condensing unit.
3. Leave the circuit breaker o until the unit is ready to charge.
NOTE: Do not apply power to a system without refrigerant.
Copeland Wiring Procedure
Use a ¼” nut driver to remove the screw securing the cover to the
compressor electrical compartment.
Step #
0
Page 24 1-855-235-5271
WM&FD 051019
WM & FD SERIES
Copeland Wiring Procedure
Remove the cover to expose the internal wires.
Step #
1
Copeland Wiring Procedure
Route the required 115V power wires into the open
clamp on the enclosure.
Step #
2
www.cellarcool.com | Page 25
Copeland Wiring Procedure
Copeland Wiring Procedure
Tighten the screws on the clamp to secure wire casing or
conduit in place.
Step #
3
Perform the following wire connections:
• Insert the Line 115V wire into the “H” lever connector
• Insert the Neutral 115V wire into the “N” lever connector
• Insert the Ground wire into the “G” lever connector
Step #
4
Page 26 1-855-235-5271
WM&FD 051019
WM & FD SERIES
Copeland Wiring Procedure
Copeland Wiring Procedure
Step #
5
Push wires back into enclosure.
Step #
6
Re-install cover.
www.cellarcool.com | Page 27
LINE SET PIPING DIAGRAMS
EXAMPLE
It is required to size the suction line tubing according to this chart.
WM/FD 3500/5000
Suction Line
Liquid Line
Condensing Unit Installed Below Fan Coil
Line Set Length<25ft26-50ft50-100ft
Vertical Rise15ft<3ft3-10ft>10ft<3ft3-10ft>10ft
Horizontal Tubing½”⁄”
Vertical Rise½”½”
Horizontal Tubing¼”
Vertical Rise¼”
Option 1
Condensing Unit Installed More Than 3’ Above Fan Coil
Option 2
Page 28 1-855-235-5271
WM&FD 051019
WM & FD SERIES
INSTALLING THE CONDENSING UNIT
DO NOT BLOCK airow through the exterior housing. This will restrict airow andvoidthe warranty.
Refrigerant Piping Overview
• Using the charts and illustrations found above, route the line set between the evaporator unit and condensing unit. Be sure to
reference the chart for correct line set sizing. All horizontal suction piping should be pitched toward the condensing unit half
an inch for every 10 feet of pipe. When installing and routing the line set, cap both ends of each tube to prevent debris from
entering the tubing.
• Prior to connecting the piping to the evaporator and condensing units, loosely connect a refrigerant manifold to the suction
and liquid line service valves.
• Purge the hoses with dry nitrogen and tighten the hose connections.
• Remove the service valve caps and turn the valve stem clockwise half a turn to unseat the valve and open the service
port. Keep the piping ports sealed until ready to braze.
• Purge the ttings with dry nitrogen at a slow rate to prevent formation of highly abrasive copper oxide.
• Perform all brazes.
• Pressure test the system and check for leaks.
• Insulate the suction line using wall cellular insulation or equivalent. Seal all seams with Armaex 520 foam insulation adhesive
or equivalent. Wrap each seam using line set tape.
Liquid Line Piping Procedure
• Refer to the line set piping chart for liquid line size measurements.
• Braze a short piece of copper tubing to the liquid line service valve.
• Connect the supplied refrigerant drier to the tubing.
• Downstream from the drier, connect the moisture-indicating sight glass in an easily visible location.
• Run the tubing to the evaporator unit and attach to the liquid line connection on the evaporator unit.
Suction Piping Procedure
• Connect an appropriately sized suction line to the suction line service valve on the condensing unit.
• Run the pre-insulated suction line to the evaporator unit and attach to the suction line connection on the evaporator unit.
Brazing Procedure
• Energize the evaporator unit and set the thermostat to call for cooling.
• Verify that the setpoint on the control is set low enough to allow the unit to run for the entire length of the brazing,
evacuation, and charging procedure.
• Remove the valve depressors from the gauge hoses on a four-valve manifold.
• Connect the manifold to the low-pressure service valve port on the condensing unit and a nitrogen tank.
• Open the suction line service valve and purge the system with nitrogen.
• Braze all connections and cool o quickly.
• Connect the high-pressure hose from the manifold to the liquid line service valve port.
• Pressure test the system at 150 psi for 20 minutes.
• Check all braze joints with leak detector or soap bubbles.
• Release the nitrogen once it is conrmed that there are no leaks.
Evacuation
• Remove the nitrogen tank from the manifold and attach the manifold to the refrigerant tank.
• Mid-seat both service valves.
• Install service caps on the valves.
• Energize the liquid line solenoid valve.
• After conrming that there is fresh oil in the vacuum pump, connect the ⁄” hose from the manifold to the pump.
• Start the pump and run it until the micron gauge on the evaporator unit reads 500 microns or less.
• Disconnect the vacuum pump from the system.
www.cellarcool.com | Page 29
INSTALLING THE CONDENSING UNIT (continued)
• Break the vacuum by pressurizing the system to approximately 5 PSI with R-134a refrigerant.
• Remove the micron gauge from the access valve.
