Carrier WeatherExpert 48LC 04 Series, WeatherExpert 48LC 06 Series, WeatherExpert48LC 05 Series Installation Instructions Manual

Page 1
WeatherExpert® 48LC 04-06
Single Package Rooftop
Gas Heating/Electric Cooling Unit
with Puron
Installation Instructions
®
(R-410A) Refrigerant
NOTE: Read the entire instruction manual before starting the installation.
CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . 1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Jobsite Survey . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Step 1 — Plan for Unit Location . . . . . . . . . . . . . . . . . 9
• ROOF MOUNT
Step 2 — Plan for Sequence of Unit Installation . . . . 9
• CURB-MOUNTED INSTALLATION
• PAD-MOUNTED INSTALLATION
• FRAME-MOUNTED INSTALLATION
Step 3 — Inspect Unit . . . . . . . . . . . . . . . . . . . . . . . . . 9
Step 4 — Provide Unit Support. . . . . . . . . . . . . . . . . . 9
• ROOF CURB MOUNT
• SLAB MOUNT (HORIZONTAL UNITS ONLY)
• ALTERNATE UNIT SUPPORT (IN LIEU OF CURB OR SLAB MOUNT)
Step 5 — Field Fabricate Ductwork . . . . . . . . . . . . . 10
Step 6 — Rig and Place Unit . . . . . . . . . . . . . . . . . . . 10
• POSITIONING ON CURB
Step 7 — Convert to Horizontal and Connect
Ductwork (when required). . . . . . . . . . . . . . . . . . . 12
Step 8 — Install Outside Air Hood . . . . . . . . . . . . . . 13
• ECONOMIZER HOOD PACKAGE REMOVAL AND SETUP - FACTORY OPTION
• ECONOMIZER HOOD
Step 9 — Units with Hinged Panels Only . . . . . . . . . 14
Step 10 — Install Flue Hood . . . . . . . . . . . . . . . . . . . 14
Step 11 — Install Gas Piping. . . . . . . . . . . . . . . . . . . 14
• FACTORY-OPTION THRU-BASE CONNECTIONS (GAS CONNECTIONS)
Step 12 — Install External Condensate Trap and
Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Step 13 — Make Electrical Connections . . . . . . . . . 18
• FIELD POWER SUPPLY
• UNITS WITH FACTORY-INSTALLED NON-FUSED DISCONNECT OR HACR
• TO FIELD-INSTALL THE NFD SHAFT AND HANDLE:
• TO FIELD-INSTALL THE HACR SHAFT AND HANDLE:
• UNITS WITHOUT FACTORY-INSTALLED NON­FUSED DISCONNECT OR HACR
• ALL UNITS
• CONVENIENCE OUTLETS
• HACR
• FACTORY-OPTION THRU-BASE CONNECTIONS (ELECTRICAL CONNECTIONS)
• UNITS WITHOUT THRU-BASE CONNECTIONS
• FIELD CONTROL WIRING
• THERMOSTAT
• UNIT WITHOUT THRU-BASE CONNECTION KIT
• HEAT ANTICIPATOR SETTINGS
Humidi-MiZer® Control Connections . . . . . . . . . . . .27
• HUMIDI-MIZER – SPACE RH CONTROLLER
• REHEAT MODES
EconoMi$er® X (Factory-Installed Option). . . . . . . .30
SystemVu™ Controller (Factory-Installed Option) .30
RTU Open Control System. . . . . . . . . . . . . . . . . . . . .30
Smoke Detectors. . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
Step 14 — Adjust Factory-Installed Options . . . . . .34
• SMOKE DETECTORS
Step 15 — Install Accessories . . . . . . . . . . . . . . . . . .34
Step 16 — Check Belt Tension . . . . . . . . . . . . . . . . .34
• BELT FORCE — DEFLECTION METHOD
• BELT TENSION METHOD
Pre-Start and Start-Up . . . . . . . . . . . . . . . . . . . . . . . .34
• START UP WITH ASSISTANT
• STANDARD DISPLAY MODE
• PARAMETERS MODE
• CHANGED PARAMETERS MODE
• DRIVE PARAMETER BACKUP MODE
•CLOCK SET MODE
• I/O SETTINGS MODE
APPENDIX A — VFD OPERATION WITH REMOTE
KEYPAD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . .CL-1

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes, including ANSI (American National Standards Institute) Z223.1. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguisher available for all brazing operations.
It is important to recognize safety information. This is the safety-alert symbol . When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety­alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
Catalog No. 04-53480187-01 Printed in U.S.A. Form 48LC-4-6-04SI Pg 1 6-19 Replaces: 48LC-4-6-03SI
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Page 2
WARNING
GAS VALVE
INLET PRESSURE
TAP SET SCREW
MANIFOLD
GAS VALVE
MANIFOLD PRESSURE
TAP SET SCREW
FIRE, EXPLOSION HAZARD Failure to follow this warning could result in death, serious
personal injury and/or property damage. Disconnect gas piping from unit when pressure testing at
pressure greater than 0.5 psig (3450 Pa). Pressures greater than 0.5 psig will cause gas valve damage resulting in haz­ardous condition. If gas valve is subjected to pressure great­er than 0.5 psig, it must be replaced before use. When pres­sure testing field-supplied gas piping at pressures of
0.5 psig or less, a unit connected to such piping must be isolated by closing the manual gas valve(s).
WARNING
FIRE HAZARD Failure to follow this warning could result in personal inju-
ry, death, and/or property damage. Inlet pressure tap set screw must be tightened and
pipe plug must be installed to prevent gas leaks.
1
/8-in. NPT
AVERTISSEMENT
RISQUE D’INTOXICATION AU MONOXYDE DE CARBONE
Si ces directives ne sont pas suivies, cela peut entraîner des blessures graves ou une intoxication au monoxyde de car­bone pouvant causer la mort, si des produits de combustion s’infiltrent dans le bâtiment.
Vérifier que toutes les ouvertures pratiquées dans le mur extérieur autour du ou des tuyaux d’évent (et de la prise d’air) sont scellées de manière à empêcher l’infiltration de produits de combustion dans le bâtiment.
Veiller à ce que la ou les sorties de l’évent de l’appareil de chauffage (et la prise d’air) ne soient, en aucune façon, ob­struées, quelle que soit la saison.
WARNING
ELECTRICAL SHOCK HAZARD Failure to follow this warning could cause personal injury
or death. Before performing service or maintenance operations on
unit, turn off main power switch to unit and install lock(s) and lockout tag(s). Ensure electrical service to rooftop unit agrees with voltage and amperage listed on the unit rating plate. Unit may have more than one power switch.
FIRE HAZARD Failure to follow this warning could result in personal inju-
ry, death, and/or property damage. Manifold pressure tap set screw must be tightened and
NPT pipe plug must be installed to prevent gas leaks.
CARBON-MONOXIDE POISONING HAZARD Failure to follow instructions could result in severe personal
injury or death due to carbon-monoxide poisoning, if combustion products infiltrate into the building.
Check that all openings in the outside wall around the vent (and air intake) pipe(s) are sealed to prevent infiltration of combustion products into the building.
Check that furnace vent (and air intake) terminal(s) are not obstructed in any way during all seasons.
WARNING
1
/8-in.
WARNING
WARNING
UNIT OPERATION AND SAFETY HAZARD Failure to follow this warning could cause personal injury,
death and/or equipment damage.
®
Puron
(R-410A) refrigerant systems operate at higher pres­sures than standard R-22 systems. Do not use R-22 service equipment or components on Puron refrigerant equipment.
WARNING
PERSONAL INJURY AND ENVIRONMENTAL HAZARD Failure to follow this warning could cause personal injury
or death. Relieve pressure and recover all refrigerant before system
repair or final unit disposal. Wear safety glasses and gloves when handling refrigerants.
Keep torches and other ignition sources away from refriger­ants and oils.
CAUTION
CUT HAZARD Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing air conditioning equipment.

