Carrier WeatherMaster 48HC14, WeatherExpert 48LC**08 Series, WeatherExpert 48LC**09 Series, WeatherExpert 48LC**12 Series Installation Instructions Manual

WeatherMaster
48HC14
Single Package Rooftop Gas Heat/Electric Cooling
®
Unit with Puron
(R-410A) Refrigerant
Installation Instructions
48HC units for installation in the United States contain use of Carrier's Staged Air Volume (SAV™) 2-speed indoor fan control system. This complies with the U.S. Department of Energy (DOE) efficiency standard of
2018. 48HC units for installation outside the United States may or may not contain use of the SAV 2-speed indoor fan control system as they are not required to comply with the U.S. Department of Energy (DOE) efficiency standard of 2018. For specific details on operation of the Carrier SAV 2-speed indoor fan system refer to the Variable Frequency Drive (VFD) Factory-Installed Option 2-Speed Motor Control Installation, Setup, and Troubleshooting manual.
®
CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . 1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Rated Indoor Airflow (cfm) . . . . . . . . . . . . . . . . . . . . . 3
INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Step 1 — Plan for Unit Location . . . . . . . . . . . . . . . . . 7
• ROOF MOUNT
Step 2 — Plan for Sequence of Unit Installation . . . . 7
• CURB-MOUNTED INSTALLATION
• PAD-MOUNTED INSTALLATION
• FRAME-MOUNTED INSTALLATION
Step 3 — Inspect Unit . . . . . . . . . . . . . . . . . . . . . . . . . 8
Step 4 — Provide Unit Support. . . . . . . . . . . . . . . . . . 8
• ROOF CURB MOUNT
• SLAB MOUNT (HORIZONTAL UNITS ONLY)
• ALTERNATE UNIT SUPPORT (IN LIEU OF CURB OR SLAB MOUNT)
Step 5 — Field Fabricate Ductwork . . . . . . . . . . . . . 10
Step 6 — Rig and Place Unit . . . . . . . . . . . . . . . . . . . 10
• POSITIONING ON CURB
Step 7 — Convert to Horizontal and Connect
Ductwork (When Required). . . . . . . . . . . . . . . . . . 11
Step 8 — Install Outside Air Hood . . . . . . . . . . . . . . 12
• ECONOMIZER HOOD REMOVAL AND SETUP — FACTORY OPTION
• TWO POSITION DAMPER HOOD REMOVAL AND SETUP — FACTORY OPTION
• ECONOMIZER HOOD AND TWO-POSITION HOOD
Step 9 — Install Flue Hood . . . . . . . . . . . . . . . . . . . . 14
Step 10 — Install Gas Piping. . . . . . . . . . . . . . . . . . . 14
• FACTORY OPTION THRU-BASE CONNECTIONS (GAS CONNECTION)
Step 11 — Install External Condensate Trap and
Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Step 12 — Make Electrical Connections . . . . . . . . . 18
• FIELD POWER SUPPLY
• ALL UNITS
• UNITS WITHOUT FACTORY-INSTALLED NON­FUSED DISCONNECT OR HACR CIRCUIT BREAKER
• UNITS WITH FACTORY-INSTALLED NON-FUSED DISCONNECT OR HACR CIRCUIT BREAKER
• CONVENIENCE OUTLETS
• HACR CIRCUIT BREAKER
• FACTORY OPTION THRU-BASE CONNECTIONS (ELECTRICAL CONNECTIONS)
• UNITS WITHOUT THRU-BASE CONNECTIONS
• FIELD CONTROL WIRING
• THERMOSTAT
• UNIT WITHOUT THRU-BASE CONNECTION KIT
• HEAT ANTICIPATOR SETTINGS
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
• HUMIDI-MIZER — SPACE RH CONTROLLER
EconoMi$er® X (Factory Option) . . . . . . . . . . . . . . .30
• SYSTEM COMPONENTS
• SPECIFICATIONS
•INPUTS
•OUTPUTS
• ENVIRONMENTAL
• ECONOMIZER MODULE WIRING DETAILS
• INTERFACE OVERVIEW
• SETUP AND CONFIGURATION
• ENTHALPY SETTINGS
• TWO-SPEED FAN OPERATION
• CHECKOUT
• TROUBLESHOOTING
Low Ambient Control (Factory Option). . . . . . . . . . .43
Staged Air Volume (SAV™) with Variable Frequency
Drive (Factory Option) . . . . . . . . . . . . . . . . . . . . . .43
ComfortLink Controls (Factory Option) . . . . . . . . . .43
PremierLink™ Controller (Factory Option) . . . . . . .47
RTU Open Controller System (Factory-Installed
Option). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Smoke Detectors. . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
• ADDITIONAL APPLICATION DATA
Step 13 — Adjust Factory-Installed Options . . . . . .48
• SMOKE DETECTORS
• ECONOMI$ER IV OCCUPANCY SWITCH
Step 14 — Install Accessories . . . . . . . . . . . . . . . . . .48
Step 15 — Check Belt Tension . . . . . . . . . . . . . . . . .48
• BELT FORCE — DEFLECTION METHOD
• BELT TENSION METHOD
Pre-Start and Start-Up . . . . . . . . . . . . . . . . . . . . . . . .49
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . .CL-1
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or
Catalog No. 04-53480222-01 Printed in U.S.A. Form 48HC-14-04SI Pg 1 2-19 Replaces: 48HC-14-03SI
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloths for brazing operations and have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and appropriate national electrical codes (in USA, ANSI/NFPA70, National Electrical Code (NEC); in Canada, CSA C22.1) for special requirements.
