Casals BT2 100, BT2 150, BT2 125, BT2 160, BT2 200 Operating Instructions Manual

...
Page 1
1
Circular Duct Fan
OPERATING INSTRUCTIONS
BT2
www.casals.tv
DECLARATION OF CONFORMITY
DECLARATION OF CONFORMITYDECLARATION OF CONFORMITY
DECLARATION OF CONFORMITY
We here
by declare, under our only responsibility, that the CASALS brand products described in this
manual comply with the directives 2006/42/CE (Machinery), 2004/10/CE (Electromagnetic compatibility), 2006/95/CE (Low Voltage) also with all the standards mentioned in this manual.
Page 2
2
All fans manufactured and supplied by VENTILACIÓN INDUSTRIAL S.L. comply with the EC regulation (MACHINES), 2006/42/CE, 2004/10/CE (Electromagnetic compatibility) as well as the security regulation for low voltage materials 2006/95/CE (former 73/23/EC). Each particular range also complies with more specific rules and regulations required.
Regulations:
GENERAL FEATURES
Range with 7 different standard diameters from Ø 100 to Ø 315, provided with single phase external rotor motor. Air-flow from 240m³/h to 1.500m³/h. Maximum working temperature 55ºC.
MANUFACTURING FEATURES:
Housing and impeller in quality steel sheet, surface finishing with strong resistance to rust. External connection box PVC. External rotor asynchronous motor IP44 with F class insulation. Standard voltages 220-230V 50Hz.
APPLICATIONS:
Designed for in-line duct installation. Suitable for general ventilation in toilets, bathrooms, kitchens, shops and small extraction applications. NOT SUITABLE TO OPERATE IN HAZARDOUS AREAS (ATEX).
CHARACTERISTICS
MODEL
Rated power
kW
Rated current
(A) 230V
Max. Airflow
m3/h
RPM
dB(A)*
Kg
BT2 100
0,066
0,32 260 2300
40
3
BT2 125
0,073
0,33 350 2130
42
3
BT2 150
0,091
0,42 550 2415
42
4,5
BT2 160
0,105
0,48 600 2120
43
5,5
BT2 200
0,175
0,8 900 2470
46
5,7
BT2 250
0,156
0,71 1000
2380
50
6
BT2 315
0,202
0,92 1600
2500
49
7
DIMENSIONS
MODEL
A B C D E F
BT2 100
98,2 286 170 243 196 275
BT2 125
125 286 170 243 196 275
BT2 150
147 377 170 33 217 365
BT2 160
160 377 170 333 217 365
BT2 200
198 377 170 333 216 365
BT2 250
247 377 170 333 216 365
BT2 315
315 444,5
170 402 255 434
Page 3
3
INSTALLATION AND OPERATION:
STANDARD INSTALLATION
1. Before connecting the fan, rotate the impeller with your hand and check that it is not blocked and that it turns smoothly.
2. Connect the fan and check that the rotation of the impeller is according to the arrow indicated on the label. Check that there are not abnormal noises or vibrations.
3. This is a fan conceived for duct installation. Current should be measured the first time it is connected to source, check that it does not exceed the rated current indicated in the fan plate.
CONNECTION DIAGRAMS
TRANSPORTATION AND STORING
The transport agency and intermediaries that have been involved in the process of transportation and storing until final destination are liable for any damages incurred during this process. They should also be responsible for all the necessary paperwork involved to attend and solve with the client all the damages incurred not covered by the manufacturer’s guarantee. Any hits or bumps can damage the most sensible components of the fan like the bearings, motors or the rotating pieces like the turbines or propellers (elements that can be deformed or stuck resulting in their unbalancing). While being stored until later installation, the protection must be guaranteed against: dust, rain, UV rays (direct exposing to sun), high atmospheric humidity, and sudden changes of temperature. These harmful agents are the main cause of sudden deterioration of the fan as they can damage it by rusting the components and deteriorating the coatings.
