Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and electrical components.
Only trained and qualified service personnel should install,
repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions
of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe
precautions in the literature, tags and labels attached to the
unit, and other safety precautions that may apply.
Follow all safety codes, including ANSI (American National
Standards Institute) Z223.1. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguisher available for all brazing operations.
It is important to recognize safety information. This is the
safety-alert symbol . When you see this symbol on the unit
and in instructions or manuals, be alert to the potential for
personal injury.
Understand the signal words DANGER, WARNING,
CAUTION, and NOTE. These words are used with the safetyalert symbol. DANGER identifies the most serious hazards
which will result in severe personal injury or death.
WARNING signifies hazards which could result in personal
injury or death. CAUTION is used to identify unsafe practices,
which may result in minor personal injury or product and
property damage. NOTE is used to highlight suggestions
which will result in enhanced installation, reliability, or
operation.
Catalog No. 04-53480187-01Printed in U.S.A.Form 48LC-4-6-04SIPg 1 6-19Replaces: 48LC-4-6-03SI
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Page 2
WARNING
GAS VALVE
INLET PRESSURE
TAP SET SCREW
MANIFOLD
GAS VALVE
MANIFOLD PRESSURE
TAP SET SCREW
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in death, serious
personal injury and/or property damage.
Disconnect gas piping from unit when pressure testing at
pressure greater than 0.5 psig (3450 Pa). Pressures greater
than 0.5 psig will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pressure greater than 0.5 psig, it must be replaced before use. When pressure testing field-supplied gas piping at pressures of
0.5 psig or less, a unit connected to such piping must be
isolated by closing the manual gas valve(s).
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal inju-
ry, death, and/or property damage.
Inlet pressure tap set screw must be tightened and
pipe plug must be installed to prevent gas leaks.
1
/8-in. NPT
AVERTISSEMENT
RISQUE D’INTOXICATION AU MONOXYDE DE
CARBONE
Si ces directives ne sont pas suivies, cela peut entraîner des
blessures graves ou une intoxication au monoxyde de carbone pouvant causer la mort, si des produits de combustion
s’infiltrent dans le bâtiment.
Vérifier que toutes les ouvertures pratiquées dans le mur
extérieur autour du ou des tuyaux d’évent (et de la prise
d’air) sont scellées de manière à empêcher l’infiltration de
produits de combustion dans le bâtiment.
Veiller à ce que la ou les sorties de l’évent de l’appareil de
chauffage (et la prise d’air) ne soient, en aucune façon, obstruées, quelle que soit la saison.
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury
or death.
Before performing service or maintenance operations on
unit, turn off main power switch to unit and install lock(s)
and lockout tag(s). Ensure electrical service to rooftop unit
agrees with voltage and amperage listed on the unit rating
plate. Unit may have more than one power switch.
FIRE HAZARD
Failure to follow this warning could result in personal inju-
ry, death, and/or property damage.
Manifold pressure tap set screw must be tightened and
NPT pipe plug must be installed to prevent gas leaks.
CARBON-MONOXIDE POISONING HAZARD
Failure to follow instructions could result in severe personal
injury or death due to carbon-monoxide poisoning, if
combustion products infiltrate into the building.
Check that all openings in the outside wall around the vent
(and air intake) pipe(s) are sealed to prevent infiltration of
combustion products into the building.
Check that furnace vent (and air intake) terminal(s) are not
obstructed in any way during all seasons.
WARNING
1
/8-in.
WARNING
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal injury,
death and/or equipment damage.
®
Puron
(R-410A) refrigerant systems operate at higher pressures than standard R-22 systems. Do not use R-22 service
equipment or components on Puron refrigerant equipment.
WARNING
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could cause personal injury
or death.
Relieve pressure and recover all refrigerant before system
repair or final unit disposal.
Wear safety glasses and gloves when handling refrigerants.
Keep torches and other ignition sources away from refrigerants and oils.
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing, safety glasses and
gloves when handling parts and servicing air conditioning
equipment.
GENERAL
See Fig. 1 for unit options. See Fig. 2 and 3 for unit dimensions.
See Fig. 4 for corner weights and clearances. See Fig. 5 for base
rail details. See Fig. 6 for thru-the-base charts.
2
Page 3
Rated Indoor Airflow (cfm)
48LCD006A0A5-0A0A 0
1234567891011 12 13 14 15 16
17 18
Model Series - WeatherExpert
®
LC – Ultra High Efficiency
Unit Heat Type
48 – Gas Heat Packaged Rooftop
Cooling Tons
04 – 3 ton
05 – 4 ton
06 – 5 ton
Heat Options
D = Low Gas Heat
E = Medium Gas Heat
F = High Gas Heat
L = Low NOx – Low Gas Heat
M = Low NOx – Medium Gas Heat
N = Low NOx – High Gas Heat
S = Low Heat w/ Stainless Steel Exchanger
R = Medium Heat w/ Stainless Steel Exchanger
T = High Heat w/ Stainless Steel Exchanger
(Low NOx models include – Stainless Steel HX)
Sens or Options
A = None
B = RA Smoke Detector
C = SA Smoke Detector
D = RA + SA Smoke Detector
E = CO
2
F = RA Smoke Detector and CO
2
G = SA Smoke Detector and CO
2
H = RA + SA Smoke Detector and CO
2
Indoor Fan Options
0 = Standard Electrical (Direct) Drive x13 ECM Motor
2 = Medium Static Belt Drive with VFD controller
3 = High Static Belt Drive with VFD controller
Refrig. Systems Options
0 = Two stage cooling capacity
A = Two stage cooling capacity
with Humidi-MiZer
A = Al/Cu - Al/Cu
B = Precoat Al/Cu – Al/Cu
C = E-coat Al/Cu – Al/Cu
D = E-coat Al/Cu – E-coat Al/Cu
E = Cu/Cu – Al/Cu
F = Cu/Cu – Cu/Cu
M = Al/Cu – Al/Cu – Louvered Hail Guard
N = Precoat Al/Cu – Al/Cu – Louvered Hail Guard
P = E-coat Al/Cu – Al/Cu – Louvered Hail Guard
Q = E-coat Al/Cu – E-coat Al/Cu – Louvered Hail Guard
R = Cu/Cu – Al/Cu – Louvered Hail Guard
S = Cu/Cu – Cu/Cu – Louvered Hail Guard
Voltage
1 = 575/3/60
5 = 208-230/3/60
6 = 460/3/60
Design Revision
– = Factory Design Revision
Base Unit Controls
0 = Base Electromechanical Controls
1 = RTU Open Multi-Protocol Controller
4 = SystemVu™ Controller
Intake / Exhaust Options
A = None
B =
Temperature Economizer with Barometric Relief
E = Enthalpy Economizer with Barometric Relief
N = Ultra Low Leak Temperature Economizer
with Barometric Relief
R = Ultra Low Leak Enthalpy Economizer with
Barometric Relief
A = None
B = HACR Breaker
C = Non-Fused Disconnect
D = Thru-The-Base Connections
E = HACR Breaker with
Thru-The-Base Connections
F = Non-Fused Disconnect and
Thru-The-Base Connections
Example:
Position:
Table 1 lists the rated indoor airflow used for the AHRI efficiency rating for the units covered in this document.
Table 1 — Rated Indoor Airflow (cfm)
MODEL NUMBER
48LC**041050
48LC**051400
48LC**061750
FULL LOAD AIRFLOW
(CFM)
Fig. 1 — 48LC 04-06 Model Number Nomenclature
3
Page 4
Fig. 2 — Dimensional Drawing of Units Built on and After 4/15/19
4
Page 5
Fig. 3 — Dimensional Drawing for Units Built On and Prior to 4/14/19
5
Page 6
Fig. 4 — Corner Weights and Clearances
6
Page 7
Fig. 5 — Base Rail Details
7
Page 8
Fig. 6 — Thru-the-Base Charts
8
Page 9
INSTALLATION
Jobsite Survey
Complete the following checks before installation.
1.Consult local building codes and the NEC (National Electrical Code) ANSI/NFPA 70 for special installation
requirements.
2.Determine unit location (from project plans) or select unit
location.
3.Check for possible overhead obstructions which may
interfere with unit lifting or rigging.
Step 1 — Plan for Unit Location
Select a location for the unit and its support system (curb or
other) that provides for the minimum clearances required for
safety. This includes the clearance to combustible surfaces,
unit performance and service access below and around unit as
specified in Fig. 4.
NOTE: Consider also the effect of adjacent units.
Be sure that unit is installed such that snow will not block the
combustion intake or flue outlet.
Unit may be installed directly on wood flooring or on Class A,
B, or C roof-covering material when roof curb is used.
Do not install unit in an indoor location. Do not locate air inlets
near exhaust vents or other sources of contaminated air. For
proper unit operation, adequate combustion and ventilation air
must be provided in accordance with Section 5.3 (Air for Combustion and Ventilation) of the National Fuel Gas Code, ANSI
Z223.1 (American National Standards Institute) and NFPA
(National Fire Protection Association) 54 TIA-54-84-1. In
Canada, installation must be in accordance with the CAN1B149 installation codes for gas burning appliances.
Although unit is weatherproof, avoid locations that permit water from higher level runoff and overhangs to fall onto the unit.
Locate mechanical draft system flue assembly at least 4 ft
(1.2 m) from any opening through which combustion products
could enter the building, and at least 4 ft (1.2 m) from any adjacent building (or per local code). Locate the flue assembly at
least 10 ft (3.05 m) from an adjacent unit’s fresh air intake
hood if within 3 ft (0.91 m) of same elevation (or per local
code). When unit is located adjacent to public walkways, flue
assembly must be at least 7 ft (2.1 m) above grade.
Select a unit mounting system that provides adequate height to
allow installation of condensate trap per requirements. Refer to
“Step 12 — Install External Condensate Trap and Line” on
page 17 for required trap dimensions.
ROOF MOUNT
Check building codes for weight distribution requirements.
The support method used for this unit will dictate different sequences for the steps of unit installation. For example, on curbmounted units, some accessories must be installed on the unit
before the unit is placed on the curb. Review the following for
recommended sequences for installation steps.
CURB-MOUNTED INSTALLATION
1.Install curb
2.Install field-fabricated ductwork inside curb
3.Install accessory thru-base service connection package
(affects curb and unit) (refer to accessory installation
instructions for details)
4.Prepare bottom condensate drain connection to suit
planned condensate line routing (refer to “Step 12 —
Install External Condensate Trap and Line” on page 17 for
details)
5.Rig and place unit
6.Install outdoor-air hood
7.Install flue hood
8.Install gas piping
9.Install condensate line trap and piping
10. Make electrical connections
11. Install other accessories
PAD-MOUNTED INSTALLATION
1.Prepare pad and unit supports
2.Check and tighten the bottom condensate drain connection
plug
3.Rig and place unit
4.Convert unit to side duct connection arrangement
5.Install field-fabricated ductwork at unit duct openings
6.Install outdoor-air hood
7.Install flue hood
8.Install gas piping
9.Install condensate line trap and piping
10. Make electrical connections
11. Install other accessories
FRAME-MOUNTED INSTALLATION
Frame-mounted applications generally follow the sequence for
a curb installation. Adapt as required to suit specific installation plan.
Step 3 — Inspect Unit
Inspect unit for transportation damage. File any claim with
transportation agency.
Confirm before installation of unit that voltage, amperage and
circuit protection requirements listed on unit data plate agree
with power supply provided.
Step 4 — Provide Unit Support
ROOF CURB MOUNT
Accessory roof curb details and dimensions are shown in Fig. 8
(see page 11). Assemble and install accessory roof curb in accordance with instructions shipped with the curb.
NOTE: The gasketing of the unit to the roof curb is critical for a
watertight seal. Install gasket supplied with the roof curb as shown
in Fig. 8. Improperly applied gasket can also result in air leaks and
poor unit performance.
Curb should be level. This is necessary for unit drain to function properly. Unit leveling tolerances are show in Fig. 7. Refer
to Accessory Roof Curb Installation Instructions for additional
information as required.
9
Page 10
Fig. 7 — Unit Leveling Tolerances
A-B
0.5 (13)
B-C
1.0 (25)
A-C
1.0 (25)
MAXIMUM ALLOWABLE
DIFFERENCE – IN. (MM)
Install insulation, cant strips, roofing felt, and counter flashing
as shown. Ductwork must be attached to curb and not to the
unit. The accessory thru-the-base power and gas connection
package must be installed before the unit is set on the roof
curb. If field-installed thru-the-roof curb gas connections are
desired, use factory-supplied
1
/2-in. pipe coupling and gas plate
assembly to mount the thru-the-roof curb connection to the
roof curb. Gas connections and power connections to the unit
must be field-installed after the unit is installed on the roof
curb.
If electric and control wiring is to be routed through the basepan,
attach the accessory thru-the-base service connections to the basepan in accordance with the accessory installation instructions.
SLAB MOUNT (HORIZONTAL UNITS ONLY)
Provide a level concrete slab that extends a minimum of 6-in.