GENERAL

See Fig. 1 for unit options. See Fig. 2 and 3 for unit dimensions. See Fig. 4 for corner weights and clearances. See Fig. 5 for base rail details. See Fig. 6 for thru-the-base charts.
2
Page 3

Rated Indoor Airflow (cfm)

48LCD006A0A5-0A0A 0
1234567891011 12 13 14 15 16
17 18
Model Series - WeatherExpert
®
LC – Ultra High Efficiency
Unit Heat Type
48 – Gas Heat Packaged Rooftop
Cooling Tons
04 – 3 ton 05 – 4 ton 06 – 5 ton
Heat Options
D = Low Gas Heat E = Medium Gas Heat F = High Gas Heat L = Low NOx – Low Gas Heat M = Low NOx – Medium Gas Heat N = Low NOx – High Gas Heat S = Low Heat w/ Stainless Steel Exchanger R = Medium Heat w/ Stainless Steel Exchanger T = High Heat w/ Stainless Steel Exchanger (Low NOx models include – Stainless Steel HX)
Sens or Options
A = None B = RA Smoke Detector C = SA Smoke Detector D = RA + SA Smoke Detector E = CO
2
F = RA Smoke Detector and CO
2
G = SA Smoke Detector and CO
2
H = RA + SA Smoke Detector and CO
2
Indoor Fan Options
0 = Standard Electrical (Direct) Drive x13 ECM Motor 2 = Medium Static Belt Drive with VFD controller 3 = High Static Belt Drive with VFD controller
Refrig. Systems Options
0 = Two stage cooling capacity A = Two stage cooling capacity with Humidi-MiZer
®
System
Coil Options: Fin/Tube (Condenser- Evaporator - Hail Guard)
A = Al/Cu - Al/Cu B = Precoat Al/Cu – Al/Cu C = E-coat Al/Cu – Al/Cu D = E-coat Al/Cu – E-coat Al/Cu E = Cu/Cu – Al/Cu F = Cu/Cu – Cu/Cu M = Al/Cu – Al/Cu – Louvered Hail Guard N = Precoat Al/Cu – Al/Cu – Louvered Hail Guard P = E-coat Al/Cu – Al/Cu – Louvered Hail Guard Q = E-coat Al/Cu – E-coat Al/Cu – Louvered Hail Guard R = Cu/Cu – Al/Cu – Louvered Hail Guard S = Cu/Cu – Cu/Cu – Louvered Hail Guard
Voltage
1 = 575/3/60 5 = 208-230/3/60 6 = 460/3/60
Design Revision
– = Factory Design Revision
Base Unit Controls
0 = Base Electromechanical Controls 1 = RTU Open Multi-Protocol Controller 4 = SystemVu™ Controller
Intake / Exhaust Options
A = None B =
Temperature Economizer with Barometric Relief E = Enthalpy Economizer with Barometric Relief N = Ultra Low Leak Temperature Economizer with Barometric Relief R = Ultra Low Leak Enthalpy Economizer with Barometric Relief
Service Options
0 = None 1 = Unpowered Convenience Outlet 2 = Powered Convenience Outlet 3 = Hinged Panels 4 = Hinged Panels and Unpowered Convenience Outlet 5 = Hinged Panels and Powered Convenience Outlet
Packaging
0 = Standard 1 = LTL
Electrical Options
A = None B = HACR Breaker C = Non-Fused Disconnect D = Thru-The-Base Connections E = HACR Breaker with Thru-The-Base Connections F = Non-Fused Disconnect and Thru-The-Base Connections
Example:
Position:
Table 1 lists the rated indoor airflow used for the AHRI effi­ciency rating for the units covered in this document.
Table 1 — Rated Indoor Airflow (cfm)
MODEL NUMBER
48LC**04 1050 48LC**05 1400 48LC**06 1750
FULL LOAD AIRFLOW
(CFM)
Fig. 1 — 48LC 04-06 Model Number Nomenclature
3
Page 4
Fig. 2 — Dimensional Drawing of Units Built on and After 4/15/19
4
Page 5
Fig. 3 — Dimensional Drawing for Units Built On and Prior to 4/14/19
5
Page 6
Fig. 4 — Corner Weights and Clearances
6
Page 7
Fig. 5 — Base Rail Details
7
Page 8
Fig. 6 — Thru-the-Base Charts
8
Page 9

INSTALLATION

Jobsite Survey

Complete the following checks before installation.
1. Consult local building codes and the NEC (National Elec­trical Code) ANSI/NFPA 70 for special installation requirements.
2. Determine unit location (from project plans) or select unit location.
3. Check for possible overhead obstructions which may interfere with unit lifting or rigging.

