This installation instruction contains basic unit installation
information, including installation of thermostats and remote
temperature sensors.
For additional information and service instructions, refer to
the Controls and Troubleshooting literature.
A factory-installed optional integral economizer and high-
capacity power exhaust is available on size 075-100 units.
A factory-installed optional return fan is available on size
075-100 units.
The staged gas control (SGC) option adds the capability to
control the rooftop unit’s gas heating system to a specified
supply-air temperature set point for purposes of tempering a
cool mixed-air condition.
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All
other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe
precautions in the literature, tags and labels attached to the unit,
and other safety precautions that may apply.
Follow all safety codes, including ANSI (American National Standards Institute) Z223.1. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguisher available for all brazing operations.
WARNING
Before performing service or maintenance operations on
unit, turn off main power switch to unit. Electrical shock
could cause personal injury.
FOR YOUR SAFETY
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance. Do not touch any electrical switch; do not use any phone in your building. Immediately call your gas supplier from a neighbor’s phone.
Follow the gas supplier’s instructions. If you cannot reach
your gas supplier, call the fire department.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors and
liquids in the vicinity of this or any other appliance.
WARNING
Improper installation, adjustment, alteration, service, or
maintenance can cause injury or property damage. Refer to
this manual. For assistance or additional information, consult a qualified installer, service agency, or the gas supplier.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53480079-01Printed in U.S.A.Form 48P-4SIPg 111-10Replaces: 48P-3SI
CAUTION
Disconnect gas piping from units when leak testing at pressures greater than 0.5 psig. Pressures greater than 0.5 psig
will cause gas valve damage resulting in a hazardous
condition. If gas valve is subjected to pressure greater than
0.5 psig, it must be replaced. When pressure testing fieldsupplied gas piping at pressures of 0.5 psig or less, the unit
connected to such piping must be isolated by manually
closing the gas valve.
INSTALLATION
Step 1 — Perform Jobsite Survey —
the following checks before installation.
1. Consult local building codes and the NEC (National
Electrical Code) (ANSI/NFPA [American National Standards Institute/National Fire Protection Association] 70)
for special installation requirements.
2. Determine unit location (from project plans) or select unit
location.
3. Check for possible overhead obstructions which may interfere with unit lifting or rigging.
Complete
CAUTION
Do not lift unit with forklift truck. Move unit with overhead rigging only.
Step 2 — Place Unit — Inspect unit for transportation
damage. File claim with transportation agency.
Provide clearance around and above unit for airflow, safety,
and service access. Do not restrict top (area above condenser
fans) in any way. Allow at least 6 ft on all sides for rated performance, code compliance, and service. On units equipped with
power exhaust option, high velocity air is exhausted out the
hood. Unit should be positioned with at least 10 ft clearance between the exhaust hood and any obstruction.
Check unit dimensional drawings for unit arrangement and
minimum performance and service clearances.
Do not install unit in an indoor location. Do not locate air inlets near exhaust vents or other sources of contaminated air.
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
Level by using unit frame as a reference. Physical data is
shown in Tables 1A-9.
Step 3 — Roof Mount Unit — Check building codes
for weight distribution requirements. Unit weight is shown in
Tables 1A-1C and 5. Unit may be mounted on class A, B, or C
roofing material.
ROOF CURB — Assemble and install roof curb as described
in instructions shipped with the accessory. Accessory roof curb
and information required to field fabricate a roof curb is shown
in Fig. 1-5. Install insulation, cant strips, roofing and counter
flashing as required. For unit condensate drain to function
properly, curb must be level or within tolerances shown in
Fig. 1-5.
STEEL BEAMS — If roof curb is not used, support unit with
steel beams along its entire length and then support steel as required. As a minimum, unit must be supported across its width
at each lifting lug location.
Step 4 — Slab Mount Unit — Provide a level con-
crete slab that extends beyond unit cabinet at least 6 inches.
Make a slab 8 in. thick with 4 in. above grade. Use gravel
apron in front of condenser coil air inlet to prevent grass and
foliage from obstructing airflow. Ensure that slab is of
sufficient height to allow for condensate trap of 4 in. on sizes
030-070 or 7 in. on sizes 075-100.
Step 5 — Install Curb Gasketing
SIZE 030-060 UNITS — After ductwork has been connected
to the roof curb, attach adhesive-backed gasketing on all end
rails, cross rails, and duct rails. Be sure all joints and corners of
gasket are square and flush to prevent possible water leaks.
Follow all applicable building codes.
SIZE 070-100 UNITS — After ductwork has been connected
to the roof curb, apply gasket material (
wide neoprene) where indicated.
Single-Thickness Gasketing (See Fig. 6-8 for Item Numbers) — Apply gasketing in the following places:
1. Along both side rails (1) — 2 places, full length
2. Along return air end rail (2) — 1 place
3. Around return air internal duct flange (3) — 1 or 2 places
4. Around supply air internal duct flanges (4) — 3 places
Double-Thickness Gasketing (See Fig. 6 and 8 and Detail
A-A) — Locate a line 93/4-in. from the supply air end of the
accessory curb. Apply a double-thickness of gasket material
along line per detail A-A.
NOTE: Do not apply gasket material along the outside edge of
the curb (area “X”). This pan area of the curb extends out
beneath the end of the unit’s air handler section; applying gasket here develops a potential water trap area on top of the curb.
Condenser Section Roof Curb (See Fig. 7)
thickness gasket along both side rails (5).
1
/2-in. thick x 11/2-in.
— Apply single-
Step 6 — Install Field-Fabricated Ductwork
WARNING
For vertical supply and return units, tools or parts could
drop into ductwork and cause an injury. Install a 90-degree
elbow in the supply and return ductwork between the unit
and the conditioned space. If a 90-degree elbow cannot be
installed, then a grille of sufficient strength and density
should be installed to prevent objects from falling into the
conditioned space. Failure to follow these instructions
could result in personal injury or property damage due to
falling objects.
The 48P2,P3 units are designed for vertical supply/return
only. Field-fabricated ductwork must be attached to the roof
curb, or to the support steel, prior to the final rigging and installation of the unit. Supply and return duct dimensions are shown
in Fig. 1-3.
To attach ductwork to roof curb, insert duct approximately 10
to 11 in. up into roof curb. Connect ductwork to 14-gage roof
curb material with sheet metal screws driven from inside the duct.
