Castell KS20-FSS-P-C/O4, KS Series User Manual

While every effort has been made to ensure the accuracy of the information provided, no liability can be taken for any errors or omission.
Castell Safety International Limited reserves the right to alter specications and introduce improvements without prior notice.
www.castell.com
1 of 6
U-KS-001-E Issue 2
KS
User Manual - Original Language Version
The KS is a key driven electrical switch designed for machine control circuits. This type of isolator should be used for short term, off load isolation. The KS is manufactured from either brass or stainless steel making it ideal for use in normal and harsh corrosive environments where the lock is subject to heavy use. The unit is able to be mounted into an existing panel or for surface mounting within its own polycarbonate IP65 rated enclosure.
Operation
KS20-FSS-P-C/O4
The Castell KS powersafe electrical key switch is used for machine isolation in order to protect the hazardous area from access while power is on.
1. While the power is on and a machine is running, the key is trapped in the KS key switch.
2. By turning and removing the key out of the switch, the contacts condition in the KS changes, switching the power off.
3. The key now can be taken to open the door lock and gain acces to the machine area.
The KS is available for different switching loads as KS20, KS32 or KS63 (20, 32 or 63 amps power isolation respectivly). Please refer to drawing on page 6 for more details.
The KS comes with 4 contacts as standard with contacts arrangements as 2NO/2NC, 4NC, but auxiliary set of contacts are available on request.
The KS is available as a back of panel mount version or as a front of panel mount with an enclosure. Please refer to drawing on page 6 for more details.
1
2
3
Key is trapped, while power is on.
Key is free, power is off.
KS20 powersafe electrical switch, back on panel mount
Turn and remove key to switch the power off by changing the contacts arrangement.
While every effort has been made to ensure the accuracy of the information provided, no liability can be taken for any errors or omission.
Castell Safety International Limited reserves the right to alter specications and introduce improvements without prior notice.
www.castell.com
2 of 6
U-KS-001-E Issue 2
KS
User Manual - Original Language Version
The KS powersafe electrical key switch is designed to be part of a safety system and is used to isolate the power releasing a key which is then used to gain access to a hazardous area via an access interlock such as the AI, AIE or Salus.
The KS key switch is not designed for security purposes.
No hazardous substances were used in the manufacture of this product. The product can be disposed of in standard waste.
Usage
Installation
Front of panel units should be mounted to a at surface using 4 off suitable xing screws. Offer up back box of enclosure in
desired position and use mounting holes as a drilling template.
Back of panel units should be mounted to a at surface using suitable fasteners (please refer to drawing on page 4 for more
details). The lock face should be sealed to the panel for ingress protection.
Cables should be connected to the switch (via the cable gland for front of panel) in accordance with the applicable wiring diagrams. Ensure that the unit is bonded for earth continuity (see drawing on page 4 for more installation details).
IMPORTANT: The interlock should be mounted using anti-tamper fasteners to prevent unauthorised removal.
The KS range of switches must be installed by a competent and qualied person who has read and understood these instructions. Please retain this document in your technical le.
Maintenance
Periodic visual checks should be carried out by the site manager / safety ofcer.
Do not lubricate lock barrel with oil or grease, use CK Dry Powder Graphite if necessary.
In case of defects beeing detected please contact your nearest Castell Support Department for further actions. Please see Contact section for contact details.
Loading...
+ 4 hidden pages