Charging
• With the power o to the condensing unit, admit liquid refrigerant through the liquid line service valve until the refrigerant
stops owing.
• Turn on the circuit breaker for the condensing unit. The compressor should turn on if the pressure in the suction line is above
20 psi.
• Add refrigerant (in vapor form) to the low side of the system through the suction line service port.
• Observe the sight glass. If bubbles are present, add more refrigerant (in vapor form) to the low side.
• Once the sight glass is clear, check the superheat at the outlet of the evaporator unit. Adjust the TXV until the superheat is
between 20-30°F degrees.
• Under normal operation, with the wine cellar at 55°F and the ambient temperature at 85°F, the low side pressure should be
between 28-32 PSI and the high side should be between 145-155 PSI.
Finalizing the Installation
• Conrm that the entire suction line from the TXV to the suction line service valve is insulated using cellular insulation or
equivalent. Seal all seams with Armaex 520 foam insulation adhesive or equivalent.
• Conrm that the control is displaying the correct temperature.
Charging Information
A. Energize the solenoid valve on the evaporator unit by plugging the unit in and adjusting the thermostat to call for cooling.
Page 30 1-855-235-5271
WM&FD 051019
WM & FD SERIES
INSTALLING THE WALL MOUNT KIT
1. If removed, reinstall the top panel of the unit housing.
2. Align the front grille with the four (4) ball studs on the housing. Push the front grille onto the ball studs until it snaps into
place.
3. Using a Phillips-head screwdriver, fasten the bottom two (2) screws to fasten the grille to the unit.
DRAIN PAN
INSTALLING THE DUCTED PLENUM
1. If removed, reinstall the top panel of the unit housing.
2. Align duct plenum with the four (4) ball studs on the housing. Push the duct plenum onto the ball studs until it snaps into
place.
3. Using a Phillips-head screwdriver, fasten the bottom two (2) screws to fasten the plenum to the unit.
4. Connect the supply and return duct work to the unit.
5. Using duct tape or foil tape, seal the seam between the plenum and unit.
6. Insulate all exposed metal on the unit to prevent surface condensation.
NOTE: Max ducting length is 25 feet.
NOTE: A 12”x12” return air lter grille must be installed to prevent contaminants from entering the cooling system. Supply duct
must be insulated so it does not sweat or pick up heat.
www.cellarcool.com | Page 31
SYSTEM OPERATION
The cooling system is equipped with the hardware needed to support a 24-volt air conditioning thermostat (not included).
Initial Start-Up
Set the thermostat to COOL and fan switch to AUTO. Lower
the setpoint to the desired cellar temperature. (A temperature
of 55°F is the recommended setpoint.) See thermostat
instructions for details.
Normal System Cycle
The thermostat should turn the cooling system on when it
senses a temperature one (1) degree higher than the setpoint.
See thermostat instructions for details.
Anti-Short Cycle
Most thermostats have a safety feature that will prevent
the condensing unit from cycling on and o within a short
period of time. During the anti-short cycle, the condensing
unit will typically remain o for 5-7 minutes. See thermostat
instructions for details.
Fan Operation
If the fan switch on the thermostat is in the AUTO position, it
will run only during the cooling cycle. If the fan switch on the
thermostat is in the ON position, the fan will continuously run
until the switch is set back to the AUTO position.
The condensing unit controller is preset at the factory. The
cut-in pressure is preset to 25psi and the cut-out pressure
at 15psi. During low ambient temperatures (40°F or below),
it will be necessary to adjust the cut-in pressure to 1015psi (15psi is preferred) and the cut-out to 5psi to ensure
compressor startup. See page 34 for instructions on adjusting
the cut-in and cut-out pressures of the condensing unit.
NOTE: To ensure correct system operation, the 24V thermostat
must be placed inside the wine cellar, preferably in a central
location away from any airow.
Anti-Frost
Systems equipped with a 24V thermostat conversion kit do
NOT have an anti-frost feature. To reduce the possibility of the
evaporator coil icing up, avoid setting the thermostat lower
than 55°F.
Operation in Low Ambient Temperatures
The condensing unit comes equipped with a LAC (Low
Ambient Control). The LAC is a three-way modulating valve
that responds to discharge pressure. When the discharge
pressure falls below the valve’s dome pressure, the valve
modulates open to the discharge port which allows discharge
gas to bypass the condenser. Mixing the discharge gas with
the liquid creates high pressure at the condenser outlet,
reducing the ow and causing liquid to backup in the
condenser. Flooding the condenser reduces the area available
for condensing. This reduction in condenser surface area
results in a rise in condensing pressure during cold ambient
conditions.
Page 32 1-855-235-5271
WM&FD 051019
MAINTENANCE SCHEDULE
WM & FD SERIES
Monthly
Quarterly
Annually
*CellarCool recommends lters with a mean eciency reporting value (MERV) of 4 or better. Filters are not included with
the unit.
