Carrier WeatherMaster Installation Instructions

Page 1
WeatherMaster
50GC**04-06
Single Package Rooftop Cooling Only/Electric Heat Unit
®
with Puron
(R-410A) Refrigerant
Installation Instructions
®
CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1
MODEL NUMBER NOMENCLATURE AND
DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Rated Indoor Airflow . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
ep 1 — Plan for Unit Location . . . . . . . . . . . . . . . . 7
St
• ROOF MOUNT
Step 2 — Plan for Sequence of Unit Installation . . . 7
• CURB-MOUNTED INSTALLATION
• PAD-MOUNTED INSTALLATION
• FRAME-MOUNTED INSTALLATION
Step 3 — Inspect Unit . . . . . . . . . . . . . . . . . . . . . . . . . 7
Step 4 — Provide Unit Support . . . . . . . . . . . . . . . . . 7
• ROOF CURB MOUNT
• SLAB MOUNT (HORIZONTAL UNITS ONLY)
• ALTERNATE UNIT SUPPORT (IN LIEU OF CURB OR
SLAB MOUNT)
Step 5 — Field Fabricate Ductwork . . . . . . . . . . . . . . 9
• UNITS WITH ACCESSORY OR OPTIONAL ELECTRIC
HEATERS
Step 6 — Rig and Place Unit . . . . . . . . . . . . . . . . . . . 9
• POSITIONING ON CURB
Step 7 — Convert to Horizontal and Connect
Ductwork (When Required) . . . . . . . . . . . . . . . . . 10
Step 8 — Install Outside Air Hood . . . . . . . . . . . . . . 11
• ECONOMIZER HOOD PACKAGE REMOVAL AND
SETUP (FACTORY OPTION)
• ECONOMIZER HOOD
Step 9 — Units with Hinged Panels Only . . . . . . . . 12
Step 10 — Install External Condensate Trap and
Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
ep 11 — Make Electrical Connections . . . . . . . . . 12
St
• FIELD POWER SUPPLY
• UNITS WITH FACTORY-INSTALLED NON-FUSED
DISCONNECT OR HACR
• UNITS WITHOUT FACTORY-INSTALLED NON-
FUSED DISCONNECT OR HACR
• ALL UNITS
• CONVENIENCE OUTLETS
• HACR AMP RATING
• FACTORY OPTION THRU-BASE CONNECTIONS
• UNITS WITHOUT THRU-BASE CONNECTIONS
(ELECTRICAL CONNECTIONS)
• FIELD CONTROL WIRING
• THERMOSTAT
• HEAT ANTICIPATOR SETTINGS
• ELECTRIC HEATERS
• HUMIDI-MIZER® CONTROL CONNECTIONS
• TYPICAL UNIT WIRING DIAGRAMS
EconoMi$er® X (Factory Option) . . . . . . . . . . . . . . . 24
• SYSTEM COMPONENTS
• SPECIFICATIONS
• INPUTS
• OUTPUTS
• ENVIRONMENTAL
• ECONOMIZER MODULE WIRING DETAILS
• S-BUS SENSOR WIRING
• CO2 SENSOR WIRING
• INTERFACE OVERVIEW
• SETUP AND CONFIGURATION
• TIME-OUT AND SCREENSAVER
• ENTHALPY SETTINGS
• STANDARD OR SINGLE SPEED FAN OPERATION
• 2 SPEED FAN OPERATION
• 2SP H/C AND 3 SPEED FAN OPERATION
• CHECKOUT
• TROUBLESHOOTING
RTU Open Controller (Factory Option) . . . . . . . . . .35
SystemVu™ Controller (Factory Option) . . . . . . . . .35
Controller Options . . . . . . . . . . . . . . . . . . . . . . . . . . .35
• LOW AMBIENT
Smoke Detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
Step 12 — Adjust Factory-Installed Options . . . . . .37
• SMOKE DETECTORS
• ECONOMI$ER® IV OCCUPANCY SWITCH
Step 13 — Install Accessories . . . . . . . . . . . . . . . . .37
St
ep 14 — Fan Speed Set Up . . . . . . . . . . . . . . . . . .38
• UNITS WITH ELECTRO-MECHANICAL CONTROLS
• UNITS WITH SYSTEMVU™ CONTROLS
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . CL-1

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes, including ANSI (American National Standards Institute) Z223.1. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguisher available for all brazing operations.
It is important to recognize safety information. This is the safety­alert symbol . When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety­alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
Catalog No. 04-53500269-01 Printed in U.S.A. Form 50GC-4-6-03SI Rev. A Pg 1 3-21 Replaces: 50GC-4-6-02SI
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Page 2
DANGER
CAUTION
ELECTRICAL SHOCK HAZARD Failure to follow this warning will result in personal injury or
death. Before performing service or maintenance operations on unit,
turn off main power switch to unit and install lock(s) and lock­out tag(s). Ensure electrical service to rooftop unit agrees with voltage and amperage listed on the unit rating plate. Unit may have more than one power switch.
WARNING
UNIT OPERATION AND SAFETY HAZARD Failure to follow this warning could cause personal injury,
death and/or equipment damage. R-410A refrigerant systems operate at higher pressures than
standard R-22 systems. Do not use R-22 service equipment or components on R-410A refrigerant equipment.
WARNING
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could cause personal injury or death.
Relieve pressure and recover all refrigerant before system repair or final unit disposal.
Wear safety glasses and gloves when handling refrigerants. Keep torches and other ignition sources away from refrigerants and oils.
PERSONAL INJURY HAZARD Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and
wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing air conditioning equipment.
MODEL NUMBER NOMENCLATURE AND
DIMENSIONS
See Fig. 1 for 50GC model number nomenclature. See Fig. 2 for unit dimensional drawings and service clearance dimensions.

Rated Indoor Airflow

Table 1 lists the rated indoor airflow used for the AHRI efficiency rating for the units covered in this document.
Table 1 — Rated Indoor Airflow
MODEL NUMBER RATED INDOOR AIRFLOW (CFM)
50GC*N/M/P04 1200 50GC*N/M/P05 1400 50GC*N/M/P06 2000
2
Page 3
50GC–M04A1 A5–0A0A 0
Cooling Tons
04 - 3 ton 05 - 4 ton 06 - 5 ton
1
Example:
Position: 2 3 4 5 6 7 8 9
10
11 12 13 14 15 16 17 18
Heat Options
= No Heat A = Low Electric Heat B = Medium Electric Heat C = High Electric Heat
Sens or Options
A = None B = RA (Return Air) Smoke Detector C = SA (Supply Air) Smoke Detector D = RA + SA Smoke Detector E = CO
2
F = RA Smoke Detector and CO
2
G = SA Smoke Detector and CO
2
H = RA + SA Smoke Detector and CO
2
J = Condensate Overflow Switch K = Condensate Overflow Swtich and RA Smoke Detectors L = Condensate Overflow Switch and RA and SA Smoke Detectors M = Condensate Overflow Swtich and SA Smoke Detectors
Indoor Fan Options
1 = Direct Drive
EcoBlue Standard Static
2 = Direct Drive
EcoBlue Medium Static
3 = Direct Drive
EcoBlue High Static
Coil Options (RTPF) (Outdoor - Indoor - Hail Guard)
A = Al/Cu - Al/Cu B = Precoat Al/Cu - Al/Cu C = E-coat Al/Cu - Al/Cu D = E-coat Al/Cu - E-coat Al/Cu E = Cu/Cu - Al/Cu F = Cu/Cu - Cu/Cu M = Al/Cu - Al/Cu — Louvered Hail Guard N = Precoat Al/Cu - Al/Cu — Louvered Hail Guard P = E-coat Al/Cu - Al/Cu — Louvered Hail Guard Q = E-coat Al/Cu - E-coat Al/Cu — Louvered Hail Guard R = Cu/Cu - Al/Cu — Louvered Hail Guard S = Cu/Cu - Cu/Cu — Louvered Hail Guard
Voltage
1 = 575/3/60 3 = 208-230/1/60 5 = 208-230/3/60 6 = 460/3/60
Design Revision
= Factory Design Revision
Base Unit Controls
0 = Electro-mechanical controls - can be used with field-installed W7212 EconoMi$er
®
IV (Non-Fault Detection and Diagnostic) 2 = RTU Open Multi-Protocol Controller 3 = SystemVu™ Controller 6 = Electro-mechanical - can be used with W7220 EconoMi$er X
(with Fault Detection and Diagnostic)
Intake / Exhaust Options
A = None B = Temperature Economizer w/ Barometric Relief F = Enthalpy Economizer w/ Barometric Relief U = Temperature Ultra Low Leak Economizer w/ Barometric Relief W = Enthalpy Ultra Low Leak Economizer w/ Barometic Relief
Service Options
0 = None 1 = Unpowered Convenience Outlet 2 = Powered Convenience Outlet 3 = Hinged Panels 4 = Hinged Panels and Unpowered Convenience Outlet 5 = Hinged Panels and Powered Convenience Outlet 6 = MERV 8 Filters C = Foil Faced Insulation
Factory Assigned
0 = Standard 1 = LTL
Electrical Options
A = None B = HACR Breaker C = Non-Fused Disconnect (NFD) D = Thru-The-Base Connections (TTB) E = HACR and Thru-The-Base Connections F = Non-Fused Disconnect and TTB N = Phase Monitor Protection P = Phase Monitor and HACR Q = Phase Monitor and NFD R = Phase Monitor and TTB S = Phase Monitor and HACR and TTB T = Phase Monitor and NFD and TTB
Refrig. Systems Options
M = Two Stage Cooling Models N = Two Stage Cooling Models with Humidi-MiZer
®
system (includes Low Ambient control) P = Two Stage Cooling Models with Low Ambient control
Note: On single phase (-3 voltage code) models, the following are not available as factory-installed options:
- Humidi-MiZer
®
System
- Coated Coils or Cu Fin Coils
- Louvered Hail Guards
- Economizer
- Powered 115 Volt Convenience Outlet
Model Series - WeatherMaster
®
GC - 16.1 SEER Efficiency
Unit Heat Type
50 - Electric Heat Packaged Rooftop
Fig. 1 — 50GC 04-06 Model Number Nomenclature (Example)
3
Page 4
4
Fig. 2 — 50GC 04-06 Unit Dimensional Drawing
Page 5
5
Fig. 2 — 50GC 04-06 Unit Dimensional Drawing (cont)
Page 6
6
Fig. 2 — 50GC 04-06 Unit Dimensional Drawing (cont)
Page 7

INSTALLATION

Jobsite Survey

Complete the following checks before installation.
1. Consult local building codes and the NEC (National Elec-
trical Code) ANSI/NFPA 70 for special installation requirements.
2. Determine unit location (from project plans) or select unit location.
3. Check for possible overhead obstructions which may inter­fere with unit lifting or rigging.

Step 1 — Plan for Unit Location

Select a location for the unit and its support system (curb or other) that provides for the minimum clearances required for safety (in­cluding clearance to combustible surfaces), unit performance and service access below, around and above unit as specified in unit drawings. See Fig. 2 on page 5.
NOTE: Consider also the effect of adjacent units. Unit may be installed directly on wood flooring or on Class A, B,
or C roof-covering material when roof curb is used. Do not install unit in an indoor location. Do not locate air inlets
near exhaust vents or other sources of contaminated air. Although unit is weatherproof, avoid locations that permit water
from higher level runoff and overhangs to fall onto unit. Select a unit mounting system that provides adequate height to al-
low installation of condensate trap per requirements. Refer to Step 10 — Install External Condensate Trap and Line on page 12 for required trap dimensions.
ROOF MOUNT Check building codes for weight distribution requirements. Unit
operating weight is shown in Table 2.
Table 2 — Operating Weights
50GC-*
Base Unit 468 (212) 510 (231) 555 (252) Economizer
Vertical 50 (23) 50 (23) 50 (23)
Horizontal 80 (36) 80 (36) 80 (36) Humidi-MiZer Cu Fins 25 (11) 43 (20) 56 (25) Powered Outlet 32 (15) 32 (15) 32 (15) Curb
14-in. (356 mm) 110 (50) 110 (50) 110 (50)
24-in. (610 mm) 145 (66) 145 (66) 145 (66)
®
System 27 (10) 34 (13) 34 (13)
UNIT LB (KG)
04 05 06

Step 2 — Plan for Sequence of Unit Installation

The support method used for this unit will dictate different se­quences for the steps of unit installation. For example, on curb­mounted units, some accessories must be installed on the unit be­fore the unit is placed on the curb. Review the following for rec­ommended sequences for installation steps:

CURB-MOUNTED INSTALLATION

1. Install curb
2. Install field-fabricated ductwork inside curb
3. Install accessory thru-base service connection package
(affects curb and unit) (refer to accessory installation instruc­tions for details)
4. Prepare bottom condensate drain connection to suit planned condensate line routing (refer to Step 10 — Install External Condensate Trap and Line on page 12 for details)
5. Rig and place unit
6. Install outdoor air hood
7. Install condensate line trap and piping
8. Make electrical connections
9. Install other accessories

PAD-MOUNTED INSTALLATION

1. Prepare pad and unit supports
2. Check and tighten the bottom condensate drain connection plug
3. Rig and place unit
4. Convert unit to side duct connection arrangement
5. Install field-fabricated ductwork at unit duct openings
6. Install outdoor air hood
7. Install condensate line trap and piping
8. Make electrical connections
9. Install other accessories
FRAME-MOUNTED INSTALLATION Frame-mounted applications generally follow the sequence for a
curb installation. Adapt the sequence as required to suit specific installation plan.

Step 3 — Inspect Unit

Inspect unit for transportation damage. File any claim with trans­portation agency.
Confirm before installation of unit that voltage, amperage and cir­cuit protection requirements listed on unit data plate agree with power supply provided.
On units with hinged panel option, check to be sure all latches are snug and in closed position.
Locate the carton containing the outside air hood parts. Do not remove carton until unit has been rigged and located in final position.

