This installation instruction contains basic unit installation
information, including installation of thermostats and remote
temperature sensors.
For additional information and service instructions, refer to
the Controls, Start-Up, Operation, Service and Troubleshooting
literature.
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All
other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe
precautions in the literature, tags and labels attached to the unit,
and other safety precautions that may apply.
Follow all safety codes, including ANSI (American National Standards Institute) Z223.1. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguisher available for all brazing operations.
WARNING
Before performing service or maintenance operations on
unit, turn off main power switch to unit. Electrical shock
could cause personal injury.
FOR YOUR SAFETY
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance. Do not touch any electrical
switch; do not use any phone in your building. Immediately
call your gas supplier from a neighbor’s phone. Follow the
gas supplier’s instructions. If you cannot reach your gas supplier, call the fire department.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors and
liquids in the vicinity of this or any other appliance.
WARNING
Improper installation, adjustment, alteration, service, or
maintenance can cause injury or property damage. Refer to
this manual. For assistance or additional information, consult a qualified installer, service agency, or the gas supplier.
CAUTION
Disconnect gas piping from units when leak testing at pressures greater than 0.5 psig. Pressures greater than 0.5 psig
will cause gas valve damage resulting in a hazardous
condition. If gas valve is subjected to pressure greater than
0.5 psig, it must be replaced. When pressure testing fieldsupplied gas piping at pressures of 0.5 psig or less, the unit
connected to such piping must be isolated by manually
closing the gas valve.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53480121-01Printed in U.S.A.Form 48N-8SIPg 1 10-16Replaces: 48N-7SI
WARNING
DO NOT USE TORCH to remove any component. System
contains oil and refrigerant under pressure.
To remove a component, wear protective gloves and goggles and proceed as follows:
a. Shut off electrical power to unit.
b. Recover refrigerant to relieve all pressure from sys-
tem using both high-pressure and low pressure ports.
c. Traces of vapor should be displaced with nitrogen
and the work area should be well ventilated. Refrigerant in contact with an open flame produces toxic
gases.
d. Cut component connection tubing with tubing cutter
and remove component from unit. Use a pan to catch
any oil that may come out of the lines and as a gage
for how much oil to add to the system.
e. Carefully unsweat remaining tubing stubs when nec-
essary. Oil can ignite when exposed to torch flame.
Failure to follow these procedures may result in personal
injury or death.
CAUTION
DO NOT re-use compressor oil or any oil that has been
exposed to the atmosphere. Dispose of oil per local codes
and regulations. DO NOT leave refrigerant system open to
air any longer than the actual time required to service the
equipment. Seal circuits being serviced and charge with
dry nitrogen to prevent oil contamination when timely
repairs cannot be completed. Failure to follow these procedures may result in damage to equipment.
ACOUSTICAL CONSIDERATIONS
In order to minimize sound transmitted to the space, please
conform to the following recommendations (see Fig. 1):
Location
• Avoid locating the unit above sound-sensitive areas.
Instead, locate the unit above restrooms, storage areas,
corridors, or other noise-tolerant areas.
• Avoid mounting the unit in the middle of large roof
expanses between vertical supports. This will minimize
the phenomenon known as roof bounce.
• Install the units close to vertical roof supports (columns
or load bearing walls).
• Locate the units at least 25 feet away from critical areas.
If this is not possible, the ductwork and ceiling structure
should be acoustically treated.
• Consider the use of vibration isolators or an acoustic curb.
Ductwork
• Utilize flexible connectors between the unit and the supply and return ducts.
• Supply and return air main trunk ducts should be located
over hallways and/or public areas.
• Provide trailing edge turning vanes in ductwork elbows
and tees to reduce air turbulence.
• Make the ductwork as stiff as possible.
• Use round duct wherever possible because it is less noisy.
• Seal all penetrations around ductwork entering the space.
• Make sure that ceiling and wall contractors do not attach
hangers or supports to ductwork.
• Provide as smooth and gradual transition as possible when
connecting the rooftop unit discharge to the supply duct.
• If a ceiling plenum return is utilized, provide a return
elbow or tee to eliminate line-of-sight noise to the space.
Face the entrance of the return duct away from other
adjacent units.
Acoustic Insulation
• Provide acoustic interior lining for first 20 feet of supply
and return duct or until the first elbow is encountered.
The elbow prevents line-of-sight transmission in the supply and return ducts.