1. Check coils
2. Check for unusual noise or vibration
3. Check the drain line to see if it is above the waterline (if draining into a vessel)
1. Use a vacuum with brush attachment to clean coils; be careful not to crush coil ns when cleaning
2. Change duct lter if the system is ducted*
1. Inspect for corrosion
2. Check wiring connections and integrity of cords
3. Pour a 50/50 bleach solution into the drain line every spring
www.cellarcool.com | Page 33
Emerson™ Electronic Unit Controller
Quick setup and troubleshooting guide
Adjusting Low Pressure Settings
Hold DOWN and SET simultaneously for 3 seconds
to enter menu (PSI light will ash)
Cycle through menu options – UP/DOWN
Select function – SET
Adjust value – UP/DOWN
Store function - SET
Exit menu - UP and SET
Low Pressure Cut-In Low Pressure Cut-Out
Accessing Alarm Code Information
Press and release ALARM
Cycle through menu options – UP/DOWN
Press SET to see number of alarms
Press SET again to return to menu options
Book of Alarms –
to enter alarm menu
Compressor
Fan light 1 & 2
(Fan cycle units only)
+
Module Restart –
push to reset
the HPL, DLL
lock out faults
(cycle power)
Set – Displays
+
set point. In
programming
mode, it con rms
an operation
When light is on, feature or component is on or active
Example: If StH=12 and StL=500, the total number of compressor starts=12,500
For more information visit
EmersonClimate.com/ElectronicUnitController
or call 1-888-367-9950
Page 34 1-855-235-5271
WM&FD 051019
DisplayLikely CausesOther Possible Causes
Controller display remains
blank after applying power
Controller displays correctly,
but the green compressor
light is off and the
compressor is not running
Controller displays correctly
and the green compressor
light is on and the
compressor is not running
Controller ashes “135” or
“P1”
Controller ashes “P2” on a
unit with fan cycling
Controller ashes “P2” on
a unit without fan cycling
after replacing a controller
Controller ashes “P3” on a
unit with DLT
Controller ashes “P3” on
a unit without DLT after
replacing a controller
Fans not running on a fan
cycling unit and the fan
lights are not on
Fans not running on a fan
cycling unit and the fan
lights are on
Controller ashes “HP” at
power-up
Controller ashes “HP” or
“HPL”
Controller ashes “DLT” or
“DLL”
Controller ashing “HPL”
or “DLL”
• Unit power not properly applied - check for proper applied voltage
• Power cable harness not plugged in properly or securely into the
back of the controller – check connections
• Jumper cable not plugged in properly or securely into the back of
the controller – check connections
• Controller is currently above the cut-in setting – check cut-in and
cut-out settings
• Power cable harness not plugged in properly or securely into the
back of the controller – check connections
• Current system pressure is above 135 PSIG – wait for system to
pull down
• Green harness not plugged in properly or securely into the back
of the controller – check connections
• Cable not connected properly with the pressure transducer –
check connections
• Green harness not plugged in properly or securely into the back
of the controller – check connections
• Controller not programmed properly – check parameters in the
advanced menu
• Jumper cable not plugged in properly or securely into the back of
the controller – check connections
• Controller not programmed properly – check parameters in the
advanced menu
• Condensing temperature is currently below the fan cut-in
• Condensing temperature sensor not properly installed – check
installation
• Power cable harness not plugged in properly or securely into the
back of the controller – check connections
• Jumper cable not plugged in properly or securely into the back of
the controller – check connections
• High pressure switch is seeing above the cut-out pressure
• For a replacing an -00 controller, ensure that the jumper cable is
the latest revision. It should have a blue wire in the harness. See
replacement instructions for more details
• System operation causing high discharge pressures, check
system operations
• System operation causing high discharge line temperatures,
check system operations
• System operation causing high discharge pressures (HPL) or
high discharge line temperatures (DLL) repeatedly, check system
operations
• To clear an “HPL” or “DLL” lockout, you can hold the Restart
button for 3 seconds twice, or cycle power to the unit. If using
the reset button, the alarm condition will have to clear (DLT
temperature drops or Hp switch resets), and any minimum off
time will need to complete (5 minutes for the xed Hp switch)
WM & FD SERIES
• Power cable miswired – inspect cable, replace if
needed
Evaporator lter or coil is dirtyRemove the lter and wash it, then clean the coil with a vacuum.
If coil is very dirty, use a spray bottle with a small amount of liquid
dish detergent or coil cleaner. Spray coil, let set for ve minutes, then
ush with fresh water.
There is something blocking the supply and/or return air
The evaporator fan is not turning on
If evaporator unit continues to ice
The set point is too lowRaise set point to recommended temperature of 55°F
Unit does not run/power up
Possible causeSolution
Evaporator unit is not plugged inMake sure the unit is plugged into an outlet
Power switch not onTurn unit on by pressing the power button on the control
Line voltage rating is incorrect for the systemCheck line voltage to make sure there is 110V-120V
Thermostat not calling for cooling
Faulty thermostat or wiringCall Customer Service at 1-800-343-9463
Remove blockage
Call customer service for details on how to perform the bypass plug
test. If all components run correctly, and the system cools during the
bypass plug test, there is either an issue with the 24V
thermostat conversion kit or the thermostat. Contact customer
service for further action.