QUALITY CONTROL
FUNCTIONING: All fans before delivery are submitted to an electric security and functioning test. Hence if
the fan has not suffered any damage during transportation and is installed correctly following these instructions, the correct functioning is assured. BALANCING: The rotating element “propeller or turbine” of the fan has dynamically balanced and may experience some residual unbalancing within the accepted tolerances according to the regulations ISO1940-1 and ISO10816-1, quality Q 2.5 or Q 6.3 depending on the models. Still it is advised to verify before installing it by manually rotating such element and check that no friction or any bumps or deformation appear due to transportation damage. Do not install nor turn on the fan if any damage is
visible, check first with our technical department
Page 4
4
PRODUCT GUARANTEE
CASALS will always supply the requested fan and in accordance to all specifications that the service or installation requires. Therefore, all elements used in the chosen model are only suitable for the working conditions specified by the client in the purchase order.
IMPORTANT: CASALS is exempt of any responsibility of any possible accident caused by the wrong manipulation of the fan and/or for non-compliance of all the warning and security regulations detailed in this manual. GUARANTEE PERIOD: The fans are guaranteed for 1 year after the purchasing date (keep the invoice).
Such period will expire even if the fan has not been installed nor used immediately after its acquisition at CASALS. The guarantee will not be valid if there is any damage or breakdown of the fan or third parties affected by wrong use or inadequate purpose, normal worn out, overcharge or any external manipulation not done by CASALS technical dept. The obligation inherent in this guarantee is limited to the replacement of defective parts previously examined by our specialists.
Installation, maintenance, possible modifications and repairing services of the fan must always be done by trained specialists. During the guarantee period of the fan, repairing can only be done under previous consent from CASALS and by authorised shops and staff. CASALS WILL ALWAYS DETERMINE WHERE ANY REPAIRING SHOULD BE DONE ON FANS THAT STILL HAVE A VALID GUARANTEE AS WELL AS THE TRANSPORT AGENCY USED FOR THE MOVING IF NEEDED. THIS GUARANTEE DOES NOT COVER THE TRANSPORT COSTS OF ANY SMALL FANS TO THE SUGGESTED TECHNICAL SERVICE. NON CONFORMITY RETURNS: Returns of non conformity material will only be accepted whenever there
is an administrative error, change or supplying mistake, if previously agreed by our commercial dept or SALES REPRESENTATIVE and also the return form is filled accordingly. The transport agency will be determined and agreed by CASALS. No return will be accepted without the form filled completely. NEW MATERIAL RETURNS: If there is a mistake from the client’s side, 25% depreciation will be applied on the new material returned. The transport costs will be assumed by the client.
INSTALLATION AND START UP OF THE FAN
ELECTRICAL CONNECTION AND INSTALLATION: Each model fan has a connection drawing inside the
terminal box. The feeding cable connection should be done inside such terminal box of the motor or fan. It is important that the feeding lines and other components used in the installation meet the requirements of the valid regulations of industrial installations.(“Low pressure electrical regulation”) and that the protection system are in accordance to the power of the fan (Motor protection system, differential protection, wiring limit and ground system).
MAINTENACE OF THE FAN
It is recommended a complete check up of the fan and its installation after the first 24 hours after start up, by electrically disconnecting it from the network in order to avoid accidents. In installations where the fan is usually not operating, periodically inspect the fan maximum every 6 months. CONSIDERATIONS DURING REVISIONS: The following are some points to be taken into account during a revision to guarantee correct functioning of the fan:
1. The functioning of the fan must be smooth and free of vibrations.
2. The ampere consumption (A) should be measured with a hook-on meter or tester can never exceed the nominal consumption “In(A)” specified in the motor’s plate.
4. In applications where the fan works in a high dust or greasy air environment, the blades of the impeller or propeller can be unbalanced due to the accumulation of particles and consequently damage the bearings. Therefore, cleaning of the rotating element must be done periodically using the maintenance stops or whenever the fan vibrates or does not work correctly. Never leave the dust inside the fan. Avoid
accumulations of dirt, dust, grease, etc. it is main cause of fires and its spreading.