(150 mm) beyond unit cabinet. Install a gravel apron in front of
condenser coil air inlet to prevent grass and foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if
required.
ALTERNATE UNIT SUPPORT (IN LIEU OF CURB OR
SLAB MOUNT)
A non-combustible sleeper rail can be used in the unit curb
support area. If sleeper rails cannot be used, support the long
sides of the unit with a minimum of 3 equally spaced 4-in. x
4-in. (102 mm x 102 mm) pads on each side.
Step 5 — Field Fabricate Ductwork
Cabinet return-air static pressure (a negative condition) shall
not exceed 0.35 in. wg (87 Pa) with economizer or 0.45 in. wg
(112 Pa) without economizer.
For vertical ducted applications, secure all ducts to roof curb
and building structure. Do not connect ductwork to unit.
Fabricate supply ductwork so that the cross-sectional dimensions are equal to or greater than the unit-supply duct opening
dimensions for the first 18-in. (458 mm) of duct length from
the unit basepan.
Insulate and weatherproof all external ductwork, joints, and
roof openings with counter flashing and mastic in accordance
with applicable codes.
Ducts passing through unconditioned spaces must be insulated
and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should
be ducted through the roof deck to comply with applicable fire
codes.
A minimum clearance is not required around ductwork.
CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in damage to roof-
ing materials.
Membrane roofs can be cut by sharp sheet metal edges. Be
careful when placing any sheet metal parts on such roof.
Step 6 — Rig and Place Unit
Keep unit upright and do not drop. Spreader bars are required.
Rollers may be used to move unit across a roof. Level by using
unit frame as a reference. See Table 2 and Fig. 9 for additional
information.
Lifting holes are provided in base rails as shown in Fig. 9. Refer to rigging instructions on unit.
Rigging materials under unit (cardboard or wood) must be removed PRIOR to placing the unit on the roof curb.
When using the standard side drain connection, ensure the red
plug in the alternate bottom connection is tight. Do this before
setting the unit in place. The red drain pan plug can be tightened with a
1
/2-in. square socket drive extension. For further
details, see “Step 12 — Install External Condensate Trap and
Line” on page 17.
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
All panels must be in place when rigging. Unit is not designed
for handling by fork truck when packaging is removed.
If using top crate as spreader bar, once unit is set, carefully
lower wooden crate off building roof top to ground. Ensure
that no people or obstructions are below prior to lowering
the crate.
Before setting the unit onto the curb, recheck gasketing on
curb.
POSITIONING ON CURB
Position unit on roof curb so that the following clearances are
maintained:
and the base rail inside the front and rear, 0.0-in. clearance between the roof curb and the base rail inside on the duct end of
the unit. This will result in the distance between the roof curb
and the base rail inside on the condenser end of the unit being
approximately
Although unit is weatherproof, guard against water from higher
level runoff and overhangs.
Flue vent discharge must have a minimum horizontal clearance of 4 ft (1220 mm) from electric and gas meters, gas regulators, and gas relief equipment. Minimum distance between
unit and other electrically live parts is 48-in. (1220 mm).
Flue gas can deteriorate building materials. Orient unit such
that flue gas will not affect building materials. Locate mechanical draft system flue assembly at least 48-in. (1220 mm) from
an adjacent building or combustible material.
NOTE: Installation of accessory flue discharge deflector kit will
reduce the minimum clearance to combustible material to 18-in.
(460 mm).
After unit is in position, remove rigging skids and shipping
materials.
1
/4-in. (6.4 mm) clearance between the roof curb
1
/4-in. (6.4 mm).
10
Page 11
1-3/4"
TYP
[44.5]
C
ACCESSORY CONVENIENCE
OUTLET WIRING CONNECTOR
FITTING
1/2" [12.7] NPT1/2" [12.7] NPT
CONTROL WIRING
FITTING
POWER WIRING
3/4" [19] NPT1 1/4" [31.7] NPT
THRU THE CURB
CRBTMPWR004A01THRU THE BOTTOM
CRBTMPWR002A01
CONNECTOR PKG. ACC. GAS CONNECTION TYPEGAS FITTING
1 3/4"
[44.5]
1.00"
[25.4]
12-1/2" [317.5] WIDE
INSULATED DECK PANELS
INSULATED DECK PANEL
9-15/16" [252.4] WIDE
"A"
1 3/4"
[44.4]
SEE NOTE #2
2-3/8"
[61]
20-3/4"
[513]
INSIDE
GAS SERVICE PLATE
THRU THE CURB
DRILL HOLE
2" [50.8] @
ASSEMBLY (IF
REQUIRED)
(SEE NOTE #8)
SECTION THRU SIDE
RETURN AIR
SUPPLY AIR
UNIT
[1987.5]
6' 6-1/4"
4' 2"
[1270.0]
"A"
NAIL (FIELD SUPPLIED)
TYPICAL (4) SIDES
7/16"
CERTIFIED DRAWING
SEE VIEW "B"
ROOFING FELT
(FIELD SUPPLIED)
COUNTER FLASHING
(FIELD SUPPLIED)
[11]
CURB ASY, ROOF
THIS DOCUMENT AND THE INFORMATION CONTAINED THEREIN
IS PROPRIETARY TO CARRIER CORPORATION AND SHALL NOT
BE USED OR DISCLOSED TO OTHERS, IN WHOLE OR IN PART,
WITHOUT THE WRITTEN AUTHORIZATION OF CARRIER CORPORATION.
1029120
TOLERANCES ON:
AUTHORIZATION NUMBERTITLE
DIMENSIONS ARE IN INCHES
----
UNLESS OTHERWISE SPECIFIED
1 DEC 2 DEC 3 DEC ANG
PRODUCTION
---
MATERIAL
DRAWING RELEASE LEVEL:
THIRD ANGLE
PROJECTION
ROOFING MATERIAL
(FIELD SUPPLIED)
CANT STRIP
(FIELD SUPPLIED)
RIGID INSULATION
SHEET 5 OF 5
50HJ405012
SIZE DRAWING NUMBERREV
D
-
-
-
DRAFTERCHECKER
ENGINEERING MANUFACTURING
-
MMC 12/16/09 --
-
T-005, Y-002
WEIGHT:
-PURCH-N/A-
ENGINEERING REQUIREMENTS
SURFACE FINISH MFG/PURCHMODEL (INTERNAL USE ONLY)NEXT DRAWINGSCALEDISTRIBUTION
5. ATTACH DUCTWORK TO CURB. (FLANGES OF DUCT REST ON CURB).
6. SERVICE CLEARANCE 4 FEET ON EACH SIDE.
7. DIRECTION OF AIR FLOW.
8. CONNECTOR PACKAGE CRBTMPWR002A01 IS FOR THRU-THE-CURB GAS TYPE
PACKAGE CRBTMPWR004A01 IS FOR THRU-THE-BOTTOM TYPE GAS CONNECTIONS.
53 1/2"
[1358.9]
11.42"
[290.0]
A
14"
24"
[356]
[610]
26"
[660.4]
6 3/64"
ROOF CURB
ACCESSORY #
CRRFCURB003A01
CRRFCURB004A01
[153.5]
1 3/4"
[44.4]
4 3/16"
[106.0]
81 3/4"
[827.1]
32 9/16"
[2076.3]
3"
40 3/16"
[76.2]
[1020.8]
VIEW "B"
CORNER DETAIL
[585.8]
23 1/16"
OPENING
RETURN AIR
OPENING
SUPPLY AIR
1 3/4"
[44.5]
[401.6]
15 13/16"
DUCT
GASKET
(FIELD SUPPLIED)
(SUPPLIED WITH CURB)
15 15/32
[392.9]
[800.9]
31 17/32"
1 3/4"
[44.5]
6' 61/4" WAS 6' 7 1/6", 4'2' WAS 4' 2 13/16";
18 GA WAS 16 GA.; 15 13/16" WAS 15 15/16"; NAIL
FIELD SUPPLIED WAS WITH CURB
C
SUPPLY AIRRETURN AIR
1/4"
[7.0]
[115.5]
4 9/16"
Fig. 8 — Roof Curb Details
11
Page 12
CAUTION - NOTICE TO RIGGERS:
AVERTISSEMENT - REMARQUE À
L’ATTENTION DES MONTEURS
ALL PANELS MUST BE IN PLACE WHEN RIGGING.
TOUS LES CAPOTS DOIVENT ÊTRE EN PLACE AVANT LE LEVAGE
• Hook rigging shackles through holes in base rail, as shown in Detail “A”.
• Use wooden top skid, when rigging, to prevent rigging straps from damaging unit.
• Max weight includes base unit plus shipping pallet plus all available FIOP's which could
be on that size unit.
• "B" dimension is based on base unit (PAC no heat or YAC w/low heat) plus economizer
option only. This dimension may vary slightly with units congured with other FIOP
options.
• Spreader bars required to lift and transport the unit.
• Accrocher les manilles des élingues de levages dans les trous situés dans le rail
de base comme indiqué au Détail « A ».
• Utiliser des cales en bois lors du levage pour éviter que les élingues n’endommagent
le haut de l’appareil.
• Le poids maximum inclut la conguration de base, le poids de la palette d'expédition,
ainsi que toutes les options pouvant être installées en usine (FIOP) pour la
plateforme sélectionnée.
• La dimension de "B" provient de la conguration de base (PAC sans chauage ou
YAC chauage au gaz natufrel) qui inclut l'option economizer seulement. Cette
dimension peut varier légèrement en fonction des diérentes options sélectionnées,
installées en usine (FIOP).
• Barres d'écartement requises pour soulever et transporter l'unité.
PLACE ALL SEAL STRIP IN PLACE
REQUIRED
SPREADER
BARS
“B”
914-1371
(36"- 54")
“C”
BEFORE PLACING UNIT ON ROOF CURB.
INSTALLER TOUTES LES BANDES
D’ISOLATION EN PLACE AVANT DE
PLACER L’APPAREIL SUR LE REBORD
DE TOIT.
Step 7 — Convert to Horizontal and Connect
Ductwork (when required)
Unit is shipped in the vertical duct configuration. Unit without
factory-installed economizer or return-air smoke detector option may be field-converted to horizontal ducted configuration.
To convert to horizontal configuration, remove screws from
side duct opening covers (see Fig. 10) and remove covers. Use
the screws to install the covers on vertical duct openings with
the insulation-side down. The panels must be inserted into the
notches on the basepan to properly seal. The notches are covered by the tape used to secure the insulation to the basepan
and are not easily seen. See Fig. 11 for position of the notches
318
377
393
345
407
423
AB
INMMINMMINMM
74.5
74.5
74.5
74.5
74.5
74.5
1890
1890
1890
1890
1890
1890
36.5
36.5
36.0
38.0
38.0
37.5
925
925
915
965
965
955
C
33.5
41.5
41.5
33.5
41.5
41.5
48HC500030 A
850
1055
1055
850
1055
1055
in the basepan. Seals around duct openings must be tight. Secure with screws as shown in Fig. 12. Cover seams with foil
duct tape.
Field-supplied flanges should be attached to horizontal duct
openings and all ductwork should be secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof
or building openings with counter flashing and mastic in accordance with applicable codes.
Do not cover or obscure visibility to the unit’s informative data
plate when insulating horizontal ductwork.
12
Page 13
packaged together, attached to a metal support tray using
REMOVABLE HORIZONTAL
SUPPLY DUCT OPENING COVER
REMOVABLE HORIZONTAL
RETURN DUCT OPENING COVER
SCREWS
DUCT COVERS
SHEET METAL
FACE UP
BASEPAN
plastic stretch wrap, and shipped in the return-air compartment behind the indoor coil access panel. The hood assembly’s metal tray is attached to the basepan and also
attached to the damper using two plastic tie-wraps.
2.To gain access to the hood, remove the filter access panel.
(See Fig. 13.)
FILTER ACCESS PANEL
Fig. 10 — Horizontal Conversion Panels
NOTCHES
BASEPAN
NOTCHES
Fig. 11 — Location of Notches
COMPRESSOR
ACCESS PANEL
OUTDOOR-AIR OPENING AND
INDOOR COIL ACCESS PANEL
Fig. 13 — Typical Access Panel Locations
3.Locate the 2 screws holding the metal tray to the basepan
and remove. Locate and cut the 2 plastic tie-wraps
securing the assembly to the damper. (See Fig. 14.) Be
careful to not damage any wiring or cut tie-wraps securing
any wiring.
Hood Parts
Plastic Tie Wrap
Qty (2)
Screws for Metal Tray
Qty (2)
Fig. 12 — Horizontal Duct Panels In Place
Step 8 — Install Outside Air Hood
ECONOMIZER HOOD PACKAGE REMOVAL AND
SETUP - FACTORY OPTION
1.The hood is shipped in knock-down form and must be
field-assembled. The indoor coil access panel is used as
the hood top while the hood sides, divider and filter are
Fig. 14 — Economizer Hood Parts Location
4.Carefully lift the hood assembly (with metal tray) through
the filter access opening and assemble per the steps outlined in Economizer Hood, below.