Step 4 — Provide Unit Support

ROOF CURB MOUNT Accessory roof curb details and dimensions are shown in Fig. 3.
Assemble and install accessory roof curb in accordance with in­structions shipped with the curb.
Curb should be level. This is necessary for unit drain to function properly. Unit leveling tolerances are shown in Fig. 4. Refer to Accessory Roof Curb Installation Instructions for additional infor­mation as required.
Install insulation, cant strips, roofing felt, and counter flashing as shown. Ductwork must be attached to curb and not to the unit. The
accessory thru-the-base power connection package must be in­stalled before the unit is set on the roof curb.
If electric and control wiring is to be routed through the basepan, attach the accessory thru-the-base service connections to the base­pan in accordance with the accessory installation instructions.
NOTE: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket supplied with the roof curb as shown in Fig. 3. Improperly applied gasket can also result in air leaks and poor unit performance.
7
Page 8
ROOF CURB
ACCESSORY #
CRRFCURB001A01
[137.7]
5.42"
A
14"
[356]
24"
[610]
11.96"
[303.8]
NOTES:
1. ROOFCURB ACCESSORY IS SHIPPED DISASSEMBLED.
2. INSULATED PANELS: 25.4 [1"] THK. POLYURETHANE FOAM, 44.5 [1-3/4] # DENSITY.
3. DIMENSIONS IN [ ] ARE IN MILLIMETERS.
4. ROOFCURB: 18 GAGE STEEL.
5. ATTACH DUCTWORK TO CURB. (FLANGES OF DUCT REST ON CURB).
6. SERVICE CLEARANCE 4 FEET ON EACH SIDE.
7. DIRECTION OF AIR FLOW.
8. CONNECTOR PACKAGE CRBTMPWR001A01 IS FOR THRU-THE-CURB GAS TYPE PACKAGE CRBTMPWR003A01 IS FOR THRU-THE-BOTTOM TYPE GAS CONNECTIONS.
CONNECTOR PKG. ACC. GAS CONNECTION TYPE GAS FITTING
CRBTMPWR001A01 3/4" [19] NPT
CRBTMPWR003A01 THRU THE BOTTOM
1-3/4" [44.5]
1.00" [25.4]
THRU THE CURB
1/2" [12.7] NPTCRRFCURB002A01
11 3/4"[298.5] WIDE INSULATED DECK PANELS
POWER WIRING
FITTING
3/4" [19] NPT
CONTROL WIRING
FITTING
1/2" [12.7] NPT 1/2" [12.7] NPT
ACCESSORY CONVENIENCE
OUTLET WIRING CONNECTOR
"A"
21.74"
[552.2]
4.96"
[126.0]
RETURN AIR
40.69"
[1033.5]
OPENING
16.03"
[407.2]
3.00" [76.2]
13.78"
[350.0]
E
15.19"
[385.8]
8
14.00"
[355.6]
1.75"
[44.5]
1/4"
[7.0] 4 9/16" [115.5]
3.00" [76.2]
1/3/4"[44.5]
21.84"
[554.7]
SUPPLY AIR OPENING
20.41"
[518.3]
SUPPLY AIR RETURN AIR
70.87"
[1800.2]
E
32.19"
[817.6]
(SUPPLIED WITH CURB)
OVERALL DIM. 5'-7 3/8" WAS 5'-7 7/8; 18GA MATERIAL WA 16 GA.; NAIL FIELD SUPPLIED WAS
A
WITH CURB
VIEW "B"
CORNER DETAIL
GASKET
DUCT
(FIELD SUPPLIED)
UNIT
NAIL (FIELD SUPPLIED)
TYPICAL (4) SIDES
7/16" [11]
COUNTER FLASHING (FIELD SUPPLIED)
RIGID INSULATION (FIELD SUPPLIED)
ROOFING FELT (FIELD SUPPLIED)
CANT STRIP (FIELD SUPPLIED)
ROOFING MATERIAL (FIELD SUPPLIED)
E-ESECTION
SCALE 0.250
1-3/4" [44.4]
"A"
8 9/16"[217.5] WIDE INSULATED DECK PANEL
GAS SERVICE PLATE THRU THE CURB DRILL HOLE 2" [50.8] @ ASSEMBLY (IF REQUIRED) (SEE NOTE #8)
SUPPLY AIR
3'-1 3/16"
[944.6]
SEE VIEW "B"
DRAWING RELEASE LEVEL:
THIRD ANGLE PROJECTION
ENGINEERING REQUIREMENTS
1067898--MMC04/22/13
SURFACE FINISH MFG/PURCH MODEL (INTERNAL USE ONLY) NEXT DRAWING SCALE DISTRIBUTION
ECN NO.APP'DCHK'DBYDATEREVISION RECORDREV
1' 4-13/16" [427] INSIDE
RETURN AIR
1-3/4" [44.5]
2-3/8" [61]
5' 7-3/8"
[1711.3]
SEE NOTE #2
CERTIFIED DRAWING
PRODUCTION
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES
TOLERANCES ON:
MATERIAL
-
-
-
T-005, Y-002
WEIGHT:
-
- PURCH - N/A MMC
1 DEC 2 DEC 3 DEC ANG
----
AUTHORIZATION NUMBER TITLE
1041738
ENGINEERING MANUFACTURING
-
MMC 06/17/11 - -
-
-
DRAFTER CHECKER
CURB ASY, ROOF
SIZE DRAWING NUMBER REV
-
48TC400427
D
SHEET 5 OF 5
1-3/4" [44.4]
B
Fig. 3 — Roof Curb Details
Page 9
A
B
C
MAXIMUM ALLOWABLE
DIFFERENCE IN. (MM)
A-B B-C A-C
0.5 (13) 1.0 (25) 1.0 (25)
Fig. 4 — Unit Leveling Tolerances
SLAB MOUNT (HORIZONTAL UNITS ONLY) Provide a level concrete slab that extends a minimum of 6-in.
(150 mm) beyond unit cabinet. Install a gravel apron in front of condenser coil air inlet to prevent grass and foliage from obstruct­ing airflow.
NOTE: Horizontal units may be installed on a roof curb if required.

ALTERNATE UNIT SUPPORT (IN LIEU OF CURB OR SLAB MOUNT)

A non-combustible sleeper rail can be used in the unit curb sup­port area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 3 equally spaced 4-in. x 4-in. (102 mm x 102 mm) pads on each side.

Step 5 — Field Fabricate Ductwork

Cabinet return-air static pressure (a negative condition) shall not exceed 0.35 in. wg (87 Pa) with economizer or 0.45 in. wg (112 Pa) without economizer.
For vertical ducted applications, secure all ducts to roof curb and building structure. Do not connect ductwork to unit.
Fabricate supply ductwork so that the cross sectional dimensions are equal to or greater than the unit supply duct opening dimen­sions for the first 18-in. (458 mm) of duct length from the unit basepan.
Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with ap­plicable codes.
Ducts passing through unconditioned spaces must be insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes.
CAUTION
PROPERTY DAMAGE HAZARD Failure to follow this caution may result in damage to roofing
materials. Membrane roofs can be cut by sharp sheet metal edges. Be
careful when placing any sheet metal parts on such roof.

UNITS WITH ACCESSORY OR OPTIONAL ELECTRIC HEATERS

All installations require a minimum clearance to combustible sur­faces of 1-in. (25 mm) from duct for first 12-in. (305 mm) away from unit.
Outlet grilles must not lie directly below unit discharge.
WARNING
PERSONAL INJURY HAZARD Failure to follow this warning could cause personal injury. For vertical supply and return units, tools or parts could drop
into ductwork and cause an injury. Install a 90 degree turn in the return ductwork between the unit and the conditioned space. If a 90 degree elbow cannot be installed, then a grille of sufficient strength and density should be installed to prevent objects from falling into the conditioned space. Due to electric heater, supply duct will require 90 degree elbow.

Step 6 — Rig and Place Unit

Keep unit upright and do not drop. Spreader bars are required. Rollers may be used to move unit across a roof. Rigging materials under unit (cardboard or wood) must be removed PRIOR to plac­ing the unit on the roof curb. Level by using unit frame as a refer­ence. See Table 2 on page 7 and Fig. 5 for additional information.
Lifting holes are provided in base rails as shown in Fig. 5. Refer to rigging instructions on unit.
Rigging materials under the unit (cardboard or wood to prevent base pan damage) must be removed PRIOR to placing the unit on the roof curb.
Before setting the unit onto the curb, recheck gasketing on curb.
.
CAUTION
UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage. All panels must be in place when rigging. Unit is not designed
for handling by fork truck when packaging is removed. If using top crate as spreader bar, once unit is set, carefully
lower wooden crate off building roof top to ground. Ensure that no people or obstructions are below prior to lowering the crate.
POSITIONING ON CURB Position unit on roof curb so that the following clearances are
maintained: the base rail inside the front and rear, 0.0-in. clearance between the roof curb and the base rail inside on the duct end of the unit. This will result in the distance between the roof curb and the base rail inside on the condenser end of the unit being approximately (6.4 mm).
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
After unit is in position, remove rigging skids and shipping materials.
1
/4-in. (6.4 mm) clearance between the roof curb and
1
/4-in.
9
Page 10
.
DETAIL "A"
PLACE ALL SEAL STRIP IN PLACE BEFORE PLACING UNIT ON ROOF CURB.
DUCT END
SEE DETAIL "A"
"A"
(914-1371)
36"- 54"
"C"
"B"
SPREADER
BARS
REQUIRED
REMOVABLE HORIZONTAL SUPPLY DUCT OPENING COVER
REMOVABLE HORIZONTAL RETURN DUCT OPENING COVER
SCREWS
DUCT COVERS SHEET METAL FACE UP
BASEPAN
UNIT
50GC-*04 780 354 74.5 1890 35.5 900 33.5 850 50GC-*05 863 391 74.5 1890 35.5 900 33.5 850 50GC-*06 969 440 74.5 1890 35.0 890 41.5 1055
NOTES:
1. SPREADER BARS REQUIRED — Top damage will occur if spreader bars are not used.
2. Dimensions in ( ) are in millimeters.
3. Hook rigging shackles through holes in base rail, as shown in detail “A.” Holes in base rails are centered around the unit center of gravity. Use wooden top to prevent rigging straps from damaging unit.
MAX WEIGHT
lb kg in. mm in. mm in. mm
Fig. 5 — Rigging Details
Step 7 — Convert to Horizontal and Connect
Ductwork (When Required)
Unit is shipped in the vertical duct configuration. Unit without factory-installed economizer or return-air smoke detector option may be field-converted to horizontal ducted configuration. To convert to horizontal configuration, remove screws from side duct opening covers (see Fig. 6) and remove covers. Use the screws to install the covers on vertical duct openings with the insulation-side down. The panels must be inserted into the notches on the basepan to properly seal. The notches are covered by the tape used to secure the insulation to the basepan and are not easily seen. See Fig. 7 for position of the notches in the basepan. Seals around duct openings must be tight. Secure with screws as shown in Fig. 8. Cover seams with foil duct tape.
Field-supplied flanges should be attached to horizontal duct openings and all ductwork should be secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof or building openings with counter flashing and mastic in accordance with applicable codes.
Do not cover or obscure visibility to the unit’s informative data plate when insulating horizontal ductwork.
DIMENSIONS
A B C
NOTCHES
BASEPAN
Fig. 7 — Location of Notches
NOTCHES
Fig. 6 — Horizontal Conversion Panels
10
Fig. 8 — Horizontal Duct Panels In Place
Page 11

Step 8 — Install Outside Air Hood

HOOD PARTS
PLASTIC TIE WRAP QTY (2)
SCREWS FOR METAL TRAY QTY (2)

ECONOMIZER HOOD PACKAGE REMOVAL AND SETUP (FACTORY OPTION)

NOTE: Economizer is not available as factory-installed options for single phase (-3 voltage code) models.
The hood is shipped in knock-down form and must be field as­sembled. The indoor coil access panel is used as the hood top while the hood sides, divider and filter are packaged together, at­tached to a metal support tray using plastic stretch wrap, and shipped in the return air compartment behind the indoor coil ac­cess panel. The hood assembly’s metal tray is attached to the base­pan and also attached to the damper using two plastic tie-wraps.
1. To gain access to the hood, remove the filter access panel. See Fig. 9.
FILTER ACCESS PANEL
COMPRESSOR ACCESS PANEL
OUTDOOR-AIR OPENING AND INDOOR COIL ACCESS PANEL
Fig. 9 — Typical Access Panel Locations
2. Locate the (2) screws holding the metal tray to the basepan and remove. Locate and cut the (2) plastic tie-wraps securing the assembly to the damper. See Fig. 10. Avoid damaging any wiring or cutting tie-wraps securing any wiring.
1. The indoor coil access panel will be used as the top of the hood. Remove the screws along the sides and bottom of the indoor coil access panel. See Fig. 11.
TOP PAN EL
TOP PAN EL
INDOOR COIL ACCESS PAN EL
INDOOR COIL ACCESS PAN EL
CAULK HERE
Fig. 11 — Indoor Coil Access Panel Relocation
2. Swing out indoor coil access panel and insert the hood sides under the panel (hood top). Use the screws provided to attach the hood sides to the hood top. Use screws provided to attach the hood sides to the unit. See Fig. 12.
TOP PAN EL
INDOOR COIL ACCESS PANEL
Fig. 10 — Economizer Hood Parts Location
3. Carefully lift the hood assembly (with metal tray) through the filter access opening and assemble per the steps outlined in the following section, “Economizer Hood”.
ECONOMIZER HOOD NOTE: If the power exhaust accessory is to be installed on the
unit, the hood shipped with the unit will not be used and must be discarded. Save the aluminum filter for use in the power exhaust hood assembly.
LEFT HOOD SIDE
19 1/16”
B
(483mm)
SCREW
HOOD DIVIDER
33 3/8”
(848mm)
Fig. 12 — Economizer Hood Construction
3. Remove the shipping tape holding the economizer barometric relief damper in place (economizer only).
4. Insert the hood divider between the hood sides. See Fig. 12 and 13. Secure hood divider with 2 screws on each hood side. The hood divider is also used as the bottom filter rack for the aluminum filter.
5. Open the filter clips which are located underneath the hood top. Insert the aluminum filter into the bottom filter rack (hood divider). Push the filter into position past the open filter clips. Close the filter clips to lock the filter into place. See Fig. 13.
6. Caulk the ends of the joint between the unit top panel and the hood top.
7. Replace the filter access panel.
11
Page 12
To use the alternate bottom drain connection, remove the red drain
DIVIDER
BAROMETRIC RELIEF
CLEANABLE ALUMINUM FILTER
FILTER
HOOD
FILTER CLIP
OUTSIDE AIR
DRAIN (FACTORY-INSTALLED)
PLUG
CONDENSATE PAN (SIDE VIEW)
STANDARD SIDE DRAIN
ALTERNATE BOTTOM DRAIN
plug from the bottom connection (use a
1
/2-in. square socket drive
extension) and install it in the side drain connection. The piping for the condensate drain and external trap can be com-
pleted after the unit is in place. See Fig. 16.
MINIMUM PITCH 1˝ (25 mm) PER 1 (3 m) OF LINE
BASE RAIL
OPEN VENT
3˝ (76 mm)
MIN
Fig. 13 — Economizer Filter Installation

Step 9 — Units with Hinged Panels Only

Relocate latch shipped inside the compressor compartment behind the hinged compressor door to location shown in Fig. 14 after unit installation.
If the unit does not have hinged panels, skip this step and continue at Step 10 below.
COMPRESSOR
DOOR
OUTDOOR COIL
LATCH
Fig. 14 — Compressor Door Latch Location
Step 10 — Install External Condensate Trap and
Line
The unit has one 3/4-in. condensate drain connection on the end of the condensate pan and an alternate connection on the bottom. See Fig. 15. Unit airflow configuration does not determine which drain connection to use. Either drain connection can be used with vertical or horizontal applications.
Fig. 15 — Condensate Drain Pan (Side View)
When using the standard side drain connection, ensure that the red plug in the alternate bottom connection is tight. Do this before set­ting the unit in place. The red drain pan plug can be tightened with
1
a
/2-in. square socket drive extension.
TO ROO F DRAIN
DRAIN PLUG
NOTE: Trap should be deep enough to offset maximum unit static difference. A 4-in. (102 mm) trap is recommended.
SEE NOTE
ROOF CURB
Fig. 16 — Condensate Drain Pan Piping Details
All units must have an external trap for condensate drainage. In­stall a trap at least 4-in. (102 mm) deep and protect against freeze-up. If drain line is installed downstream from the external trap, pitch the line away from the unit at 1-in. per 10 ft (25 mm per 3 m) of run. Do not use a pipe size smaller than the unit connection (
3
/4-in.).