It is important to recognize safety information. This is the safety-alert symbol . When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety­alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
WARNING
FIRE, EXPLOSION HAZARD Failure to follow this warning could result in death, serious
personal injury and/or property damage. Disconnect gas piping from unit when pressure testing at
pressure greater than 0.5 psig. Pressures greater than 0.5 psig will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pressure greater than
0.5 psig, it must be replaced before use. When pressure testing field-supplied gas piping at pressures of 0.5 psig or less, a unit connected to such piping must be isolated by closing the manual gas valve(s).
WARNING
ELECTRICAL SHOCK HAZARD Failure to follow this warning could cause personal injury
or death. Before performing service or maintenance operations on
unit, turn off main power switch to unit and install lock(s) and lockout tag(s). Ensure electrical service to rooftop unit agrees with voltage and amperage listed on the unit rating plate. Unit may have more than one power switch.
WARNING
WARNING
CARBON-MONOXIDE POISONING HAZARD Failure to follow instructions could result in severe personal
injury or death due to carbon-monoxide poisoning, if com­bustion products infiltrate into the building.
Check that all openings in the outside wall around the vent (and air intake) pipe(s) are sealed to prevent infiltration of combustion products into the building.
Check that furnace vent (and air intake) terminal(s) are not obstructed in any way during all seasons.
AVERTISSEMENT
RISQUE D’INTOXICATION AU MONOXYDE DE CARBONE
Si ces directives ne sont pas suivies, cela peut entraîner des blessures graves ou une intoxication au monoxyde de carbone pouvant causer la mort, si des produits de combustion s’infiltrent dans le bâtiment.
Vérifier que toutes les ouvertures pratiquées dans le mur extérieur autour du ou des tuyaux d’évent (et de la prise d’air) sont scellées de manière à empêcher l’infiltration de produits de combustion dans le bâtiment.
Veiller à ce que la ou les sorties de l’évent de l’appareil de chauffage (et la prise d’air) ne soient, en aucune façon, obstruées, quelle que soit la saison.
WARNING
PERSONAL INJURY AND ENVIRONMENTAL HAZARD Failure to follow this warning could cause personal injury
or death. Relieve pressure and recover all refrigerant before system
repair or final unit disposal. Wear safety glasses and gloves when handling refrigerants.
Keep torches and other ignition sources away from refriger­ants and oils.
WARNING
CUT HAZARD Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing air conditioning equipment.
UNIT OPERATION AND SAFETY HAZARD Failure to follow this warning could cause personal injury,
death and/or equipment damage.
®
Puron
(R-410A) refrigerant systems operate at higher pres­sures than standard R-22 systems. Do not use R-22 service equipment or components on Puron refrigerant equipment.
2
WARNING
GAS VALVE
INLET PRESSURE
TAP SET SCREW
WARNING
FIRE HAZARD Failure to follow this warning could result in personal inju-
ry, death, and/or property damage. Inlet pressure tap set screw must be tightened and
1
/8-in.
NPT pipe plug must be installed to prevent gas leaks.
FIRE HAZARD Failure to follow this warning could result in personal inju-
ry, death, and/or property damage. Manifold pressure tap set screw must be tightened and
1
/8-in.
NPT pipe plug must be installed to prevent gas leaks.
MANIFOLD PRESSURE
TAP SET SCREW
MANIFOLD
GAS VALVE
GENERAL
See Fig. 1-3 for unit options and dimensions.
Rated Indoor Airflow (cfm)
Table 1 lists the rated indoor airflow used for the AHRI effi­ciency rating for the units covered in this document.
