This installation instruction contains basic unit installation
information, including installation of thermostats and remote
temperature sensors.
For additional information and service instructions, refer to
the Controls, Start-Up, Operation, Service and Troubleshooting
literature.
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All
other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe
precautions in the literature, tags and labels attached to the unit,
and other safety precautions that may apply.
Follow all safety codes, including ANSI (American National Standards Institute) Z223.1. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguisher available for all brazing operations.
WARNING
Before performing service or maintenance operations on
unit, turn off main power switch to unit. Electrical shock
could cause personal injury.
FOR YOUR SAFETY
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance. Do not touch any electrical
switch; do not use any phone in your building. Immediately
call your gas supplier from a neighbor’s phone. Follow the
gas supplier’s instructions. If you cannot reach your gas supplier, call the fire department.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors and
liquids in the vicinity of this or any other appliance.
WARNING
Improper installation, adjustment, alteration, service, or
maintenance can cause injury or property damage. Refer to
this manual. For assistance or additional information, consult a qualified installer, service agency, or the gas supplier.
CAUTION
Disconnect gas piping from units when leak testing at pressures greater than 0.5 psig. Pressures greater than 0.5 psig
will cause gas valve damage resulting in a hazardous
condition. If gas valve is subjected to pressure greater than
0.5 psig, it must be replaced. When pressure testing fieldsupplied gas piping at pressures of 0.5 psig or less, the unit
connected to such piping must be isolated by manually
closing the gas valve.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53480121-01Printed in U.S.A.Form 48N-8SIPg 1 10-16Replaces: 48N-7SI
WARNING
DO NOT USE TORCH to remove any component. System
contains oil and refrigerant under pressure.
To remove a component, wear protective gloves and goggles and proceed as follows:
a. Shut off electrical power to unit.
b. Recover refrigerant to relieve all pressure from sys-
tem using both high-pressure and low pressure ports.
c. Traces of vapor should be displaced with nitrogen
and the work area should be well ventilated. Refrigerant in contact with an open flame produces toxic
gases.
d. Cut component connection tubing with tubing cutter
and remove component from unit. Use a pan to catch
any oil that may come out of the lines and as a gage
for how much oil to add to the system.
e. Carefully unsweat remaining tubing stubs when nec-
essary. Oil can ignite when exposed to torch flame.
Failure to follow these procedures may result in personal
injury or death.
CAUTION
DO NOT re-use compressor oil or any oil that has been
exposed to the atmosphere. Dispose of oil per local codes
and regulations. DO NOT leave refrigerant system open to
air any longer than the actual time required to service the
equipment. Seal circuits being serviced and charge with
dry nitrogen to prevent oil contamination when timely
repairs cannot be completed. Failure to follow these procedures may result in damage to equipment.
ACOUSTICAL CONSIDERATIONS
In order to minimize sound transmitted to the space, please
conform to the following recommendations (see Fig. 1):
Location
• Avoid locating the unit above sound-sensitive areas.
Instead, locate the unit above restrooms, storage areas,
corridors, or other noise-tolerant areas.
• Avoid mounting the unit in the middle of large roof
expanses between vertical supports. This will minimize
the phenomenon known as roof bounce.
• Install the units close to vertical roof supports (columns
or load bearing walls).
• Locate the units at least 25 feet away from critical areas.
If this is not possible, the ductwork and ceiling structure
should be acoustically treated.
• Consider the use of vibration isolators or an acoustic curb.
Ductwork
• Utilize flexible connectors between the unit and the supply and return ducts.
• Supply and return air main trunk ducts should be located
over hallways and/or public areas.
• Provide trailing edge turning vanes in ductwork elbows
and tees to reduce air turbulence.
• Make the ductwork as stiff as possible.
• Use round duct wherever possible because it is less noisy.
• Seal all penetrations around ductwork entering the space.
• Make sure that ceiling and wall contractors do not attach
hangers or supports to ductwork.
• Provide as smooth and gradual transition as possible when
connecting the rooftop unit discharge to the supply duct.
• If a ceiling plenum return is utilized, provide a return
elbow or tee to eliminate line-of-sight noise to the space.
Face the entrance of the return duct away from other
adjacent units.
Acoustic Insulation
• Provide acoustic interior lining for first 20 feet of supply
and return duct or until the first elbow is encountered.
The elbow prevents line-of-sight transmission in the supply and return ducts.
• Install a double layer of 2-in. low density quilted fiberglass acoustical pad with a
facing on top of the roof deck before building insulation
and roofing installation occur. Place the material inside
the curb and for 4 to 8 ft beyond the unit perimeter,
dependent upon unit size (larger units require a wider
apron outside the curb). Openings in the pad should only
be large enough for the supply and return ducts. An alternate approach is to use two layers of gypsum board with
staggered seams in addition to the acoustical pad.
1
/8-in. barium-loaded vinyl
2
Flexible
Fig. 1 — Acoustical Considerations
Connectors
Supply and
Return
Vibration
Isolators
in Roof
Curb
Intake
Plenum
Supply
Fan
Supply and Return
Ducts Lined with
Acoustical Duct Liner
Discharge
Plenum
Compressor/
Condensing
Section
Round Duct Controls
Rumble Best
All Roof
Penetrations
Should Be
Sealed
Air Tight
INSTALLATION
Step 1 — Perform Jobsite Survey —
the following checks before installation.
1. Consult local building codes and the NEC (National
Electrical Code) (ANSI/NFPA [American National Standards Institute/National Fire Protection Association] 70)
for special installation requirements.
2. Determine unit location (from project plans) or select unit
location. Refer to Acoustical Considerations section.
3. Check for possible overhead obstructions which may interfere with unit lifting or rigging.
Complete
CAUTION
Do not lift unit with forklift truck. Move unit with overhead rigging only.
Step 2 — Place Unit — Inspect unit for transportation
damage. If any damage is found, file a claim with the transportation agency.
Provide clearance around and above unit for airflow, safety,
and service access. Do not restrict top (area above condenser
fans) in any way. Allow at least 6 ft on all sides for rated performance, code compliance, and service. On units equipped with
power exhaust option, high velocity air is exhausted out the
hood. Unit should be positioned with at least 10 ft clearance between the exhaust hood and any obstruction. See Fig. 2 for
multiple unit minimum separation. See Tables 1-6 for additional unit and fan data.
Check unit dimensional drawings on pages 19-23 for unit
arrangement and minimum performance and service
clearances.
Do not install unit in an indoor location. Do not locate air inlets near exhaust vents or other sources of contaminated air.
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
Level by using unit frame as a reference.
Step 3 — Roof Mount Unit — Check building codes
for weight distribution requirements. Refer to Acoustical Considerations section. Unit and accessory weights are shown in
Tables 1 and 2. Unit may be mounted on class A, B, or C roofing material.
ROOF CURB — Assemble and install roof curb as described
in instructions shipped with the accessory. Accessory roof curb
and information required to field fabricate a roof curb is shown
in Fig. 3 and 4. Install insulation, cant strips, roofing, and
counter flashing as required. For unit condensate drain to function properly, curb must be level or within tolerances shown in
Fig. 3.
NOTE: Units with double-wall floor design (“Double Wall onthe-bottom”) are not compatible with roof curbs.
STEEL BEAMS — If roof curb is not used, support unit with
steel beams along its entire length and then support steel as required. Cross members are required to support across its width
at each lifting lug location; use more cross members for support as needed.
Step 4 — Slab Mount Unit — Provide a level con-
crete slab that extends beyond unit cabinet at least 6 inches.
Use gravel apron in front of condenser coil air inlet to prevent
grass and foliage from obstructing airflow. Provide a slab minimum 8 in. thick with sufficient height above grade to allow for
condensate trap as described in Step 8.
