Carrier WeatherExpert 48N3, WeatherExpert 48N5, WeatherExpert 48N6, WeatherExpert 48N4, WeatherExpert 48N7 Installation Instructions Manual

...
WeatherExpert
48N2,N3,N4,N5,N6,N7,N8,N9
Packaged Rooftop Cooling Units with Gas Heat and
ComfortLink Controls
Installation Instructions
®
CONTENTS
Page
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
SAFETY CONSIDERATIONS. . . . . . . . . . . . . . . . . . . . .1,2
ACOUSTICAL CONSIDERATIONS . . . . . . . . . . . . . . .2,3
Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Acoustic Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-37
Step 1 — Perform Jobsite Survey . . . . . . . . . . . . . . . . 3
Step 2 — Place Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Step 3 — Roof Mount Unit. . . . . . . . . . . . . . . . . . . . . . . . 3
Step 4 — Slab Mount Unit . . . . . . . . . . . . . . . . . . . . . . . . 3
Step 5 — Install Curb Gasketing . . . . . . . . . . . . . . . . 15
Step 6 — Install Field-Fabricated Ductwork . . . . . 15
Step 7 — Rig Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Step 8 — Connect Condensate Drain. . . . . . . . . . . . 15
Step 9 — Install Outdoor Hoods. . . . . . . . . . . . . . . . . 24
Step 10 — Route Field Wiring . . . . . . . . . . . . . . . . . . . 25
Step 11 — Make Field Electrical Connections . . . 26
Step 12 — Connect Air Pressure Tubing . . . . . . . . 28
• VARIABLE FREQUENCY DRIVE
• POWER EXHAUST
•RETURN FAN
Step 13 — Remove Supply-Fan Shipping
Bracket Screws . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Step 14 — Remove Power Exhaust Shipping
Bracket Screws . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Step 15 — Remove Optional Return-Fan
Shipping Brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Step 16 — Connect Gas Piping. . . . . . . . . . . . . . . . . . 30
Step 17 — Configure Optional Modulating Gas
Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Step 18 — Install Flue/Inlet Hoods . . . . . . . . . . . . . . 31
Step 19 — Install Supply-Air Thermistors . . . . . . . 32
Step 20 — Install Unit Accessories. . . . . . . . . . . . . . 32
Two-Piece Unit Fit Up . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
CONTROLS INSTALLATION. . . . . . . . . . . . . . . . . . 37-49
Constant Volume (CV)/Staged Air Volume
(SAV) Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
• CONTROL WIRING
Variable Air Volume (VAV) Units . . . . . . . . . . . . . . . . 38
Option and Accessory Control Wiring. . . . . . . . . . . 38
Carrier Comfort Network
Optional UPC Open Installation . . . . . . . . . . . . . . . . . 44
Smoke Control Modes . . . . . . . . . . . . . . . . . . . . . . . . . . 46
®
(CCN) Interface . . . . . . 44

GENERAL

This installation instruction contains basic unit installation information, including installation of thermostats and remote temperature sensors.
For additional information and service instructions, refer to the Controls, Start-Up, Operation, Service and Troubleshooting literature.

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical compo­nents. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func­tions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service per­sonnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes, including ANSI (American Nation­al Standards Institute) Z223.1. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguisher available for all brazing operations.
WARNING
Before performing service or maintenance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury.
FOR YOUR SAFETY
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance. Do not touch any electrical switch; do not use any phone in your building. Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. If you cannot reach your gas sup­plier, call the fire department.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WARNING
Improper installation, adjustment, alteration, service, or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information, con­sult a qualified installer, service agency, or the gas supplier.
CAUTION
Disconnect gas piping from units when leak testing at pres­sures greater than 0.5 psig. Pressures greater than 0.5 psig will cause gas valve damage resulting in a hazardous condition. If gas valve is subjected to pressure greater than
0.5 psig, it must be replaced. When pressure testing field­supplied gas piping at pressures of 0.5 psig or less, the unit connected to such piping must be isolated by manually closing the gas valve.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53480121-01 Printed in U.S.A. Form 48N-8SI Pg 1 10-16 Replaces: 48N-7SI
WARNING
DO NOT USE TORCH to remove any component. System contains oil and refrigerant under pressure.
To remove a component, wear protective gloves and gog­gles and proceed as follows:
a. Shut off electrical power to unit. b. Recover refrigerant to relieve all pressure from sys-
tem using both high-pressure and low pressure ports.
c. Traces of vapor should be displaced with nitrogen
and the work area should be well ventilated. Refrig­erant in contact with an open flame produces toxic gases.
d. Cut component connection tubing with tubing cutter
and remove component from unit. Use a pan to catch any oil that may come out of the lines and as a gage for how much oil to add to the system.
e. Carefully unsweat remaining tubing stubs when nec-
essary. Oil can ignite when exposed to torch flame.
Failure to follow these procedures may result in personal injury or death.
CAUTION
DO NOT re-use compressor oil or any oil that has been exposed to the atmosphere. Dispose of oil per local codes and regulations. DO NOT leave refrigerant system open to air any longer than the actual time required to service the equipment. Seal circuits being serviced and charge with dry nitrogen to prevent oil contamination when timely repairs cannot be completed. Failure to follow these proce­dures may result in damage to equipment.

ACOUSTICAL CONSIDERATIONS

In order to minimize sound transmitted to the space, please
conform to the following recommendations (see Fig. 1):

Location

• Avoid locating the unit above sound-sensitive areas. Instead, locate the unit above restrooms, storage areas, corridors, or other noise-tolerant areas.
• Avoid mounting the unit in the middle of large roof expanses between vertical supports. This will minimize the phenomenon known as roof bounce.
• Install the units close to vertical roof supports (columns or load bearing walls).
• Locate the units at least 25 feet away from critical areas. If this is not possible, the ductwork and ceiling structure should be acoustically treated.
• Consider the use of vibration isolators or an acoustic curb.

Ductwork

• Utilize flexible connectors between the unit and the sup­ply and return ducts.
• Supply and return air main trunk ducts should be located over hallways and/or public areas.
• Provide trailing edge turning vanes in ductwork elbows and tees to reduce air turbulence.
• Make the ductwork as stiff as possible.
• Use round duct wherever possible because it is less noisy.
• Seal all penetrations around ductwork entering the space.
• Make sure that ceiling and wall contractors do not attach hangers or supports to ductwork.
• Provide as smooth and gradual transition as possible when connecting the rooftop unit discharge to the supply duct.
• If a ceiling plenum return is utilized, provide a return elbow or tee to eliminate line-of-sight noise to the space. Face the entrance of the return duct away from other adjacent units.

Acoustic Insulation

• Provide acoustic interior lining for first 20 feet of supply and return duct or until the first elbow is encountered. The elbow prevents line-of-sight transmission in the sup­ply and return ducts.
• Install a double layer of 2-in. low density quilted fiber­glass acoustical pad with a facing on top of the roof deck before building insulation and roofing installation occur. Place the material inside the curb and for 4 to 8 ft beyond the unit perimeter, dependent upon unit size (larger units require a wider apron outside the curb). Openings in the pad should only be large enough for the supply and return ducts. An alter­nate approach is to use two layers of gypsum board with staggered seams in addition to the acoustical pad.
1
/8-in. barium-loaded vinyl
2
Flexible
Fig. 1 — Acoustical Considerations
Connectors Supply and Return
Vibration Isolators in Roof Curb
Intake Plenum
Supply Fan
Supply and Return Ducts Lined with Acoustical Duct Liner
Discharge Plenum
Compressor/ Condensing Section
Round Duct Controls Rumble Best
All Roof Penetrations Should Be Sealed Air Tight