Table 1 — Rated Indoor Airflow (cfm)
MODEL NUMBER
48HC*D/E/G14 4375
FULL LOAD AIRFLOW
(CFM)
3
Model Series - WeatherMaster
®
HC - High Efficiency
Unit Heat Type
48 - Gas Heat Packaged Rooftop
Cooling Tons
14 - 12.5 ton
Heat Options
D = Low Gas Heat E = Medium Gas Heat F = High Gas Heat S = Low Heat w/ Stainless Steel Exchanger R = Medium Heat w/ Stainless Steel Exchanger T = High Heat w/ Stainless Steel Exchanger
Sens or Options
A = None B = RA Smoke Detector C = SA Smoke Detector D = RA + SA Smoke Detector E = CO
2
F = RA Smoke Detector and CO
2
G = SA Smoke Detector and CO
2
H = RA + SA Smoke Detector and CO
2
Indoor Fan Options
1 = Standard Static Option - Belt Drive 2 = Medium Static Option - Belt Drive 3 = High Static Option - Belt Drive C = High Static Option with High Efficiency Motor - Belt Drive
Refrig. Sys te ms Options
D = Two stage cooling model E = Two stage cooling models with Humidi-MiZer G = Two stage cooling models with Motormaster Low Ambient Controller
Coil Options (RTPF) (Outdoor - Indoor - Hail Guard)
A = Al/Cu - Al/Cu B = Precoat Al/Cu - Al/Cu C = E-coat Al/Cu - Al/Cu D = E-coat Al/Cu - E-coat Al/Cu E = Cu/Cu - Al/Cu F = Cu/Cu - Cu/Cu M = Al/Cu -Al/Cu — Louvered Hail Guard N = Precoat Al/Cu - Al/Cu — Louvered Hail Guard P = E-coat Al/Cu - Al/Cu — Louvered Hail Guard Q = E-coat Al/Cu - E-coat Al/Cu — Louvered Hail Guard R = Cu/Cu - Al/Cu — Louvered Hail Guard S = Cu/Cu - Cu/Cu — Louvered Hail Guard
Voltage
1 = 575/3/60 5 = 208-230/3/60 6 = 460/3/60
Design Revision
A = Factory Design Revision
Base Unit Controls
0 = Electro-mechanical Controls Can be used with W7212 EconoMi$er IV (Non-Fault Detection and Diagnostic) 1 = PremierLink Controller 2 = RTU Open Multi-Protocol Controller 6 = Electro-mechanical w/ 2-speed fan and W7220 Econo controller Controls. Can be used with W7220 EconoMi$er X (with Fault Detection and Diagnostic) D = ComfortLink Controls
Intake / Exhaust Options
A = None B = Temperature Economizer w/ Barometric Relief F = Enthalpy Economizer w/ Barometric Relief K = 2-Position Damper U =
Temp Ultra Low Leak Economizer w/ Baro Relief
W =
Enthalpy Ultra Low Leak Economizer w/ Baro Relief
Service Options
0 = None 1 = Unpowered Convenience Outlet 2 = Powered Convenience Outlet 3 = Hinged Panels 4 = Hinged Panels and Unpowered Convenience Outlet 5 = Hinged Panels and Powered Convenience Outlet C = Foil Faced Insulation D = Foil Faced Insulation with Unpowered Convenience Outlet E = Foil Faced Insulation with Powered Convenience Outlet F = Foil Faced Insulation & Hinged Panels G = Foil Faced Insulation & Hinged Panels with Unpowered Convenience Outlet H = Foil Faced Insulation & Hinged Panels with Powered Convenience Outlet
Factory Assigned
0 = Standard 1 = LTL
Electrical Options
A = None B = HACR Breaker C = Non-Fused Disconnect D = Thru-The-Base Connections E = HACR and Thru-The-Base Connections F = Non-Fused Disconnect and Thru-The-Base G = 2-Speed Indoor Fan (VFD) Controller H = 2-Speed Fan Controller (VFD) and HACR J = 2 Speed Fan Controller & Non-Fused Disconnect K =
2-Speed Fan Controller w/ Thru-The-Base L = HACR w/ Thru-The-Base & 2-Speed Fan Controller M = 2-Speed Fan Controller w/ Non-Fused Disconnect & Thru-The-Base
Example:
Position:
48HCDE14A2A6A0A3B0
1234567891011 12 13 14 15 16 17 18
Fig. 1 — 48HC 14 Model Number Nomenclature
4
Fig. 2 — Unit Dimensional Drawing — 14 Size Unit
5
Fig. 2 — Unit Dimensional Drawing — 14 Size Unit (cont)
6
NOTE: Unit not designed to have overhead obstruction. Contact Application Engineering for guidance on any application planning overhead obstruc­tion or for vertical clearances.