Step 11 — Make Electrical Connections

WARNING
ELECTRIC SHOCK HAZARD Failure to follow this warning could result in personal injury or
death. Unit cabinet must have an uninterrupted, unbroken electrical
ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC; ANSI/NFPA 70, latest edition (in Canada, Canadian Electrical Code CSA [Canadian Standards Association] C22.1), and local electrical codes.
NOTE: Field-supplied wiring shall conform with the limitations of minimum 63°F (33°C) rise.
FIELD POWER SUPPLY If equipped with optional powered convenience outlet, the power
source leads to the convenience outlet’s transformer primary are not factory connected. Installer must connect these leads accord­ing to required operation of the convenience outlet. If an always­energized convenience outlet operation is desired, connect the source leads to the line side of the unit-mounted disconnect. (Check with local codes to ensure this method is acceptable in your area.) If a de-energize via unit disconnect switch operation of the convenience outlet is desired, connect the source leads to the load side of the unit disconnect. On a unit without a unit-mounted disconnect, connect the source leads to compressor contactor C and indoor fan contactor IFC pressure lugs with unit field power leads. See Convenience Outlets on page 15 for power transformer connections.
The field power wires are connected to the unit at line-side pres­sure lugs on compressor contactor C and indoor fan contactor IFC (see wiring diagram label for control box component
12
Page 13
arrangement) or at factory-installed option non-fused disconnect
COPPER
WIRE ONLY
ELECTRIC
DISCONNECT
SWITCH
ALUMINUM
WIRE
switch or HACR. Maximum wire size is #2ga AWG (copper only) per pole on contactors, #2ga AWG (copper only) per pole on op­tional disconnect or HACR, and 4/0 AWG (copper only) per pole on terminal or fuse blocks on units with single point box (see Fig. 17). See Fig. 18 and unit label diagram for field power wiring connections.
NOTE: Unit may be equipped with short test leads (pigtails) on the field line connection points on contactor C or optional discon­nect switch. These leads are for factory-run test purposes only; re­move and discard before connecting field power wires to unit con­nection points. Make field power connections directly to line con­nection pressure lugs only.
UNITS WITH FACTORY-INSTALLED NON-FUSED DIS­CONNECT OR HACR
The factory-installed optional non-fused disconnect (NFD) or HACR switch is located in a weatherproof enclosure located un­der the main control box. The manual switch handle and shaft are shipped in the disconnect or HACR enclosure. Assemble the shaft and handle to the switch at this point. Discard the factory test leads (see Fig. 18).
Units Without Single Point Box, Disconnect or HACR Option
Equip
GR Lug
TB TB
11 12
Disconnect
per
NEC
208/230-1-60
Ground
(GR)
11 12 13
Disconnect
per
NEC
L1 L2 L3
208/230-3-60
460-3-60 575-3-60
Units With Disconnect or HACR Option
L1
L2
3 Phase Only 3 Phase Only
L3
2
Optional
Disconnect
4
6
Switch
1
3
5
Factory Wiring
WARNING
FIRE HAZARD Failure to follow this warning could result in personal injury,
death, or property damage. Do not connect aluminum wire between disconnect switch and
unit. Use only copper wire.
Fig. 17 — Disconnect Switch and Unit
Connect field power supply conductors to LINE side terminals when the switch enclosure cover is removed to attach the handle.
Ground
(GR)
Disconnect factory test leads; discard.
Equip GR Lug
Units With Electric Heat Option with Single Point Box
and Without Disconnect or HACR Option
Single Point Box
L1
L2
L3
Ground (GR)
Terminal Block
Equip GR
Lug
— OR —
Single Point Box
L1
L2
L3
Ground (GR)
Fuse/Terminal Block
Fuse
Fuse
Fuse
Equip GR
Lug
Fig. 18 — Power Wiring Connections
Factory Wiring
Factory Wiring
Field-Install the NFD Shaft and Handle
1. Remove the Control Box access panel. The NFD enclosure is located below the Control Box (see Fig. 19).
2. Remove (3) cap head screws that secure the NFD enclosure front cover — (2) on the face of the cover and (1) on the left side cover. See Fig. 20.
3. Remove the front cover of the NFD enclosure.
4. Make sure the NFD shipped from the factory is at OFF posi­tion (the arrow on the black handle knob is at OFF).
5. Insert the shaft with the cross pin on the top of the shaft in the horizontal position. See Fig. 20.
13
Page 14
6. Measure from the tip of the shaft to the top surface of the black pointer; the measurement should be 3.75 to 3.88-in. (95 to 99 mm).
7. Tighten the locking screw to secure the shaft to the NFD.
8. Turn the handle to the OFF position with red arrow pointing at OFF.
9. Install the handle on to the painted cover horizontally with the red arrow pointing to the left.
10. Secure the handle to the painted cover with (2) screws and lock washers supplied.
11. Engaging the shaft into the handle socket, re-install (3) hex screws on the NFD enclosure.
12. Re-install the unit front panel.
6. Tighten the locking screw to secure the shaft to the HACR.
7. Turn the handle to the OFF position with red arrow pointing at OFF.
8. Install the handle on to the painted cover horizontally with the red arrow pointing to the left.
9. Secure the handle to the painted cover with (2) screws and lock washers supplied.
10. Engaging the shaft into the handle socket, re-install (3) hex screws on the HACR enclosure.
11. Re-install the unit front panel.
Fig. 19 — NFD Enclosure Location
Fig. 20 — NFD Handle and Shaft Assembly
Field-Install the HACR Shaft and Handle
1. Remove the Control Box access panel. The HACR enclosure is located below the Control Box (see Fig. 21).
2. Remove (3) cap head screws that secure the HACR enclosure — (2) on the face of the cover and (1) on the left side cover. See Fig. 22.
3. Remove the front cover of the HACR enclosure.
4. Make sure the HACR shipped from the factory is at OFF position (the white arrow pointing at OFF).
5. Insert the shaft all the way with the cross pin on the top of the shaft in the horizontal position. See Fig. 22.
Fig. 21 — HACR Enclosure Location
Fig. 22 — HACR Handle and Shaft Assembly

UNITS WITHOUT FACTORY-INSTALLED NON-FUSED DISCONNECT OR HACR

When installing units, provide a disconnect switch per NEC (Na­tional Electrical Code) of adequate size. Disconnect sizing data is provided on the unit informative plate. Locate on unit cabinet or within sight of the unit per national or local codes. Do not cover unit informative plate if mounting the disconnect on the unit cabinet.
ALL UNITS All field wiring must comply with NEC and all local codes. Size
wire based on MCA (Minimum Circuit Amps) on the unit infor­mative plate. See Fig. 18 and the unit label diagram for power wir­ing connections to the unit power terminal blocks and equipment ground. Maximum wire size is #2ga AWG (copper only) per pole on contactors, #2ga AWG (copper only) per pole on optional dis­connect or HACR, and 4/0 AWG (copper only) per pole on
14
Page 15
terminal or fuse block on units with single point box. See Fig. 18
WEATHERPROOF
COVER
and unit label diagram for field power wiring connections. Provide a ground fault and short circuit over-current protection de-
vice (fuse or breaker) per NEC Article 440 (or local codes). Refer to unit informative data plate for MOCP (Maximum Over-Current Protection) device size.
NOTE: Units ordered with factory installed HACR do not need an additional ground fault and short circuit over-current protective device unless required by local codes.
All field wiring must comply with the NEC and local requirements.
All units except 208/230v units are factory wired for the voltage shown on the nameplate. If the 208/230v unit is to be connected to
a 208v power supply, the control transformer must be rewired by removing the black wire with the from the 230v connection and moving it to the 200v
1
/4-in. female spade connector
1
/4-in. male terminal on the primary side of the transformer. Refer to unit label diagram for additional information. Field power wires will be connected at line-side pressure lugs on the power terminal block or at factory-installed option non-fused disconnect.
NOTE: Check all factory and field electrical connections for tightness.