Secure all ducts to the building structure, using flexible duct
connectors between roof curbs and ducts as required. Ducts
passing through an unconditioned space must be insulated and
covered with a vapor barrier. Outlet grilles must not lie directly
below unit discharge.
Design supply duct strong enough to handle expected static
pressures.
Step 7 — Rig Unit — Do not drop unit; keep upright.
Use spreader bars over unit to prevent sling or cable damage.
Sheets of plywood placed along the condenser coils will provide additional protection. All lifting lugs MUST be used when
lifting unit. Level by using unit frame as a reference. See Fig. 9
and 10 for information. Unit and accessory weights are shown
in Tables 1A-1C and 5. Weight distribution and center of gravity can be found in Fig. 11.
Low Heat5310581054105910
High Heat5440594055406040
With Economizer
Low Heat5610611057106210
High Heat5740624058406340
COMPRESSORSScroll
Quantity...Type1...ZP154/1...ZP1541...ZP182/1...ZP182
Oil Charge (oz) per Compressor110110
Number of Refrigerant Circuits22
REFRIGERANTR-410A
Operating Charge (lb), Ckt 1/Ckt 2
Standard Evaporator Coil15.4/14.818.4/17.6
Standard Evaporator with Humidi-MiZer®15.4/24.918.4/27.7
Alternate High-Capacity Evaporator Coil18.4/17.7N/A
Alternate High-Capacity Evaporator with Humidi-MiZer18.4/27.8N/A
CONDENSER COILSAluminum Novation® Heat Exchanger with Microchannel Coils
Quantity11
Total Face Area (sq ft)33.333.3
EVAPORATOR COILS
Quantity1
Total Face Area (sq ft)32.1
Refrigerant Feed Device...No. per CircuitTXV...1
Standard Evaporator Coils
Rows...Fins/in.3...15.04...15.0
Fin TypeDouble WavyDouble Wavy
Tube TypeCross HatchedCross Hatched
Alternate, High-Capacity Evaporator Coils
Rows...Fins/in.4...15.0N/A
Fin TypeDouble WavyN/A
Tube TypeCross HatchedN/A
HEATING SECTIONLow HeatHigh HeatLow HeatHigh Heat
Number of Heat Exchangers714714
Input (MBtuh)325650325650
Output (MBtuh) (Vertical/Horizontal)263/260527/520263/260527/520
Temperature Rise Range (F)10-4025-5510-4025-55
Efficiency (%) (Vertical/Horizontal)81/8081/8081/8081/80
Burner Orifice Diameter
Manifold Pressure (in. wg)3.53.53.53.5
Line Pressure (in. wg) (min...max)5.0...13.05.0...13.05.0...13.05.0...13.0
Firing Stages2222
Number of Gas Valves1212
CONDENSER FANSPropeller Type
Quantity...Diameter (in.)2...302...30
Nominal Cfm18,00019,500
Motor Hp...Rpm1.0...11401.0...1140
SUPPLY FANCentrifugal 25 x 25 in.
Nominal Cfm
Maximum Allowable Cfm15,00015,000
Maximum Allowable Rpm900900
Shaft Diameter at Pulley (in.)111/
SUPPLY-FAN MOTOR AND DRIVE(Any motor available on any unit)
Motor Hp7.510152025
Motor Frame Size213T215T254T256T284T
Efficiency at Full Load (%)
High Efficiency88.589.591.091.091.7
Premium Efficiency91.7 91.793.0 93.6 93.6
Fan Pulley Pitch Diameter (in.)13.713.713.713.713.7
Motor Pulley Pitch Diameter (in.)3.44.34.95.56.5
Resulting Fan Speed (rpm)438549626703830
Belts Quantity...Type2...BX602...5VX630 2...5VX6302...5VX6302...5VX650
Center Distance Range (in.)17.74-14.3017.74-14.3017.63...14.0117.63...14.0116.63...12.87
OPTIONAL POWER EXHAUST†Centrifugal, 18 x 15 in. (Any motor available on any unit)
Quantity...Motor Hp2...3.02...5.02...7.52...10
Motor Frame SizeHigh Eff56HZ184T213T215T
Efficiency at Full Load (%) High/Premium81.0/88.587.5/89.588.5/91.789.5/91.7
Fan Pulley Pitch Diameter (in.)High Eff1110.41212
Motor Pulley Pitch Diameter Range (in.)High Eff4.1-3.14.7-3.76.0-4.87.0-5.8
Motor Pulley Pitch Diameter Factory Setup (in.)4.14.25.46.4
Blower Shaft Diameter at Pulley (in.)1
Fan Rpm Range500-656621-785717-882854-1000
Factory Setup Fan Rpm656703800927
Maximum Allowable Rpm1000100010001000
FILTERS
Standard Efficiency Throwaway (Standard)
Quantity...Size (in.)8...20 x 25 x 2, 8...20 x 20 x 28...20 x 25 x 2, 8...20 x 20 x 2
Medium Efficiency (30%) Pleated (Optional)
Quantity...Size (in.)8...20 x 25 x 2, 8...20 x 20 x 28...20 x 25 x 2, 8...20 x 20 x 2
High Efficiency (90%) Bag Filters
with High Velocity Prefilters (Opt)
Quantity...Size (in.)
Bag Filter6...20 x 24 x 22, 6...20 x 20 x 226...20 x 24 x 22, 6...20 x 20 x 22
Prefilter12...16 x 20 x 2, 3...20 x 24 x 212...16 x 20 x 2, 3...20 x 24 x 2
MERV 15 Cartridge Filters with High Velocity Prefilters (Opt)
Quantity...Size (in.)