Observe ice formation pattern. If only part way up the coil face, the
system could be low on refrigerant. If all the way up, the coil may be
dirty or airow is blocked.
Adjust thermostat to a lower temperature
Cellar temperature is too warm
Possible causeSolution
The temperature of the room to which the condensing unit exhausts
exceeds 110°F
The system is undersized for the cellarOrder correct size system
There is something blocking the supply and/or return air on the
evaporator unit or the condensing unit
Evaporator unit is mounted too low in the cellarRelocate unit so the distance from the ceiling and top of the unit is
One or more of the fans is not turning on
Compressor is not turning on
Compressor keeps cycling on overload
Poor seal around door or other areas requiring a seal (around the
unit, wall joints, etc.)
Thermostat set too high
Evaporator coil is frosted or iced upObserve ice formation pattern. If only part way up the coil face,
Intake temperature needs to drop below 110°F
Remove air ow obstruction
no more than 18”
Please contact the installing technician to troubleshoot
Please contact the installing technician to troubleshoot
Make sure all fans are working and there is no airow obstruction
Make sure there are no air gaps around the door. If door seal is
damaged, replace it.
Adjust thermostat to a lower temperature
evaporator unit could be low on refrigerant. If so,
contact your installing technician to assist with troubleshooting.
System runs constantly
Possible causeSolution
Leaky door seal or poorly insulated cellarFix leaky door seal and insulate cellar
Page 36 1-855-235-5271
WM&FD 051019
WM & FD SERIES
Unit leaks water
Possible causeSolution
Evaporator unit is not levelEvaporator unit should be level on the wall to prevent leaking
Drain line clogged or kinkedCheck drain line to make sure water can ow freely
Drain is clogged, preventing water from escapingDisconnect drain and clear it out, open access door and check drain
for blockage
Drain line does not have a downward slopeFix drain line so there is a downward slope from the unit to the drain
Coil is iced, causing drain pan to freeze and water to overowMelt ice with blow drier. Soak up with a towel.
Unit runs but does not cool
Possible causeSolution
Lack of air owMake sure fan is unobstructed and that the evaporator lter,
evaporator coil, and condenser coil are clean and free of debris
System undersizedContact Customer Service at 1-800-343-9463
Compressor is overheatingShut system o for 1 hour to allow compressor to cool. Turn back on
and check for cooler air ow out. If compressor runs, check for and
clean condenser coil as possible cause of compressor overheating.
If problem repeats, contact you installing technician to assist with
troubleshooting.
Evaporator fan runs but compressor does not
Possible causeSolution
Compressor and/or starting components faultyPlease contact the installing technician to troubleshoot
Compressor may have overheatedShut system o for 1 hour to allow compressor to cool. Turn back on
and check for cooler air ow out. If compressor runs, check for and
clean condenser coil as possible cause of compressor overheating.
If problem repeats, contact your installing technician to assist with
troubleshooting.
Thermostat not sending power to Y terminalCall customer service for details on how to perform bypass plug test
24V thermostat conversion kit solenoid relay not working correctlyCall customer service for details on how to perform bypass plug test
Compressor runs but evaporator fan does not
Possible causeSolution
Faulty fan motorPlease contact the installing technician to troubleshoot
Faulty thermostatPlease contact the installing technician to troubleshoot
Compressor short cycles
Possible causeSolution
Evaporator unit thermostat location Move thermostat out of airow
System low on refrigerant chargePlease contact the installing technician to troubleshoot
Condensing fan motor/capacitor faultyPlease contact the installing technician to troubleshoot
Compressor and /or starting components faultyPlease contact the installing technician to troubleshoot
Humidity in cellar too low
Possible causeSolution
Not enough moisture Purchase and place a humidier (or a decorative fountain) in cellar
www.cellarcool.com | Page 37
Units equipped with the 24V Thermostat Conversion Kit:
Unit does not power up/run
Possible causeSolution
Batteries on thermostat have lost their chargeChange batteries
Thermostat wired incorrectlyCheck wiring on 24V thermostat and correct
Wiring issue at evaporator unitContact Customer Service for troubleshooting
24V transformer in evaporator unit has failedContact Customer Service for troubleshooting
Evaporator fan runs continuously
Possible causeSolution
Fan switch on thermostat set to "on"Set fan switch to the "auto" position
Fan relay in thermostat or 24V conversion kit stuck onCall Customer Service for details on how to perform the bypass plug
test
Page 38 1-855-235-5271
WM&FD 051019
MAINTENANCE SCHEDULE
WM & FD SERIES
Monthly
Quarterly
Annually
*CellarCool recommends lters with a mean eciency reporting value (MERV) of 4 or better. Filters are not included with the
unit.
1. Check coils
2. Check for unusual noise or vibration
3. Check the drain line to see if it is above the waterline (if draining into a vessel)
1. Use a vacuum with brush attachment to clean coils; be careful not to crush coil ns when cleaning
2. Change duct lter if the system is ducted*
1. Inspect for corrosion
2. Check wiring connections and integrity of cords
3. Pour a 50/50 bleach solution into the drain line every spring
www.cellarcool.com | Page 39
AE
AE5-1340
Care and Cleaning of
Air Cooled Condensing Units
Introduction
Proper care is essential to assure good life of condensing
units. Dirty or damaged condensers will reduce the
efciency and capacity of the system.