CONVENIENCE OUTLETS

WARNING
Fig. 24 — Convenience Outlet Utilization
Notice Label
Installing Weatherproof Cover
A weatherproof while-in-use cover for the factory-installed conve­nience outlets is now required by UL standards. This cover cannot be factory-mounted due its depth; it must be installed at unit instal­lation. For shipment, the convenience outlet is covered with a blank cover plate.
On units with electro-mechanical controls the weatherproof cover kit is shipped in the unit’s control box. The kit includes the hinged cover, a backing plate and gasket.
On units with a factory installed direct digital controller (System­Vu™ controls or RTU Open controller) the weatherproof cover kit is secured to the basepan underneath the control box. See Fig. 25.
ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or
death. Units with convenience outlet circuits may use multiple
disconnects. Check convenience outlet for power status before opening unit for service. Locate its disconnect switch, if appropriate, and open it. Lock-out and tag-out this switch, if necessary.
Two types of convenience outlets are offered on 50GC models: non-powered and unit-powered. Both types provide a 125-v GFCI (ground-fault circuit interrupter) duplex receptacle rated at 15A behind a hinged waterproof access cover, located on the end panel of the unit. See Fig. 23.
Figure 23 shows the Convenience Outlet Utilization label which is located below the convenience outlet.
NOTE: Unit powered convenience outlets are not available as fac­tory installed options for single phase (-3 voltage code) models.
CONVENIENCE OUTLET GFCI
PWD-CO TRANSFORMER
PWD-CO FUSE SWITCH
Fig. 23 — Convenience Outlet Location
Fig. 25 — Weatherproof Cover - Shipping Location
on Units with Factory-Installed DDC
WARNING
ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or
death. Using unit-mounted convenience outlets: Units with unit-
mounted convenience outlet circuits will often require that two disconnects be opened to de-energize all power to the unit. Treat all units as electrically energized until the convenience outlet power is also checked and de-energization is confirmed. Observe National Electrical Code Article 210, Branch Circuits, for use of convenience outlets.
1. Remove the blank cover plate at the convenience outlet; dis-
card the blank cover.
2. Loosen the two screws at the GFCI duplex outlet, until approximately Press the gasket over the screw heads.
3. Slip the backing plate over the screw heads at the keyhole slots and align with the gasket; tighten the two screws until snug (do not over-tighten).
1/
-in. (13 mm) under screw heads is exposed.
2
15
Page 16
TOP
TOP
TOP
WET LOC
A
TIONS
WET LO
CATIONS
4. Mount the weatherproof cover to the backing plate as shown in Fig. 26.
5. Remove two slot fillers in the bottom of the cover to permit service tool cords to exit the cover.
6. Check for full closing and latching.
COVER - WHILE-IN-USE
WEATHERPROOF
BASEPLATE FOR
GFCI RECEPTACLE
GFCI RECEPTACLE
NOT INCLUDED
GASKET
Fig. 26 — Weatherproof Cover Installation
Non-Powered Convenience Outlet
This type requires the field installation of a general-purpose 125-v 15A circuit powered from a source elsewhere in the building. Ob­serve national and local codes when selecting wire size, fuse or breaker requirements, and disconnect switch size and location. Route 125-v power supply conductors into the bottom of the utili­ty box containing the duplex receptacle.
Unit-Powered Convenience Outlet
A unit-mounted transformer is factory-installed to step down the main power supply voltage to the unit to 115-v at the duplex re­ceptacle. This option also includes a manual switch with fuse, lo­cated in a utility box and mounted on a bracket behind the conve­nience outlet; access is through the unit’s control box access panel. See Fig. 23.
The primary leads to the convenience outlet transformer are not factory-connected. Selection of primary power source is a custom­er option. If local codes permit, the transformer primary leads can be connected at the line-side terminals on the unit-mounted non­fused disconnect or HACR breaker switch; this will provide ser­vice power to the unit when the unit disconnect switch or HACR switch is open. Other connection methods will result in the conve­nience outlet circuit being de-energized when the unit disconnect or HACR switch is open. See Fig. 27.
Using Unit-Mounted Convenience Outlets
Units with unit-mounted convenience outlet circuits will often re­quire that two disconnects be opened to de-energize all power to the unit. Treat all units as electrically energized until the conve­nience outlet power is also checked and de-energization is con­firmed. Observe National Electrical Code Article 210, Branch Cir­cuits, for use of convenience outlets.
Fuse On Power Type
1
The factory fuse is a Bussman
“Fusetron” T-15, non-renewable
screw-in (Edison base) type plug fuse. Test the GFCI receptacle by pressing the TEST button on the face
of the receptacle to trip and open the receptacle. Check for proper grounding wires and power line phasing if the GFCI receptacle does not trip as required. Press the RESET button to clear the tripped condition.
1. Bussman and Fusetron are trademarks of Cooper Technologies
Company.
UNIT
VOLTAGE
208, 230 240
460 480
575 600
CONNECT ASPRIMARY
CONNECTIONS
L1: RED + YEL L2: BLU + GRA
L1: RED Splice BLU + YEL L2: GRA
L1: RED L2: GRA
TRANSFORMER
TERMINALS
H1 + H3 H2 + H4
H1
H2 + H3
H4 H1
H2
Fig. 27 — Powered Convenience Outlet Wiring
HACR AMP RATING The amp rating of the HACR factory-installed option is based on
the size, voltage, indoor motor and other electrical options of the unit as shipped from the factory. If field-installed accessories are added or changed in the field (for example, power exhaust, ERV), the HACR may no longer be of the proper amp rating and therefore will need to be removed from the unit. See unit name­plate and label on factory-installed HACR for the amp rating of the HACR that was shipped with the unit from the factory (Fig. 28). See unit nameplates for the proper fuse, HACR or maximum over-current protection device required on the unit with field installed accessories.
Fig. 28 — HACR Caution Label
FACTORY OPTION THRU-BASE CONNECTIONS This service connection kit consists of a 1/2-in. electrical bulkhead
connector and a 3/4-in. electrical bulkhead connector, connected to an “L” bracket covering the embossed (raised) section of the unit basepan in the condenser section (see Fig. 29 for shipping position).
16
Page 17
The 3/4-in. bulkhead connector enables the low-voltage control
LOW VOLTAGE CONDUIT CONNECTOR
HIGH VOLTAGE CONDUIT CONNECTOR
AUXILIARY POWER SUPPLY (OPTIONAL)
wires to pass through the basepan. The 1/2-in. bulkhead connector allows the high-voltage power wires to pass through the basepan. See Fig. 30.
Check tightness of connector lock nuts before connecting electri­cal conduits.
Field-supplied and field-installed liquid-tight conduit connectors and conduit may be attached to the connectors on the basepan. Pull correctly rated high voltage and low voltage through appropriate conduits. Connect the power conduit to the internal disconnect (if unit is so equipped) or to the external disconnect (through unit side panel). Remove one of the two knockouts located on the bottom left side of the unit control box. Use this hole for the control conduit.
UNITS WITHOUT THRU-BASE CONNECTIONS (ELEC­TRICAL CONNECTIONS)
1. Install power wiring conduit through side panel openings. Install conduit between disconnect and control box.
2. Install power lines to terminal connections as shown in Fig. 18 on page 13.
Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate. On 3-phase units, volt­ages between phases must be balanced within 2% and the current within 10%. Use the formula shown in the example below to de­termine the percent of voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Carrier warranty.
Example: Supply voltage is 230-3-60
Fig. 29 — Thru-the-Base Fitting Assembly (Shown in
Shipping Position)
Fig. 30 — Thru-Base Connection Fittings
1. Remove the “L” bracket assembly from the unit.
2. Remove connector plate assembly from the “L” bracket and discard the “L” bracket, but retain the washer head screws and the gasket (located between the “L” bracket and the con­nector plate assembly).
NOTE: Take care not to damage the gasket, as it is reused in the following step.
3. Place the gasket over the embossed area in the basepan, align­ing the holes in the gasket to the holes in the basepan. See Fig. 30.
4. Install the connector plate assembly to the basepan using 8 of the washer head screws.
NOTE: If electrical connections are not going to occur at this time, tape or otherwise cover the fittings so that moisture does not get into the building or conduit in the interim.
% Voltage Imbalance
Example: Supply voltage is 230-3-60
ABC
MOTOR
Average Voltage =
Determine maximum deviation from average voltage. (AB) 227-224 = 3 v (BC) 231-227 = 4 v (AC) 227-226 = 1 v Maximum deviation is 4 v. Determine percent of voltage imbalance.
% Voltage Imbalance = 100x
This amount of phase imbalance is satisfactory as it is below the maxi­mum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
= 100 x
AB = 224 v BC = 231 v AC = 226 v
max voltage deviation from average voltage
average voltage
(224 + 231 + 226)
3 3
4
227
= 1.78%
681
=
= 227
FIELD CONTROL WIRING The 50GC unit requires an external temperature control device.
This device can be a thermostat (field-supplied) or a System­Vu™ controller (available as factory-installed option for use on a Carrier Comfort Network
®
or as a stand alone control) or the RTU Open Controller for Building Management Systems using non-CCN protocols (RTU Open is available as a factory­installed option only).
THERMOSTAT Select a Carrier-approved accessory thermostat. When electric
heat is installed in the 50GC unit, the thermostat must be capable of energizing the G terminal (to energize the Indoor Fan Contac­tor) whenever there is a space call for heat (energizing the W1 ter­minal). The accessory thermostats listed on the unit price pages can provide this signal but they are not configured to enable this signal as shipped.
17
Page 18
Install the accessory thermostat according to installation instruc-
C
HUM
G
W2
R
C
W2
G
W1
O/B/Y2
Y2
W1
R
Y1
Y1
T H E R M O
S
T A T
(Note 1)
(Note 2)
(Note 3)
1. Typical multi-function marking. Follow manufacturer’s configuration instructions to select Y2.
2. Y2 to Y2 connection required on single-stage cooling units when integrated economizer function is desired
3. W2 connection not required on units with single-stage heating.
Field Wiring
Unit Control
Board
NOTES:
Typical
Thermostat
Connections
RACEWAY
HOLE IN END PANEL (HIDDEN)
tions included with the accessory. Locate the thermostat accessory on a solid wall in the conditioned
space to sense average temperature in accordance with the ther­mostat installation instructions.
If the thermostat contains a logic circuit requiring 24-v power, use a thermostat cable or equivalent single leads of different colors with minimum of seven leads. If the thermostat does not require a 24-v source (no “C” connection required), use a thermostat cable or equivalent with minimum of six leads. See Fig. 31. Check the thermostat installation instructions for additional features which might require additional conductors in the cable.
For wire runs up to 50 ft (15 m), use no. 18 AWG (American Wire Gage) insulated wire [35°C (95°F) minimum]. For 50 to 75 ft (15 to 23 m), use no. 16 AWG insulated wire [35°C (95°F) minimum]. For over 75 ft (23 m), use no. 14 AWG insulated wire [35°C (95°F) minimum]. Wire sizes larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.
Thermostat Wiring, Units Without Thru-Base Connection Kit
Pass the thermostat control wires through the hole provided in the corner post; then feed the wires through the raceway built into the corner post to the control box. Pull the wires over to the terminal strip on the upper-left corner of the Unit Control Board. See Fig. 32.
NOTE: If thru-the-bottom connections accessory is used, refer to the accessory installation instructions for information on routing power and control wiring.
Fig. 31 — Low-Voltage Thermostat Connections
Fig. 32 — Field Control Wiring Raceway
HEAT ANTICIPATOR SETTINGS Set heat anticipator settings at 0.14 amp for the first stage and
0.14 amp for second-stage heating, when available.
ELECTRIC HEATERS The 50GC units may be equipped with factory or field installed
electric heaters. The heaters are modular in design, with heater frames holding open coil resistance wires strung through ceramic insulators, line-break limit switches and a control contactor. One or two heater modules may be used in a unit.
Heater modules are installed in the compartment below the indoor (supply) fan outlet. Access is through the indoor access panel. See Fig. 33-35.
Not all available heater modules may be used in every unit. Use only those heater modules that are UL listed for use in a specific size unit. Refer to the label on the unit cabinet for the list of ap­proved heaters.
Refer to the Small Roof Top Units Accessory Electric Heater and Single Point Box installation instructions for further details.
18
Page 19
INDOOR
OPTIONAL FACT ORY­INSTALLED DISCONNECT
MAIN CONTROL BOX
CENTER POST
VANE AXIAL INDOOR FAN SYSTEM
SINGLE POINT BOX
HEATER COVER
CONTROL WIRE TERMINAL BLOCK
MANUAL RESET LIMIT SWITCH
HEATER MOUNTING BRACKET
HEATER MODULE
VIO HR1 BRN
UCB
Field Connections
HR1: Heater Circuit 1 HR2: Heater Circuit 2
(if two-circuit module installed)
2
3
C
13
PNK
ORN
ORN PNK BRN
VIO
BRN BRNVIO
2
TB4
VIO HR2 BRN
Elec Htr
TRAN 1
ACCESS
CONTROL BOX ACCESS PANEL
PAN EL
Fig. 33 — Typical Access Panel Location (3-5 Ton)
CONTROL WIRING
FOAM POWER
WIRING
HEATER RELAY
HEATER MOUNTING SCREWS
Fig. 36 — Typical Single Point Installation
Low-Voltage Control Connections
Pull the low-voltage control leads from the heater module — VIO and BRN (two of each if a two-circuit heater module is installed; identify for circuit #1) — to the 4-pole terminal board TB4 located on the heater bulkhead to the left of the Heater module. Connect the VIO lead from Heater circuit #1 to terminal TB4-1. For 2 stage heating, connect the VIO lead from Heater circuit #2 to terminal TB4-2. See Fig. 37.
Fig. 34 — Typical Component Location
Fig. 35 — Typical Module Installation
Single Point Boxes and Supplementary Fuses
When the unit MOCP device value exceeds 60-A, unit-mounted supplementary fuses are required for each heater circuit. These fuses are included in accessory single point boxes, with power dis­tribution and fuse blocks. The single point box will be installed di­rectly under the unit control box, just to the left of the partition separating the indoor section (with electric heaters) from the out­door section. The single point box has a hinged access cover. See Fig. 36. The single point box also includes a set of power taps and pigtails to complete the wiring between the single point box and the unit’s main control box terminals. Refer to the Small Roof Top Units Accessory Electric Heater and Single Point Box installation instructions for details on tap connections on the field-installed electric heat accessory.
All fuses on 50GC units are 60-A. (Note that all heaters are quali­fied for use with a 60-A fuse, regardless of actual heater ampacity, so only 60-A fuses are necessary.)
Fig. 37 — Accessory Electric Heater Control
Connections
HUMIDI-MIZER
®
CONTROL CONNECTIONS
Humidi-MiZer Space RH Controller
NOTE: The Humidi-MiZer system is a factory-installed option. Humidi-MiZer system is not available for single phase (-3 voltage code) models.
The Humidi-MiZer dehumidification system requires a field-sup­plied and field-installed space relative humidity control device. This device may be a separate humidistat control (contact closes on rise in space RH above control setpoint) or a combination ther­mostat-humidistat control device such as Carrier’s Edge
®
Pro
19
Page 20
Thermidistat™ with isolated contact set for dehumidification con-
HUMIDISTAT
UNIT CONTROL
BOARD
THERMOSTAT
C HUM G W2 W1 Y2 Y1 R
trol. See Fig. 38 and Fig. 39. The humidistat is normally used in applications where a temperature control is already provided (units with SystemVu™ control).
% RELATIVE HUMIDITY
Fig. 38 — Accessory Field-Installed Humidistat
Connecting the Carrier Humidistat (HL38MG029)
1. Route the humidistat 2-conductor cable (field-supplied) through the hole provided in the unit corner post.
2. Feed wires through the raceway built into the corner post (see Fig. 32) to the 24v barrier located on the left side of the con­trol box. The raceway provides the UL-required clearance between high-voltage and low-voltage wiring.
3. Connect one of the leads from the 2-conductor cable to the HUM terminal on the UCB (Unit Control Board). Connect the other lead to the R terminal on the UCB. See Fig. 40.
Fig. 39 — Edge
®
®
Pro Thermidistat
Fig. 40 — Humidistat Connections to UCB
Connecting the Thermidistat device (33CS2PPRH-01)
1. Route the Thermidistat multi-conductor thermostat cable (field-supplied) through the hole provided in the unit corner post.
2. Feed wires through the raceway built into the corner post (see Fig. 32 on page 18) to the 24-v barrier located on the left side of the control box. The raceway provides the UL-required clearance between high-voltage and low-voltage wiring.
3. The Thermidistat has dry contacts at terminals D1 and D2 for dehumidification operation (see Fig. 41). Connect D1 to the R terminal on the UCB. Connect D2 to the HUM termi­nal on the UCB. Refer to the installation instructions included with the Carrier Edge Pro Thermidistat device for more information.
TYPICAL UNIT WIRING DIAGRAMS See Fig. 42 and 43 for examples of typical unit control and power
wiring diagrams. These wiring diagrams are mounted on the in­side of the unit control box cover.
20
Page 21
Rc Rh
W1
G
Y2
C
O/W2/B
Y1
OAT
RRS
SRTN
HUM
D1 D2 V+ Vg
C
HUM
G
W2
W1
Y2
Y1
R
PROGRAMMABLE
THERMOSTAT
UNIT CONTROL BOARD
THERMOSTAT CONNECTIONS
Fig. 41 — Typical Rooftop Unit with Humidi-MiZer
and Edge
®
Pro Thermidistat Device
®
Adaptive Dehumidification System
21
Page 22
22
Fig. 42 — Typical 50GC 04-06 Control Wiring Diagram (208-230V W7220 Control Unit Shown)
Page 23
Fig. 43 — Typical 50GC 04-06 Power Wiring Diagram (208/230V Unit Shown)
23
Page 24

EconoMi$er® X (Factory Option)

The EconoMi$er X system is an expandable economizer control system, which includes a W7220 economizer module (controller) with an LCD and keypad (see Fig. 44). The W7220 can be config­ured with optional sensors.
Fig. 44 — W7220 Economizer Module
The W7220 economizer module can be used as a stand-alone economizer module wired directly to a commercial set-back space thermostat and sensors to provide outside air dry-bulb economizer control.
The W7220 economizer module can be connected to optional sensors for single or differential enthalpy control. The W7220 economizer module provides power and communications for the sensors.
The W7220 economizer module automatically detects sensors by polling to determine which sensors are present. If a sensor loses communications after it has been detected, the W7220 economizer controller indicates a device fail error on its LCD.
SYSTEM COMPONENTS The EconoMi$er X system includes an economizer module, 20k
mixed air sensor, damper actuator, and either a 20k outdoor air temperature sensor or S-Bus enthalpy sensors.
Economizer Module
The module is the core of the EconoMi$er X system. The module is mounted in the unit’s control box, and includes the user inter­face for the system. The W7220 economizer module provides the basic inputs and outputs to provide simple economizer control. When used with the optional sensors, the economizer module pro­vides more advanced economizer functionality.
S-Bus Enthalpy Control Sensors
The sensor is a combination temperature and humidity sensor which is powered by and communicates on the S-Bus. Up to three sensors may be configured with the W7220 economizer module.
Sensor (optional)
CO
2
The sensor can be added for Demand Controlled Ventilation (DCV).

SPECIFICATIONS

W7220 Economizer Module
The module is designed for use with 2 to 10 Vdc or bus communi­cating actuator. The module includes terminals for CO Mixed Air sensor, and an Outdoor Dry Bulb sensor. Enthalpy and other options are available with bus sensors.
User Interface
Provides status for normal operation, setup parameters, checkout tests, and alarm and error conditions with a 2-line 16 character LCD display and four button keypad.
sensor,
2
Electrical
Rated Voltage — 20 to 30 Vac RMS, 50/60 Hz
Transformer — 100 va maximum system input
Nominal Power Consumption (at 24 Vac, 60 Hz) —
11.5 VA without sensors or actuators
Relay Digital Output Rating at 30 Vac (maximum power from Class 2 input only) — 1.5A run:
3.5A inrush at 0.45PF (200,000 cycles) or
7.5A inrush at 0.45PF (100,000 cycles)
External Sensors Power Output — 21 Vdc ± 5% at 48 mA
IMPORTANT: All inputs and outputs must be Class 2 wiring.

