STANDARD HEATER APPLICATIONS
INSTALLATION & OPERATION INSTRUCTIONS
WARNING: Improper installation, adjustment,
alteration, excessive vibration, service or maintenance
can cause property damage, injury or death. Read the
installation, operating and maintenance instructions
thoroughly before installation or servicing this equipment.
Æ
BKI
1418
The Cata-Dyne™ heater can be used in all
industrial indoor locations where a source of
infrared radiant heat is required, providing
adequate ventilation is available.
CERTIFICATION
Model WX (Series X) & MKII Cata-Dyne™
Explosion-proof, flameless infrared catalytic gas
heaters are certied by the Canadian Standards
Association (CSA) for use in Class I, Divisions 1
and 2, Group D hazardous (classied) locations
and FM Approvals, for use in Class I, Division
1, Group D hazardous (classied) locations,
temperature code T2C at an ambient temperature
of 40ºC (104ºF). WXS models are suitable for
Class I, Division I, Group D, temperature code
T2B at an ambient temperature of 40°C (104°F).
Models WX & MKII are certied ATEX/CE for use
in gas environments, Category 2, Zone 1 & 2,
Group IIA.
The Model BX (Series G) Cata-Dyne™ heater
is certied by CSA and FM for use in general
industrial non-hazardous locations. Models listed
are certied for industrial use only, for either
natural gas or propane gas. CSA approved models
are equipped for high altitudes: 0 - 4,500 ft. (0-
1,370 m) above sea level.
INSTALLATION
To ensure maximum efciency of your Cata-
Dyne™ heater, it should be installed with the
heating surface positioned plus or minus 45° from
the vertical plane at a height of no more than
8 ft. (2.44 m). All heaters must be installed in
accordance with the latest revisions of the codes
described in table 4 and in accordance with any
local codes and regulations. Before installing the
heater, all information on the heater nameplate
must be carefully reviewed. The nameplate lists all
the fuel and electrical requirements for the heater.
Table 1
Cata-Dyne™ Heater - Models Available - CSA Only
Approved for use in Class I, Division 1 and 2, Group D hazardous (classified) locations by both FM and CSA T-Code T2C @ 40°C Ambient
Model Number Model Number
WX 6 x 6
WX 6 x 12
WX 6 x 24
WX 6 x 60
WX 8 x 8
WX 10 x 12
WX 12 x 12
WX 12 x 24
WX 12 x 36
WX 12 x 48
WX 12 x 60
WX 12 x 72
Approved for use in Class I, Division 1 and 2, Group D hazardous (classified) locations by both FM and CSA T-Code T2C @ 40°C Ambient
Model Number
BX 6 x 6
BX 6 x 12
BX 6 x 24
BX 6 x 60
BX 8 x 8
BX 10 x 12
BX 12 x 12
BX 12 x 24
BX 12 x 36
BX 12 x 48
BX 12 x 60
BX 12 x 72 30,000 36,000 8.786
The WX Series Cata-Dyne™ features an improved efciency catalyst pad that required nearly 33%
less fuel to generate the same value as our BX Series Cata-Dyne™ heater.
