Carrier weathermaker 8000 Installation, Start-up And Operator's manual

WeatherMaker 8000™
58WAV
Upflow Induced-Combustion Furnaces
Installation, Start-Up, and Operating Instructions
Sizes 045-155, Series 141
NOTE: Read the entire instruction manual before starting the
installation.
This symbol indicates a change since the last issue.
SAFETY CONSIDERATIONS .....................................................1
Clearances From Combustible Materials .................................1
Dimensional Drawing ...............................................................2
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
PROCEDURE........................................................................2-3
INTRODUCTION ..........................................................................3
LOCATION....................................................................................3
General ......................................................................................3
Location Relative to Cooling Equipment ................................3
Hazardous Locations.................................................................3
AIR FOR COMBUSTION AND VENTILATION...................3-5
Unconfined Space .....................................................................4
Confined Space......................................................................4-5
FILTER ARRANGEMENT .......................................................5-6
LEVELING LEGS (IF REQUIRED).........................................5-6
GAS PIPING...............................................................................6-7
ELECTRICAL CONNECTIONS ..................................................7
115-v Wiring.............................................................................7
24-v Wiring...............................................................................7
Accessories................................................................................7
VENTING ......................................................................................7
START-UP, ADJUSTMENT, AND SAFETY CHECK.........8-14
General ......................................................................................8
Sequence Of Operation .......................................................9-11
Heating Mode ......................................................................9-11
Cooling Mode .........................................................................11
Continuous Blower Mode.......................................................11
Heat Pump Mode ....................................................................11
Start-Up Procedures ................................................................11
Adjustments .......................................................................11-16
Set Gas Input Rate ............................................................11-15
Set Temperature Rise..............................................................15
Set Thermostat Heat Anticipator ......................................15-16
Check Safety Controls .................................................................16
Checklist .......................................................................................16
SAFETY CONSIDERATIONS
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified person­nel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions in the literature, on tags, and on labels attached to or shipped with the unit and other safety precautions that may apply.
Follow all safety codes. In the United States, follow all safety codes including the National Fuel Gas Code (NFGC) NFPA No. 54-1992/ANSI Z223.1-1992 and the Installation Standards, Warm
Air Heating and Air Conditioning Systems (NFPA 90B) ANSI/NFPA 90B. In Canada, refer to the current edition of the National Standard of Canada CAN/CGA-B149.1- and .2-M95 Natural Gas and Propane Installation Codes (NSCNGPIC). Wear safety glasses and work gloves. Have fire extinguisher available during start-up and adjustment procedures and service calls.
Recognize safety information. This is the safety-alert symbol
. When you see this symbol on the furnace and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAU­TION. These words are used with the safety-alert symbol. DAN­GER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances, these instructions exceed certain local codes and ordinances, especially those that may not have kept up with changing residen­tial construction practices. We require these instructions as a minimum for a safe installation.
ama
®
CANADIAN GAS ASSOCIATION
APPROVED
R
Table 1—Minimum Clearances From
Combustible Materials (In.)
UNIT SIZE 045 AND 070 091-155
Sides Single-Wall Vent 1 0
Type B-1 Double-Wall Vent 0 0
Back 00
Plenum Top 11
Vent Single-Wall Vent 6 6
Type B-1 Double-Wall Vent 1 1
Front Single-Wall Vent 6 6
Type B-1 Double-Wall Vent 3 3 Service 30 30
NOTES:
1. Provide 30-in. front clearance for servicing. An open door in front of the unit can meet this requirement.
2. A minimum clearance of 3 in. must be provided in front of the unit for combustion air and proper operation.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Tab 6a 8a
PC 101 Catalog No. 565-980 Printed in U.S.A. Form 58WAV-7SI Pg 1 5-96 Replaces: 58WAV-6SI
39 7⁄8
28 1⁄2
FLUE COLLAR
7
8-IN. DIA HOLE
POWER ENTRY
7
8-IN. DIA
ACCESSORY
1 3⁄4-IN. DIA HOLE
GAS ENTRY
1
2-IN. DIA HOLE
THERMOSTAT
WIRE ENTRY
2 1⁄16
1
5 3⁄8
5 13⁄16
2 3⁄8
12 5⁄16
AIRFLOW
A D
13
16
5 3⁄8
5 13⁄16
2 3⁄8
2 11⁄16
2 1⁄16
1
7
8-IN. DIA
POWER ENTRY
1 1⁄2-IN. DIA R.H. GAS ENTRY
7
8-IN. DIA ACCESSORY
1
2-IN. DIA THERMOSTAT
WIRE ENTRY
19
OUTLET
13
16
SIDE INLET
TYP 1
11
11
16
24 5⁄16
AIR INLET
3
NOTES:
11
16
1. Two additional 7⁄8-in. dia knockouts are located in the top plate.
2. Minimum return-air opening at furnace: a. For 800 CFM–16-in. round or 141⁄2 x 12-in. rectangle. b. For 1200 CFM–20-in. round or 141⁄2 x 191⁄2-in. rectangle. c. For 1600 CFM–22-in. round or 141⁄2 x 231⁄4-in. rectangle. d. For airflow requirements above 1800 CFM, use both side inlets, a combination of 1 side inlet and the bottom, or the bottom only.
E
16
5
TYP
8″
SIDE INLET
231⁄4″
SIDE RETURN
DUCT LOCATION
Fig. 1—Dimensional Drawing
Table 2—Dimensions (In.)
UNIT SIZE A D E VENT CONN SHIP. WT (LB)
045-08 14-3/16 12-9/16 12-11/16 4 122
045-12 14-3/16 12-9/16 12-11/16 4 124
070-08 14-3/16 12-9/16 12-11/16 4 132
070-12 14-3/16 12-9/16 12-11/16 4 134
091-14 17-1/2 15-7/8 16 4 150
091-16 21 19-3/8 19-1/2 4 154
111-12 17-1/2 15-7/8 16 4 160
111-16 21 19-3/8 19-1/2 4 166
111-20 24-1/2 22-7/8 23 4 184
136-16 21 19-3/8 19-1/2 5 178
136-20 24-1/2 22-7/8 23 5 194
155-20 24-1/2 22-7/8 23 5 204
141⁄2
3
4
1
1
A88367
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
PROCEDURE
Electrostatic discharge can affect electronic components. Take precautions during furnace installation and servicing to protect the furnace electronic control. Precautions will pre­vent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same electrostatic potential.
1. Disconnect all power to the furnace. DO NOT TOUCH THE
CONTROL OR ANY WIRE CONNECTED TO THE CON­TROL PRIOR TO DISCHARGING YOUR BODY’S ELEC­TROSTATIC CHARGE TO GROUND.
2. Firmly touch a clean, unpainted, metal surface of the furnace chassis which is close to the control. Tools held in a person’s hand during grounding will be satisfactorily discharged.
3. After touching the chassis you may proceed to service the control or connecting wires as long as you do nothing that recharges your body with static electricity (for example; DO NOT move or shuffle your feet, DO NOT touch ungrounded objects, etc.).
4. If you touch ungrounded objects (recharge your body with static electricity), firmly touch furnace again before touching control or wires.
5. Use this procedure for installed and uninstalled (ungrounded) furnaces.
6. Before removing a new control from its container, discharge your body’s electrostatic charge to ground to protect the
2
control from damage. If the control is to be installed in a
furnace, follow items 1 through 5 before bringing the control or yourself into contact with the furnace. Put all used AND new controls into containers before touching ungrounded objects.
7. An ESD service kit (available from commercial sources) may also be used to prevent ESD damage.
The Model 58WAV, Series 141 Furnace is available in sizes 45,000 through 155,000 Btuh input capacities.
The design of the upflow gas-fired furnace is A.G.A./C.G.A. certified for natural and propane gas and for installation on combustible flooring, in alcoves, attics, basements, closets, or utility rooms. The design of this furnace line is not A.G.A./C.G.A. certified for installation in mobile homes, recreation vehicles, or outdoors. Before installing the furnace, refer to the current edition of the
NFGC and the NFPA 90B. Canadian installations must be installed in accordance with NSCNGPIC and all authorities having juris­diction. For further information, the NFGC and the NFPA 90B are available from National Fire Protection Association Inc., Battery­march Park, Quincy, MA 02269; American Gas Association, 1515 Wilson Boulevard, Arlington, VA 22209; or from Literature Distribution.