Cartridge Filter6...20 x 24 x 12, 6...20 x 20 x 126...20 x 24 x 12, 6...20 x 20 x 12
Prefilter12...16 x 20 x 2, 3...20 x 24 x 212...16 x 20 x 2, 3...20 x 24 x 2
Low Heat5810631060256525
High Heat5940644061556655
With Economizer
Low Heat6110661063256825
High Heat6240674064556955
COMPRESSORSScroll
Quantity...Type2...ZP103/1...ZP1822...ZP120/2...ZP137
Oil Charge (oz) per Compressor110110
Number of Refrigerant Circuits22
REFRIGERANTR-410A
Operating Charge (lb), Ckt 1/Ckt 2
Standard Evaporator Coil21.6/26.729.4/29.0
Standard Evaporator with Humidi-MiZer®21.6/39.129.4/41.4
Alternate High-Capacity Evaporator Coil35.1/37.238.2/36.5
Alternate High-Capacity Evaporator with Humidi-MiZer31.1/49.638.2/48.9
CONDENSER COILSAluminum Novation® Heat Exchanger with Microchannel Coils
Quantity22
Total Face Area (sq ft)66.766.7
EVAPORATOR COILS
Quantity1
Total Face Area (sq ft)45.5
Refrigerant Feed Device...No. per CircuitTXV...2
Standard Evaporator Coils
Rows...Fins/in.3...15.04...15.0
Fin TypeDouble WavyDouble Wavy
Tube TypeCross HatchedCross Hatched
Alternate, High-Capacity Evaporator Coils
Rows...Fins/in.6...16.06...16.0
Fin TypeDouble WavyDouble Wavy
Tube TypeCross HatchedCross Hatched
HEATING SECTIONLow HeatHigh HeatLow HeatHigh Heat
Number of Heat Exchangers714714
Input (MBtuh)325650325650
Output (MBtuh) (Vertical/Horizontal)263/260527/520263/260527/520
Temperature Rise Range (F)10-4025-5510-4025-55
Efficiency (%) (Vertical/Horizontal)81/8081/8081/8081/80
Burner Orifice Diameter
Manifold Pressure (in. wg)3.53.53.53.5
Line Pressure (in. wg) (min...max)5.0...13.05.0...13.05.0...13.05.0...13.0
Firing Stages2222
Number of Gas Valves1212
CONDENSER FANSPropeller Type
Quantity...Diameter (in.)3...304...30
Nominal Cfm30,00038,000
Motor Hp...Rpm1.0...11401.0...1140
SUPPLY FANCentrifugal 25 x 25 in.
Nominal Cfm14,00014,000
Maximum Allowable Cfm20,00020,000
Maximum Allowable Rpm900900
Shaft Diameter at Pulley (in.)111/
SUPPLY-FAN MOTOR AND DRIVE(Any motor available on any unit)
Motor Hp7.51015202530*
Motor Frame Size213T215T254T256T284T 286T
Efficiency at Full Load (%)
High Efficiency 88.589.591.091.091.792.4
Premium Efficiency91.7 91.7 93.0 93.6 93.693.6
Fan Pulley Pitch Diameter (in.)13.713.713.713.713.712.5
Motor Pulley Pitch Diameter (in.)3.44.34.95.56.56.5
Resulting Fan Speed (rpm)438 549 626 703 830 910
Belts Quantity...Type2...BX602...5VX630 2...5VX6302...5VX6302...5VX6503...5VX630
Center Distance Range (in.)17.74-14.3017.74-14.3017.63...14.0117.63...14.0116.63...12.8716.63...12.87
OPTIONAL POWER EXHAUST†Centrifugal, 18 x 15 in. (Any motor available on any unit)
Quantity...Motor Hp2...3.02...5.02...7.52...10
Motor Frame SizeHigh Eff56HZ184T213T215T
Efficiency at Full Load (%) High/Premium81.0/88.587.5/89.588.5/91.789.5/91.7
Fan Pulley Pitch Diameter (in.)High Eff1110.41212
Motor Pulley Pitch Diameter Range (in.)High Eff4.1-3.14.7-3.76.0-4.87.0-5.8
Motor Pulley Pitch Diameter Factory Setup (in.)4.14.25.46.4
Blower Shaft Diameter at Pulley (in.)17/
Fan Rpm Range500-656621-785717-882854-1000
Factory Setup Fan Rpm656703800927
Maximum Allowable Rpm1000100010001000
FILTERS
Standard Efficiency Throwaway (Standard)
Quantity...Size (in.)8...20 x 25 x 2, 8...20 x 20 x 28...20 x 25 x 2, 8...20 x 20 x 2
Medium Efficiency (30%) Pleated (Optional)
Quantity...Size (in.)8...20 x 25 x 2, 8...20 x 20 x 28...20 x 25 x 2, 8...20 x 20 x 2
High Efficiency (90%) Bag Filters
with High Velocity Prefilters (Opt)
Quantity...Size (in.)
Bag Filter6...20 x 24 x 22, 6...20 x 20 x 226...20 x 24 x 22, 6...20 x 20 x 22
Prefilter12...16 x 20 x 2, 3...20 x 24 x 212...16 x 20 x 2, 3...20 x 24 x 2
MERV 15 Cartridge Filters with High Velocity Prefilters (Opt)
Quantity...Size (in.)
Cartridge Filter6...20 x 24 x 12, 6...20 x 20 x 126...20 x 24 x 12, 6...20 x 20 x 12
Prefilter12...16 x 20 x 2, 3...20 x 24 x 212...16 x 20 x 2, 3...20 x 24 x 2
Low Heat7810836078658 41582058755
High Heat794084907995854583358885
With Economizer
Low Heat8340889083958 94587359285
High Heat847090208525907588659415
COMPRESSORSScroll
Quantity...Type2...ZP137/2...ZP1372...ZP154/2...ZP1541...ZP54,1...ZP182/1...ZP54,1...ZP182
Oil Charge (oz) per Compressor110110110
Number of Refrigerant Circuits22 2
REFRIGERANTR-410A
Operating Charge (lb), Ckt 1/Ckt 2
Standard Evaporator Coil37.6/37.942.2/41.843.5/44.8
Standard Evaporator with Humidi-MiZer®37.6/50.342.2/54.243.5/57.2
Alternate High-Capacity Evaporator Coil46.5/45.847.6/46.555.4/55.5
Alternate High-Capacity Evaporator with
Humidi-MiZer
CONDENSER COILSAluminum Novation® Heat Exchanger with Microchannel Coils
Quantity22 4
Total Face Area (sq ft)66.766.7106.7
EVAPORATOR COILS
Quantity2
Total Face Area (sq ft)61.5
Refrigerant Feed Device...No. per CircuitTXV...2
Standard Evaporator Coils
Number of Heat Exchangers142114211421
Input (MBtuh)650975650975650975
Output (MBtuh) (Vertical/Horizontal)527/520790/780527/520790/780527/520790/780
Temperature Rise Range (F)10-4020-5010-4020-5010-4020-50
Efficiency (%) (Vertical/Horizontal)81/8081/8081/8081/8081/8081/80
Burner Orifice Diameter
Manifold Pressure (in. wg)3.53.53.53.53.53.5
Line Pressure (in. wg) (min...max)5.0...13.05.0...13.05.0...13.05.0...13.05.0...13.05.0...13.0
Firing Stages22222 2
Number of Gas Valves23232 3
CONDENSER FANSPropeller Type
Quantity...Diameter (in.)4...304...304...30
Nominal Cfm36,00036,60039,000
Motor Hp...Rpm1.0...11401.0...11401.0...1140
SUPPLY FANCentrifugal 30 x 27.5 in.