INPUTS

Sensors
NOTE: A Mixed Air (MA) analog sensor is required on all W7220 units; either an Outdoor Air (OA) sensor for dry bulb change over or an OA bus sensor for outdoor enthalpy change over is required in addition to the MA sensor. An additional Re­turn Air (RA) bus sensor can be added to the system for differen­tial enthalpy or dry bulb changeover. For differential dry bulb changeover a 20k ohm sensor is required in the OA and a bus sen­sor in the RA. DIP switch on RA bus sensor must be set in the RA position.
Dry Bulb Temperature (optional) and Mixed Air (required), 20k NTC
2-wire (18 to 22 AWG); Temperature range –40°F to 150°F (–40°C to 65°C) Temperature accuracy –0°F/+2°F
Temperature and Humidity, C7400S1000 (optional)
S-Bus; 2-wire (18 to 22 AWG) Temperature range: –40°F to 150°F (–40°C to 65°C) Temperature accuracy: –0°F/+2°F Humidity range: 0 to 100% RH with 5% accuracy. NOTE: Up to three (3) S-Bus sensors may be connected to the
W7220 economizer module. For outdoor air (OA), return air (RA) and discharge (supply) air (DA).
4 Binary Inputs
1-wire 24 Vac + common GND (see page 26 for wiring details).
24 Vac power supply
20 to 30 Vac 50/60Hz; 100 VA Class 2 transformer.

OUTPUTS

Actuator Signal
2-10 Vdc; minimum actuator impedance is 2k ohm; bus two-wire output for bus communicating actuators.
Exhaust fan, Y1, Y2 and AUX1 O
All Relay Outputs (at 30 Vac): Running: 1.5A maximum Inrush: 7.5A maximum