Installation must conform to the regulations of the serving gas supplier and the local building, heating, and plumbing codes in effect in the area in which the installation is made, or in the absence of local codes with the requirements of the NFGC.
Application of this furnace should be indoors with special attention given to vent sizing and material, gas input rate, air temperature rise, and unit sizing. Improper installation or misapplication of the furnace can require excessive servicing or cause premature component failure.
This furnace is designed for a minimum continuous return-air temperature of 60°F db or an intermittent operation down to 55°F db such as when used with a night setback thermostat. Return-air temperature must not exceed a maximum of 85°F db.
Improper installation, adjustment, alteration, service, mainte­nance, or use can cause carbon monoxide poisoning, explo­sion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, local gas supplier, or your distribu­tor or branch for information or assistance. The qualified installer or agency must use only factory-authorized and listed kits or accessories when modifying this product. Failure to follow this warning can cause electrical shock, fire, personal injury, or death.
For accessory installation details, refer to the applicable instruction literature. NOTE: Remove all shipping brackets and materials before operating the furnace.
Step 1—Location
GENERAL
INTRODUCTION
Do not use this furnace during construction when adhesives, sealers, and/or new carpets are being installed. If the furnace is required during construction, use clean outside air for combustion and ventilation. Compounds of chlorine and fluorine when burned with combustion air form acids which cause corrosion of the heat exchangers and metal vent system. Some of these compounds are found in paneling and dry wall adhesives, paints, thinners, masonry cleaning materials, and many other solvents commonly used in the construction process. Excessive exposure to contaminated combustion air will result in safety and performance related problems.
This furnace must be installed so the electrical components are protected from water. This furnace shall not be installed directly on carpeting, tile, or any combustible material other than wood flooring.
Locate furnace as close to the chimney/vent and as near the center of the air distribution system as possible. The furnace should be installed as level as possible.
When a furnace is installed so that the supply ducts carry air to areas outside the space containing the furnace, the return air must also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
Provide ample space for servicing and cleaning. Always comply with the minimum fire protection clearances shown on the unit rating plate.
LOCATION RELATIVE TO COOLING EQUIPMENT — The cooling coil must be installed parallel with or on the downstream side of the unit to avoid condensation in the heat exchangers. When installed parallel with a furnace, dampers or other means used to control the flow of air must prevent chilled air from entering the unit. If the dampers are manually operated, they must be equipped with means to prevent operation of either unit unless the damper is in the full-heat or full-cool position.
HAZARDOUS LOCATIONS — When the furnace is installed in a residential garage, it must be installed so that the burners and ignition source are located at least 18 in. above the floor. The furnace should be protected from physical damage by vehicles. When a furnace is installed in public garages, airplane hangars, or other buildings having hazardous atmospheres, the unit must be installed in accordance with the recommended good practice requirements of the National Fire Protection Association, Inc.
Step 2—Air For Combustion and Ventilation
Provisions for adequate combustion and ventilation air must be provided in accordance with Section 5.3 of the NFGC, Air for Combustion and Ventilation, or applicable provisions of the local building codes.
Canadian installations must be installed in accordance with NSC­NGPIC and all authorities having jurisdiction.
Do not install furnace in a corrosive or contaminated atmo­sphere. Make sure all combustion and circulating air require­ments are met, in addition to all local codes and ordinances.
3
Air for combustion must not be contaminated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements are found in aerosol sprays, deter­gents, bleaches, cleaning solvents, salts, air fresheners, and other household products.
All fuel-burning equipment must be supplied with air for combus­tion of the fuel. Sufficient air MUST be provided to ensure there will not be a negative pressure in the equipment room or space. In addition, a positive seal MUST be made between the furnace cabinet and the return-air duct to prevent pulling air from the burner area and draft safeguard opening.
The operation of exhaust fans, kitchen ventilation fans, clothes dryers, or fireplaces could create a NEGATIVE PRESSURE CONDITION at the furnace. Make-up air MUST BE PROVIDED for the ventilation devices, in addition to that required by the furnace.
The requirements for combustion and ventilation air depend upon whether the furnace is located in an unconfined or confined space.
UNCONFINED SPACE — An unconfined space must have at least 50 cubic ft for each 1000 Btuh of input for all the appliances (such as furnaces, clothes dryer, water heaters, etc.) in the space.
For Example:
58WAV FURNACE
INPUT BTUH
44,000 293 66,000 440
88,000 587 110,000 733 132,000 880 154,000 1026
MINIMUM SQ FT WITH
7-1/2 FT CEILING
If the unconfined space is constructed unusually tight, air for combustion and ventilation MUST come from either the outdoors or spaces freely communicating with the outdoors. Combustion and ventilation openings must be sized the same as for a confined space. A minimum opening with a total of at least 1 sq in. per 5000 Btuh of total input rating for all equipment must be provided. Return air must not be taken from the room unless an equal or greater amount of air is supplied to the room.
CONFINED SPACE — A confined space has volume less than 50 cu ft per 1000 Btuh of the total input rating for all appliances installed in that space. A confined space MUST have 2 permanent openings, 1 within 12 in. of the ceiling and the other within 12 in. of the floor. (See Fig. 2.)
NOTE: In determining the free area of an opening, the blocking effect of the louvers, grilles, and screens must be considered. If the free area of a louver or grille design is unknown, it may be assumed that wood louvers have a 20 percent free area, and metal louvers or grilles have a 60 percent free area. Screens, when used, must not be smaller than 1/4-in. mesh. Louvers and grilles must be constructed so they cannot be closed.
The size of the openings depends upon whether the air comes from inside or outside of the structure.
1. All air from inside the structure:
a. Each opening MUST have at least 1 sq in. of free area per
1000 Btuh of the total input for all equipment within the confined space, but not less than 100 sq in. per opening. (See Fig. 2.)
INTERIOR
HEATED
SPACE
RETURN AIR
* Minimum opening size is 100 square in. with minimum dimensions of 3-In.
Minimum of 3-In. when type-B1 vent is used.
Fig. 2—Air For Combustion and Ventilation
For Example:
58WAV FURNACE
INPUT BTUH
44,000 100 66,000 100
88,000 100 110,000 110 132,000 132 154,000 154
b. If the building is constructed unusually tight, in addition to
the 2 permanent openings that freely communicate with an unconfined space, a permanent opening directly communi­cating with the outdoors should be provided. This opening shall have a minimum free area of 1 sq in. per 5000 Btuh of total input rating for all equipment in the enclosure.
c. If the furnace is installed on a raised platform to provide a
return-air plenum, and return air is taken directly from the hallway or space adjacent to the furnace, all air for combustion must come from outdoors.
2. All air from outside the structure:
a. If combustion air is taken from outdoors through vertical
ducts, the openings and ducts MUST have at least 1 sq in. of free area per 4000 Btuh of the total input for all equipment within the confined space. (See Fig. 3.)
b. If combustion air is taken from the outdoors through
horizontal ducts, the openings and ducts MUST have at least 1 sq in. of free area per 2000 Btuh of the total input for all equipment within the confined space.
4
SUPPLY
AIR
VENT THROUGH ROOF
CONFINED
(Inside Air)
FREE AREA PER OPENING
(SQ IN.)
12 MAX
1 SQ IN. PER 1000 BTUH* IN DOOR OR WALL
UNCONFINED SPACE
SPACE
6 MIN (FRONT)
1 SQ IN. PER 1000 BTUH* IN DOOR OR WALL
12 MAX
A89012
For Example:
FILTER RETAINER
WASHABLE
FILTER
58WAV FURNACE
INPUT BTUH
44,000 11.0 4 66,000 16.5 5
88,000 22.0 6 110,000 27.5 6 132,000 33.0 7 154,000 38.5 7
FREE AREA PER OPENING
(SQ IN.)
ROUND PIPE
(IN. DIA)
For Example:
58WAV FURNACE
INPUT BTUH
44,000 22.0 6
66,000 33.0 7
88,000 44.0 8 110,000 55.0 9 132,000 66.0 10 154,000 77.0 10
FREE AREA PER OPENING
(SQ IN.)
ROUND PIPE
(IN. DIA)
c. When ducts are used, they must be of the same cross-
sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular ducts must not be less than 3 in. (See Fig. 3.)