ECONOMIZER HOOD
NOTE: If the power exhaust accessory is to be installed on the
unit, the hood shipped with the unit will not be used and must be
discarded. Save the aluminum filter for use in the power exhaust
hood assembly.
1.The indoor coil access panel will be used as the top of the
hood. Remove the screws along the sides and bottom of
the indoor coil access panel. See Fig. 15.
13
Page 14
TOP
PANEL
INDOOR
COIL
ACCESS
PANEL
INDOOR
COIL
ACCESS
PANEL
CAULK
HERE
TOP
PANEL
B
TOP
PANEL
INDOOR COIL
ACCESS PANEL
19 1/16”
SCREW
HOOD DIVIDER
LEFT
HOOD
SIDE
33 3/8”
(848mm)
(483mm)
DIVIDER
BAROMETRIC
RELIEF
CLEANABLE
ALUMINUM
FILTER
FILTER
HOOD
FILTER
CLIP
OUTSIDE
AIR
BLOWER
ACCESS
PANEL
Fig. 15 — Indoor Coil Access Panel Relocation
2.Swing out indoor coil access panel and insert the hood
sides under the panel (hood top). Use the screws provided
to attach the hood sides to the hood top. Use screws provided to attach the hood sides to the unit. See Fig. 16.
Fig. 16 — Economizer Hood Construction
3.Remove the shipping tape holding the economizer barometric relief damper in place (economizer only).
4.Insert the hood divider between the hood sides. See
Fig. 16 and Fig. 17. Secure hood divider with 2 screws on
each hood side. The hood divider is also used as the bottom filter rack for the aluminum filter.
5.Open the filter clips which are located underneath the
hood top. Insert the aluminum filter into the bottom filter
rack (hood divider). Push the filter into position past the
open filter clips. Close the filter clips to lock the filter into
place. See Fig. 17.
6.Caulk the ends of the joint between the unit top panel and
the hood top.
7.Replace the filter access panel.
Fig. 17 — Economizer Filter Installation
Step 9 — Units with Hinged Panels Only
Relocate latch shipped inside the hinged compressor door to
location shown in Fig. 18 after unit installation. If the unit does
not have hinged panels, skip Step 9 and continue at Step 10.
Fig. 18 — Compressor Door Latch Location
Step 10 — Install Flue Hood
Flue hood is shipped screwed to the basepan beside the burner
compartment access panel. Remove from shipping location and
using screws provided, install flue hood and screen in location
shown in Fig. 19.
Fig. 19 — Flue Hood Details
Step 11 — Install Gas Piping
Installation of the gas piping must be in accordance with local
building codes and with applicable national codes. In U.S.A.,
refer to NFPA 54/ANSI Z223.1 National Fuel Gas Code (NFGC). In Canada, installation must be in accordance with the
CAN/CSA B149.1 and CAN/CSA B149.2 installation codes
for gas burning appliances.
14
Page 15
This unit is factory-equipped for use with natural gas (NG) fuel
at elevations up to 2000 ft (610 m) above sea level. Unit may
be field converted for operation at elevations above 2000 ft
(610 m) and/or for use with liquefied petroleum fuel. See accessory kit installation instructions regarding these accessories.
NOTE: Furnace gas input rate on rating plate is for installation up
to 2000 ft (610 m) above sea level. In U.S.A. the input rating for
altitudes above 2000 ft (610 m) must be derated by 4% for each
1000 ft (305 m) above sea level. In Canada the input rating must
be derated by 10% for altitudes of 2000 ft (610 m) to 4500 ft
(1372 m) above sea level.
For natural gas applications, gas pressure at unit gas connection must not be less than 4 in. wg (996 Pa) or greater than
13 in. wg (3240 Pa) while the unit is operating. On 48LCF/N/
T*05-06 (high-heat) units, the gas pressure at unit gas connection must not be less than 5 in. wg (1245 Pa) or greater than
13 in. wg (3240 Pa) while the unit is operating. For liquified
petroleum applications, the gas pressure must not be less than
11 in. wg (2740 Pa) or greater than 13.0 in. wg (3240 Pa) at the
unit connection. See Tables 3 and 4.
Table 3 — Natural Gas Supply Line Pressure Ranges
UNIT MODEL
48LCD/E/L/M/S/R 04, 05, 06
48LCF/N/T
(High Heat units
only)
UNIT
SIZE
05, 06
MINMAX
4.0 in. wg (996
Pa)
5.0 in. wg
(1245 Pa)
13.0 in. wg (3240
Pa)
13.0 in. wg
(3240 Pa)
CAUTION
EQUIPMENT DAMAGE
Failure to follow this caution may result in equipment damage.
When connecting the gas line to the unit gas valve, the in-
staller MUST use a backup wrench to prevent damage to
the valve.
Install a gas supply line that runs to the unit heating section.
Refer to the NFPA 54/NFGC or equivalent code for gas pipe
sizing data. Do not use a pipe size smaller than
gas supply line to allow for a maximum pressure drop of
0.5 in. wg (124 Pa) between gas regulator source and unit gas
valve connection when unit is operating at high-fire flow rate.
The gas supply line can approach the unit in three ways: horizontally from outside the unit (across the roof), thru-curb/under
unit basepan (accessory kit required) or through unit basepan
(factory-option or accessory kit required). Consult accessory
kit installation instructions for details on these installation
methods. Observe clearance to gas line components per
Fig. 20.
X
9” MINIMUM CLEARANCE
FOR PANEL REMOVAL
MANUAL GAS
BASE UNIT
SHUTOFF VALVE
1
GAS
REGULATOR
*
/2-in. Size the
*
Table 4 — Liquid Propane Supply Line Pressure
Ranges
UNIT MODELUNIT SIZEMINMAX
48LCD/E/S/R04, 05, 06
48LCF/T
(High Heat units only)
05, 06
11.0 in. wg
(2740 Pa)
11.0 in. wg
(2740 Pa)
13.0 in. wg
(3240 Pa)
13.0 in. wg
(3240 Pa)
The gas supply pipe enters the unit at the burner access panel
on the front side of the unit, through the long slot at the bottom
of the access panel. The gas connection to the unit is made to
1
the
/2-in. FPT gas inlet port on the unit gas valve.
Manifold pressure is factory-adjusted for NG fuel use. Adjust
as required to obtain best flame characteristics. See Table 5.
Table 5 — Natural Gas Manifold Pressure Ranges
UNIT MODELUNIT SIZEHIGH FIRELOW FIRE
48LCD/E/L/M/S/R04, 05, 06
48LCF/N/T
(High Heat units only)
05, 06
3.5 in. wg
(872 Pa)
3.5 in. wg
(872 Pa)
1.7 in. wg
(423 Pa)
1.7 in. wg
(423 Pa)
Manifold pressure for liquid propane (LP) fuel use must be adjusted to specified range. Follow instructions in the accessory kit
to make initial readjustment. See Table 6.
This service connection kit consists of a
er fitting (brass), two
3
a
/4-in. electrical bulkhead connector, all factory-installed in
1
/2-in. electrical bulkhead connectors and
1
/2-in. NPT gas adapt-
the embossed (raised) section of the unit basepan in the condenser section.
15
Page 16
Fig. 21 — Fittings
LOW VOLTAGE
CONDUIT
CONNECTOR
HIGH VOLTAGE
CONDUIT
CONNECTOR
BRASS FITTING FOR
3 TO 6 TON UNITS
AUXILIARY
POWER
SUPPLY
(OPTIONAL)
9” (229mm) MIN
UNION
SHUT OFF
VALV E
DRIP
LEG
THRU-CURB ADAPTER
UNIT BASE RAIL
SHUT OFF
VALV E
UNION
9” (229 mm) MIN
UNIT BASE RAIL
BURNER
ACCESS
PAN EL
THRU-CURB ADAPTER
DRIP
LEG
The thru-base gas connector has male and female threads. The
male threads protrude above the basepan of the unit; the female
threads protrude below the basepan.
Check tightness of connector lock nuts before connecting gas
piping.
Install a
Attach a
1
/2-in. NPT street elbow on the thru-base gas fitting.
1
/2-in. pipe nipple with minimum length of 16-in.
(406 mm) (field-supplied) to the street elbow and extend it
through the access panel at the gas support bracket. See
Fig. 22.
does not block access to the unit’s main control box or limit the
required working space in front of the control box.
Fig. 23 — Gas Piping
EMBOSSMENT
Fig. 22 — Gas Line Piping for 3 to 5 Ton Units Only
Other hardware required to complete the installation of the gas
supply line will include a manual shutoff valve, a sediment trap
(drip leg) and a ground-joint union. A pressure regulator valve
may also be required (to convert gas pressure from pounds to
inches of pressure). The manual shutoff valve must be located
within 6 ft (1.83 m) of the unit. The union, located in the final
leg entering the unit, must be located at least 9-in. (230 mm)
away from the access panel to permit the panel to be removed
for service. If a regulator valve is installed, it must be located a
minimum of 4 ft (1220 mm) away from the unit’s flue outlet.
Some municipal codes require that the manual shutoff valve be
located upstream of the sediment trap. See Fig. 23 and 24 for
typical piping arrangements for gas piping that has been routed
through the sidewall of the curb. See Fig. 25 for typical piping
arrangement when thru-base is used. Ensure that all piping
BRASS FITTING
FOR GAS PIPING
SUPPORT
BRACKET
Fig. 24 — Gas Piping
Fig. 25 — Gas Piping Thru-Base Connections
16
Page 17
When installing the gas supply line, observe local codes per-
BURNER
ORIFICE
NOTE: Trap should be deep enough to offset maximum unit static
difference. A 4” (102) trap is recommended.
MINIMUM PITCH
1” (25mm) PER
10’ (3m) OF LINE
BASE RAIL
OPEN
VENT
TO ROOF
DRAIN
DRAIN PLUG
ROOF
CURB
SEE NOTE
2˝ (51) MIN
taining to gas pipe installations. Refer to the NFPA 54/ANSI
Z223.1 NFGC latest edition (in Canada, CAN/CSA B149.1).
In the absence of local building codes, adhere to the following
pertinent recommendations:
1.Avoid low spots in long runs of pipe. Grade all pipe
1
/4-in.
in every 15 ft (7 mm in every 5 m) to prevent traps. Grade
all horizontal runs downward to risers. Use risers to connect
to heating section and to meter.
2.Protect all segments of piping system against physical and
thermal damage. Support all piping with appropriate
straps, hangers, etc. Use a minimum of one hanger every
6 ft (1.8 m). For pipe sizes larger than
1
/2-in., follow rec-
ommendations of national codes.
3.Apply joint compound (pipe dope) sparingly and only to
male threads of joint when making pipe connections. Use
only pipe dope that is resistant to action of liquefied petroleum gases as specified by local and/or national codes. If
using PTFE (Teflon
1
) tape, ensure the material is Double
Density type and is labeled for use on gas lines. Apply
tape per manufacturer’s instructions.
4.Pressure-test all gas piping in accordance with local and
national plumbing and gas codes before connecting piping
to unit.
NOTE: Pressure-test the gas supply system after the gas supply
piping is connected to the gas valve. The supply piping must be
disconnected from the gas valve during the testing of the piping
systems when test pressure is in excess of 0.5 psig (3450 Pa).
Pressure-test the gas supply piping system at pressures equal to
or less than 0.5 psig (3450 Pa). The unit heating section must be
isolated from the gas piping system by closing the external main
manual-shutoff valve and slightly opening the ground-joint
union.
Check for gas leaks at the field-installed and factory-installed
gas lines after all piping connections have been completed. Use
soap-and-water solution (or method specified by local codes
and/or regulations).
Fig. 26 — Orifice Hole
Step 12 — Install External Condensate Trap and
Line
The unit has one 3/4-in. condensate drain connection on the end
of the condensate pan and an alternate connection on the bottom. See Fig. 27. Unit airflow configuration does not determine which drain connection to use. Either drain connection
can be used with vertical or horizontal applications.
To use the alternate bottom drain connection, remove the red
drain plug from the bottom connection (use a
et drive extension) and install it in the side drain connection.
The piping for the condensate drain and external trap can be
completed after the unit is in place. See Fig. 28.
1
/2-in. square sock-
WARNING
Failure to follow this warning could result in personal injury, death and/or property damage.
•Connect gas pipe to unit using a backup wrench to
avoid damaging gas controls.
•Never purge a gas line into a combustion chamber.
•Never test for gas leaks with an open flame. Use a
commercially available soap solution made specifically
for the detection of leaks to check all connections.
•Use proper length of pipe to avoid stress on gas control
manifold.
NOTE: If orifice hole appears damaged or it is suspected to have
been re-drilled, check orifice hole with a numbered drill bit of correct size. Never re-drill an orifice. A burr-free and squarely
aligned orifice hole is essential for proper flame characteristics.
See Fig. 26.