Nominal Cfm17,50021,00024,500
Maximum Allowable Cfm25,00030,00030,000
Maximum Allowable Rpm800800800
Shaft Diameter at Pulley (in.)111/
SUPPLY-FAN MOTOR AND DRIVE(Any motor available on any unit)
Motor Hp1520253040†
Motor Frame Size254T256T284T286TS324T
Efficiency at Full Load (%)
High Efficiency91.091.091.792.493.0
Premium Efficiency93.093.693.693.694.5
Fan Pulley Pitch Diameter (in.)13.713.713.715.516.1
Motor Pulley Pitch Diameter (in.)4.55.15.55.96.7
Resulting Fan Speed (rpm)575651703711740
Belts Quantity...Type2...5VX12302...5VX12302...5VX12302...5VX12303...5VX1250
Center Distance Range (in.)48.25-44.0048.25-44.0048.50-44.2548.50-44.2548.25-44.00
OPTIONAL POWER EXHAUST*Centrifugal, 18 x 15 in. (Any motor available on any unit)
Quantity...Motor Hp2...52...7.52...10
Motor Frame Size184T213T215T
Efficiency at Full Load (%) High/Premium87.5/89.588.5/91.789.5/91.7
Resulting Fan Rpm 740820920
Maximum Allowable Rpm100010001000
FILTERS
Standard Efficiency Throwaway (Standard)
Quantity...Size (in.)12...20 x 25 x 2, 12...20 x 20 x 212...20 x 25 x 2, 12...20 x 20 x 212...20 x 25 x 2, 12...20 x 20 x 2
Medium Efficiency (30%) Pleated (Optional)
Quantity...Size (in.)12...20 x 25 x 2, 12...20 x 20 x 212...20 x 25 x 2, 12...20 x 20 x 212...20 x 25 x 2, 12...20 x 20 x 2
High Efficiency (90%) Bag Filters
with High Velocity Prefilters (Optional)
Quantity...Size (in.)
Bag Filter6...24 x 24 x 22, 6...24 x 20 x 226...24 x 24 x 22, 6...24 x 20 x 226...24 x 24 x 22, 6...24 x 20 x 22
Prefilter6...24 x 24 x 2, 6...20 x 24 x 26...24 x 24 x 2, 6...20 x 24 x 26...24 x 24 x 2, 6...20 x 24 x 2
MERV 15 Cartridge Filters with
High Velocity Prefilters (Optional)
Quantity...Size (in.)
Cartridge Filter6...24 x 24 x 12,, 6...24 x 20 x 126...24 x 24 x 12,, 6...24 x 20 x 126...24 x 24 x 12, 6...24 x 20 x 12
Prefilter6...24 x 24 x 2, 6...20 x 24 x 26...24 x 24 x 2, 6...20 x 24 x 26...24 x 24 x 2, 6...20 x 24 x 2
OUTSIDE AIR SCREENS
Standard Hood (25%) Quantity...Size (in.)4...25 x 16 x 1, 2...20 x 16 x 14...25 x 16 x 1, 2...20 x 16 x 14...25 x 16 x 1, 2...20 x 16 x 1
OPTIONAL ECONOMIZER FILTERAluminum Frame, Permanent
Quantity...Size (in.)12...16 x 25 x 1, 2...16 x 20 x 112...16 x 25 x 1, 2...16 x 20 x 112...16 x 25 x 1, 2...16 x 20 x 1
LEGEND*See Table 7 — Power Exhaust Fan Drive Data on page 9 for more information.
MBtuh — Btuh in Thousands
TXV— Thermostatic Expansion Valve
46.5/58.247.6/58.955.4/67.9
16
111/
16
111/
16
5
Table 1C — Physical Data 48P2,P3,P4,P5075-100
BASE UNIT48P2,P3,P4,P507548P2,P3,P4,P509048P2,P3,P4,P5100
NOMINAL CAPACITY (tons)7590100
OPERATING WEIGHT (lb)Standard
Base Unit
Low Heat90659615966510,215968510,235
High Heat91959745979510,345981510,365
With Economizer
Low Heat959510,14510,19510,74510,21510,765
High Heat972510,27510,32510,87510,34510,895
COMPRESSORSScroll
Quantity...Type2...ZP82/2...ZP1823...ZP154,3...ZP1543...ZP154,3...ZP182
Oil Charge (oz) per Compressor110110110
Number of Refrigerant Circuits222
REFRIGERANTR-410A
Operating Charge (lb), Ckt 1/Ckt 2
Standard Evaporator Coil43.8/45.050.4/51.350.8/52.8
Standard Evaporator with Humidi-MiZer®43.8/57.450.4/69.150.8/70.6
Alternate High-Capacity Evaporator Coil55.1/54.961.5/62.959.3/62.8
Alternate High-Capacity Evaporator with
Humidi-MiZer
CONDENSER COILSAluminum Novation® Heat Exchanger with Microchannel Coils
Quantity466
Total Face Area (sq ft)106.7160.0160.0
EVAPORATOR COILS
Quantity2
Total Face Area (sq ft)61.5
Refrigerant Feed Device...No. per CircuitTXV...2
Standard Evaporator Coils
Rows...Fins/in.4...154...154...15
Fin TypeDouble WavyDouble WavyDouble Wavy
Tub e Ty p eCross HatchedCross HatchedCross Hatched
Alternate, High-Capacity Evaporator Coils
Rows...Fins/in.6...166...166...16
Fin TypeDouble WavyDouble WavyDouble Wavy
Tub e Ty p eCross HatchedCross HatchedCross Hatched
Number of Heat Exchangers232323
Input (MBtuh)650975650975650975
Output (MBtuh) (Vertical/Horizontal)527/520790/780527/520790/780527/520790/780
Temperature Rise Range (F)10-4020-5010-4020-5010-4020-50
Efficiency (%) (Vertical/Horizontal)81/8081/8081/8081/8081/8081/80
Burner Orifice Diameter
Manifold Pressure (in. wg)3.53.53.53.53.53.5
Line Pressure (in. wg) (Min...Max)5.0...13.05.0...13.05.0...13.05.0...13.05.0...13.05.0...13.0
Number of Gas Valves232323
CONDENSER FANPropeller Type
Quantity...Diameter (in.)4...306...306...30
Nominal Cfm39,00058,00058,000
Motor Hp (ea)...rpm1.0...11401.0...11401.0...1140
STANDARD SUPPLY FANForward Curved Centrifugal 36 x 30 in.
