CARRON CAST IRON STOVE, DANTE SE Installation And Operating Instructions Manual

A qualified solid fuel engineer must carry out the installation of this stove.
We cannot accept responsibility for products not installed in this way.
All local regulations, including those referring to national and European
Standards need to be complied with when installing the appliance.
A list of qualified engineers is available from: www.hetas.co.uk
CARRON CAST IRON STOVE
INSTALLATION AND OPERATING INSTRUCTIONS
CARRON DANTE STOVE SE (WOOD BURNING ONLY) BHC401-406 – Dated 12th Jan 2011
JIG UK Ltd, Hurlingham Business Park, Fulbeck Heath,
Grantham, Lincolnshire, NG32 3HL
email: sales@carron.uk.net freephone: 0808 129 2224
www.carron.uk.net
Technical Data
Flue Connection
JIG UK Ltd
Hurlingham Business Park
Fulbeck Heath
Grantham
Lincolnshire
NG32 3HL
07
EN13240:2001
THE CARRON STOVE
Minimum distance to combustible materials:
Behind the stove: 400mm
To the side of the stove: 400mm
CO at 13% 02: 0.64%
Flue gas temperature: 268ºC
Efficiency:76.9%
Nominal Output: 5.0kW
Fuel Type: Wood
Output 5.0 kW Efficiency 76.9 % CO at 13% 02 0.64 % Flue temperature 268 °C Flue draught 12 Pa Flue gas mass flow 4.0 g/s Weight of Stove 70.5 Kg
Wood
Attach the flue outlet to the stove with the screws and nuts provided. Use a steel closure. Attach the flue outlet to the stove with the screws and nuts provided. Use a steel closure plate to seal off the chimney; a cleaning door must be fitted into the plate or flue, and a steel sealing collar must be used to fit the flue into the steel plate. Seal all joins with fire cement.
Replacement parts list
1
2
3
4
5
67
1. Asphan (BHC213) 4. Front firebar (BHC208) 7. Glass (BHC211)
2. Grate frame (BHC210) 5. Firebrick set (BHC212)
3. Grate (BHC209) 6. Handle (BHC214)
Installation instructions
Ensure that the floor has sufficient load bearing capacity. Fit a load bearing plate if necessary.
To ensure that your chimney meets the required specifications it must: -
- be at least 5 metres high
- have no bends sharper than 45 degrees
- be swept clear of any obstructions by a qualified chimney sweep
- terminate at least 1 metre above any roof ridge
- have an internal cross-section of between 0.018m
2
and 0.14m
2
- be free from sources of leakage
- be connected only to the one appliance i.e. not a shared flue system
- be well insulated, or have a wall thickness of at least 100mm
- Please note this stove has had its secondary air supply modified with a permanent 14mm supply.
Place the stove on a solid non-combustible hearth extending 300mm at the front of the stove, 150mm either side of the stove and 50mm at the rear. The hearth must have a thickness of at least 12mm. The maximum hearth temperature attained during testing was 78.6°C (Refer to document J of the UK Building Regulations)
Ensure there is a permanent air entry opening or openings with a total free area of at least 550mm
2
per kW of appliance rated output above 5kW,
ie 2kw x 550 mm
2
=1100 mm2.
When installing any air inlet grilles ensure they are positioned so they are not liable to blockage.
Note: The Stove must not be installed in a room with an extractor fan operating.
Operating Instructions
Fuels suitable for use in your Carron Stove: -
Wood – logs (no larger than 225mmx75mmx75mm) should be dried for at least a year prior to burning, for other fuels please contact the manufacturer. The stove is suitable for intermittent operation and we recommend a refuel time of 1 hour.
Fuels unsuitable for use in your Carron Stove: -
Petroleum Coke – this burns with an extremely high heat and its use will cause damage to the stove.
Household Waste – can produce dangerous fumes and should not be burnt in the stove. No liquid fuels to be used on this stove, please remember that this stove is not an incinerator.
Lighting the stove for Woodburning
Please note that the first fire you light in your stove should be small. This will prevent possible damage to the stove.