INSTALLATION

Step 1 — Perform Jobsite Survey —
the following checks before installation.
1. Consult local building codes and the NEC (National Electrical Code) (ANSI/NFPA [American National Stan­dards Institute/National Fire Protection Association] 70) for special installation requirements.
2. Determine unit location (from project plans) or select unit location. Refer to Acoustical Considerations section.
3. Check for possible overhead obstructions which may in­terfere with unit lifting or rigging.
Complete
CAUTION
Do not lift unit with forklift truck. Move unit with over­head rigging only.
Step 2 — Place Unit — Inspect unit for transportation
damage. If any damage is found, file a claim with the transpor­tation agency.
Provide clearance around and above unit for airflow, safety, and service access. Do not restrict top (area above condenser fans) in any way. Allow at least 6 ft on all sides for rated perfor­mance, code compliance, and service. On units equipped with power exhaust option, high velocity air is exhausted out the hood. Unit should be positioned with at least 10 ft clearance be­tween the exhaust hood and any obstruction. See Fig. 2 for multiple unit minimum separation. See Tables 1-6 for addition­al unit and fan data.
Check unit dimensional drawings on pages 19-23 for unit arrangement and minimum performance and service clearances.
Do not install unit in an indoor location. Do not locate air in­lets near exhaust vents or other sources of contaminated air.
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
Level by using unit frame as a reference.
Step 3 — Roof Mount Unit — Check building codes
for weight distribution requirements. Refer to Acoustical Con­siderations section. Unit and accessory weights are shown in Tables 1 and 2. Unit may be mounted on class A, B, or C roof­ing material.
ROOF CURB — Assemble and install roof curb as described in instructions shipped with the accessory. Accessory roof curb and information required to field fabricate a roof curb is shown in Fig. 3 and 4. Install insulation, cant strips, roofing, and counter flashing as required. For unit condensate drain to func­tion properly, curb must be level or within tolerances shown in Fig. 3.
NOTE: Units with double-wall floor design (“Double Wall on­the-bottom”) are not compatible with roof curbs.
STEEL BEAMS — If roof curb is not used, support unit with steel beams along its entire length and then support steel as re­quired. Cross members are required to support across its width at each lifting lug location; use more cross members for sup­port as needed.
Step 4 — Slab Mount Unit — Provide a level con-
crete slab that extends beyond unit cabinet at least 6 inches. Use gravel apron in front of condenser coil air inlet to prevent grass and foliage from obstructing airflow. Provide a slab mini­mum 8 in. thick with sufficient height above grade to allow for condensate trap as described in Step 8.
3
D
a48-8682
MINIMUM SPACING (ft)
UNIT A B C D E F
48
Series
12 8 12 10 10 10
50
Series
10 8 8 10 10 10
Fig. 2 — Multiple Unit Minimum Separation
A
E
F
B
C
4
Table 1 — Physical Data 48N Sizes N-T (75-150 Tons Nominal Capacity)
BASE UNIT N P Q R S T NOMINAL CAPACITY (tons) 75 90 105 120 130 150 WEIGHT (lb)
Base Unit* 12,000 12,455 12,455 16,170 16,860 17,040 Split Unit - Main Section 9,110 9,565 9,565 12,880 13,570 13,750 Split Unit - Return Section 2,890 2,890 2,890 3,290 3,290 3,290 COMPRESSORS Scroll
Quantity 566 8 8 8
Oil Charge (oz) per Compressor 110 110 110 110 110 110 Compressor A1 ZP182 ZP154 ZP182 ZP182 ZP154 ZP182 Compressor A2 ZP182 ZP154 ZP182 ZP154 ZP182 ZP182 Compressor A3 0 ZP154 ZP182 ZP154 ZP182 ZP182 Compressor A4 0 0 0 ZP154 ZP182 ZP182 Compressor B1 ZP137 ZP182 ZP182 ZP182 ZP154 ZP182 Compressor B2 ZP137 ZP182 ZP182 ZP154 ZP182 ZP182 Compressor B3 ZP137 ZP182 ZP182 ZP154 ZP182 ZP182 Compressor B4 0 0 0 ZP154 ZP182 ZP182 Stages of Capacity, % Total Capacity 0,18,23,41,65,
Number of Refrigerant Circuits 222 2 2 2 REFRIGERANT Type R-410A Charge Amount See Table 6 METERING DEVICE Type... Quantity per Circuit Electronically controlled expansion devices... two (2) per circuit STANDARD EFFICIENCY UNIT CONDENSER MCHX
Material Aluminum Aluminum Aluminum Aluminum Aluminum Aluminum Number of Total Coils 444 4 6 6
Total Face Area (sq ft) 138.7 173.3 173.3 173.3 173.3 260.0 HIGH EFFICIENCY UNIT CONDENSER MCHX
Material Aluminum Aluminum Aluminum Aluminum Aluminum Number of Total Coils 466 6 6
Total Face Area (sq ft) 138.7 173.3 260.0 260.0 260.0 EVAP-STANDARD CAPACITY with STD EFFICIENCY RTPF
Material CU-AL CU-AL CU-AL CU-AL CU-AL CU-AL
Quantity 222 2 2 2
Tube Type Cross Hatched Cross Hatched Cross Hatched Cross Hatched Cross Hatched Cross Hatched
Rows (each) 446 4 6 6
FPI 16 16 16 16 16 16
Total Face Area (sq ft) 78.8 78.8 78.8 99.6 99.6 99.6 EVAP-STANDARD CAPACITY with HIGH
EFFICIENCY
Material CU-AL CU-AL CU-AL CU-AL CU-AL
Quantity 222 2 2
Tube Type Cross Hatched Cross Hatched Cross Hatched Cross Hatched Cross Hatched
Rows (each) 446 4 6
FPI 16 16 16 16 16
Total Face Area (sq ft) 78.8 78.8 78.8 99.6 99.6 EVAP-HIGH CAPACITY with STD EFFICIENCY RTPF
Material CU-AL CU-AL CU-AL CU-AL CU-AL CU-AL
Quantity 222 2 2 2
Tube Type Cross Hatched Cross Hatched Cross Hatched Cross Hatched Cross Hatched Cross Hatched
Rows (each) 668 6 8 8
FPI 16 16 16 16 16 16
Total Face Area (sq ft) 78.8 78.8 78.8 99.6 99.6 99.6 EVAP-HIGH CAPACITY with HIGH EFFICIENCY RTPF
Material CU-AL CU-AL CU-AL CU-AL CU-AL
Quantity 222 2 2
Tube Type Cross Hatched Cross Hatched Cross Hatched Cross Hatched Cross Hatched
Rows (each) 668 6 8
FPI 16 16 16 16 16
Total Face Area (sq ft) 78.8 78.8 78.8 99.6 99.6 CONDENSER FAN, STANDARD EFFICIENCY Number of Fans 466 6 9 9 Type Prop/Metal Prop/Metal Prop/Plastic Prop/Plastic Prop/Metal Prop/Plastic Diameter (in.) 30.5 30 30.5 30.5 30 30.5 Motor Hp 1111 1 1 Nominal Cfm 41,000 81,000 81,000 81,000 93,000 122,400 Motor Rpm 1140 1140 1140 1140 1140 1140 CONDENSER FAN, HIGH EFFICIENCY Number of Fans 699 9 9 Type Prop/Metal Prop/Plastic Prop/Plastic Prop/Plastic Prop/Plastic Diameter (in.) 30.5 30.5 30.5 30.5 30.5 Motor Hp 1111 1 Nominal Cfm 61,000 93,000 93,000 93,000 93,000 Motor Rpm 1140 1140 1140 1140 1140
LEGEND * Base unit includes: economizer dampers and hoods, filter tracks less filters, evaporator coil
Cu-Al Copper-to-Aluminum DWDI Double Width Double Inlet FPI Fins per Inch MBtuh Btuh in Thousands MCHX Microchannel Heat Exchanger RTPF Round Tube Plate Fin SWSI Single Width Single Inlet
82,100
0,11,15,33,49,
67,82,100
mounting less the evaporator, extended plenum, and standard efficiency condenser. For 75­105 nominal ton units only, base unit weight also includes the short supply fan section.
0,13,17,33,50,
67,83,100
RTPF
0,11,14,28,40,
52,64,76,88,100
0,8,11,22,35,
48,61,74,87,100
0,9,13,25,38,
50,63,75,88,90
NA
NA
NA
NA
5
Table 1 — Physical Data 48N Sizes N-T (75-150 Tons Nominal Capacity) (cont)
BASE UNIT N P Q R S T NOMINAL CAPACITY (tons) 75 90 105 120 130 150 HUMIDI-MIZER Type MCHX Material Aluminum Quantity 1 Surface E-Coated Total Face Area (sq ft) 34.5 43 43 43 43 STANDARD AND HIGH CAPACITY HOT WATER COILS Type RTPF Material Aluminum Fin, Copper Tube Quantity 2 Tube Type Smooth Rows (each) 2 FPI 12 Total Face Area (sq ft) 22.4 26.4 STANDARD AND HIGH CAPACITY STEAM COIL Type RTPF Material Aluminum Fin, Copper Tube, Steel Header, Sloped Casing Quantity 2 Tube Type Smooth Connection Size, Length (in.) 2.50, 3.00 Total Face Area (sq ft) 40.1 49.0 HEATING SECTION LOW (48N ONLY) Heating Section 22233 3
Number of Heat Exchangers 18 18 18 27 27 27 Output (MBtuh) 648 648 648 972 972 972 Temperature Rise Range (F) 10-40 10-40 10-40 15-45 15-45 15-45 Efficiency (%) 81 81 81 81 81 81 Burner Orifice Quantity, Diameter (in.), Drill No. 18, 0.1285, 30 18, 0.1285, 30 18, 0.1285, 30 27, 0.1285, 30 27, 0.1285, 30 27, 0.1285, 30 Manifold Pressure (in. wg) 3.1 3.1 3.1 3.1 3.1 3.1 Line Pressure (in. wg) (min...max) 5.8-11 5.8-11 5.8-11 6.2-11 6.2-11 6.2-11 Firing Stages (Standard) 2222 2 2 Firing Stages (Modulating) 14-100% 14-100% 14-100% 9-100% 9-100% 9-100%
Number of Gas Valves 2223 3 3 HEATING SECTION MED (48N ONLY) Heating Section
Number of Heat Exchangers 27 27 36 36 36
Input/Output (MBtuh) 972 972 1296 1296 1296
Temperature Rise Range (F) 20-50 20-50 20-50 20-50 20-50
Efficiency (%) 81 81 81 81 81
Burner Orifice Quantity, Diameter (in.), Drill No. 27, 0.1285, 30 27, 0.1285, 30 36, 0.1285, 30 36, 0.1285, 30 36, 0.1285, 30
Manifold Pressure (in. wg) 3.1 3.1 3.1 3.1 3.1
Line Pressure (in. wg) (min...max) 6.3-11 6.3-11 6.2-11 6.2-11 6.2-11
Firing Stages (Standard) 222 2 2
Firing Stages (Modulating) 9-100% 9-100% 7-100% 7-100% 7-100%
Number of Gas Valves 334 4 4 HEATING SECTION HIGH (48N ONLY) Heating Section 34455 5
Number of Heat Exchangers 27 36 36 45 45 45
Input/Output (MBtuh) 972 1296 1296 1620 1620 1620
Temperature Rise Range (F) 20-50 25-65 25-65 25-55 25-55 25-55
Efficiency (%) 81 81 81 81 81 81
Burner Orifice Quantity, Diameter (in.), Drill No. 27, 0.1285, 30 36, 0.1285, 30 36, 0.1285, 30 45, 0.1285, 30 45, 0.1285, 30 45, 0.1285, 30
Manifold Pressure (in. wg) 3.1 3.1 3.1 3.1 3.1 3.1
Line Pressure (in. wg) (min...max) 6.3-11 6.3-11 6.3-11 6.2-11 6.2-11 6.2-11
Firing Stages (Standard) 2222 2 2
Firing Stages (Modulating) 9-100% 7-100% 7-100% 5-100% 5-100% 5-100%
Number of Gas Valves 3445 5 5 SUPPLY FAN Standard Supply Fan Diameter (in.) 28 Wheel and Blade Type DWDI Airfoil Maximum Allowable Cfm 42,000 Maximum Allowable Speed (rpm) 1,800 Shaft Diameter at Pulley (in.) 2.25 High Static Supply Fan Diameter (in.) 40 Wheel and Blade Type DWDI Airfoil Maximum Allowable Cfm 52,500 Maximum Allowable Speed (rpm) 1,250 Shaft Diameter at Pulley (in.) 3