Nominal Cfm24,50029,75035,000
Maximum Allowable Cfm30,00034,00040,000
Maximum Allowable Rpm680680680
Shaft Diameter at Pulley (in.)1
STANDARD SUPPLY-FAN MOTOR AND DRIVE(Any motor available on any unit)
Motor Hp30405060
Motor Frame SizeS268TS324TS36TS364T
Efficiency at Full Load (%)
High Efficiency92.493.093.093.6
Premium Efficiency93.694.594.595.4
Fan Pulley Pitch Diameter (in.)18.518.518.518.5
Motor Pulley Pitch Diameter (in.)5.35.76.57.1
Resulting Fan Rpm501539615672
Belts Quantity...Type3...5VX13204...5VX13204...5VX13204...5VX1320
Center Distance Range (in.)47.88-45.0147.64-44.7647.42-44.5247.42-44.52
ALTERNATE, AIRFOIL FANAirfoil
Nominal Airflow (cfm)24,50029,75035,000
Maximum Allowable Airflow (cfm)30,00034,00040,000
Maximum Allowable Wheel Speed (rpm)184618461846
Shaft Diameter at Pulley (in.)2
ALTERNATE SUPPLY-FAN MOTOR AND DRIVE(Any motor available on any unit)
Motor Hp3040506075
Motor Frame SizeS268TS324TS36TS364T365T
Efficiency at Full Load (%)
High Efficiency92.493.093.093.694.1
Premium Efficiency93.694.594.595.495.4
Fan Pulley Pitch Diameter (in.)9.710.28.98.910.8
Motor Pulley Pitch Diameter (in.)7.58.78.18.711.1
Resulting Fan Rpm13531493159317111799
Belts Quantity...Type2...5VX11502...5VX11803...5VX11503...5VX11503...5VX1230
Center Distance Range (in.)42.96...45.8242.96...45.5742.96...45.5742.45...45.3542.45...45.35
Chassis
LEGEND*See Table 3 — High-Capacity Power Exhaust Data for more information. See
MBtuh — Btuh in Thousands
TXV— Thermostatic Expansion Valve
Extended
Chassis
Standard
Chassis
Extended
Chassis
Standard
Chassis
55.1/67.361.5/80.759.3/80.6
11
/
16
11
/
16
111/
211/
16
16
111/
211/
16
16
Table 7 — Power Exhaust Fan Drive Data on page 9 for more information.
Extended
Chassis
6
Table 1C — Physical Data 48P2,P3,P4,P5075-100 (cont)
BASE UNIT48P2,P3,P4,P507548P2,P3,P4,P509048P2,P3,P4,P5100
OPTIONAL POWER EXHAUST*Centrifugal, 18 x 15 in. (Any motor available on any unit.)
Quantity...Motor Hp2...52...7.52...10
Motor Frame Size184T213T215T
Efficiency at Full Load (%)
High Efficiency87.588.589.5
Premium Efficiency89.591.791.7
Fan Pulley Pitch Diameter (in.)10.610.610.6
Motor Pulley Pitch Diameter (in.)4.55.05.6
Shaft Diameter at Pulley (in.)1
Resulting Fan Rpm740820920
Maximum Allowable Rpm100010001000
FILTERS
Standard Efficiency Throwaway
(Standard)
Quantity...Size (in.)12...20 x 25 x 2, 12...20 x 20 x 212...20 x 25 x 2, 12...20 x 20 x 212...20 x 25 x 2, 12...20 x 20 x 2
30% and 65% Pleated (Optional)
Quantity...Size (in.)12...20 x 25 x 2, 12...20 x 20 x 212...20 x 25 x 2, 12...20 x 20 x 212...20 x 25 x 2, 12...20 x 20 x 2
OUTSIDE AIR SCREENS
Standard Hood (25%) Quantity...Size (in.)4...25 x 16 x 1, 2...20 x 16 x 14...25 x 16 x 1, 2...20 x 16 x 14...25 x 16 x 1, 2...20 x 16 x 1
Quantity...Size (in.)12...16 x 25 x 1, 2...16 x 20 x 112...16 x 25 x 1, 2...16 x 20 x 112...16 x 25 x 1, 2...16 x 20 x 1
LEGEND*See Table 3 — High-Capacity Power Exhaust Data for more information. See
MBtuh — Btuh in Thousands
TXV— Thermostatic Expansion Valve
7
/
16
17/
16
17/
16
Table 7 — Power Exhaust Fan Drive Data on page 9 for more information.
Table 2 — Optional Return Fan Physical Data (48P075-100 Only)
BASE UNIT48P2,P3,P4,P5075-100
RETURN FANPlenum Fan, 47.13 in. (Any motor available on any unit.)