1. Teflon is a registered trademark of DuPont.
CONDENSATE PAN (SIDE VIEW)
STANDARD
SIDE DRAIN
DRAIN
PLUG
(FACTORY-INSTALLED)
Fig. 27 — Condensate Drain Pan (Side View)
Fig. 28 — Condensate Drain Piping Details
ALTERNATE
BOTTOM DRAIN
17
Page 18
All units must have an external trap for condensate drainage.
Disconnect
per
NEC
13
L1L2L3
IFTB
C
208/230-3-60
460-3-60
575-3-60
Units Without Disconnect or HACR Option
Units With Disconnect or HACR Option
L1
L2
L3
2
4
6
1
5
Optional
Disconnect
Switch
Factory
Wiring
3
Ground
(GR)
Equip
GR Lug
Equip GR Lug
Ground
(GR)
3 Phase On ly3 Phase Only
Install a trap at least 4-in. (102 mm) deep and protect against
freeze-up. If drain line is installed downstream from the external trap, pitch the line away from the unit at 1-in. per 10 ft
(25 mm in 3 m) of run. Do not use a pipe size smaller than the
unit connection (
3
/4-in.).
Step 13 — Make Electrical Connections
WARNING
Failure to follow this warning could result in personal injury or death.
Do not use gas piping as an electrical ground.
Unit cabinet must have an uninterrupted, unbroken electri-
cal ground to minimize the possibility of personal injury if
an electrical fault should occur. This ground may consist of
electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when
installed in accordance with NEC (National Electrical
Code); ANSI/NFPA 70, latest edition (in Canada, Canadian
Electrical Code CSA [Canadian Standards Association]
C22.1), and local electrical codes.
NOTE: Field-supplied wiring shall conform with the limitations
of minimum 63°F (33°C) rise.
FIELD POWER SUPPLY
If equipped with optional powered convenience outlet
The power source leads to the convenience outlet’s transformer
primary are not factory connected. Installer must connect these
leads according to required operation of the convenience outlet. If an always-energized convenience outlet operation is desired, connect the source leads to the line side of the unitmounted disconnect. (Check with local codes to ensure this
method is acceptable in your area.) If a de-energize via unit
disconnect switch operation of the convenience outlet is desired, connect the source leads to the load side of the unit disconnect. On a unit without a unit-mounted disconnect, connect
the source leads to compressor contactor C and indoor fan terminal block (IFTB) pressure lugs with unit field power leads.
Refer to Fig. 41 for power transformer connections and the discussion on connecting the convenience outlet on page 25.
Field power wires are connected to the unit at line-side pressure
lugs on compressor contactor C and indoor fan terminal block
(IFTB) (see wiring diagram label for control box component arrangement) or at factory-installed option non-fused disconnect
switch or HACR. Max wire size is #2ga AWG (copper only) per
pole on contactors. #2ga AWG per pole on optional disconnect
or HACR and 4/0 AWG per pole on terminal or fuse block on
units with single point box. See Fig. 29 and unit label diagram
for field power wiring connections. See Fig. 30-33 for typical
wiring diagrams.
Fig. 29 — Power Wiring Connections
18
Page 19
Fig. 30 — 48LC Control Wiring Diagram
19
Page 20
Fig. 31 — 48LC Control Wiring Diagram with Humidi-MiZer
Fig. 33 — 48LC Power Wiring Diagram, 575-v 3 Phase
22
Page 23
COPPER
WIRE ONLY
ELECTRIC
DISCONNECT
SWITCH
ALUMINUM
WIRE
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal inju-
ry, death, or property damage.
Do not connect aluminum wire between disconnect switch
and unit. Use only copper wire.
Fig. 34 — Disconnect Switch and Unit
UNITS WITH FACTORY-INSTALLED NON-FUSED DISCONNECT OR HACR
The factory-installed optional non-fused disconnect (NFD) or
HACR switch is located in a weatherproof enclosure located
under the main control box. The manual switch handle and
shaft is shipped in the disconnect or HACR enclosure. Assemble the shaft and handle to the switch at this point.
TO FIELD-INSTALL THE NFD SHAFT AND HANDLE:
1.Remove the control box access panel. The NFD enclosure
is located below the control box (see Fig. 35)
2.Remove (3) cap head screws that secure the NFD enclosure front cover – (2) on the face of the cover and (1) on
the left side cover. See Fig. 36.
3.Remove the front cover of the NFD enclosure.
4.Make sure the NFD shipped from the factory is at OFF
position (the arrow on the black handle knob is at OFF).
5.Insert the shaft with the cross pin on the top of the shaft in
the horizontal position.
6.Measure from the tip of the shaft to the top surface of the
black pointer; the measurement should be 3.75-in. to
3.88-in. (95 mm to 99 mm).
7.Tighten the locking screw to secure the shaft to the NFD.
8.Turn the handle to the OFF position with red arrow pointing at OFF.
9.Install the handle on to the painted cover horizontally with
the red arrow pointing to the left.
10. Secure the handle to the painted cover with (2) screws and
lock washers supplied.
11. Engaging the shaft into the handle socket, re-install (3) cap
head screws on the front cover.
Re-install the unit front panel.
Fig. 35 — Location of Non-Fused Disconnect
Enclosure
Fig. 36 — Handle and Shaft Assembly for NFD
TO FIELD-INSTALL THE HACR SHAFT AND HANDLE:
1.Remove the control box access panel. The HACR enclosure is located below the control box (see Fig. 37).
2.Remove (3) cap head screws that secure the HACR enclosure – (2) on the face of the cover and (1) on the left side
cover. See Fig. 38.
3.Remove the front cover of the HACR enclosure.
4.Make sure the HACR shipped from the factory is at OFF
position (the white arrow pointing at OFF).
5.Insert the shaft all the way with the cross pin on the top of
the shaft in the horizontal position.
6.Tighten the locking screw to secure the shaft to the HACR.
7.Turn the handle to the OFF position with red arrow pointing at OFF.
8.Install the handle on to the painted cover horizontally with
the red arrow pointing to the left.
9.Secure the handle to the painted cover with (2) screws and
lock washers supplied.
10. Engaging the shaft into the handle socket, re-install (3) cap
head screws on the front cover.
Re-install the unit front panel.
23
Page 24
Fig. 37 — Location of HACR Enclosure
Convenience
Outlet
GFCI
Pwd-CO
Fuse
Switch
Pwd-CO
Tr ansformer
Control Box
Access Panel
ALL UNITS
All field wiring must comply with NEC and all local codes.
Size wire based on MCA (Minimum Circuit Amps) on the unit
informative plate. See Fig. 29 and the unit label diagram for
power wiring connections to the unit power terminal blocks
and equipment ground. Maximum wire size is #2ga AWG per
pole on contactors. #2ga AWG per pole on optional disconnect
or HACR. See Fig. 29 and unit label diagram for field power
wiring connections.
Provide a ground-fault and short-circuit over-current protection
device (fuse or breaker) per NEC Article 440 (or local codes).
Refer to unit informative data plate for MOCP (Maximum
Over-Current Protection) device size.
NOTE: Units ordered with factory installed HACR do not need an
additional ground-fault and short-circuit over-current protective
device unless required by local codes.
All field wiring must comply with the NEC and local
requirements.
All units except 208/230-v units are factory-wired for the voltage shown on the nameplate. If the 208/230-v unit is to be connected to a 208-v power supply, the control transformer must
be rewired by moving the black wire with the
spade connector from the 230-v connection and moving it to
the 200-v
1
/4-in. male terminal on the primary side of the trans-
1
/4-in. female
former. Refer to unit label diagram for additional information.
NOTE: Check all factory and field electrical connections for
tightness.
CONVENIENCE OUTLETS
Fig. 38 — Handle and Shaft Assembly for HACR
UNITS WITHOUT FACTORY-INSTALLED NON-FUSED
DISCONNECT OR HACR
When installing units, provide a disconnect switch per NEC
(National Electrical Code) of adequate size. Disconnect sizing
data is provided on the unit informative plate. Locate disconnect sizing data on unit cabinet or within sight of the unit per
national or local codes. Do not cover unit informative plate if
mounting the disconnect on the unit cabinet.
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal inju-
ry or death.
Units with convenience outlet circuits may use multiple
disconnects. Check convenience outlet for power status before opening unit for service. Locate its disconnect switch,
if appropriate, and open it. Lock-out and tag-out this
switch, if necessary.
Two types of convenience outlets are offered: non-powered
and unit-powered. Both types provide a 125-v GFCI (groundfault circuit-interrupter) duplex receptacle rated at 15-A behind
a hinged waterproof access cover, located on the end panel of
the unit. See Fig. 39.
Fig. 39 — Convenience Outlet Location
24
Page 25
Installing Weatherproof Cover:
TOP
TOP
TOP
WET LOCATIONS
WET LOCAT IONS
COVER - WHILE-IN-USE
WEATHERPROOF
BASEPLATE FOR
GFCI RECEPTACLE
GASKET
GFCI RECEPTACLE
NOT INCLUDED
A weatherproof while-in-use cover for the factory-installed
convenience outlets is now required by UL standards. This
cover cannot be factory-mounted due to its depth; it must be installed at unit installation. For shipment, the convenience outlet
is covered with a blank cover plate.
The weatherproof cover kit is shipped in the unit’s control box.
The kit includes the hinged cover, a backing plate, and gasket.
DISCONNECT ALL POWER TO UNIT AND CONVENIENCE OUTLET. LOCK-OUT AND TAG-OUT ALL
POWER.
Remove the blank cover plate at the convenience outlet; discard the blank cover.
Loosen the two screws at the GFCI duplex outlet, until approximately
1
/2-in. (13 mm) under screw heads are exposed. Press
the gasket over the screw heads. Slip the backing plate over the
screw heads at the keyhole slots and align with the gasket;
tighten the two screws until snug (do not over-tighten).
Mount the weatherproof cover to the backing plate as shown in
Fig. 40. Remove two slot fillers in the bottom of the cover to
permit service tool cords to exit the cover. Check for full closing and latching.
UNIT
VOLTAGE
208, 230240
460480
575600
CONNECT
AS
PRIMARY
CONNECTIONS
L1: RED +YEL
L2: BLU + GRA
L1: RED
Splice BLU + YEL
L2: GRA
L1: RED
L2: GRA
TRANSFORMER
TERMINALS
H1 + H3
H2 + H4
H1
H2 + H3
H4
H1
H2
Fig. 41 — Powered Convenience Outlet Wiring
Using unit-mounted convenience outlets:
Units with unit-mounted convenience outlet circuits will often
require that two disconnects be opened to de-energize all power to the unit. Treat all units as electrically energized until the
convenience outlet power is also checked and de-energization
is confirmed. Observe National Electrical Code Article 210,
Branch Circuits, for use of convenience outlets.
Fuse on power type:
The factory fuse is a Bussman
1
“Fusetron” T-15, non-renew-
able screw-in (Edison base) type plug fuse.
Non-powered type:
This type requires the field installation of a general-purpose
125-v 15-A circuit powered from a source elsewhere in the
building. Observe national and local codes when selecting wire
size, fuse, or breaker requirements and disconnect switch size
and location. Route 125-v power supply conductors into the
bottom of the utility box containing the duplex receptacle.
Unit-powered type:
A unit-mounted transformer is factory-installed to stepdown
the main power supply voltage to the unit to 115-v at the duplex receptacle. This option also includes a manual switch with
fuse, located in a utility box and mounted on a bracket behind
the convenience outlet; access is through the unit’s control box
access panel. See Fig. 36.
The primary leads to the convenience outlet transformer are
not factory-connected. Selection of primary power source is a
customer option. If local codes permit, the transformer primary
leads can be connected at the line-side terminals on the unitmounted non-fused disconnect or HACR breaker switch; this
will provide service power to the unit when the unit disconnect
switch or HACR switch is open. Other connection methods
will result in the convenience outlet circuit being de-energized
when the unit disconnect or HACR switch is open. See Fig. 41.
The unit-powered convenience outlet has a duty cycle limitation. The transformer is intended to provide power on an intermittent basis for service tools, lamps, etc; it is not intended to
provide 15 amps loading for continuous duty loads (such as
electric heaters for overnight use). Observe a 50% limit on circuit loading above 8 amps.
Convenience outlet usage rating:
Continuous usage: 8 amps maximum
Test the GFCI receptacle by pressing the TEST button on the
face of the receptacle to trip and open the receptacle. Check for
proper grounding wires and power line phasing if the GFCI
1. Bussman and Fusetron are trademarks of Cooper Technologies
Company.
25
Page 26
receptacle does not trip as required. Press the RESET button to
clear the tripped condition.