LEGEND * Base unit includes: economizer dampers and hoods, filter tracks less filters, evaporator coil
Cu-Al Copper-to-Aluminum DWDI Double Width Double Inlet FPI Fins per Inch MBtuh Btuh in Thousands MCHX Microchannel Heat Exchanger RTPF Round Tube Plate Fin SWSI Single Width Single Inlet
®
COIL
NA
43
334 4 4
32
DWDI Airfoil
60,000
1,550
2.5
40
DWDI Airfoil
60,000
1,250
3
mounting less the evaporator, extended plenum, and standard efficiency condenser. For 75­105 nominal ton units only, base unit weight also includes the short supply fan section.
6
Table 1 — Physical Data 48N Sizes N-T (75-150 Tons Nominal Capacity) (cont)
BASE UNIT N P Q R S T NOMINAL CAPACITY (tons) 75 90 105 120 130 150 OPTIONAL POWER EXHAUST Power Exhaust Diameter (in.) 20 Wheel and Blade Type DWDI Forward Curve Maximum Allowable Cfm 42,000 Maximum Allowable Speed (rpm) 1,200 1,200 Shaft Diameter at Pulley (in.) 1.75 1.75 High Static Power Exhaust Diameter (in.) 36 Wheel and Blade Type DWDI Forward Curve DWDI Forward Curve Maximum Allowable Cfm 42,000 Maximum Allowable Speed (rpm) 650 Shaft Diameter at Pulley (in.) 2.5 OPTIONAL RETURN FAN Return Fan Diameter (in.) 40 40 Wheel and Blade Type SWSI Plenum Airfoil SWSI Plenum Airfoil Maximum Allowable Cfm 52,500 Maximum Allowable Speed (rpm) 1236 1236 Shaft Diameter at Pulley (in.) 2.5 2.5 High Static Return Fan Diameter (in.) 45 Wheel and Blade Type SWSI Plenum Airfoil Maximum Allowable Cfm 60,000 Maximum Allowable Speed (rpm) 850
50 56
60,000 60,000
780 720
Shaft Diameter at Pulley (in.) 3 MIXED AIR FILTERS MERV 7 Pleated Filters 2 inch, MERV 7 2 inch, MERV 7 Quantity 28 28 Size (in.) 20x24x2 20x25x2 MERV 8 Pleated Filters 4 inch, MERV 8 4 inch, MERV 8 Quantity 28 28 Size (in.) 20x24x4 20x25x4 MERV 14 Pleated Filters 4 inch, MERV 14 4 inch, MERV 14 Quantity 28 28 Size (in.) 20x24x4 20x25x4 MERV 14 Cartridge Filters, 2 or 4-in. in Pre-Filters 12 inch, MERV 14 Cartridge Filters 12 inch, MERV 14 Cartridge Filters Quantity 20 20 Size (in.) (15) 20x24x12, (5) 24x24x12 24x24x12 MERV 14 Bag, 2 or 4-in. in Pre-Filters 12 inch, MERV 14 Bag Filters 12 inch, MERV 14 Bag Filters Quantity 20 20 Size (in.) (15) 20x24x12, (5) 24x24x12 24x24x12 MERV 15 Bag, 2 or 4-in. in Pre-Filters 19 inch, MERV 15 Bag Filters 19 inch, MERV 15 Bag Filters Quantity 20 20 Size (in.) (15) 20x24x19, (5) 24x24x19 24x24x19 FINAL FILTERS MERV 14 Cartridge Filters, 2 or 4-in. in Pre-Filters 12 inch, MERV 14 Cartridge Filters 12 inch, MERV 14 Cartridge Filters Quantity
19 19
Size (in.) (14) 20x24x12, (5) 24x24x12 24x24x12 MERV 15 Bag, 2 or 4-in. in Pre-Filters 19 inch, MERV 15 Bag Filters 19 inch, MERV 15 Bag Filters Quantity 19 19 Size (in.) (14) 20x24x19, (5) 24x24x19 24x24x19 MERV 17 HEPA, 2 or 4-in. in Pre-Filters 12 inch, MERV 17 HEPA Filters, 99.99% 12 inch, MERV 17 HEPA Filters, 99.99% Quantity 19 19 Size (in.) (14) 24x12x12, (5) 24x24x12 24x24x12 OUTSIDE AIR SCREENS Standard Hood (Motorized OA and Economizer
Options)
Aluminum Frame, Permanent
Quantity 12 Screens 16 Screens Size (in.) 16 7/8 x 31 16 7/8 x 31
LEGEND * Base unit includes: economizer dampers and hoods, filter tracks less filters, evaporator coil
Cu-Al Copper-to-Aluminum DWDI Double Width Double Inlet FPI Fins per Inch MBtuh Btuh in Thousands MCHX Microchannel Heat Exchanger RTPF Round Tube Plate Fin SWSI Single Width Single Inlet
mounting less the evaporator, extended plenum, and standard efficiency condenser. For 75­105 nominal ton units only, base unit weight also includes the short supply fan section.
23
60,000
40
60,000
600
3
60,000
7
Table 2 — Operating Weights of Options and Accessories (lb)
OPTION OR ACCESSORY
N
(75)
P
(90)
Q
(105)
R
(120)
S
(130)
Economizer 140 140 140 140 140 140
48N UNIT SIZE (TON NOMINAL CAPACITY)
Filters
2 in. MERV 7 90 90 90 100 100 100 4 in. MERV 8 150 150 150 175 175 175 4 in. MERV 14 175 175 175 210 210 210 12 in. MERV 14 Bag with 2 in. Pre-Filter 200 200 200 225 225 225 12 in. MERV 14 Bag with 4 in. Pre-Filter 260 260 260 300 300 300 19 in. MERV 15 Bag with 2 in. Pre-Filter 300 300 300 335 335 335 19 in. MERV 15 Bag with 4 in. Pre-Filter 320 320 320 350 350 350 12 in. MERV 14 Cartridge with 2 in. Pre-Filter 350 350 350 375 375 375
12 in. MERV 14 Cartridge with 4 in. Pre-Filter 370 370 370 400 400 400 Field Use Filter Section 635 635 635 665 665 665 Evaporator Standard Capacity 625 625 832 795 1053 1053 High Capacity 832 832 1110 1053 1402 1402 High-Efficiency Condenser 310 691 691 691 None NA Extended Chassis 320 320 320 335 335 335
®
Humidi-MiZer Gas Heat
Low 937 937 937 1099 1099 1099 Medium NA 1067 1067 1229 1229 1229 High 1067 1197 1197 1469 1469 1469 Modulating 50 50 50 50 50 50
Blank Section
4 ft 530 530 530 555 555 555
Dehumidification System 475 495 495 510 510 510
8 ft 1060 1060 1060 1110 1110 1110 Post Filters
19 in. MERV 15 Bag with 2 in. Pre-Filter 830 830 830 890 890 890 19 in. MERV 15 Bag with 4 in. Pre-Filter 850 850 850 905 905 905 12 in. MERV 14 Cart with 2 in. Pre-Filter 880 880 880 930 930 930 12 in. MERV 14 Cart with 4 in. Pre-Filter 900 900 900 955 955 955 12 in. MERV 17 HEPA with 2 in. Pre-Filter 905 905 905 965 965 965 12 in. MERV 17 HEPA with 4 in. Pre-Filter 930 930 930 980 980 980
Supply Fan
High-Static Supply Fan 1274 1274 1274 1169 1169 1169
Standard Supply Fan 965 965 965 1071 1071 1071 PE (Power Exhaust) Fan
High-Static PE Fan 927 927 927 927 927 927
Standard PE Fan 619 727 727 727 727 727 Return Fan
High-Static Return Fan 974 1086 1298 1298 1298 1298
Standard Return Fan 895 895 895 895 895 895 Supply/PE/Return Motor Includes VFD
460 Volt ODP
7.5 Hp 183 183 183 183 183 183 10 Hp 209 209 209 209 209 209 15 Hp 320 320 320 320 320 320 20 Hp 374 374 374 374 374 374 25 Hp 417 417 417 417 417 417 30 Hp 456 456 456 456 456 456 40 Hp 697 697 697 697 697 697 50 Hp 784 784 784 784 784 784 60 Hp 897 897 897 897 897 897 75 Hp 1275 1275 1275 1275 1275 1275 100 Hp 1488 1488 1488 1488 1488 1488
LEGEND
ODP Open Drip Proof TEFC Totally Enclosed, Fan Cooled VFD Variable Frequency Drive
NOTE: Please refer to E-CAT for selection.
T
(150)
8
Table 2 — Operating Weights of Options and Accessories (lb) (cont)
OPTION OR ACCESSORY
Supply/PE/Return Motor Includes VFD 460 Volt TEFC
7.5 Hp 267 267 267 267 267 267 10 Hp 283 283 283 283 283 283 15 Hp 368 368 368 368 368 368 20 Hp 437 437 437 437 437 437 25 Hp 576 576 576 576 576 576 30 Hp 604 604 604 604 604 604 40 Hp 991 991 991 991 991 991 50 Hp 925 925 925 925 925 925 60 Hp 1163 1163 1163 1163 1163 1163 75 Hp 1275 1275 1275 1275 1275 1275 100 Hp 1488 1488 1488 1488 1488 1488
Supply/PE/Return Motor Includes VFD 575 Volt ODP
7.5 Hp 186 186 186 186 186 186 10 Hp 204 204 204 204 204 204 15 Hp 327 327 327 327 327 327 20 Hp 369 369 369 369 369 369 25 Hp 433 433 433 433 433 433 30 Hp 456 456 456 456 456 456 40 Hp 697 697 697 697 697 697 50 Hp 784 784 784 784 784 784 60 Hp 897 897 897 897 897 897 75 Hp 1194 1194 1194 1194 1194 1194 100 Hp 1488 1488 1488 1488 1488 1488
Supply/PE/Return Motor Includes VFD 575 Volt TEFC
7.5 Hp 228 228 228 228 228 228 10 Hp 277 277 277 277 277 277 15 Hp 382 382 382 382 382 382 20 Hp 436 436 436 436 436 436 25 Hp 616 616 616 616 616 616 30 Hp 652 652 652 652 652 652 40 Hp 795 795 795 795 795 795 50 Hp 897 897 897 897 897 897 60 Hp 933 933 933 933 933 933 75 Hp 1194 1194 1194 1194 1194 1194 100 Hp 1488 1488 1488 1488 1488 1488
Supply/PE/Return Motor Includes VFD Bypass
7.5 Hp 10 10 10 10 10 10 10 Hp 10 10 10 10 10 10 15 Hp 10 10 10 10 10 10 20 Hp 20 20 20 20 20 20 25 Hp 20 20 20 20 20 20 30 Hp 40 40 40 40 40 40 40 Hp 40 40 40 40 40 40 50 Hp 60 Hp 40 40 40 40 40 40 75 Hp 60 60 60 60 60 60 100 Hp 75 75 75 75 75 75
Condenser Grilles
Standard Efficiency 100 100 100 100 125 125 High Efficiency 100 125 125 125 125 NA
Condenser Louvers
Standard Efficiency 225 225 225 225 290 290
High Efficiency 225 290 290 290 290 NA Service Valves and Replacable Core Filter Drier 40 45 45 50 50 50 Low Ambient 50 50 50 50 50 50 UV Lights 100 100 100 130 130 130 Marine Lights 75 75 75 75 75 75 Split - 2 Piece Unit 268 268 268 280 280 280
LEGEND
ODP Open Drip Proof TEFC Totally Enclosed, Fan Cooled VFD Variable Frequency Drive
NOTE: Please refer to E-CAT for selection.
N
(75)
40 40 40 40 40 40
48N UNIT SIZE (TON NOMINAL CAPACITY)
P
(90)
Q
(105)
R
(120)
S
(130)
T
(150)
9
FAN
Standard Fan 75-105 Tons Nominal Capacity
Standard Fan 120-150 Tons Nominal Capacity
High Static 75-150 Tons Nominal Capacity
FAN
Standard Fan 75 Tons Nominal Capacity
Standard Fan 90-150 Tons Nominal Capacity
High Static 75-090 Tons Nominal Capacity
High Static 105-150 Tons Nominal Capacity
Table 3 — Supply Fan and Drive Data
MOTOR HPMOTOR
100 1775 2.875 1250
RPM
50 1770 2.125 1800 40 1770 2.125 1600 3B5V68 B 2 1/8 3B5V74 B 2 1/4 5VX540 3 1628/1628 30 1765 1.875 1450 3B5V70 B 1 7/8 3B5V86 B 2 1/4 BX55 3 1448/1448 25 1765 1.875 1400 3B5V64 B 1 7/8 3B5V80 B 2 1/4 BX53 3 1425/1425 20 1765 1.625 1250 3B5V56 B 1 5/8 3B5V80 B 2 1/4 BX53 3 1255/1255 60 1775 2.375 1550 50 1770 2.125 1400 4B5V70 B 2 1/8 4R5V90 R1 2 1/2 5VX630 4 1412/1412 40 1770 2.125 1300 3B5V68 B 2 1/8 3R5V92 R1 2 1/2 5VX630 3 1328/1328 30 1765 1.875 1200 3B5V70 B 1 7/8 3R5V103 R1 2 1/2 5VX670 3 1229/1229 25 1765 1.875 1100 3B5V64 B 1 7/8 3R5V103 R1 2 1/2 5VX660 3 1125/1125
75 1775 2.375 1100 4B5V80 B 2 3/8 4R5V132 R1 3 5VX840 4 1098/1098 60 1775 2.375 1050 4B5V70 B 2 3/8 4R5V118 R1 3 5VX800 4 1077/1077 50 1770 2.125 1000 4B5V70 B 2 1/8 4R5V125 R1 3 5VX830 4 1013/1013 40 1770 2.125 900 3B5V68 B 2 1/8 3R5V140 R1 3 5VX850 3 918/918 30 1765 1.875 800 3B5V70 B 1 7/8 3B154R R1 3 BX88 3 821/821 25 1765 1.875 750 3B5V64 B 1 7/8 3B154R R1 3 BX87 3 753/753
MOTOR
SHAFT
SIZE (in.)
FAN RPM
FAN
SHAFT
SIZE (in.)
2.25
2.5
3
DRIVE
SHEAVE
BROWNING
4B5V70 B 2 1/8 4B5V68 B 2 1/4 5VX530 4 1821/1821