ENVIRONMENTAL

Operating Temperature
–40°F to 150°F (–40°C to 65°C). Exception of display operation down to –4°F (–20°C) with full re-
covery at –4°F (–20°C) from exposure to –40°F (–40°C)
Storage Temperature
–40°F to 150°F (–40°C to 65°C)
Shipping Temperature
–40°F to 150°F (–40°C to 65°C)
24
Page 25
Relative Humidity
NA
AUX2-
OCC
E-GND
EXH1
AUX 1- O
Y2-
Y1-
Y2-O
Y1-O
C
R
50048848-002
Rev. A
NA
A2
OCC
EX
A1
Y2I
Y2O
Y1I
Y1O
C
R
MAT
MAT
OAT
OAT
S-BUS
S-BUS
IAQ 2-10
IAQCOM
IAQ 24V
ACT 2-10
ACT COM
ACT 24V
MA MA
OA OA
SB SB
SB SB
SB SB
V C R
V C R
NA
50040839-001
Rev. G
HJW10
www.energy.ca.gov
Certified FDD Product
California Title 24, Part 6
DIP SWITCH LABEL
DIP SWITCHES (3)
S-BUS 2 PIN SIDE CONNECTOR
S-BUS TERMINALS (1 AND 2)
5% to 95% RH non-condensing
ECONOMIZER MODULE WIRING DETAILS Use Fig. 45 and Tables 3 and 4 to locate the wiring terminals for
the Economizer module. NOTE: The four terminal blocks are removable. Slide out each
terminal block, wire it, and then slide it back into place.
Table 4 — Economizer Module - Right Hand Terminal
Blocks
LABEL TYPE DESCRIPTION
Top Right Terminal Blocks
AUX2 I 24 vac IN The first terminal is not used.
Shut Down (SD) or HEAT (W)
OCC 24 vac IN
E-GND E-GND Occupied/Unoccupied Input EXH1 24 vac OUT Exhaust Fan 1 Output
AUX1 O 24 vac OUT
Bottom Right Terminal Blocks
Y2-I 24 vac IN
Y2-O 24 vac OUT
Y1-I 24 vac IN
Y1-O 24 vac OUT
C COM 24 vac Common R 24 vac 24 vac Power (hot)
Conventional only and Heat Pump Changeover (O-B) in Heat Pump mode.
Programmable: Exhaust fan 2 output or ERV or System alarm output
Y2 in - Cooling Stage 2 Input from space thermostat
Y2 out - Cooling Stage 2 Output to stage 2 mechanical cooling
Y1 in - Cooling Stage 2 Input from space thermostat
Y1 out - Cooling Stage 2 Output to stage 2 mechanical cooling
S-BUS SENSOR WIRING The labels on the sensors and controller are color coded for ease of
installation. Orange labeled sensors can only be wired to orange terminals on the controller. Brown labeled sensors can only be wired to S-bus (brown) terminals. Use Fig. 46 and Table 5 to lo­cate the wiring terminals for each S-Bus sensor.
Use Fig. 46 and Table 5 to locate the wiring terminals for each en­thalpy control sensor.
MAT MAT
OAT OAT
S-BUS S-BUS
IAQ 2-10 2-10 vdc Air Quality Sensor Input (e.g. CO IAQ COM COM Air Quality Sensor Common IAQ 24V 24 vac Air Quality Sensor 24 vac Source ACT 2-10 2-10 vdc Damper Actuator Output (2-10 vdc) ACT COM COM Damper Actuator Output Common ACT 24v 24 vac Damper Actuator 24 vac Source
*Sylk is a trademark of Honeywell International Inc.
Fig. 45 — W7220 Wiring Terminals
Table 3 — Economizer Module - Left Hand Terminal
LABEL TYPE DESCRIPTION
20k NTC and COM
20k NTC and COM
S-BUS (Sylk* Bus)
Bottom Left Terminal Block
Blocks
Top Left Terminal Block
Mixed Air Temperature Sensor (Polarity Insensitive Connection)
Outdoor Air Temperature Sensor (Polarity Insensitive Connection)
Enthalpy Control Sensor (Polarity Insensitive Connection)
sensor)
2
Fig. 46 — S-Bus Sensor DIP Switches
25
Page 26
Table 5 — HH57AC081 Sensor Wiring Terminations
CO2 SENSOR
24V
ANALOG
OUT
L1 (HOT)
L2
RED
BLACK
YELLOW
BROWN
ORANGE
GREEN
+
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1
1
TERMINAL
NUMBER LABEL
1 S-BUS S-BUS
2 S-BUS S-BUS
TYPE DESCRIPTION
S-BUS Communications (Enthalpy Control
Sensor Bus)
S-BUS Communications (Enthalpy Control
Sensor Bus)
Use Fig. 46 and Table 6 to set the DIP switches for the desired use of the sensor.
Table 6 — HH57AC081 Sensor DIP Switch
To use the keypad when working with menus:
Press the ▲ (Up arrow) button to move to the previous menu.
Press the ▼ (Down arrow) button to move to the next menu.
Press the (Enter) button to display the first item in the currently displayed menu.
Press the (Menu Up/Exit) button to exit a menu’s item and return to the list of menus.
NOTE: When an S-Bus sensor is connected to an existing net­work, it will take 60 minutes for the network to recognize and auto-configure itself to use the new sensor.
During the 60 minute setup period, no alarms for sensor failures (except SAT) will be issued and no economizing function will be available.
CO When using a CO2 sensor, the black and brown common wires are
internally connected and only one is connected to “IAQ COM” on the W7220. Use the power from the W7220 to power the CO sensor OR make sure the ground for the power supplies are com­mon. See Fig. 47 for CO
INTERFACE OVERVIEW This section describes how to use the EconoMi$er
for:
User Interface
The user interface consists of a 2-line LCD display and a 4-button keypad on the front of the economizer controller.
Keypad
Use the four navigation buttons (see Fig. 48) to scroll through the menus and menu items, select menu items, and to change parame­ter and configuration settings.
USE
DA OFF ON OFF RA ON OFF OFF OA OFF OFF OFF
DIP SWITCH POSITIONS FOR SWITCHES 1, 2, AND 3
1 2 3
SENSOR WIRING
2
sensor wiring.
2
Fig. 47 — CO
Sensor Wiring
2
®
user interface
Keypad and menu navigation
Settings and parameter changes
Menu structure and selection
Fig. 48 — W7220 Controller Navigation Buttons
To use the keypad when working with Setpoints, System and Ad­vanced Settings, Checkout tests and Alarms:
1. Navigate to the desired menu.
2
2. Press the (Enter) button to display the first item in the currently displayed menu.
3. Use the ▲ and ▼ buttons to scroll to the desired parameter.
4. Press the (Enter) button to display the value of the cur­rently displayed item.
5. Press the ▲ button to increase (change) the displayed param­eter value.
6. Press the ▼ button to decrease (change) the displayed param­eter value.
NOTE: When values are displayed, pressing and holding the ▲or ▼ button causes the display to automatically increment or decrement.
1. Press the (Enter) button to accept the displayed value and store it in nonvolatile RAM. “CHANGE STORED” displays.
2. Press the (Enter) button to return to the current menu parameter.
3. Press the (Menu Up/Exit) button to return to the previous menu.
Menu Structure
Table 7 illustrates the complete hierarchy of menus and parame­ters for the EconoMi$er
®
X system.
The Menus in display order are:
STATUS
SETPOINTS
SYSTEM SETUP
ADVANCED SETUP
CHECKOUT
ALARMS
26
Page 27
IMPORTANT: Table 7 illustrates the complete hierarchy. Your menu parameters may be different depending on your configuration.
For example, if you do not have a DCV (CO
) sensor, then none
2
of the DCV parameters appear and only MIN POS will display. If you have a CO
sensor, the DCV MIN and DCV MAX will
2
appear.
NOTE: Some parameters in the menus use the letters MA or MAT, indicating a mixed air temperature sensor location before the cooling coil. This unit application has the control sensor locat­ed after the cooling coil, in the fan section, where it is designated as (Cooling) Supply Air Temperature or SAT sensor.
SETUP AND CONFIGURATION Before being placed into service, the W7220 Economizer module
must be set up and configured for the installed system.
IMPORTANT: During setup, the economizer module is live at all times.
The setup process uses a hierarchical menu structure that is easy to use. Press the ▲ and ▼ arrow buttons to move forward and back­ward through the menus and press the button to select and confirm setup item changes.
TIME-OUT AND SCREENSAVER When no buttons have been pressed for 10 minutes, the LCD dis-
plays a screen saver, which cycles through the Status items. Each Status items displays in turn and cycles to the next item after 5 seconds.
27
Page 28
Table 7 — W7220 Menu Structure*
MENU PARAMETER
ECONO AVAIL NO YES/NO
ECONOMIZING NO YES/NO
OCCUPIED NO YES/NO
HEAT PUMP N/A**
COOL Y1—IN OFF ON/OFF
COOL Y1—OUT OFF ON/OFF
COOL Y2—IN OFF ON/OFF
COOL Y2—OUT OFF ON/OFF
MA TEMP _ _ . _ F
DA TEMP _ _ . _ F
STATUS
OA TEMP _ _ . _ F
OA HUM _ _ % 0 to 100%
RA TEMP _ _ . _ F
RA HUM _ _ % 0 to 100%
IN CO2 _ _ _ ppm 0 to 2000 ppm
DCV STATUS N/A ON/OFF
DAMPER OUT 2.0v 2.0 to 10.0v Displays voltage output to the damper actuator. ACT POS N/A 0 to 100% Displays actual position of outdoor air damper actuator
ACT COUNT N/A 1 to 65535
ACTUATOR N/A
EXH1 OUT OFF ON/OFF
EXH2 OUT OFF ON/OFF
ERV OFF ON/OFF
PARAMETER
DEFAULT
VALUE
PARAMETER
RANGE AND
INCREMENT
COOL HEAT
0°F to 140°F (–17°C to 60°C)
0°F to 140°F (–17°C to 60°C)
–40°F to 140°F (–40°C to 60°C)
0°F to 140°F (–17°C to 60°C)
OK/Alarm (on Alarm menu)
NOTES
FIRST STAGE COOLING DEMAND (Y1–IN) YES = economizing available; the system can use outside air for free cooling when required
FIRST STAGE COOLING RELAY OUTPUT YES = outside air being used for 1 stage cooling
OCCUPIED YES = OCC signal received from space thermostat or unitary controller YES = 24 Vac on terminal OCC NO = 0 Vac on terminal OCC
HEAT PUMP MODE Displays COOL or HEAT when system is set to heat pump (Non-conventional)
FIRST STAGE COOLING DEMAND (Y1-IN) Y1–I signal from space thermostat or unitary controller for cooling stage 1. ON = 24 Vac on terminal Y1–I OFF = 0 Vac on terminal Y1–I
FIRST STAGE COOLING RELAY OUTPUT Cool stage 1 Relay Output to stage 1 mechanical cooling (Y1–OUT terminal)
SECOND STAGE COOLING DEMAND (Y2–IN) Y2–I signal from space thermostat our unitary controller for second stage cooling. ON = 24 Vac on terminal Y2–I OFF = 0 Vac on terminal Y2–I
SECOND STAGE COOLING RELAY OUTPUT Cool Stage 2 Relay Output to mechanical cooling (Y2–OUT terminal)
SUPPLY AIR TEMPERATURE, Cooling Mode Displays value of measured mixed air from MAT sensor. Displays _ _ . _ F if not connected, short or out-of-range.
DISCHARGE AIR TEMPERATURE, after Heating section Displays when Discharge Air sensor is connected and displays measured discharge temperature. Displays _ _ . _F if sensor sends invalid value, if not connected, short or out-of-range.
OUTSIDE AIR TEMP Displays measured value of outdoor air temperature. Displays _ _ . _F if sensor sends invalid value, short or out-of­range.
OUTSIDE AIR RELATIVE HUMIDITY Displays measured value of outdoor humidity from OA sensor. Displays _ _% if not connected short, or out-of-range.
RETURN AIR TEMPERATURE Displays measured value of return air temperature from RAT sensor. Displays _ _ . _ F if sensor sends invalid value, if not connected, short or out-of-range
RETURN AIR RELATIVE HUMIDITY Displays measured value of return air humidity from RA sensor. Displays _ _% if sensor sends invalid value, if not connected, short or out-of-range
SPACE/RETURN AIR CO Displays value of measured CO2 from CO2 sensor. Invalid if not
2
connected, short or out-of-range DEMAND CONTROLLED VENTILATION STATUS
Displays ON if above setpoint and OFF if below setpoint, and ONLY if a CO
sensor is connected.
2
Displays number of times actuator has cycled. 1 cycles equals 180 deg. of actuator movement in any direction.
Displays ERROR if voltage or torque is below actuator range.
EXHAUST STAGE 1 RELAY OUTPUT Output of EXH1 terminal: ON = relay closed OFF = relay open
EXHAUST STAGE 2 RELAY OUTPUT Output of AUX terminal; displays only if AUX = EXH2
ENERGY RECOVERY VENTILATOR Output of AUX terminal; displays only if AUX = ERV
28
Page 29
Table 7 — W7220 Menu Structure* (cont)
MENU PARAMETER
MECH COOL ON or
STATUS
(cont)
HEAT STAGES ON
FAN SPEED N/A LOW or HIGH
W (HEAT ON) N/A ON/OFF
MAT SET 53°F
LOW T LOCK 32°F
DRYBLB SET 63°F
DRYBLB DIFF 0°F
ENTH CURVE ES3
DCV SET 1100ppm
MIN POS 4.4 V 2 to 10 Vdc
MIN POS L 6.0 V 2 to 10 Vdc
SETPOINTS
MIN POS M 5.4 V 2 to 10 Vdc
MIN POS H 4.4 V 2 to 10 Vdc
VENTMAX L 6.0V 2 to 10 Vdc
VENTMAX M 5.4 V 2 to 10 Vdc
VENTMAX H 4.4 V 2 to 10 Vdc
VENTMIN L 3.7 V 2 to 10 Vdc
VENTMIN M 3.4 V 2 to 10 Vdc
VENTMIN H 2.8 V 2 to 10 Vdc
PARAMETER
DEFAULT
VALUE
PARAMETER
RANGE AND
INCREMENT
0 0, 1, or 2
38°F to 70°F (3°C to 21°C); increment by 1°F
–45°F to 80°F (–43°C to 27°C); increment by 1°F
48°F to 80°F (9°C to 27°C); increment by 1°F
0°F to 6°F Increment by 2°F
ES1, ES2, ES3, ES4, or ES5
500 to 2000 ppm; increment by 100
NOTES
Displays stage of mechanical cooling that is active.
Displays the stage of heat pump heating that is active. SUPPLY FAN SPEED
Displays speed setting of fan on a 2-speed fan unit. HEAT DEMAND STATUS
Displays status of heat demand on a 2-speed fan unit. MIXED AIR SETPOINT Setpoint determines where the economizer
will modulate the OA damper to maintain the mixed air temperature.
COMPRESSOR LOW TEMPERATURE LOCKOUT Setpoint determines outdoor temperature when the mechanical cooling cannot be turned on. Commonly referred to as the Compressor lockout.
OA DRY BULB TEMPERATURE CHANGEOVER SETPOINT Setpoint determines where the economizer will assume outdoor air temperature is good for free cooling; e.g.; at 63°F unit will economize at 62°F and below and not economize at 64°F and above. There is a 2°F deadband. DRYBULB SET is only displayed if the economizer has a single dry bulb sensor.
Drybulb Differential will only show if using dual drybulb - i.e. when an outdoor air temperature sensor C7250 is attached to OAT terminals and C7400S sensor is wired to S-Bus and configured for RAT (return air). Free cooling will be assumed whenever OA temp is at or below RAT minus this drybulb setting.
ENTHALPY CHANGEOVER CURVE (Requires enthalpy sensor option) Enthalpy boundary “curves” for economizing using single enthalpy.
DEMAND CONTROLLED VENTILATION SETPOINT Displays only if CO Controlled Ventilation of space. Above the setpoint, the OA
sensor is connected. Setpoint for Demand
2
dampers will modulate open to bring in additional OA to maintain a space ppm level below the setpoint.
VENTILATION MINIMUM POSITION. Only displayed if controller is set for single speed unit under FAN TYPE, and if DCV is NOT used.
VENTILATION MINIMUM POSITION AT LOW SPEED. Only displays if unit is set for 2 or 3 speed and CO 2 speed with 1 heat and 1 cool then set for HEATING ventilation. If
is not used. If using
2
using 3 speed with 1 heat and 2 cool then set for LOW SPEED COOLING ventilation.
VENTILATION MINIMUM POSITION AT MEDIUM SPEED. Only displays if unit is set for 3 speed with 1 heat and 2 cool, and CO not used. Set for HEATING ventilation.
VENTILATION MINIMUM POSITION AT HIGH SPEED. Only displays if unit is set for 2 or 3 speed and CO 2 speed with 1 heat and 1 cool then set for COOLING ventilation. If
is not used. IF using
2
using 3 speed with 1 heat and 2 cool then set for HIGH SPEED COOLING ventilation
DCV MAXIMUM DAMPER POSITION AT LOW SPEED. Only displays if unit is set for 2 speed or 3 speed with 1 heat and 2 cool. IF using 2 speed with 1 heat and 1 cool then set for HEATING ventilation. If using 3 speed with 1 heat and 2 cool then set for LOW SPEED COOLING
DCV MAXIMUM DAMPER POSITION AT MEDIUM SPEED. Only displays if unit is set for 3 speed with 1 heat and 2 cool. Set for HEATING ventilation.
DCV MAXIMUM DAMPER POSITION AT HIGH SPEED. Only displays if unit is set for 2 speed or 3 speed with 1 heat and 2 cool. IF using 2 speed with 1 heat and 1 cool then set for COOLING ventilation. If using 3 speed with 1 heat and 2 cool then set for HIGH SPEED COOLING ventilation
DCV MINIMUM DAMPER POSITION AT LOW SPEED. Only displays if unit is set for 2 speed or 3 speed with 1 heat and 2 cool. IF using 2 speed with 1 heat and 1 cool then set for HEATING ventilation. If using 3 speed with 1 heat and 2 cool then set for LOW SPEED COOLING
DCV MINIMUM DAMPER POSITION AT MEDIUM SPEED. Only displays if unit is set for 3 speed with 1 heat and 2 cool. Set for HEATING ventilation.
DCV MINIMUM DAMPER POSITION AT HIGH SPEED. Only displays if unit is set for 2 speed or 3 speed with 1 heat and 2 cool. IF using 2 speed with 1 heat and 1 cool then set for COOLING ventilation. If using 3 speed with 1 heat and 2 cool then set for HIGH SPEED COOLING ventilation
is
2
29
Page 30
Table 7 — W7220 Menu Structure* (cont)
MENU PARAMETER
ERV OAT SP
EXH1 SET 50% 0 to 100%
EXH1 L SET 65% 0 to 100%
EXH1 M SET 60% 0 to 100%
SETPOINTS
(cont)
EXH1 H SET 50% 0 to 100%
EXH2 L SET 80% 0 to 100%
EXH2 M SET 77% 0 to 100%
EXH2 H SET 75% 0 to 100%
INSTALL 01/01/17 N/A
UNITS DEG F F or C Sets economizer controller in degrees Fahrenheit or Celsius
EQUIPMENT CONV
AUX2 IN W
FAN SPEED 2 speed
SYSTEM
SETUP
FAN CFM 5000cfm
AUX1 OUT NONE
OCC INPUT
FACTORY DEFAULT NO NO or YES
MA LO SET 45°F
ADVANCED
SETUP
FREEZE POS CLO CLO or MIN
CO2 ZERO 0ppm
CO2 SPAN 2000ppm
PARAMETER
DEFAULT
VALUE
††
32°F
PARAMETER
RANGE AND
INCREMENT
0°F to 50°F (–18°C to 10°C); increment by 1°F
NOTES
ENERGY RECOVERY VENTILATOR UNIT OUTDOOR AIR TEMPERATURE SETPOINT Only displayed when AUX1 O = ERV
Exhaust fan set point for single speed units. Based on OA Damper position to activate power exhaust.
EXHAUST FAN 1 SETPOINT AT LOW SPEED on 2 speed or 3 speed with 1 heat and 2 cool. Based on economizer OA damper position to activate power exhaust.
EXHAUST POINT 1 SETPOINT AT MEDIUM SPEED. Only displays if unit is set for 3 speed with 1 heat and 2 cool. Based on economizer OA damper position to activate power exhaust.
EXHAUST FAN 1 SETPOINT AT HIGH SPEED on 2 speed or 3 speed with 1 heat and 2 cool. Based on economizer OA damper position to activate power exhaust.
EXHAUST FAN 2 SETPOINT AT LOW SPEED on 2 speed or 3 speed with 1 heat and 2 cool. Based on economizer OA damper position to activate power exhaust.
EXHAUST FAN 2 SETPOINT AT MEDIUM SPEED. Only displays if unit is set for 3 speed with 1 heat and 2 cool. Based on economizer OA damper position to activate power exhaust.
EXHAUST FAN 2 SETPOINT AT HIGH SPEED on 2 speed or 3 speed with 1 heat and 2 cool. Based on economizer OA damper position to activate power exhaust.
Display order = MM/DD/YY Setting order = DD, MM, then YY.
CONV = conventional; Conventional or HP
HP O/B = Enable Heat Pump mode. Use AUX2 I for Heat Pump
input from thermostat or controller.
See Menu Note 4.
In CONV mode:
SD + Enables configuration of shutdown (default);
W = Informs controller that system is in heating mode.
SD/W or HP(O)/ HP(B)
NOTE: If using 2-speed fan mode, you must program CONV mode
for W. Shutdown is not available in 2-speed fan mode. See Menu
Note 4.
In HP O/B mode:
HP(O) = energize heat pump on Cool (default);
HP(B) = energize heat pump on heat. 1 speed
2 speed 2SP H/C 3 speed
100 to 15000 cfm; increment by 100
Sets the economizer controller operation based on 1 speed, 2
speed, 2 speed heat/cool (2SP H/C), or 3 speed supply fan.
NOTE: Multi-speed fan options also need Heat (W1) programmed
in AUX 2 In. See Menu Note 4.
UNIT DESIGN AIRFLOW (CFM)
Enter only if using DCVAL ENA = AUTO
The value is found on the nameplate label for the specific unit.
Select OUTPUT for AUX1 O relay NONE ERV EXH2 SYS
• NONE = not configured (output is not used)
• ERV = Energy Recovery Ventilator
• EXH2 = second damper position relay closure for second exhaust
††
fan
• SYS = use output as an alarm signal
OCCUPIED MODE BY EXTERNAL SIGNAL
INPUT or ALWAYS
When using a setback thermostat with occupancy out (24 vac), the
24 vac is input “INPUT” to the OCC terminal. If no occupancy
output from the thermostat then change program to “ALWAYS” OR
add a jumper from terminal R to OCC terminal.
Resets all set points to factory defaults when set to YES. LCD
will briefly flash YES and change to NO but all parameters will change to the factory default values. NOTE: RECHECK AUX2 IN and FANTYPE for required 2-speed values.
35°F to 55°F (2°C to 13°C); Incremented by 10°F
SUPPLY AIR TEMPERATURE LOW LIMIT Temperature to achieve Freeze Protection (close damper and alarm if temperature falls below setup value).
FREEZE PROTECTION DAMPER POSITION Damper position when freeze protection is active (closed or MIN POS).
0 to 500 ppm; Increment by 10
1000 to 3000 ppm; Increment by 10
ppm level to match CO2 sensor start level.
CO
2
ppm span to match CO2 sensor.
CO
2
30
Page 31
Table 7 — W7220 Menu Structure* (cont)
MENU PARAMETER
STG3 DLY 2.0h
SD DMPR POS CLO CLO or OPN
DA LO ALM 45°F (7°C)
DA HI ALM 80°F (27°C)
DCVCAL ENA MAN
ADVANCED
SETUP
(cont)
MAT T CAL 0.0°F ±2.5°F
OAS T CAL 0.0°F ±2.5°F
OA H CAL 0% RH ±10% RH
RA T CAL 0.0°F ±2.5°F
RA H CAL 0% RH ±10% RH
DA T CAL 0.0°F ±2.5°F
2SP FAN DELAY 5 Minutes
DAMPER MINIMUM POSITION
DAMPER OPEN N/A N/A
DAMPER CLOSE N/A N/A Positions damper to the fully closed position
CHECKOUT
CONNECT Y1–O N/A N/A Closes the Y1-O relay (Y1-O) CONNECT Y2–O N/A N/A Closes the Y2-O relay (Y2-O)
CONNECT AUX1-O N/A N/A
CONNECT EXH1 N/A N/A Closes the power exhaust fan 2 relay (EXH1)
Alarms display only when they are active. The menu title “ALARMS(#)” includes the number of active alarms in parenthesis ( ). When using SYLK bus sensors, “SYLK” will appear on the screen, and when using 20k OA temperature sensors, “SENS T” will
MA T SENS ERR N/A N/A
ALARMS
CO2 SENS ERR N/A N/A
OA SYLK T ERR N/A N/A OUTSIDE AIR S-BUS SENSOR ERROR
OA SYLK H ERR N/A N/A
RA SYLK T ERR N/A N/A RETURN AIR S-BUS SENSOR ERROR
RA SYLK H ERR N/A N/A
PARAMETER
DEFAULT
VALUE
0 min, 5 min, 15 min, then 15 min intervals. Up to 4 hrs or OFF
35°F to 65°F (2°C to 18°C); Incremented by 5°F.
70°F to 180°F (21°C to 82°C); Incremented by 5°F
MAN (manual) AUTO
0 to 20 minutes in 1 minute increments
N/A N/A
PARAMETER
RANGE AND
INCREMENT
appear on the screen
NOTES
COOLING STAGE 3 DELAY Delay after stage 2 cool has been active. Turns on second stage of cooling when economizer is first stage and mechanical cooling is second stage. Allows three stages of cooling, 1 economizer and 2 mechanical. OFF = no Stage 3 cooling
Indicates shutdown signal from space thermostat or unitary controller. When controller receives 24 Vac input on the SD terminal in conventional mode, the OA damper will open if programmed for OPN and OA damper will close if programmed for CLO. All other controls, e.g., fans, etc. will shut off.
Used for alarm for when the DA air temperature is too low. Set lower range of alarm, below this temperature the alarm will show on the display.
Used for alarm for when the DA air temperature is too high. Set upper range of alarm, above this temperature the alarm will show on the display.
Turns on the DCV automatic control of the dampers. Resets ventilation based on the RA, OA, and MA sensor conditions. Requires all 3 RA, OA, and MA sensors.
SUPPLY AIR TEMPERATURE CALIBRATION Allows for the operator to adjust for an out of calibration temperature sensor.
OUTSIDE AIR TEMPERATURE CALIBRATION Allows for the operator to adjust for an out of calibration temperature sensor.
OUTSIDE AIR HUMIDITY CALIBRATION Allows for operator to adjust for an out of calibration humidity sensor.
RETURN AIR TEMPERATURE CALIBRATION Allows for the operator to adjust for an out of calibration temperature sensor.
RETURN AIR HUMIDITY CALIBRATION Allows for operator to adjust for an out of calibration humidity sensor.
DISCHARGE AIR TEMPERATURE CALIBRATION Allows for the operator to adjust for an out of calibration temperature sensor.
TIME DELAY ON SECOND STAGE ECONOMIZING When in economizing mode this is the delay for the high speed fan to try to satisfy the call for second stage cooling before the first stage mechanical cooling is enabled.
The checkout for the damper minimum position is based on the system.
Position damper to the full open position. Exhaust fan contacts enable during the DAMPER OPEN test. Make sure you pause in the mode to allow exhaust contacts to energize due to the delay in the system.
Energizes the AUX output. If Aux setting is:
• NONE — not action taken
• ERV — 24 Vac out. Turns on or signals an ERV that the conditions are not good for economizing but are for ERV operation.
• SYS — 24 Vac out. Issues a system alarm
††
SUPPLY AIR TEMPERATURE SENSOR ERROR Mixed air sensor has failed or become disconnected - check wiring then replace sensor if the alarm continues.
SENSOR ERROR
CO
2
sensor has failed, gone out of range or become disconnected -
CO
2
check wiring then replace sensor if the alarm continues.
Outdoor air enthalpy sensor has failed or become disconnected ­check wiring then replace sensor if the alarm continues.
Return air enthalpy sensor has failed or become disconnected ­check wiring then replace sensor if the alarm continues.
31
Page 32
Table 7 — W7220 Menu Structure* (cont)
MENU PARAMETER
PARAMETER
DEFAULT
VALUE
PARAMETER
RANGE AND
INCREMENT
DA SYLK T ERR N/A N/A
OA SENS T ERR N/A N/A
ACT ERROR N/A N/A
FREEZE ALARM N/A N/A
AL
(cont)
ARMS
SHUTDOWN ACTIVE N/A N/A
DMP CAL RUNNING N/A N/A
DA SENS ALM N/A N/A
SYS ALARM N/A N/A
ACT UNDER V N/A N/A
ACT OVER V N/A N/A
ACT STALLED N/A N/A
LEGEND
CLO Compressor Lockout ERV Energy Recovery Ventilator LCD Liquid Crystal Display MA Mixed Air MAT Mixed Air Temperature N/A Not Applicable OA Outdoor Air OAT Outdoor Air Temperature OCC Occupied RA Return Air RAT Return Air Temperature RTU Rooftop Unit SYS System
* Table 7 illustrates the complete hierarchy. Your menu parameters
may be different depending on your configuration. For example if you do not have a DCV (CO
) sensor, then none of the DCV parameters
2
appear.
† When values are displayed, pressing and holding the or button
causes the display to automatically increment. ** N/A = Not Applicable. †† ERV Operation: When in cooling mode AND the conditions are NOT
OK for economizing - the ERV terminal will be energized. In the Heat-
ing mode, the ERV terminal will be energized when the OA is below
the ERV OAT setpoint in the setpoint menu.
NOTES
DISCHARGE AIR S-BUS SENSOR ERROR Discharge air sensor has failed or become disconnected - check wiring then replace sensor if the alarm continues.
OUTSIDE AIR TEMPERATURE SENSOR ERROR Outdoor air temperature sensor has failed or become disconnected
- check wiring then replace if the alarm continues. ACTUATOR ERROR
Actuator has failed or become disconnected - check for stall, over voltage, under voltage and actuator count. Replace actuator if damper is movable and supply voltage is between 21.6-v and
26.4-v. Check actuator count on STATUS menu. Check if outdoor temperature is below the LOW Temp Lockout on
setpoint menu. Check if Mixed air temperature on STATUS menu is below the Lo Setpoint on Advanced menu. When conditions are back in normal range then the alarm will go away.
AUX2 IN is programmed for SHUTDOWN and 24 V has been applied to AUX2 IN terminal.
DAMPER CALIBRATION ROUTINE RUNNING If DCV Auto enable has been programmed, when the W7220 is completing a calibration on the dampers, this alarm will display. Wait until the calibration is completed and the alarm
will
go away. Must have OA, MA and RA sensors for DCV calibration; set up in the Advanced setup menu.
DISCHARGE AIR TEMPERATURE SENSOR ALARM Discharge air temperature is out of the range set in the ADVANCED SETUP Menu. Check the temperature of the discharge air.
When AUX1-O is set to SYS and there is any alarm (e.g., failed sensors, etc.), the AUX1-O terminal has 24 Vac out.
ACTUATOR VOLTAGE LOW Voltage received by actuator is above expected range.
ACTUATOR VOLTAGE HIGH Voltage received by actuator is below expected range.
ACTUATOR STALLED Actuator stopped before achieving commanded position.
NOTES:
1. STATUS OCCUPIED — The factory-standard Occupancy signal originates with a thermostat or other controller call for indoor fan operation at UCB terminal G. This signal passes through the Unit
Control Board’s OCCUPANCY jumper to the ECONO connector and to the W7220’s OCC input terminal.An external timeclock or
relay is required to implement an Occupancy schedule on the economizer damper position.
2. STATUS MA TEMP, SETPOINTS MAT SET — The W7220 menu parameters and labels include designations MA, MAT and Mixed Air for the economizer cooling control sensor. On these roof­top units, the economizer control sensor is located downstream of the evaporator/indoor coil in the supply fan section where this sen­sor is designated as Supply Air Temperature (SAT) sensor.
3. SETPOINTS D
RYBLB SET — This point is not displayed if a
Return Air (differential) temperature sensor or an Outdoor Air enthalpy sensor is connected.
4. SYSTEM SETUP parameters must be configured as noted for Multi-Speed unit operation: EQUIPMENT = CONV AUX2 IN = W FAN SPEED = 2SPEED NOTE: 1SPEED, 2SP H/C and 3SPEED are not used on 50GC units.
32
Page 33
ENTHALPY SETTINGS When the OA temperature, enthalpy and dew point are below the
respective setpoints, the Outdoor Air can be used for economiz­ing. Fig. 49 shows the new single enthalpy boundaries in the W7220. There are 5 boundaries (setpoints ES1 through ES5), which are defined by dry bulb temperature, enthalpy and dew point.
Refer to Table 8 for ENTH CURVE setpoint values. The W7220 calculates the enthalpy and dew point using the OA
temperature and humidity input from the OA enthalpy sensor.
When the OA temperature, OA humidity and OA dew point are all below the selected boundary, the economizer sets the econo­mizing mode to YES, economizing is available.
When all of the OA conditions are above the selected boundary, the conditions are not good to economize and the mode is set to NO.
Figure 49 shows the 5 current boundaries. There is also a high lim­it boundary for differential enthalpy. The high limit boundary is ES1 when there are no stages of mechanical cooling energized and HL (high limit) when a compressor stage is energized.
ECONOMIZING
AVAILABLE
NOT AVAILABLE
ENTHALPY
RA HUM (%RH)
ABSOLUTE HUMIDITY
RA TEMP
TEMPERATURE
DUAL ENTHALPY
SINGLE ENTHALPY
P2 (T,RH)
ES4
ES5
ES3
HIGH LIMIT
P1 (T,RH)
ES2 ES1
Fig. 49 — Single Enthalpy Curve Boundaries
Table 8 — Single Enthalpy and Dual Enthalpy High Limit Curves
ENTHALPY
CURVE
ES1 80 60 28.0 80 36.8 66.3 80.1 ES2 75 57 26.0 75 39.6 63.3 80.0 ES3 70 54 24.0 70 42.3 59.7 81.4 ES4 65 51 22.0 65 44.8 55.7 84.2 ES5 60 48 20.0 60 46.9 51.3 88.5
HL 86 66 32.4 86 38.9 72.4 80.3
TEMP. DRY
BULB (F)
TEMP.
DEWPOINT (F)
ENTHALPY
(btu/lb/da)
TEMP. (F)
POINT P1 POINT P2
HUMIDITY
(%RH)
TEMP. (F)
HL
HUMIDITY
(%RH)
33
Page 34
STANDARD OR SINGLE SPEED FAN OPERATION FAN TYPE = 1SPEED is not used on 50GC units.