Specifications (Btu/hr Input Ratings)
For Both Natural and Propane Gas
Max. Btu/hr
1,250
2,500
5,000
12,500
2,222
4,167
5,000
10,000
15,000
20,000
25,000
30,000
Model Number
MKII 12x12
MKII 12x24
MKII 18x24
MKII 18x48
MKII 24x24
MKII 24x48
Approved for use in general industrial non-hazardous locations by both FM and CSA
Specifications (Btu/hr Input Ratings)
For Both Natural and Propane Gas
Max. Btu/hr
LPG NAT LPG NAT LPG
1,250 1,500 0.366 0.439 15,000
2,500 3,000
5,000 6,000 1.464 1.757 22,500 27,000 6.590 7.908
12,500
15,000 3.661 4.393 30,000
2,222 2,667 0.651 0.781
4,167 5,000 1.220 1.464 45,000 54,000 13.179
6,000
5,000
10,000 12,000 2.929 3.514
15,000 18,000
20,000 24,000 5.857 7.029 40,000
25,000 30,000 7.322 8.786
Approved for use in Class I, Division 1, Group D hazardous (classified) locations by FM, T-code T2B at 40°C ambient
Model Number
WXS 6 x 6
WXS 6 x 12
WXS 6 x 24
WXS 8 x 8
WXS 12 x 12
WXS 12 x 24
5918 Roper Road, Edmonton, Alberta, Canada T6B 3E1
Telephone: (780) 466-3178 Fax: (780) 468-5904
WX Model (Series X)
Max. kW
0.366
0.732
1.464
3.661
0.651
1.220
1.464
2.929
4.393
5.857
7.322
8.786
MK II Model (Series X)
BX Model (Series G)
Max. kW
LPG
0.732
1.464 1.757
4.393 5.272 30,000 36,000
WX 18 x 24
WX 18 x 30
WX 18 x 36
WX 18 x 48
WX 18 x 60
WX 18 x 72
WX 24 x 24
WX 24 x 30
WX 24 x 36
WX 24 x 48
WX 24 x 60
WX 24 x 72
Specifications (Btu/hr Input Ratings)
For Both Natural and Propane Gas
Max. Btu/hr
5,000
10,000
15,000
30,000
20,000
40,000
Model Number
NAT
BX 18 x 24
BX 18 x 36
BX 18 x 48
BX 18 x 60
BX 18 x 72
BX 24 x 24
BX 24 x 30
BX 24 x 36
BX 24 x 48
BX 24 x 60
10.543
Specifications (Btu/hr Input Ratings)
For Both Natural and Propane Gas
Max. Btu/hr Max. kW
1,750
3,500
7,000
3,111
5,833
7,000
14,000
Head Ofce & Factory:
Toll Free: 1-800-661-8529
Specifications (Btu/hr Input Ratings)
For Both Natural and Propane Gas
Max. Btu/hr Max. kW
15,000
18,750
22,500
30,000
37,500
45,000
25,000
30,000
40,000
50,000
60,000
Max. kW
1.464
2.929
4.393
8.786
5.857
11.715
Specifications (Btu/hr Input Ratings)
For Both Natural and Propane Gas
Max. Btu/hr Max. kW
18,000 4.393 5.272
36,000 8.786 10.543
45,000
37,500
20,000 24,000
50,000 60,000
10.983
48,000 11.715 14.058
14.644 17.572
0.513
1.025
2.050
0.911
1.708WXS 10 x 12
2.050
4.100
E-mail: info@ccithermal.com www.ccithermal.com
M20724-009 Date of Issue: July 2010
4.393
5.491
6.590
8.786
10.983
13.179
5.85720,000
7.322
8.786
11.715
14.644
17.572
NAT
5.4910.879 18,750 22,500BX 18 x 30
6.590
13.179
15.815
5.857 7.029
7.322 7.32225,000 25,000
8.786 10.543
![](/html/f1/f1e3/f1e31914bdae53d5bffc2d12e8a1b4df479c1746cec4faabfd6402b97f92732e/bg2.png)
Table 2
Cata-Dyne™ Heater - Models Available
CATA-DYNE
TM
HEATER- MODELS AVAILABLE FOR FM ONLY
Approved for use in Class I, Division 1 and 2, Group D h azardous (classified) locations by both FM and CSA T-Code T2C @ 40°C Ambient
Model Number
WX 6 x 12
WX 6 x 24
WX 8 x 8
WX 12 x 12
WX 12 x 24
WX 12 x 48
Approved for use in Class I, Division 1 and 2, Group D h azardous (classified) locations by both FM and CSA T-Code T2C @ 40°C Ambient
Model Number
MKII12x12
MKII18x24
MKII18x48
MKII24x48
Model Number
BX6x12 3,000 0.879
BX6x24
BX10x12
BX12x12
BX12x36
BX12x60
BX12x72
Approved for use in Class I, Division 1, Group D hazardous (classified) locations by FM, T-code T2B at 40°C ambient
Model Number
WXS 6 x 12
WXS 10 x 12
WXS 12 x 24
The WX Series Cata-Dyne™ features an improved efciency catalyst pad that required nearly 20%
less fuel to generate the same value as our BX Series Cata-Dyne™ heater.