Step 1 — Plan for Unit Location

Select a location for the unit and its support system (curb or other) that provides for the minimum clearances required for safety. This includes the clearance to combustible surfaces, unit performance and service access below and around unit as specified in Fig. 4.
NOTE: Consider also the effect of adjacent units. Be sure that unit is installed such that snow will not block the
combustion intake or flue outlet. Unit may be installed directly on wood flooring or on Class A,
B, or C roof-covering material when roof curb is used. Do not install unit in an indoor location. Do not locate air inlets
near exhaust vents or other sources of contaminated air. For proper unit operation, adequate combustion and ventilation air must be provided in accordance with Section 5.3 (Air for Com­bustion and Ventilation) of the National Fuel Gas Code, ANSI Z223.1 (American National Standards Institute) and NFPA (National Fire Protection Association) 54 TIA-54-84-1. In Canada, installation must be in accordance with the CAN1­B149 installation codes for gas burning appliances.
Although unit is weatherproof, avoid locations that permit wa­ter from higher level runoff and overhangs to fall onto the unit.
Locate mechanical draft system flue assembly at least 4 ft (1.2 m) from any opening through which combustion products could enter the building, and at least 4 ft (1.2 m) from any adja­cent building (or per local code). Locate the flue assembly at least 10 ft (3.05 m) from an adjacent unit’s fresh air intake hood if within 3 ft (0.91 m) of same elevation (or per local code). When unit is located adjacent to public walkways, flue assembly must be at least 7 ft (2.1 m) above grade.
Select a unit mounting system that provides adequate height to allow installation of condensate trap per requirements. Refer to “Step 12 — Install External Condensate Trap and Line” on page 17 for required trap dimensions.
ROOF MOUNT Check building codes for weight distribution requirements.
Unit operating weight is shown in Table 2.
Table 2 — Operating Weights
48LC**
Base Unit 505 (229) 590 (268) 600 (272) Economizer Vertical 50 (23) 50 (23) 50 (23) Horizontal 80 (36) 80 (36) 80 (36) Humidi-MiZer Cu Fins 25 (11) 43 (20) 56 (25) Powered Outlet 35 (16) 35 (16) 35 (16) Curb 14-in./356 mm 115 (52) 115 (52) 115 (52) 24-in./610 mm 197 (89) 197 (89) 197 (89)
®
System 50 (23) 55 (25) 55 (25)
UNITS LB (KG)
04 05 06

Step 2 — Plan for Sequence of Unit Installation

The support method used for this unit will dictate different se­quences for the steps of unit installation. For example, on curb­mounted units, some accessories must be installed on the unit before the unit is placed on the curb. Review the following for recommended sequences for installation steps.

CURB-MOUNTED INSTALLATION

1. Install curb
2. Install field-fabricated ductwork inside curb
3. Install accessory thru-base service connection package (affects curb and unit) (refer to accessory installation instructions for details)
4. Prepare bottom condensate drain connection to suit planned condensate line routing (refer to “Step 12 — Install External Condensate Trap and Line” on page 17 for details)
5. Rig and place unit
6. Install outdoor-air hood
7. Install flue hood
8. Install gas piping
9. Install condensate line trap and piping
10. Make electrical connections
11. Install other accessories

PAD-MOUNTED INSTALLATION

1. Prepare pad and unit supports
2. Check and tighten the bottom condensate drain connection plug
3. Rig and place unit
4. Convert unit to side duct connection arrangement
5. Install field-fabricated ductwork at unit duct openings
6. Install outdoor-air hood
7. Install flue hood
8. Install gas piping
9. Install condensate line trap and piping
10. Make electrical connections
11. Install other accessories
FRAME-MOUNTED INSTALLATION Frame-mounted applications generally follow the sequence for
a curb installation. Adapt as required to suit specific installa­tion plan.

Step 3 — Inspect Unit

Inspect unit for transportation damage. File any claim with transportation agency.
Confirm before installation of unit that voltage, amperage and circuit protection requirements listed on unit data plate agree with power supply provided.

Step 4 — Provide Unit Support

ROOF CURB MOUNT Accessory roof curb details and dimensions are shown in Fig. 8
(see page 11). Assemble and install accessory roof curb in ac­cordance with instructions shipped with the curb.
NOTE: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket supplied with the roof curb as shown in Fig. 8. Improperly applied gasket can also result in air leaks and poor unit performance.
Curb should be level. This is necessary for unit drain to func­tion properly. Unit leveling tolerances are show in Fig. 7. Refer to Accessory Roof Curb Installation Instructions for additional information as required.
9
Page 10
Fig. 7 — Unit Leveling Tolerances
A-B
0.5 (13)
B-C
1.0 (25)
A-C
1.0 (25)
MAXIMUM ALLOWABLE
DIFFERENCE – IN. (MM)
Install insulation, cant strips, roofing felt, and counter flashing as shown. Ductwork must be attached to curb and not to the
unit. The accessory thru-the-base power and gas connection package must be installed before the unit is set on the roof curb. If field-installed thru-the-roof curb gas connections are
desired, use factory-supplied
1
/2-in. pipe coupling and gas plate assembly to mount the thru-the-roof curb connection to the roof curb. Gas connections and power connections to the unit must be field-installed after the unit is installed on the roof curb.
If electric and control wiring is to be routed through the basepan, attach the accessory thru-the-base service connections to the base­pan in accordance with the accessory installation instructions.
SLAB MOUNT (HORIZONTAL UNITS ONLY) Provide a level concrete slab that extends a minimum of 6-in.
(150 mm) beyond unit cabinet. Install a gravel apron in front of condenser coil air inlet to prevent grass and foliage from ob­structing airflow.
NOTE: Horizontal units may be installed on a roof curb if required.

ALTERNATE UNIT SUPPORT (IN LIEU OF CURB OR SLAB MOUNT)

A non-combustible sleeper rail can be used in the unit curb support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 3 equally spaced 4-in. x 4-in. (102 mm x 102 mm) pads on each side.