Care must be taken in choosing solutions to be used for
cleaning condensers and condensate pans. Chlorinated
cleaners and anti-bacterial cleaning agents can be
damaging and should be avoided. Caustic and acidic
cleaners should be avoided as well. Failure to do so
may accelerate component corrosion and ultimately
lead to component failure.
Condenser Coils
There are many commercially available condenser coil
cleaners on the market. Coil cleaners should be designed
to remove build-up on ns and coils. Coils should be
thoroughly rinsed of the cleaners once cleaning has
been completed. Follow the manufactures instruction
for proper usage. Preventive maintenance and routine
cleaning of coils is important to assure good life.
When cleaning the coil, an absorbent type material
should be placed under the area to be cleaned in
order to capture most of the cleaning compound, thus
minimizing any type of chemical attack.
Condensate Pans
Condensing units with condensate pans and condensate
tubes are designed to evaporate condensate water
only. Other ingredients introduced into the condensate
pan can accelerate pan and/or tube corrosion. As
foreign agents are introduced into the condensate pan,
condensate water will be evaporated leaving the foreign
agent behind. This can lead to a high concentration of the
agent and possible corrosion of the tubing and/or base.
October 2006
Coil cleaning agents must not be allowed to drain into
the condensate pan as this may cause damage. Upon
completing the coil cleaning, be certain that all residue
is removed from the condensate pan.
Only non corrosive cleaners should be used to assure
good life of the condensing unit components. No
hydrocarbon based cleaners should be used to clean
the unit. Bleach solutions must be avoided due to its
high corrosive nature.
Under no circumstances should cleaning agent
ingredients contain any of the solutions listed below:
Maintenance should be performed at regular intervals.
Coils should be cleaned at least monthly, possibly more
depending on the environment. Condensing units with
condensate pans should also be checked and cleaned
regularly to prevent damaging build up in the pan.
Safety
Please follow all safety recommendations listed by the
manufacturer of the cleaning agent(s), these would
include proper clothing, gloves and eye protection.
Page 40 1-855-235-5271
WM&FD 051019
WM & FD SERIES
BYPASS TEST PROCEDURE
NOTE: If instructed by a CellarCool representative, follow the directions below to test the cooling unit using the bypass plug
provided in the accessory kit.
1. Disconnect power from the evaporator unit.
2. Loosen the two (2) screws on the front of the grille or duct plenum.
3. Pull the grille or duct plenum away from the evaporator unit.
4. Remove the screw securing the control panel in place.
5. Slide the control panel down, out of the evaporator housing. The control panel has two (2) hooks which allow it to attach to
the evaporator unit for easy serviceability.
6. Disconnect the Molex connector.
7. Locate the bypass plug included in the accessory kit.
8. Plug the bypass plug into the male Molex connector.
9. Connect power to the evaporator unit. The unit should immediately turn on. If all the components are not operational,
disconnect power immediately and contact customer service. If all components seem to be operating correctly, allow the unit
to run for four (4) hours. Monitor the temperature of the cellar to determine if the unit is cooling properly.
10. Once the test is complete, remove the bypass plug. Plug the Molex connector back in to the unit’s wiring.
www.cellarcool.com | Page 41
TECHNICAL ASSISTANCE
CellarCool Customer Service is available Monday through Friday from 6:00 a.m. to 4:00 p.m. Pacic Standard Time.
The appointed customer service representative will be able to assist you with your questions and warranty information more
eectively if you provide them with the following:
• The model and serial number of your CellarCool system(s).
• Location of unit and installation details, such as ventilation, ducting, construction of your wine cellar, and room size.
• Photos of the cellar and installation location may be needed.
Contact CellarCool Customer Service
1738 E. Alpine Ave
Stockton, CA, 95205
www.cellarcool.com
Visit www.emersonclimate.com/electronicunitcontroller for online brochures, bulletins, instruction videos, and general product
information.
Download the Copeland Mobile App on your mobile device for additional troubleshooting and technical information.
ACCESSORIES FOR COOLING UNITS
CellarCool offers accessories to enhance and customize your wine cooling unit.
Condensate Pump Kit
The condensate pump kit automatically removes water that drips out of the evaporator unit’s drain line. The pump is controlled
by a float/switch mechanism that turns the pump on when approximately 2¼” of water collects in the tank, and automatically
switches off when the tank drains to approximately 1¼”. The condensate pump kit allows the excess condensate to be pumped up
to 20 feet away from the unit.
Exterior Housing
If the cooling unit is installed outside, it will need protection from sun, wind, and rain. The exterior housing protects the condensing
unit portion of the split system from the elements when installed outdoors.