To establish clean burning, it is important to get the appliance hot as quickly as possible and these instructions must be followed. Clean burning can be achieved with the following regime:-
Open primary and secondary air controls to maximum Light a double-handful of kindling with a couple of firelighters leaving the door open
5-10mm. Allow these sticks to become well-alight before :­After about 8 mins, add two small sized logs (each about half the size of a "standard" 9
inch log). Let these burn well and after another 8 mins approx, add a normal fuel load of two 9 inch logs and leave the door open for a further 3 mins. You may now operate the stove as normal.
In normal operation, keep the primary air closed and control the burning rate (output) with the secondary air control
Do not leave the stove unattended during lighting. After the ignition procedure is complete, the stove must not be operated with the door open.
Refuelling
Following refuelling the door must reamin open by 5-10mm for 5 minutes with the primary air control open. This ensures a clean burning is achieved. Following this 5 minutes the door and the primary air control should be closed and the secondary air control to be set as required.
Always allow a bed of embers to become established on the grate. There is normally no need to de-ash the grate, simply gently break up the nearly burnt-out logs with the refueled logs when placing the new fuel on the fire.
If there is insufficient burning material in the fire bed to light a new fuel charge, excessive smoke emission can occur. Refuelling must be carried out onto a sufficient quantity of glowing embers and ash that the new fuel charge will ignite. If the fire bed is too low or cool, suitable kindling must be used to relight fires.
Do not fill the stove to a level higher than the bricks. The maximum amount of fuel specified for this manual should not be exceeded, overloading can cause excess smoke. Operation with the door open can also cause excess smoke. The appliance must not be operated with the air controls or dampers doors left open except as directed in the instructions. Do not leave the fire unattended until the new fuel added has ignited.
Controlling the stove - Setting the primary air supply (the inlet below the glass door) air control – sliding the air control to the right will allow the maximum amount of air into the stove, and cause the fire to burn quickly. Sliding it to the left will allow the minimum of air into the stove, and the fire will burn more slowly, and give off less heat. Setting the secondary air supply (the inlet above the glass door) air control – is the same operation as above. These air supplies must be kept clear of blockages and regularly checked.
If the stove goes out with fuel still in it, the air controls are set too low. Generally the ideal setting is to have the primary inlet almost closed and the secondary inlet 1/2 open. However this may vary depending on the flue draught and you will need to fine tune these settings to suit your preferred burn rate. Should the stove overheat, shut down the stove by ensuring the door and all inlets are closed. Operation with the air controls or dampers open can cause excess smoke. The appliance must not be operated with the air controls or dampers doors left open, except as directed in the instructions.
Cleaning the stove – To ensure the performance of your stove is not affected, regular cleaning is necessary. To clean, allow the stove to cool, then wipe with a soft damp cloth. The throat plate should be removed and cleaned monthly along with checking the door seals for damage.
Do not use any abrasive cleaning products, as they will damage the finish of the stove. The window is self-cleaning due to the “air-wash” at the top of the door. The use of
damp fuels may cause staining of the window. After long periods of non-use it is necessary to check the flue for blockages.
Emptying ashes – ensure ashes are entirely cool before they come into contact with plastic dustbins or bin-bags. It is important that ash does not build up to the extent that it contacts the underside of the grate.
Precautions to note:
Carron stoves do not contain asbestos. However, please take care not to disturb any existing asbestos when removing an old stove.
The stove is very heavy; move it with assistance. Take care to ensure fire cement does not come into contact with skin. In the unlikely event of a chimney fire, close the stove door and both air supplies,
evacuate the property immediately, and call the fire brigade. Do not attempt to extinguish your stove.
Persistent fume emission should not occur if the product is properly installed and operated. However, should this occur, take immediate action as follows:-
- ventilate the room
- extinguish the fire
- check the chimney/flue for blockages and clean if required
Seek expert advice if necessary. The stove and flue pipe will become extremely hot during use; take care especially
when children or the infirm are present. Do not store flammable materials near to the stove. Any combustible furnishings must be at least 500mm away.
Only use replacement parts supplied by the manufacturer and do not modify the stove in any way.
Loading...