• Install a double layer of 2-in. low density quilted fiberglass acoustical pad with a
facing on top of the roof deck before building insulation
and roofing installation occur. Place the material inside
the curb and for 4 to 8 ft beyond the unit perimeter,
dependent upon unit size (larger units require a wider
apron outside the curb). Openings in the pad should only
be large enough for the supply and return ducts. An alternate approach is to use two layers of gypsum board with
staggered seams in addition to the acoustical pad.
1
/8-in. barium-loaded vinyl
2
Flexible
Fig. 1 — Acoustical Considerations
Connectors
Supply and
Return
Vibration
Isolators
in Roof
Curb
Intake
Plenum
Supply
Fan
Supply and Return
Ducts Lined with
Acoustical Duct Liner
Discharge
Plenum
Compressor/
Condensing
Section
Round Duct Controls
Rumble Best
All Roof
Penetrations
Should Be
Sealed
Air Tight
INSTALLATION
Step 1 — Perform Jobsite Survey —
the following checks before installation.
1. Consult local building codes and the NEC (National
Electrical Code) (ANSI/NFPA [American National Standards Institute/National Fire Protection Association] 70)
for special installation requirements.
2. Determine unit location (from project plans) or select unit
location. Refer to Acoustical Considerations section.
3. Check for possible overhead obstructions which may interfere with unit lifting or rigging.
Complete
CAUTION
Do not lift unit with forklift truck. Move unit with overhead rigging only.
Step 2 — Place Unit — Inspect unit for transportation
damage. If any damage is found, file a claim with the transportation agency.
Provide clearance around and above unit for airflow, safety,
and service access. Do not restrict top (area above condenser
fans) in any way. Allow at least 6 ft on all sides for rated performance, code compliance, and service. On units equipped with
power exhaust option, high velocity air is exhausted out the
hood. Unit should be positioned with at least 10 ft clearance between the exhaust hood and any obstruction. See Fig. 2 for
multiple unit minimum separation. See Tables 1-6 for additional unit and fan data.
Check unit dimensional drawings on pages 19-23 for unit
arrangement and minimum performance and service
clearances.
Do not install unit in an indoor location. Do not locate air inlets near exhaust vents or other sources of contaminated air.
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
Level by using unit frame as a reference.
Step 3 — Roof Mount Unit — Check building codes
for weight distribution requirements. Refer to Acoustical Considerations section. Unit and accessory weights are shown in
Tables 1 and 2. Unit may be mounted on class A, B, or C roofing material.
ROOF CURB — Assemble and install roof curb as described
in instructions shipped with the accessory. Accessory roof curb
and information required to field fabricate a roof curb is shown
in Fig. 3 and 4. Install insulation, cant strips, roofing, and
counter flashing as required. For unit condensate drain to function properly, curb must be level or within tolerances shown in
Fig. 3.
NOTE: Units with double-wall floor design (“Double Wall onthe-bottom”) are not compatible with roof curbs.
STEEL BEAMS — If roof curb is not used, support unit with
steel beams along its entire length and then support steel as required. Cross members are required to support across its width
at each lifting lug location; use more cross members for support as needed.
Step 4 — Slab Mount Unit — Provide a level con-
crete slab that extends beyond unit cabinet at least 6 inches.
Use gravel apron in front of condenser coil air inlet to prevent
grass and foliage from obstructing airflow. Provide a slab minimum 8 in. thick with sufficient height above grade to allow for
condensate trap as described in Step 8.
