C&D Technologies RS-937 User Manual

RS-937
STANDBY BATTERY RACKS ASSEMBLY INSTRUCTIONS
Applies to All rdb series pAcks
(reAd All instructions prior to instAllAtion)
These instructions detail the proper procedure for installing C&D Standard and EP (Earthquake Protected) battery racks. The following describes how to locate, assemble, and load open-frame battery racks for C &D battery mounting applications. Proper attention to these instructions will help ensure safe, trouble-free performance.
Two Tier Standard Rack Two Tier EP Rack
Figure 1. Standard Vs. EP Rack
Standard and Earthquake-Protected (EP) Racks:
Earthquake-protected racks are similar to standard racks, with the exception of additional frame bracing, battery constraints and spacer elements. Frames are the same for both Standard and EP series. EP racks are certified to Section 1630 of the Uniform Building Code, 1994 edition. See Figure 1.
Configuration:
Racks are available in single or multiple tier/step arrangements as shown in Figure 2. Rack components are supplied loose and must be assembled and secured on-site in accordance with these C&D assembly instructions, the drawings included with the rack shipment, and applicable codes.
Rack Location:
Locate racks in a clean, cool, dry place so the batteries are not affected by sources of radiant heat, such as sunshine, heating units, radiators, steam pipes, etc. Variations of more than 5 degrees F between cells may cause the battery to become electrically unbalanced. Top rows of batteries in multiple-tier configurations tend to operate at slightly higher temperature than those on lower tiers. Always provide adequate ceiling clearance for ventilation and maintenance.
Anchoring:
To provide stability, safety, and seismic integrity (for EP series), racks must be securely anchored to the floor. Anchor bolts are to be installed per contractor specifications and in accordance with applicable codes. Do not attach rack to walls without consulting C&D first. Mounting holes are provided in the base of each frame. All frames must be secured to floor using all anchor bolt locations. It is the responsibility of the customer to secure racks in accordance with allowable floor loading, applicable codes and regulations.
Grounding:
Rack grounding provisions are integrated into the base of each frame. Two through holes are located at the center of the frame’s bottom cross member and may be used to secure a standard NEMA lug. These holes are 0.44” in diameter and 1.0” between centers. The surfaces surrounding the holes have been masked and are free of powder coat to allow electrical contact. Frame to frame grounding integrity is accomplished via the lower support rail, attached to each frame with Internal/External “star” washers.
2-Step 1 Tier 2 Tier 3 Tier
Figure 2. Typical Rack Configurations
CAUTION:
• Donotinstallbatteriesuntiltherackhasbeenproperly
installed, with all bolts tightened to specified torque and frames anchored to the floor.
• Donotuseoilorgreaseasalubricantforcellinstallation.
Lubrication is usually not required due to the low friction interface of the insulating covers. If necessary, a small amount of water or unscented talcum can be applied to the rail covers to reduce friction.
Assembly InstructIons for stAndArd And eP rAcks
1 Material Verification : Battery racks are shipped
unassembled with a complete set of related drawings and documentation. Check received parts and quantities against the rack’s bill of materials on provided drawings and /or packing list. Do not assemble rack if parts are missing or quantities are incomplete.
2 Required Tools : Torque wrench (0 to 65 ft.-lb.) with 9/16”
and 3/4” Hex socket. Adjustable wrench or 9/16” and 3/4” box wrenches, tape measure, square and leveling device. Note: Consult manufacturer’s instructions for tools required to install floor mounting hardware.
2” Typical Clearance Around
Existing Boundary
3 Location of Rack Assembly: When determining rack
location and floor bolt pat tern, use applicable drawings provided with rack shipment. Locate the rack’s general position, considering boundar y and aisle clearances. Locate floor mounting locations using provided drawings. See Figure 3. Note: Floor mounting hardware is to be determined in accordance with applicable building codes, not by C& D.
4 Initial Assembly: Place frames over installed floor
mounting hardware, finger tight. (Hardware not supplied by C&D). All frames must face the same direction. Install back cross braces, finger tight. See Figure 4. Do not install front cross braces at this time (if required).
Note: Cross bracing pattern along the length of the rack may not necessarily be symmetric. Cross bracing pattern and location(front, middle, or back) is detailed on assembly drawing provided with the racks.
Cross Brace (s)
Frame
External Rack Dimensions.
See Assembly Drawing.
36” Typical Aisle
Clearance
Figure 3. Rack Assembly Location
and Anchor Bolt Pattern
Frame and Cross
Brace Connection.
See Detail 1.
Floor Mounting
Hardware
Figure 4. Initial Assembly
Frame Upright
Cross Brace
1/2-13 Bolt, Lock
Washer and Nut
Detail 1. Brace to Frame
connection ( Reverse View)
Loading...
+ 4 hidden pages