BASE UNITNPQRST
NOMINAL CAPACITY (tons)7590105120130150
WEIGHT (lb)
Base Unit*12,00012,45512,45516,17016,86017,040
Split Unit - Main Section9,1109,5659,56512,88013,57013,750
Split Unit - Return Section2,8902,8902,8903,2903,2903,290
COMPRESSORSScroll
Quantity566 8 8 8
Oil Charge (oz) per Compressor110110110110110110
Compressor A1ZP182ZP154ZP182ZP182ZP154ZP182
Compressor A2ZP182ZP154ZP182ZP154ZP182ZP182
Compressor A30ZP154ZP182ZP154ZP182ZP182
Compressor A4000ZP154ZP182ZP182
Compressor B1ZP137ZP182ZP182ZP182ZP154ZP182
Compressor B2ZP137ZP182ZP182ZP154ZP182ZP182
Compressor B3ZP137ZP182ZP182ZP154ZP182ZP182
Compressor B4000ZP154ZP182ZP182
Stages of Capacity, % Total Capacity0,18,23,41,65,
Number of Refrigerant Circuits222 2 2 2
REFRIGERANT
TypeR-410A
Charge AmountSee Table 6
METERING DEVICE
Type... Quantity per CircuitElectronically controlled expansion devices... two (2) per circuit
STANDARD EFFICIENCY UNIT CONDENSERMCHX
MaterialAluminumAluminumAluminumAluminumAluminumAluminum
Number of Total Coils444 4 6 6
Total Face Area (sq ft)138.7173.3173.3173.3173.3260.0
HIGH EFFICIENCY UNIT CONDENSERMCHX
MaterialAluminumAluminumAluminumAluminumAluminum
Number of Total Coils466 6 6
Total Face Area (sq ft)138.7173.3260.0260.0260.0
EVAP-STANDARD CAPACITY with STD EFFICIENCYRTPF
Total Face Area (sq ft)78.878.878.899.699.6
CONDENSER FAN, STANDARD EFFICIENCY
Number of Fans466 6 9 9
TypeProp/MetalProp/MetalProp/PlasticProp/PlasticProp/MetalProp/Plastic
Diameter (in.)30.53030.530.53030.5
Motor Hp1111 1 1
Nominal Cfm41,00081,00081,00081,00093,000122,400
Motor Rpm114011401140114011401140
CONDENSER FAN, HIGH EFFICIENCY
Number of Fans699 9 9
TypeProp/MetalProp/PlasticProp/PlasticProp/PlasticProp/Plastic
Diameter (in.)30.530.530.530.530.5
Motor Hp1111 1
Nominal Cfm61,00093,00093,00093,00093,000
Motor Rpm11401140114011401140
LEGEND* Base unit includes: economizer dampers and hoods, filter tracks less filters, evaporator coil
Cu-Al— Copper-to-Aluminum
DWDI— Double Width Double Inlet
FPI— Fins per Inch
MBtuh— Btuh in Thousands
MCHX— Microchannel Heat Exchanger
RTPF— Round Tube Plate Fin
SWSI— Single Width Single Inlet
82,100
0,11,15,33,49,
67,82,100
mounting less the evaporator, extended plenum, and standard efficiency condenser. For 75105 nominal ton units only, base unit weight also includes the short supply fan section.
BASE UNITNPQRST
NOMINAL CAPACITY (tons)7590105120130150
HUMIDI-MIZER
TypeMCHX
MaterialAluminum
Quantity1
SurfaceE-Coated
Total Face Area (sq ft)34.543434343
STANDARD AND HIGH CAPACITY HOT WATER COILS
TypeRTPF
MaterialAluminum Fin, Copper Tube
Quantity2
Tube TypeSmooth
Rows (each)2
FPI12
Total Face Area (sq ft)22.426.4
STANDARD AND HIGH CAPACITY STEAM COIL
TypeRTPF
MaterialAluminum Fin, Copper Tube, Steel Header, Sloped Casing
Quantity2
Tube TypeSmooth
Connection Size, Length (in.)2.50, 3.00
Total Face Area (sq ft)40.149.0
HEATING SECTION LOW (48N ONLY)
Heating Section22233 3
Number of Gas Valves3445 5 5
SUPPLY FAN
Standard Supply Fan
Diameter (in.)28
Wheel and Blade TypeDWDI Airfoil
Maximum Allowable Cfm42,000
Maximum Allowable Speed (rpm)1,800
Shaft Diameter at Pulley (in.)2.25
High Static Supply Fan
Diameter (in.)40
Wheel and Blade TypeDWDI Airfoil
Maximum Allowable Cfm52,500
Maximum Allowable Speed (rpm)1,250
Shaft Diameter at Pulley (in.)3
LEGEND* Base unit includes: economizer dampers and hoods, filter tracks less filters, evaporator coil
Cu-Al— Copper-to-Aluminum
DWDI— Double Width Double Inlet
FPI— Fins per Inch
MBtuh— Btuh in Thousands
MCHX— Microchannel Heat Exchanger
RTPF— Round Tube Plate Fin
SWSI— Single Width Single Inlet
®
COIL
NA
43
334 4 4
32
DWDI Airfoil
60,000
1,550
2.5
40
DWDI Airfoil
60,000
1,250
3
mounting less the evaporator, extended plenum, and standard efficiency condenser. For 75105 nominal ton units only, base unit weight also includes the short supply fan section.
BASE UNITNPQRST
NOMINAL CAPACITY (tons)7590105120130150
OPTIONAL POWER EXHAUST
Power Exhaust
Diameter (in.)20
Wheel and Blade TypeDWDI Forward Curve
Maximum Allowable Cfm42,000
Maximum Allowable Speed (rpm)1,2001,200
Shaft Diameter at Pulley (in.)1.751.75
High Static Power Exhaust
Diameter (in.)36
Wheel and Blade TypeDWDI Forward CurveDWDI Forward Curve
Maximum Allowable Cfm42,000
Maximum Allowable Speed (rpm)650
Shaft Diameter at Pulley (in.)2.5
OPTIONAL RETURN FAN
Return Fan
Diameter (in.)4040
Wheel and Blade TypeSWSI Plenum AirfoilSWSI Plenum Airfoil
Maximum Allowable Cfm52,500
Maximum Allowable Speed (rpm)12361236
Shaft Diameter at Pulley (in.)2.52.5
High Static Return Fan
Diameter (in.)45
Wheel and Blade TypeSWSI Plenum Airfoil
Maximum Allowable Cfm60,000
Maximum Allowable Speed (rpm)850
5056
60,00060,000
780720
Shaft Diameter at Pulley (in.)3
MIXED AIR FILTERS
MERV 7 Pleated Filters2 inch, MERV 72 inch, MERV 7
Quantity2828
Size (in.)20x24x220x25x2
MERV 8 Pleated Filters4 inch, MERV 84 inch, MERV 8
Quantity2828
Size (in.)20x24x420x25x4
MERV 14 Pleated Filters4 inch, MERV 144 inch, MERV 14
Quantity2828
Size (in.)20x24x420x25x4
MERV 14 Cartridge Filters, 2 or 4-in. in Pre-Filters12 inch, MERV 14 Cartridge Filters12 inch, MERV 14 Cartridge Filters
Quantity2020
Size (in.)(15) 20x24x12, (5) 24x24x1224x24x12
MERV 14 Bag, 2 or 4-in. in Pre-Filters12 inch, MERV 14 Bag Filters12 inch, MERV 14 Bag Filters
Quantity2020
Size (in.)(15) 20x24x12, (5) 24x24x1224x24x12
MERV 15 Bag, 2 or 4-in. in Pre-Filters19 inch, MERV 15 Bag Filters19 inch, MERV 15 Bag Filters
Quantity2020
Size (in.)(15) 20x24x19, (5) 24x24x1924x24x19
FINAL FILTERS
MERV 14 Cartridge Filters, 2 or 4-in. in Pre-Filters12 inch, MERV 14 Cartridge Filters12 inch, MERV 14 Cartridge Filters
Quantity
1919
Size (in.)(14) 20x24x12, (5) 24x24x1224x24x12
MERV 15 Bag, 2 or 4-in. in Pre-Filters19 inch, MERV 15 Bag Filters19 inch, MERV 15 Bag Filters
Quantity1919
Size (in.)(14) 20x24x19, (5) 24x24x1924x24x19
MERV 17 HEPA, 2 or 4-in. in Pre-Filters12 inch, MERV 17 HEPA Filters, 99.99%12 inch, MERV 17 HEPA Filters, 99.99%
Quantity1919
Size (in.)(14) 24x12x12, (5) 24x24x1224x24x12
OUTSIDE AIR SCREENS
Standard Hood (Motorized OA and Economizer
Options)
Aluminum Frame, Permanent
Quantity12 Screens16 Screens
Size (in.)16 7/8 x 3116 7/8 x 31
LEGEND* Base unit includes: economizer dampers and hoods, filter tracks less filters, evaporator coil
Cu-Al— Copper-to-Aluminum
DWDI— Double Width Double Inlet
FPI— Fins per Inch
MBtuh— Btuh in Thousands
MCHX— Microchannel Heat Exchanger
RTPF— Round Tube Plate Fin
SWSI— Single Width Single Inlet
mounting less the evaporator, extended plenum, and standard efficiency condenser. For 75105 nominal ton units only, base unit weight also includes the short supply fan section.