Step 5 — Field Fabricate Ductwork

Cabinet return-air static pressure (a negative condition) shall not exceed 0.35 in. wg (87 Pa) with economizer or 0.45 in. wg (112 Pa) without economizer.
For vertical ducted applications, secure all ducts to roof curb and building structure. Do not connect ductwork to unit.
Fabricate supply ductwork so that the cross-sectional dimen­sions are equal to or greater than the unit-supply duct opening dimensions for the first 18-in. (458 mm) of duct length from the unit basepan.
Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through unconditioned spaces must be insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes.
A minimum clearance is not required around ductwork.
CAUTION
PROPERTY DAMAGE HAZARD Failure to follow this caution may result in damage to roof-
ing materials. Membrane roofs can be cut by sharp sheet metal edges. Be
careful when placing any sheet metal parts on such roof.

Step 6 — Rig and Place Unit

Keep unit upright and do not drop. Spreader bars are required. Rollers may be used to move unit across a roof. Level by using unit frame as a reference. See Table 2 and Fig. 9 for additional information.
Lifting holes are provided in base rails as shown in Fig. 9. Re­fer to rigging instructions on unit.
Rigging materials under unit (cardboard or wood) must be re­moved PRIOR to placing the unit on the roof curb.
When using the standard side drain connection, ensure the red plug in the alternate bottom connection is tight. Do this before setting the unit in place. The red drain pan plug can be tight­ened with a
1
/2-in. square socket drive extension. For further details, see “Step 12 — Install External Condensate Trap and Line” on page 17.
CAUTION
UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage. All panels must be in place when rigging. Unit is not designed
for handling by fork truck when packaging is removed. If using top crate as spreader bar, once unit is set, carefully
lower wooden crate off building roof top to ground. Ensure that no people or obstructions are below prior to lowering the crate.
Before setting the unit onto the curb, recheck gasketing on curb.
POSITIONING ON CURB Position unit on roof curb so that the following clearances are
maintained: and the base rail inside the front and rear, 0.0-in. clearance be­tween the roof curb and the base rail inside on the duct end of the unit. This will result in the distance between the roof curb and the base rail inside on the condenser end of the unit being approximately
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
Flue vent discharge must have a minimum horizontal clear­ance of 4 ft (1220 mm) from electric and gas meters, gas regu­lators, and gas relief equipment. Minimum distance between unit and other electrically live parts is 48-in. (1220 mm).
Flue gas can deteriorate building materials. Orient unit such that flue gas will not affect building materials. Locate mechan­ical draft system flue assembly at least 48-in. (1220 mm) from an adjacent building or combustible material.
NOTE: Installation of accessory flue discharge deflector kit will reduce the minimum clearance to combustible material to 18-in. (460 mm).
After unit is in position, remove rigging skids and shipping materials.
1
/4-in. (6.4 mm) clearance between the roof curb
1
/4-in. (6.4 mm).
10
Page 11
1-3/4"
TYP
[44.5]
C
ACCESSORY CONVENIENCE
OUTLET WIRING CONNECTOR
FITTING
1/2" [12.7] NPT 1/2" [12.7] NPT
CONTROL WIRING
FITTING
POWER WIRING
3/4" [19] NPT 1 1/4" [31.7] NPT
THRU THE CURB
CRBTMPWR004A01 THRU THE BOTTOM
CRBTMPWR002A01
CONNECTOR PKG. ACC. GAS CONNECTION TYPE GAS FITTING
1 3/4"
[44.5]
1.00"
[25.4]
12-1/2" [317.5] WIDE
INSULATED DECK PANELS
INSULATED DECK PANEL
9-15/16" [252.4] WIDE
"A"
1 3/4"
[44.4]
SEE NOTE #2
2-3/8"
[61]
20-3/4"
[513]
INSIDE
GAS SERVICE PLATE
THRU THE CURB
DRILL HOLE
2" [50.8] @
ASSEMBLY (IF
REQUIRED)
(SEE NOTE #8)
SECTION THRU SIDE
RETURN AIR
SUPPLY AIR
UNIT
[1987.5]
6' 6-1/4"
4' 2"
[1270.0]
"A"
NAIL (FIELD SUPPLIED)
TYPICAL (4) SIDES
7/16"
CERTIFIED DRAWING
SEE VIEW "B"
ROOFING FELT
(FIELD SUPPLIED)
COUNTER FLASHING
(FIELD SUPPLIED)
[11]
CURB ASY, ROOF
THIS DOCUMENT AND THE INFORMATION CONTAINED THEREIN
IS PROPRIETARY TO CARRIER CORPORATION AND SHALL NOT
BE USED OR DISCLOSED TO OTHERS, IN WHOLE OR IN PART,
WITHOUT THE WRITTEN AUTHORIZATION OF CARRIER CORPORATION.
1029120
TOLERANCES ON:
AUTHORIZATION NUMBER TITLE
DIMENSIONS ARE IN INCHES
----
UNLESS OTHERWISE SPECIFIED
1 DEC 2 DEC 3 DEC ANG
PRODUCTION
---
MATERIAL
DRAWING RELEASE LEVEL:
THIRD ANGLE
PROJECTION
ROOFING MATERIAL
(FIELD SUPPLIED)
CANT STRIP
(FIELD SUPPLIED)
RIGID INSULATION
SHEET 5 OF 5
50HJ405012
SIZE DRAWING NUMBER REV
D
-
-
-
DRAFTER CHECKER
ENGINEERING MANUFACTURING
-
MMC 12/16/09 - -
-
T-005, Y-002
WEIGHT:
- PURCH - N/A -
ENGINEERING REQUIREMENTS
SURFACE FINISH MFG/PURCH MODEL (INTERNAL USE ONLY) NEXT DRAWING SCALE DISTRIBUTION
ECN NO.APP'DCHK'DBYDATEREVISION RECORDREV
1067898--MMC4/22/13
(FIELD SUPPLIED)
2 1/4"
[57.2]
14 3/4"
[374.7]
NOTES:
1. ROOFCURB ACCESSORY IS SHIPPED DISASSEMBLED.
2. INSULATED PANELS: 25.4 [1"] THK. POLYURETHANE FOAM, 44.5 [1-3/4] # DENSITY.
3. DIMENSIONS IN [ ] ARE IN MILLIMETERS.
4. ROOFCURB: 18 GAGE STEEL.
5. ATTACH DUCTWORK TO CURB. (FLANGES OF DUCT REST ON CURB).
6. SERVICE CLEARANCE 4 FEET ON EACH SIDE.
7. DIRECTION OF AIR FLOW.
8. CONNECTOR PACKAGE CRBTMPWR002A01 IS FOR THRU-THE-CURB GAS TYPE
PACKAGE CRBTMPWR004A01 IS FOR THRU-THE-BOTTOM TYPE GAS CONNECTIONS.
53 1/2"
[1358.9]
11.42"
[290.0]
A
14"
24"
[356]
[610]
26"
[660.4]
6 3/64"
ROOF CURB
ACCESSORY #
CRRFCURB003A01
CRRFCURB004A01
[153.5]
1 3/4"
[44.4]
4 3/16"
[106.0]
81 3/4"
[827.1]
32 9/16"
[2076.3]
3"
40 3/16"
[76.2]
[1020.8]
VIEW "B"
CORNER DETAIL
[585.8]
23 1/16"
OPENING
RETURN AIR
OPENING
SUPPLY AIR
1 3/4"
[44.5]
[401.6]
15 13/16"
DUCT
GASKET
(FIELD SUPPLIED)
(SUPPLIED WITH CURB)
15 15/32
[392.9]
[800.9]
31 17/32"
1 3/4"
[44.5]
6' 61/4" WAS 6' 7 1/6", 4'2' WAS 4' 2 13/16";
18 GA WAS 16 GA.; 15 13/16" WAS 15 15/16"; NAIL
FIELD SUPPLIED WAS WITH CURB
C
SUPPLY AIR RETURN AIR
1/4"
[7.0]
[115.5]
4 9/16"
Fig. 8 — Roof Curb Details
11
Page 12
CAUTION - NOTICE TO RIGGERS: AVERTISSEMENT - REMARQUE À
L’ATTENTION DES MONTEURS
ALL PANELS MUST BE IN PLACE WHEN RIGGING.
TOUS LES CAPOTS DOIVENT ÊTRE EN PLACE AVANT LE LEVAGE
• Hook rigging shackles through holes in base rail, as shown in Detail “A”.
• Use wooden top skid, when rigging, to prevent rigging straps from damaging unit.
• Max weight includes base unit plus shipping pallet plus all available FIOP's which could be on that size unit.
• "B" dimension is based on base unit (PAC no heat or YAC w/low heat) plus economizer option only. This dimension may vary slightly with units congured with other FIOP options.
• Spreader bars required to lift and transport the unit.
• Accrocher les manilles des élingues de levages dans les trous situés dans le rail de base comme indiqué au Détail « A ».
• Utiliser des cales en bois lors du levage pour éviter que les élingues n’endommagent le haut de l’appareil.
• Le poids maximum inclut la conguration de base, le poids de la palette d'expédition, ainsi que toutes les options pouvant être installées en usine (FIOP) pour la plateforme sélectionnée.
• La dimension de "B" provient de la conguration de base (PAC sans chauage ou YAC chauage au gaz natufrel) qui inclut l'option economizer seulement. Cette dimension peut varier légèrement en fonction des diérentes options sélectionnées, installées en usine (FIOP).
• Barres d'écartement requises pour soulever et transporter l'unité.
PLACE ALL SEAL STRIP IN PLACE
REQUIRED SPREADER
BARS
“B”
914-1371
(36"- 54")
C
BEFORE PLACING UNIT ON ROOF CURB.
INSTALLER TOUTES LES BANDES D’ISOLATION EN PLACE AVANT DE PLACER L’APPAREIL SUR LE REBORD DE TOIT.
DUCT END
PASSAGES CONDUITES
DETAIL A
DÉTAIL « A »
A
SEE DETAIL “A”
VOIR DÉTAIL « A »
MODEL
50LC_004 50LC_005 50LC_006 48LC_004 48LC_005 48LC_006
MAX WEIGHT
LB KG
700
830 865
760 895 930
Fig. 9 — Rigging Label

