1. Read and follow all instructions contained in this manual before
installing, operating and maintaining this equipment. Failure to
do so could void the warranty, damage the equipment, or cause
sever injury or death.
2. Relieve all pressure before dismantling unit.
FLO-DRI - Cartridges
1. Do not use cartridge if the package has been damaged or seal
is broken.
2. Store cartridges at room temperature in a dry, dark place.
3. Avoid contact with eyes or exposed skin.
4. Contents may be harmful if swallowed or inhaled as dust.
5. Spilled or discarded product should be disposed of in accordance
with all applicable government regulations.
6. Contents may become hot if exposed to water.
HOW TO ORDER
Natural Gas Scrubber cartridge and mounting kit coded numbering system
is presented in Table 1, while the parts list is in Table 2.
INSTRUCTIONS
INSTALLATION PROCEDURE
A. Read and follow all instructions contained in this manual before
installing, operating and maintaining this equipment. Failure to do so
could void the warranty, damage the equipment, or cause sever injury
or death.
B. Review Figure 2 for NGS 1000 scrubber component nomenclature.
Refer to Figure 3 for mounting dimensions and NGS scrubber general
arrangement. Install scrubber units only in vertical position shown.
C. Install the NGS 1000 scrubber using appropriate mounting hardware.
Optional (factory supplied) universal mounting brackets are available.
D. Relieve and block all pressure before installing, maintaining, or
dismantling the NGS 1000 scrubber.
E. Remove the NGS 1000 scrubber cover (Item 3). Carefully inspect the
spring (Item 6), the O-ring (Item 8), and the covering/housing threads.
Remove any dirt, contaminants or residue from the cover/housing
threads prior to final assembly.
F. Read the label on the FLO-DRI Natural Gas Cartridge (Item 2) then remove
the cartridge from the factory-sealed bag. Ensure the contents of the
FLO-DRI cartridge are never exposed to water.
G. Insert the FLO-DRI cartridge (Item 2) into the scrubber housing (Item 1).
To help with this process you may choose to insert a sheet of rolled
paper or transparency into the scrubber hosing (Item 1) prior to
inserting the FLO-DRI cartridge. Remember to remove the paper or
transparency once the NGS cartridge has been installed.
H. Re-install the NGS cover (Item 3) using a 3/4” wrench and ensure
the cover has completely bottomed out and there is zero gap
between the cover and housing. CAUTION: DO NOT OVERTIGHTEN the cover or thread damage may occur. Contact the factory if
threads are damaged, corroded, stripped or galled. Ensure O-ring
is not pinched/deformed and that is not displaced from
the groove - realign O-ring into groove if necessary; ensure no dirt,
chips or foreign matter is trapped.
I. Ensure all fittings are installed and sealed in accordance with the
manufacturer’s specifications.
J. Verify that the drain cock (Item 7) is in the fully closed position
(clockwise hand tight) before pressurizing the system.
Figure 2 NGS 1000 Natural Gas Scrubber and FLO-DRI Cartridge
Table 2 Parts List
ITEM
DESCRIPTION
SCRUBBER HOUSING
1
CARTRIDGE
2
3
THREAD COVER
4
THREADED BASE
5
BAFFLE
6
CONICAL SPRING
7
DRAIN COCK
O-RING
8
SNAP RING
9
MOUNTING BRACKET
10
LABEL
11
FLODRI-10MS
PART NUMBER
NGS - 4
-
--
--
A16146-01
A16149-01
A10069-42
A16154-01
NGS-K
NGS - 12
FLODRI-25MS
A16146-02
-
A10069-43
A16154-02
-
MAINTENANCE PROCEDURE
I. Refer to Table 4 to determine the suggested change-out
frequency for your Cata-Dyne
II. Relieve and block all pressure before installing, maintaining,
or dismantling the NGS 1000 scrubber.
III. Release and contain any residual water and contaminates from the
drain bowl by opening the drain cock (Item 7) counterclockwise.
IV. Repeat step E of the Installation Procedure.
V. Remove and properly dispose of used or contaminated cartridges
in accordance with all applicable government regulations.
VI. Repeat steps F through J of the Installation Procedure.
When contacting the factory for service, replacement parts, supplies, or technical information, provide the model number of the scrubber and the
cartridge. Also, include the purchase order number, and the date of purchase
(if available).
CHANGE-OUT FREQUENCY
[
]
[]
6 x 61,2505601,5124401,184
6 x 122,500280756220592
6 x 245,000140378110296
8 x 8
10 x 124,166168454132355
12 x 125,000140378110296
12 x 2410,0007018955148
12 x 3615,000471263799
12 x 4820,00035952874
12 x 6025,00028762259
12 x 7230,00023631849
18 x 2415,000471263799
18 x 3018,750371012979
18 x 3622,50031842466
18 x 4830,00023631849
18 x 6037,50019501539
18 x 7245,00016421233
24 x 2420,00035952874
24 x 3025,00028762259
24 x 3630,00023631849
24 x 4840,00018471437
24 x 6050,00014381130
24 x 7260,0001232925
Table 4 FLO-DRI Cartridge Change Schedule in Days
WX Series
Heater
2
S (10 ppm)
2
FLODRI-25MS
Days
Moisture (50 ppm)
FLODRI-10MS
Days
FLODRI-25MS
2
Sour Gas H
Rating
(Btu/hr)
2,222240648189508
Table 4 shows cartridge change-out frequencies in days for each model
heater and gas scrubber for H S and moisture.