4B5V70 B 2 3/8 4R5V80 R1 2 1/2 5VX600 4 1595/1595
5R5V90 R1 2 7/8 5B5V124 R1 3 5VX830 5 1264/1264
BUSHING
TYPE
DRIVEN
SHEAVE
BROWNING
BUSHING
TYPE BELTS
QTY OF
BELTS
FAN
SPEED
(rpm)
Table 4 — Power Exhaust Fan and Drive Data
MOTOR HPMOTOR
7.5 1760 1.375 1100 2BK52H H 1 3/8 2B5V74 B 1 3/4 BX51 2 1120/1120
7.5 1760 1.375 950 2BK52H H 1 3/8 2B5V90 B 1 3/4 BX53 2 927/927
7.5 1760 1.375 425 2BK52H H 1 3/8 2TB184 Q1 2 1/2 AX81 2 425/425
RPM
30 1765 1.875 1200 25 1765 1.875 1150 3B5V64 B 1 7/8 3R5V103 R1 1 3/4 5VX560 3 1125/1125 20 1765 1.625 1125 3B5V56 B 1 5/8 3B5V90 B 1 3/4 BX52 3 1120/1120 15 1770 1.625 1100 2B5V64 B 1 5/8 2Q5V103 Q1 1 3/4 5VX580 2 1128/1128 10 1755 1.375 1100 2BK52H H 1 3/8 2B5V74 B 1 3/4 BX51 2 1117/1117
50 1770 2.125 1200 40 1770 2.125 1175 3B5V68 B 2 1/8 3R5V103 R1 1 3/4 5VX540 3 1197/1197 30 1765 1.875 1150 3B5V70 B 1 7/8 3B5V110 B 1 3/4 5VX580 3 1129/1129 25 1765 1.875 1125 3B5V64 B 1 7/8 3R5V103 R1 1 3/4 5VX550 3 1125/1125 20 1765 1.625 1100 3B5V56 B 1 5/8 3B5V90 B 1 3/4 BX52 3 1120/1120 15 1770 1.625 1050 2B5V64 B 1 5/8 2B5V110 B 1 3/4 5VX590 2 1036/1036 10 1755 1.375 1000 2BK52H H 1 3/8 2B5V80 B 1 3/4 BX51 2 1036/1036
40 1770 2.125 650 30 1765 1.875 625 3B5V70 B 1 7/8 3TB200 Q1 2 1/2 BX86 3 635/635 25 1765 1.875 600 3B5V64 B 1 7/8 3TB200 Q1 2 1/2 BX85 3 583/583 20 1765 1.625 550 3B5V56 B 1 5/8 3TB184 Q1 2 1/2 BX82 3 557/557 15 1770 1.625 500 2B5V64 B 1 5/8 25V2360E E 2 1/2 5VX950 2 490/490 10 1755 1.375 450 2BK52H H 1 3/8 2TB184 Q1 2 1/2 BX82 2 460/460
60 1775 2.375 600 50 1770 2.125 575 4B5V70 B 2 1/8 4R5V212 R1 3 5VX950 4 596/596 40 1770 2.125 550 3B5V68 B 2 1/8 3R5V212 R1 3 5VX930 3 579/579 30 1765 1.875 525 3B5V70 B 1 7/8 3B250R R1 3 BX103 3 509/509 25 1765 1.875 500 3B5V64 B 1 7/8 35V2360E E 3 5VX1000 3 488/488 20 1765 1.625 450 3B5V56 B 1 5/8 35V2360E E 3 5VX1000 3 428/428 15 1770 1.625 400 2B5V64 B 1 5/8 2B300R R1 3 BX112 2 391/391
MOTOR
SHAFT
SIZE (in.)
FAN RPM
FAN
SHAFT
SIZE (in.)
1.75
1.75
2.5
3
DRIVE
SHEAVE
BROWNING
3B5V70 B 1 7/8 3R5V103 R1 1 3/4 5VX570 3 1229/1229
4B5V70 B 2 1/8 4R5V103 R1 1 3/4 5VX540 4 1225/1225
3B5V68 B 2 1/8 35V1870E E 2 1/2 5VX830 3 657/657
4B5V70 B 2 3/8 4R5V212 R1 3 5VX930 4 597/597
BUSHING
TYPE
DRIVEN
SHEAVE
BROWNING
BUSHING
TYPE BELTS
QTY OF
BELTS
SPEED
(rpm)
FAN
10
FAN
Standard Return Fan All Sizes
High Static Return Fan 75 Tons Nominal Capacity
High Static Return Fan 90 Tons Nominal Capacity
High Static Return Fan 105-150 Tons Nominal Capacity
Table 5 — Return Fan Drive Data
MOTOR HPMOTOR
50 1770 2.125 1236 40 1770 2.125 1149 3B5V68 B 2 1/8 3R5V109 R1 2 1/2 5VX1000 3 1131/1131 30 1765 1.875 1025 3B5V70 B 1 7/8 3TB124 Q1 2 1/2 BX98 3 1015/1015 25 1765 1.875 940 3B5V64 B 1 7/8 3TB124 Q1 2 1/2 BX98 3 931/931 20 1765 1.625 930 3B5V56 B 1 5/8 3TB110 Q1 2 1/2 BX93 3 922/922 15 1770 1.625 890 2B5V64 B 1 5/8 2Q5V132 Q1 2 1/2 5VX1000 2 878/878 10 1755 1.375 770 2BK52H H 1 3/8 2TB110 Q1 2 1/2 BX90 2 761/761
7.5 1760 1.375 720 2BK52H H 1 3/8 2TB110 Q1 2 1/2 AX89 2 717/717 30 1765 1.875 850 25 1765 1.875 825 3B5V64 B 1 7/8 3R5V140 R1 3 5VX1120 3 825/825 15 1770 1.625 680 2B5V64 B 1 5/8 2B160R R1 3 BX112 2 728/728 10 1755 1.375 600 2BK52H H 1 3/8 2B154R R1 3 BX105 2 548/548
7.5 1760 1.375 550 2BK52H H 1 3/8 2B154R R1 3 BX105 2 549/549 40 1770 2.125 780 30 1765 1.875 750 3B5V70 B 1 7/8 3B160R R1 3 BX120 3 790/790 25 1765 1.875 720 3B5V64 B 1 7/8 3B160R R1 3 BX120 3 725/725 20 1765 1.625 650 3B5V56 B 1 5/8 3B154R R1 3 BX113 3 663/663 15 1770 1.625 600 2B5V64 B 1 5/8 2B200R R1 3 BX123 2 584/584 10 1755 1.375 520 2BK52H H 1 3/8 2B160R R1 3 BX112 2 528/528
7.5 1760 1.375 480 2BK52H H 1 3/8 2B184R R1 3 BX116 2 461/461 60 1775 2.375 720 50 1770 2.125 680 4B5V70 B 2 1/8 45V1870E E 3 5VX1320 4 676/676 40 1770 2.125 650 3B5V68 B 2 1/8 35V1870E E 3 5VX1320 3 657/657 30 1765 1.875 580 3B5V70 B 1 7/8 3R5V212 R1 3 5VX1400 3 594/594 25 1765 1.875 550 3B5V64 B 1 7/8 3B200R R1 3 AX128 3 555/555 20 1765 1.625 500 3B5V56 B 1 5/8 3B200R R1 3 BX128 3 513/513 15 1770 1.625 450 2B5V64 B 1 5/8 2B250R R1 3 AX136 2 444/444 10 1755 1.375 400 2BK52H H 1 3/8 2B200R R1 3 AX128 2 392/392
RPM
MOTOR
SHAFT
SIZE (in.)
FAN RPM
FAN
SHAFT
SIZE (in.)
2.5
3
3
3
DRIVE
SHEAVE
BROWNING
4B5V70 B 2 1/8 4R5V103 R1 2 1/2 5VX1000 4 1232/1232
3B5V70 B 1 7/8 3R5V150 R1 3 5VX1120 3 841/841
3B5V68 B 2 1/8 3R5V160 R1 3 5VX1230 3 768/768
4B5V70 B 2 3/8 4B174R R1 3 BX133 4 693/693
BUSHING
TYPE
DRIVEN
SHEAVE
BROWNING
BUSHING
TYPE BELTS
QTY OF
BELTS
FAN SPEED
(rpm)
Table 6 — Refrigerant Charge
(NOMINAL CAPACITY, TONS) UNIT CONFIGURATION
UNIT SIZE
N
(75)
P
(90)
Q
(105)
R
(120)
S
(130)
T
(150)
Standard Capacity Standard Efficiency 46.5 52.6 46.5 69.6
High Capacity Standard Efficiency 62.9 69.0 62.9 86.0 Standard Capacity High Efficiency 50.2 56.5 50.2 73.5
High Capacity High Efficiency 67.0 73.5 67.0 90.5
Standard Capacity Standard Efficiency 55.4 52.0 55.4 71.5
High Capacity Standard Efficiency 67.8 68.5 67.8 88.3 Standard Capacity High Efficiency 59.0 57.2 59.0 76.7
High Capacity High Efficiency 73.8 73.8 73.8 94.0
Standard Capacity Standard Efficiency 71.5 67.9 71.5 87.4
High Capacity Standard Efficiency 89.5 81.9 89.5 101.4 Standard Capacity High Efficiency 77.5 72.9 77.5 92.4
High Capacity High Efficiency 91.6 88.2 91.6 107.7
Standard Capacity Standard Efficiency 59.9 57.1 59.9 76.6
High Capacity Standard Efficiency 80.3 77.1 80.3 96.6 Standard Capacity High Efficiency 66.5 63.3 66.5 82.8
High Capacity High Efficiency 87.1 83.3 87.1 102.8
Standard Capacity Standard Efficiency 84.9 81.2 84.9 100.7
High Capacity Standard Efficiency 106.0 99.5 106.0 119.0 Standard Capacity High Efficiency 84.5 80.7 84.5 100.2
High Capacity High Efficiency 105.5 99.0 105.5 118.5
Standard Capacity Standard Efficiency 82.5 82.0 82.5 101.5
High Capacity Standard Efficiency 103.5 101.2 103.5 121.7
CHARGE (LB) CHARGE (LB)
UNITS WITHOUT HUMIDI-MIZER
SYSTEM
Circuit A Circuit B Circuit A Circuit B
®
UNITS WITH HUMIDI-MIZER®
SYSTEM
11
G SUPPORT
TO END OF PEDESTAL
SEE CONDENSER
SECTION
DIMENSIONS ARE SHOWN IN INCHES. DIMENSIONS IN [ ] ARE IN MILLIMETERS.
SEE CONDENSER
SECTION
Fig. 3 — Roof Curb
12
48N Roof Curb Sizes N, P, Q
(75-105 Ton Nominal Capacity)
* Use Applied Rooftop Builder program to select the proper roof curb.
48N Roof Curb Sizes R, S, T
(120-150 Ton Nominal Capacity)
Fig. 3 — Roof Curb (cont)
PART NUMBER*
DIMENSION
A (in.)
DIMENSION
B (in.)
DIMENSION
C (in.) CRRFCURB225A00 361.11 258.61 49.50 CRRFCURB226A00 376.20 273.70 49.50 CRRFCURB227A00 385.11 282.61 49.50 CRRFCURB228A00 400.20 297.70 49.50 CRRFCURB229A00 427.61 325.11 49.50 CRRFCURB230A00 439.86 337.36 49.50 CRRFCURB231A00 442.70 340.20 49.50 CRRFCURB232A00 451.61 349.11 49.50 CRRFCURB233A00 454.95 352.45 49.50 CRRFCURB234A00 463.86 361.36 49.50 CRRFCURB235A00 466.70 364.20 49.50 CRRFCURB236A00 475.86 373.36 49.50 CRRFCURB237A00 478.95 376.45 49.50 CRRFCURB238A00 488.11 385.61 49.50 CRRFCURB239A00 490.95 388.45 49.50 CRRFCURB240A00 499.86 397.36 49.50 CRRFCURB241A00 503.20 400.70 49.50 CRRFCURB242A00 512.11 409.61 49.50 CRRFCURB243A00 514.95 412.45 49.50 CRRFCURB244A00 527.20 424.70 49.50 CRRFCURB245A00 536.36 433.86 49.50 CRRFCURB246A00 551.45 448.95 49.50 CRRFCURB247A00 560.36 457.86 49.50 CRRFCURB248A00 575.45 472.95 49.50
PART NUMBER*
DIMENSION
A (in.)
DIMENSION
B (in.)
DIMENSION
C (in.) CRRFCURB261A00 386.04 283.54 49.50 CRRFCURB262A00 398.04 283.54 61.50 CRRFCURB263A00 410.04 307.54 49.50 CRRFCURB264A00 422.04 307.54 61.50 CRRFCURB265A00 440.29 325.79 61.50 CRRFCURB266A00 452.54 350.04 49.50 CRRFCURB267A00 464.54 350.04 61.50 CRRFCURB268A00 464.79 362.29 49.50 CRRFCURB269A00 476.54 374.04 49.50 CRRFCURB270A00 476.79 362.29 61.50 CRRFCURB271A00 488.54 374.04 61.50 CRRFCURB272A00 488.79 386.29 49.50 CRRFCURB273A00 500.79 398.29 49.50 CRRFCURB274A00 500.79 386.29 61.50 CRRFCURB275A00 512.79 398.29 61.50 CRRFCURB276A00 513.04 410.54 49.50 CRRFCURB277A00 524.79 422.29 49.50 CRRFCURB278A00 525.04 410.54 61.50 CRRFCURB279A00 536.79 422.29 61.50 CRRFCURB280A00 537.04 434.54 49.50 CRRFCURB281A00 549.04 434.54 61.50 CRRFCURB282A00 561.29 458.79 49.50 CRRFCURB283A00 573.29 458.79 61.50 CRRFCURB284A00 585.29 482.79 49.50 CRRFCURB285A00 597.29 482.79 61.50
13
Fig. 4 — Roof Curb Condenser Section
Roof Curb Condenser Support
UNIT SIZE
NOMINAL TONS
COND COILS 2V COND COIL 3V
DIM.
D
DIM.
E
DIM.
F
DIM.
G
75 ALL YES 129.50 10.98 131.75±0.75 133.50
90 STD EFFICIENCY YES 129.50 10.98 131.75±0.75 133.50
90 HIGH EFFICIENCY YES 181.50 10.36 183.75±0.75 183.25
105 STD EFFICIENCY YES 129.50 10.98 131.75±0.75 133.50
105 HIGH EFFICIENCY YES 181.50 10.36 183.75±0.75 183.25
120 STD EFFICIENCY YES 129.50 10.98 131.75±0.75 133.50
120 HIGH EFFICIENCY YES 181.50 10.36 183.75±0.75 183.25
130 ALL YES 181.50 10.36 183.75±0.75 183.25
150 ALL YES 181.50 10.36 183.75±0.75 183.25
ACCESSORY PART
NUMBER
CRRFCURB286A00 129.50 10.98
CRRFCURB287A00 181.50 10.36
DIMENSIONS ARE SHOWN IN INCHES. DIMENSIONS IN [ ] ARE IN MILLIMETERS.
14
Step 5 — Install Curb Gasketing — After ductwork
SUPPLY
RETURN
1
2
3
4
5 ALONG SUPPLY SECTION END RAIL
Fig. 5 — Gasket Location on Roof Curb
a48-8724
5
5
Fig. 6 — Gasket Location — Condenser Section Roof Curb
has been connected to the roof curb, apply gasket material
1
(
/2-in. thick x 11/2-in. wide neoprene) where indicated.
Single-Thickness Gasketing (See Fig. 5 for Item Numbers) — Apply gasketing in the following places:
1. Along both side rails (1) — 2 places, full length
2. Along return air end rail (2) — 1 place
3. Around return air internal duct flange (3) — 1 or 2 places
4. Around supply air internal duct flanges (4) — 3 places
5. Along supply section base rail (5) — 1 place
Condenser Section Roof Curb (See Fig. 6)
— Apply single-
thickness gasket along both side rails (5).