Quantity...Motor Hp1...201...251...30 1...40
Motor Frame Size256T284T286T 324T
Efficiency at Full Load (%) High/Premium91.0/93.691.7/93.692.4/93.6 93.0/93.8
Fan Pulley Pitch Diameter (in.)8.59.88.5 8.5
Motor Pulley Pitch Diameter (in.)5.36.76.1 6.7
Shaft Diameter at Pulley (in.)2
Resulting Fan Rpm110412091271 1396
Maximum Allowable Rpm144714471447 1447
15
/
16
215/
16
215/
16
215/
16
Table 3 — Optional High-Capacity Power Exhaust Physical Data (48P075-100 Only)
BASE UNIT48P2,P3,P4,P5075-100
POWER EXHAUSTCentrifugal, 22 x 20 in., 1
Tot a l Hp2030405060
Quantity...Motor Hp2...102...152...202...252...30
Motor Frame SizeS215TD254TS256TS284TS286T
Efficiency at Full Load (%)
High Efficiency89.5919191.792.4
Premium Efficiency91.793 93.693.693.6
Fan Sheave Pitch Diameter (in.)12.412.411.111.111.1
Motor Sheave Pitch Diameter (in.)4.85.85.9 6.56.9
Resulting Fan Rpm71484192810201094
Maximum Allowable Rpm11751175117511751175
Belts — Quantity...Type2...BX932...BX932...5VX9502...5VX9502...5VX950
Table 4 — Optional Humidi-MiZer
UNIT SIZE 48/50P030-075090,100
Humidi-MiZer Coil ConstructionAluminum Novation
Quantity11
Face Area (sq ft)26.733.3
11
/16 in. shaft diameter (Any motor available on any unit)
®
Coil Data
®
Coil
7
Table 5 — Operating Weights of Options and Accessories (lb)
Standard Length455495605605605605605605
Extended Length54554512001200————
With High-Capacity Power Exhaust—— ———700700700
High-Efficiency Filters2020202020202020
Bag Filters and Cartridge Filters3535404040———
Hail Guard120150145145210210210210
Inlet Guide Vanes9595115115115115115115
Variable Frequency Drive
7.5 hp
10 hp
15 hp
20 hp
25 hp
30 hp
40 hp
50 hp
60 hp
75 hp
High-Capacity Evaporator Coil
Airfoil Fan — ————350350350
Humidi-MiZer® Adaptive Dehumidification System 72 72 72 72 72 72 92 92
030,035040,050055060070075090100
20
20
35
35
53
—
—
—
—
—
150 300300300300300300300
20
20
35
35
53
—
—
—
—
—
—
—
35
35
53
53
53
—
—
—
48/50P UNIT SIZE
—
—
35
35
53
53
53
—
—
—
—
—
35
35
53
53
53
—
—
—
—
—
—
—
—
53
53
53
53
152
—
—
—
—
—
53
53
53
53
152
—
—
—
—
—
53
53
53
53
152
*Includes hood.
Table 6 — Supply Fan Drive Data
HP
SHAFT
DIA (in.)
Sizes 030-050
7.51
101
151
201
251
30*1
3
/
8
3
/
8
5
/
8
5
/
8
7
/
8
7
/
8
Sizes 055-070
151
201
251
301
402
5
/
8
5
/
8
7
/
8
7
/
8
1
/
8
Sizes 075-100 (Forward-Curved Fan)
301
402
502
602
7
/
8
1
/
8
1
/
8
3
/
8
Sizes 075-100 (Airfoil Fan)
301
402
502
602
752
7
/
8
1
/
8
1
/
8
3
/
8
3
/
8
*Sizes 040,050 only.NOTE: Part numbers are Browning Manufacturing Corp. reference.
NOTE: Part numbers are Browning Manufacturing Corp. reference.
Table 8 — Optional High-Capacity Power Exhaust Fan Drive Data
TOTALHPMOTOR
QTY...HP
MOTOR
SHAFT
DIA. (in.)
SPEED
RPM
202...101.3757142B5V484.82B5V12412.42...BX9332.8 to 36.7
302...151.6258412B5V585.82B5V12412.42...BX9332.6 to 36.5
402...201.6259282B5V585.92B5V11011.12...5VX95032.6 to 36.5
502...251.87510202B5V646.52B5V11011.12...5VX95032.5 to 36.3
602...301.87510942B5V686.92B5V11011.12...5VX95032.5 to 36.3
MOTOR SHEAVEBLOWER SHEAVE
Part
Number
Pitch Diameter
(in.)
Part
Number
Pitch Diameter
(in.)
QTY...BELT
CENTER DISTANCE
RANGE (in.)
CENTER
DISTANCE
RANGE (in.)
Table 9 — Optional Return Fan Drive Data
TOTALHPMOTOR
QTY...HP
MOTOR
SHAFT
DIA. (in.)
SPEED
RPM
201...201.62511043B5V525.33R5V858.53...5VX100038.1 to 41.0
251...251.87512093B5V666.73R5V979.83...5VX106038.9 to 41.8
301...301.87512713B5V606.13R5V858.53...5VX103038.9 to 41.8
401...402.12513963B5V666.73R5V858.53...5VX106039.9 to 42.8
Fig. 8 — Gasket Location on Roof Curb (48P075-100 Units with Optional High-Capacity Power Exhaust)
are a total of five drain connections required on each unit: one
primary drain (on right-hand side of the unit) and four secondary drains (two on each side of unit).
PRIMARY DRAIN — The primary drain is a 2-in. FPT pipe
connection located on the right-hand side of the unit looking at
the unit from the return air end. See Fig. 12-21. Fig. 22 shows
the additional length of units with an extended chassis.
With field-supplied fittings and pipe sections, plumb the primary condensate drain to the 2-in. FPT connector on the base
rail. Use a trap height of at least 4-in. for size 030-070 units
and 7-in. for size 075-100 units. See Fig. 23 and 24. Install with
a height dimension of at least 2-in. from the top of the exit pipe
from the trap section to the bottom of the connector. Apply a
bead of RTV or similar sealant around the pipe joint at the connector in the base rail.
SECONDARY DRAINS (Units Installed on
Curb) — There are two secondary drain connections on each
side of the unit. See Fig. 25. There are secondary drains on
each side of the unit in the filter section and on each side of the
unit in the supply fan section. There are labels marking each location on the unit base rail. See Fig. 12-21.
Locate the four 1
mounting screws (shipped in a bag taped to the basepan in the
supply fan section, located behind the access panel marked
FAN SECTION). The drain couplings are a 10-gage plate with
1
a 1
/4 in. half coupling welded to the plate.
At each secondary drain hole location, there is a 1
hole pre-drilled in the bottom of the base rail, surrounded by
1
/4-in. drain coupling assemblies and
3
/8-in.
four 0.20-in. engagement holes. Install a drain coupling assembly using screws provided at each secondary drain hole location. See Fig. 26. Do not attach any drain coupling assemblies
in the condenser section base rail.
Using field-supplied fittings and pipe sections, assemble Utraps at each secondary drain fitting. See Fig. 27. Provide a
minimum size of ½-in. pipe for secondary drains. Use a trap at
least 4-in. deep for size 030-070 units and 7-in. deep for size
075-100 units. Apply a bead of RTV or similar sealant around
the drain assemblies.