Accessories can be purchased at www.cellarcool.com
Page 42 | 1-855-235-5271
WM&FD 071217
Split System Series
Product Warranty Information
CellarCool Product Terms and Conditions
Including Product Limited Warranty And Product Installation Requirements
For CellarCool Split System Series
ATTENTION: PLEASE READ THESE TERMS OF USE CAREFULLY BEFORE INSTALLING YOUR CELLARCOOL COOLING
SYSTEM. INSTALLING YOUR CELLARCOOL COOLING SYSTEM INDICATES THAT YOU ACCEPT AND AGREE TO EACH OF
THE TERMS AND CONDITIONS SET FORTH HEREIN (“TERMS OF USE”). IF YOU DO NOT ACCEPT THESE TERMS OF USE,
YOU RISK VOIDING YOUR WARRANTY AND ASSUMING ADDITIONAL REPAIR AND REPLACEMENT COSTS.
1. Purchase of a CellarCool Cooling System assumes that the Purchaser (“End User”) fully accepts and agrees
to the Terms and Conditions set forth in this document. The Terms and Conditions of Sale and Owner’s Manual
are shipped with each unit and, if another copy is needed, replacement copies can be downloaded from the
company website (cellarcool.com) or by contacting CellarCool directly for a new copy. CellarCool reserves the
right, in its sole discretion, to change its Terms and Conditions at any time, for any reason, without notice.
2. CellarCool Product Installation and Limited Warranty
A. Purchaser of the product must arrange for the product to be installed by a certied HVAC/R technician in
accordance with procedures set forth by CellarCool and described in the CellarCool Owner’s Manual.
B. The HVAC/R technician installing the product must complete the designated portion of the Split Startup Checklist
and provide licensing or certication identication number information to assist in the warranty registration
process.
C. Purchaser must return the completed Split Startup Checklist to CellarCool within thirty (30) days of installation
of Product. The Split Startup Checklist must be approved by CellarCool to activate the Limited Warranty. If the
Split Startup Checklist is approved, Purchaser will be sent activation approval documents and will start receiving
the benets of the Limited Warranty throughout the warranty period. If the Split Startup Checklist is incomplete,
Purchaser will be informed they have ve days to complete the Split Startup Checklist and re-submit to
CellarCool. The Split Startup Checklist will be reviewed again, and if denied, Purchaser will be informed that they
have 10 business days for corrective action. Failure to register the Product may result in loss of warranty.
D. Purchaser is responsible for the full costs of installation and any additional parts required for the proper and
complete installation of the product.
E. For Split Systems returned to CellarCool in accordance with the terms and conditions of the Limited Warranty,
CellarCool warrants against defects in material and workmanship as follows:
1. LABOR - For a period of two (2) years commencing on the date of purchase, CellarCool will, at its option
and discretion, reimburse up to $250 to the End User for cost incurred for servicing, repairing, removing or
installing warranty parts. Invoice for service must be forwarded to CellarCool for assessment and
processing. The Split System warranty is invalid if there is attempted repair by anyone other than an HVAC/R
technician approved by CellarCool to service the Product.
2. PARTS - For a period of two (2) years commencing on the date of purchase, CellarCool will supply, at no
charge, new or rebuilt replacement parts in exchange for defective parts. Replacement parts are warranted
only for the remainder of the original warranty period.
3. FREIGHT - For a period of two (2) years commencing on the date of purchase, if after CellarCool approved
evaluation the original Product failure is determined to be the cause of a manufacturers defect, and not the
cause of an installation error or other cause, CellarCool will cover at its option, freight for the replacement
parts or Product.
The following part or cause of failure is not the responsibility of CellarCool:
www.cellarcool.com | Page 43
• Improper voltage supply
• Line set with screw connectors (high end and low end)
• Leaks found at the braze points when performing pressure check
• Unit that has been charged incorrectly
• Incorrect tubing diameter used on line set
• A unit that has been wired incorrectly
• Valve stem on condenser side
• Improper installation of P-Trap
• Lack of P-Trap (if required)
• Condensers that are installed outdoors or in elements that would aect operation without proper cover or
housing. (Housing is available from Manufacturer).
Product Warranty Limitations and Exclusions.
1. This limited warranty does not cover cosmetic damage caused during installation, damage due to acts
of God, commercial use, accident, misuse, abuse, negligence, or modication to any part of the Product.
Delivery and installation of the Product, any additional parts required, as well as removal of the Product if
warranty work is required, are all at the sole cost, risk and obligation of the End User.
2. This limited warranty does not cover damage due to improper installation or operation or lack of proper
maintenance of the Product, connection of the Product to improper voltage supply, or attempted repair of
the Product by anyone other than a technician approved by CellarCool to service the Product.
3. This limited warranty does not cover any Product sold “AS IS” or “WITH ALL FAULTS.”
4. Product that has been replaced during warranty period does not extend the warranty period past the
original date of purchase.
5. This limited warranty is valid only in the continental United States. Sales elsewhere are excluded from this
warranty.
6. Proof of purchase of the Product in the form of a bill of sale, receipted invoice or serial number, which is
evidence that the Product is within the Limited Warranty Period, must be presented by the End User to
CellarCool in order to obtain limited warranty service.
7. This limited warranty is void if the factory applied serial number has been altered or removed from the
Product.
8. This limited warranty is voided if installed in an enclosure of insucient design that does not follow the
Product installation requirements stated herein and in the owner’s manual.