LOCATION DIMENSION CONDITION
A
48-in. (1219 mm) 18-in. (457 mm) 18-in. (457) mm 12-in. (305 mm)
Unit disconnect is mounted on panel No disconnect, convenience outlet option Recommended service clearance Minimum clearance
B
42-in. (1067 mm) 36-in. (914 mm) Special
Surface behind servicer is grounded (e.g., metal, masonry wall) Surface behind servicer is electrically non-conductive (e.g., wood, fiberglass) Check sources of flue products within 10 ft (3 m) of unit fresh air intake hood
C
36-in. (914 mm) 18-in. (457 mm)
Side condensate drain is used Minimum clearance
D
48-in. (1219 mm) 42-in. (1067 mm) 36-in. (914 mm) Special
No flue discharge accessory installed, surface is combustible material Surface behind servicer is grounded (e.g., metal, masonry wall, another unit) Surface behind servicer is electrically non-conductive (e.g., wood, fiberglass) Check for adjacent units or building fresh air intakes within 10 ft (3 m) of this unit’s flue outlet
C
B
A
D
Fig. 3 — Service Clearance Dimensional Drawing
INSTALLATION
Jobsite Survey
Complete the following checks before installation.
1. Consult local building codes and the NEC (National Elec­trical Code) ANSI/NFPA 70 for special installation requirements.
2. Determine unit location (from project plans) or select unit location.
3. Check for possible overhead obstructions which may interfere with unit lifting or rigging.
Step 1 — Plan for Unit Location
Select a location for the unit and its support system (curb or other) that provides for at least the minimum clearances re­quired for safety. This includes the clearance to combustible surfaces, unit performance and service access below, around and above unit as specified in unit drawings. See Fig. 3.
NOTE: Consider also the effect of adjacent units. Unit may be installed directly on wood flooring or on Class A,
B, or C roof-covering material when roof curb is used. Do not install unit in an indoor location. Do not locate air inlets
near exhaust vents, relief valves, or other sources of contami­nated air.
Although unit is weatherproof, avoid locations that permit wa­ter from higher level runoff and overhangs to fall onto the unit.
Select a unit mounting system that provides adequate height to allow installation of condensate trap per requirements. Refer to “Step 11 — Install External Condensate Trap and Line” on page 17 for required trap dimensions.
ROOF MOUNT Check building codes for weight distribution requirements.
Unit operating weight is shown in Table 2.
Step 2 — Plan for Sequence of Unit Installation
The support method used for this unit will dictate different se­quences for the steps of unit installation. For example, on curb­mounted units, some accessories must be installed on the unit before the unit is placed on the curb. Review the following for recommended sequences for installation steps.
CURB-MOUNTED INSTALLATION
1. Install curb
2. Install field-fabricated ductwork inside curb
3. Install accessory thru-base service connection package (affects curb and unit) (refer to accessory installation instructions for details)
4. Prepare bottom condensate drain connection to suit planned condensate line routing (refer to “Step 11 — Install External Condensate Trap and Line” on page 17 for details)
5. Rig and place unit
7
6. Install outdoor air hood
7. Install condensate line trap and piping
8. Make electrical connections
9. Install other accessories
PAD-MOUNTED INSTALLATION
1. Prepare pad and unit supports
2. Check and tighten the bottom condensate drain connection plug
3. Rig and place unit
4. Convert unit to side duct connection arrangement
5. Install field-fabricated ductwork at unit duct openings
6. Install outdoor air hood
7. Install condensate line trap and piping
8. Make electrical connections
9. Install other accessories
FRAME-MOUNTED INSTALLATION Frame-mounted applications generally follow the sequence for
a curb installation. Adapt as required to suit specific installa­tion plan.
Step 3 — Inspect Unit
Inspect unit for transportation damage. File any claim with transportation agency.
Confirm before installation of unit that voltage, amperage and circuit protection requirements listed on unit data plate agree with power supply provided.
On units with hinged panel option, check to be sure all latches are snug and in closed position.
Locate the carton containing the outside air hood parts; see Fig. 13 and 14. Do not remove carton until unit has been rigged and located in final position.
Step 4 — Provide Unit Support
ROOF CURB MOUNT Accessory roof curb details and dimensions are shown in
Fig. 4. Assemble and install accessory roof curb in accordance with instructions shipped with the curb.
NOTE: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket supplied with the roof curb as shown in Fig. 4. Improperly applied gasket can also result in air leaks and poor unit performance.
Curb should be level. This is necessary for unit drain to func­tion properly. Unit leveling tolerances are show in Fig. 5. Refer to Accessory Roof Curb Installation Instructions for additional information as required.