Do not install the furnace on its back; safety control operation will be adversely affected. Never connect return-air ducts to the back of the furnace. A failure to follow this warning can cause a fire, personal injury, or death.
Step 3—Filter Arrangement
The factory-supplied filter(s) is shipped in the blower compart­ment. Determine location for the filter and relocate filter retaining wire if necessary. See Fig. 4 for side return application and Fig. 5 for bottom return application. See Table 3 to determine correct filter size for desired filter location. Table 3 indicates filter size, location, and quantity shipped with the furnace.
1 SQ IN.
SPACE
E
12 MAX
PER 4000 BTUH*
1 SQ IN. PER 4000 BTUH*
DUCTS
A
B
TO
SUPPLY
AIR
OUTDOORS
12 MAX
1 SQ IN. PER 2000 BTUH*
DUCTS
TO
OUTDOORS
1 SQ IN. PER 2000 BTUH*
12
MAX
RETURN AIR
*Minimum dimensions of 3-In.
NOTE:
Use any of the following combinations of openings: A & B C & D D & E F & G
D
VENT THROUGH ROOF
C
DUCT
TO
OUTDOORS
CONFINED
Fig. 3—Air For Combustion and Ventilation
(Outside Air)
F
G
12 MAX
1 SQ IN.
PER
4000
BTUH*
OUTDOORS
1 SQ IN.
PER 4000
BTUH*
12 MAX
A89013
A93045
Fig. 4—Side Filter Arrangement
(Control Removed for Clarity)
For bottom air-return applications, filter may need to be cut to fit some furnace casing widths. A bottom closure panel is factory installed in the bottom of the furnace. When bottom return inlet is desired, remove and discard the bottom closure panel. Two sets of hardware are needed for furnaces in 24-1/2-in. wide casings using 2 filters for bottom return. All hardware is provided for filter installation.
NOTE: Furnaces with a 17-1/2-in. wide casing require an addi­tional procedure when locating the filter for bottom return-air application. Field fabricate a sheet metal filler strip1X3X24-1/2 in. and install it along side of the filter as shown in Fig. 5. Drive 2 screws through the casing side and into the filler strip to secure it in place. Filter should rest on the top of the filler strip when installed.
Never operate unit without a filter or with filter access door removed. Failure to follow this warning can cause fire, personal injury, or death.
Step 4—Leveling Legs (If Required)
When the furnace is used with side inlet(s) and leveling legs are required, refer to Fig. 6, and install field-supplied, corrosion­resistant 5/16-in. machine bolts and nuts.
NOTE: The maximum length of the bolt should not exceed 1-1/2 in.
1. Lay furnace on its back. Locate and drill 5/16-in. diameter hole in each bottom corner of furnace as shown in Fig. 6.
2. Install nut on bolt and install bolt and nut in hole. (Install flat washer if desired.)
3. Install another nut on other side of furnace base. (Install flat washer if desired.)
5
171⁄2-IN. WIDE  CASINGS ONLY:
INSTALL FIELD-SUPPLIED FILTER FILLER STRIP UNDER FILTER.
3
1
24
/2″
1
241⁄2-IN. WIDE  CASINGS ONLY:
CUT AND FOLD FACTORY-PROVIDED FILTERS AS SHOWN TO DESIRED SIZE.
5
16
5
16
1 3⁄4
1 3⁄4
5
16
5
16
1 3⁄4
1 3⁄4
Fig. 6—Leveling Leg Installation
A89014
WASHABLE FILTER
FILTER SUPPORT
FILTER RETAINER
A96030
Fig. 5—Bottom Filter Arrangement
(Control Removed for Clarity)
Table 3—Filter Information (In.)
FURNACE
CASING WIDTH
14-3/16 (1) 16 X 25 X 1† (1) 14 X 25 X 1 Cleanable
17-1/2 (1) 16 X 25 X 1† (1) 16 X 25 X 1 Cleanable
21 (1) 16 X 25 X 1 (1) 20 X 25 X 1† Cleanable
24-1/2 (2) 16 X 25 X 1† (1) 24 X 25 X 1 Cleanable
* Filters can be field modified by cutting the frame as marked and folding to the desired size. Alternate sizes can be ordered from your distributor or dealer. † Factory provided with the furnace.
4. Adjust outside nut to provide desired height, and tighten inside nut to secure arrangement.
Step 5—Gas Piping
Gas piping must be installed in accordance with national and local codes. Refer to the current edition of the NFGC. Canadian installations must be installed in accordance with NSCNGPIC and all authorities having jurisdiction.
Refer to Table 4 for the recommended gas pipe size. Risers must be used to connect to the furnace and the meter.
FILTER SIZE*
Side Return Bottom Return
FILTER
TYPE
If a flexible connector is required or allowed by the authority having jurisdiction, black iron pipe shall be installed at the gas valve and extend a minimum of 2 in. outside the furnace casing.
Table 4—Maximum Capacity of Pipe*
NOMINAL IRON
PIPE SIZE
(IN.)
1/2 0.622 175 120 97 82 73 3/4 0.824 360 250 200 170 151
1 1.049 680 465 375 320 285 1-1/4 1.380 1400 950 770 660 580 1-1/2 1.610 2100 1460 1180 990 900
* Cubic ft of gas per hr for gas pressures of 0.5 psig (14-in. wc) or less, and a pressure drop of 0.5-in. wc (based on a 0.60 specific gravity gas). Ref: Table 10-2 NFPA 54-1992.
Piping should be pressure tested in accordance with local and national plumbing and gas codes before the furnace has been attached. If the pressure exceeds 0.5 psig (14-in. wc), the gas supply pipe must be disconnected from the furnace and capped before the pressure test. If the test pressure is equal to or less than
0.5 psig (14-in. wc), turn off electric shutoff switch located on the gas valve before the test. It is recommended that the ground joint union be loosened before pressure testing. After all connections have been made, purge the lines and check for leakage with regulated gas supply pressure.
Install a sediment trap in the riser leading to the furnace. The trap can be installed by connecting a tee to the riser leading from the furnace. Connect a capped nipple into the lower end of the tee. The capped nipple should extend below the level of the gas controls. (See Fig. 7.)
Apply joint compound (pipe dope) sparingly and only to the male threads of each joint. The compound must be resistant to the action of propane gas.
INTERNAL
DIAMETER
(IN.)
LENGTH OF PIPE (FT)
10 20 30 40 50
6
GAS
SUPPLY
MANUAL SHUTOFF VALVE (REQUIRED)
SEDIMENT TRAP
UNION
A89417
Fig. 7—Typical Gas Pipe Arrangement
An accessible manual shutoff valve MUST be installed upstream of the furnace gas controls and within 72 in. of the furnace. A 1/8-in. NPT plugged tapping, accessible for test gage connection, MUST be installed immediately upstream of the gas supply connection to the furnace and downstream of the manual shutoff valve. Place ground joint union between the gas control manifold and the manual shutoff valve.
Use the proper length of pipes to avoid stress on the gas control manifold. Failure to follow this warning can result in a gas leak, causing fire, explosion, personal injury, or death.
Connect the gas pipe to the furnace using a backup wrench to avoid damaging gas controls.
Never purge a line into a combustion chamber. Never use matches, candles, flame, or other sources of ignition for the purpose of checking leakage. Use a soap-and-water solution to check for leakage. Failure to follow this warning can cause a fire, explosion, personal injury, or death.
Step 6—Electrical Connections
115-V WIRING — Refer to the unit rating plate or Table 5 for equipment electrical requirements. The control system requires an earth ground for proper operation.
Do not connect aluminum wire between disconnect switch and furnace. Use only copper wire.
trical connections must be made in accordance with CSA C22.1 Canadian Electrical Code, or authorities having jurisdiction.
The cabinet MUST have an uninterrupted or unbroken ground according to NEC, ANSI/NFPA 70-1996 and Canadian Electrical Code, CSA C22.1 or local codes to minimize personal injury if an electrical fault should occur. This may consist of electrical wire or conduit approved for electrical ground when installed in accordance with existing electrical codes. Do not use gas piping as an electrical ground. Failure to follow this warning could result in electrical shock, fire, or death.
The auxiliary junction box (J-box) can be moved to the left-hand side of the furnace when a left-side power supply is desired. Remove the 2 screws holding the auxiliary J-box. Mount the J-box on the left-hand side of the furnace (holes have been pre-drilled in casing). When moved, tuck the wiring harness behind the clip provided to keep extra wire lengths out of the way.