23
60,000
40
60,000
600
3
60,000
7
Table 2 — Operating Weights of Options and Accessories (lb)
OPTION OR ACCESSORY
N
(75)
P
(90)
Q
(105)
R
(120)
S
(130)
Economizer140140140140140140
48N UNIT SIZE (TON NOMINAL CAPACITY)
Filters
2 in. MERV 7 909090100100100
4 in. MERV 8150150150175175175
4 in. MERV 14175175175210210210
12 in. MERV 14 Bag with 2 in. Pre-Filter200200200225225225
12 in. MERV 14 Bag with 4 in. Pre-Filter260260260300300300
19 in. MERV 15 Bag with 2 in. Pre-Filter300300300335335335
19 in. MERV 15 Bag with 4 in. Pre-Filter320320320350350350
12 in. MERV 14 Cartridge with 2 in. Pre-Filter350350350375375375
12 in. MERV 14 Cartridge with 4 in. Pre-Filter370370370400400400
Field Use Filter Section635635635665665665
Evaporator
Standard Capacity62562583279510531053
High Capacity8328321110105314021402
High-Efficiency Condenser310691691691NoneNA
Extended Chassis320320320335335335
19 in. MERV 15 Bag with 2 in. Pre-Filter830830830890890890
19 in. MERV 15 Bag with 4 in. Pre-Filter850850850905905905
12 in. MERV 14 Cart with 2 in. Pre-Filter880880880930930930
12 in. MERV 14 Cart with 4 in. Pre-Filter900900900955955955
12 in. MERV 17 HEPA with 2 in. Pre-Filter905905905965965965
12 in. MERV 17 HEPA with 4 in. Pre-Filter930930930980980980
Supply Fan
High-Static Supply Fan127412741274116911691169
Standard Supply Fan965965965107110711071
PE (Power Exhaust) Fan
High-Static PE Fan927927927927927927
Standard PE Fan619727727727727727
Return Fan
High-Static Return Fan97410861298129812981298
Standard Return Fan895895895895895895
Supply/PE/Return Motor Includes VFD
has been connected to the roof curb, apply gasket material
1
(
/2-in. thick x 11/2-in. wide neoprene) where indicated.
Single-Thickness Gasketing (See Fig. 5 for Item Numbers)
— Apply gasketing in the following places:
1. Along both side rails (1) — 2 places, full length
2. Along return air end rail (2) — 1 place
3. Around return air internal duct flange (3) — 1 or 2 places
4. Around supply air internal duct flanges (4) — 3 places
5. Along supply section base rail (5) — 1 place
Condenser Section Roof Curb (See Fig. 6)
— Apply single-
thickness gasket along both side rails (5).
Step 6 — Install Field-Fabricated Ductwork
WARNING
For vertical supply and return units, tools or parts could
drop into ductwork and cause an injury. Install a 90-degree
elbow in the supply and return ductwork between the unit
and the conditioned space. If a 90-degree elbow cannot be
installed, then a grille of sufficient strength and density
should be installed to prevent objects from falling into the
conditioned space. Failure to follow these instructions
could result in personal injury or property damage due to
falling objects.
Field-fabricated ductwork for vertical supply/vertical return
units must be attached to the roof curb, or to the support steel,
prior to the final rigging and installation of the unit. Supply and
return duct dimensions are shown in Fig. 3.
To attach ductwork to roof curb, insert duct approximately
10 to 11 in. up into roof curb. Connect ductwork to 14-gage
roof curb material with sheet metal screws driven from inside
the duct.
Secure all ducts to the building structure, using flexible duct
connectors between roof curbs and ducts as required. Ducts
passing through an unconditioned space must be insulated and
covered with a vapor barrier. Outlet grilles must not lie directly
below unit discharge.
Design supply duct strong enough to handle expected
static pressures. Field-fabricated ductwork for horizontal
supply/return units must be attached to the unit.
Step 7 — Rig Unit — Do not drop unit; keep upright.
Use spreader bars over the unit to prevent sling or cable damage. Sheets of plywood placed along the condenser coils will
provide additional protection. All lifting lugs MUST be used
when lifting unit. Level by using unit frame as a reference. See
Fig. 7-9 for information. Unit and accessory weights are shown
in Tables 1 and 2. Weight distribution and center of gravity can
be found in Fig. 10. Additional unit dimensional data can be
found in Fig. 11 and 12.
Step 8 — Connect Condensate Drain — The drain
is a 2-in. FPT pipe connection located on the right-hand side of
the unit looking at the unit from the return air end. See Fig. 11
and 12. Figure 13 shows the additional length of units with an
extended chassis.
With field-supplied fittings and pipe sections, plumb the primary condensate drain to the 2-in. FPT connector on the base
rail. Use a trap height of at least 7 inches. See Fig. 14 and 15.
Apply a bead of RTV or similar sealant around the pipe joint at
the connector in the base rail.
15
Fig. 7 — 48N 75-150 Ton Non-Split Rigging
Econ, Bar Rel, Standard
filters, High Cap Evap,
High Efficiency,
High Static Supply Fan
w/ largest motor, High
Static PE w/ largest
motor, No Heat, No Post section, No Humidimizer,
No Extended Chassis,
No Split, No Field Filter Section
Econ, Bar Rel, Standard
filters, High Cap Evap, High
Efficiency, High Static Supply
Fan w/ largest motor,
High Static Power Exhaust
w/ Largest motor, Low gas he
at,
No Post section, No Extended
chassis, No humidimizer,
No Split, No Field filter section
16
Fig. 8 — 48N 75-150 Ton Split (Main Unit) Rigging
Econ, Bar Rel, Cartridge filters, Hi Cap
Evap, High Efficiency, High Static Supply Fan w/ largest motor, Hi Static
Return Fan w/ largest motor, High
Electric Heat, 8' Blank section w/ post
filters, Extended chassis w/ humidimizer,
Split, No Field filter section
Econ, Bar Rel, Cartridge filters,
Hi Cap Evap, High Efficiency,
High Static Supply Fan w/ largest motor,
Hi Static Return Fan w/ largest motor,
High gas heat, 8' Blank section
w/ pos
t filters, Extended chassis
w/ humidimizer, Split, No Field filter
17
Fig. 9 — 48N 75-150 Ton Split (Return Section) Rigging
High Efficiency, High Static Supply Fan
w/ largest motor, Hi Static Return Fan
w/ largest motor, High Electric Heat, 8' Blank
section w/ post filters, Extended chassis
w/ humidimizer, Split, No Field filter section
Econ, Bar Rel, Cartridge filters, Hi Cap Evap,
High Efficiency, High Static Supply Fan
w/ largest motor,Hi Static Return Fan
w/ largest motor, High gas heat, 8' Blank
section w/ post filters
, Extended chassis
w/ humidimizer, Split, No Field filter
18
1
A
3
00
B
Cond End00
Return End
00
24
NOMINAL
CAPACITY
(tons)
CORNER WEIGHTS (lb)
TOTAL (lb)
CENTER OF
GRAVITY
1234
A (in.)B (in.)