HACR
The amp rating of the HACR factory-installed option is based
on the size, voltage, indoor motor, and other electrical options
of the unit as shipped from the factory. If field-installed accessories are added or changed in the field (i.e. electric heat, power exhaust, ERV), the HACR may no longer be of the proper
amp rating and therefore will need to be removed from the
unit. See unit nameplate and label on factory-installed HACR
for the amp rating of the HACR that was shipped with the unit
from the factory. See unit nameplates for the proper fuse,
HACR, or maximum over-current protection device required
on the unit with field-installed accessories. See Fig. 43.
and the current within 10%. Use the following formula to determine the percent of voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes
abuse and may cause damage to electrical components. Such
operation would invalidate any applicable Carrier warranty.
% Voltage Imbalance:
= 100 x
Example: Supply voltage is 230-3-60
Average Voltage=
Determine maximum deviation from average voltage.
(AB) 227-224 = 3 v
(BC) 231-227 = 4 v
(AC) 227-226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
This service connection kit consists of a
er fitting (brass), a
3
/4-in. electrical bulkhead connector, all factory-installed in the
embossed (raised) section of the unit basepan in the condenser
section. The
1
/2-in. electrical bulkhead connector and a
3
/4-in. bulkhead connector enables the low-voltage
control wires to pass through the basepan. The
1
/2-in. NPT gas adapt-
1
/2-in. electrical
bulkhead connector allows the high-voltage power wires to
pass through the basepan. See Fig. 21.
Check tightness of connector lock nuts before connecting electrical conduits.
Field-supplied and field-installed liquid-tight conduit connectors and conduit may be attached to the connectors on the basepan. Pull correctly-rated high voltage and low voltage through
appropriate conduits. Connect the power conduit to the internal
disconnect (if unit is so equipped) or to the external disconnect
(through unit side panel). A hole must be field-cut in the main
control box bottom on the left side so the 24-v control connections can be made. Connect the control power conduit to the
unit control box at this hole.
UNITS WITHOUT THRU-BASE CONNECTIONS
1.Install power wiring conduit through side panel openings.
Install conduit between disconnect and control box.
2.Install power lines to terminal connections as shown in
Fig. 29.
Voltage to compressor terminals during operation must be
within voltage range indicated on unit nameplate. On 3-phase
units, voltages between phases must be balanced within 2%
% Voltage Imbalance =100x
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.
NOTE: Check all factory and field electrical connections for tightness.
4
227
= 1.78%
FIELD CONTROL WIRING
The 48LC unit requires an external-temperature control device.
This device can be a thermostat (field-supplied) or, the RTU
Open Controller for Building Management Systems using nonCCN protocols (RTU Open is available as a factory-installed
option only), or a space temperature sensor (SPT) with factory
installed SystemVu™ controller.
THERMOSTAT
Install a Carrier-approved accessory thermostat according to
installation instructions included with the accessory. For complete economizer function and two-stage compressor operation, select a two-stage cooling thermostat. Locate the thermostat accessory on a solid wall in the conditioned space to sense
average temperature in accordance with the thermostat installation instructions.
If the thermostat contains a logic circuit requiring 24-v power,
use a thermostat cable or equivalent single leads of different
colors with minimum of seven leads. If the thermostat does not
require a 24-v source (no “C” connection required), use a thermostat cable or equivalent with minimum of six leads. Check
the thermostat installation instructions for additional features
which might require additional conductors in the cable.
For wire runs up to 50 ft. (15 m), use no. 18 AWG (American
Wire Gage) insulated wire [35°C (95°F) minimum]. For 50 to
75 ft. (15 to 23 m), use no. 16 AWG insulated wire [35°C
(95°F) minimum]. For over 75 ft. (23 m), use no. 14 AWG insulated wire [35°C (95°F) minimum]. All wire sizes larger than
no. 18 AWG cannot be directly connected to the thermostat and
will require a junction box and splice at the thermostat. See
Fig. 44.
Note 2: Y2 to Y2 connection required for 2 stage cooling operation and when
integrated economizer function is desired.
Field Wiring
Central
Terminal
Board
Typical
Thermostat
Connections
RACEWAY
HOLE IN END PANEL (HIDDEN)
Pass the thermostat control wires through the hole provided in
the corner post; then feed the wires through the raceway built
into the corner post to the control box. Pull the wires over to
the terminal strip on the upper-left corner of the Controls Connection Board. See Fig. 45.
Fig. 44 — Low-Voltage Connections
NOTE: If thru-the-bottom connections accessory is used, refer to
the accessory installation instructions for information on routing
power and control wiring.
HEAT ANTICIPATOR SETTINGS
Set heat anticipator settings at 0.14 amp for the first stage and
0.14 amp for second-stage heating, when available.
Humidi-MiZer® Control Connections
NOTE: It is recommended the Auto-Changeover function of an
installed thermostat be enabled when used in conjunction with the
Humidi-MiZer Adaptive Dehumidification system.
HUMIDI-MIZER – SPACE RH CONTROLLER
The Humidi-MiZer dehumidification system requires a field-
supplied and field-installed space-relative humidity control device. This device may be a separate humidistat control (contact
closes on rise in space RH above control setpoint) or a combination thermostat-humidistat control device such as Carrier’s
®
Edge
Pro Thermidistat with isolated contact set for dehumidification control. The humidistat is normally used in applications where a temperature control is already provided (units
with SystemVu™ controls).
To connect the Carrier humidistat (HL38MG029):
1.Route the humidistat 2-conductor cable (field-supplied)
through the hole provided in the unit corner post.
2.Feed wires through the raceway built into the corner post
(see Fig. 45) to the 24-v barrier located on the left side of
the control box. The raceway provides the UL-required
clearance between high-voltage and low-voltage wiring.
3.Use wire nuts to connect humidistat cable to the leads in
the low-voltage wiring (as shown in Fig. 48), connecting
PKN to PNK and PNK/BLK to PNK/BLK.
To connect the Thermidistat device (33CS2PPRH-03):
1.Route the Thermidistat multi-conductor thermostat cable
(field-supplied) through the hole provided in the unit corner post.
2.Feed wires through the raceway built into the corner post
(see Fig. 45) to the 24-v barrier located on the left side of
the control box. The raceway provides the UL-required
clearance between high-voltage and low-voltage wiring.
3.The Thermidistat has dry contacts at terminals D1 and D2
for dehumidification operation (see Fig. 52). The dry contacts must be wired between CTB terminal R and the PNK/
BLK lead to the LTLO switch with field-supplied wire nuts.
Refer to the installation instructions included with the Carrier Edge Thermidistat device for more information.
Fig. 45 — Field Control Raceway
27
Page 28
%RELATIVEHUMIDITY
®
Fig. 46 — Accessory Field-Installed Humidistat
Fig. 47 — Edge
®
Pro Thermidistat
®
Fig. 48 — Typical Humidi-MiZer
Adaptive Dehumidification System Humidistat Wiring
REHEAT MODES
Dehumidification (reheat) is a cooling mode function. Refer to
Cooling Operation for cooling mode control. With HumidiMiZer units, there are three additional HVAC Mode (HVAC)
expanded texts available for the user: Reheat1, Reheat2, and
Reheat1/Reheat2. Selection of the reheat mode for each refrigerant circuit is determined by the dehumidification demand and
the cooling demand. Table 7 shows the corresponding circuit
mode and output status for the different demand combinations.
Units with multiple circuits can operate with a combination of
Reheat1 and Reheat2 circuits, as determined by the amount of
space cooling demand.
NOTE: Compressor staging control for Humidi-MiZer units requires that circuit A always operates when circuit B is on. This applies to normal operation, service test, and for control alarm responses. This operation difference is required due to the fact that
the Motormaster outdoor fan control senses circuit A only. Operation of the revised refrigerant circuit for each mode is described
below.
Normal Cooling
For 48LC04-6 units, refrigerant flows from the outdoor condenser through the normally open Cooling Liquid Valve (CLV)
to the expansion device. Reheat Liquid Valve (RLV) and Reheat Discharge Valve (RDV) are closed. (See Fig. 49.)
Reheat 1 (Subcooling Mode)
This mode increases latent cooling and decreases sensible
cooling compared to normal cooling.
For 48LC04-6 units, refrigerant flows from the outdoor condenser, through the normally open Reheat Liquid Valve (RLV),
and through the reheat condenser coil to the expansion device.
Cooling Liquid Valve (CLV) and Reheat Discharge Valve
(RDV) are closed. (See Fig. 50.)
Reheat 2 (Hot Gas ReheatMode)
This mode provides maximum latent cooling with little to no
sensible capacity. This mode can operate to provide dehumidification when there is no cooling demand. Similar to Reheat 1
mode, refrigerant flows from the outdoor condenser, through
the normally open Reheat Liquid Valve (RLV1), or through the
energized 3-way Liquid Diverter Valve (LDV), and through the
reheat condenser coil to the expansion device. Reheat Discharge Valve (RDV) is open, which provides some compressor
discharge gas to the reheat condenser to further increase the reheat of the evaporator air stream (See Fig. 51).
RDV
VALV E
RLV
VALV E
CONDENSER COIL
OUTDOOR AIR
CLV
VALV E
COMPRESSOR
= CLOSED VALVE
= OPEN VALVE
HUMIDI-MIZER COIL
EVAPORATOR COIL
Fig. 49 — Normal Cooling Mode — Humidi-MiZer System
RDV
VALV E
CONDENSER COIL
RLV
VALV E
HUMIDI-MIZER COIL
INDOOR SUPPLY
AIR
EXPANSION
VALV E
(TXV)
INDOOR RETURN
AIR
INDOOR SUPPLY
AIR
OUTDOOR AIR
CLV
VALV E
COMPRESSOR
EVAPORATOR COIL
= CLOSED VALVE
= OPEN VALVE
INDOOR RETURN
AIR
Fig. 50 — Subcooling Mode (Reheat 1) — Humidi-MiZer System
29
EXPANSION
VALV E
(TXV)
Page 30
RDV
Rc
Rh
W1
G
Y2
C
O/W2/B
Y1
OAT
RR
S
S
RTN
HUM
D1
D2
V+
Vg
X
*
C
G
W2
W1
Y2
Y1
R
Edge Programable Thermostat
Unit CTB
THERMOSTAT
*Connection not required.
Humidi-MiZer FIOP
VALV E
INDOOR SUPPLY
AIR
CONDENSER COIL
RLV
VALV E
OUTDOOR AIR
CLV
VALV E
COMPRESSOR
= CLOSED VALVE
= OPEN VALVE
HUMIDI-MIZER COIL
EXPANSION
VALV E
(TXV)
EVAPORATOR COIL
INDOOR RETURN
AIR
Fig. 51 — Hot Gas Reheat Mode (Reheat 2) — Humidi-MiZer System
Fig. 52 — Typical Rooftop Unit with Humidi-MiZer Adaptive Dehumidification System with Edge
EconoMi$er® X (Factory-Installed Option)
For details on operating 48LC units equipped with the factoryinstalled EconoMi$er X option, refer to EconoMi$er X Facto-
ry-Installed Option Low Leak Economizer for 2 Speed SAV™
(Staged Air Volume) Systems.
SystemVu™ Controller (Factory-Installed Option)
For details on operating 48LC units equipped with the factoryinstalled SystemVu control option, refer to 48/50LC 04-26 Sin-
gle Package Rooftop Units with SystemVu Controls Version 2.X
Controls, Start-up, Operation and Troubleshooting manual.
RTU Open Control System
For details on operating 48LC**04-06 units equipped with the
factory-installed RTU Open controller option, refer to the Fac-
Thermidistat Device
tory Installed Option RTU Open Multi-Protocol Controller
Controls, Start-Up, Operation, Troubleshooting manual. See
Fig. 53 and 54.
30
®
Pro
Page 31
Fig. 53 — RTU Open System Control Wiring Diagram
31
Page 32
Fig. 54 — RTU Open System Control Wiring Diagram with Humidi-MiZer
32
®
System
Page 33
Smoke Detectors
RETURN AIR
SMOKE DETECTOR
(AS SHIPPED)
Smoke detectors are available as factory-installed options on
48LC models. Smoke detectors may be specified for supply-air
only, for return-air without or with economizer, or in combination of supply-air and return-air. All components necessary for
operation are factory-provided and mounted. The unit is factory-configured for immediate smoke detector shutdown operation; additional wiring or modifications to unit terminal board
may be necessary to complete the unit and smoke detector configuration to meet project requirements.
Units equipped with factory-optional return-air smoke detectors require a relocation of the sensor module at unit installation. See Fig. 55 for the as-shipped location.
Completing Installation of Return Air Smoke Sensor:
1.Unscrew the two screws holding the return-air smoke
detector assembly. See Fig. 56, Step 1. Save the screws.
2.Turn the assembly 90 degrees and then rotate end to end.
Make sure that the elbow fitting is pointing down. See
Fig. 56, Step 2.
3.Screw the sensor and detector plate into its operating position using screws from Step 1. See Fig. 56, Step 3.
4.Connect the flexible tube on the sampling inlet to the sampling tube on the basepan.
Additional Application Data
Refer to the application data document “Factory Installed
Smoke Detectors for Small and Medium Rooftop Units 2 to
25 Tons” for discussions on additional control features of these
smoke detectors, including multiple unit coordination.