Specifications (Btu/hr Input Ratings)
For Both Natural and Propane Gas
Max. Btu/hr Max. kW
2,500
5,000
2,222
5,000
10,000
20,000
0.732
1.464
0.651
1.464
2.929
5.857
Model Number
WX 18 x 30
WX 18 x 36
WX 18 x 60
WX 24 x 24
WX 24 x 30
WX 24 x 48
Specifications (Btu/hr Input Ratings)
For Both Natural and Propane Gas
Max. Btu/hr Max. kW
18,750
22,500
37,500
20,000
25,000
40,000
MK II Model (Series X)
Specifications (Btu/hr Input Ratings)
For Both Natural and Propane Gas
5,000
15,000
30,000
40,000
Approved for use in general industrial non-hazardous locations by both FM and CSA
Specifications (Btu/hr Input Ratings)
For Both Natural and Propane Gas
Max. Btu/hr
6,000
5,000
6,000
18,000
30,000
36,000
1.757
1.464
1.757
5.272
8.786
10.543
Model Number
BX18x30
BX18x36
BX18x60
BX18x72
BX24x30
BX24x48
BX24x60
Specifications (Btu/hr Input Ratings)
For Both Natural and Propane Gas
Max. Btu/hr Max. kWMax. kW
22,500
27,000
45,000
54,000
30,000
48,000
60,000
WXS Model (Series X)
Nat. Gas Btu/hr
3,500
5,833
14,000 4.100
Propane Btu/hr Nat. Gas kW
3,500
5,833
14,000
1.025
1.708
Max. kWMax. Btu/hr
11.715
1.464
4.393
8.786
5.491
6.590
10.983
5.857
7.322
11.715
6.590
7.908
13.179
15.815
8.786
14.058
17.572
Propane kW
1.025
1.708
4.100
Table 3
All Cata-Dyne™ Heaters
Installed In Canada
CSA/CAN – C22.1-02, Canadian
Electrical Code
CSA/CAN – B149.1-00, Natural
Gas and Propane Installation
Code
All Cata-Dyne™ Heaters
Installed In the USA
NFPA 70, National Electrical Code
NFPA 54, National Fuel Gas Code
NOTE: Ensure that the heater is not operational in an ex-
cessive vibration environment or premature failure of the
heater may occur.
All Cata-Dyne™ Heaters
Installed Internationally
Install according to local and
national/international fuel and
electrical codes.
Table 4
HEATER CLEARANCE
SPECIFICATIONS
Clearances
Appropriate clearances from the heating surface must be
observed during the installation of the Cata-Dyne™ heaters
(See Figure 1 & Table 4). Maintain nameplate clearances
from combustible materials such as wood, cloth, paper, etc.
If the heater is to be installed overhead maintain clearances
as stated in gure 1 & table 4 from vehicles parked below.
Fuels
The Cata-Dyne™ flameless gas heater is designed to
operate on clean, dry natural gas or propane as specied
on the heater nameplate.
Natural Gas - these heaters are designed to use natural
gas (1,000 Btu/ft3, 37 MJ/m3 ) at 7 in. w.c. (1.73 kPa), 4.5
in. w.c. (1.12 kPa), or 3.5 in. w.c. (0.86 kPa).
Propane - these heaters are designed to use propane
gas (2,500 Btu/ft3, 92 MJ/m3) at 11 in. w.c.
(2.72 kPa).
FIGURE 1
C
D
Note: Maintain nameplate clearances
from combustible materials such as
wood, cloth, paper as well as any
vehicles parked in the area of the
heater.