NOTE: Proper polarity must be maintained for 115-v wiring. If polarity is incorrect, control board fault code indicator light will flash rapidly and the furnace will not operate.
24-V WIRING
Make field 24-v connections at the 24-v terminal strip. (See Fig.
9.) Connect terminal Y as shown in Fig. 8 for proper cooling operation. Use only AWG No. 18, color-coded, copper thermostat wire.
The 24-v circuit contains an automotive-type, 3-amp fuse located on the main control board. Any direct shorts during installation, service, or maintenance could cause this fuse to blow. If fuse replacement is required, use ONLY a 3-amp fuse of identical size.
ACCESSORIES
1. Electronic Air Cleaner (EAC)
Two spring clamp terminals (for 12 gage maximum, solid or stranded wire), marked EAC-1 and EAC-2 are provided for EAC connection. (See Fig. 9.) These terminals are energized with 115-v, (1-amp maximum) during blower motor opera­tion. To connect EAC power leads to furnace control center, strip approximately 1/8 in. of insulation from wire. Open terminal by depressing switch arm with a screwdriver or finger, and insert wire as shown in Fig. 10.
2. Humidifier (HUM)
Screw terminals (HUM and Com) are provided for 24-v humidifier connection. The terminals are energized with 24-v
0.5-amp maximum after inducer motor prepurge period.
NOTE: A field-supplied, 115-v controlled relay connected to EAC terminals may be added if humidifier operation is desired during blower operation.
Step 7—Venting
Refer to the National or Local Installation Code such as; National Fuel Gas Code Z223.1-1992, or the Canadian Installation Code, CAN B149.1- and .2-M95, for proper vent sizing and installation requirements. Use the enclosed Venting Tables for Category I Fan-Assisted Furnaces for a quick, easy reference. The horizontal portion of the venting system shall maintain a minimum of 1/4-in. upward slope per linear ft and it shall be rigidly supported every 5 ft or less with hangers or straps to ensure that there will be no movement after installation.
Make all electrical connections in accordance with the National Electrical Code (NEC) ANSI/NFPA 70-1996 and local codes or ordinances that might apply. For Canadian installations, all elec-
7
BLK
WHT
115-VOLT FIELD-
SUPPLIED
FUSED
DISCONNECT
BLK
WHT
GND
FIELD 24-VOLT WIRING FIELD 115-, 208/230-, 460-VOLT WIRING FACTORY 24-VOLT WIRING FACTORY 115-VOLT WIRING
FIVE
WIRE
THREE-WIRE
HEATING-
ONLY
GND
AUXILIARY J-BOX
CONTROL
BOX
FURNACE
NOTE 2
24-VOLT
TERMINAL
BLOCK
WCR GY
W
R
G
C
Y
NOTE 1
NOTES: Connect Y-terminal as shown for proper operation.
THERMOSTAT TERMINALS
CONDENSING UNIT
TWO WIRE
1.
2.
3.
Some thermostats require a "C" terminal connection as shown. If any of the original wire, as supplied, must be replaced, use same type or equivalent wire.
Fig. 8—Heating and Cooling Application Wiring Diagram
FIELD-SUPPLIED FUSED DISCONNECT
208/230- OR 460-VOLT THREE PHASE
208/230- VOLT SINGLE
GND
PHASE
A95241
Table 5—Electrical Data
UNIT SIZE
HERTZ—
PHASE
045-08 115—60—1 127 104 6.0 14 47 15 045-12 115—60—1 127 104 8.3 14 34 15 070-08 115—60—1 127 104 5.9 14 47 15 070-12 115—60—1 127 104 8.7 14 32 15 091-14 115—60—1 127 104 9.0 14 31 15 091-16 115—60—1 127 104 10.4 14 27 15 111-12 115—60—1 127 104 8.0 14 35 15 111-16 115—60—1 127 104 10.1 14 28 15 111-20 115—60—1 127 104 14.4 12 31 20 136-16 115—60—1 127 104 10.1 14 28 15 136-20 115—60—1 127 104 13.3 12 33 20 155-20 115—60—1 127 104 14.0 12 31 20
VOLTS—
* Permissible limits of the voltage range at which the unit operates satisfactorily. † Time-delay fuse is recommended. ‡ Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.
Step 8—Start-Up, Adjustment, and Safety Check
GENERAL NOTE: Proper polarity must be maintained for 115-v wiring. If
polarity is incorrect, control board fault indicator light will flash rapidly and furnace will not operate.
The furnace must have a 115-v power supply properly connected and grounded. Proper polarity must be maintained for correct operation. Thermostat wire connections at R, W, C, and Y must be made at the 24-v terminal block on the control board. The gas service pressure must not exceed 0.5 psig (14-in. wc), but must be no less than 0.16 psig (4.5-in. wc).
OPERATING
VOLTAGE RANGE
Maximum* Minimum*
MAXIMUM
UNIT AMPS
MINIMUM
WIRE GAGE
MAXIMUM
WIRE LENGTH (FT)‡
This furnace is equipped with a manual reset limit switch or fuse link in the gas control area. The switch or fuse link opens and shuts off power to the gas valve if a flame rollout or overheating condition occurs in the gas control area. DO NOT bypass the switch. Correct inadequate combustion air supply problem and reset the switch or replace the fuse link.
Before operating the furnace, check each manual reset switch for continuity. If necessary, press the button to reset the switch.
The blower compartment door must be in place to complete the 115-v circuit to the furnace.
MAXIMUM
FUSE OR
HACR-TYPE CKT
BKR AMPS†
8
BLOWER OFF DELAY ADJUSTMENT SWITCH
115-VAC (L1)
POWER
SUPPLY
HOT SURFACE
CONNECTOR
TEST/TWIN
SEC-1
3-AMP FUSE
COOL
HEAT
IGNITOR
G
R
Y
W
Com
24V 
HUM
115-VAC (L2) NEUTRAL CONNECTION
INDUCER MOTOR CONNECTOR
24V THERMOSTAT
TERMINALS
HUMIDIFIER TERMINAL
(24-VAC 0.5 AMP MAX)
LED OPERATION &
DIAGNOSTIC LIGHT
HARNESS CONNECTOR
24V TRANSFORMER SEC-2
SPARE 1
BLOWER SPEED
SELECTION TERMINALS
SPARE 2
EAC 1 (BLACK)
EAC-ELECTRONIC AIR CLEANER
TERMINALS (115-VAC 1.5 AMP MAX)
EAC 2 (WHITE)
Fig. 9—Control Board
A93052
EAC1
EAC2
A93053
Fig. 10—EAC Terminals on Control Board
SEQUENCE OF OPERATION
Furnace control must be grounded for proper operation, or control will lockout. Control is grounded through green wire routed to gas valve and burner bracket screw.
Using the schematic diagram shown in Fig. 11, follow the sequence of operation through the different modes. Read and follow the wiring diagram very carefully.
NOTE: If there is a power interruption and any thermostat call, the control initiates a 90-sec blower only on period before starting another cycle.
1. Heating mode
When the wall thermostat "calls for heat," the R-W circuit closes. The furnace control performs a self-check, verifies the pressure switch contacts are open, and starts inducer motor.
a. Prepurge period—As the inducer motor comes up to speed,
the pressure switch contacts close to begin a 15-sec prepurge period.
b. Ignitor warm-up—At the end of the prepurge period, the
ignitor is energized for a 17-sec ignitor warm-up period.
c. Ignition sequence—When the ignitor warm-up period is
completed, the gas valve opens, permitting gas flow to the burners where it is ignited. After 5 sec, the ignitor is de-energized and a 2-sec flame-sensing period begins.
d. HUM terminal is energized with the gas valve. See
accessories in the Electrical Connections section.
e. Flame-sensing—When burner flame is sensed, the control
begins the blower on delay period and continues holding the gas valve open. If burner flame is not sensed, the control closes the gas valve and repeats ignition cycle.
NOTE: Ignition sequence will repeat 3 additional time before a lockout occurs. Lockout automatically resets after 3 hrs, or can be manually reset by turning 115v off (not at thermostat) for 3 sec minimum, then on again.
f. Blower on delay—Forty sec after burner flame is proven,
the blower motor is energized on heating speed. Simulta­neously, the humidifier and electronic air cleaner terminals (HUM and Com for humidifier, EAC-1 and EAC-2 for electronic air cleaner) are energized. If jumper is on pin 6 and pin 9, blower on delay is 60 sec.
