Carrier Access KSALA0201R22, KSALA0301410 Installation Instructions Manual

Page 1
KSALA0201R22 KSALA0301410
Installation Instructions
Low-Ambient Pressure Switch
NOTE: Read the entire instruction manual before starting the installation.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factoryauthorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit.. Consult local building codes and current editions of the National Electrical Code ( NEC ) NFPA
70. In Canada, refer to current editions of the Canadian electrical code CSA 22.1.
!
Recognize safety information. This is the safetyalert symbol When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safetyalert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
!
INTRODUCTION
These instructions cover the installation of Low−Ambient Pressure Switch Part No. KSALA0201R22 and KSALA0301410 in all singlespeed air conditioners or heat pumps using R22 or R410A refrigerant. This kit is also acceptable for use on 2stage air conditioners or heat pumps using R410A and permanent split capacitor (PSC) fan motors.. Refer to Table 1 for kit usage.
DESCRIPTION AND USAGE
The LowAmbient Pressure Switch Kit is a longlife pressure switch which turns the fan on and off as shown in Table 1. It is wired in series with black fan lead. Sleevebearing motors can be used with this control.
Other accessories may be required. Refer to the Required Changes for Cooling Units and Heat Pump Units section in this document for further details.
.
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts.
!
CAUTION
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
Page 2
INSTALLATION
The pressure switch is mounted inside the outdoor unit cabinet by using adapter tube supplied. The adapter tee is mounted to liquid service valve and tube is either routed through one of the knockout holes in unit cabinet (vertical discharge product) or through one of the service valve holes in unit cabinet (horizontal discharge product). From inside cabinet, the flare nut is attached to extender tube. (See Fig. 1.) The pressure switch is wired in series with black or common fan lead.
WIRING FOR ALL VOLTAGES OF COOLING UNITS
A. Single And TwoStage NonCommunicating Capable
For all voltages of cooling units, refer to Fig. 2 and wire lowambient pressure switch as follows:
1. Disconnect black fan lead from contactor and connect this lead to yellow or violet wire from lowambient pressure switch using connector supplied.
NOTE: To ensure electrical isolation and strain relief, it is recommended to wrap connector with UL approved electrical tape overlapping the wires on each side by a minimum of 1 inch.
2. Connect remaining blue wire from lowambient pressure switch to contactor terminal from which black fan lead was removed.
B. Single− And TwoStage Communicating Capable
For all stages of cooling units, refer to Fig. 3 and use LowAmbient Pressure Switch as follows:
1. Disconnect black fan lead from control board and connect it it to yellow or violet wire from low ambient pressure switch connector supplied.
NOTE: To ensure electrical isolation and strain relief, it is recommended to wrap connector with UL approved electrical tape overlapping the wires on each side by a minimum of 1 inch.
2. Connect blue wire from lowambient pressure switch to control board terminal from black fan lead was removed.
WIRING FOR HEAT PUMPS
Heat pumps require a normally closed Isolation Relay (Part No. KHAIR0201AAA or equivalent) with the 24v coil connected to the C and O terminals of defrost board or control board.
A 208/230v Applications
For 208/230v heat pump applications, refer to Fig. 4 and wire lowambient pressure switch as follows:
1. Remove black lead of outdoor fan motor connected to de­frost board OF2 or control board ODF depending on type of unit.
2. Install piggyback female terminal on violet wire harness (provided in isolation relay kit) to tab 1 of isolation relay. Connect nonpiggyback female termination of same violet wire to one side of provided connector. Connect the female termination of violet (or yellow) lead of low ambient pres­sure switch to the other side of the provided connector. Connect the female termination of the black fan motor lead to the male piggy back terminal located at tab 1 of relay.
NOTE: To ensure electrical isolation and strain relief it is recommended to wrap connector with UL approved electrical tape overlapping the wires on each side by a minimum of 1”.
3. Install piggyback female terminal on black wire harness (provided in isolation relay kit) to tab 2 of relay. Connect nonpiggyback female termination of same black wire to OF2 on defrost board or ODF on control board. Connect the female termination of blue lead of low ambient pressure switch to the male piggy back terminal located at tab 2 of relay.