Table 2 — Operating Weights
48HC**14
COMPONENT UNITS LB (KG) BASE UNIT ECONOMIZER Vertical Horizontal Powered Outlet Humidi-MiZer System CURB 14-in. (356 mm) 24-in. (610 mm)
1430 (649)
103 (47)
242 (110)
35 (16) 90 (41)
180 (82)
255 (116)
8
Fig. 4 — Roof Curb Details
9
MAXIMUM ALLOWABLE DIFFERENCE IN. (MM)
A-B B-C A-C
0.5” (13) 1.0” (25) 1.0” (25)
A
B
C
Step 5 — Field Fabricate Ductwork
NOTE: Cabinet return-air static pressure (a negative condition) shall not exceed 0.35 in. wg (87 Pa) with economizer or
0.45 in. wg (112 Pa) without economizer. For vertical ducted applications, secure all ducts to roof curb
and building structure. Do not connect ductwork to unit. Fabricate supply ductwork so that the cross sectional dimen-
sions are equal to or greater than the unit supply duct opening dimensions for the first 18-in. (458 mm) of duct length from the unit basepan.
Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through unconditioned spaces must be insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes.
Fig. 5 — Unit Leveling Tolerances
Install insulation, cant strips, roofing felt, and counter flashing as shown. Ductwork must be attached to curb and not to the unit.
IMPORTANT: If the unit’s gas connection and/or electric and control wiring is to be routed through the basepan and the unit is equipped with the factory-installed Thru-the-Base service option see the following sections:
• Factory-Option Thru-Base Connections (Gas Connec­tion) on page 15
• Factory-Option Thru-Base Connections (Electrical Con­nections) on page 23
If using the field-installed Thru-the-Base accessory follow the instructions provided with the accessory kit.
NOTE: If gas and/or electrical connections are not going to occur at this time, tape or otherwise cover the fittings so that moisture does not get into the building or conduit in the interim.
SLAB MOUNT (HORIZONTAL UNITS ONLY) Provide a level concrete slab that extends a minimum of 6-in.
(150 mm) beyond unit cabinet. Install a gravel apron in front of condenser coil air inlet to prevent grass and foliage from ob­structing airflow.
NOTE: Horizontal units may be installed on a roof curb if required.
ALTERNATE UNIT SUPPORT (IN LIEU OF CURB OR SLAB MOUNT)
A non-combustible sleeper rail can be used in the unit curb support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 3 equally spaced 4-in. x 4-in. (102 mm x 102 mm) pads on each side.
CAUTION
PROPERTY DAMAGE HAZARD Failure to follow this caution may result in damage to roofing
materials. Membrane roofs can be cut by sharp sheet metal edges. Be
careful when placing any sheet metal parts on such roof.
Step 6 — Rig and Place Unit
When the unit is ready to be rigged and no longer will be lifted by a fork truck, the wood protector under the basepan must be removed. Remove 4 screws from each base rail. Wood protec­tor will drop to the ground. See instructions on the unit base rails.
Keep unit upright and do not drop. Spreader bars are not re­quired. Rollers may be used to move unit across a roof. Level by using unit frame as a reference. See Table 2 and Fig. 6 for additional information.
Lifting holes are provided in base rails as shown in Fig. 6. Re­fer to rigging instructions on unit.
CAUTION
UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage. All panels must be in place when rigging. Unit is not designed
for handling by fork truck when packaging is removed. If using top crate as spreader bar, once unit is set, carefully
lower wooden crate off building roof top to ground. Ensure that no people or obstructions are below prior to lowering the crate.
Before setting the unit onto the curb, recheck gasketing on curb.
10
NOTES:
1. SPREADER BARS REQUIRED — Top damage will occur if spreader bars are not used.
2. Dimensions in ( ) are in millimeters.
3. Hook rigging shackles through holes in base rail, as shown in detail “A.” Holes in base rails are centered around the unit center of gravity. Use wooden top to prevent rigging straps from damaging unit.
UNIT
MAX
WEIGHT
DIMENSIONS
ABC
lb kg in. mm in. mm in. mm
48HC**14 2215 1009 116.0 2945 62.5 1590 59.5 1510
DETAIL “A
PLACE ALL SEAL STRIP IN PLACE BEFORE PLACING UNIT ON ROOF CURB.
DUCT END
SEE DETAIL “A
“B
“A
“C
36"-54"
(914-1371)
Original Position
New Position (moved 12.5-in.)
POSITIONING ON CURB For full perimeter curbs CRRFCURB074A00 and 075A00,the
clearance between the roof curb and the front and rear base rails should be curb and the end base rails should be
1
/4-in. (6.4 mm). The clearance between the
1
/2-in. (13 mm). For retro­fit applications with curbs CRRFCURB003A01 and 4A01, the unit should be position as shown in Fig. 7. Maintain the
1
15
/2-in. (394 mm) and 85/8-in. (220 mm) clearances and allow
5
the 22
/16-in. (567 mm) dimension to float if necessary.
Fig. 7 — Retrofit Installation Dimensions
If the alternative condensate drain location through the bottom of the unit is used in conjunction with a retrofit curb, the hole in the curb must be moved 12
1
/2-in. (320 mm) towards the end
of the unit. (See Fig. 8.) Although unit is weatherproof, guard against water from higher
level runoff and overhangs. Remove all shipping materials and top skid. Remove extra cen-
ter post from the condenser end of the unit so that the condens­er end of the unit matches Fig. 29 and 30. Recycle or dispose of all shipping materials.