2 SPEED FAN OPERATION The W7220 controller has the capability to work with a system us-

ing a 2 speed supply fan. The W7220 does not control the supply directly but uses the following input status to determine the speed of the supply fan and controls the OA damper to the required posi­tion, see Table 9.
The W (heating mode) is not controlled by the W7220 but it re­quires the status to know where to position the OA damper for minimum position for the fan speed.
The 2 speed fan delay is available when the system is programmed for 2 speed fan (in the System Setup menu item). The 2 speed fan delay is defaulted to 5 minutes and can be changed in the Ad­vanced Setup menu item. When the unit has a call for Y1 In and in the free cooling mode and there is a call for Y2 In, the 2-speed fan delay starts and the OA damper will modulate 100% open, the supply fan should be set to high speed by the unit controller. See
Table 9 — Fan Speed
STATE FAN SPEED
OCC Low
Y1 Low Y2 High
W High
Table 10. After the delay one of two actions will happen:
The Y2 In call will be satisfied with the damper 100% open and fan on high speed and the call will turn off
OR If the call for additional cooling in the space has not been satisfied
then the first stage of mechanical cooling will be enabled through Y1 Out or Y2 Out.
Table 10 — Economizer Operation - FAN TYPE = 2SPEED
INPUTS OUTPUTS
DEMAND
CONTROLLED
VENTILATION
(DCV)
NONE
Below CO
Above CO
*With stage 3 delay (STG3 DLY) in Advanced setup, COOL Y2-OUT will be turned ON after the delay time specified. N/A = Not applicable
2
2
Set
Set
OUTSIDE AIR
GOOD TO
ECONOMIZE
NO
YES
NO
YES
NO
YES
W
(HEAT ON)
ON N/A N/A OFF OFF HIGH MIN POS H Closed OFF OFF OFF OFF OFF LOW MIN POS L Closed OFF ON OFF ON OFF LOW MIN POS L Closed OFF ON ON ON ON HIGH MIN POS H Closed
ON N/A N/A OFF OFF HIGH MIN POS H Closed OFF OFF OFF OFF OFF LOW MIN POS L Closed
OFF ON OFF OFF OFF LOW
OFF ON ON ON OFF* HIGH
ON N/A N/A OFF OFF HIGH VENTMIN H Closed OFF OFF OFF OFF OFF LOW VENTMIN L Closed OFF ON OFF ON OFF LOW VENTMIN L Closed OFF ON ON ON ON HIGH VENTMIN H Closed
ON N/A N/A OFF OFF HIGH VENTMIN H Closed OFF OFF OFF OFF OFF LOW VENTMIN L Closed
OFF ON OFF OFF OFF LOW
OFF ON ON ON OFF* HIGH
ON N/A N/A OFF OFF HIGH
OFF OFF OFF OFF OFF LOW
OFF ON OFF ON OFF LOW
OFF ON ON ON ON HIGH
ON N/A N/A OFF OFF HIGH
OFF OFF OFF OFF OFF LOW
OFF ON OFF OFF OFF* LOW
OFF ON ON ON OFF* HIGH
COOL
Y1-IN
COOL
Y2-IN
COOL
Y1-OUT
COOL
Y2-OUT
FAN SPEED
(reference
only)
OCCUPIED UNOCCUPIED
MIN POS L to
Full Open
MIN POS H to
Full Open
VENTMIN L to
Full Open
VENTMIN H to
Full Open
VENTMIN H to
VENTMAX H
VENTMIN L to
VENTMAX L
VENTMIN L to
VENTMAX L
VENTMAX H to
VENTMAX H
VENTMIN H to
VENTMAX H
VENTMIN L to
VENTMAX L
VENTMIN L to
Full Open
VENTMIN H to
Full Open
DAMPER POSITION
Closed to
Full Open Closed to
Full Open
Closed to Full Open
Closed to Full Open
Closed
Closed
Closed
Closed
Closed
Closed
Closed to Full Open
Closed to Full Open
34
Page 35

2SP H/C AND 3 SPEED FAN OPERATION FAN TYPE = 2SP H/C and FAN TYPE = 3SPEED are not used

on 50GC units.
CHECKOUT Inspect all wiring connections at the economizer module’s termi-
nals, and verify compliance with the installation wiring diagrams. For checkout, review the Status of each configured parameter and perform the Checkout tests.
NOTE: For information about menu navigation and use of the keypad see Interface Overview on page 26.
WARNING
ELECTRIC SHOCK HAZARD Failure to follow this warning could result in personal injury,
property damage, or death. Before performing service or maintenance operations on unit,
always turn off main power switch to unit and install lock(s) and lockout tag(s). Unit may have more than one power switch. Ensure electrical service to rooftop unit agrees with voltage and amperage listed on the unit rating plate.
If any wiring changes are required, first be sure to remove power from the economizer module before starting work. Pay particular attention to verifying the power connection (24 vac).
Power Up
After the W7220 module is mounted and wired, apply power.
Initial Menu Display
On initial start up, Honeywell displays on the first line and econo­mizer W7220 on the second line. After a brief pause, the revision of the software appears on the first line and the second line will be blank.
Power Loss (Outage or Brownout)
All setpoints and advanced settings are restored after any power loss or interruption.
NOTE: All settings are stored in non-volatile flash memory.
Status
Use the Status menu (see Table 7) to check the parameter values for the various devices and sensors configured.
NOTE: For information about menu navigation and use of the keypad, see Interface Overview on page 26.
Checkout Tests
Use the Checkout menu (see page 31) to test the damper operation and any configured outputs. Only items that are configured are shown in the Checkout menu.
NOTE: For information about menu navigation and use of the keypad, see Interface Overview on page 26.
To perform a Checkout test:
1. Scroll to the desired test in the Checkout menu using the ▲ and ▼ buttons.
2. Press the (Enter) button to select the item. RUN? appears.
3. Press the (Enter) button to start the test. The unit pauses and then displays IN PROGRESS. When the test is complete, DONE appears.
4. When all desired parameters have been tested, press the (Menu Up/Exit) button to end the test.
The Checkout tests can all be performed at the time of installation or at any time during the operation of the system as a test that the system is operable.
CAUTION
EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage. Be sure to allow enough time for compressor start-up and
shutdown between checkout tests so that you do not short­cycle the compressors.