48 Series Non-Split
75
4,1294,0474,8924,79617,864275.967.2
90
4,3964,3105,3595,25419,319308.167.2
105
4,4784,3905,5265,41719,810309.867.2
120
5,4555,3476,4746,34623,622309.767.2
130
5,3855,2796,7196,58723,970316.767.2
150
5,4365,3296,8166,68224,263317.567.2
48 Series Split
75
4,6844,5925,6905,57820,544355.167.2
90
4,9694,8716,2736,14922,261390.367.2
105
5,0524,9526,5446,41522,964394.867.2
120
6,0585,9397,5837,44327,013401.067.2
130
5,9725,8547,8457,69127,361409.667.2
150
6,0215,9037,9447,78727,654410.367.2
Fig. 10 — Weight Distribution and Center of Gravity
a48-8793
19
20
Fig. 11 — 48N Unit Sizes N, P, Q (75-105 Ton Nominal Capacity)
Fig. 11 — 48N Unit Sizes N, P, Q (75-105 Ton Nominal Capacity) (cont)
120 HIGH EFFICIENCY—YESYES 102.06
120 STANDARD EFFICIENCYYES—YES102.06
130 STANDARD EFFICIENCY—YESNO 96.62
130 HIGH EFFICIENCY—YESYES 102.06
150 STANDARD EFFICIENCY—YESYES 102.06
23
Fig. 13 — Units with Optional Extended Chassis — Location of Coil Tracks
B
"J"
AUXILIARY COIL LOCATION
Auxiliary Coil Location — in.
UNIT
SIZES 48N (TONS)
HEIGHT BDISTANCE J
N, P, Q (75-105)12.85
See dimension J on certified
drawings, pages 21-24
R, S, T (120-150)12.85
Fig. 14 — Primary Drain Connection
A = 7-in. (178 mm) min
Fig. 15 — Condensate Drain Piping Details
(Slab and Curb Mounted)
SEALANT
3 IN DRAIN
INSIDE OF
BASE RAIL
A MIN.
A/2
UNIT CURB
UNIT
BASE
RAIL
DRAIN PIPE IS FIELD SUPPLIED
Step 9 — Install Outdoor Hoods — Unit sizes 75
to 105 nominal tons will have three hoods on both sides. Unit
sizes 120 to 150 nominal tons will have four hoods on both
sides. Reference images shown are for three hoods. However,
assembly of four hoods for the larger units is the same. Instructions for unpacking and assembly of hoods are below.
1. For shipping, outdoor air hoods are packaged in a box located inside the unit.
2. Remove the box from the unit (see Fig.16).
a. Shipping support straps are bolted to the unit.
Remove four bolts on each, and discard straps.
b. Remove the hood supports (quantity 2 or 3 for
larger units) (see Fig. 17).
c. Remove packaging from the unit.
d. Reinstall hood supports (Fig. 17).
3. Remove filters located between return/exhaust fan and
economizer dampers; these are packaged separately from
hoods for shipping (see Fig. 16). Screws, other hardware
and seal strips are packaged with the outdoor hoods
(Fig. 16).
4. Apply seal strip to the unit. Strip should extend around
entire opening (see Fig. 18).
5. Assemble hoods (see Fig. 19).
a. Attach hood sides (Items 1 and 2) to the hood top
(Item 3). Fasten hood using six screws on each side.
b. Attach hood support (Item 4) to hood top (Item 3).
c. Attach angle (Item 5) to hood sides (two per hood).
Fasten angle to the hood side using three screws
per side.
d. Attach hood support (Item 7) to top (Item 3) using
six screws.
e. Attach clips (Item 8) to hood support (Item 7).
f. Attach angle (Item 10) to hood support (Item 7)
using eight screws.
g. Attach angle (Item 9) to angle (Item 10) using two
pop rivets.
h. Place RTV or similar sealant on all of the 6 corners
to prevent water leaks.
i. Install hood assembly to unit using four screws on
each side and nine screws on the top.
j. Install filters (Item 6) to hood assembly.
6. Repeat Step 5 for each hood.
24
FILTERS
PACKAGING
OUTDOOR
HOODS
(BOTH SIDES)
SHIPPING
SUPPORT
STRAPS
Fig. 16 — Packaging Locations
a48-8725
HOOD SUPPORTS
(BOTH SIDES)
Fig. 17 — Hood Supports
a48-8726
SEAL STRIP
SEAL STRIP
Fig. 18 — Seal Strips
a48-8727
Fig. 19 — Hood Assembly
a48-8728
3
4
9
1
8
2
5
7
10
6
Step 10 — Route Field Wiring — Field power wir-
ing is brought into the unit through the back of the power box
near the bottom. Wiring can be brought through the roof curb
through field-supplied watertight connections. See Fig. 20.
There are two 3
power box and a 7/8-in. hole in the side post for 24-v control
wiring provided. Field-supplied couplings must be used when
routing wiring into the control box.
See Fig. 20 for recommended disconnect location.
25
5
/8-in. holes for field power wiring in the
Step 11 — Make Field Electrical Connections
RECOMMENDED
FIELD-SUPPLIED
DISCONNECT
LOCATION
Fig. 20 — Disconnect Location
CAUTION
Use care when drilling into corner post to avoid damage to condenser coil.
a48-8729
IMPORTANT: All units have variable frequency drives
(VFD) factory installed. VFDs generate, use, and can radiate radio frequency energy. If units are not installed and
used in accordance with these instructions, they may cause
radio interference. They have been tested and found to
comply with limits of a Class A computing device pursuant to International Standard EN 61000-2/3, which are
designed to provide reasonable protection against such
interference when operated in a commercial environment.
POWER WIRING — Units are factory-wired for the voltage
shown on the unit nameplate. The main terminal block is suitable for use with copper wires only. Maximum wire size varies
according to disconnect size.
DISCONNECT SIZE
250 Amps
400 Amps
600 Amps
QUANTITY...MAXIMUM WIRE SIZE
(MCM)
1...300
1...600
2...600
NOTE: Conduit used for field wiring must be sealed at the unit
end of the conduit. Failure to do so could cause the conduit to
act as a chimney in cold climates causing warm building air to
condense in the power box.
Units without Factory-Installed Disconnect
— When installing units, provide a disconnect per NEC (National Electrical
Code) of adequate size (MOCP [maximum overcurrent protection] of unit is on the informative plate). All field-wiring must
comply with NEC and all local codes. Size wire based on
MCA (minimum circuit amps) on the unit informative plate.
See Fig. 21 for power wiring connections to the unit power
terminal block and equipment ground. Maximum wire size is
two (2) 500 MCM (maximum wire size) conductors per pole.
Units with Factory-Installed Disconnect
— The factoryinstalled disconnect is an interlocking, door-type. The disconnect handle locks the door when it is in the ON position. The
disconnect handle must be in the OFF position to open the control box door. The disconnect is located in the power box behind the power box door for all units. See Fig. 22.
All field wiring must comply with NEC and all local codes.
Wire must be sized based on MCA (minimum circuit amps) on
the unit informative plate. See Fig. 23 for power wiring connections to the unit disconnect and equipment ground.
Operating Voltage
— Operating voltage to the unit must be
within the voltage range indicated on the unit nameplate.
Voltages between phases must be balanced within 2%, and
the current must be balanced within 10%. See Table 7 for
motor limits.
Use the following formula to determine the percentage of
voltage imbalance.
Voltage Imbalance
= 100 x
max voltage deviation from average voltage
average voltage
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
452 + 464 + 455
1371
=
3
= 457
Determine maximum deviation from average voltage:
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent voltage imbalance:
% Voltage Imbalance = 100 x
7
457
= 1.53%
This amount of phase imbalance is satisfactory as it is be-
low the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact local utility immediately.
Unit failure as a result of operation on improper line voltage
or excessive phase imbalance constitutes abuse and may cause
damage to electrical components.