Fig. 6 — Rigging Details
Fig. 8 — Alternative Condensate Drain Hole Positions
IMPORTANT: If the unit has the factory-installed Thru-the­Base option, make sure to complete installation of the option before placing the unit on the roof curb. See the following sec­tions:
• Factory-Option Thru-Base Connections (Gas Connec­tion) on page 15
• Factory-Option Thru-Base Connections (Electrical Con­nections) on page 23
NOTE: If gas and/or electrical connections are not going to occur at this time, tape or otherwise cover the fittings so that moisture does not get into the building or conduit in the interim.
Step 7 — Convert to Horizontal and Connect Ductwork (When Required)
Unit is shipped in the vertical duct configuration. Unit without factory-installed economizer or return-air smoke detector op­tion may be field-converted to horizontal ducted configuration. To convert to horizontal configuration, remove screws from
11
side duct opening covers (see Fig. 9) and remove covers. Use
REMOVABLE HORIZONTAL SUPPLY DUCT OPENING COVER
REMOVABLE HORIZONTAL RETURN DUCT OPENING COVER
SCREWS
DUCT COVERS SHEET METAL FACE UP
BASEPAN
FILTER ACCESS PANEL
INDOOR COIL ACCESS PANEL
the screws to install the covers on vertical duct openings with the insulation-side down. The panels must be inserted into the notches on the basepan to properly seal. The notches are cov­ered by the tape used to secure the insulation to the basepan and are not easily seen. See Fig. 10 for position of the notches in the basepan. Seals around duct openings must be tight. Se­cure with screws as shown in Fig. 11. Cover seams with foil duct tape.
Field-supplied flanges should be attached to horizontal duct openings and all ductwork should be secured to the flanges. In­sulate and weatherproof all external ductwork, joints, and roof or building openings with counter flashing and mastic in accor­dance with applicable codes.
Do not cover or obscure visibility to the unit’s informative data plate when insulating horizontal ductwork.
Fig. 9 — Horizontal Conversion Panels
NOTCHES
NOTCHES
Fig. 11 — Horizontal Duct Panels In Place
Step 8 — Install Outside Air Hood
ECONOMIZER HOOD REMOVAL AND SETUP FAC­TORY OPTION
1. The hood is shipped in knock-down form and located in the return air compartment. It is attached to the econo­mizer using two plastic tie-wraps.
2. To gain access to the hood, remove the filter access panel. (See Fig. 12.)
3. Locate and cut the (2) plastic tie-wraps, being careful to not damage any wiring. (See Fig. 13.)
4. Carefully lift the hood assembly through the filter access opening and assemble per the steps outlined in Econo­mizer Hood and Two-Position Hood on page 13.
BASEPAN
Fig. 10 — Location of Notches
Fig. 12 — Typical Access Panel Locations
12
Economizer
Cut Plastic Ties (2) Places
Remove Hood Parts
HOOD PARTS
PLASTIC TIE WRAP QTY (2)
SCREWS FORMETAL TRAY QTY (2)
TOP PAN EL
INDOOR COIL ACCESS PAN EL
INDOOR COIL ACCESS PAN EL
CAULK HERE
TOP PAN EL
Fig. 13 — Economizer Hood Package Location
TWO POSITION DAMPER HOOD REMOVAL AND SETUP — FACTORY OPTION
1. The hood is shipped in knock-down form and assembled to a metal support tray using plastic stretch wrap. Located in the return air compartment, the assembly’s metal tray is attached to the basepan and also attached to the damper using two plastic tie-wraps.
2. To gain access to the hood, remove the filter access panel. (See Fig. 12.)
3. Locate the (2) screws holding the metal tray to the basepan and remove. In order to remove the screws, it may be nec­essary to remove the panel underneath the two-position damper. Remove the two screws. Locate and cut the (2) plastic tie-wraps securing the assembly to the damper. (See Fig. 14.) Be careful to not damage any wiring or cut tie-wraps securing any wiring.
4. Carefully lift the hood assembly (with metal tray) through the filter access opening and assemble per the steps out­lined in Economizer Hood and Two-Position Hood.
5. If removed, reattach the panel under the damper.
ECONOMIZER HOOD AND TWO-POSITION HOOD NOTE: If the power exhaust accessory is to be installed on the
unit, the hood shipped with the unit will not be used and must be discarded. Save the aluminum filter for use in the power exhaust hood assembly.
1. The indoor coil access panel will be used as the top of the hood. If the panel is still attached to the unit, remove the screws along the sides and bottom of the panel. See Fig. 15.