Step 7 — Convert to Horizontal and Connect Ductwork (when required)

Unit is shipped in the vertical duct configuration. Unit without factory-installed economizer or return-air smoke detector op­tion may be field-converted to horizontal ducted configuration. To convert to horizontal configuration, remove screws from side duct opening covers (see Fig. 10) and remove covers. Use the screws to install the covers on vertical duct openings with the insulation-side down. The panels must be inserted into the notches on the basepan to properly seal. The notches are cov­ered by the tape used to secure the insulation to the basepan and are not easily seen. See Fig. 11 for position of the notches
318 377 393 345
407 423
AB
IN MM IN MM IN MM
74.5
74.5
74.5
74.5
74.5
74.5
1890 1890 1890 1890 1890 1890
36.5
36.5
36.0
38.0
38.0
37.5
925 925 915 965 965 955
C
33.5
41.5
41.5
33.5
41.5
41.5
48HC500030 A
850 1055 1055
850 1055 1055
in the basepan. Seals around duct openings must be tight. Se­cure with screws as shown in Fig. 12. Cover seams with foil duct tape.
Field-supplied flanges should be attached to horizontal duct openings and all ductwork should be secured to the flanges. In­sulate and weatherproof all external ductwork, joints, and roof or building openings with counter flashing and mastic in accor­dance with applicable codes.
Do not cover or obscure visibility to the unit’s informative data plate when insulating horizontal ductwork.
12
Page 13
packaged together, attached to a metal support tray using
REMOVABLE HORIZONTAL SUPPLY DUCT OPENING COVER
REMOVABLE HORIZONTAL RETURN DUCT OPENING COVER
SCREWS
DUCT COVERS SHEET METAL FACE UP
BASEPAN
plastic stretch wrap, and shipped in the return-air compart­ment behind the indoor coil access panel. The hood assem­bly’s metal tray is attached to the basepan and also attached to the damper using two plastic tie-wraps.
2. To gain access to the hood, remove the filter access panel. (See Fig. 13.)
FILTER ACCESS PANEL
Fig. 10 — Horizontal Conversion Panels
NOTCHES
BASEPAN
NOTCHES
Fig. 11 — Location of Notches
COMPRESSOR ACCESS PANEL
OUTDOOR-AIR OPENING AND INDOOR COIL ACCESS PANEL
Fig. 13 — Typical Access Panel Locations
3. Locate the 2 screws holding the metal tray to the basepan and remove. Locate and cut the 2 plastic tie-wraps securing the assembly to the damper. (See Fig. 14.) Be careful to not damage any wiring or cut tie-wraps securing any wiring.
Hood Parts
Plastic Tie Wrap Qty (2)
Screws for Metal Tray Qty (2)
Fig. 12 — Horizontal Duct Panels In Place