To determine the cartridge change-out frequency in days for other H S or
moisture concentrations, use the formulas provided in the
following examples:
FLODRI-10MS
Days
Days
Example 1: Sour Gas H S
Change-out
Frequency
Your installation has a Cata-Dyne™ heater, model
WX 12 x 24, 10,000 Btu/hr (2.928 kW/hr) natural gas using a model
FLODRI-10MS cartridge
=
The concentration of H S in your gas supply is 25 ppm.
•
•
The change-out frequency for 10 ppm is 70 days (derived from
Table 4).
COF = 70 days x 10ppm / 25 ppm = 28 days.
•
The FLODRI-10MS scrubber cartridge should be changed once
•
every 28 days.
2
# DAYS
(Table 3)
X
4
2
10 ppm
H S in Gas Supply
2
Example 2: Moisture
Change-out
Frequency
Your installation has a Cata-Dyne™ heater, model
WX 12 x 24, 10,000 Btu/hr (2.928 kW/hr) natural gas using a model
FLODRI-10MS cartridge.
•
•
•
•
# DAYS
=
(Table 3)
The concentration of moisture in your gas supply is 25 ppm.
The change-out frequency for 50 ppm is 55 days (derived from
Table 4).
COF = 55 days x 50 ppm / 25 ppm = 110 days.
The FLODRI-10MS scrubber cartridge should be changed once
every 110 days.
PLEASE ADHERE TO INSTRUCTIONS PUBLISHED IN THIS MANUAL.
Failure to do so may be dangerous and may void certain provisions of your warranty.
For further assistance, please call:
24 Hr. Hotline: 1-800-661-8529
(U.S.A. and Canada)
Please have model and serial numbers available before calling.
WARRANTY: Under normal use the Company
warrants to the purchaser that defects in material or
workmanship will be repaired or replaced
without charge for a period of 18 months from
date of shipment, or 12 months from the start date of
product was purchased for authorized repair or
replacement within the terms of this warranty.
Subject to State or Provincial law to the contrary, the
Company will not be responsible for any expense for
installation, removal from service, transportation, or
damages of any type whatsoever, including damages
arising from lack of use, business interruptions, or
incidental or consequential damages.
The Company cannot anticipate or control the
conditions of product usage and therefore
accepts no responsibility for the safe application and
suitability of its products when used alone or in
combination with other products. Tests for the safe
application and suitability of the products are the sole
responsibility of the user.
This warranty will be void if, in the judgment of the
Company, the damage, failure or defect is the result of:
• vibration, radiation, erosion, corrosion, process
contamination, abnormal process conditions,
temperature and pressures, unusual surges or
pulsation, fouling, ordinary wear and tear, lack of
maintenance, incorrectly applied utilities such as
voltage, air, gas, water, and others or any
combination of the aforementioned causes not
• any act or omission by the Purchaser, its agents,
servants or independent contractors which for
greater certainty, but not so as to limit the generality
of the foregoing, includes physical, chemical or
mechanical abuse, accident, improper
installation of the product, improper storage and
handling of the product, improper application or the
misalignment of parts.
manufacturing defects apparent within 30 days from
the date of installation.
The Company neither assumes nor
authorizes any person to assume for it any other
obligation or liability in connection with the product(s).
The Purchaser agrees that all warranty work required
after the initial commissioning of the product will be
provided only if the Company has been paid by the
Purchaser in full accordance with the terms and
conditions of the contract.
The Purchaser agrees that the Company makes
no warranty or guarantee, express, implied or
statutory, (INCLUDING ANY WARRANTY OF
MERCHANTABILITY OR WARRANTY OF FITNESS
FOR A PARTICULAR PURPOSE) written or oral, of
the Article or incidental labour, except as is expressed
or contained in the agreement herein.
LIABILITY: Technical data contained in the catalog or
on the website is subject to change without notice. The
Company reserves the right to make dimensional and
other design changes as required. The Purchaser
acknowledges the Company shall not be obligated
to modify those articles manufactured before the
formulation of the changes in design or improvements
of the products by the Company.
The Company shall not be liable to compensate or
indemnify the Purchaser, end user or any other party
against any actions, claims, liabilities, injury, loss, loss
of use, loss of business, damages, indirect or conse-
es (including legal expenses), costs, obligations and
causes of action of any kind arising wholly or partly
from negligence or omission of the user or the misuse, incorrect application, unsafe application, incorrect storage and handling, incorrect installation, lack
of maintenance, improper maintenance or improper
operation of products furnished by the Company.
Edmonton
1-800-661-8529
(780) 466-3178
F 780-468-5904
Oakville
1-800-410-3131
(905) 829-4422
F 905-829-4430
Orillia
1-877-325-3473
(705) 325-3473
F 705-325-2106
Greensburg
1-800-473-2402
(812) 663-4141
F 812-663-4202
Houston
1-855-219-2101
(281) 506-2310
F 281-506-2316
Denver
1-855-244-3128
(303) 979-7339
F 303-979-7350
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.