Fig. 55 — Return-Air Smoke Detector, Shipping
Position
Step 1Step 2Step 3
Fig. 56 — Completing Installation of Return-Air Smoke Sensor
33
Page 34
Step 14 — Adjust Factory-Installed Options
Table 1
Table 2
BELT
CROSS
SECTION
SMALLEST
SHEAVE
DIAMETER
BELT DEFLECTION FORCE (LBS)
UNNOTCHED
BELTS
NOTCHED BELTS
USEDNEWUSEDNEW
A, AX
3.0-3.63.75.54.1 6.1
3.8-4.84.56.85.0 7.4
5.0-7.05.48.05.7 8.4
B, BX
3.4-4.2——4.9 7.2
4.4-5.65.37.97.110.5
5.8-8.66.39.48.512.6
BELT CONDITIONTENSION FORCE IN BELT (LBS)
New100
Used80
SMOKE DETECTORS
Smoke detector(s) will be connected at the Central Terminal
Board (CTB), at terminals marked “Smoke Shutdown”. Remove jumper JMP 3 when ready to energize unit.
Refer to separate installation instructions for information on installing these accessories.
Step 16 — Check Belt Tension
Measure the belt span length as shown in Fig. 57. Calculate the required deflection by multiplying the belt span length by
example, if the belt span length is 32 inches:
1
32 x
/64 = 1/2-in. deflection.
BELT FORCE — DEFLECTION METHOD
Check the belt tension with a spring-force belt force deflection
gage (available from drive belt manufacturer).
1.Place a straightedge along the belt between the two pulleys. Measure the distance between the motor shaft and the
blower shaft.
2.Set the tension gage to the desired tension (see Table 1 in
Fig. 57). Place the large O-ring at that point.
3.Press the tension checker downward on the belt until the
large O-ring is at the bottom of the straightedge.
4.Adjust the belt tension as needed.
Adjust belt tension by loosing the motor mounting plate front bolts
and rear bolt (see Fig. 58) and slide the plate towards the fan (to
reduce tension) or away from the fan (to increase tension). Ensure
the blower shaft and motor shaft are parallel to each other (pulleys
aligned). Tighten all bolts securely when finished.
1
/64. For
Fig. 57 — V-Belt Force Label
BELT TENSION METHOD
Requires belt tension gage that measures tension in belt in units of
lbs force.
BLOWER PULLEY
V-B ELT
MOTOR
PULLEY
MOTOR
MOUNTING
BOLTS (4)
MOTOR MOUNTING
PLATE
Fig. 58 — Belt Drive Motor Mounting
Pre-Start and Start-Up
This completes the mechanical installation of the unit. Refer to
the unit’s Service Manual for detailed Pre-Start and Start-Up
instructions. Download the latest versions from HVAC Partners (www.hvacpartners.com).
34
Page 35
APPENDIX A — VFD OPERATION WITH REMOTE KEYPAD
All 48LC size 04-06 units are equipped with a VFD (Variable
Frequency Drive) to automatically adjust the indoor-fan motor
speed in sequence with the unit’s ventilation, cooling and heating operation. The VFD keypad is included as standard on
electromechanical and RTU Open models. See Fig. B for location of the VFD and the VFD keypad in these units.
NOTE: SystemVu™ models do not include the VFD keypad as
VFD control operation is accessed through the SystemVu™
controls.
The VFD keypad is shown in Fig. A. The function of SOFT
KEYS 1 and 2 change depending on what is displayed on the
screen. The function of SOFT KEY 1 matches the word in the
lower left-hand box on the display screen. The function of
SOFT KEY 2 matches the word in the lower right-hand box on
the display screen. If the box is empty, then the SOFT KEY
does not have a function on that specific screen. The UP and
DOWN keys are used to navigate through the menus. The OFF
key is used to turn off the VFD. The AUTO key is used to
change control of the drive to automatic control. The HAND
key is used to change control of the drive to local (hand held)
control. The HELP button is used to access the help screens.
For the VFD to operate on the units covered by this document,
the drive must be set in AUTO mode. The word “AUTO” will
appear in the upper left hand corner of the VFD display. Press
the AUTO button to set the drive in AUTO mode.
Fig. A — VFD Keypad
Use the RJ-45 (CAT5) cable (bundled with the Control Harness
- see Fig. B) to provide easier access for using the VFD Remote Keypad. The cable’s length is long enough to route it
through to the unit’s control box, if desired.
To Connect the VFD Keypad using the RJ-45 Cable
1.Remove the Keypad from the front of the VFD.
2.Remove the RJ-45 adapter from the back of the Remote
Keypad and insert the adapter into the RJ-45 port on the
front of the VFD.
3.Separate the RJ-45 (CAT5) cable from the Control Harness.
4.Use the CAT5 cable to connect the Remote Keypad to the
VFD.
START UP WITH ASSISTANT
Initial start-up has been performed at the factory. Use of the
start up assistant will override factory VFD configurations. DO
NOT USE THE START-UP ASSISTANT ON THESE LC
UNITS!
35
Page 36
RJ-45 (CAT5) Cable
(Bundled with Control Harness)
ABB VFD
w/ Remote Keypad
Fig. B — Location of VFD in 48LC 04-06 Units
Start Up by Changing Parameters Individually
Initial start-up is performed at the factory. To start up the VFD
by changing individual parameters, perform the following procedure:
1.Select MENU (SOFT KEY 2). The Main menu will be
displayed.
2.Use the UP or DOWN keys to highlight PARAMETERS
on the display screen and press ENTER (SOFT KEY 2).
3.Use the UP or DOWN keys to highlight the desired
parameter group and press SEL (SOFT KEY 2).
4.Use the UP or DOWN keys to highlight the desired
parameter and press EDIT (SOFT KEY 2).
5.Use the UP or DOWN keys to change the value of the
parameter.
6.Press SAVE (SOFT KEY 2) to store the modified value.
Press CANCEL (SOFT KEY 1) to keep the previous
value. Any modifications that are not saved will not be
changed.
7.Choose another parameter or press EXIT (SOFT KEY 1)
to return to the listing of parameter groups. Continue until
all the parameters have been configured and then press
EXIT (SOFT KEY 1) to return to the main menu.
NOTE: The current parameter value appears above the highlight
parameter. To view the default parameter value, press the UP and
DOWN keys simultaneously. To restore the default factory settings, select the application macro “HVAC Default.”
VFD Modes
The VFD has several different modes for configuring, operating, and diagnosing the VFD. The modes are:
•Standard Display mode—shows drive status information
and operates the drive
•Start-up Assistant mode—guides the start up and configuration. DO NOT USE THE START-UP ASSISTANT ON
THESE LC UNITS!
•Changed Parameters mode—shows all changed parameters
•Drive Parameter Backup mode—stores or uploads the
parameters
•Clock Set mode—sets the time and date for the drive
•I/O Settings mode—checks and edits the I/O settings
STANDARD DISPLAY MODE
Use the standard display mode to read information on the drive
status and operate the drive. To reach the standard display
mode, press EXIT until the LCD display shows status information as described below. (See Fig. C.)
The top line of the LCD display shows the basic status information of the drive. The HAND icon indicates that the drive
control is local from the control panel. The AUTO icon indicates that the drive is in remote control mode, such as the basic
I/O or field bus.
36
Page 37
The arrow icon indicates the drive and motor rotation status. A
60.0Hz
100.0 %SP
1.9 A
10.0 Vdc
rotating arrow (clockwise or counterclockwise) indicates that
the drive is running and at set point and the shaft direction is
forward or reverse. A rotating blinking arrow indicates that the
drive is running but not at setpoint. A stationary arrow indicates that the drive is stopped. For the units covered in this
manual, the correct display rotation is clockwise.
The upper-right corner shows the frequency setpoint that the
drive will maintain.
Using parameter group 34, the middle of the LCD display can
be configured to display 3 parameter values. The default display shows parameters 0103 (OUTPUT FREQ) in percent
speed, 0104 (CURRENT) in amperes, and 0120 (Al1) in voltage DC.
The bottom corners of the LCD display show the functions currently assigned to the two soft keys. The lower middle screen
displays the current time (if configured to show the time).
The first time the drive is powered up, it is in the OFF mode.
To switch to local hand-held control and control the drive using
the control panel, press and hold the HAND button. Pressing
the HAND button switches the drive to hand control while
keeping the drive running. Press the AUTO button to switch to
remote input control. To start the drive press the HAND or
AUTO buttons, to stop the drive press the OFF button.
Fig. C — Standard Display Example
To adjust the speed in HAND mode, press the UP or DOWN
buttons (the reference changes immediately). The reference
can be modified in the local control (HAND) mode, and can be
parameterized (using Group 11 reference select) to also allow
modification in the remote control mode.
PARAMETERS MODE
The Parameters mode is used to change the parameters on the
drive. To change parameters, perform the following procedure.
See Tables A through C for a listing of the VFD parameters per
motor and VFD drive models:
1.Select MENU (SOFT KEY 2). The main menu will be
displayed.
2.Use the UP or DOWN keys to highlight PARAMETERS
on the display screen and press ENTER (SOFT KEY 2).
3.Use the UP or DOWN keys to highlight the desired
parameter group and press SEL (SOFT KEY 2).
4.Use the UP or DOWN keys to highlight the desired
parameter and press EDIT (SOFT KEY 2).
5.Use the UP or DOWN keys to change the value of the
parameter.
6.Press SAVE (SOFT KEY 2) to store the modified value.
Press CANCEL (SOFT KEY 1) to keep the previous
value. Any modifications that are not saved will not be
changed.
7.Choose another parameter or press EXIT (SOFT KEY 1)
to return to the listing of parameter groups. Continue until
all the parameters have been configured and then press
EXIT (SOFT KEY 1) to return to the main menu.
NOTE: The current parameter value appears above the highlight
parameter. To view the default parameter value, press the UP and
DOWN keys simultaneously. To restore the default factory settings, select the Carrier application macro.
CHANGED PARAMETERS MODE
The Changed Parameters mode is used to view and edit recent-
ly changed parameters on the drive. To view the changed parameters, perform the following procedure:
1.Select MENU (SOFT KEY 2). The main menu will be
displayed.
2.Use the UP or DOWN keys to highlight CHANGED PAR
on the display screen and press ENTER (SOFT KEY 2). A
list of the recently changed parameters will be displayed.
3.Use the UP or DOWN keys to highlight the desired
parameter group and press EDIT (SOFT KEY 2) to change
the parameter if desired.
4.Press EXIT (SOFT KEY 1) to exit the Changed Parameters mode.
DRIVE PARAMETER BACKUP MODE
The drive parameter back-up mode is used to export the param-
eters from one drive to another. The parameters can be uploaded from a VFD to the removable control panel. The control
panel can then be transferred to another drive and the parameters are downloaded into memory.
Depending on the motor and application, there are two options
available. The first option is to download all parameters. This
copies both application and motor parameters to the drive from
the control panel. This is recommended when using the same
application for drives of the same size. This can also be used to
create a backup of the parameters group for the drive.
The second option downloads only the application parameters
to the drive. This is recommended when using the same application for drives of different sizes.
Upload All Parameters
To upload and store parameters in the control panel from the
VFD, perform the following procedure:
1.Select MENU (SOFT KEY 2). The main menu will be
displayed.
2.Use the UP or DOWN keys to highlight PAR BACKUP on
the display screen and press ENTER (SOFT KEY 2).
3.Use the UP or DOWN keys to highlight UPLOAD TO
PANEL and press SEL (SOFT KEY 2).
4.The text “Copying Parameters” will be displayed with a
progress indicator. To stop the process, select ABORT
(SOFT KEY 1).
5.When the upload is complete, the text “Parameter upload
successful” will be displayed.
6.The display will then return to the PAR BACKUP menu.
Select EXIT (SOFT KEY 1) to return to the main menu.
7.The control panel can now be disconnected from the drive.
Download All Parameters
To download all parameters from the control panel to the VFD,
perform the following procedure:
1.Install the control panel with the correct parameters onto
the VFD.
2.Select MENU (SOFT KEY 2). The main menu will be
displayed.
3.Use the UP or DOWN keys to highlight PAR BACKUP on
the display screen and press ENTER (SOFT KEY 2).
4.Use the UP or DOWN keys to highlight DOWNLOAD
TO DRIVE ALL and press SEL (SOFT KEY 2).
5.The text “Restoring Parameters” will be displayed with a
progress indicator. To stop the process, select ABORT
(SOFT KEY 1).
6.When the download is complete, the text “Parameter
download successful” will be displayed.
7.The display will then return to the PAR BACKUP menu.
Select EXIT (SOFT KEY 1) to return to the main menu.
37
Page 38
8.The control panel can now be disconnected from the drive.
Download Application Parameters
To download application parameters only to the control panel
from the VFD, perform the following procedure:
1.Install the control panel with the correct parameters onto
the VFD.
2.Select MENU (SOFT KEY 2). The main menu will be
displayed.