9. Removing the rivets from the Product’s unit housing without prior authorization from CellarCool voids this
limited warranty.
10. The End User must rst contact CellarCool Customer Service by telephone (at 1-800-343-9463) prior to
attempting service on any Product still under the limited warranty; else the limited warranty is voided.
11. 11. This limited warranty does not cover Product being concealed by, but not limited to, vegetation, fabric,
shelving, mud, snow, or dirt. Product must not be painted or limited warranty will be void.
12. This limited warranty does not cover exposure to corroding environments such as, but not limited to,
petroleum and gasoline products, cleaning solvents, caustic pool chemicals, and marine air.
13. This limited warranty does not cover any cause not relating to Product defect.
14. THE REPAIR OR REPLACEMENT OF THE PRODUCT AS PROVIDED UNDER THIS LIMITED WARRANTY IS THE
EXCLUSIVE REMEDY OF YOU, THE END USER, AS WELL AS ANYONE ELSE IN THE CHAIN OF TITLE OF THE
PRODUCT, DOES NOT START A NEW LIMITED WARRANTY TIME PERIOD, AND IS IN LIEU OF ALL OTHER
WARRANTIES (EXPRESS OR IMPLIED) WITH REGARD TO THE PRODUCT. IN NO EVENT SHALL CELLARCOOL
BE LIABLE FOR INCIDENTAL, CONSEQUENTIAL, SPECIAL OR CONTINGENT DAMAGES FOR BREACH OF ANY
EXPRESS OR IMPLIED WARRANTY ON THIS PRODUCT. THE IMPLIED WARRANTIES OF MERCHANTABILITY
AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY EXPRESSLY DISCLAIMED. Some states do not
Page 44 | 1-855-235-5271
WM&FD 071217
1. allow the exclusion or limitation of incidental or consequential damages, or allow limitations on how
long an implied warranty lasts, so the above limitations or exclusions may not apply to you. This limited
warranty gives you specic legal rights, and you may have other rights, which vary from state to state.
2. Failure of the End User to comply with all of the Product Installation Requirements, Maintenance
Requirements and End User Requirements may, at CellarCool’s sole discretion, void this limited warranty.
3. No one has any authority to add to or vary the limited warranty on this Product.
3. Maintenance Requirements
The End User is responsible for checking the coils on the condenser unit and vacuuming them every three months
to maintain them free of debris. It is the End User’s responsibility to clean o any accumulated dust, lint, or other
debris from the front and rear intake grills; failure to do this on a regular basis will restrict the airow and may
aect the Product’s ability to function properly. Periodically cleaning the Product’s vents will help assure maximum
cooling eciency. The drain tube must also be checked and kept clean and free of debris and mold to maintain
proper performance.
Mold is a natural living organism in the environment. It exists in the air in the form of microscopic spores that move
in and out of buildings through doors, windows, vents, HVAC systems and anywhere else that air enters. Once it is
discovered, mold must be addressed quickly and appropriately. Delayed or improper treatment of mold issues can
result in costly and reoccurring repairs. If the End User suspects a mold problem, it is always best to hire a qualied
and experienced mold remediation specialist.
4. Additional End User Costs And Responsibilities
Terms and conditions for replacing the Product that is being evaluated for limited warranty.
1. After evaluation by a certied HVAC/R technician and the Product is found to be irreparable in the eld,
contact CellarCool Customer Service to arrange for replacement under the warranty guidelines. When a
claim for warranty is submitted for a condenser skid, the End User must purchase a new condenser skid
from CellarCool at retail price. Upon installation of the new condenser skid by a certied HVAC/R Technician,
the HVAC/R Technician must complete the Installation Checklist and End User must submit the Installation
Checklist to CellarCool Customer Service for approval. The original condenser skid must be returned within
21 days to CellarCool for failure analysis. If the Installation Checklist is approved and the failure is evaluated
as defective and not installation error or other reason, the End User will be refunded for the cost of the
replacement skid.
2. If the Product failure is evaluated and it is determined that it is an installation error or other reason, all costs,
including shipping will be the responsibility of the End User.
The following items are not covered under any warranty and are the sole responsibility of the End User:
A. End Users should satisfy themselves that the Product they are purchasing is suitable for their particular
needs and requirements, and thus no responsibility will be placed with CellarCool for the End User’s
decisions in this regard.
B. End Users must assure that the product is installed by a certied HVAC/R technician. Failure to do so will
result in Voiding the Limited Warranty.
C. It is the End User’s responsibility to secure safe haven/storage for ANY AND ALL items that are being kept
and stored in the End User’s wine cellar, including any Product. CellarCool takes no responsibility for
the safety and preservation of the aforementioned items in the event that the environment becomes
unsuitable to maintain a proper storage environment.
D. End User is responsible for initial installation costs, including, but not limited to, labor costs and the cost of
any additional parts necessary to complete the installation.
E. End User is responsible for all costs incurred for the installation and/or removal of the Product, or any part
thereof, unless such cost has been agreed by CellarCool to be a warranty repair prior to the work being
performed.