9
L2
CAP
BLWM
START
SCHEMATIC DIAGRAM
(NATURAL GAS & PROPANE)
NOTE #4
EQUIPMENT GROUND
OL
LO
HI
MED LO
MED HI
COM
NOTE #8
COM
HEAT
COOL
SPARE-1
SPARE-2
HI/LO
IDM
HSI
1
2
1
PR2
PL52
1
PL2
115VAC
EAC-2
EAC-1
PR1
NOT USED
PL3
2
3
24VAC
TRAN
TO 115VAC FIELD DISCONNECT
NEUTRAL
L1
PRS
ALS
NOTE #12
(WHEN USED)
DSS
ORN
GRY
W
SW1
SW2
OFF
DELAY
BLOWER
NOTE #9
(NOT ON ALL MODELS)
PCB
ILK
OM
C
YEL
HUM
TEST/TWIN
SELECTION CHART
BLOWER OFF DELAY
BLU
LED
90 SEC
BLWR
L1
FRS1 FRS2
RED
135 SEC
3-P
1-M
1
2
3
PL1
180 SEC
GV
FL
LS
WHT
4
(WHEN USED)
FSE
5 6
225 SEC
HSIR
87 9
IDR
NOTE #5
2-C
GRN
RED
SEC-2
SEC-1
GRN
CAP
WHT (COM)
WHT
BLK
BRN
TRAN
START
RED
BLU
HI/LO
OL
NOTE #8
BLK (HI)
YEL (MED HI)
SPARE-1
FUSE
24 VAC-3A
COOL
FU1
SPEED
SELECT
BLOWER
RELAY
GVR
HSIR IDR BLWR
NOTE #6
FU1
TEST/TWIN
FL
PRS
NOTE #11
ALS
LS
FRS1 FRS2
(WHEN USED
1
7
SEC-2
SEC-1
GVR-2
HUM
NOTE #12
BRN
BLWM
RED (LO)
BLU (MED LO)
1.5 AMP
SPARE-2
EAC-1
EAC-2
HEAT
OM
L2
PR2
C
123
PL3
2
1
PL2
PR1
VAC
L1
120
PL1
4
GVR
HI/LO
BLWR
IDR
HSIR
R
W
NOTE #4
FUSED DISCONNECT
SWITCH (WHEN REQ’D)
JB
BLK
ILK
WHT
WHT (COM)
WHT
PL5
WHT
BLK
BLK
BLK
(WHEN USED)
DSS
3
L1
FU2
BLK
IDM
WHT
12
3-P
GV
NEUTRAL
WHT
BLK
HSI
2-C
2
GVR-1
CPU
GRN
GRN
1-M
8
Y
NOTE #5
FSE
6
5
G
PCB PRINTED CIRCUI T BOARD
PL1 9-CIRCUIT CONNECTOR
PL2 2-CIRCUIT PCB CONNECTOR
ALS AUXILIARY LIMIT SWITCH, OVERTEMP. -MANUAL RESET, SPST-(N.C.)
BLWR BLOWER MOTOR RELAY, SPST-(N.O.)
LEGEND
BLWM BLOWER MOTOR
A95335
322869-101 REV. C
NOT USED
NOT USED
9
OM
C
NOTES:
optimum speed selection.
4. Use only copper wire between the disconnect switch and the furnace junction box (JB).
5. This wire must be connected to furnace sheetmetal for control to detect flame.
6. Replace only with a 3 amp fuse.
1. If any of the original equipment wire is replaced use wire rated for 105°C.
2. Inducer (IDM) and blower (BLWM) motors contain internal auto-reset thermal overload switches (OL).
3. Blower motor speed selections are for average conditions, see installation instructions for details on
JUNCTION
7. Yellow lead not on all motors.
UNMARKED TERMINAL
PCB TERMINAL
FACTORY WIRING (115VAC)
FACTORY WIRING (24VAC)
FIELD WIRING (115VAC)
after three hours.
models only.
(135 seconds only on some models)
11. When used auxiliary limit switch (ALS) is on downflow models only. When used FL is on upflow
8. Blower-on delay, gas heating 45 seconds, cooling or heat pump 2 seconds.
9. Blower-off delay, gas heating 90, 135, 180 or 225 seconds, cooling or heat pump 90 seconds.
FIELD WIRING (24VAC)
CONDUCTOR ON PCB
FIELD WIRING TERMINAL
12. Some models may have spade quick connect terminals.
10. Ignition-lockout will occur after four consecutive unsuccessful trials-for-ignition. Control will auto-reset
FIELD GROUND
EQUIPMENT GROUND
FIELD SPLICE
PLUG RECEPTACLE
Fig. 11—Unit Wiring Diagram
PL3 3-CIRCUIT IDM CONNECTOR
PL5 2-CIRCUIT HSI/PCB CONNECTOR
PRS PRESSURE SWITCH, SPST-(N.O.)
TEST/TWIN COMPONENT TEST & TWIN TERMINAL
TRAN TRANSFORMER-115VAC/24VAC
(FIELD INSTALLED & SUPPLIED)
CAP CAPACITOR
CPU M ICROPROCESSOR AND CIRCUITRY
DSS DRAFT SAFEGUARD SWITCH
EAC-1 ELECTRONIC AIR CLEANE R CONNECTION (115 VAC 1.5 AMP MAX.)
EAC-2 ELECTRONIC AIR CLEA NER CONNECTION (COMMON)
FL FUSIBLE LINK
FRS FLAME ROLLOU T SW. -MANUAL RESET, SPST-(N.C.)
FSE FLAME PROVING ELECTRODE
FU1 FUSE, 3 AMP, AUTOMOTIVE BLADE TYPE, FACTORY INSTALLED
FU2 FUSE OR CIRCUIT BREAKER CURRENT INTERRUPT DEVICE
GV GAS VALVE-REDUNDANT OPERATORS
GVR GAS VALVE RELAY, DP ST-(N.O.)
HI/LO BLOWER MOTOR SPEED CHANGE RELAY, SPDT
HSI HOT SURFACE IGNITOR (115 VAC)
HSIR HOT SU RFACE IGNITOR RELAY, SPST-(N.O.)
HUM 24VAC HUMIDIFIER CONNECTION (.5 AMP. MAX.)
IDM INDUCED DRA FT MOTOR
IDR INDUCED DRAFT RELAY, SPST-(N.O.)
ILK BLOWER ACCESS PANEL INTERLOCK SWITCH, SPST-(N.O.)
JB JUNCTION BOX
LED LIGHT-EMITTING DIODE FOR STATUS CODES
LGPS LOW GAS PRESSURE SWITCH, SPST-(N.O.)
LS LIMIT SWITCH, AUTO RESET, SPST(N.C.)
OL AUTO-RESE T INTERNAL MOTOR OVERLOAD TEMP. SW.
10
g. Blower off delay—When the thermostat is satisfied, the
circuit between R-W is broken, de-energizing the gas valve stopping gas flow to the burners. The blower motor and EAC remain energized 90, 135, 180, or 225 sec (depending on the blower off-time selection). The furnace is factory set for a 135-sec blower off delay.
h. Post-purge—The inducer motor remains energized 5 sec
after the burners are extinguished. If jumper is on pin 6 and pin 9, the post-purge period is 15 sec.
2. Cooling mode
When the thermostat "calls for cooling," R-G and R-Y circuits close. The R-Y circuit starts the outdoor condensing unit and the combined R-Y and R-G circuits start the furnace blower motor on cooling speed. The EAC-1 terminal is energized with 115v when the blower is operating on cooling speed.
When the thermostat is satisfied, R-G and R-Y circuits are broken. The furnace blower and EAC continue operating on cooling speed for an additional 90 sec.
3. Continuous blower mode
NOTE: EAC-1 terminal is energized with 115v whenever blower operates.
When the R-G circuit is made, the blower motor operates on heating speed. During a call for heat, the blower stops, allowing the furnace heat exchangers to heat up more quickly, then restarts at the end of the 40-sec blower on delay period. If jumper is on pin 6 and pin 9, the blower on delay is 60 sec.