3.Use the UP or DOWN keys to highlight PAR BACKUP on
the display screen and press ENTER (SOFT KEY 2).
4.Use the UP or DOWN keys to highlight DOWNLOAD
APPLICATION and press SEL (SOFT KEY 2).
5.The text “Downloading Parameters (partial)” will be displayed with a progress indicator. To stop the process,
select ABORT (SOFT KEY 1).
6.When the download is complete, the text “Parameter
download successful” will be displayed.
7.The display will then return to the PAR BACKUP menu.
Select EXIT (SOFT KEY 1) to return to the main menu.
8.The control panel can now be disconnected from the drive.
CLOCK SET MODE
The clock set mode is used for setting the date and time for the
internal clock of the VFD. In order to use the timer functions of
the VFD control, the internal clock must be set. The date is
used to determine weekdays and is visible in the fault logs.
To set the clock, perform the following procedure:
1.Select MENU (SOFT KEY 2). The main menu will be
displayed.
2.Use the UP or DOWN keys to highlight CLOCK SET on
the display screen and press ENTER (SOFT KEY 2). The
clock set parameter list will be displayed.
3.Use the UP or DOWN keys to highlight CLOCK VISIBILITY and press SEL (SOFT KEY 2). This parameter is
used to display or hide the clock on the screen. Use the UP
or DOWN keys to change the parameter setting. Press OK
(SOFT KEY 2) to save the configuration and return to the
Clock Set menu.
4.Use the UP or DOWN keys to highlight SET TIME and
press SEL (SOFT KEY 2). Use the UP or DOWN keys to
Table A — 48LC 04 VFD Parameters
change the hours and minutes. Press OK (SOFT KEY 2) to
save the configuration and return to the Clock Set menu.
5.Use the UP or DOWN keys to highlight TIME FORMAT
and press SEL (SOFT KEY 2). Use the UP or DOWN
keys to change the parameter setting. Press OK (SOFT
KEY 2) to save the configuration and return to the Clock
Set menu.
6.Use the UP or DOWN keys to highlight SET DATE and
press SEL (SOFT KEY 2). Use the UP or DOWN keys to
change the day, month, and year. Press OK (SOFT KEY 2)
to save the configuration and return to the Clock Set menu.
7.Use the UP or DOWN keys to highlight DATE FORMAT
and press SEL (SOFT KEY 2). Use the UP or DOWN
keys to change the parameter setting. Press OK (SOFT
KEY 2) to save the configuration and return to the Clock
Set menu.
8.Press EXIT (SOFT KEY 1) twice to return to the main
menu.
I/O SETTINGS MODE
The I/O Settings mode is used for viewing and editing the I/O
settings.
To configure the I/O settings, perform the following procedure:
1.Select MENU (SOFT KEY 2). The main menu will be
displayed.
2.Use the UP or DOWN keys to highlight I/O SETTINGS
on the display screen and press ENTER (SOFT KEY 2).
The I/O Settings parameter list will be displayed.
3.Use the UP or DOWN keys to highlight the desired I/O
setting and press SEL (SOFT KEY 2).
4.Use the UP or DOWN keys to select the parameter to
view. Press OK (SOFT KEY 2).
5.Use the UP or DOWN keys to change the parameter setting. Press SAVE (SOFT KEY 2) to save the configuration. Press CANCEL (SOFT KEY 1) to keep the previous
value. Any modifications that are not saved will not be
changed.
6.Press EXIT (SOFT KEY 1) twice to return to the main
menu.
PARAMETER
GROUP
START-UP
DATA
START/STOP/
DIR
REFERENCE
SELECT
UNIT SIZE48LC 04
Motor Description1.7 HP 575v1.7 HP 208-230v1.7 HP 460v2.4 HP 575v2.4 HP 208-230v
2101Start Function(1) AUTO(1) AUTO(1) AUTO(1) AUTO(1) AUTO
2102Stop Function(1) Coast(1) Coast(1) Coast(1) Coast(1) Coast
2109EM STOP Sel(0) NOT SEL(0) NOT SEL(0) NOT SEL(0) NOT SEL(0) NOT SEL
2201Acc/Dec 1/2 Sel(0) NOT SEL(0) NOT SEL(0) NOT SEL(0) NOT SEL(0) NOT SEL
2202Accelerate Time30.0 s30.0 s30.0 s30.0 s30.0 s
2203Decelerate Time10.0 s10.0 s10.0 s10.0 s10.0 s
2606
2607
Motor Part
Number
VFD Part
Number
ABB Part
Number
Application
Macro
Motor
Nominal Voltage
Motor
Nominal Current
Motor
Nominal
Frequency
Motor
Nominal Speed
Motor
Nominal Power
Constant Speed
Select
Constant Speed
1
Constant Speed
2
Constant Speed
3
Maximum
Current
Minimum
Frequency
Maximum
Frequency
Switching
Frequency
Switching
Frequency
Control
2.4 HP 460v1.7 HP 575v1.7 HP 208-230v1.7 HP 460v2.4 HP 575v
Motor Part NumberHD56FE653HD56FE653HD58FE654HD58FE654HD58FE577
VFD Part NumberHK30WA001HK30WA008HK30WA001HK30WA008HK30WA021
ABB Part Number
Switching Frequency
Control
VFD DIAGNOSTICS
The drive detects error situations and reports them using:
1.Green and red LEDs on the body of the drive (located
under the keypad)
2.Status LED on the control panel
3.Control panel display
4.The Fault Word and Alarm Word parameter bits (parameters 0305 to 0309)
The form of the display depends on the severity of the error.
The user can specify the severity for many errors by directing
the drive to ignore the error situation, report the situation as an
alarm, or report the situation as a fault.
Faults (Red LED Lit)
The VFD signals that it has detected a severe error, or fault, by:
1.Enabling the red LED on the drive (LED is either steady
or flashing)
2.Setting an appropriate bit in a Fault Word parameter (0305
to 0307)
3.Overriding the control panel display with the display of a
fault code
4.Stopping the motor (if it was on)
5.Sets an appropriate bit in Fault Word parameter 0305-0307
The fault code on the control panel display is temporary. Pressing the MENU, ENTER, UP button or DOWN buttons removes the fault message. The message reappears after a few
2.4 HP 208230v
ACH550-
CARUH
-012A-2
(1) ON(1) ON(1) ON(1) ON(1) ON
2.4 HP 460v
ACH550-
CARUH
-06A9-4
seconds if the control panel is not touched and the fault is still
active.
Alarms (Green LED Flashing)
For less severe errors, called alarms, the diagnostic display is
advisory. For these situations, the drive is simply reporting that
it detects something unusual.
In these situations, the drive:
1.Flashes the green LED on the drive (does not apply to
alarms that arise from control panel operation errors)
2.Sets an appropriate bit in an Alarm Word parameter (0308
or 0309)
3.Overrides the control panel display with the display of an
alarm code and/or name
Alarm messages disappear from the control panel display after
a few seconds. The message returns periodically as long as the
alarm condition exists.
Correcting Faults
The recommended corrective action for faults is shown in
Table D. The VFD can also be reset to remove the fault. If an
external source for a start command is selected and is active,
the VFD may start immediately after fault reset.
To reset a fault indicated by a flashing red LED, turn off the power
for 5 minutes. To reset a fault indicated by a red LED (not flashing), press RESET from the control panel or turn off the power for
5 minutes. Depending on the value of parameter 1604 (FAULT
RESET SELECT), digital input or serial communication could
2.9 HP 208230v
ACH550-
CARUH
-012A-2
2.9 HP 460v3.7 HP 575v
ACH550-
CARUH
-06A9-4
ACH550-
CARUH
-06A1-6
42
Page 43
also be used to reset the drive. When the fault has been corrected,
the motor can be started.
History
For reference, the last three fault codes are stored into parameters 0401, 0412, 0413. For the most recent fault (identified by
parameter 0401), the drive stores additional data (in parameters
0402 through 0411) to aid in troubleshooting a problem. For
example, a parameter 0404 stores the motor speed at the time
of the fault. To clear the fault history (all of Group 04, Fault
History parameters), follow these steps:
1.In the control panel, Parameters mode, select parameter
0401.
2.Press EDIT.
3.Press the UP and DOWN buttons simultaneously.
4.Press SAVE.
Correcting Alarms
To correct alarms, first determine if the Alarm requires any
corrective action (action is not always required). Use Table E
If diagnostics troubleshooting has determined that the drive is
defective during the warranty period, contact ABB Automation
Inc., at 1-800-435-7365, option 4, option 3. A qualified technician will review the problem with the caller and make a determination regarding how to proceed. This may involve dispatching a designated service station (DSS) representative
from an authorized station, dispatching a replacement unit, or
advising return for repair.
Control Panel Cleaning
Use a soft damp cloth to clean the control panel. Avoid harsh
cleaners which could scratch the display window.
Battery Replacement
A battery is only used in assistant control panels that have the
clock function available and enabled. The battery keeps the
clock operating in memory during power interruptions. The expected life for the battery is greater than ten years. To remove
the battery, use a coin to rotate the battery holder on the back of
the control panel. Replace the battery with type CR2032.
to find and address the root cause of the problem.
Table D — FAULT CODES
FAULT CODEFAULT NAME IN PANELDESCRIPTION AND RECOMMENDED CORRECTIVE ACTION
1OVERCURRENT
2DC OVERVOLT
3DEV OVERTEMP
4SHORT CIRCFault current. Check for short-circuit in the motor cable(s) or motor or supply disturbances.
5OVERLOADInverter overload condition. The drive output current exceeds the ratings.
6DC OVERVOLT
7AI1 LOSS
8AI2 LOSS
9MOT OVERTEMP
10PANEL LOSS
11ID RUN FAILThe motor ID run was not completed successfully. Check motor connections.
12MOTOR STALL
13RESERVEDNot used.
14EXT FAULT 1Digital input defined to report first external fault is active. See parameter 3003 EXTERNAL FAULT 1.
15EXT FAULT 2
16EARTH FAULT
17UNDERLOAD
18THERM FAIL
19OPEX LINK
20
21CURR MEASInternal fault. Current measurement is out of range. Contact Carrier.
22SUPPLY PHASERipple voltage in the DC link is too high. Check for missing main phase or blown fuse.
23RESERVEDNot used.
24OVERSPEED
25RESERVEDNot used.
26DRIVE IDInternal fault. Configuration block drive ID is not valid.
OPEX PWRInternal fault. Low voltage condition detected on the OINT board. Contact Carrier.
Output current is excessive. Check for excessive motor load, insufficient acceleration time (parameters
2202 ACCELER TIME 1, default 30 seconds), or faulty motor, motor cables or connections.
Intermediate circuit DC voltage is excessive. Check for static or transient over voltages in the input
power supply, insufficient deceleration time (parameters 2203 DECELER TIME 1, default 30 seconds),
or undersized brake chopper (if present).
Drive heat sink is overheated. Temperature is at or above 115°C (239°F). Check for fan failure,
obstructions in the airflow, dirt or dust coating on the heat sink, excessive ambient temperature, or
excessive motor load.
Intermediate circuit DC voltage is not sufficient. Check for missing phase in the input power supply,
blown fuse, or under voltage on main circuit.
Analog input 1 loss. Analog input value is less than AI1 FLT LIMIT (3021). Check source and
connection for analog input and parameter settings for AI1 FLT LIMIT (3021) and 3001 AI<MIN
FUNCTION.
Analog input 2 loss. Analog input value is less than AI2 FLT LIMIT (3022). Check source and
connection for analog input and parameter settings for AI2 FLT LIMIT (3022) and 3001 AI<MIN
FUNCTION.
Motor is too hot, as estimated by the drive. Check for overloaded motor. Adjust the parameters used
for the estimate (3005 through 3009). Check the temperature sensors and Group 35 parameters.
Panel communication is lost and either drive is in local control mode (the control panel displays LOC),
or drive is in remote control mode (REM) and is parameterized to accept start/stop, direction or
reference from the control panel. To correct check the communication lines and connections. Check
parameter 3002 PANEL COMM ERROR, parameters in Group 10: Command Inputs and Group
11:Reference Select (if drive operation is REM).
Motor or process stall. Motor is operating in the stall region. Check for excessive load or insufficient
motor power. Check parameters 3010 through 3012.
Digital input defined to report second external fault is active. See parameter 3004 EXTERNAL FAULT
2.
The load on the input power system is out of balance. Check for faults in the motor or motor cable.
Verify that motor cable does not exceed maximum specified length.
Motor load is lower than expected. Check for disconnected load. Check parameters 3013
UNDERLOAD FUNCTION through 3015 UNDERLOAD CURVE.
Internal fault. The thermistor measuring the internal temperature of the drive is open or shorted.
Contact Carrier.
Internal fault. A communication-related problem has been detected between the OMIO and OINT
boards. Contact Carrier.
Motor speed is greater than 120% of the larger (in magnitude) of 2001 MINIMUM SPEED or 2002
MAXIMUM SPEED parameters. Check parameter settings for 2001 and 2002. Check adequacy of
motor braking torque. Check applicability of torque control. Check brake chopper and resistor.