5. Sales and Use Tax
www.cellarcool.com | Page 45
CellarCool only collects California sales tax for orders shipped within the State of California; CellarCool does not
collect sales tax for orders shipped to other states. However, the Purchaser and the End User may be liable to the
taxing authority in their state for sales tax and/or use tax on the Product. The Purchaser and the End User should
each check with their state’s taxing authority for sales and use tax regulations.
6. Customer Service and Troubleshooting
CellarCool’s customer service department is available to answer any questions or inquiries for End Users regarding a
CellarCool Product, as well as to assist in performing basic troubleshooting, Monday through Friday, from 6:30 a.m.
to 4:00 p.m. PST, at telephone number 1-800-343-9463. CellarCool reserves the right to have a certied, CellarCoolapproved, HVAC/R technician go on site and inspect the product if the initial trouble shooting warrants further
investigation. CellarCool Corporation is located at 1738 East Alpine Avenue, Stockton, California 95205.
7. Request for Product Evaluation and Repair Under Warranty
SPLIT SYSTEM FIELD SERVICE WARRANTY POLICY: This Policy is to clarify what falls under Warranty Service and
what becomes the responsibility of the Owner. CellarCool (“manufacturer”) strives to provide our customers with a
superior Product and we back our Product with a Two Year Limited Warranty. Please review the CellarCool Product
Terms and Conditions including Product Limited Warranty and Product Installation Requirements to ensure you
have a complete understanding of our Policy and coverage of your Split System.
ARBITRATION: Any disputes arising out of or in connection with the installation and warranty of the Split System
shall be referred to and nally resolved by a CellarCool approved Independent Certied HVAC/R Technician. The
evaluation of the Technician on all issues or matters of identifying the responsible party (CellarCool or Installing
Technician) shall be determined in a written report. This report will be made available to all concerned parties. If
discovered under warranty, CellarCool will assume the nancial responsibility under their warranty guidelines.
If the report nds the Owner’s Installer as the responsible party, CellarCool will provide all documentation to
the customer to substantiate the ndings. This will include the Invoice from the Independent Certied HVAC/R
Technician and the written report of the ndings. The Owner will become responsible for payment directly to
CellarCool for all charges incurred for repairs (labor, parts and shipping costs) on the Split System.
8. Miscellaneous Terms and Conditions
A. Return Policy. All return inquiries must be made within thirty (30) calendar days of the original purchase of a
Product and are subject to a twenty ve percent (25%) restocking fee. Shipping costs are not refundable and the
Purchaser is responsible for all return shipping costs (including customs fees and duties, if applicable).
B. Security Interest. CellarCool retains a security interest in each Product until payment in full.
C. Construction and Severability. Every provision of these Terms and Conditions shall be construed, to the extent
possible, so as to be valid and enforceable. If any provision of these Terms and Conditions is held by a court of
competent jurisdiction to be invalid, illegal or otherwise unenforceable, such provision will, to the extent so held,
be deemed severed from the contract of sale between Purchaser and CellarCool, and all of the other non-severed
provisions will remain in full force and eect.
D. Governing Law/Choice of Forum. The laws of the State of California (without regard for conicts of law) shall
govern the construction and enforcement of the these Terms and Conditions of Sale (Sections 1 through 9
inclusive, including Product Limited Warranty And Product Installation Requirements), and further these Terms
and Conditions of Sale shall be interpreted as through drafted jointly by CellarCool and Purchaser. Any dispute
will be resolved by the courts in and for the County of San Joaquin, State of California, and all parties, CellarCool,
Purchaser and End User, hereby irrevocably submit to the personal jurisdiction of such courts for that purpose.
No waiver by CellarCool of any breach or default of the contract of sale (including these Terms and Conditions of
Sale) concerning a Product will be deemed to be a waiver of any preceding or subsequent breach or default.
E. Correction of Errors and Inaccuracies. These Terms and Conditions may contain typographical errors or other
errors or inaccuracies. CellarCool reserves the right to correct any errors, inaccuracies or omissions, and to change
or update these Terms and Conditions, at any time without prior notice.
9. Questions, Additional Information And Technical Assistance
A. Questions. If you have any questions regarding these Terms and Conditions or wish to obtain additional
Page 46 | 1-855-235-5271
WM&FD 071217
information, contact us via phone at 1-800-343-9463 or please send a letter via U.S. Mail to:
Customer Service
CellarCool Corporation
1738 E Alpine Ave
Stockton, CA 95205
B. Technical Assistance. CellarCool Customer Service is available Monday through Friday from 6:30 a.m. to 4:00 p.m.
PST. The Customer Service representative will be able to assist you with your questions and warranty information
more eectively if you provide them with the following:
1. The model and serial number of your CellarCool UNIT.
2. The location of the system and installation details, such as ventilation, construction of your wine cellar, and
room size.
Model ______________________________________ Serial Number __________________________
CWM/FD
Installed by __________________________________________ Date __________________________
www.cellarcool.com | Page 47
CellarCool
1738 E. Alpine Ave
Stockton, CA 95205
1(800) 343-9463
www.cellarcool.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.