NOTE: Extensive motor and electrical testing on the Carrier units
has ensured that the full horsepower range of the motor can be utilized with confidence. Using fan motors up to the horsepower ratings
shown in the Motor Limitations table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
Table 7 — Motor Limits
MAX AMPS (EA)
460 V575 V
27
RATED
EFFICIENCY
Step 12 — Connect Air Pressure Tubing — Be-
fore options such as the variable frequency drive (VFD) and/or
modulating power exhaust can operate properly, the pneumatic
tubing for pressure sensing must be installed. Use fire-retardant
plenum tubing (field-supplied). All control devices use
tubing. Tubing must be run from the appropriate sensing location (in the duct or in the building space) to the control device
location in the unit.
VARIABLE FREQUENCY DRIVE — The tubing for the
duct pressure (DP) control option should sample supply duct
pressure approximately
2
/3 of the way out from the unit in the
main trunk duct, at a location where a constant duct pressure is
desired.
On these units, the duct pressure is sensed by a pressure
transducer. The pressure transducer output is directed to the
unit control module. On all sizes, the DP transducer is located
in the unit control box. See Fig. 24 for control box details. Use
a nominal
1
/4-in. plastic tubing.
Refer to appropriate base unit Controls, Start-Up, Operation, Service and Troubleshooting book for instructions on adjusting set points for duct pressure controls.
POWER EXHAUST — The tubing for the building pressure
(BP) control (achieved via the modulating power exhaust option) should sample building pressure in the area near the entrance lobby (or other appropriate and sensitive location) so
that location is controlled as closely to design pressures as
possible.
These units use a pressure transducer for sensing building
pressure. The BP transducer is located in the unit control box.
Use a nominal
1
/4-in. plastic tubing.
For instructions on adjusting BP control set points, refer to
the Controls, Start-Up, Operation, Service, and
Troubleshooting book.
RETURN FAN — The tubing for the building pressure
(BP) control (achieved via the return fan option) should
sample building pressure in the area near the entrance lobby
(or other appropriate and sensitive location) so that location
is controlled as closely to design pressures as possible.
The units use a pressure transducer for sensing building
pressure. The BP transducer is located in the unit control
box. Use a nominal
1
/4-in. plastic tubing. For instructions on
1
/4-in.
adjusting BP control set points, refer to the Controls, StartUp, Operation, Service, and Troubleshooting book.
must be removed from each corner of the fan sled before starting unit. See Fig. 26.
To remove shipping brackets, remove 2 screws holding
each bracket to the cross rail. There are 4 brackets per unit.
After removing all shipping brackets, level the fan using the
adjustment screws.
Optional return fan shipping brackets
28
Fig. 24 — Control Box Component Arrangement
a48-8731
29
Fig. 25 — Supply Fan and Power Exhaust Fan Shipping Bracket Bolts
a48-8732
RETURN FAN SHIPPING
BRACKET BOLTS
Fig. 26 — Return Fan Shipping Bracket Bolts
a48-8733
SHIPPING BRACKET
SCREWS (4) EACH SPRING
SPRING
SUPPORT
Step 16 — Connect Gas Piping — Unit is equipped
for use with natural gas only. Installation must conform with
local building codes, or in the absence of local codes, with the
National Fuel Gas Code (NFGC), ANSI Z223.1.
1
A
/8-in. NPT tapping plug, accessible for test gage connection, must be field-installed immediately upstream of gas supply connection to unit, but after manual gas valve. See Fig. 27.
Natural gas pressure at unit gas connection must not be less
than 5 in. wg or greater than 13 in. wg.
Size gas supply piping for 0.5 in. wg maximum pressure
drop. Do not use supply pipe smaller than unit gas connection.
CAUTION
Disconnect gas piping from unit when leak testing at pressures greater than 0.5 psig. Pressures greater than 0.5 psig
will cause gas valve damage resulting in a hazardous condition. If gas valve is subjected to pressure greater than
0.5 psig, it must be replaced.
Step 17 — Configure Optional Modulating Gas
Control —
dered with an optional factory-installed modulating gas control
system that monitors heating operation of the rooftop.
Refer to the Controls, Start-Up, Operation, Service, and
Troubleshooting book for information on configuring the modulating gas control.
30
The 48N Series large rooftop units may be or-
Step 18 — Install Flue/Inlet Hoods — The
*NPT plug is field supplied.
NOTE: Follow all local codes.
OUTLET
FLUE
HOOD
INLET
HOOD
INLET
HOOD
Fig. 28 — Flue/Inlet Hood Locations
a48-8734
Fig. 29 — Flue Outlet Hood
flue/inlet hoods are shipped in a package taped to the basepan
in the fan section. The flue (outlet) hoods are pre-assembled.
The inlet hoods require assembly.
The hoods are to be installed on the heating section access
panel as shown in Fig. 28. See Table 8 for a list of parts used to
assemble each hood and quantities of each hood type used with
each unit.
1. Remove shipping block-offs and shipping tape from
all openings in the access panel.
2. Attach flue outlet hoods (see Fig. 28) to access panel
using screws provided. Hoods are placed over each
combustion outlet.
3. Inlet hoods are shipped unassembled and must be assembled on the access panel (see Fig. 29-31). Flanges
of the hood top and sides should be installed on the inside of the access panel openings with the screws provided. The sides should be placed on the inside of the
top hoods for all hood assemblies (6-in. and 14-in.).
Attach speed clips to screen. Insert screen into bottom
opening of 6-in. and 14-in. hoods and secure it with 3
screws. Attach view port cover over 14-in. inlet hood
opening (Fig. 31). Secure with two screws.
Table 8 — Flue Hood and Inlet Hood Usage
Sizes 75-105
(Low Heat)
—— — — 333
23 3 4 3 4 4
HOOD TYPEPART LIST
Top (6-in.)
6-in.
Inlet Hood
14-in.
Inlet Hood
Flue
Outlet Hood
Side (Left)
Side (Right)
Screen
Speed Clips
Screws
Top (14-in.)
Side (Left)
Side (Right)
Screen
Speed Clips
Screws
View Port Cover
Pre-assembled2334345
Size 75
(High Heat)
Sizes 90, 105
(Medium Heat)
QUANTITY USED
Sizes 90, 105
(High Heat)
Sizes 120-150
(Low Heat)
Sizes 120-150
(Medium Heat)
Sizes 120-150
(High Heat)
31
Fig. 30 — Inlet Hood Assembly (6-in. and 14-in.)
VIEW PORT
COVER
Fig. 31 — Inlet Hood View Port Cover
Installation (14-in.)
ACCESS PANEL
OPENING
SIDE (TYP
BOTH SIDES)
COVER
(14-IN. HOOD ONLY)
SCREEN
SPEED CLIP
(TYP 3)
HOOD
Step 19 — Install Supply-Air Thermistors
(Modulating Gas Units Only) — Supply-air therm-
istors are a field-installed, factory-provided component.
Three supply-air thermistors are shipped with modulating
gas units inside the unit control box. Thermistor wires must
be connected to the SGC (staged gas control) in the unit
control box. See Table 9. The supply-air thermistors should
be located in the supply duct with the following criteria:
• downstream of the heat exchanger cells
• equally spaced as far as possible from the heat exchanger
cells
• a duct location where none of the supply air thermistors
are within sight of the heat exchanger cells
• a duct location with good mixed supply air
Table 9 — SGC Thermistor Designations
Step 20 — Install Unit Accessories — For appli-
cations requiring accessories, the following packages are
available:
All units:
• space temperature sensor
•CO
sensor
2
• space temperature sensor with CO
• airflow switch
• filter switch
• smoke detector
Refer to the individual accessory installation instruc-
tions in each accessory package for information on installing accessories.
sensor
2
THERMISTOR
SAT1J8 – 1,2 (SGC)
SAT2J8 – 3,4 (SGC)
SAT3J8 – 5,6 (SGC)
LIMTTEMPJ8 – 15,16 (SGC)
SGC — Staged Gas Controller
PIN
CONNECTION
POINT
FUNCTION AND LOCATION
Thermistors
Supply-Air Thermistor (SAT) — Inserted into supply section underneath the
gas heat section (factory-provided, field-installed)
Supply-Air Thermistor (SAT) — Inserted into supply section underneath the
gas heat section (factory-provided, field-installed)
Supply-Air Thermistor (SAT) — Inserted into supply section underneath the
gas heat section (factory-provided, field-installed)
Limit switch Thermistor (LIMTTEMP) — Inserted next to the lower limit switch
(factory-installed)
32
PART NO.