43
Page 44
Table D — FAULT CODES (cont)
FAULT CODEFAULT NAME IN PANELDESCRIPTION AND RECOMMENDED CORRECTIVE ACTION
27CONFIG FILEInternal configuration file has an error. Contact Carrier.
28SERIAL 1 ERR
29EFB CON FILEError in reading the configuration file for the field bus adapter.
30FORCE TRIPFault trip forced by the field bus. See the field bus reference literature.
31EFB 1Fault code reserved for the EFB protocol application. The meaning is protocol dependent.
32EFB 2Fault code reserved for the EFB protocol application. The meaning is protocol dependent.
33EFB 3Fault code reserved for the EFB protocol application. The meaning is protocol dependent.
34MOTOR PHASE
35OUTP WIRING
101-105SYSTEM ERRORError internal to the drive. Contact Carrier and report the error number.
201-206SYSTEM ERRORError internal to the drive. Contact Carrier and report the error number.
1000PAR HZRPM
1001PAR PFA REFNG
1002PAR PFA IOCNF
1003PAR AI SCALE
1004PAR AO SCALE
1005PAR PCU 2
1006PAR EXT RO
1007PAR FBUS
1008PAR PFA MODE
1009PAR PCU 1
1010OVERRIDE/PFA CONFLICT
Field bus communication has timed out. Check fault setup (3018 COMM FAULT FUNC and 3019
COMM FAULT TIME). Check communication settings (Group 51 or 53 as appropriate). Check for poor
connections and/or noise on line.
Fault in the motor circuit. One of the motor phases is lost. Check for motor fault, motor cable fault,
thermal relay fault, or internal fault.
Error in power wiring suspected. Check that input power is wired to drive output. Check for ground
faults.
Parameter values are inconsistent. Check for any of the following:
2001 MINIMUM SPEED > 2002 MAXIMUM SPEED
2007 MINIMUM FREQ > 2008 MAXIMUM FREQ
2001 MINIMUM SPEED / 9908 MOTOR NOM SPEED is outside of the range: -128/+128
2002 MAXIMUM SPEED / 9908 MOTOR NOM SPEED is outside of the range: -128/+128
2007 MINIMUM FREQ / 9907 MOTOR NOM FREQ is outside of the range: -128/+128
2008 MAXIMUM FREQ / 9907 MOTOR NOM FREQ is outside of the range: -128/+128
Parameter values are inconsistent. Check that 2007 MINIMUM FREQ is negative, when 8123 PFA
ENABLE is active.
Parameter values are inconsistent. The number of programmed PFA relays does not match with
Interlock configuration, when 8123 PFA ENABLE is active. Check consistency of RELAY OUTPUT
parameters 1401 through 1403, and 1410 through 1412. Check 8117 NR OF AUX MOTORS, 8118
AUTOCHANGE INTERV, and 8120 INTERLOCKS.
Parameter values are inconsistent. Check that parameter 1301 AI 1 MIN > 1302 AI 1 MAX and that
parameter 1304 AI 2 MIN > 1305 AI 2 MAX.
Parameter values are inconsistent. Check that parameter 1504 AO 1 MIN > 1505 AO 1 MAX and that
parameter 1510 AO 2 MIN > 1511 AO 2 MAX.
Parameter values for power control are inconsistent: Improper motor nominal kVA or motor nominal
power. Check the following parameters:
1.1 < (9906 MOTOR NOM CURR * 9905 MOTOR NOM VOLT * 1.73 / PN) < 2.6
Where: PN = 1000 * 9909 MOTOR NOM POWER (if units are kW) or PN = 746
* 9909 MOTOR NOM POWER (if units are HP, e.g., in US)
Parameter values are inconsistent. Check the extension relay module for connection and 1410
through 1412 RELAY OUTPUTS 4 through 6 have non-zero values.
Parameter values are inconsistent. Check that a parameter is set for field bus control (e.g., 1001 EXT1
COMMANDS = 10 (COMM)), but 9802 COMM PROT SEL = 0.
Parameter values are inconsistent. The 9904 MOTOR CTRL MODE must = 3 (SCALAR SPEED)
when 8123 PFA ENABLE activated.
Parameter values for power control are inconsistent or improper motor nominal frequency or speed.
Check for both of the following:
1 < (60 * 9907 MOTOR NOM FREQ / 9908 MOTOR NOM SPEED < 16
0.8 < 9908 MOTOR NOM SPEED / (120 * 9907 MOTOR NOM FREQ / Motor poles) < 0.992
Override mode is enabled and PFA is activated at the same time. This cannot be done because PFA
interlocks cannot be observed in the override mode.
44
Page 45
Table E — ALARM CODES
ALARM CODE ALARM NAME IN PANELDESCRIPTION AND RECOMMENDED CORRECTIVE ACTION
2001-Reserved
2002-Reserved
2003-Reserved
2004DIR LOCK
2005I/O COMM
2006AI1 LOSS
2007AI2 LOSS
2008PANEL LOSS
2009-Reserved
2010MOT OVERTEMP
2011UNDERLOAD
2012MOTOR STALLMotor is operating in the stall region. This alarm warns that a Motor Stall fault trip may be near.
2013*AUTORESET
2014AUTOCHANGE
2015PFA INTERLOCK
2016-Reserved
2017*OFF BUTTONThis alarm indicates that the OFF button has been pressed.
2018PID SLEEP
2019ID RUNThe VFD is performing an ID run.
2020OVERRIDEOverride mode is activated.
2021START ENABLE 1 MISSING
2022START ENABLE 2 MISSING
2023EMERGENCY STOPEmergency stop is activated.
The change in direction being attempted is not allowed. Do not attempt to change the direction of
motor rotation, or change parameter 1003 DIRECTION to allow direction change (if reverse operation
is safe).
Field bus communication has timed out. Check fault setup (3018 COMM FAULT FUNC and 3019
COMM FAULT TIME). Check communication settings (Group 51 or 53 as appropriate). Check for
poor connections and/or noise on line.
Analog input 1 is lost, or value is less than the minimum setting. Check input source and connections.
Check the parameter that sets the minimum (3021) and the parameter that sets the Alarm/Fault
operation (3001).
Analog input 2 is lost, or value is less than the minimum setting. Check input source and connections.
Check parameter that sets the minimum (3022) and the parameter that sets the Alarm/Fault operation
(3001).
Panel communication is lost and either the VFD is in local control mode (the control panel displays
HAND), or the VFD is in remote control mode (AUTO) and is parameterized to accept start/stop,
direction or reference from the control panel. To correct, check the communication lines and
connections, Parameter 3002 PANEL LOSS, and parameters in groups 10 COMMAND INPUTS and
11 REFERENCE SELECT (if drive operation is REM).
Motor is hot, based on either the VFD estimate or on temperature feedback. This alarm warns that a
Motor Overload fault trip may be near. Check for overloaded motor. Adjust the parameters used for
the estimate (3005 through 3009). Check the temperature sensors and Group 35 parameters.
Motor load is lower than expected. This alarm warns that a Motor Underload fault trip may be near.
Check that the motor and drive ratings match (motor is NOT undersized for the drive). Check the
settings on parameters 3013 to 3015.
This alarm warns that the drive is about to perform an automatic fault reset, which may start the
motor. To control automatic reset, use parameter group 31 (AUTOMATIC RESET).
This alarm warns that the PFA autochange function is active. To control PFA, use parameter group 81
(PFA) and the Pump Alternation macro.
This alarm warns that the PFA interlocks are active, which means that the drive cannot start any
motor (when Autochange is used), or a speed regulated motor (when Autochange is not used).
This alarm warns that the PID sleep function is active, which means that the motor could accelerate
when the PID sleep function ends. To control PID sleep, use parameters 4022 through 4026 or 4122
through 4126.
This alarm warns that the Start Enable 1 signal is missing. To control Start Enable 1 function, use
parameter 1608. To correct, check the digital input configuration and the communication settings.
This alarm warns that the Start Enable 2 signal is missing. To control Start Enable 2 function, use
parameter 1609. To correct, check the digital input configuration and the communication settings.
Catalog No. 04-53480187-01Printed in U.S.A.Form 48LC-4-6-04SIPg 46 6-19Replaces: 48LC-4-6-03SI
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Page 47
START-UP CHECKLIST FOR 48LC SINGLE PACKAGE ROOFTOP COOLING ONLY
(REMOVE AND STORE IN JOB FILE)
NOTE: To avoid injury to personnel and damage to equipment or
property when completing the procedures listed in this start-up
checklist, use good judgment, follow safe practices, and adhere
to the safety considerations/information as outlined in preceding sections of this Installation Instruction document.
I. PRELIMINARY INFORMATION
MODEL NO ____________________________________________
Verify that all packaging materials have been removed from unit (Y/N) _____
Verify installation of outdoor air hood (Y/N) _____
Verify installation of flue exhaust and inlet hood (Y/N) _____
Verify that condensate connection is installed per instructions (Y/N) _____
Verify that all electrical connections and terminals are tight (Y/N) _____
Verify gas pressure to unit gas valve is within specified range (Y/N) _____
Check gas piping for leaks (Y/N) _____
Check that indoor-air filters are clean and in place (Y/N) _____
Check that outdoor-air inlet screens are in place (Y/N) _____
Verify that unit is level (Y/N) _____
Check fan wheels and propeller for location in housing/orifice and verify setscrew is tight (Y/N) _____
Verify that fan sheaves are aligned and belts are properly tensioned (Y/N) _____
Verify that scroll compressors are rotating in the correct direction (Y/N) _____
Verify installation of thermostat (Y/N) _____
Verify that crankcase heaters have been energized for at least 24 hours (Y/N) _____
Outdoor-Air Temperature _____________ °F DB (Dry Bulb)
Return-Air Temperature _____________ °F DB _____________ °F Wb (Wet Bulb)
Cooling Supply Air Temperature _____________ °F
Gas Heat Air Temperature _____________ °F
Catalog No. 04-53480187-01Printed in U.S.A.Form 48LC-4-6-04SIPg CL-1 6-19Replaces: 48LC-4-6-03SI
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Page 48
PRESSURES
Gas Inlet Pressure _____________ IN. WG
Gas Manifold PressureSTAGE 1 _____________ IN. WG
STAGE 2 _____________ IN. WG
Refrigerant SuctionCIRCUIT A _____________ PSIG
CIRCUIT B _____________ PSIG
Refrigerant Discharge CIRCUIT A _____________ PSIG
CIRCUIT B _____________ PSIG
Verify Refrigerant Charge using Charging Charts (Y/N) _____
GENERAL
Economizer minimum vent and changeover settings to job requirements (if equipped) (Y/N) _____
Verify smoke detector unit shutdown by utilizing magnet test (Y/N) _____
IV. HUMIDI-MIZER® START-UP
NOTE: Units equipped with either SystemVu™ or RTU Open controls have Service Test menus or modes that can assist with the
Humidi-MiZer System Start-Up function and provide the means to make the observations listed for this start-up.
STEPS
1. Check CTB for jumper 5, 6, 7 (Jumper 5, 6, 7 must be cut and open) (Y/N) _____
2. Open humidistat contacts (Y/N) _____
3. Start unit In cooling (Close Y1) (Y/N) _____
OBSERVE AND RECORD
A. Suction pressure _______________ PSIG
B. Discharge pressure _______________ PSIG
C. Entering air temperature _______________ ° F
D. Liquid line temperature at outlet or reheat coil _______________ ° F
E. Confirm correct rotation for compressor (Y/N) _____
F. Check for correct ramp-up of outdoor fan motor as condenser coil warms (Y/N) _____
4. Check unit charge per charging chart (Y/N) _____
(Jumper 32L Motormaster
5. Switch unit to high-latent mode (sub-cooler) by closing humidistat with Y1 closed (Y/N) _____
®
temperature sensor during this check. Remove jumper when complete.)
OBSERVE
A. Reduction in suction pressure (5 to 7 psi expected) (Y/N) _____
B. Discharge pressure unchanged (Y/N) _____
C. Liquid temperature drops to 50°F to 55°F range (Y/N) _____
D. LSV solenoid energized (valve closes) (Y/N) _____
6. Switch unit to dehumid (reheat) by opening Y1 (Y/N) _____
OBSERVE
A. Suction pressure increases to normal cooling level
B. Discharge pressure decreases (35 to 50 psi) (Limited by Motormaster control)
C. Liquid temperature returns to normal cooling level
D. LSV solenoid energized (valve closes)
E. DSV solenoid energized, valve opens
7. With unit in dehumid mode close W1 compressor and outdoor fan stop; LSV and DSV solenoids de-energized
(Y/N) _____
8. Open W1 restore unit to dehumid mode (Y/N) _____
9. Open humidistat input compressor and outdoor fan stop; LSV and DSV solenoids de-energized (Y/N) _____
10. Restore set-points for thermostat and humidistat (Y/N) _____