Step 8 — Install Outside Air Hood

ECONOMIZER HOOD PACKAGE REMOVAL AND SETUP - FACTORY OPTION

1. The hood is shipped in knock-down form and must be field-assembled. The indoor coil access panel is used as the hood top while the hood sides, divider and filter are
Fig. 14 — Economizer Hood Parts Location
4. Carefully lift the hood assembly (with metal tray) through the filter access opening and assemble per the steps out­lined in Economizer Hood, below.
ECONOMIZER HOOD NOTE: If the power exhaust accessory is to be installed on the
unit, the hood shipped with the unit will not be used and must be discarded. Save the aluminum filter for use in the power exhaust hood assembly.
1. The indoor coil access panel will be used as the top of the hood. Remove the screws along the sides and bottom of the indoor coil access panel. See Fig. 15.
13
Page 14
TOP PANEL
INDOOR COIL ACCESS PANEL
INDOOR COIL ACCESS PANEL
CAULK HERE
TOP PANEL
B
TOP PANEL
INDOOR COIL ACCESS PANEL
19 1/16”
SCREW
HOOD DIVIDER
LEFT HOOD SIDE
33 3/8”
(848mm)
(483mm)
DIVIDER
BAROMETRIC RELIEF
CLEANABLE ALUMINUM FILTER
FILTER
HOOD
FILTER CLIP
OUTSIDE AIR
BLOWER ACCESS PANEL
Fig. 15 — Indoor Coil Access Panel Relocation
2. Swing out indoor coil access panel and insert the hood sides under the panel (hood top). Use the screws provided to attach the hood sides to the hood top. Use screws pro­vided to attach the hood sides to the unit. See Fig. 16.
Fig. 16 — Economizer Hood Construction
3. Remove the shipping tape holding the economizer baro­metric relief damper in place (economizer only).
4. Insert the hood divider between the hood sides. See Fig. 16 and Fig. 17. Secure hood divider with 2 screws on each hood side. The hood divider is also used as the bot­tom filter rack for the aluminum filter.
5. Open the filter clips which are located underneath the hood top. Insert the aluminum filter into the bottom filter rack (hood divider). Push the filter into position past the open filter clips. Close the filter clips to lock the filter into place. See Fig. 17.
6. Caulk the ends of the joint between the unit top panel and the hood top.
7. Replace the filter access panel.
Fig. 17 — Economizer Filter Installation

Step 9 — Units with Hinged Panels Only

Relocate latch shipped inside the hinged compressor door to location shown in Fig. 18 after unit installation. If the unit does not have hinged panels, skip Step 9 and continue at Step 10.
Fig. 18 — Compressor Door Latch Location

Step 10 — Install Flue Hood

Flue hood is shipped screwed to the basepan beside the burner compartment access panel. Remove from shipping location and using screws provided, install flue hood and screen in location shown in Fig. 19.
Fig. 19 — Flue Hood Details