Step 6 — Install Field-Fabricated Ductwork

WARNING
For vertical supply and return units, tools or parts could drop into ductwork and cause an injury. Install a 90-degree elbow in the supply and return ductwork between the unit and the conditioned space. If a 90-degree elbow cannot be installed, then a grille of sufficient strength and density should be installed to prevent objects from falling into the conditioned space. Failure to follow these instructions could result in personal injury or property damage due to falling objects.
Field-fabricated ductwork for vertical supply/vertical return units must be attached to the roof curb, or to the support steel, prior to the final rigging and installation of the unit. Supply and return duct dimensions are shown in Fig. 3.
To attach ductwork to roof curb, insert duct approximately 10 to 11 in. up into roof curb. Connect ductwork to 14-gage roof curb material with sheet metal screws driven from inside the duct.
Secure all ducts to the building structure, using flexible duct connectors between roof curbs and ducts as required. Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier. Outlet grilles must not lie directly below unit discharge.
Design supply duct strong enough to handle expected static pressures. Field-fabricated ductwork for horizontal supply/return units must be attached to the unit.
Step 7 — Rig Unit — Do not drop unit; keep upright.
Step 8 — Connect Condensate Drain — The drain
is a 2-in. FPT pipe connection located on the right-hand side of the unit looking at the unit from the return air end. See Fig. 11 and 12. Figure 13 shows the additional length of units with an extended chassis.
With field-supplied fittings and pipe sections, plumb the pri­mary condensate drain to the 2-in. FPT connector on the base rail. Use a trap height of at least 7 inches. See Fig. 14 and 15. Apply a bead of RTV or similar sealant around the pipe joint at the connector in the base rail.
15
Fig. 7 — 48N 75-150 Ton Non-Split Rigging
Econ, Bar Rel, Standard filters, High Cap Evap, High Efficiency, High Static Supply Fan w/ largest motor, High Static PE w/ largest motor, No Heat, No Post section, No Humidimizer, No Extended Chassis, No Split, No Field Filter Section
Econ, Bar Rel, Standard filters, High Cap Evap, High Efficiency, High Static Supply Fan w/ largest motor, High Static Power Exhaust w/ Largest motor, Low gas he
at, No Post section, No Extended chassis, No humidimizer, No Split, No Field filter section
16
Fig. 8 — 48N 75-150 Ton Split (Main Unit) Rigging
Econ, Bar Rel, Cartridge filters, Hi Cap Evap, High Efficiency, High Static Supply Fan w/ largest motor, Hi Static Return Fan w/ largest motor, High Electric Heat, 8' Blank section w/ post filters, Extended chassis w/ humidimizer, Split, No Field filter section
Econ, Bar Rel, Cartridge filters, Hi Cap Evap, High Efficiency, High Static Supply Fan w/ largest motor, Hi Static Return Fan w/ largest motor, High gas heat, 8' Blank section w/ pos
t filters, Extended chassis
w/ humidimizer, Split, No Field filter
17
Fig. 9 — 48N 75-150 Ton Split (Return Section) Rigging
High Efficiency, High Static Supply Fan w/ largest motor, Hi Static Return Fan w/ largest motor, High Electric Heat, 8' Blank section w/ post filters, Extended chassis w/ humidimizer, Split, No Field filter section
Econ, Bar Rel, Cartridge filters, Hi Cap Evap, High Efficiency, High Static Supply Fan w/ largest motor,Hi Static Return Fan w/ largest motor, High gas heat, 8' Blank section w/ post filters
, Extended chassis
w/ humidimizer, Split, No Field filter
18
1
A
3
00
B
Cond End 0 0
Return End
00
24
NOMINAL
CAPACITY
(tons)
CORNER WEIGHTS (lb)
TOTAL (lb)
CENTER OF
GRAVITY
1234
A (in.) B (in.)
48 Series Non-Split
75
4,129 4,047 4,892 4,796 17,864 275.9 67.2
90
4,396 4,310 5,359 5,254 19,319 308.1 67.2
105
4,478 4,390 5,526 5,417 19,810 309.8 67.2
120
5,455 5,347 6,474 6,346 23,622 309.7 67.2
130
5,385 5,279 6,719 6,587 23,970 316.7 67.2
150
5,436 5,329 6,816 6,682 24,263 317.5 67.2
48 Series Split
75
4,684 4,592 5,690 5,578 20,544 355.1 67.2
90
4,969 4,871 6,273 6,149 22,261 390.3 67.2
105
5,052 4,952 6,544 6,415 22,964 394.8 67.2
120
6,058 5,939 7,583 7,443 27,013 401.0 67.2
130
5,972 5,854 7,845 7,691 27,361 409.6 67.2
150
6,021 5,903 7,944 7,787 27,654 410.3 67.2
Fig. 10 — Weight Distribution and Center of Gravity
a48-8793
19
20
Fig. 11 — 48N Unit Sizes N, P, Q (75-105 Ton Nominal Capacity)
Fig. 11 — 48N Unit Sizes N, P, Q (75-105 Ton Nominal Capacity) (cont)
NOMINAL
CAPACITY/
EFFICIENCY
EXTENDED
CHASSIS
SUPPLY
FAN
FIELD
USE
FILTER
SECTION
BLANK
SECTION
2-PIECE
UNIT
COND A B C D E F G H J K
75 ALL
90 STD EFF
105 STD EFF
NO
STD
NO
NO NO 2 498.11 314.42 48 177.02 266.07 499.35 202.75 119.76 313.36 4 FT YES 2 564.61 380.92 48 195.27 284.32 565.85 221.00 119.76 379.86 8 FT YES 2 612.86 429.17 48 195.27 284.32 614.10 221.00 119.76 428.11
YES
NO YES 2 576.86 393.17 48 255.77 344.82 578.10 281.50 119.76 392.11 4 FT YES 2 625.11 441.42 48 255.77 344.82 626.35 281.50 119.76 440.36 8 FT YES 2 673.36 489.67 48 255.77 344.82 674.60 281.50 119.76 488.61
HIGH
NO
NO NO 2 513.20 329.51 48 177.02 281.16 514.44 217.84 119.76 328.45 4 FT YES 2 579.70 396.01 48 195.27 299.41 580.94 236.09 119.76 394.95 8 FT YES 2 627.95 444.26 48 195.27 299.41 629.19 236.09 119.76 443.20
YES
NO YES 2 591.95 408.26 48 255.77 359.91 593.19 296.59 119.76 407.20 4 FT YES 2 640.20 456.51 48 255.77 359.91 641.44 296.59 119.76 455.45 8 FT YES 2 688.45 504.76 48 255.77 359.91 689.69 296.59 119.76 503.70
YES
STD
NO
NO NO 2 522.11 338.42 48 177.02 290.07 523.35 226.75 119.76 185.75 337.36 4 FT YES 2 588.61 404.92 48 195.27 308.32 589.85 245.00 119.76 204.00 403.86 8 FT YES 2 636.86 453.17 48 195.27 308.32 638.10 245.00 119.76 204.00 452.11
YES
NO YES 2 600.86 417.17 48 255.77 368.82 602.10 305.50 119.76 264.50 416.11 4 FT YES 2 649.11 465.42 48 255.77 368.82 650.35 305.50 119.76 264.50 464.36 8 FT YES 2 697.36 513.67 48 255.77 368.82 698.60 305.50 119.76 264.50 512.61
HIGH
NO
NO NO 2 537.20 353.51 48 177.02 305.16 538.44 241.84 119.76 185.75 352.45 4 FT YES 2 603.70 420.01 48 195.27 323.41 604.94 260.09 119.76 204.00 418.95 8 FT YES 2 651.95 468.26 48 195.27 323.41 653.19 260.09 119.76 204.00 467.20
YES
NO YES 2 615.95 432.26 48 255.77 383.91 617.19 320.59 119.76 264.50 431.20 4 FT YES 2 664.20 480.51 48 255.77 383.91 665.44 320.59 119.76 264.50 479.45 8 FT YES 2 712.45 528.76 48 255.77 383.91 713.69 320.59 119.76 264.50 527.70
90 HI EFF
105 HI EFF
NO
STD
NO
NO NO 3 550.11 314.42 48 177.02 266.07 551.35 202.75 171.76 313.36 4 FT YES 3 616.61 380.92 48 195.27 284.32 617.85 221.00 171.76 379.86 8 FT YES 3 664.86 429.17 48 195.27 284.32 666.10 221.00 171.76 428.11
YES
NO YES 3 628.86 393.17 48 255.77 344.82 630.10 281.50 171.76 392.11 4 FT YES 3 677.11 441.42 48 255.77 344.82 678.35 281.50 171.76 440.36 8 FT YES 3 725.36 489.67 48 255.77 344.82 726.60 281.50 171.76 488.61
HIGH
NO
NO NO 3 565.20 329.51 48 177.02 281.16 566.44 217.84 171.76 328.45 4 FT YES 3 631.70 396.01 48 195.27 299.41 632.94 236.09 171.76 394.95 8 FT YES 3 679.95 444.26 48 195.27 299.41 681.19 236.09 171.76 443.20
YES
NO YES 3 643.95 408.26 48 255.77 359.91 645.19 296.59 171.76 407.20 4 FT YES 3 692.20 456.51 48 255.77 359.91 693.44 296.59 171.76 455.45 8 FT YES 3 740.45 504.76 48 255.77 359.91 741.69 296.59 171.76 503.70
YES
STD
NO
NO NO 3 574.11 338.42 48 177.02 290.07 575.35 226.75 171.76 185.75 337.36 4 FT YES 3 640.61 404.92 48 195.27 308.32 641.85 245.00 171.76 204.00 403.86 8 FT YES 3 688.86 453.17 48 195.27 308.32 690.10 245.00 171.76 204.00 452.11
YES
NO YES 3 652.86 417.17 48 255.77 368.82 654.10 305.50 171.76 264.50 416.11 4 FT YES 3 701.11 465.42 48 255.77 368.82 702.35 305.50 171.76 264.50 464.36 8 FT YES 3 749.36 513.67 48 255.77 368.82 750.60 305.50 171.76 264.50 512.61
HIGH
NO
NO NO 3 589.20 353.51 48 177.02 305.16 590.44 241.84 171.76 185.75 352.45 4 FT YES 3 655.70 420.01 48 195.27 323.41 656.94 260.09 171.76 204.00 418.95 8 FT YES 3 703.95 468.26 48 195.27 323.41 705.19 260.09 171.76 204.00 467.20
YES
NO YES 3 667.95 432.26 48 255.77 383.91 669.19 320.59 171.76 264.50 431.20 4 FT YES 3 716.20 480.51 48 255.77 383.91 717.44 320.59 171.76 264.50 479.45 8 FT YES 3 764.45 528.76 48 255.77 383.91 765.69 320.59 171.76 264.50 527.70
Condenser Detail
UNIT
COND
COILS 2V
COND COIL 3VLOW
SOUND
DIMENSION
“S” 75 ALL YES NO 92.62 75 ALL YES YES 98.06
90 STANDARD EFFICIENCY YES NO 92.62
90 HIGH EFFICIENCY —YESYES 98.06
90 STANDARD EFFICIENCY YES YES 98.06
105 STANDARD EFFICIENCY YES NO 98.06
105 HIGH EFFICIENCY —YESYES 98.06
105 STANDARD EFFICIENCY YES YES 98.06
21
Fig. 12 — 48N Unit Sizes R, S, T (120-150 Ton Nominal Capacity)
139.88
BASE FRAME
A48-
22
Fig. 12 — 48N Unit Sizes R, S, T (120-150 Ton Nominal Capacity) (cont)
*Vertical discharge only.
NOMINAL
CAPACITY/
EFFICIENCY
EXTENDED
CHASSIS
HIGH
GAS
HEAT*
FIELD
USE
FILTER
SECTION
BLANK
SECTION
2-
PIECE
UNIT
COND A B C D E F G H J K
L
HI
L
MED
LOW
120 STD EFF
NO
NO
NO
NO NO 2 523.04 339.35 48 186.86 291.00 524.28 227.68 119.76 — 338.29 2 1.5 4 FT YES 2 589.54 405.85 48 205.11 309.25 590.78 245.93 119.76 — 404.79 2 1.5 8 FT YES 2 637.79 454.10 48 205.11 309.25 639.03 245.93 119.76 — 453.04 2 1.5
YES
NO YES 2 601.79 418.10 48 265.61 369.75 603.03 306.43 119.76 — 417.04 2 1.5 4 FT YES 2 650.04 466.35 48 265.61 369.75 651.28 306.43 119.76 — 465.29 2 1.5 8 FT YES 2 698.29 514.60 48 265.61 369.75 699.53 306.43 119.76 — 513.54 2 1.5
YES
NO
NO NO 2 535.04 339.35 60 186.86 291.00 536.28 227.68 119.76 2 4 FT YES 2 601.54 405.85 60 205.11 309.25 602.78 245.93 119.76 2 8 FT YES 2 649.79 454.10 60 205.11 309.25 651.03 245.93 119.76 2
YES
NO YES 2 613.79 418.10 60 265.61 369.75 615.03 306.43 119.76 2 4 FT YES 2 662.04 466.35 60 265.61 369.75 663.28 306.43 119.76 2 8 FT YES 2 710.29 514.60 60 265.61 369.75 711.53 306.43 119.76 2
YES
NO
NO
NO NO 2 547.04 363.35 48 186.86 315.00 548.28 251.68 119.76 195.56 362.29 2 1.5 4 FT YES 2 613.54 429.85 48 205.11 333.25 614.78 269.93 119.76 213.81 428.79 2 1.5 8 FT YES 2 661.79 478.10 48 205.11 333.25 663.03 269.93 119.76 213.81 477.04 2 1.5
YES
NO YES 2 625.79 442.10 48 265.61 393.75 627.03 330.43 119.76 274.31 441.04 2 1.5 4 FT YES 2 674.04 490.35 48 265.61 393.75 675.28 330.43 119.76 274.31 489.29 2 1.5 8 FT YES 2 722.29 538.60 48 265.61 393.75 723.53 330.43 119.76 274.31 537.54 2 1.5
YES
NO
NO NO 2 559.04 363.35 60 186.86 315.00 560.28 251.68 119.76 195.56 — 2 4 FT YES 2 625.54 429.85 60 205.11 333.25 626.78 269.93 119.76 213.81 — 2 8 FT YES 2 673.79 478.10 60 205.11 333.25 675.03 269.93 119.76 213.81 — 2
YES
NO YES 2 637.79 442.10 60 265.61 393.75 639.03 330.43 119.76 274.31 — 2 4 FT YES 2 686.04 490.35 60 265.61 393.75 687.28 330.43 119.76 274.31 — 2 8 FT YES 2 734.29 538.60 60 265.61 393.75 735.53 330.43 119.76 274.31 — 2
120 HI EFF
130 ALL
150 STD EFF
NO
NO
NO
NO NO 3 575.04 339.35 48 186.86 291.00 576.28 227.68 171.76 — 338.29 2 1.5 4 FT YES 3 641.54 405.85 48 205.11 309.25 642.78 245.93 171.76 — 404.79 2 1.5 8 FT YES 3 689.79 454.10 48 205.11 309.25 691.03 245.93 171.76 — 453.04 2 1.5
YES
NO YES 3 653.79 418.10 48 265.61 369.75 655.03 306.43 171.76 — 417.04 2 1.5 4 FT YES 3 702.04 466.35 48 265.61 369.75 703.28 306.43 171.76 — 465.29 2 1.5 8 FT YES 3 750.29 514.60 48 265.61 369.75 751.53 306.43 171.76 — 513.54 2 1.5
YES
NO
NO NO 3 587.04 339.35 60 186.86 291.00 588.28 227.68 171.76 2 4 FT YES 3 653.54 405.85 60 205.11 309.25 654.78 245.93 171.76 2 8 FT YES 3 701.79 454.10 60 205.11 309.25 703.03 245.93 171.76 2
YES
NO YES 3 665.79 418.10 60 265.61 369.75 667.03 306.43 171.76 2 4 FT YES 3 714.04 466.35 60 265.61 369.75 715.28 306.43 171.76 2 8 FT YES 3 762.29 514.60 60 265.61 369.75 763.53 306.43 171.76 2
YES
NO
NO
NO NO 3 599.04 363.35 48 186.86 315.00 600.28 251.68 171.76 195.56 362.29 2 1.5 4 FT YES 3 665.54 429.85 48 205.11 333.25 666.78 269.93 171.76 213.81 428.79 2 1.5 8 FT YES 3 713.79 478.10 48 205.11 333.25 715.03 269.93 171.76 213.81 477.04 2 1.5
YES
NO YES 3 677.79 442.10 48 265.61 393.75 679.03 330.43 171.76 274.31 441.04 2 1.5 4 FT YES 3 726.04 490.35 48 265.61 393.75 727.28 330.43 171.76 274.31 489.29 2 1.5 8 FT YES 3 774.29 538.60 48 265.61 393.75 775.53 330.43 171.76 274.31 537.54 2 1.5
YES
NO
NO YES 3 629.29 381.60 60 205.11 333.25 630.53 269.93 171.76 213.81 — 2 4 FT YES 3 677.54 429.85 60 205.11 333.25 678.78 269.93 171.76 213.81 — 2 8 FT YES 3 725.79 478.10 60 205.11 333.25 727.03 269.93 171.76 213.81 — 2
YES
NO YES 3 689.79 442.10 60 265.61 393.75 691.03 330.43 171.76 274.31 — 2 4 FT YES 3 738.04 490.35 60 265.61 393.75 739.28 330.43 171.76 274.31 — 2 8 FT YES 3 786.29 538.60 60 265.61 393.75 787.53 330.43 171.76 274.31 — 2
Condenser Detail
UNIT
COND
COILS 2V
COND
COIL 3V
LOW
SOUND
DIMENSION
“S”
120 STANDARD EFFICIENCY YES NO 96.62
120 HIGH EFFICIENCY —YESYES 102.06 120 STANDARD EFFICIENCY YES YES 102.06 130 STANDARD EFFICIENCY —YESNO 96.62
130 HIGH EFFICIENCY —YESYES 102.06 150 STANDARD EFFICIENCY —YESYES 102.06
23
Fig. 13 — Units with Optional Extended Chassis — Location of Coil Tracks
B
"J"
AUXILIARY COIL LOCATION
Auxiliary Coil Location — in.
UNIT
SIZES 48N (TONS)
HEIGHT B DISTANCE J
N, P, Q (75-105) 12.85
See dimension J on certified
drawings, pages 21-24
R, S, T (120-150) 12.85
Fig. 14 — Primary Drain Connection
A = 7-in. (178 mm) min
Fig. 15 — Condensate Drain Piping Details
(Slab and Curb Mounted)
SEALANT
3 IN DRAIN
INSIDE OF BASE RAIL
A MIN.
A/2
UNIT CURB
UNIT BASE RAIL
DRAIN PIPE IS FIELD SUPPLIED
Step 9 — Install Outdoor Hoods — Unit sizes 75
to 105 nominal tons will have three hoods on both sides. Unit sizes 120 to 150 nominal tons will have four hoods on both sides. Reference images shown are for three hoods. However, assembly of four hoods for the larger units is the same. Instruc­tions for unpacking and assembly of hoods are below.
1. For shipping, outdoor air hoods are packaged in a box lo­cated inside the unit.
2. Remove the box from the unit (see Fig.16). a. Shipping support straps are bolted to the unit.
Remove four bolts on each, and discard straps.
b. Remove the hood supports (quantity 2 or 3 for
larger units) (see Fig. 17). c. Remove packaging from the unit. d. Reinstall hood supports (Fig. 17).
3. Remove filters located between return/exhaust fan and economizer dampers; these are packaged separately from hoods for shipping (see Fig. 16). Screws, other hardware and seal strips are packaged with the outdoor hoods (Fig. 16).
4. Apply seal strip to the unit. Strip should extend around entire opening (see Fig. 18).
5. Assemble hoods (see Fig. 19). a. Attach hood sides (Items 1 and 2) to the hood top
(Item 3). Fasten hood using six screws on each side. b. Attach hood support (Item 4) to hood top (Item 3). c. Attach angle (Item 5) to hood sides (two per hood).
Fasten angle to the hood side using three screws
per side. d. Attach hood support (Item 7) to top (Item 3) using
six screws. e. Attach clips (Item 8) to hood support (Item 7). f. Attach angle (Item 10) to hood support (Item 7)
using eight screws. g. Attach angle (Item 9) to angle (Item 10) using two
pop rivets. h. Place RTV or similar sealant on all of the 6 corners
to prevent water leaks. i. Install hood assembly to unit using four screws on
each side and nine screws on the top. j. Install filters (Item 6) to hood assembly.
6. Repeat Step 5 for each hood.
24
FILTERS
PACKAGING
OUTDOOR
HOODS
(BOTH SIDES)
SHIPPING SUPPORT STRAPS
Fig. 16 — Packaging Locations
a48-8725
HOOD SUPPORTS
(BOTH SIDES)
Fig. 17 — Hood Supports
a48-8726
SEAL STRIP
SEAL STRIP
Fig. 18 — Seal Strips
a48-8727
Fig. 19 — Hood Assembly
a48-8728
3
4
9
1
8
2
5
7
10
6
Step 10 — Route Field Wiring — Field power wir-
ing is brought into the unit through the back of the power box near the bottom. Wiring can be brought through the roof curb through field-supplied watertight connections. See Fig. 20.
There are two 3
power box and a 7/8-in. hole in the side post for 24-v control wiring provided. Field-supplied couplings must be used when routing wiring into the control box.
See Fig. 20 for recommended disconnect location.
25
5
/8-in. holes for field power wiring in the