HH79NZ033
TOP RAIL
GUIDES
BASE RAIL
GUIDES
a50-8877
Fig. 32 — Base and Top Rail Guide Locations
a50-8878
Fig. 33 — Base Rail Guide
TOP RAIL
GUIDE
a50-8879
Fig. 34 — Top Rail Guide
Two-Piece Unit Fit Up
1. Locate and remove split parts package from return section of unit. Open package and remove split unit parts.
See Tables 10 and 11 for parts list.
2. Rig main unit section and return section separately.
3. Do not assemble main unit section and return section on
ground and attempt to lift. Unit pieces must be assembled
on roof curb.
4. Insert base rail guides into the base rails of the main unit
section. Do not attach with screws yet. See Fig. 32 and 33.
5. Insert top rail guides into top rails of the main unit section. Do not attach with screws yet. See Fig. 32 and 34.
6. Rig and set the main unit section on the unit roof curb.
Align the unit bulkhead with the supply opening in the
roof curb.
7. Remove the roof cap, top cover and L brackets from the
filter end of the return section. Save these parts for later
installation. See Fig. 35 and 36.
8. Rig and set return section onto the roof curb using rail
guides as an alignment aid. The return section must be
within 2 in. of the main unit section. Slide base rail and
top rail guides from main unit section rails partially into
return section rails.
9. Install tar tape on edge of main unit base rails to seal base
rail splice. See Fig. 37.
10. Using ¾-in. x 30-in. threaded rod, nuts, washers and
backing plates provided, pull and secure the base rails together. See Fig. 38.
11. Attach (4) brackets to top rails. Using
threaded rods, nuts, washers and backing plates provided,
pull the top rails together and secure with top rail guide
from Step 5. See Fig. 39. Remove threaded rods and
brackets after securing top rail guide.
12. Place seal strip along both sides of basepan joint. Attach
basepan covers to basepan joint. See Fig. 40.
13. Install L brackets, top cover and top cap joining main unit
section and return section top cover assemblies. See
Fig. 41 and 42.
14. Connect control wiring plugs located at unit split. All
same color plugs should be connected together.
On units equipped with return air fan or power exhaust
fan option, locate black, yellow, and blue power wires located at the split in main section. Run the wires through
the grommet below the return air filters and through the
grommet at the economizer damper. See Fig. 43. Run
wires through wire trays, separate from control wires, to
the return fan/power exhaust fan VFD on back wall of return section. Connect wires to VFD power terminal connections: Black to UL1, Yellow to V1, and Blue to W1.
On units equipped with VFD bypass option connect the
wires to the power distribution in the VFD bypass box:
Black to L1, Yellow to L2, and Blue to L3. See Fig. 44.
Connect air pressure tubes located at split. All same numbered tubes should be connected together. See Table 12
for tubes associated with unit options.
15. Install side post on far side of unit. See Fig. 45.
16. Install side panels at main unit section/return section split.
Install panel side brackets, 2 on each panel. See Fig. 45.
3348NG5016292PLATEJOIN SPLIT UNITS
40PF01443 SEALER, PRESTITE2-in. WIDE ROLL
Table 12 — Air Pressure Tube Connections
OPTIONCONTROLTUBE NUMBER
Return Air FanRACFM Control PPSS4, 5 and 6
Power Exhaust
Fan with CFM
Sensor
Outdoor Air CFMOACFM Control7 and 8
EACFM Control5 and 6
34
ROOF
a50-8880
Fig. 35 — Roof Cap and Top Cover Removal
L BRACKETS
a50-8881
Fig. 36 — L Bracket Removal
INSTALL TAR TAPE ON
ENTIRE BASE RAIL EDGE
A50-8882
Fig. 37 — Tar Tape Location
a50-8883
Fig. 38 — Secure Base Rails
a50-8884
Fig. 39 — Top Rail Brackets
a50-8885
Fig. 40 — Basepan Joint/Cover
CAP
TOP
COVER
BASEPAN JOINT/COVER
35
L BRACKETS
A50-8886
Fig. 41 — L Bracket Installation
a50-8887
Fig. 42 — Main Unit and Return Section
Top Cover Assemblies
L
Fig. 43 — Wire Routing
TOP CAPS
TOP
COVER
END CAPS
VFD
36
SEE DETAIL A
DETAIL A
RUN VFD POWER WIRES
THROUGH THIS BUSHING,
SEPARATE FROM CONTRO
WIRES
VFD WITH BYPASS
A50-8889
Fig. 44 — Return Section Component Locations
A50-8890
Fig. 45 — Side Post and Panel Installation
DETAIL NN
VFD WITHOUT BYPASS
SEE DETAIL NN
SIDE POST
FAR SIDE ONLY
SIDE
PAN EL
SIDE
PAN EL
BRACKETS
DETAIL NN
VFD DETAILS
CONTROLS INSTALLATION
Constant Volume (CV) / Staged Air Volume
(SAV™) Units —
tions with additional control features, options, or accessories.
Refer to the appropriate accessory installation instructions for
more information on installing that accessory. Control options
and accessories available for CV/SAV units are:
• thermostats
• differential enthalpy sensor
• return air humidity sensor
• outdoor air humidity sensor
• relative humidity space sensor
•CO
sensors
2
• fan status switch
• filter pressure transducer
• return smoke detector
• CEM (controls expansion module)
• EXB (economizer control board) module
CONTROL WIRING — The unit can be controlled with a
Carrier-approved accessory electro-mechanical or electronic
thermostat that has two stages of cooling, two stages of heating
control, and an output for fan control. The thermostat may also
include time of day scheduling or use scheduling routines built
into the ComfortLink controls.
Install the thermostat according to the installation instructions shipped with the accessory thermostat. Locate thermostat
assembly on a solid interior wall to sense average temperature.
The 48N units may be used in applica-
37
Route thermostat cable or equivalent leads of colored wire
Fig. 46 — Field Control Thermostat Wiring
a48-8735
Fig. 47 — T-55 or T-56 Wiring
a48-8736
from subbase terminals through conduit into the low voltage
connections in the main control box. For thermostat TB201
connections, see Fig. 46.
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American
Wire Gage) insulated wire (35 C minimum). For over 75 ft, use
no. 14 AWG insulated wire (35 C minimum). All wire larger
than no. 18 AWG cannot be directly connected at the thermostat
and will require a junction box and splice at the thermostat.
FIELD SUPPLIED THERMOSTAT
Y1Y2W1W2G
RC
R
C
R
Y1Y2W1W2G
TB201
X
Variable Air Volume (VAV) Units — The 48N
units may be used in applications with additional control features, options, or accessories. Refer to the appropriate accessory installation instructions for more information on installing
that accessory. Refer to the Controls and Troubleshooting manual for more information concerning installation and configuration of options and accessories. Control options and accessories
available for VAV units are:
• thermostats
• differential enthalpy sensor
• return air humidity sensor
• outdoor air humidity sensor
• relative humidity space sensor
•CO
sensors
2
• fan status switch
• filter pressure transducer
• return smoke detector
• CEM (controls expansion module)
• EXB (economizer control board) module
VAV CONTROL WIRING — The recommended types of
control wiring are shown below:
MANUFACTURER
Alpha1895—
AmericanA21451A48301
Belden8205884421
ColumbiaD6451—
ManhattanM13402M64430
Quabik6130—
Regular WiringPlenum Wiring
PART NO.
COMMUNICATING SPACE TEMPERATURE SENSOR
(T-58) — The communicating space temperature sensor (P/N
33ZCT58SPT) is wired to the Carrier Comfort Network
(CCN) connections on TB202.
SPACE TEMPERATURE AVERAGING — Applications
that require averaging using multiple space temperature sensors can be satisfied using either 4 or 9 sensors as shown in Fig.