2. Swing out indoor coil access panel and insert the hood sides under the panel (hood top). Be careful not to lift the panel too far as it might fall out. Use the screws provided to attach the hood sides to the hood top. Use screws pro­vided to attach the hood sides to the unit. See Fig. 16.
3. Remove the shipping tape holding the economizer baro­metric relief damper in place.
4. Insert the hood divider between the hood sides. See Fig. 17. Secure hood divider with 3 screws on each hood side. The hood divider is also used as the bottom filter rack for the aluminum filter.
5. Attach the post that separates the filters with the screws provided.
6. Open the filter clips which are located underneath the hood top. Insert the aluminum filters into the bottom filter rack (hood divider). Push the filter into position past the open filter clips. Close the filter clips to lock the filters into place. See Fig. 17.
7. Install the two rain deflectors on the edge of the hood top as shown in Fig. 16.
8. Caulk the ends of the joint between the unit top panel and the hood top as shown in Fig. 15.
9. Replace the filter access panel.
Fig. 14 — Two-Position Damper Hood Package
Location
Fig. 15 — Indoor Coil Access Panel Relocation
13
DIVIDER
BAROMETRIC RELIEF
CLEANABLE ALUMINUM FILTER
FILTER
HOOD
FILTER CLIP
OUTSIDE AIR
FLUE HOOD
CONTROL BOX ACCESS PANEL
SCREW
LEFT HOOD SIDE
HOOD DIVIDER
TOP PAN EL
INDOOR COIL ACCESS PANEL
Fig. 16 — Economizer Hood Construction
Fig. 17 — Economizer Filter Installation
Step 9 — Install Flue Hood
The flue hood is shipped screwed to the basepan beside the burner compartment access panel. Remove the panel below the control box access panel to access the flue hood shipping loca­tion. Using screws provided, install flue hood and screen in lo­cation shown in Fig. 18.
Fig. 18 — Flue Hood Details
Step 10 — Install Gas Piping
Installation of the gas piping must be accordance with local building codes and with applicable national codes. In U.S.A., re­fer to NFPA 54/ANSI Z223.1 National Fuel Gas Code (NFGC). In Canada, installation must be in accordance with the CAN/ CSA B149.1 and CAN/CSA B149.2 installation codes for gas burning appliances.
This unit is factory equipped for use with natural gas (NG) fuel at elevations up to 2000 ft (610 m) above sea level. Unit may be field converted for operation at elevations above 2000 ft (610 m) and/or for use with liquefied petroleum fuel. See ac­cessory kit installation instructions regarding these accessories.
NOTE: In U.S.A. the input rating for altitudes above 2000 ft (610 m) must be derated by 4% for each 1000 ft (305 m) above sea level. In Canada the input rating must be derated by 10% for altitudes of 2000 ft (610 m) to 4500 ft. (1372 m) above sea level.
For natural gas applications, gas pressure at unit gas connec­tion must not be less than 5 in. wg (1250 Pa) or greater than 13 in. wg (3240 Pa) while the unit is operating (see Tables 3 and 4). For liquified petroleum (LP) applications, the gas pres­sure must not be less than 11 in. wg (2740 Pa) or greater than 13 in. wg (3240 Pa) at the unit connection (see Tables 5 and 6).
The gas supply pipe enters the unit at the burner access panel on the front side of the unit, through the long slot at the bottom of the access panel. The gas connection to the unit is made to the
Manifold pressure is factory-adjusted for NG fuel use. Adjust as required to obtain best flame characteristics.
Table 3 — Natural Gas Supply Line Pressure Ranges
3
/4-in. FPT gas inlet port on the unit gas valve.
UNIT MIN MAX
48HC**14 5.0 in. wg (1250 Pa) 13.0 in. wg (3240 Pa)
Table 4 — Liquid Propane Supply Line Pressure
Ranges
UNIT MIN MAX
48HC**14 11.0 in. wg (2740 Pa) 13.0 in. wg (3240 Pa)
Table 5 — Natural Gas Manifold Pressure Ranges
UNIT MODEL HIGH FIRE LOW FIRE
48HC**14 3.5 in. wg (872 Pa) 2.0 in. wg (498 Pa)
14
Manifold pressure for liquid propane (LP) fuel use must be ad-
STEEL PIPE NOMINAL
DIAMETER (in.)
SPACING OF SUPPORTS X
DIMENSION (ft)
1
/
2
6
3
/4 or 1 8
1
1
/4 or larger 10
LEGEND NFGC — National Fuel Gas Code * Field supplied. NOTE: Follow all local codes.