The blower reverts to continuous operation after the heating cycle is completed.
When the thermostat "calls for cooling," the blower operates on cooling speed. When the thermostat is satisfied, the blower operates an additional 90 sec before reverting back to con­tinuous operation on heating speed.
4. Heat pump mode
When installed with a heat pump, the furnace control auto­matically changes the timing sequence to avoid long blower off time during demand defrost cycles. When the W-Y or W-Y-G thermostat inputs are received at the same time, the control changes the blower to heating speed or starts the blower if it was off, and begins a heating cycle. The blower remains on until the end of the prepurge period, then shuts off until the end of the ignition warm-up and trial for ignition periods (a total of 24 sec). The blower then comes back on at heating speed.
When the W input signal disappears, the control begins the normal inducer post-purge period and the blower changes to cooling speed after a 1-sec delay. If the W-Y-G signals disappear at the same time, the blower remains on for the selected heating blower off delay period and the inducer goes through its normal post-purge period. If the W-Y inputs should disappear, leaving the G signal input, the control goes into continuous blower and the inducer remains on for the normal post-purge period.
Anytime the control senses false flame, the control locks out of the heating mode. This occurs because the control cannot sense the W input due to the false flame signal, and as a result, sees only the Y input and goes into cooling mode, blower off delay. All other control functions remain in standard format.
NOTE: EAC-1 terminal is energized whenever blower operates. HUM terminal is only energized when gas valve is energized
START-UP PROCEDURES
1. Purge gas lines—After all connections have been made, purge the lines and check for leaks.
Never purge a line into a combustion chamber. Never use matches, candles, flame, or other sources of ignition for the purpose of checking leakage. Use a soap-and-water solution to check for leakage. Failure to follow this warning can cause fire, explosion, personal injury, or death.
2. Component test—The furnace control board allows all com­ponents, except gas valve, to be run for a short period of time.
This feature helps diagnose a system problem in case of a component failure. To initiate component test procedure, short (jumper) the TEST 1/4-in. quick connect terminal on control board (adjacent to diagnostic light) and the Com terminal on thermostat connection block for approximately 2 sec. (See Fig.
9.)
NOTE: Component test feature will not operate if any thermostat signal is present at control board.
Component test sequence is as follows.
a. Momentarily jumper TEST and Com terminals until LED
goes off.
b. LED will display previous fault 4 times.
c. Inducer motor starts and continues to run for entire com-
ponent test.
d. Hot surface ignitor is energized for 15 sec, then de-
energized.
e. Blower motor operates on cooling speed for 10 sec, then
stops.
f. Blower motor operates on heating speed for 10 sec, then
stops.
g. Inducer motor stops.
3. To operate furnace, follow procedures on operating instruc­tions label attached to furnace.
4. With furnace operating, set thermostat below room tempera­ture and observe that furnace goes off. Set thermostat above room temperature and observe that furnace restarts.
ADJUSTMENTS
1. Set gas input rate Furnace gas input rate on rating plate is for installations at altitudes up to 2000 ft. Furnace input rate must be within ±2 percent of input on furnace rating plate.
a. Determine natural gas orifice size and manifold pressure
for correct input.
(1.) Obtain average yearly heat value (at installed altitude)
from local gas supplier.
(2.) Obtain average yearly specific gravity from local gas
supplier.
(3.) Verify furnace model. Table 6 can only be used for
model 58WAV Furnaces.
(4.) Find installation altitude in Table 6.
NOTE: For Canada altitudes of 2000 to 4500 ft, use U.S.A. altitudes of 2001 to 3000 ft in Table 6.
(5.) Find closest natural gas heat value and specific gravity
in Table 6.
(6.) Follow heat value and specific gravity lines to point of
intersection to find orifice size and manifold pressure settings for proper operation.
11
Table 6—Model 58WAV Orifice Size and Manifold Pressure for Correct Input
(Tabulated Data Based on 22,000 Btuh per Burner, Derated 4% per 1000 Ft Above Sea Level)
ALTITUDE
RANGE
(FT)
0 925 43 3.7 42 3.2 42 3.3 42 3.4 42 3.5
to 975 43 3.4 43 3.5 43 3.6 43 3.7 43 3.8
2000 1025 44 3.5 43 3.2 43 3.3 43 3.4 43 3.5
U.S.A. and Canada
ALTITUDE
RANGE
(FT)
U.S.A. 775 42 3.4 42 3.5 42 3.6 42 3.7 42 3.8
Altitudes 800 43 3.8 42 3.3 42 3.4 42 3.5 42 3.6
2001 825 43 3.6 43 3.7 42 3.2 42 3.3 42 3.4
to 850 43 3.4 43 3.5 43 3.6 43 3.8 42 3.2
3000 875 43 3.2 43 3.3 43 3.4 43 3.5 43 3.6
or 900 43 3.0 43 3.1 43 3.2 43 3.3 43 3.4
Canada 925 43 2.9 43 3.0 43 3.1 43 3.2 43 3.3
Altitudes 950 43 2.7 43 2.8 43 2.9 43 3.0 43 3.1
U.S.A. and Canada
2000 975 43 2.6 43 2.7 43 2.8 43 2.9 43 2.9
to 1000 43 2.5 43 2.5 43 2.6 43 2.7 43 2.8
4500 1025 43 2.3 43 2.4 43 2.5 43 2.6 43 2.7
ALTITUDE
RANGE
(FT)
3001 825 43 3.2 43 3.3 43 3.4 43 3.5 43 3.6
to 875 43 2.8 43 2.9 43 3.0 43 3.1 43 3.2
U.S.A. Only
4000 925 43 2.5 43 2.6 43 2.7 43 2.8 43 2.9
ALTITUDE
RANGE
(FT)
4001 800 43 3.0 43 3.1 43 3.2 43 3.3 43 3.4
to 850 43 2.6 43 2.7 43 2.8 43 2.9 43 3.0
U.S.A. Only
5000 900 43 2.3 43 2.4 43 2.5 43 2.6 43 2.7
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
850 42 3.6 42 3.8 41 3.5 41 3.6 41 3.7 875 42 3.4 42 3.6 42 3.7 42 3.8 41 3.5 900 42 3.2 42 3.4 42 3.5 42 3.6 42 3.7
950 43 3.6 43 3.7 43 3.8 42 3.2 42 3.3
1000 43 3.2 43 3.3 43 3.4 43 3.5 43 3.6
1050 44 3.3 44 3.4 44 3.6 43 3.2 43 3.3 1075 45 3.8 44 3.3 44 3.4 44 3.5 43 3.2 1100 45 3.7 45 3.8 44 3.2 44 3.4 44 3.5
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
750 43 3.8 42 3.3 42 3.4 42 3.5 42 3.6 775 43 3.6 43 3.7 43 3.8 42 3.3 42 3.4 800 43 3.4 43 3.5 43 3.6 43 3.7 43 3.8
850 43 3.0 43 3.1 43 3.2 43 3.3 43 3.4
900 43 2.7 43 2.8 43 2.9 43 2.9 43 3.0
950 43 2.4 43 2.5 43 2.6 43 2.6 43 2.7 975 43 2.3 43 2.4 43 2.4 43 2.5 43 2.6
1000 43 2.2 43 2.2 43 2.3 43 2.4 43 2.5
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
725 43 3.6 43 3.7 42 3.2 42 3.3 42 3.4 750 43 3.4 43 3.5 43 3.6 43 3.7 43 3.8 775 43 3.2 43 3.3 43 3.4 43 3.5 43 3.6
825 43 2.8 43 2.9 43 3.0 43 3.1 43 3.2
875 43 2.5 43 2.6 43 2.6 43 2.7 43 2.8
925 43 2.2 43 2.3 43 2.4 43 2.4 43 2.5 950 43 2.1 43 2.2 43 2.2 43 2.3 43 2.4
0.58 0.60 0.62 0.64 0.66
Orifice
Orifice
Orifice
Orifice
Manifold
No.
Pressure
0.58 0.60 0.62 0.64 0.66 Manifold
No.
Pressure
0.58 0.60 0.62 0.64 0.66 Manifold
No.
Pressure
0.58 0.60 0.62 0.64 0.66 Manifold
No.
Pressure
Orifice
Orifice
Orifice
Orifice
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
No.
Pressure
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
No.
Pressure
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
No.
Pressure
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
No.