A
C
B
Radiant
Surface
Position
Vertical (0°)
0-45° up
0-45° down
Heaters
Up To
12,000 Btu/hr
(3.514 kW)
Over 12,000
Up To
48,000 Btu/hr
(14.058 kW)
Over 48,000
Up To
60,000 Btu/hr
(17.572 kW)
28 in. (711 mm) 42 in. (1067 mm) 60 in. (1524 mm) 12 in. (305 mm) 18 in. (457 mm) 18 in. (457 mm) 42 in. (1067 mm) 7 in. (178 mm)
42 in. (1067 mm)
28 in. (711 mm)
42 in. (1067 mm)
60 in. (1524 mm)
60 in. (1524 mm) 42 in. (1067 mm)24 in. (610 mm)22 in. (559 mm)
C - SidesD - Radiant Surface A - Top B - Bottom
All Heaters
Up To
60,000 Btu/hr
(17.572 kW)
12 in. (305 mm)
Heaters
Up To
12,000 Btu/hr
(3.514 kW)
18 in. (457 mm)12 in. (305 mm)
Over 12,000
Up To
48,000 Btu/hr
(14.058 kW)
Over 48,000
Up To
60,000 Btu/hr
(17.572 kW)
32 in. (813 mm) 54 in. (1372 mm)
18 in. (457 mm)18 in. (457 mm)18 in. (457 mm)
Heaters
Up To
12,000 Btu/hr
(3.514 kW)
0 in. (0 mm)
Over 12,000
Up To
48,000 Btu/hr
(14.058 kW)
12 in. (305 mm) 18 in. (457 mm)
12 in. (305 mm)28 in. (711 mm)
Over 48,000
Up To
60,000 Btu/hr
(17.572 kW)
18 in. (457 mm)
![](/html/f1/f1e3/f1e31914bdae53d5bffc2d12e8a1b4df479c1746cec4faabfd6402b97f92732e/bg3.png)
Piping
A main shut-off valve must be installed upstream of
1.
all auxiliary heater controls.
The 100% safety shut-off valve and appliance
2.
regulator (natural gas heaters only) must be installed
in the upright position (horizontally).
The thermostatic temperature controller should be
3.
installed with the dial shaft in the horizontal position.
The maximum inlet pressure to the 100% safety
4.
shut-off valve, thermostatic temperature control
and appliance regulator is 1/2 psi (3.4 kPa). If the
inlet pressure is higher than this, a low-pressure
service regulator must be installed upstream of these
components.
The maximum inlet pressure to the low-pressure
5.
service regulator (available from CCI Thermal) is
250 psi (1.7 MPa). If the inlet pressure is higher than
this, a high-pressure regulator must be installed
upstream.
FIGURE 2
Diagram illustrates typical Natural Gas installation.
Gas appliance regulators and manual shut off valves are
required standard components for all CSA approved heaters;
they are available as optional accessories for FM approved
heaters.
All components should be installed as indicated in
6.
Figure 2 (WX and BX models only) or Figure 3 (MKII
model only).
Electrical
1.
All wiring is to be installed in accordance with the latest
revisions of the Canadian Electrical Code (CEC)/
National Electrical Code (NEC) and/or any applicable
local codes.
2.
It is desirable to install an indicating light on all starting
systems. This will reduce the possibility of the power
being left on once the heater is started, which can
severely reduce the lifespan of the heater.
3.
Ground connections for 120 V and higher voltage
heaters are required as indicated in Figures 4 and 5.
The number of terminals in the junction box can be two
.
4
of four depending on the number of elements used in
the fabrication of the heater. All MKII models incorporate
a single element and therefore have only two terminals.
The connection procedure for the different combinations
is as described in Figures 4 and 5:
FIGURE 3
Diagram illustrates typical Natural Gas installation.
Gas appliance regulators and manual shut off valves are required
standard components for all CSA approved heaters; they are
available as optional accessories for FM approved heaters.
CAUTION:
Install MKII series heaters with controls on sides or bottom of heater
only.
FIGURE 4
FIGURE 5