BASE UNITNPQRST
NOMINAL CAPACITY (tons)7590105120130150
WEIGHT (lb)
Base Unit*12,00012,45512,45516,17016,86017,040
Split Unit - Main Section9,1109,5659,56512,88013,57013,750
Split Unit - Return Section2,8902,8902,8903,2903,2903,290
COMPRESSORSScroll
Quantity566 8 8 8
Oil Charge (oz) per Compressor110110110110110110
Compressor A1ZP182ZP154ZP182ZP182ZP154ZP182
Compressor A2ZP182ZP154ZP182ZP154ZP182ZP182
Compressor A30ZP154ZP182ZP154ZP182ZP182
Compressor A4000ZP154ZP182ZP182
Compressor B1ZP137ZP182ZP182ZP182ZP154ZP182
Compressor B2ZP137ZP182ZP182ZP154ZP182ZP182
Compressor B3ZP137ZP182ZP182ZP154ZP182ZP182
Compressor B4000ZP154ZP182ZP182
Stages of Capacity, % Total Capacity0,18,23,41,65,
Number of Refrigerant Circuits222 2 2 2
REFRIGERANT
TypeR-410A
Charge AmountSee Table 6
METERING DEVICE
Type... Quantity per CircuitElectronically controlled expansion devices... two (2) per circuit
STANDARD EFFICIENCY UNIT CONDENSERMCHX
MaterialAluminumAluminumAluminumAluminumAluminumAluminum
Number of Total Coils444 4 6 6
Total Face Area (sq ft)138.7173.3173.3173.3173.3260.0
HIGH EFFICIENCY UNIT CONDENSERMCHX
MaterialAluminumAluminumAluminumAluminumAluminum
Number of Total Coils466 6 6
Total Face Area (sq ft)138.7173.3260.0260.0260.0
EVAP-STANDARD CAPACITY with STD EFFICIENCYRTPF
Total Face Area (sq ft)78.878.878.899.699.6
CONDENSER FAN, STANDARD EFFICIENCY
Number of Fans466 6 9 9
TypeProp/MetalProp/MetalProp/PlasticProp/PlasticProp/MetalProp/Plastic
Diameter (in.)30.53030.530.53030.5
Motor Hp1111 1 1
Nominal Cfm41,00081,00081,00081,00093,000122,400
Motor Rpm114011401140114011401140
CONDENSER FAN, HIGH EFFICIENCY
Number of Fans699 9 9
TypeProp/MetalProp/PlasticProp/PlasticProp/PlasticProp/Plastic
Diameter (in.)30.530.530.530.530.5
Motor Hp1111 1
Nominal Cfm61,00093,00093,00093,00093,000
Motor Rpm11401140114011401140
LEGEND* Base unit includes: economizer dampers and hoods, filter tracks less filters, evaporator coil
Cu-Al— Copper-to-Aluminum
DWDI— Double Width Double Inlet
FPI— Fins per Inch
MBtuh— Btuh in Thousands
MCHX— Microchannel Heat Exchanger
RTPF— Round Tube Plate Fin
SWSI— Single Width Single Inlet
82,100
0,11,15,33,49,
67,82,100
mounting less the evaporator, extended plenum, and standard efficiency condenser. For 75105 nominal ton units only, base unit weight also includes the short supply fan section.
BASE UNITNPQRST
NOMINAL CAPACITY (tons)7590105120130150
HUMIDI-MIZER
TypeMCHX
MaterialAluminum
Quantity1
SurfaceE-Coated
Total Face Area (sq ft)34.543434343
STANDARD AND HIGH CAPACITY HOT WATER COILS
TypeRTPF
MaterialAluminum Fin, Copper Tube
Quantity2
Tube TypeSmooth
Rows (each)2
FPI12
Total Face Area (sq ft)22.426.4
STANDARD AND HIGH CAPACITY STEAM COIL
TypeRTPF
MaterialAluminum Fin, Copper Tube, Steel Header, Sloped Casing
Quantity2
Tube TypeSmooth
Connection Size, Length (in.)2.50, 3.00
Total Face Area (sq ft)40.149.0
HEATING SECTION LOW (48N ONLY)
Heating Section22233 3
Number of Gas Valves3445 5 5
SUPPLY FAN
Standard Supply Fan
Diameter (in.)28
Wheel and Blade TypeDWDI Airfoil
Maximum Allowable Cfm42,000
Maximum Allowable Speed (rpm)1,800
Shaft Diameter at Pulley (in.)2.25
High Static Supply Fan
Diameter (in.)40
Wheel and Blade TypeDWDI Airfoil
Maximum Allowable Cfm52,500
Maximum Allowable Speed (rpm)1,250
Shaft Diameter at Pulley (in.)3
LEGEND* Base unit includes: economizer dampers and hoods, filter tracks less filters, evaporator coil
Cu-Al— Copper-to-Aluminum
DWDI— Double Width Double Inlet
FPI— Fins per Inch
MBtuh— Btuh in Thousands
MCHX— Microchannel Heat Exchanger
RTPF— Round Tube Plate Fin
SWSI— Single Width Single Inlet
®
COIL
NA
43
334 4 4
32
DWDI Airfoil
60,000
1,550
2.5
40
DWDI Airfoil
60,000
1,250
3
mounting less the evaporator, extended plenum, and standard efficiency condenser. For 75105 nominal ton units only, base unit weight also includes the short supply fan section.