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
12
Table 6—Model 58WAV Orifice Size and Manifold Pressure for Correct Input Continued
(TABULATED DATA BASED ON 22,000 BTUH PER BURNER, DERATED 4% PER 1000 FT ABOVE SEA LEVEL)
ALTITUDE
RANGE
(FT)
5001 800 43 2.6 43 2.7 43 2.8 43 2.8 43 2.9
to 850 43 2.3 43 2.4 43 2.4 43 2.5 43 2.6
U.S.A. Only
6000 900 43 2.0 43 2.1 43 2.2 43 2.2 43 2.3
ALTITUDE
RANGE
(FT)
6001 725 43 2.7 43 2.8 43 2.9 43 3.0 43 3.1
to 775 43 2.4 43 2.5 43 2.5 43 2.6 43 2.7
U.S.A. Only
7000 825 43 2.1 43 2.2 43 2.2 43 2.3 43 2.4
ALTITUDE
RANGE
(FT)
7001 700 43 2.5 43 2.6 43 2.7 43 2.8 43 2.9
to 750 43 2.2 43 2.3 43 2.3 43 2.4 43 2.5
U.S.A. Only
8000 800 48 3.6 48 3.7 43 2.1 43 2.1 43 2.2
ALTITUDE
RANGE
(FT)
8001 650 43 2.5 43 2.6 43 2.7 43 2.8 43 2.8
to 700 43 2.2 43 2.2 43 2.3 43 2.4 43 2.4
U.S.A. Only
9000 750 48 3.5 48 3.6 43 2.0 43 2.1 43 2.1
AVG GAS HEAT VALUE AT ALTITUDE
(BTU/CU FT)
700 43 3.4 43 3.5 43 3.6 43 3.7 43 3.8 725 43 3.1 43 3.2 43 3.4 43 3.5 43 3.6 750 43 2.9 43 3.0 43 3.1 43 3.2 43 3.3 775 43 2.7 43 2.8 43 2.9 43 3.0 43 3.1
825 43 2.4 43 2.5 43 2.6 43 2.7 43 2.8
875 43 2.2 43 2.2 43 2.3 43 2.4 43 2.5
925 48 3.6 48 3.8 43 2.1 43 2.1 43 2.2 950 48 3.4 48 3.6 48 3.7 43 2.0 43 2.1 975 49 3.8 48 3.4 48 3.5 48 3.6 48 3.7
1000 49 3.6 49 3.8 48 3.3 48 3.4 48 3.5
AVG GAS HEAT VALUE AT ALTITUDE
(BTU/CU FT)
650 43 3.4 43 3.5 43 3.6 43 3.7 43 3.8 675 43 3.1 43 3.2 43 3.4 43 3.5 43 3.6 700 43 2.9 43 3.0 43 3.1 43 3.2 43 3.3
750 43 2.5 43 2.6 43 2.7 43 2.8 43 2.9
800 43 2.2 43 2.3 43 2.4 43 2.5 43 2.5
850 48 3.7 43 2.0 43 2.1 43 2.2 43 2.3 875 48 3.5 48 3.6 48 3.8 43 2.1 43 2.1
AVG GAS HEAT VALUE AT ALTITUDE
(BTU/CU FT)
625 43 3.1 43 3.3 43 3.4 43 3.5 43 3.6 650 43 2.9 43 3.0 43 3.1 43 3.2 43 3.3 675 43 2.7 43 2.8 43 2.9 43 3.0 43 3.1
725 43 2.3 43 2.4 43 2.5 43 2.6 43 2.7
775 43 2.0 43 2.1 43 2.2 43 2.3 43 2.3
825 48 3.4 48 3.5 48 3.6 48 3.8 43 2.1 850 49 3.8 48 3.3 48 3.4 48 3.5 48 3.6
AVG GAS HEAT VALUE AT ALTITUDE
(BTU/CU FT)
600 43 2.9 43 3.0 43 3.1 43 3.2 43 3.3 625 43 2.7 43 2.8 43 2.9 43 3.0 43 3.1
675 43 2.3 43 2.4 43 2.5 43 2.6 43 2.6
725 43 2.0 43 2.1 43 2.1 43 2.2 43 2.3
775 48 3.3 48 3.4 48 3.5 48 3.6 48 3.8 800 49 3.6 49 3.8 48 3.3 48 3.4 48 3.5
0.58 0.60 0.62 0.64 0.66
Orifice
Orifice
Orifice
Orifice
Manifold
No.
Pressure
0.58 0.60 0.62 0.64 0.66 Manifold
No.
Pressure
0.58 0.60 0.62 0.64 0.66 Manifold
No.
Pressure
0.58 0.60 0.62 0.64 0.66 Manifold
No.
Pressure
Orifice
Orifice
Orifice
Orifice
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
No.
Pressure
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
No.
Pressure
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
No.
Pressure
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
No.
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
13
Table 6—Model 58WAV Orifice Size and Manifold Pressure for Correct Input Continued
(TABULATED DATA BASED ON 22,000 BTUH PER BURNER, DERATED 4% PER 1000 FT ABOVE SEA LEVEL)
ALTITUDE
RANGE
(FT)
9001 625 43 2.3 43 2.4 43 2.4 43 2.5 43 2.6
to 675 48 3.7 43 2.0 43 2.1 43 2.2 43 2.2
U.S.A. Only
10,000 725 49 3.8 48 3.3 48 3.4 48 3.5 48 3.6
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
575 43 2.7 43 2.8 43 2.9 43 3.0 43 3.1 600 43 2.5 43 2.6 43 2.7 43 2.7 43 2.8
650 43 2.1 43 2.2 43 2.3 43 2.3 43 2.4
700 48 3.4 48 3.6 48 3.7 43 2.0 43 2.1
750 49 3.5 49 3.6 49 3.8 48 3.3 48 3.4 775 49 3.3 49 3.4 49 3.5 49 3.6 49 3.7
0.58 0.60 0.62 0.64 0.66
Orifice
No.
Manifold
Pressure
Orifice
SPECIFIC GRAVITY OF NATURAL GAS
No.
Manifold Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Table 7—Altitude Derate Multiplier for U.S.A.
EXAMPLE: (0—2000 ft altitude) Heating value = 1025 Btu/cu ft Specific gravity = 0.62 Therefore: Orifice No. 43*
Manifold pressure 3.3-in. wc * Furnace is shipped with No. 43 orifices. In this example all main burner orifices are the correct size and do not need to be changed to obtain proper input rate.
(7.) Check and verify burner orifice size in furnace.
NEVER ASSUME ORIFICE SIZE. ALWAYS CHECK AND VERIFY.
b. Adjust manifold pressure to obtain input rate.
(1.) Remove regulator adjustment seal cap. (See Fig. 14.)
(2.) Turn adjusting screw, counterclockwise (out) to de-
crease manifold pressure or clockwise (in) to increase manifold pressure.
NOTE: This furnace has been approved for a manifold pressure of 3.2-in. wc to 3.8-in. wc when installed at altitudes up to 2000 ft. For altitudes above 2000 ft, the manifold pressure can be adjusted from 2.0-in. wc to 3.8-in. wc.
DO NOT bottom out gas valve regulator adjusting screw. This can result in unregulated manifold pressure and result in excess overfire and heat exchanger failures.
NOTE: If orifice hole appears damaged or it is suspected to have been redrilled, check orifice hole with a numbered drill bit of correct size. Never redrill an orifice. A burr-free and squarely aligned orifice hole is essential for proper flame characteristics.
(3.) After correct manifold pressure is obtained, replace
gas valve regulator adjustment screw cap and verify adjusted gas input rate using method outlined in item c.
(4.) Burner flame should be clear blue, almost transparent.
(See Fig. 15.)
c. Verify natural gas input rate by clocking gas meter.
NOTE: High-Altitude Adjustment
United States
At installation altitudes above 2000 ft, this furnace has been approved for a 4% derate for each 1000 ft above sea level. See Table 7 for derate multiplier factor.
ALTITUDE
(FT)
0—2000 0 1.00 2001—3000 8—12 0.90 3001—4000 12—16 0.86 4001—5000 16—20 0.82 5001—6000 20—24 0.78 6001—7000 24—28 0.74 7001—8000 28—32 0.70 8001—9000 32—36 0.66
9001—10,000 36—40 0.62
* Derate multiplier factor is based on midpoint altitude for altitude range.