TROUBLESHOOTING

Alarms
The economizer module provides alarm messages that display on the 2-line LCD.
NOTE: Upon power up, the module waits 60 minutes before checking for alarms. This allows time for all the configured devic­es (e.g. sensors, actuator) to become operational. The exception is the SAT sensor which will alarm immediately.
If one or more alarms are present and there has been no keypad ac­tivity for at least 5 minutes, the Alarms menu displays and cycles through the active alarms.
You can also navigate to the Alarms menu at any time.
Clearing Alarms
Once the alarm has been identified and the cause has been removed (e.g. replaced faulty sensor) the alarm can be cleared from the display.
To clear an alarm, perform the following:
1. Navigate to the desired alarm.
2. Press the (Enter) button. ERASE? displays.
3. Press the (Enter) button. ALARM ERASED displays.
4. Press the (Menu Up/Exit) button to complete the action and return to the previous menu.
NOTE: If the alarm still exists after clearing it, it is redisplayed within 5 seconds.

RTU Open Controller (Factory Option)

For details on operating 50GC**04-06 units equipped with the factory-installed RTU Open controller option, refer to the Factory-
Installed Option RTU Open Multi-Protocol Controller Controls, Start-Up, Operation and Troubleshooting manual.

SystemVu™ Controller (Factory Option)

For details on operating 50GC**04-06 units equipped with the factory-installed SystemVu controller option, refer to the FC/GC
Series Single Package Rooftop Units with SystemVu Controller Controls, Start-up, Operation and Troubleshooting manual.

Controller Options

LOW AMBIENT If the unit comes with Electro-Mechanical (EM) control, then no
adjustment is necessary. If the unit comes with SystemVu™ or RTU Open control option,
then refer to its installation control manual for details on adjusting “Cooling Lock-Out” setting and configure for the specific job re­quirements.

Smoke Detectors

Smoke detectors are available as factory-installed options on 50GC models. Smoke detectors may be specified for supply air only, for return air without or with economizer, or in combination of supply air and return air. Return-air smoke detectors are ar­ranged for vertical return configurations only. All components necessary for operation are factory-provided and mounted. The unit is factory-configured for immediate smoke detector shutdown operation; additional wiring or modifications to unit control board
35
Page 36
may be necessary to complete the unit and smoke detector config-
STEP 1 STEP 2 STEP 3
uration to meet project requirements. Units equipped with factory-optional return-air smoke detectors
require a relocation of the sensor module at unit installation. See Fig. 50 for the as-shipped location.
Completing Return Air Smoke Sensor Installation
1. Unscrew the two screws holding the return-air smoke detec-
tor assembly. See Fig. 51, Step 1. Save the screws.
2. Turn the assembly 90 degrees and then rotate end to end. Make sure that the elbow fitting is pointing down. See Fig. 51, Step 2.
3. Screw the sensor and detector plate into its operating position using screws from Step 1. See Fig. 51, Step 3.
4. Connect the flexible tube on the sampling inlet to the sam­pling tube on the basepan.
Additional Application Data
Refer to the application data document “Factory Installed Smoke Detectors for Small and Medium Rooftop Units 2 to 25 Tons” for
discussions on additional control features of these smoke detectors including multiple unit coordination.
RETURN AIR SMOKE DETECTOR (AS SHIPPED)
Fig. 50 — Return-Air Smoke Detector,
Shipping Position
Fig. 51 — Completing Installation of Return Air Smoke Sensor
36
Page 37

Step 12 — Adjust Factory-Installed Options

SMOKE DETECTORS Smoke detector(s) will be connected at the Unit Control Board, at
terminals marked “Smoke Shutdown.” Detach the jumper cover­ing the Smoke Shutdown terminals on the UCB and then attach the wiring harness from the smoke detector.
®
ECONOMI$ER
IV OCCUPANCY SWITCH
See Fig. 52 for general EconoMi$er IV wiring. External occupan­cy control is managed through a connection on the Unit Control Board.
If external occupancy control is desired, connect a time clock or remotely controlled switch (closed for Occupied, open for Unoc­cupied sequence) at terminals marked OCCUPANCY. Detach the jumper covering the “Occupancy” terminals on the UCB and then attach the required connections.

Step 13 — Install Accessories

Available accessories include:
Roof curb
Thru-base connection kit (must be installed before unit is set on curb)
Electric heaters and single-point connection kits
Manual outside air damper
Two-position motorized outside air damper
EconoMi$er IV (with control)
EconoMi$er2 (without control/for external signal)
Power Exhaust
Differential dry-bulb sensor (EconoMi$er IV)
Outdoor enthalpy sensor
Differential enthalpy sensor
CO
sensor
2
Louvered hail guard
Phase monitor control
Refer to separate installation instructions for information on in­stalling these accessories.
Fig. 52 — EconoMi$er IV Wiring
37
Page 38

Step 14 — Fan Speed Set Up

FAN SPEED SET UP CONTROLS
UNITS WITH ELECTRO-MECHANICAL CONTROLS The fan speed set up controls are located on the lower section of
the Unit Control Board (UCB). See Fig. 53 for location.
1. Check the job specifications for the CFM (cubic feet per min-
ute) and ESP (external static pressure) required.
2. Using the chart on the fan speed set up labels (see Fig. 54), calculate the Vdc from the CFM and ESP for the base unit. Then add Vdc for any accessories installed per the “Field Accessories” section of the label.
NOTE: The fan speed set up labels are located on the High Volt­age cover in the Control Box.
3. Connect a multimeter to the Vdc terminals on the UCB.
4. Set the Range Switch to either A, B, or C per the Switch Range table.
5. Using a straight blade screwdriver, turn the Vdc control dial to fine tune the Vdc reading.
6. Record the reading in the Field Setting field.
NOTE: Fan set-up Vdc is not affected by the operating stage of the unit.
Fig. 53 — UCB Fan Speed Controls
38
Page 39

UNITS WITH SYSTEMVU™ CONTROLS

Factory Setting:
9.0 VDC
Field Setting:
V

Switch Range:
A B C
B
A
C
Field Accessories:
ESP in. wg
VDC Calculator
CFM
0.2
5.4
5.8
6.1
6.5
6.8
7.2
7.6
7.9
8.3
1500 1625 1750 1875 2000 2125 2250 2375 2500
0.1
0.4
6.2
6.5
6.8
7.1
7.4
7.7
8.0
8.4
8.7
0.1
0.6
6.9
7.1
7.4
7.7
7.9
8.2
8.5
8.8
0.1
0.8
7.5
7.7
8.0
8.2
8.5
8.7
9.0
0.1
1.0
8.1
8.3
8.5
8.7
9.0
0.1
1.2
8.6
8.8
9.0
9.2
0.1
1.4
9.1
9.3
9.5
0.1
1.6 1.8 2.0
9.6
0.1Economizer
1 Stage E Heat 2 Stage E Heat
UNIT MODEL NUMBER
4.1 - 7.5
6.9 - 8.7
7.7 - 10.0
0.2
0.3
0.2
0.3
0.2
0.3
0.2
0.3
0.2
0.3
0.2
0.3
0.2
0.3
0.2
0.3
9.8
9.9
9.7
9.99.5
9.7
10.0
9.2
9.5
9.8
9.3
9.69.2
Record field setting here
*
* Overlap in A, B, C switch range
designed for maximum field adjustment potential. For example
7.2 can be set at either A or B.
On units equipped with the factory-installed SystemVu controller the Fan Speed settings are accessed through the SystemVu inter­face.
1. Check the job specifications for the CFM (cubic feet per min-
ute) and ESP (external static pressure) required.
2. Using the chart on the fan speed set up labels (see Fig. 55), calculate the RPM from the CFM and ESP for the base unit plus any field accessories (as listed on the label).
NOTE: The fan speed set up labels are located on the High Volt­age cover in the Control Box.
3. Press any key on the SystemVu interface to activate the dis­play backlight and then press the MENU key.
4. Using the UP and DOWN arrow keys highlight SETTINGS and then press ENTER.
5. Use the DOWN arrow key highlight the UNIT CONFIGU­RATIONS menu then press ENTER.
6. Highlight UNIT CONFIGURATIONS then press ENTER.
Fig. 54 — Example of Fan Speed Set Up Labels for Electro-Mechanical Controls
7. Highlight INDOOR FAN and then press ENTER.
8. Refer to the job specifications to set the following, determin-
ing the values per the RPM Calculator label (see Fig. 55). Use
IDF VENT SPD
IDF HEAT SPD
IDF LOW COOL SPD
IDF HIGH SPD
IDF FREE COOL SPD
For further details, see the FC/GC Series Single Package Rooftop
Units with SystemVu Controller Controls, Start-up, Operation and Troubleshooting manual.
39
the UP and DOWN arrow keys and the BACK key to set the values. Press ENTER after setting each value to continue to the next selection.
Page 40
Fig. 55 — Example of Fan Speed Set Up Labels for SystemVu™ Controls
Field Accessories:
2500
Economizer
ESP in. wg
RPM
Calculator
CFM
0.2
1301 1381 1463 1548 1633 1720 1808 1897 1987
1500 1625 1750 1875 2000 2125 2250 2375
66 80
107
0.4
1477 1544 1615 1688 1764 1842 1921 2003 2068
66
0.6
1639 1699 1763 1828 1897 1967 2040 2115 2191
0.8
1788 1843 1902 1962 2025 2090 2157 2227 2298
66
1.0
1925 1976 2031 2087 2146 2208 2271 2336
66
1.2
2054 2101 2152 2206 2262 2320 2380
66
1.4
2174 2220 2268 2318 2372
66
1.6 1.8 2.0
2289 2332 2378
66 66
80 80 80 80 80 80 80
107 107 107 107 107 107 107
1 Stage E Heat 2 Stage E Heat
UNIT MODEL NUMBER
40
Page 41
Page 42
© 2021 Carrier
Catalog No. 04-53500269-01 Printed in U.S.A. Form 50GC-4-6-03SI Rev. A Pg 42 3-21 Replaces: 50GC-4-6-02SI
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Page 43
Start-Up Checklist for 50GC**04-06 Single Package Rooftop
Cooling Only/Electric Heat Unit
(Remove and use for job file)
NOTE: To avoid injury to personnel and damage to equipment or property when completing the procedures listed in this start-up checklist, use good judgment, follow safe practices, and adhere to
the safety considerations/information as outlined in preceding sec-
tions of this Installation Instruction document.
I. PRELIMINARY INFORMATION
MODEL NO. ____________________________________________
JOB NAME_____________________________________________
SERIAL NO. ____________________________________________
ADDRESS _____________________________________________
START-UP DATE________________________________________
TECHNICIAN NAME ___
AD
DITIONAL ACCESSORIES
_____________________________________________________________________________________________________
__________________________________
II. PRE-START-UP
Verify that all packaging materials have been removed from unit (Y/N) _____ Verify installation of outdoor air hood (Y/N) _____ Verify that condensate connection is installed per instructions (Y/N) _____ Verify that all electric Check that indoor-air filters are clean and in place (Y/N) _____ Check that outdoor air inlet screens are in place (Y/N) _____ Verify that unit is level (Y/N) _____ Verify that fan assembly is free of obstructions and rotor spins freely (Y/N) _____ Verify that scroll compressors are rotating in the correct direction (Y/N) _____ Verify installation of th
al connections and terminals are tight (Y/
ermostat (Y/
N) _____
N) _____
III. START-UP
ELECTRICAL
Supply Voltage L1-L2_____________ L2-L3_____________ L3-L1_____________ Compressor Amps 1 L1 _____________ L2 _____________ L3 _____________ Compressor Amps 2 L1 _____________ L2 _____________ L3 _____________ Supply Fan Amps L1 _____________ L2 _____________ L3 _____________
TEMPERATURES
Outdoor-air Temperature _____________ °F DB (Dry Bulb) Return-air Temperature _____________ °F DB _____________ °F Wb (Wet Bu Cooling Supply Air Temperature _____________ °F
lb)
Catalog No. 04-53500269-01 Printed in U.S.A. Form 50GC-4-6-03SI Rev. A Pg CL-1 3-21 Replaces: 50GC-4-6-02SI
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Page 44
PRESSURES
Refrigerant Suction CIRCUIT A _____________ PSIG
CIRCUIT B _____________ PSIG
Refrigerant Discharge CIRCUIT A _____________ PSIG
CIRCUIT B _____________ PSIG
Verify Refrigerant Charge using Charging Charts (Y/N) _____
GENERAL
Economizer minimum vent and changeover settings to job requirements (if equipped) (Y/N) _____ Verify smoke detector unit shutdown by utilizing magnet test (Y/
N) _____
IV. HUMIDI-MIZER® START-UP
STEPS
1. Check UCB for jumper 1, 2, 3 (Jumper 1, 2, 3 must be cut and open) (Y/N) _____
2. Open humidistat contacts (Y/N) _____
3. Start unit In cooling (Close Y1) (Y/N) _____
OBSERVE AND RECORD
A. Suction pressure _______________ PSIG B. Discharge pressure _______________ PSIG C. Entering air temperature _______________ ° F D. Liquid line temperature at outlet or reheat E. Confirm correct rotation for compressor (Y/N) _____ F. Check for correct ramp-up of outdoor fan motor as condenser coil warms (Y/N) _____
4. Switch unit to high-latent mode (sub-cooler) by closing humidistat with Y1 closed (Y/N) _____
5. Check unit charge per charging chart (Y/N) _____
coil __
OBSERVE
A. Reduction in suction pressure (5 to 7 psi expected) (Y/N) _____ B. Discharge pressure unchanged (Y/N) _____
C.
Liquid temperature drops to 50°F to 55°F range (Y/N) _____
D. LSV solenoid energized (valve closes) (Y/N) _____
6. Switch unit to dehumid (reheat) by opening Y1 (Y/N) _____
OBSERVE
A. Suction pressure increases to normal cooling level B. Discharge pressure decreases (35 to 50 psi) (Limited by head pressure control) C. Liquid temperature returns to normal cooling level D. LSV solenoid energized (valve closes) E. DSV solenoid energized, valve opens
7. Wit
h unit in dehumid mode close W1 compressor and outdoor fan stop; LSV
8. Open W1 restore unit to dehumid mode (Y/N) _____
9. Open humidistat input compressor and outdoor fan stop; LSV and DSV solenoids de-energized (Y/N) _____
10. Restore setpoints for thermostat and humidistat (Y/N) _____
_____________ ° F
and DSV solenoids de-energized (Y/N) _____
© 2021 Carrier
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500269-01 Printed in U.S.A. Form 50GC-4-6-03SI Rev. A Pg CL-2 3-21 Replaces: 50GC-4-6-02SI
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
Loading...