X
BASE UNIT
BASE RAIL
ROOF CURB
9” MINIMUM CLEARANCE FOR PANEL REMOVAL
MANUAL GAS SHUTOFF VALVE
*
GAS REGULATOR
*
48” MINIMUM
DRIP LEG PER NFGC
*
FIELD-FABRICATED SUPPORT
*
FROM GAS METER
11/2” ELECTRICAL BULKHEAD CONNECTOR
1
/2” ELECTRICAL BULKHEAD CONNECTOR
3
/4” NPT GAS ADAPTER FITTING
justed to specified range. Follow instructions in the accessory kit to make initial readjustment.
Table 6 — Liquid Propane Manifold Pressure Ranges
UNIT HIGH FIRE LOW FIRE
48HC**14 10.0 in. wg (2490 Pa) 5.7 in. wg (1420 Pa)
CAUTION
EQUIPMENT DAMAGE Failure to follow this caution may result in equipment damage. When connecting the gas line to the unit gas valve, the in-
staller MUST use a backup wrench to prevent damage to the valve.
Install a gas supply line that runs to the unit heating section. Refer to the NFPA 54/NFGC or equivalent code for gas pipe sizing data. Size the gas supply line to allow for a maximum pressure drop of 0.5 in. wg (124 Pa) between gas regulator source and unit gas valve connection when unit is operating at high-fire flow rate.
The gas supply line can approach the unit in three ways: hori­zontally from outside the unit (across the roof), thru-curb/under unit basepan (accessory kit required) or through unit basepan (factory-option or accessory kit required). Consult accessory kit installation instructions for details on these installation methods. Observe clearance to gas line components per Fig. 19.
Fig. 19 — Gas Piping Guide
FACTORY OPTION THRU-BASE CONNECTIONS (GAS CONNECTION)
3
This service connection kit consists of a er fitting (stainless steel), a 1/2-in. electrical bulkhead connec­tor and a 1
1
/2-in. electrical bulkhead connector, connected to an
/4-in. NPT gas adapt-
“L” bracket covering the embossed (raised) section of the unit basepan in the condenser section. See Fig. 20.
Fig. 20 — Thru-the-Base Option, Shipping Position
1. Remove the “L” bracket assembly from the unit (see Fig. 20).
2. Cut and discard the wire tie on the gas fitting. Hand tighten the fitting if it has loosened in transit.
3. Remove connector plate assembly from the “L” bracket and discard the “L” bracket, but retain the washer head screws and the gasket (located between the “L” bracket and the connector plate assembly.)
NOTE: Take care not to damage the gasket, as it is reused in the following step.
4. Place the gasket over the embossed area in the basepan, aligning the holes in the gasket to the holes in the basepan. See Fig. 21.
5. Install the connector plate assembly to the basepan using 8 of the washer head screws.
NOTE: If gas and/or electrical connections are not going to occur at this time, tape or otherwise cover the fittings so that moisture does not get into the building or conduit in the interim.
The thru-base gas connector has male and female threads. The male threads protrude above the basepan of the unit; the female threads protrude below the basepan.
Check tightness of connector lock nuts before connecting gas piping.
Install a Attach a
3
/4-in. NPT street elbow on the thru-base gas fitting.
3
/4-in. pipe nipple with minimum length of 16-in. (406 mm) (field-supplied) to the street elbow and extend it through the access panel at the gas support bracket. (See Fig. 22.)
15
Fig. 21 — Completing Installation of Thru-the-Base
GASKET
CONNECTOR PLATE ASSEMBLY
3
/4-in NPT STREET ELBOW
THRU-BASE GAS FITTING
GAS SUPPORT BRACKET
9” (229mm) min
Union
Shut Off
Valve
Drip Leg
Thru-Curb Adapter
Unit Base Rail
Drip Leg
Shut Off
Valve
Union
Thru-Curb Adapter
Burner Access Panel
9 (229mm) min
Unit Base Rail
Other hardware required to complete the installation of the gas supply line will include a manual shutoff valve, a sediment trap (drip leg) and a ground-joint union. A pressure regulator valve may also be required (to convert gas pressure from pounds to inches of pressure). The manual shutoff valve must be located within 6 ft (1.83 m) of the unit. The union, located in the final leg entering the unit, must be located at least 9-in. (230 mm) away from the access panel to permit the panel to be removed for service. If a regulator valve is installed, it must be located a minimum of 4 ft (1220 mm) away from the unit’s flue outlet. Some municipal codes require that the manual shutoff valve be located upstream of the sediment trap. See Fig. 23 and 24 for typical piping arrangements for gas piping that has been routed through the sidewall of the curb. See Fig. 25 for typical piping arrangement when thru-base is used. Ensure that all piping does not block access to the unit’s main control box or limit the required working space in front of the control box.
Option
Fig. 22 — Gas Line Piping
Fig. 23 — Gas Piping
Fig. 24 — Gas Piping
Fig. 25 — Gas Piping Thru-Base Connections
16
Loading...
+ 36 hidden pages