Step 11 — Make Field Electrical Connections

RECOMMENDED FIELD-SUPPLIED DISCONNECT LOCATION
Fig. 20 — Disconnect Location
CAUTION
Use care when drilling into corner post to avoid damage to con­denser coil.
a48-8729
IMPORTANT: All units have variable frequency drives (VFD) factory installed. VFDs generate, use, and can radi­ate radio frequency energy. If units are not installed and used in accordance with these instructions, they may cause radio interference. They have been tested and found to comply with limits of a Class A computing device pursu­ant to International Standard EN 61000-2/3, which are designed to provide reasonable protection against such interference when operated in a commercial environment.
POWER WIRING — Units are factory-wired for the voltage shown on the unit nameplate. The main terminal block is suit­able for use with copper wires only. Maximum wire size varies according to disconnect size.
DISCONNECT SIZE
250 Amps 400 Amps 600 Amps
QUANTITY...MAXIMUM WIRE SIZE
(MCM)
1...300
1...600
2...600
NOTE: Conduit used for field wiring must be sealed at the unit end of the conduit. Failure to do so could cause the conduit to act as a chimney in cold climates causing warm building air to condense in the power box.
Units without Factory-Installed Disconnect
— When install­ing units, provide a disconnect per NEC (National Electrical Code) of adequate size (MOCP [maximum overcurrent protec­tion] of unit is on the informative plate). All field-wiring must comply with NEC and all local codes. Size wire based on MCA (minimum circuit amps) on the unit informative plate. See Fig. 21 for power wiring connections to the unit power terminal block and equipment ground. Maximum wire size is two (2) 500 MCM (maximum wire size) conductors per pole.
Units with Factory-Installed Disconnect
— The factory­installed disconnect is an interlocking, door-type. The discon­nect handle locks the door when it is in the ON position. The disconnect handle must be in the OFF position to open the con­trol box door. The disconnect is located in the power box be­hind the power box door for all units. See Fig. 22.
All field wiring must comply with NEC and all local codes. Wire must be sized based on MCA (minimum circuit amps) on the unit informative plate. See Fig. 23 for power wiring con­nections to the unit disconnect and equipment ground.
Operating Voltage
— Operating voltage to the unit must be
within the voltage range indicated on the unit nameplate.
Use the following formula to determine the percentage of
voltage imbalance.
Voltage Imbalance
= 100 x
max voltage deviation from average voltage
average voltage
Example: Supply voltage is 460-3-60. AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
452 + 464 + 455
1371
=
3
= 457
Determine maximum deviation from average voltage: (AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v
Maximum deviation is 7 v. Determine percent voltage imbalance:
% Voltage Imbalance = 100 x
7
457
= 1.53%
This amount of phase imbalance is satisfactory as it is be-
low the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact local utility immediately.
Unit failure as a result of operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components.
26
3
21
11
22
12
23
13
DISCONNECT PER NEC
EQUIP GND
TB1
LEGEND
Fig. 21 — Field Power Wiring Connections
EQUIP — Equipment GND — Ground NEC — National Electrical Code TB — Terminal Block
a48-8466
POWER
Fig. 22 — Factory-Installed Disconnect Location
(End of Unit Shown)
a48-8730
23
13 12 11
22 21
DISCONNECT
PER NEC
EQUIP
GND
FIELD WIRE
FACTORY WIRE
Fig. 23 — Field Power Wiring Connections
for Factory-Installed Disconnect
LEGEND
EQUIP — Equipment GND Ground NEC National
Electrical Code
WIRING ENTRY
NOMINAL
HP
FACTORY-INSTALLED DISCONNECT HANDLE LOCATION
BkW MAX BHP MAX BkW
7.5 5.6 8.6 6.39 12.0 10.0 91.7 10 7.5 11.5 8.56 14.3 12.0 91.7 15 11.2 17.3 12.89 22.0 19.0 93.0 20 14.9 22.9 17.10 28.7 23.0 93.6 25 18.7 28.7 21.41 36.3 28.4 93.6 30 22.4 34.5 25.71 41.7 36.3 94.1 40 29.8 45.9 34.27 55.0 43.8 94.1 50 37.3 57.4 42.83 71.0 52.8 94.5 60 44.8 68.9 51.41 83.0 60.5 95.0 75 59.5 86.1 64.25 101.0 80.5 95.0
100 74.6 114.8 85.67 132.0 106.0 95.4
LEGEND
Bhp — Brake Horsepower BkW — Brake Kilowatts
NOTE: Extensive motor and electrical testing on the Carrier units has ensured that the full horsepower range of the motor can be uti­lized with confidence. Using fan motors up to the horsepower ratings shown in the Motor Limitations table will not result in nuisance trip­ping or premature motor failure. Unit warranty will not be affected.
Table 7 — Motor Limits
MAX AMPS (EA)
460 V 575 V
27
RATED
EFFICIENCY
Step 12 — Connect Air Pressure Tubing — Be-
fore options such as the variable frequency drive (VFD) and/or modulating power exhaust can operate properly, the pneumatic tubing for pressure sensing must be installed. Use fire-retardant plenum tubing (field-supplied). All control devices use tubing. Tubing must be run from the appropriate sensing loca­tion (in the duct or in the building space) to the control device location in the unit.
VARIABLE FREQUENCY DRIVE — The tubing for the duct pressure (DP) control option should sample supply duct pressure approximately
2
/3 of the way out from the unit in the main trunk duct, at a location where a constant duct pressure is desired.
On these units, the duct pressure is sensed by a pressure transducer. The pressure transducer output is directed to the unit control module. On all sizes, the DP transducer is located in the unit control box. See Fig. 24 for control box details. Use a nominal
1
/4-in. plastic tubing.
Refer to appropriate base unit Controls, Start-Up, Opera­tion, Service and Troubleshooting book for instructions on ad­justing set points for duct pressure controls.
POWER EXHAUST — The tubing for the building pressure (BP) control (achieved via the modulating power exhaust op­tion) should sample building pressure in the area near the en­trance lobby (or other appropriate and sensitive location) so that location is controlled as closely to design pressures as possible.
These units use a pressure transducer for sensing building pressure. The BP transducer is located in the unit control box. Use a nominal
1
/4-in. plastic tubing.
For instructions on adjusting BP control set points, refer to the Controls, Start-Up, Operation, Service, and Troubleshooting book.
RETURN FAN — The tubing for the building pressure (BP) control (achieved via the return fan option) should sample building pressure in the area near the entrance lobby (or other appropriate and sensitive location) so that location is controlled as closely to design pressures as possible.
The units use a pressure transducer for sensing building pressure. The BP transducer is located in the unit control box. Use a nominal
1
/4-in. plastic tubing. For instructions on
1
/4-in.
adjusting BP control set points, refer to the Controls, Start­Up, Operation, Service, and Troubleshooting book.
Step 13 — Remove Supply-Fan Shipping Bracket Screws —
must be removed from each corner of the fan sled before start­ing unit. See Fig. 25.
1. To remove shipping bracket screws, raise fan sled by turning adjusting bolt counterclockwise until spring is compressed slightly.
2. Remove screws holding shipping bracket to spring sup­port.
NOTE: It is not necessary to remove the shipping brack­et, only remove the screws.
3. After removing all shipping bracket screws, level fan sled using the adjusting screws.
Supply-fan shipping bracket screws
Step 14 — Remove Optional Power Exhaust Shipping Bracket Screws — Optional power exhaust
shipping bracket screws must be removed from each corner of the fan sled before starting unit.
1. To remove shipping bracket screws, raise fan sled by turning adjusting bolt counterclockwise until spring is compressed slightly.
2. Remove screws holding shipping bracket to spring sup­port.
NOTE: It is not necessary to remove the shipping brack­et, only remove the screws.
3. After removing all shipping bracket screws, level fan sled using the adjusting screws.
Step 15 — Remove Optional Return-Fan Ship­ping Brackets —
must be removed from each corner of the fan sled before start­ing unit. See Fig. 26.
To remove shipping brackets, remove 2 screws holding
each bracket to the cross rail. There are 4 brackets per unit.
After removing all shipping brackets, level the fan using the
adjustment screws.
Optional return fan shipping brackets
28
Fig. 24 — Control Box Component Arrangement
a48-8731
29
Fig. 25 — Supply Fan and Power Exhaust Fan Shipping Bracket Bolts
a48-8732
RETURN FAN SHIPPING BRACKET BOLTS
Fig. 26 — Return Fan Shipping Bracket Bolts
a48-8733
SHIPPING BRACKET SCREWS (4) EACH SPRING
SPRING SUPPORT
Step 16 — Connect Gas Piping — Unit is equipped
for use with natural gas only. Installation must conform with local building codes, or in the absence of local codes, with the National Fuel Gas Code (NFGC), ANSI Z223.1.
1
A
/8-in. NPT tapping plug, accessible for test gage connec­tion, must be field-installed immediately upstream of gas sup­ply connection to unit, but after manual gas valve. See Fig. 27. Natural gas pressure at unit gas connection must not be less than 5 in. wg or greater than 13 in. wg.
Size gas supply piping for 0.5 in. wg maximum pressure
drop. Do not use supply pipe smaller than unit gas connection.
CAUTION
Disconnect gas piping from unit when leak testing at pres­sures greater than 0.5 psig. Pressures greater than 0.5 psig will cause gas valve damage resulting in a hazardous con­dition. If gas valve is subjected to pressure greater than
0.5 psig, it must be replaced.
Step 17 — Configure Optional Modulating Gas Control —
dered with an optional factory-installed modulating gas control system that monitors heating operation of the rooftop.
Refer to the Controls, Start-Up, Operation, Service, and Troubleshooting book for information on configuring the mod­ulating gas control.
30
The 48N Series large rooftop units may be or-
Step 18 — Install Flue/Inlet Hoods — The
*NPT plug is field supplied. NOTE: Follow all local codes.
OUTLET FLUE HOOD
INLET HOOD
INLET
HOOD
Fig. 28 — Flue/Inlet Hood Locations
a48-8734
Fig. 29 — Flue Outlet Hood
flue/inlet hoods are shipped in a package taped to the basepan in the fan section. The flue (outlet) hoods are pre-assembled. The inlet hoods require assembly.
The hoods are to be installed on the heating section access panel as shown in Fig. 28. See Table 8 for a list of parts used to assemble each hood and quantities of each hood type used with each unit.
1. Remove shipping block-offs and shipping tape from all openings in the access panel.
2. Attach flue outlet hoods (see Fig. 28) to access panel using screws provided. Hoods are placed over each combustion outlet.
3. Inlet hoods are shipped unassembled and must be as­sembled on the access panel (see Fig. 29-31). Flanges of the hood top and sides should be installed on the in­side of the access panel openings with the screws pro­vided. The sides should be placed on the inside of the top hoods for all hood assemblies (6-in. and 14-in.). Attach speed clips to screen. Insert screen into bottom opening of 6-in. and 14-in. hoods and secure it with 3 screws. Attach view port cover over 14-in. inlet hood opening (Fig. 31). Secure with two screws.
Table 8 — Flue Hood and Inlet Hood Usage
Sizes 75-105
(Low Heat)
—— — — 3 3 3
23 3 4 3 4 4
HOOD TYPE PART LIST
Top (6-in.)
6-in. Inlet Hood
14-in. Inlet Hood
Flue Outlet Hood
Side (Left) Side (Right) Screen Speed Clips Screws
Top (14-in.) Side (Left) Side (Right) Screen Speed Clips Screws View Port Cover
Pre-assembled 2 3 3 4 3 4 5
Size 75
(High Heat)
Sizes 90, 105
(Medium Heat)
QUANTITY USED
Sizes 90, 105
(High Heat)
Sizes 120-150
(Low Heat)
Sizes 120-150
(Medium Heat)
Sizes 120-150
(High Heat)
31
Fig. 30 — Inlet Hood Assembly (6-in. and 14-in.)
VIEW PORT COVER
Fig. 31 — Inlet Hood View Port Cover
Installation (14-in.)
ACCESS PANEL OPENING
SIDE (TYP BOTH SIDES)
COVER (14-IN. HOOD ONLY)
SCREEN
SPEED CLIP
(TYP 3)
HOOD
Step 19 — Install Supply-Air Thermistors (Modulating Gas Units Only) — Supply-air therm-
istors are a field-installed, factory-provided component. Three supply-air thermistors are shipped with modulating gas units inside the unit control box. Thermistor wires must be connected to the SGC (staged gas control) in the unit control box. See Table 9. The supply-air thermistors should be located in the supply duct with the following criteria:
• downstream of the heat exchanger cells
• equally spaced as far as possible from the heat exchanger cells
• a duct location where none of the supply air thermistors are within sight of the heat exchanger cells
• a duct location with good mixed supply air
Table 9 — SGC Thermistor Designations
Step 20 — Install Unit Accessories — For appli-
cations requiring accessories, the following packages are available:
All units:
• space temperature sensor
•CO
sensor
2
• space temperature sensor with CO
• airflow switch
• filter switch
• smoke detector Refer to the individual accessory installation instruc-
tions in each accessory package for information on install­ing accessories.
sensor
2
THERMISTOR
SAT1 J8 – 1,2 (SGC)
SAT2 J8 – 3,4 (SGC)
SAT3 J8 – 5,6 (SGC)
LIMTTEMP J8 – 15,16 (SGC)
SGC — Staged Gas Controller
PIN
CONNECTION
POINT
FUNCTION AND LOCATION
Thermistors
Supply-Air Thermistor (SAT) — Inserted into supply section underneath the gas heat section (factory-provided, field-installed)
Supply-Air Thermistor (SAT) — Inserted into supply section underneath the gas heat section (factory-provided, field-installed)
Supply-Air Thermistor (SAT) — Inserted into supply section underneath the gas heat section (factory-provided, field-installed)
Limit switch Thermistor (LIMTTEMP) — Inserted next to the lower limit switch (factory-installed)
32
PART NO.
HH79NZ033
TOP RAIL
GUIDES
BASE RAIL
GUIDES
a50-8877
Fig. 32 — Base and Top Rail Guide Locations
a50-8878
Fig. 33 — Base Rail Guide
TOP RAIL GUIDE
a50-8879
Fig. 34 — Top Rail Guide