48.
NOTE: Only Carrier sensors may be used for standard T-55
space averaging. Sensors must be used in multiples of 1, 4, and
9 only, with total sensors wiring not to exceed 1000 ft.
NOTE: Do not use T-56 sensors for space temperature averaging because the 5-degree offset function will not work in a
multiple sensor application.
HEAT INTERLOCK RELAY (VAV Units Only — Not Necessary for Digital Air Volume Applications) — Variable air volume (VAV) units using morning warm-up and/or occupied
heating require that room terminals be controlled to a position
that provides the minimum required heating cfm or greater
when the unit goes into Heating mode. The HIR (heat interlock
relay) function is provided for this control. When the unit goes
into Heating mode, the HIR is energized to provide switch closure or opening (depending on how the field-supplied power
source is set up) to open the room terminals. The field connections for the HIR are at TB201 terminals 9 and 10. See Fig. 49.
Option and Accessory Control Wiring —
The 48N Series units may be used in applications with additional control features, options, or accessories. Refer to the
Controls, Start-Up, Operation, Service and Troubleshooting
manual for more information concerning installation and configuration of options and accessories. Figures 49-59 contain
wiring information on the following features:
• heat interlock relay (Fig. 49)
• outdoor air enthalpy switch (Fig. 50)
•CO
space sensor (Fig. 51)
2
• filter status switch (Fig. 52)
• fan status switch (Fig. 53)
• space humidity sensor (Fig. 54)
• return air humidity sensor (Fig. 54)
• return air CO
• return air smoke detector (Fig. 56)
• smoke control — fire shutdown (Fig. 57)
• smoke control — purge (Fig. 58)
• smoke control — evacuation (Fig. 58)
• smoke control — pressurization (Fig. 58)
• CCN connections (Fig. 59)
sensor (Fig. 55)
2
SEN
T56- SPTT55- SPT
SENSET
JUMPER
TERMINALS
®
SENSORS — Sensors should be wired using single twisted
pairs of 20 AWG (American Wire Gage) conductor cable rated
for the application, except for the T-56 accessory sensor which
requires 3-conductor cable.
HUMIDITY CONTROL AND HOT WATER AND
STEAM VALVES — These devices require 20 AWG twisted
pair conductor cables rated for the application for the 4 to
20 mA signal.
SPACE TEMPERATURE SENSOR (T-55) — The space
temperature sensor (P/N 33ZCT55SPT), if used, is wired to
terminals in the unit main control box. To connect the space
temperature sensor, see Fig. 47.
SPACE TEMPERATURE SENSOR (T-56) — The space
temperature sensor (P/N 33ZCT56SPT), if used, is wired to
terminals in the unit main control box. To connect the space
temperature sensor, see Fig. 47.
38
UNIT
TB201
1
3
24
TB201
11
7
8
T55
9
10
21
3
5
6
13
15
12
16
14
T55
Fig. 48 — Space Temperature Averaging Wiring
NOTE: Use T-55 sensor only.
a48-8737
13
14
15
10
9
RCB
J8
RELAY 5
Fig. 49 — Heat Interlock Relay Wiring
a48-8477
TB201
1
2
RED
BLK
T55
TB201
1
2
SENSOR 1
SPACE TEMPERATURE AVERAGING (4 SENSOR
APPLICATION)
SENSOR 1
SENSOR 4
SENSOR 2
SENSOR 2
SENSOR 5
SENSOR 3
SENSOR 4
SENSOR 3
SENSOR 6
SENSOR 7
SPACE TEMPERATURE AVERAGING (9 SENSOR
APPLICATION)
39
SENSOR 8
SENSOR 9
FIELD INSTALLED (FIELD
SUPPLIED) JUMPER WHEN
ENTHALPY SWITCH NOT USED
RCB
J4
6
5
Fig. 50 — Outdoor Air Enthalpy Switch Wiring
a48-8478
MBB
J8
7
8
TB201
Fig. 51 — CO2 Space Sensor Wiring
a48-8479
FILTER STATUS - RETURN SWITCH
GRA
BLK
1
CEM
J5
AN 5
2
180 OHM
3
4
5
6
180 OHM
CEM
J5
CEM
J6
FILTER PRESSURE RETURN
FILTER STATUS - POST FILTER
FILTER PRESSURE - POST FILTER
BLU
VIO
AN 6
AN 7
GRA
ORN
_
+
BLU
RED
_
+
Fig. 52 — Filter Status Wiring
a48-8738
40
RXB
J4
Fig. 53 — Fan Status Switch Wiring
a48-8741
CEM
J6
OA HUMIDITY
4 - 20 ma
SPACE HUMIDITY
4 - 20 ma
RETURN HUMIDITY
4 - 20 ma
PL29-1
PL29-2
RED
BLK
3
RED
BLK
4
5
+
ACCSY
ACCSY
ACCSY
+
-
+
-
24VDC
AN8
24VDC
AN9
24VDC
AN10
6
7
8
9
10
11
12
ORN
GRN
BLU
BLU
VIO
VIO
PL37-5
PL37-6
TB202
3
4
MIXED AIR HUMIDITY
4 - 20 ma
ACCSY
+
-
AN7
1
2
RED
ORN
TB203
8
7
Fig. 54 — Space and Return Air Humidity Sensor Wiring
a48-8740
41
RED
BRN
Fig. 55 — Return Air CO2 Sensor Wiring
a48-8483
TB201TB201
1
2
PL45-1
PL45-3
PL45-2
PL45-6
PL45-5
PL45-4
Fig. 56 — Return Air Smoke Detector Wiring
a48-8739
MBB
J6
TB201
1
2
BLU
WHT
FIRE SHUTDOWN
Fig. 57 — Fire Shutdown Wiring
a48-8485
42
14
Fig. 58 — Purge, Evacuation, and Pressurization Wiring
a48-8486
TB201
MBB
J5
Fig. 59 — CCN Connections
a48-8487
15
16
17
18
19
TB 202
RCB J4
43
Carrier Comfort Network® (CCN) Interface —
The 48N Series units can be connected to the CCN system if
desired. The communication bus wiring is supplied and
installed in the field. It consists of shielded, 3-conductor cable
with shield wire.
The system elements are connected to the communication
bus in a daisy chain arrangement. The positive pin of each
system element communication connector must be wired to the
positive pins of the system element on either side of it, the
negative pins must be wired to the negative pins, and the signal
pins must be wired to common pins. Wiring connections for
the CCN system should be made at the terminal block using the
screw terminals. The board also contains an RJ14 CCN plug
that can be used to connect a field service computer. There is
also another RJ14 LEN (Local Equipment Network) connection that is used to download software or connect a Navigator™ device.
NOTE: Conductors and drain wire must be 20 AWG minimum
stranded, tinned copper. Individual conductors must be insulated with PVC, PVC/nylon, vinyl, Teflon*, or polyethylene.
An aluminum/polyester 100% foil shield and an outer jacket of
PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum
operating temperature range of –4 to 140 F (–20 C to 60 C) is
required. See Table 13 for cables that meet the requirements.
Table 13 — CCN Connection Approved
MANUFACTURERCABLE PART NO.
Alpha2413 or 5463
AmericanA22503
Belden8772
Columbia02525
IMPORTANT: When connecting the CCN communication bus to a system element, use a color coding system for
the entire network to simplify installation and checkout.
The following color code is recommended:
SIGNAL
TYPE
+RED1
COMMONWHITE2
–BLACK3
NOTE: If a cable with a different color scheme is selected, a
similar color code should be adopted for the entire network.
At each system element, the shields of its communication
bus cables must be tied together. If the communication bus is
entirely within one building, the resulting continuous field
must be connected to a ground at one point only. If the communication bus cable exits from one building and enters another,
the shields must be connected to grounds at the lightning
suppressor in each building where the cable enters or exits the
building (one point per building only).
To connect the unit to the network (Fig. 59):
1. Turn off power to the control box.
2. Cut the CCN wire and strip the ends of the red (+), white
(common) and black (–) conductors. (If a different network color scheme is used, substitute appropriate colors.)