Step 11 — Install Gas Piping

Installation of the gas piping must be in accordance with local building codes and with applicable national codes. In U.S.A., refer to NFPA 54/ANSI Z223.1 National Fuel Gas Code (NF­GC). In Canada, installation must be in accordance with the CAN/CSA B149.1 and CAN/CSA B149.2 installation codes for gas burning appliances.
14
Page 15
This unit is factory-equipped for use with natural gas (NG) fuel at elevations up to 2000 ft (610 m) above sea level. Unit may be field converted for operation at elevations above 2000 ft (610 m) and/or for use with liquefied petroleum fuel. See ac­cessory kit installation instructions regarding these accessories.
NOTE: Furnace gas input rate on rating plate is for installation up to 2000 ft (610 m) above sea level. In U.S.A. the input rating for altitudes above 2000 ft (610 m) must be derated by 4% for each 1000 ft (305 m) above sea level. In Canada the input rating must be derated by 10% for altitudes of 2000 ft (610 m) to 4500 ft (1372 m) above sea level.
For natural gas applications, gas pressure at unit gas connec­tion must not be less than 4 in. wg (996 Pa) or greater than 13 in. wg (3240 Pa) while the unit is operating. On 48LCF/N/ T*05-06 (high-heat) units, the gas pressure at unit gas connec­tion must not be less than 5 in. wg (1245 Pa) or greater than 13 in. wg (3240 Pa) while the unit is operating. For liquified petroleum applications, the gas pressure must not be less than 11 in. wg (2740 Pa) or greater than 13.0 in. wg (3240 Pa) at the unit connection. See Tables 3 and 4.
Table 3 — Natural Gas Supply Line Pressure Ranges
UNIT MODEL
48LCD/E/L/M/S/R 04, 05, 06
48LCF/N/T
(High Heat units
only)
UNIT
SIZE
05, 06
MIN MAX
4.0 in. wg (996 Pa)
5.0 in. wg (1245 Pa)
13.0 in. wg (3240 Pa)
13.0 in. wg (3240 Pa)
CAUTION
EQUIPMENT DAMAGE Failure to follow this caution may result in equipment damage. When connecting the gas line to the unit gas valve, the in-
staller MUST use a backup wrench to prevent damage to the valve.
Install a gas supply line that runs to the unit heating section. Refer to the NFPA 54/NFGC or equivalent code for gas pipe sizing data. Do not use a pipe size smaller than gas supply line to allow for a maximum pressure drop of
0.5 in. wg (124 Pa) between gas regulator source and unit gas valve connection when unit is operating at high-fire flow rate.
The gas supply line can approach the unit in three ways: hori­zontally from outside the unit (across the roof), thru-curb/under unit basepan (accessory kit required) or through unit basepan (factory-option or accessory kit required). Consult accessory kit installation instructions for details on these installation methods. Observe clearance to gas line components per Fig. 20.
X
9” MINIMUM CLEARANCE FOR PANEL REMOVAL
MANUAL GAS
BASE UNIT
SHUTOFF VALVE
1
GAS REGULATOR
*
/2-in. Size the
*
Table 4 — Liquid Propane Supply Line Pressure
Ranges
UNIT MODEL UNIT SIZE MIN MAX
48LCD/E/S/R 04, 05, 06
48LCF/T
(High Heat units only)
05, 06
11.0 in. wg (2740 Pa)
11.0 in. wg (2740 Pa)
13.0 in. wg (3240 Pa)
13.0 in. wg (3240 Pa)
The gas supply pipe enters the unit at the burner access panel on the front side of the unit, through the long slot at the bottom of the access panel. The gas connection to the unit is made to
1
the
/2-in. FPT gas inlet port on the unit gas valve.
Manifold pressure is factory-adjusted for NG fuel use. Adjust as required to obtain best flame characteristics. See Table 5.
Table 5 — Natural Gas Manifold Pressure Ranges
UNIT MODEL UNIT SIZE HIGH FIRE LOW FIRE
48LCD/E/L/M/S/R 04, 05, 06
48LCF/N/T
(High Heat units only)
05, 06
3.5 in. wg (872 Pa)
3.5 in. wg (872 Pa)
1.7 in. wg (423 Pa)
1.7 in. wg (423 Pa)
Manifold pressure for liquid propane (LP) fuel use must be ad­justed to specified range. Follow instructions in the accessory kit to make initial readjustment. See Table 6.
Table 6 — Liquid Propane Manifold Pressure Ranges
UNIT MODEL UNIT SIZE HIGH FIRE LOW FIRE
48LCD/E/S/R 04, 05, 06
48LCF/T
(High Heat units only)
05, 06
10.0 in. wg (2490 Pa)
10.0 in. wg (2490 Pa)
5.0 in. wg (1245 Pa)
5.0 in. wg (1245 Pa)
48” MINIMUM
DRIP LEG
BASE RAIL
FROM GAS METER
STEEL PIPE
NOMINAL DIAMETER
1
1
(in.)
1
3
/
4
/
or larger
4
PER NFGC
ROOF CURB
NFGC – National Fuel Gas Code
Field supplied.
*
NOTE: Follow all local codes.
/
2
or 1
LEGEND
*
FIELD-FABRICATED SUPPORT
SPACINGOFSUPPORTS
X DIMENSION
(ft)
10
*
6 8
Fig. 20 — Gas Piping Guide (with Accessory
Thru-the-Curb Service Connections)

FACTORY-OPTION THRU-BASE CONNECTIONS (GAS CONNECTIONS)

This service connection kit consists of a er fitting (brass), two
3
a
/4-in. electrical bulkhead connector, all factory-installed in
1
/2-in. electrical bulkhead connectors and
1
/2-in. NPT gas adapt-
the embossed (raised) section of the unit basepan in the con­denser section.
15
Page 16
Fig. 21 — Fittings
LOW VOLTAGE CONDUIT CONNECTOR
HIGH VOLTAGE CONDUIT CONNECTOR
BRASS FITTING FOR 3 TO 6 TON UNITS
AUXILIARY POWER SUPPLY (OPTIONAL)
9 (229mm) MIN
UNION
SHUT OFF
VALV E
DRIP LEG
THRU-CURB ADAPTER
UNIT BASE RAIL
SHUT OFF
VALV E
UNION
9” (229 mm) MIN
UNIT BASE RAIL
BURNER ACCESS PAN EL
THRU-CURB ADAPTER
DRIP LEG
The thru-base gas connector has male and female threads. The male threads protrude above the basepan of the unit; the female threads protrude below the basepan.
Check tightness of connector lock nuts before connecting gas piping.
Install a Attach a
1
/2-in. NPT street elbow on the thru-base gas fitting.
1
/2-in. pipe nipple with minimum length of 16-in. (406 mm) (field-supplied) to the street elbow and extend it through the access panel at the gas support bracket. See Fig. 22.
does not block access to the unit’s main control box or limit the required working space in front of the control box.
Fig. 23 — Gas Piping
EMBOSSMENT
Fig. 22 — Gas Line Piping for 3 to 5 Ton Units Only
Other hardware required to complete the installation of the gas supply line will include a manual shutoff valve, a sediment trap (drip leg) and a ground-joint union. A pressure regulator valve may also be required (to convert gas pressure from pounds to inches of pressure). The manual shutoff valve must be located within 6 ft (1.83 m) of the unit. The union, located in the final leg entering the unit, must be located at least 9-in. (230 mm) away from the access panel to permit the panel to be removed for service. If a regulator valve is installed, it must be located a minimum of 4 ft (1220 mm) away from the unit’s flue outlet. Some municipal codes require that the manual shutoff valve be located upstream of the sediment trap. See Fig. 23 and 24 for typical piping arrangements for gas piping that has been routed through the sidewall of the curb. See Fig. 25 for typical piping arrangement when thru-base is used. Ensure that all piping
BRASS FITTING FOR GAS PIPING
SUPPORT BRACKET
Fig. 24 — Gas Piping
Fig. 25 — Gas Piping Thru-Base Connections
16
Page 17
When installing the gas supply line, observe local codes per-
BURNER
ORIFICE
NOTE: Trap should be deep enough to offset maximum unit static difference. A 4” (102) trap is recommended.
MINIMUM PITCH 1” (25mm) PER 10’ (3m) OF LINE
BASE RAIL
OPEN VENT
TO ROOF DRAIN
DRAIN PLUG
ROOF CURB
SEE NOTE
2˝ (51) MIN
taining to gas pipe installations. Refer to the NFPA 54/ANSI Z223.1 NFGC latest edition (in Canada, CAN/CSA B149.1). In the absence of local building codes, adhere to the following pertinent recommendations:
1. Avoid low spots in long runs of pipe. Grade all pipe
1
/4-in. in every 15 ft (7 mm in every 5 m) to prevent traps. Grade all horizontal runs downward to risers. Use risers to connect to heating section and to meter.
2. Protect all segments of piping system against physical and thermal damage. Support all piping with appropriate straps, hangers, etc. Use a minimum of one hanger every 6 ft (1.8 m). For pipe sizes larger than
1
/2-in., follow rec-
ommendations of national codes.
3. Apply joint compound (pipe dope) sparingly and only to male threads of joint when making pipe connections. Use only pipe dope that is resistant to action of liquefied petro­leum gases as specified by local and/or national codes. If using PTFE (Teflon
1
) tape, ensure the material is Double Density type and is labeled for use on gas lines. Apply tape per manufacturer’s instructions.
4. Pressure-test all gas piping in accordance with local and national plumbing and gas codes before connecting piping to unit.
NOTE: Pressure-test the gas supply system after the gas supply piping is connected to the gas valve. The supply piping must be disconnected from the gas valve during the testing of the piping systems when test pressure is in excess of 0.5 psig (3450 Pa). Pressure-test the gas supply piping system at pressures equal to or less than 0.5 psig (3450 Pa). The unit heating section must be isolated from the gas piping system by closing the external main manual-shutoff valve and slightly opening the ground-joint union.
Check for gas leaks at the field-installed and factory-installed gas lines after all piping connections have been completed. Use soap-and-water solution (or method specified by local codes and/or regulations).
Fig. 26 — Orifice Hole