Two-Piece Unit Fit Up

1. Locate and remove split parts package from return sec­tion of unit. Open package and remove split unit parts. See Tables 10 and 11 for parts list.
2. Rig main unit section and return section separately.
3. Do not assemble main unit section and return section on ground and attempt to lift. Unit pieces must be assembled on roof curb.
4. Insert base rail guides into the base rails of the main unit section. Do not attach with screws yet. See Fig. 32 and 33.
5. Insert top rail guides into top rails of the main unit sec­tion. Do not attach with screws yet. See Fig. 32 and 34.
6. Rig and set the main unit section on the unit roof curb. Align the unit bulkhead with the supply opening in the roof curb.
7. Remove the roof cap, top cover and L brackets from the filter end of the return section. Save these parts for later installation. See Fig. 35 and 36.
8. Rig and set return section onto the roof curb using rail guides as an alignment aid. The return section must be within 2 in. of the main unit section. Slide base rail and top rail guides from main unit section rails partially into return section rails.
9. Install tar tape on edge of main unit base rails to seal base rail splice. See Fig. 37.
10. Using ¾-in. x 30-in. threaded rod, nuts, washers and backing plates provided, pull and secure the base rails to­gether. See Fig. 38.
11. Attach (4) brackets to top rails. Using threaded rods, nuts, washers and backing plates provided, pull the top rails together and secure with top rail guide from Step 5. See Fig. 39. Remove threaded rods and brackets after securing top rail guide.
12. Place seal strip along both sides of basepan joint. Attach basepan covers to basepan joint. See Fig. 40.
13. Install L brackets, top cover and top cap joining main unit section and return section top cover assemblies. See Fig. 41 and 42.
14. Connect control wiring plugs located at unit split. All same color plugs should be connected together.
On units equipped with return air fan or power exhaust fan option, locate black, yellow, and blue power wires lo­cated at the split in main section. Run the wires through the grommet below the return air filters and through the grommet at the economizer damper. See Fig. 43. Run wires through wire trays, separate from control wires, to the return fan/power exhaust fan VFD on back wall of re­turn section. Connect wires to VFD power terminal con­nections: Black to UL1, Yellow to V1, and Blue to W1. On units equipped with VFD bypass option connect the wires to the power distribution in the VFD bypass box: Black to L1, Yellow to L2, and Blue to L3. See Fig. 44.
Connect air pressure tubes located at split. All same num­bered tubes should be connected together. See Table 12 for tubes associated with unit options.
15. Install side post on far side of unit. See Fig. 45.
16. Install side panels at main unit section/return section split. Install panel side brackets, 2 on each panel. See Fig. 45.
3
/8-in. x 6-in.
BASE RAIL GUIDE
33
Table 10 — 75-105 Nominal Ton Units Parts List
ITEM COMPONENT NUMBER QUANTITY COMPONENT NAME COMPONENT QUALIFIER
1 48NG501939 2 RAIL,MOUNTING SPLIT,BASE,GUIDE
3
2 48NG501935 2 ROD,THREADED 3 48NG501937 8 WASHER,PLATE 4 AU02AB361 4 WASHER,FLAT 5 AT11AB361 6 NUT,HEAVY HEX
/4-10 UNC 2A 30-in. L
3
/4-in. LRT SPLIT
3
/
4
3
/4-10
6 48NG501938 4 BRACKET,TIE LRT SPLIT TOP 7 AL48AM307 12 SCREW,HEXHD SR 8 48NG501936 2 ROD,THREADED 9 AU02AB242 4 WASHER,FLAT
10 AT39AB241 4 NUT,HEX
1
/4 X 5/
3
/8-16
8
3
/
8
3
/8-16 UNC 2A 6" L
11 48NG501940 1 PLATE,COVER SPLIT,BASEPAN 12 48NG501941 1 PLATE,COVER SPLIT,BASEPAN 15 AL31AY308 34 SCREW 16 AL79AU216 2 SCREW,HEXHD TF #10 X 1/2 17 48NG401017 1 POST ASSY,SIDE 6-in. (75-105 T) 18 48NG401072 2 PANEL ASSY,SIDE 12-in. (75-105 T) 19 48NG501897 3 BRACKET,PANEL SKIN JOINT 75-105T 21 AA06BS168 40 BOLT,HEXHD 28 AL56ZA003 42 SCREW
1
/4 X 0.75
1
/4 AB-14 X 5/8-in. SERR.
31 99SR120216142001 2 SEAL STRIP 33 48NG501629 2 PLATE JOIN SPLIT UNITS 40 PF0144 3 SEALER,PRESTITE 2-in. WIDE ROLL
Table 11 — 120-150 Nominal Ton Units Parts List
ITEM COMPONENT NUMBER QUANTITY COMPONENT NAME COMPONENT QUALIFIER
1 48NG501939 2 RAIL, MOUNTING SPLIT,BASE,GUIDE
2 48NG501935 2 ROD, THREADED 3 48NG501937 8 WASHER, PLATE 4 AU02AB361 4 WASHER, FLAT 5 AT11AB361 6 NUT, HEAVY HEX
3
/4-10 UNC 2A 30-in. L
3
/4-in. LRT SPLIT
3
/
4
3
/4-10
6 48NG501938 4 BRACKET, TIE LRT SPLIT TOP
1
7 AL48AM307 12 SCREW, HEXHD SR 8 48NG501936 2 ROD, THREADED 9 AU02AB242 4 WASHER, FLAT
10 AT39AB241 4 NUT, HEX
/4 X 5/
3
/8-16
8
3
/
8
3
/8-16 UNC 2A 6-in. L
11 48NG501940 1 PLATE, COVER SPLIT,BASEPAN 12 48NG501941 1 PLATE, COVER SPLIT,BASEPAN 15 AL31AY308 34 SCREW 16 AL79AU216 2 SCREW, HEXHD TF #10 X
1
/
2
17 48NG401018 1 POST ASSY, SIDE 6-in. (120-150 T) 18 48NG401070 2 PANEL ASSY, SIDE 12-in. (120-150 T) 19 48NG501896 3 BRACKET, PANEL SKIN JOINT 120-150T 20 48NG500998 2 HANDLE 21 AA06BS168 40 BOLT, HEXHD 38 AL56ZA003 42 SCREW
1
/4 X 0.75
1
/4 AB-14 X 5/8-in. SERR.
33 48NG501629 2 PLATE JOIN SPLIT UNITS 40 PF0144 3 SEALER, PRESTITE 2-in. WIDE ROLL
Table 12 — Air Pressure Tube Connections
OPTION CONTROL TUBE NUMBER
Return Air Fan RACFM Control PPSS 4, 5 and 6
Power Exhaust
Fan with CFM
Sensor
Outdoor Air CFM OACFM Control 7 and 8
EACFM Control 5 and 6
34
ROOF
a50-8880
Fig. 35 — Roof Cap and Top Cover Removal
L BRACKETS
a50-8881
Fig. 36 — L Bracket Removal
INSTALL TAR TAPE ON ENTIRE BASE RAIL EDGE
A50-8882
Fig. 37 — Tar Tape Location
a50-8883
Fig. 38 — Secure Base Rails
a50-8884
Fig. 39 — Top Rail Brackets
a50-8885
Fig. 40 — Basepan Joint/Cover
CAP
TOP COVER
BASEPAN JOINT/COVER
35
L BRACKETS
A50-8886
Fig. 41 — L Bracket Installation
a50-8887
Fig. 42 — Main Unit and Return Section
Top Cover Assemblies
L
Fig. 43 — Wire Routing
TOP CAPS
TOP
COVER
END CAPS
VFD
36
SEE DETAIL A
DETAIL A
RUN VFD POWER WIRES THROUGH THIS BUSHING, SEPARATE FROM CONTRO WIRES
VFD WITH BYPASS
A50-8889
Fig. 44 — Return Section Component Locations
A50-8890
Fig. 45 — Side Post and Panel Installation
DETAIL NN
VFD WITHOUT BYPASS
SEE DETAIL NN
SIDE POST FAR SIDE ONLY
SIDE
PAN EL
SIDE PAN EL BRACKETS
DETAIL NN
VFD DETAILS

CONTROLS INSTALLATION

Constant Volume (CV) / Staged Air Volume (SAV™) Units —
tions with additional control features, options, or accessories. Refer to the appropriate accessory installation instructions for more information on installing that accessory. Control options and accessories available for CV/SAV units are:
• thermostats
• differential enthalpy sensor
• return air humidity sensor
• outdoor air humidity sensor
• relative humidity space sensor
•CO
sensors
2
• fan status switch
• filter pressure transducer
• return smoke detector
• CEM (controls expansion module)
• EXB (economizer control board) module CONTROL WIRING — The unit can be controlled with a
Carrier-approved accessory electro-mechanical or electronic thermostat that has two stages of cooling, two stages of heating control, and an output for fan control. The thermostat may also include time of day scheduling or use scheduling routines built into the ComfortLink controls.
Install the thermostat according to the installation instruc­tions shipped with the accessory thermostat. Locate thermostat assembly on a solid interior wall to sense average temperature.
The 48N units may be used in applica-
37
Route thermostat cable or equivalent leads of colored wire
Fig. 46 — Field Control Thermostat Wiring
a48-8735
Fig. 47 — T-55 or T-56 Wiring
a48-8736
from subbase terminals through conduit into the low voltage connections in the main control box. For thermostat TB201 connections, see Fig. 46.
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be directly connected at the thermostat and will require a junction box and splice at the thermostat.
FIELD SUPPLIED THERMOSTAT
Y1 Y2 W1 W2 G
RC
R
C
R
Y1 Y2 W1 W2 G
TB201
X
Variable Air Volume (VAV) Units — The 48N
units may be used in applications with additional control fea­tures, options, or accessories. Refer to the appropriate accesso­ry installation instructions for more information on installing that accessory. Refer to the Controls and Troubleshooting man­ual for more information concerning installation and configura­tion of options and accessories. Control options and accessories available for VAV units are:
• thermostats
• differential enthalpy sensor
• return air humidity sensor
• outdoor air humidity sensor
• relative humidity space sensor
•CO