BASE UNITNPQRST
NOMINAL CAPACITY (tons)7590105120130150
OPTIONAL POWER EXHAUST
Power Exhaust
Diameter (in.)20
Wheel and Blade TypeDWDI Forward Curve
Maximum Allowable Cfm42,000
Maximum Allowable Speed (rpm)1,2001,200
Shaft Diameter at Pulley (in.)1.751.75
High Static Power Exhaust
Diameter (in.)36
Wheel and Blade TypeDWDI Forward CurveDWDI Forward Curve
Maximum Allowable Cfm42,000
Maximum Allowable Speed (rpm)650
Shaft Diameter at Pulley (in.)2.5
OPTIONAL RETURN FAN
Return Fan
Diameter (in.)4040
Wheel and Blade TypeSWSI Plenum AirfoilSWSI Plenum Airfoil
Maximum Allowable Cfm52,500
Maximum Allowable Speed (rpm)12361236
Shaft Diameter at Pulley (in.)2.52.5
High Static Return Fan
Diameter (in.)45
Wheel and Blade TypeSWSI Plenum Airfoil
Maximum Allowable Cfm60,000
Maximum Allowable Speed (rpm)850
5056
60,00060,000
780720
Shaft Diameter at Pulley (in.)3
MIXED AIR FILTERS
MERV 7 Pleated Filters2 inch, MERV 72 inch, MERV 7
Quantity2828
Size (in.)20x24x220x25x2
MERV 8 Pleated Filters4 inch, MERV 84 inch, MERV 8
Quantity2828
Size (in.)20x24x420x25x4
MERV 14 Pleated Filters4 inch, MERV 144 inch, MERV 14
Quantity2828
Size (in.)20x24x420x25x4
MERV 14 Cartridge Filters, 2 or 4-in. in Pre-Filters12 inch, MERV 14 Cartridge Filters12 inch, MERV 14 Cartridge Filters
Quantity2020
Size (in.)(15) 20x24x12, (5) 24x24x1224x24x12
MERV 14 Bag, 2 or 4-in. in Pre-Filters12 inch, MERV 14 Bag Filters12 inch, MERV 14 Bag Filters
Quantity2020
Size (in.)(15) 20x24x12, (5) 24x24x1224x24x12
MERV 15 Bag, 2 or 4-in. in Pre-Filters19 inch, MERV 15 Bag Filters19 inch, MERV 15 Bag Filters
Quantity2020
Size (in.)(15) 20x24x19, (5) 24x24x1924x24x19
FINAL FILTERS
MERV 14 Cartridge Filters, 2 or 4-in. in Pre-Filters12 inch, MERV 14 Cartridge Filters12 inch, MERV 14 Cartridge Filters
Quantity
1919
Size (in.)(14) 20x24x12, (5) 24x24x1224x24x12
MERV 15 Bag, 2 or 4-in. in Pre-Filters19 inch, MERV 15 Bag Filters19 inch, MERV 15 Bag Filters
Quantity1919
Size (in.)(14) 20x24x19, (5) 24x24x1924x24x19
MERV 17 HEPA, 2 or 4-in. in Pre-Filters12 inch, MERV 17 HEPA Filters, 99.99%12 inch, MERV 17 HEPA Filters, 99.99%
Quantity1919
Size (in.)(14) 24x12x12, (5) 24x24x1224x24x12
OUTSIDE AIR SCREENS
Standard Hood (Motorized OA and Economizer
Options)
Aluminum Frame, Permanent
Quantity12 Screens16 Screens
Size (in.)16 7/8 x 3116 7/8 x 31
LEGEND* Base unit includes: economizer dampers and hoods, filter tracks less filters, evaporator coil
Cu-Al— Copper-to-Aluminum
DWDI— Double Width Double Inlet
FPI— Fins per Inch
MBtuh— Btuh in Thousands
MCHX— Microchannel Heat Exchanger
RTPF— Round Tube Plate Fin
SWSI— Single Width Single Inlet
mounting less the evaporator, extended plenum, and standard efficiency condenser. For 75105 nominal ton units only, base unit weight also includes the short supply fan section.