Consult local plumbing codes for direction on joining multiple drain lines. Total size of any combined line does not need
to exceed nominal 2-in. size of primary drain connection.
Fill the U-traps at the secondary drain locations prior to unit
start-up. Also check the U-traps before each cooling season to
ensure the traps are filled and functioning properly.
SECONDARY DRAINS (Units Installed on Steel Beam or
Slab) — There are two secondary drain connections required
on each side of the unit. There are secondary drains on the bottom of the base rail on each side of the unit in the filter section
and on each side of the unit in the supply fan section. There are
labels marking each location on the unit base rail. See Fig. 12-
21. Drain holes will need to be drilled in these locations at the
side of the base rail. The existing secondary drain holes in the
bottom of the base rail must be sealed. Prior to final positioning
of the unit, apply a bead of RTV or similar sealant around each
secondary drain hole in the bottom of the unit base rail. See
Fig. 27. Install the metal seal plates then position the unit into
final location.
16
48ZZ501077 2.0
NOTE: Rig with four cables and spread with two 95 inch (2413 MM) spreader bars.
1. Weights do not include economizer or
power exhaust.
Fig. 9 — Rigging Label — Units without Optional Return Fan or High-Capacity Power Exhaust
a48-8455
17
48ZZ501078 2.0
NOTE: Rig with four cables and spread with two 95 inch (2413 MM) spreader bars.
ALL PANELS MUST BE IN PLACE WHEN RIGGING.
CAUTION - NOTICE TO RIGGERS:
MMNIMMNIMMNISGKSBL543,2,1
50P 2,3,4,5-,B,C50 P2, P3, P4, P5
075 119215407220.1559040.21021255.76495
Vert Supply/Return w/ RE Fan
090 125215679228.4580041.51054255.76495
Horz Supply Vert Return w/ RE Fan
100 125415689227.8578641.51054255.76495
48P 2,3,4,5B,D,H48 P2, P3, P4, P5 Low Gas Heat
075 123215589224.6570640.21021255.76495
Vert Supply/Return w/ RE Fan
090 129215861232.6590841.51054255.76495
Horz Supply Vert Return w/ RE Fan
100 129415870230.4585341.51054255.76495
48P 2,3,4,5C,E,J48 P2, P3, P4, P5 High Gas Heat
075 124515648226.9576440.21021255.76495
Vert Supply/Return w/ RE Fan
090 130515920233.7593641.51054255.76495
Horz Supply Vert Return w/ RE Fan
100 130715929232.9591541.51054255.76495
50P 2,3,4,5 R,T,V,W50 P2, P3, P4, P5
075 12471 5657231.7588540.21021 280.87132
Vert Sup/Ret, Horz Sup/ Vert Ret
090 13071 5929240.1609841.51054 280.87132
w/ RE Fan, w/ Ext Chassis
100 13091 5938239.2607541.51054 280.87132
48P 2,3,4,5P,R,W48 P2, P3, P4, P5 Low Gas Heat
075 12871 5838236.2600040.21021 280.87132
Vert Sup/Ret, Horz Sup/ Vert Ret
090 13471 6110244.3620541.51054 280.87132
w/ RE Fan, w/ Ext Chassis
100 13491 6119241.8614241.51054 280.87132
48P 2,3,4,5Q,S,X48 P2, P3, P4, P5 High Gas Heat
075 13001 5897238.5605840.21021 280.87132
Vert Sup/Ret, Horz Sup/ Vert Ret
090 13601 6169245.4623441.51054 280.87132
w/ RE Fan, w/ Ext Chassis
100 13621 6178244.2620341.51054 280.87132
48P 2,3,4,5B,D,H48 P2, P3, P4, P5 Low Gas Heat
075 13499 6123290.1736740.21021 312.17927
Vert Sup/Ret, Horz Sup/Ret
090 14097 6394297.7756141.51054 312.17927
w/ Hi Cap PE
100 14119 6404297.1754641.51054 312.17927
48P 2,3,4,5C,E,J48 P2, P3, P4, P5 High Gas Heat
075 13629 6182291.3740040.21021 312.17927
Vert Sup/Ret, Horz Sup/Ret
090 14227 6453298.9759341.51054 312.17927
w/ Hi Cap PE
100 14249 6463298.2757541.51054 312.17927
50P 2,3,4,5-,B,C50 P2, P3, P4, P5
075 13099 5942287.1729340.21021 312.17927
Vert Sup/Ret, Horz Sup/Ret
090 13697 6213295.1749641.51054 312.17927
w/ Hi Cap PE
100 13719 6223294.4747841.51054 312.17927
48P 2,3,4,5 R,T,V,W48 P2, P3, P4, P5 Low Gas Heat
075 14049 6373483.5 1228040.21021337.38567
Vert Sup/Ret, Horz Sup/Ret
090 14647 6644484.3 1230241.51054337.38567
w/ Hi Cap PE w/ Ext Chassis
100 14669 6654493.8 1254241.51054337.38567
48P 2,3,4,5P,R,W48 P2, P3, P4, P5 High Gas Heat
075 14179 6432483.5 1228040.21021337.38567
Vert Sup/Ret, Horz Sup/Ret
090 14777 6703484.3 1230141.51054337.38567
w/ Hi Cap PE w/ Ext Chassis
100 14799 6713493.8 1254241.51054337.38567
50P 2,3,4,5Q,S,X50 P2, P3, P4, P5
075 13649 6191483.5 1228140.21021337.38567
Vert Sup/Ret, Horz Sup/Ret
090 14247 6462484.4 1230441.51054337.38567
w/ Hi Cap PE w/ Ext Chassis
100 14269 6472493.8 1254341.51054337.38567
MODEL POSITION
UNITS
SIZE
C
CENTER OF GRAVITY
LIFTING LUGS
WEIGHTAB
Fig. 10 — Rigging Label — Units with Optional Return Fan or High-Capacity Power Exhaust
a48-8456
18
3
2
A
B
4
1
NOTE: The weight distribution and center of gravity information include the impact of an economizer, the largest indoor fan motor, and a VFD (variable frequency
drive). On units with a return fan or high-capacity power exhaust, the largest motors and VFD are also included. These weights do not include the impact of other
factory-installed options such as barometric relief, power exhaust, high-capacity indoor coil, hot water coil, or indoor fan.