sensors

2
• fan status switch
• filter pressure transducer
• return smoke detector
• CEM (controls expansion module)
• EXB (economizer control board) module VAV CONTROL WIRING — The recommended types of
control wiring are shown below:
MANUFACTURER
Alpha 1895
American A21451 A48301
Belden 8205 884421
Columbia D6451
Manhattan M13402 M64430
Quabik 6130
Regular Wiring Plenum Wiring
PART NO.
COMMUNICATING SPACE TEMPERATURE SENSOR (T-58) — The communicating space temperature sensor (P/N 33ZCT58SPT) is wired to the Carrier Comfort Network (CCN) connections on TB202.
SPACE TEMPERATURE AVERAGING — Applications that require averaging using multiple space temperature sen­sors can be satisfied using either 4 or 9 sensors as shown in Fig.
48. NOTE: Only Carrier sensors may be used for standard T-55
space averaging. Sensors must be used in multiples of 1, 4, and 9 only, with total sensors wiring not to exceed 1000 ft.
NOTE: Do not use T-56 sensors for space temperature averag­ing because the 5-degree offset function will not work in a multiple sensor application.
HEAT INTERLOCK RELAY (VAV Units Only — Not Neces­sary for Digital Air Volume Applications) — Variable air vol­ume (VAV) units using morning warm-up and/or occupied heating require that room terminals be controlled to a position that provides the minimum required heating cfm or greater when the unit goes into Heating mode. The HIR (heat interlock relay) function is provided for this control. When the unit goes into Heating mode, the HIR is energized to provide switch clo­sure or opening (depending on how the field-supplied power source is set up) to open the room terminals. The field connec­tions for the HIR are at TB201 terminals 9 and 10. See Fig. 49.
Option and Accessory Control Wiring —
The 48N Series units may be used in applications with addi­tional control features, options, or accessories. Refer to the Controls, Start-Up, Operation, Service and Troubleshooting manual for more information concerning installation and con­figuration of options and accessories. Figures 49-59 contain wiring information on the following features:
• heat interlock relay (Fig. 49)
• outdoor air enthalpy switch (Fig. 50)
•CO
space sensor (Fig. 51)
2
• filter status switch (Fig. 52)
• fan status switch (Fig. 53)
• space humidity sensor (Fig. 54)
• return air humidity sensor (Fig. 54)
• return air CO
• return air smoke detector (Fig. 56)
• smoke control — fire shutdown (Fig. 57)
• smoke control — purge (Fig. 58)
• smoke control — evacuation (Fig. 58)
• smoke control — pressurization (Fig. 58)
• CCN connections (Fig. 59)
sensor (Fig. 55)
2
SEN
T56- SPTT55- SPT
SEN SET
JUMPER TERMINALS
®
SENSORS — Sensors should be wired using single twisted pairs of 20 AWG (American Wire Gage) conductor cable rated for the application, except for the T-56 accessory sensor which requires 3-conductor cable.
HUMIDITY CONTROL AND HOT WATER AND STEAM VALVES — These devices require 20 AWG twisted pair conductor cables rated for the application for the 4 to 20 mA signal.
SPACE TEMPERATURE SENSOR (T-55) — The space temperature sensor (P/N 33ZCT55SPT), if used, is wired to terminals in the unit main control box. To connect the space temperature sensor, see Fig. 47.
SPACE TEMPERATURE SENSOR (T-56) — The space temperature sensor (P/N 33ZCT56SPT), if used, is wired to terminals in the unit main control box. To connect the space temperature sensor, see Fig. 47.
38
UNIT TB201
1
3
24
TB201
11
7
8
T55
9
10
21
3
5
6
13
15
12
16
14
T55
Fig. 48 — Space Temperature Averaging Wiring
NOTE: Use T-55 sensor only.
a48-8737
13
14
15
10
9
RCB
J8
RELAY 5
Fig. 49 — Heat Interlock Relay Wiring
a48-8477
TB201
1
2
RED
BLK
T55
TB201
1
2
SENSOR 1
SPACE TEMPERATURE AVERAGING (4 SENSOR APPLICATION)
SENSOR 1
SENSOR 4
SENSOR 2
SENSOR 2
SENSOR 5
SENSOR 3
SENSOR 4
SENSOR 3
SENSOR 6
SENSOR 7
SPACE TEMPERATURE AVERAGING (9 SENSOR APPLICATION)
39
SENSOR 8
SENSOR 9
FIELD INSTALLED (FIELD SUPPLIED) JUMPER WHEN ENTHALPY SWITCH NOT USED
RCB J4
6
5
Fig. 50 — Outdoor Air Enthalpy Switch Wiring
a48-8478
MBB J8
7
8
TB201
Fig. 51 — CO2 Space Sensor Wiring
a48-8479
FILTER STATUS - RETURN SWITCH
GRA
BLK
1
CEM
J5
AN 5
2
180 OHM
3
4
5
6
180 OHM
CEM
J5
CEM
J6
FILTER PRESSURE RETURN
FILTER STATUS - POST FILTER
FILTER PRESSURE - POST FILTER
BLU
VIO
AN 6
AN 7
GRA
ORN
_
+
BLU RED
_
+
Fig. 52 — Filter Status Wiring
a48-8738
40
RXB
J4
Fig. 53 — Fan Status Switch Wiring
a48-8741
CEM J6
OA HUMIDITY
4 - 20 ma
SPACE HUMIDITY
4 - 20 ma
RETURN HUMIDITY
4 - 20 ma
PL29-1
PL29-2
RED
BLK
3
RED
BLK
4
5
+
­ACCSY
ACCSY
ACCSY
+
-
+
-
24VDC
AN8
24VDC
AN9
24VDC
AN10
6
7
8
9
10
11
12
ORN
GRN
BLU
BLU
VIO
VIO
PL37-5
PL37-6
TB202
3
4
MIXED AIR HUMIDITY
4 - 20 ma
ACCSY
+
-
AN7
1
2
RED
ORN
TB203
8
7
Fig. 54 — Space and Return Air Humidity Sensor Wiring
a48-8740
41
RED
BRN
Fig. 55 — Return Air CO2 Sensor Wiring
a48-8483
TB201TB201
1
2
PL45-1
PL45-3
PL45-2
PL45-6
PL45-5
PL45-4
Fig. 56 — Return Air Smoke Detector Wiring
a48-8739
MBB
J6
TB201
1
2
BLU
WHT
FIRE SHUTDOWN
Fig. 57 — Fire Shutdown Wiring
a48-8485
42
14
Fig. 58 — Purge, Evacuation, and Pressurization Wiring
a48-8486
TB201
MBB
J5
Fig. 59 — CCN Connections
a48-8487
15
16
17
18
19
TB 202
RCB J4
43
Carrier Comfort Network® (CCN) Interface —
The 48N Series units can be connected to the CCN system if desired. The communication bus wiring is supplied and installed in the field. It consists of shielded, 3-conductor cable with shield wire.
The system elements are connected to the communication bus in a daisy chain arrangement. The positive pin of each system element communication connector must be wired to the positive pins of the system element on either side of it, the negative pins must be wired to the negative pins, and the signal pins must be wired to common pins. Wiring connections for the CCN system should be made at the terminal block using the screw terminals. The board also contains an RJ14 CCN plug that can be used to connect a field service computer. There is also another RJ14 LEN (Local Equipment Network) connec­tion that is used to download software or connect a Naviga­tor™ device.
NOTE: Conductors and drain wire must be 20 AWG minimum stranded, tinned copper. Individual conductors must be insu­lated with PVC, PVC/nylon, vinyl, Teflon*, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum operating temperature range of –4 to 140 F (–20 C to 60 C) is required. See Table 13 for cables that meet the requirements.
Table 13 — CCN Connection Approved
MANUFACTURER CABLE PART NO.
Alpha 2413 or 5463
American A22503
Belden 8772
Columbia 02525
IMPORTANT: When connecting the CCN communica­tion bus to a system element, use a color coding system for the entire network to simplify installation and checkout.
The following color code is recommended:
SIGNAL
TYPE
+ RED 1
COMMON WHITE 2
BLACK 3
NOTE: If a cable with a different color scheme is selected, a similar color code should be adopted for the entire network.
At each system element, the shields of its communication bus cables must be tied together. If the communication bus is entirely within one building, the resulting continuous field must be connected to a ground at one point only. If the commu­nication bus cable exits from one building and enters another, the shields must be connected to grounds at the lightning suppressor in each building where the cable enters or exits the building (one point per building only).
To connect the unit to the network (Fig. 59):
1. Turn off power to the control box.
2. Cut the CCN wire and strip the ends of the red (+), white (common) and black (–) conductors. (If a different net­work color scheme is used, substitute appropriate colors.)
Shielded Cables
CCN BUS CONDUCTOR
INSULATION COLOR
COMM1 PLUG
PIN NO.
3. Wire the CCN to the screw terminals on the COMM board as follows:
a. Secure the red (+) wire to CCN screw terminal +
on the COMM board.
b. Secure the white (common) wire to CCN screw
terminal C on the COMM board.
c. Secure the black (–) wire to CCN screw terminal –
on the COMM board.
d. Secure shield wire to CCN screw terminal
SHIELD on the COMM board.
IMPORTANT: A shorted CCN bus cable will prevent some routines from running and may prevent unit from starting. If abnormal conditions occur, unplug the connec­tor. If conditions return to normal, check CCN connector, and run new cable if necessary. A short in one section of the bus can cause problems with all system elements on the bus.

Optional UPC Open Installation

WIRING THE UPC OPEN TO THE MS/TP NET­WORK — The UPC Open controller communicates using BACnet† on an MS/TP network segment communications at 9600 bps, 19.2 kbps, 38.4 kbps, or 76.8 kbps.
Wire the controllers on an MS/TP network segment in a dai­sy-chain configuration. Wire specifications for the cable are 22 AWG (American Wire Gage) or 24 AWG, low-capacitance, twisted, stranded, shielded copper wire. The maximum length is 2000 ft.
Install a BT485 terminator on the first and last controller on a network segment to add bias and prevent signal distortions due to echoing. See Fig. 60-62.
To wire the UPC Open controller to the BAS network:
1. Pull the screw terminal connector from the controller's BAS Port.
2. Check the communications wiring for shorts and grounds.
3. Connect the communications wiring to the BAS port’s screw terminals labeled Net +, Net -, and Shield.
NOTE: Use the same polarity throughout the network segment.
4. Insert the power screw terminal connector into the UPC Open controller's power terminals if they are not current­ly connected.
5. Verify communication with the network by viewing a module status report. To perform a module status report using the BACview keypad/display unit, press and hold the “FN” key then press the “.” key.
To install a BT485 terminator, push the BT485 on to the
BT485 connector located near the BACnet connector. NOTE: The BT485 terminator has no polarity associated with
it.
To order a BT485 terminator, consult Commercial Products
®
i-Vu
Open Control System Master Prices.
*Teflon is a registered trademark of DuPont. †BACnet is a registered trademark of ASHRAE (American Society of Heating, Refrigerating and Air-Conditioning Engineers).
44
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
BACNET BAUD RATE DIP SWITCHES
ADDRESS ROTARY SWITCHES
POWER LED
RUN LED
ERROR LED
BACNET CONNECTION
BT485 TERMINATOR
Tx2 LED
Rx2 LED
Tx1 LED
Rx1 LED
Fig. 60 — UPC Open Controller
Fig. 61 — Open System Network Wiring
45
Fig. 62 — BT485 Installation
SPECIFICATION RECOMMENDATION
Cable Single twisted pair, low capacitance, CL2P, 22 AWG (7x30), TC foam FEP, plenum rated cable
Conductor 22 or 24 AWG stranded copper (tin plated)
Insulation Foamed FEP 0.015 in. (0.381 mm) wall 0.060 in. (1.524 mm) O.D.
Color Code Black/White
Twist Lay 2 in. (50.8 mm) lay on pair 6 twists/foot (20 twists/meter) nominal Shielding Aluminum/Mylar shield with 24 AWG TC drain wire
Jacket
DC Resistance 15.2 Ohms/1000 feet (50 Ohms/km) nominal
Capacitance 12.5 pF/ft (41 pF/meter) nominal conductor to conductor
Characteristic Impedance 100 Ohms nominal
Weight 12 lb/1000 feet (17.9 kg/km)
UL Temperature Rating
Voltage 300 Vac, power limited
Listing UL: NEC CL2P, or better
LEGEND
AWG American Wire Gage CL2P Class 2 Plenum Cable DC Direct Current FEP Fluorinated Ethylene Polymer NEC National Electrical Code O.D. Outside Diameter TC Tinned Copper UL Underwriters Laboratories
Table 15 — Open System Wiring Specifications and Recommended Vendors
MS/TP WIRING RECOMMENDATIONS — Recom­mendations are shown in Tables 14 and 15. The wire jacket and UL temperature rating specifications list two acceptable alternatives. The Halar* specification has a higher tempera­ture rating and a tougher outer jacket than the SmokeGard† specification, and it is appropriate for use in applications where the user is concerned about abrasion. The Halar jack­et is also less likely to crack in extremely low temperatures.
NOTE: Use the specified type of wire and cable for maximum signal integrity.
Smoke Control Modes — Rooftop units can be used
for aid in building smoke control in the event of a building fire. The available functions include: Fire Shutdown, Pressuriza­tion, Evacuation, and Smoke Purge. These functions are enhanced when multiple rooftop units are used to zone a build­ing. See Table 16 and Fig. 57 and 58.
FIRE SHUTDOWN — Fire Shutdown mode terminates all unit operation (cooling, heating, supply fan, and power exhaust). This mode prevents recirculation of contaminated air back into the space. The mode will not allow admission into the space of unsuitable outside air. See Fig. 57 for wiring.
Table 14 — MS/TP Wiring Recommendations
SmokeGard Jacket (SmokeGard PVC) 0.021 in. (0.5334 mm) wall 0.175 in. (4.445 mm) O.D. Halar Jacket (E-CTFE) 0.010 in. (0.254 mm) wall 0.144 in. (3.6576 mm) O.D.
SmokeGard 167°F (75°C) Halar -40 to 302°F (-40 to 150°C)
WIRING SPECIFICATIONS RECOMMENDED VENDORS AND PART NUMBERS
Wire Type Description
MS/TP Network (RS-485)
Rnet 4 conductor, unshielded, CMP, 18 AWG, plenum rated. W184C-2099BLB 6302UE 21450 CLP0442
LEGEND
AWG American Wire Gage CL2P Class 2 Plenum Cable CMP Communications Plenum Rated FEP Fluorinated Ethylene Polymer TC Tinned Copper
*Halar is a registered trademark of Solvay Plastics. †SmokeGard is a trademark of AlphaGary-Mexichem Corp.
22 AWG, single twisted shielded pair, low capacitance, CL2P, TC foam FEP, plenum rated. See MS/TP Installation Guide for specifications.
24 AWG, single twisted shielded pair, low capacitance, CL2P, TC foam FEP, plenum rated. See MS/TP Installation Guide for specifications.
Connect Air
International
W221P-22227 25160PV CLP0520LC
W241P-2000F 82841 25120-OR
Belden RMCORP
46
Contractors
Wire and Cable
PRESSURIZATION — Pressurization mode is intended to keep smoke out of a zone. The factory-installed optional economizer is required for this function. Pressurization is ac­complished by the following:
• opening the economizer (option)
• running the supply fan (optional inlet guide vanes open or optional VFD at normal duct static pressure set point)
• closing the power exhaust dampers (if installed as option or accessory)
• shutting off the power exhaust fans (if installed as option or accessory)
This allows the space to be overpressurized relative to adjacent zones and prevents or slows entry of smoke into this space from adjacent zones. See Fig. 58 for wiring.
EVACUATION — Evacuation mode removes smoke or un­desirable air from interior spaces without reintroducing unsuit­able air. The factory-installed optional economizer with option/ accessory power exhaust is required for this function. Evacua­tion is accomplished by the following:
• turning the supply fan off
• opening the economizer (option required)
• running the exhaust fans (option or accessory required)
• opening the exhaust dampers.
See Fig. 58 for wiring.
SMOKE PURGE — Smoke Purge mode removes smoke from the interior spaces and replaces it with fresh outside air. The factory-installed optional economizer with option/accessory power exhaust are required for this function. Smoke purge is accomplished by the following:
• turning supply fan on
• opening the economizer (option required)
• running the exhaust fans (option or accessory required)
• opening the exhaust dampers See Fig. 58 for wiring.
SMOKE CONTROL INSTALLATION — Implementa­tion of the various smoke control modes on these units re­quires the installer to modify the unit wiring to add con­tacts (via either manual switches or relays) that will selec­tively interrupt and override standard factory control sequences. See Table 16 and Fig. 56 and 57 and the Con­trols, Start-Up, Operation, Service and Troubleshooting manual for more information.
Table 16 — Smoke Control Modes
FUNCTION
Supply Fan Off On Off On VFD† Open/On Open/On Economizer Closed Open Open Open Return Air
Damper Exhaust
Fans Exhaust
Damper
LEGEND
VAV — Variable Air Volume VFD — Variable Frequency Drive
*Power exhaust option required for this mode.
†Applicable to VAV units with appropriate options.
Fire
Shutdown
Open Closed Closed Closed
Off Off On On
Closed Closed Open Open
Pressur-
ization
MODE
Evacuation*
Smoke Purge*
47
© Carrier Corporation 2016
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53480121-01 Printed in U.S.A. Form 48N-8SI Pg 48 10-16 Replaces: 48N-7SI
Loading...