23
60,000
40
60,000
600
3
60,000
7
Table 2 — Operating Weights of Options and Accessories (lb)
OPTION OR ACCESSORY
N
(75)
P
(90)
Q
(105)
R
(120)
S
(130)
Economizer140140140140140140
48N UNIT SIZE (TON NOMINAL CAPACITY)
Filters
2 in. MERV 7 909090100100100
4 in. MERV 8150150150175175175
4 in. MERV 14175175175210210210
12 in. MERV 14 Bag with 2 in. Pre-Filter200200200225225225
12 in. MERV 14 Bag with 4 in. Pre-Filter260260260300300300
19 in. MERV 15 Bag with 2 in. Pre-Filter300300300335335335
19 in. MERV 15 Bag with 4 in. Pre-Filter320320320350350350
12 in. MERV 14 Cartridge with 2 in. Pre-Filter350350350375375375
12 in. MERV 14 Cartridge with 4 in. Pre-Filter370370370400400400
Field Use Filter Section635635635665665665
Evaporator
Standard Capacity62562583279510531053
High Capacity8328321110105314021402
High-Efficiency Condenser310691691691NoneNA
Extended Chassis320320320335335335
19 in. MERV 15 Bag with 2 in. Pre-Filter830830830890890890
19 in. MERV 15 Bag with 4 in. Pre-Filter850850850905905905
12 in. MERV 14 Cart with 2 in. Pre-Filter880880880930930930
12 in. MERV 14 Cart with 4 in. Pre-Filter900900900955955955
12 in. MERV 17 HEPA with 2 in. Pre-Filter905905905965965965
12 in. MERV 17 HEPA with 4 in. Pre-Filter930930930980980980
Supply Fan
High-Static Supply Fan127412741274116911691169
Standard Supply Fan965965965107110711071
PE (Power Exhaust) Fan
High-Static PE Fan927927927927927927
Standard PE Fan619727727727727727
Return Fan
High-Static Return Fan97410861298129812981298
Standard Return Fan895895895895895895
Supply/PE/Return Motor Includes VFD
has been connected to the roof curb, apply gasket material
1
(
/2-in. thick x 11/2-in. wide neoprene) where indicated.
Single-Thickness Gasketing (See Fig. 5 for Item Numbers)
— Apply gasketing in the following places:
1. Along both side rails (1) — 2 places, full length
2. Along return air end rail (2) — 1 place
3. Around return air internal duct flange (3) — 1 or 2 places
4. Around supply air internal duct flanges (4) — 3 places
5. Along supply section base rail (5) — 1 place
Condenser Section Roof Curb (See Fig. 6)
— Apply single-
thickness gasket along both side rails (5).
Step 6 — Install Field-Fabricated Ductwork
WARNING
For vertical supply and return units, tools or parts could
drop into ductwork and cause an injury. Install a 90-degree
elbow in the supply and return ductwork between the unit
and the conditioned space. If a 90-degree elbow cannot be
installed, then a grille of sufficient strength and density
should be installed to prevent objects from falling into the
conditioned space. Failure to follow these instructions
could result in personal injury or property damage due to
falling objects.
Field-fabricated ductwork for vertical supply/vertical return
units must be attached to the roof curb, or to the support steel,
prior to the final rigging and installation of the unit. Supply and
return duct dimensions are shown in Fig. 3.
To attach ductwork to roof curb, insert duct approximately
10 to 11 in. up into roof curb. Connect ductwork to 14-gage
roof curb material with sheet metal screws driven from inside
the duct.
Secure all ducts to the building structure, using flexible duct
connectors between roof curbs and ducts as required. Ducts
passing through an unconditioned space must be insulated and
covered with a vapor barrier. Outlet grilles must not lie directly
below unit discharge.
Design supply duct strong enough to handle expected
static pressures. Field-fabricated ductwork for horizontal
supply/return units must be attached to the unit.
Step 7 — Rig Unit — Do not drop unit; keep upright.
Use spreader bars over the unit to prevent sling or cable damage. Sheets of plywood placed along the condenser coils will
provide additional protection. All lifting lugs MUST be used
when lifting unit. Level by using unit frame as a reference. See
Fig. 7-9 for information. Unit and accessory weights are shown
in Tables 1 and 2. Weight distribution and center of gravity can
be found in Fig. 10. Additional unit dimensional data can be
found in Fig. 11 and 12.
Step 8 — Connect Condensate Drain — The drain
is a 2-in. FPT pipe connection located on the right-hand side of
the unit looking at the unit from the return air end. See Fig. 11
and 12. Figure 13 shows the additional length of units with an
extended chassis.
With field-supplied fittings and pipe sections, plumb the primary condensate drain to the 2-in. FPT connector on the base
rail. Use a trap height of at least 7 inches. See Fig. 14 and 15.
Apply a bead of RTV or similar sealant around the pipe joint at
the connector in the base rail.
15
Loading...
+ 33 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.