%OF
DERATE
DERATE MULTIPLIER
FACTOR FOR U.S.A*
EXAMPLE: 88,000 Btuh input furnace installed at 4300 ft.
Furnace Input
Rate at
Sea Level
88,000 X 0.82 = 72,160
X
Derate
Multiplier
Factor
Furnace Input Rate
=
at Installation
Altitude
Canada
At installation altitudes from 2000 to 4500 ft, this furnace must be derated 10% by an authorized Gas Conversion Station. To deter­mine correct input rate for altitude, see example above and use
0.90 as derate multiplier factor.
a. Turn off all other gas appliances and pilots.
b. Start furnace and let operate for 3 minutes.
c. Measure time (in sec) for gas meter test dial to complete 1
revolution.
d. Refer to Table 8 for cu ft of gas per hr.
e. Multiply gas rate (cu ft/hr) X heating value (Btu/cu ft)
using natural gas heating value from local gas utility/supplier.
EXAMPLE: (0—2000 ft altitude) Btu heating input = Btu/cu ft X cu ft/hr Heating value of gas = 1050 Btu/cu ft Time for 1 revolution of 2-cu ft dial = 70 sec Gas rate = 103 cu ft/hr (from Table 8) Btu heating input = 103 X 1050 = 108,150 Btuh In this example, the orifice size and manifold pressure adjustment is within ±2 percent of the furnace input rate.
14
SECONDS
FOR 1
REVOLUTION
10 11 12 13 14
15 16 17 18 19
20 21 22 23 24
25 26 27 28 29
30 31 32 33 34
35 36 37 38 39
40 41 42 43 44
45 46 47 48 49
Table 8—Gas Rate Cu Ft/Hr
SIZE OF
TEST DIAL
1
cu ft2cu ft5cu ft
720
360
655
327
600
300
555
277
514
257
480
240
450
225
424
212
400
200
379
189
360
180
343
171
327
164
313
157
300
150
288
144
277
138
267
133
257
129
248
124
240
120
232
116
225
113
218
109
212
106
206
103
200
100
195
97
189
95
185
92
180
90
176
88
172
86
167
84
164
82
160
80
157
78
153
76
150
75
147
73
1800 1636 1500 1385 1286
1200 1125 1059
100 947
900 857 818 783 750
720 692 667 643 621
600 581 563 545 529
514 500 486 474 462
450 439 429 419 409
400 391 383 375 367
SECONDS
FOR 1
REVOLUTION
50 51 52 53 54
55 56 57 58 59
60 62 64 66 68
70 72 74 76 78
80 82 84 86 88
90 92 94 96 98
100 102 104 106 108
110 112 116 120
ON AND OFF SWITCH
SIZE OF
TEST DIAL
1
cu ft2cu ft5cu ft
360
144
72 71 69 68 67
65 64 63 62 61
60 58 56 54 53
51 50 48 47 46
45 44 43 42 41
40 39 38 38 37
36 35 35 34 33
33 32 31 30
GAS PRESSURE REGULATOR ADJUSTMENT
141 138 136 133
131 129 126 124 122
120 116 112 109 106
103 100
97 95 92
90 88 86 84 82
80 78 76 75 74
72 71 69 68 67
65 64 62 60
355 346 340 333
327 321 316 310 305
300 290 281 273 265
257 250 243 237 231
225 220 214 209 205
200 196 192 188 184
180 178 173 170 167
164 161 155 150
BURNER FLAME
BURNER
MANIFOLD
A89020
Fig. 13—Burner Flame
a. Place duct thermometers in return and supply ducts as near
furnace as possible. Be sure thermometers do not "see" heat exchangers so that radiant heat will not affect thermometer readings. This is particularly important with straight-run ducts.
b. When thermometer readings stabilize, subtract return-air
temperature from supply-air temperature to determine tem­perature rise.
c. Adjust air temperature rise by adjusting blower speed.
Increase blower speed to reduce temperature rise. Decrease blower speed to increase temperature rise.
Disconnect the electrical power before changing the speed tap. A failure to follow this warning can cause personal injury.
d. To change blower motor speed selections for heating mode,
remove blower motor lead from control board HEAT terminal. (See Fig. 11.) Select desired blower motor speed lead from 1 of the other terminals and relocate it to HEAT terminal. See Table 9 for lead color identification. Recon­nect original lead on SPARE terminal.
Table 9—Speed Selector
COLOR SPEED
Black High COOL
Yellow (When
present)
Blue Medium-Low HEAT
Red Low SPARE
White Common COM
Medium-High SPARE
FACTORY-
ATTACHED TO
INLET PRESSURE TAP
MANIFOLD PRESSURE TAP
A95618
Fig. 12—Redundant Automatic Gas Control Valve
2. Set temperature rise.
Furnace must operate within range of temperature rise speci­fied on the unit rating plate. Determine the air temperature rise as follows.
Recheck temperature rise. It must be within limits specified on unit rating plate. Recommended operation is at midpoint of rise or above.
3. Set thermostat heat anticipator.
The thermostat heat anticipator must be set to match the amp draw of the electrical components in the R-W circuit. Accurate amp draw readings can be obtained at thermostat subbase terminals R and W. Fig. 14 illustrates an easy method of obtaining the actual amp draw. The amp reading should be
15
taken after the blower motor has started. See the thermostat manufacturer’s instructions for adjusting the heat anticipator and for varying the heating cycle length.
NOTE: When using an electronic thermostat, set the cycle rate for 3 cycles per hr.
THERMOSTAT SUBBASE TERMINALS WITH THERMOSTAT REMOVED
HOOK-AROUND
VOLT/AMMETER
R Y W G
10 TURNS
FROM UNIT 24-VOLT TERMINAL BLOCK
EXAMPLE:
5.0 AMPS ON AMMETER 10 TURNS AROUND JAWS
= 0.5 AMPS FOR THERMOSTAT SETTING
A80201
Fig. 14—Amp Draw Check With Ammeter
CHECK SAFETY CONTROLS — The flame sensor, gas valve, and pressure switch were all checked in the Start-Up Procedures section as part of normal operation.
1. Check primary limit control.
This control shuts off the combustion control system and energizes the circulating-air blower motor if the furnace overheats.
The preferred method of checking the limit control is to gradually block off the return air after the furnace has been operating for a period of at least 5 minutes. As soon as the limit has shut off the burners, the return-air opening should be unblocked. By using this method to check the limit control, it can be established that the limit is functioning properly and operates if there is a motor failure.
2. Check draft safeguard switch.
The purpose of this control is to permit the safe shutdown of the furnace during certain blocked vent conditions.
a. Disconnect power to furnace and remove vent connector
from furnace outlet collar. Be sure to allow time for vent pipe to cool down before removing.
b. Restore power to furnace and set room thermostat above
room temperature.
c. After normal start-up, allow furnace to operate for 2
minutes, then block flue outlet 100 percent. Furnace should cycle off within 2 minutes.
d. Remove blockage and reconnect vent pipe to furnace outlet
collar.
e. Wait 5 minutes and then reset draft safeguard switch.
3. Check pressure switch.
This control proves operation of draft inducer blower.
a. Turn off 115-v power to furnace.
b. Remove control door and disconnect inducer motor lead
wires from wire harness.
c. Turn on 115-v power to furnace.
d. Set thermostat to "call for heat" and wait 1 minute. When
pressure switch is functioning properly, hot surface ignitor should NOT glow and control center diagnostic light flashes a 31 fault. If hot surface ignitor glows when inducer motor is disconnected, shut down furnace immediately. Determine reason pressure switch did not function properly and correct condition.
e. Turn off 115-v power to furnace.
f. Reconnect inducer motor wires, replace control door, and
turn on 115-v power.
CHECKLIST
1. Put away tools, instruments, and clean up debris.
2. Verify manual reset switches have continuity.
3. Ensure blower and control access doors are properly installed.
4. Cycle test furnace with room thermostat.
5. Check operation of accessories per manufacturer’s instruc­tions.
6. Review User’s Manual with owner.
7. Leave literature packet near furnace.
Copyright 1996 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231 58wav7si
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Tab 6a 8a
PC 101 Catalog No. 565-980 Printed in U.S.A. Form 58WAV-7SI Pg 16 5-96 Replaces: 58WAV-6SI
Loading...