4. Install orange wire (provided in isolation relay kit) to one side of the relay coil. Connect the other side to the O wire coming from defrost board or control board.
5. Install black wire (provided in isolation relay kit) to oppos­ite side of the relay coil. Connect the other side to the C wire coming from defrost board or control board.
6. Reinstall control box cover and reconnect power to unit.
B. 460v Applications
For 460v heat pump applications, refer to Fig. 5 and wire
ambient pressure switch as follows:
low
1. Remove black lead of outdoor fan motor connected to out­door fan relay terminal 3.
2. Install piggyback female terminal on violet wire harness (provided in isolation relay kit) to tab 1 of isolation relay. Connect nonpiggyback female termination of same violet wire to one side of provided connector. Connect the female termination of violet (or yellow) lead of low ambient pres­sure switch to the other side of the provided connector. Connect the female termination of the black fan motor lead to the male piggy back terminal located at tab 1 of relay.
NOTE: To ensure electrical isolation and strain relief it is recommended to wrap connector with UL approved electrical tape overlapping the wires on each side by a minimum of 1” (25.4 mm).
3. Install piggyback female terminal on black wire harness (provided in isolation relay kit) to tab 2 of relay. Connect nonpiggyback female termination of same black wire to outdoor fan relay terminal 3. Connect the female termina­tion of blue lead of low ambient pressure switch to the male piggy back terminal located at tab 2 of relay.
4. Install orange wire (provided in isolation relay kit) to one side of the relay coil. Connect the other side to the O wire coming from defrost board or control board.
5. Install black wire (provided in isolation relay kit) to oppos­ite side of the relay coil. Connect the other side to the C wire coming from defrost board or control board.
6. Reinstall control box cover and reconnect power to unit.
REQUIRED CHANGES FOR COOLING UNITS AND HEAT PUMP UNITS
1. Crankcase heaters are required on all applications where lowambient controls are used.
2. Start capacitor and relay (hard start) kits are required on all singlephase applications where lowambient controls are used.
3. Evaporator freeze thermostat KAAFT0101AAA is required on all applications where lowambient controls are used.
4. Wind baffles are recommended for temperatures below 0_F (17.80_C) or where there is substantial wind. For vertical discharge outdoor products see Fig. 7 for dimensions of Baffle Assembly. For horizontal discharge outdoor products consult Product Data for Wind Baffle Kits.
NOTE: When wind baffles are used on vertical discharge products, raising the unit off of pad a minimum of 4 in. is required to provide better airflow for moderate− and high−ambient temperatures. Check presale literature for available support feet or unit risers.
5. For cooling applications only, winter start control KAAWS0101AAA must be used where low−pressure switch tripping may be encountered. Winter start control must be wired in parallel with low−pressure switch. This al- lows a delay of 3 minutes before lowpressure switch be­comes part of control circuit. (See Fig. 6.)
2
Page 3
NOTE: See Winter Start Control Kit for detailed Installation Instruction.