48P2,P3,P4,P5 UNITSSIZE
CORNER WEIGHTS (lb)
TOTAL
(lb)
AB
1234in. in.
Vertical Supply/Return
Horizontal Supply/Return
Low Heat
No Extended Chassis
0302002100910082000 6,019170
5
/
8
45 7/
8
0352056103110292053 6,169170 7/
8
45 7/
8
0401983137413721981 6,710198 1/
4
45 7/
8
0502079138613842076 6,925201 1/
4
45 7/
8
0552408220522022404 9,220228 7/
8
45 7/
8
0602417222322202414 9,275228 1/
2
45 7/
8
0702950245019132303 9,615244 5/
8
40 1/
4
075338526042033264310,665253 1/
8
40 1/
4
090325529112407269111,26526141 1/
2
100
324829292422268611,28526041
1
/
2
Vertical Supply/Return
Horizontal Supply/Return
High Heat
No Extended Chassis
0302034104210412032 6,149169
3
/
4
45 7/
8
0352088106410622085 6,29917045 7/
8
0402013141014082010 6,840197 3/
8
45 7/
8
0502108142214202105 7,055200 3/
8
45 7/
8
0552443223622332439 9,35022945 7/
8
0602452225422502449 9,405228 1/
2
45 7/
8
0702991248119372335 9,745244 3/
4
40 1/
4
075344426182044268910,795254 3/
8
40 1/
4
090330729312424273411,395262 1/
8
41 1/
2
100
330329462436273111,415261
1
/
4
41 1/
2
Vertical Supply/Return
Horizontal Supply/Return
Low Heat
with Extended Chassis
0302166109610942163 6,519187
1
/
8
45 7/
8
0352223111411122220 6,669187 3/
4
45 7/
8
0402148146014582145 7,210214 3/
4
45 7/
8
0502244147114692241 7,425217 7/
8
45 7/
8
0552558233123282554 9,770242 5/
8
45 7/
8
060
2567234923462563 9,825242
1
/
8
45 7/
8
070311725412023243410,165258 7/
8
40 1/
4
075355127472145277311,215266 3/
4
40 1/
4
090341930482521282711,815274 5/
8
41 1/
2
100
340930702538281911,835273
3
/
8
41 1/
2
Vertical Supply/Return
Horizontal Supply/Return
High Heat
with Extended Chassis
Vertical Supply/Return
Horizontal Supply/Return
High Heat
075423034242673330213,629291
3
/
8
40 1/
4
090405837303084335614,22729941 1/
2
100
405437453097335214,249298
1
/
4
41 1/
2
Vertical Supply/Return
Horizontal Supply/Return
Low Heat with Extended Chassis
0756905 984 768539114,049483
1
/
2
40 1/
4
090648415341268536214,647484 3/
8
41 1/
2
100
662014091165547414,669493
3
/
4
41 1/
2
Vertical Supply/Return
Horizontal Supply/Return
High Heat with Extended Chassis
0756969 993 776544114,179483
1
/
2
40 1/
4
090654115471280540914,777484 1/
4
41 1/
2
100
667914221176552314,799493
3
/
4
41 1/
2
Fig. 11 — Weight Distribution and Center of Gravity
19
1
3
2
A
B
4
1
NOTE: The weight distribution and center of gravity information include the impact of an economizer, the largest indoor fan motor, and a VFD (variable frequency
drive). On units with a return fan or high-capacity power exhaust, the largest motors and VFD are also included. These weights do not include the impact of other
factory-installed options such as barometric relief, power exhaust, high-capacity indoor coil, hot water coil, or indoor fan.
Vertical Supply/Return
Horizontal Supply/Return
High Heat
075354334492693276612,451226
7
/
8
40 1/
4
090337737673115279313,051233 3/
4
41 1/
2
100
337037853130278713,071232
7
/
8
41 1/
2
Vertical Supply/Return
Horizontal Supply/Return
Low Heat with Extended Chassis
075360936182825281812,871236
1
/
4
40 1/
4
090346739063230286713,471244 1/
4
41 1/
2
100
343739483264284213,491241
3
/
4
41 1/
2
Vertical Supply/Return
Horizontal Supply/Return
High Heat with Extended Chassis
075368136202826287413,001238
1
/
2
40 1/
4
090351739283248290813,601245 3/
8
41 1/
2
100
350539513267289813,621244
1
/
4
41 1/
2
Fig. 11 — Weight Distribution and Center of Gravity (cont)
Locate the four 1
/4-in. drain coupling assemblies and
mounting screws (shipped in a bag taped to the basepan in the
supply fan section, located behind the access panel marked
FAN SECTION). The drain couplings are a 10-gage plate with
1
a 1
/4 in. half coupling welded to the plate.
After final positioning of the unit, perform the following
procedure:
1. At each of the four secondary drain locations (marked
with labels on the unit base rail), position the drain coupling assembly in the side of the base rail. Mark the
screw holes and the drain hole locations on the base rail.
2. Drill holes for drain outlet (use 1
the mounting screws (use
3
3
/8-in. hole saw) and for
/16-in. drill bit).
3. Install a drain coupling assembly using screws provided
at each secondary drain hole location.
4. Using field-supplied fittings and pipe sections, assemble
U-traps at each secondary drain fitting. See Fig. 24. Provide minimum size of ½-in. pipe for secondary drains.
Use a trap at least 4-in. deep for size 030-070 units and
7-in. deep for size 075-100 units.
5. Apply a bead of RTV or similar sealant around the drain
assemblies.
Consult local plumbing codes for direction on joining multiple drain lines. Total size of any combined line does not need to
exceed nominal 2-in. size of primary drain connection.
Fill the U-traps at the secondary drain locations prior to unit
start-up. Also check the U-traps before each cooling season to
ensure the traps are filled and functioning properly.
20
Fig. 12 — Base Unit Dimensional Drawing — 48P2,P3030,035 (Standard Chassis Unit Shown)
a48-8613
21
Fig. 13 — Base Unit Dimensional Drawing — 48P4,P5030,035 (Standard Chassis Unit Shown)
a48-8614
22
23
Fig. 14 — Base Unit Dimensional Drawing — 48P2,P3040-050 (Standard Chassis Unit Shown)
a48-8615