Shielded Cables
CCN BUS CONDUCTOR
INSULATION COLOR
COMM1 PLUG
PIN NO.
3. Wire the CCN to the screw terminals on the COMM
board as follows:
a. Secure the red (+) wire to CCN screw terminal +
on the COMM board.
b. Secure the white (common) wire to CCN screw
terminal C on the COMM board.
c. Secure the black (–) wire to CCN screw terminal –
on the COMM board.
d. Secure shield wire to CCN screw terminal
SHIELD on the COMM board.
IMPORTANT: A shorted CCN bus cable will prevent
some routines from running and may prevent unit from
starting. If abnormal conditions occur, unplug the connector. If conditions return to normal, check CCN connector,
and run new cable if necessary. A short in one section of
the bus can cause problems with all system elements on
the bus.
Optional UPC Open Installation
WIRING THE UPC OPEN TO THE MS/TP NETWORK — The UPC Open controller communicates using
BACnet† on an MS/TP network segment communications at
9600 bps, 19.2 kbps, 38.4 kbps, or 76.8 kbps.
Wire the controllers on an MS/TP network segment in a daisy-chain configuration. Wire specifications for the cable are
22 AWG (American Wire Gage) or 24 AWG, low-capacitance,
twisted, stranded, shielded copper wire. The maximum length
is 2000 ft.
Install a BT485 terminator on the first and last controller on
a network segment to add bias and prevent signal distortions
due to echoing. See Fig. 60-62.
To wire the UPC Open controller to the BAS network:
1. Pull the screw terminal connector from the controller's
BAS Port.
2. Check the communications wiring for shorts and
grounds.
3. Connect the communications wiring to the BAS port’s
screw terminals labeled Net +, Net -, and Shield.
NOTE: Use the same polarity throughout the network
segment.
4. Insert the power screw terminal connector into the UPC
Open controller's power terminals if they are not currently connected.
5. Verify communication with the network by viewing a
module status report. To perform a module status report
using the BACview keypad/display unit, press and hold
the “FN” key then press the “.” key.
To install a BT485 terminator, push the BT485 on to the
BT485 connector located near the BACnet connector.
NOTE: The BT485 terminator has no polarity associated with
it.
To order a BT485 terminator, consult Commercial Products
®
i-Vu
Open Control System Master Prices.
*Teflon is a registered trademark of DuPont.
†BACnet is a registered trademark of ASHRAE (American Society
of Heating, Refrigerating and Air-Conditioning Engineers).
Conductor 22 or 24 AWG stranded copper (tin plated)
Insulation Foamed FEP 0.015 in. (0.381 mm) wall 0.060 in. (1.524 mm) O.D.
Color Code Black/White
Twist Lay 2 in. (50.8 mm) lay on pair 6 twists/foot (20 twists/meter) nominal
Shielding Aluminum/Mylar shield with 24 AWG TC drain wire
Jacket
DC Resistance 15.2 Ohms/1000 feet (50 Ohms/km) nominal
Capacitance 12.5 pF/ft (41 pF/meter) nominal conductor to conductor
Characteristic Impedance 100 Ohms nominal
Weight 12 lb/1000 feet (17.9 kg/km)
UL Temperature Rating
Voltage 300 Vac, power limited
Listing UL: NEC CL2P, or better
LEGEND
AWG— American Wire Gage
CL2P— Class 2 Plenum Cable
DC— Direct Current
FEP— Fluorinated Ethylene Polymer
NEC— National Electrical Code
O.D.— Outside Diameter
TC— Tinned Copper
UL— Underwriters Laboratories
Table 15 — Open System Wiring Specifications and Recommended Vendors
MS/TP WIRING RECOMMENDATIONS — Recommendations are shown in Tables 14 and 15. The wire jacket
and UL temperature rating specifications list two acceptable
alternatives. The Halar* specification has a higher temperature rating and a tougher outer jacket than the SmokeGard†
specification, and it is appropriate for use in applications
where the user is concerned about abrasion. The Halar jacket is also less likely to crack in extremely low temperatures.
NOTE: Use the specified type of wire and cable for maximum
signal integrity.
Smoke Control Modes — Rooftop units can be used
for aid in building smoke control in the event of a building fire.
The available functions include: Fire Shutdown, Pressurization, Evacuation, and Smoke Purge. These functions are
enhanced when multiple rooftop units are used to zone a building. See Table 16 and Fig. 57 and 58.
FIRE SHUTDOWN — Fire Shutdown mode terminates all
unit operation (cooling, heating, supply fan, and power
exhaust). This mode prevents recirculation of contaminated air
back into the space. The mode will not allow admission into
the space of unsuitable outside air. See Fig. 57 for wiring.
Table 14 — MS/TP Wiring Recommendations
SmokeGard Jacket (SmokeGard PVC) 0.021 in. (0.5334 mm) wall 0.175 in. (4.445 mm) O.D.
Halar Jacket (E-CTFE) 0.010 in. (0.254 mm) wall 0.144 in. (3.6576 mm) O.D.
SmokeGard 167°F (75°C)
Halar -40 to 302°F (-40 to 150°C)
WIRING SPECIFICATIONS RECOMMENDED VENDORS AND PART NUMBERS
AWG— American Wire Gage
CL2P— Class 2 Plenum Cable
CMP— Communications Plenum Rated
FEP— Fluorinated Ethylene Polymer
TC— Tinned Copper
*Halar is a registered trademark of Solvay Plastics.
†SmokeGard is a trademark of AlphaGary-Mexichem Corp.
22 AWG, single twisted shielded pair, low capacitance, CL2P, TC foam
FEP, plenum rated. See MS/TP Installation Guide for specifications.
24 AWG, single twisted shielded pair, low capacitance, CL2P, TC foam
FEP, plenum rated. See MS/TP Installation Guide for specifications.
Connect Air
International
W221P-22227—25160PVCLP0520LC
W241P-2000F8284125120-OR—
Belden RMCORP
46
Contractors
Wire and Cable
PRESSURIZATION — Pressurization mode is intended to
keep smoke out of a zone. The factory-installed optional
economizer is required for this function. Pressurization is accomplished by the following:
• opening the economizer (option)
• running the supply fan (optional inlet guide vanes open or
optional VFD at normal duct static pressure set point)
• closing the power exhaust dampers (if installed as option or
accessory)
• shutting off the power exhaust fans (if installed as option or
accessory)
This allows the space to be overpressurized relative to adjacent
zones and prevents or slows entry of smoke into this space
from adjacent zones. See Fig. 58 for wiring.
EVACUATION — Evacuation mode removes smoke or undesirable air from interior spaces without reintroducing unsuitable air. The factory-installed optional economizer with option/
accessory power exhaust is required for this function. Evacuation is accomplished by the following:
• turning the supply fan off
• opening the economizer (option required)
• running the exhaust fans (option or accessory required)
• opening the exhaust dampers.
See Fig. 58 for wiring.
SMOKE PURGE — Smoke Purge mode removes smoke from
the interior spaces and replaces it with fresh outside air. The
factory-installed optional economizer with option/accessory
power exhaust are required for this function. Smoke purge is
accomplished by the following:
• turning supply fan on
• opening the economizer (option required)
• running the exhaust fans (option or accessory required)
• opening the exhaust dampers
See Fig. 58 for wiring.
SMOKE CONTROL INSTALLATION — Implementation of the various smoke control modes on these units requires the installer to modify the unit wiring to add contacts (via either manual switches or relays) that will selectively interrupt and override standard factory control
sequences. See Table 16 and Fig. 56 and 57 and the Controls, Start-Up, Operation, Service and Troubleshooting
manual for more information.
Table 16 — Smoke Control Modes
FUNCTION
Supply FanOffOnOffOn
VFD†—Open/On—Open/On
EconomizerClosedOpenOpenOpen
Return Air
Damper
Exhaust
Fans
Exhaust
Damper
LEGEND
VAV — Variable Air Volume
VFD — Variable Frequency Drive
*Power exhaust option required for this mode.
†Applicable to VAV units with appropriate options.