adjusting. (Fig.5)
to lock its position after
Snap the knob back down
increase pressure. (Fig. 4)
pressure or clockwise (+) to
clockwise (-) to decrease
Fig. 3
(Fig.3) then turn counter
Adjustment Knob upward
pull the ORANGE
To adjust outlet pressure,
Pressure Adjustment:
PRESSURE REDUCING VALVE
For Water Service, with Bronze or Stainless Steel Body and Inbuilt Back-Pass-Check
2400 7th Ave. SW,
Cullman, Al 35055
www.cashacme.com
1-877-700-4242
3
A division of the Reliance Worldwide Corporation
Fig. 1
Arrow
adjust outlet pressure
pressure indicator to
Do not turn
IMPORTANT!
outlet pressure. (Fig. 2)
display approximate
Pressure Indicator will
Pressure Indicator. The
indicated by the
preset to the value
outlet pressure is factory
Pressure Indicator. The
rotated to best view the
Fig. 2
Cartridge can be
Pressure Reducer
If necessary, the
Indicator:
Viewing Pressure
Direction
Cartridge
Reducer
Pressure
Indicator
Pressure
Knob
Adjustment
aligned.
inlet and outlet pipework are properly supported and
Body)(Fig. 1). Avoid stressing the valve by ensuring that
with the direction of flow (indicated by arrow on the Valve
accessible location and orient the valve to correspond
downstream to ease in servicing the valve. Install in an
ing valves be installed both upstream and
installing valve. It is recommended that isolatThoroughly flush out the system before
Installation:
1 2
![](/html/ec/ec3f/ec3f52d83ec81000705135283ae7fbe08b1bff0b36888502beb57d683914e5d2/bg2.png)
Maintenance:
Close isolating valves upstream and
downstream before attempting to
4 5
Cartridge Nut. (Fig. 6 and Fig. 7)
service the valve. Unscrew the
After valve is installed, reset pressure if necessary,
(see Operation Instructions). Make sure valve is
clean of dirt and debris. Slip provided O-Ring
over cartridge until seated against Cartridge Nut.
Burial Instructions (Optional Cover)
Available for sizes 1/2", 3/4" & 1" only:
Burial Depth should be in accordance
with local plumbing codes.
Fig. 6
Fig. 7
Remove the Pressure Reducer Cartridge by pulling
straight up. (Fig. 8) Clean with cold water only.
Replace the Strainer Screen before re-installing the
Pressure Reducer Cartridge. (Fig. 9) Orient the
Pressure Reducer Cartridge to best view indicator.
Fig. 8
Fig. 9
Performance:
Outlet pressure range:
EB25 . . . . . . . . . . . . . . 8-35 or 20-90 psi
EB25-400 & EB25-SS . . . . . . 20-90 psi
Maximum temperature . . . . . . . .180° F
Maximum initial pressure:
EB25 & EB25SS . . . . . . . 300 psi
EB25-400 . . . . . . . . . . . . 400 psi
EB25 Multi-Cartridge . . 250 psi
Service . . . . . . . . . . . . . . . . . Water
Cold
Typical Installation
Schematic
Supply to
Fixtures
Tempered
Supply to
Fixtures
VR-801
Vacuum
Relief
Heatguard
110-D
Mixing Valve
Fig. 10
Fig. 11
Orient direct burial cover in such a way that it can
be snapped into position. (Fig. 12 and 13)
Fig. 13
Burial Cover
Sold Separately
I0445 REV. B
Strainer Screen
Coupling Nut
Union Tailpiece
INLET
Fig. 12
Pressure Indicator
O-Ring
O-Ring
Adjustment Knob
Pressure Reducer Cartridge
Cartridge Nut
Valve Body
TE Thermal
Expansion
Tank
Water
2000
Main
Supply
California “Propostition 65” Warning:
This product contains a chemical known to the State of California to cause cancer,
birth defects or other reproductive harm.
Note to Installer/Contractor: California law requires that this notice be provided to the
consumer/end user of this product.
Series
Ball
Valve
Meter
BF
Backflow
Preventer
EB-25
Pressure
Regulator
2000
Series
Ball
Valve
Floor
Drain
NCLX
T&P
Valve
Type EB25, EB25-SS & EB25-400
PRESSURE REDUCING VALVE
For Water Service, with Bronze or Stainless Steel Body
and Inbuilt Back-Pass-Check
2400 7th Ave. SW • Cullman, Al 35055 • www.cashacme.com