SERVICE FITTING CAP
VALVE CORE END
FLARE NUT
ON PRESSURE
ADAPTER TEE
EXTENDER TUBE
FLARE NUT
SWITCH
CONNECTOR
CONTACTOR
PRESSURE
SWITCH
BLUE
YELLOW
OR
VIOLET
BLACK
FAN
MOTOR
LIQUID REFRIGERANT SERVICE VALVE SERVICE FITTING
A00025
Fig. 1Low Ambient Pressure Switch
CONTROL
BOARD
ODF
BLUE
PRESSURE SWITCH
CONNECTOR
YELLOW
OR
VIOLET
BLACK
FAN
MOTOR
A13042
Fig. 3Power Wiring for All Voltages of Cooling Applica-
tions Single and TwoStage Communicating Capable
13
DEFROST
BOARD
OUTDOOR
FAN RELAY
O
C
ISOLATION
RELAY
Wire provided in Isolation Relay Kit
2
1
VIOLET
BLACK
BLUE
YELLOW
OR VIOLET
PRESSURE
SWITCH
CONNECTOR
Fig. 2Power Wiring for All Voltages of Cooling Applica-
A97326
tions Single and TwoStage NonCommunicating Capable
ODF OR OF2
DEFROST BOARD OR CONTROL BOARD
O
C
BLACK (Wire provided in Isolation Relay Kit)
ISOLATION
RELAY
Wires provided in Isolation Relay Kit
2
1
VIOLET
BLACK
BLUE
YELLOW OR VIOLET
FAN MOTOR
PRESSURE
SWITCH
CONNECTOR
A12593
Fig. 4Power Wiring for 208/230v Heat Pump
Applications
T
TDR
C
LPS
FAN MOTOR
Wires provided in Isolation Relay Kit
A12594
Fig. 5Power Wiring for 460v Heat Pump Applications
LPS
LOW-PRESSURE SWITCH
C
CONTACTOR COIL
TDR
TIME DELAY RELAY
T
RELAY COIL
FACTORY WIRING FIELD WIRING
Fig. 6Low Voltage Wiring for Winter Start Control
3
A93165
Page 4
STARTUP
To start units equipped with the lowambient pressure switch, perform the following steps:
1. Turn power on to unit.
2. Set thermostat below room temperature.
3. Wait for the unit to start. There may be a 5minute delay in the thermostat or in the outdoor unit.
4. Observe unit operation as described below.
a. The fan will be off when compressor starts.
b. At outdoor temperatures around 0_F (−17.8_C), fan
may not run at all.
c. At summer temperatures, fan will start after 10 to 30
seconds of compressor operation and may not turn off until thermostat is satisfied.
d. At outdoor ambient between 80_F (26.7_C) and 20_F
(6.7_C), fan will turn on and off to maintain pressure as shown in Table 1.
Table 1—Kit Usage and CutIn / CutOut Pressures
KIT PART NO. REFRIGERANT
KSALA0201R22 R-22 225 100 Blue and Yellow
KSALA0301410 R-410A 365 200 Blue and Violet
PRESSURE SWITCH CLOSES
(PSIG)
PRESSURE SWITCH OPENS
(PSIG)
WIRE COLORS
4
Page 5
A06450
UNIT SIZE AA UNIT HEIGHT A B C-1 C-2 C-3 D
Mini Base 23-1/8
Small 25-3/4
Medium 31-1/4
Large 35
25-5/16 20-3/8 10-1/16
28-11/16 23-13/16 11-3/4
32-1/8 27-3/16 13-1/2 35-1/2 30-5/8 15-3/16
38-15/16 34 16-7/8
42-5/16 37-3/8 18-9/16
45-11/16 40-13/16 20-1/4
25 20-3/8 10-1/16
28-7/16 23-13/16 11-3/4
31-13/16 27-3/16 13-1/2
35-1/4 30-5/8 15-3/16 38-5/8 34 16-7/8
42 37-3/8 18-9/16
45-7/16 40-13/16 20-1/4
25-1/2 20-3/8 10-1/16
28-15/16 23-13/16 11-3/4
32-5/16 27-3/16 13-1/2
35-3/4 30-5/8 15-3/16 39-1/8 34 16-7/8 42-1/2 37-3/8 18-9/16
45-15/16 40-13/16 20-1/4
25-1/2 20-3/8 10-1/16
28-15/16 23-13/16 11-3/4
32-5/16 27-3/16 13-1/2
35-3/4 30-5/8 15-3/16 39-1/8 34 16-7/8 42-1/2 37-3/8 18-9/16
45-15/16 40-13/16 20-1/4
Vertical Units (in.)
1-5/16 8-1/4 3-1/2 39-1/4
3-15/16 10-7/8 6-1/8 41-7/8
9-3/8 16-5/16 11-9/16 47-3/8
13-3/16 20-1/8 15-3/8 51-1/8
Fig. 7Vertical Discharge Products Baffle Assembly
5
Page 6
Copyright 2015 CAC / BDP S 7310 W. Morris St. S Indianapolis, IN 46231
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Edition Date: 01/15
6
Catalog No: IIK−KSALA0301−02
Replaces: IIKKSALA30101
Loading...