Step 12 — Install External Condensate Trap and Line

The unit has one 3/4-in. condensate drain connection on the end of the condensate pan and an alternate connection on the bot­tom. See Fig. 27. Unit airflow configuration does not deter­mine which drain connection to use. Either drain connection can be used with vertical or horizontal applications.
To use the alternate bottom drain connection, remove the red drain plug from the bottom connection (use a et drive extension) and install it in the side drain connection.
The piping for the condensate drain and external trap can be completed after the unit is in place. See Fig. 28.
1
/2-in. square sock-
WARNING
Failure to follow this warning could result in personal inju­ry, death and/or property damage.
Connect gas pipe to unit using a backup wrench to avoid damaging gas controls.
Never purge a gas line into a combustion chamber.
Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections.
Use proper length of pipe to avoid stress on gas control manifold.
NOTE: If orifice hole appears damaged or it is suspected to have been re-drilled, check orifice hole with a numbered drill bit of cor­rect size. Never re-drill an orifice. A burr-free and squarely aligned orifice hole is essential for proper flame characteristics. See Fig. 26.
1. Teflon is a registered trademark of DuPont.
CONDENSATE PAN (SIDE VIEW)
STANDARD SIDE DRAIN
DRAIN
PLUG
(FACTORY-INSTALLED)
Fig. 27 — Condensate Drain Pan (Side View)
Fig. 28 — Condensate Drain Piping Details
ALTERNATE BOTTOM DRAIN
17
Page 18
All units must have an external trap for condensate drainage.
Disconnect
per
NEC
13
L1 L2 L3
IFTB
C
208/230-3-60
460-3-60 575-3-60
Units Without Disconnect or HACR Option
Units With Disconnect or HACR Option
L1
L2
L3
2
4
6
1
5
Optional
Disconnect
Switch
Factory Wiring
3
Ground
(GR)
Equip
GR Lug
Equip GR Lug
Ground
(GR)
3 Phase On ly 3 Phase Only
Install a trap at least 4-in. (102 mm) deep and protect against freeze-up. If drain line is installed downstream from the exter­nal trap, pitch the line away from the unit at 1-in. per 10 ft (25 mm in 3 m) of run. Do not use a pipe size smaller than the unit connection (
3
/4-in.).

Step 13 — Make Electrical Connections

WARNING
Failure to follow this warning could result in personal inju­ry or death.
Do not use gas piping as an electrical ground. Unit cabinet must have an uninterrupted, unbroken electri-
cal ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control com­partment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code); ANSI/NFPA 70, latest edition (in Canada, Canadian Electrical Code CSA [Canadian Standards Association] C22.1), and local electrical codes.
NOTE: Field-supplied wiring shall conform with the limitations of minimum 63°F (33°C) rise.

FIELD POWER SUPPLY

If equipped with optional powered convenience outlet
The power source leads to the convenience outlet’s transformer primary are not factory connected. Installer must connect these leads according to required operation of the convenience out­let. If an always-energized convenience outlet operation is de­sired, connect the source leads to the line side of the unit­mounted disconnect. (Check with local codes to ensure this method is acceptable in your area.) If a de-energize via unit disconnect switch operation of the convenience outlet is de­sired, connect the source leads to the load side of the unit dis­connect. On a unit without a unit-mounted disconnect, connect the source leads to compressor contactor C and indoor fan ter­minal block (IFTB) pressure lugs with unit field power leads.
Refer to Fig. 41 for power transformer connections and the dis­cussion on connecting the convenience outlet on page 25.
Field power wires are connected to the unit at line-side pressure lugs on compressor contactor C and indoor fan terminal block (IFTB) (see wiring diagram label for control box component ar­rangement) or at factory-installed option non-fused disconnect switch or HACR. Max wire size is #2ga AWG (copper only) per pole on contactors. #2ga AWG per pole on optional disconnect or HACR and 4/0 AWG per pole on terminal or fuse block on units with single point box. See Fig. 29 and unit label diagram for field power wiring connections. See Fig. 30-33 for typical wiring diagrams.
Fig. 29 — Power Wiring Connections
18
Page 19
Fig. 30 — 48LC Control Wiring Diagram
19
Page 20
Fig. 31 — 48LC Control Wiring Diagram with Humidi-MiZer
20
®
System
Page 21
Fig. 32 — 48LC Power Wiring Diagram, 208/230-v, 460-v 3 Phase
21
Page 22
Fig. 33 — 48LC Power Wiring Diagram, 575-v 3 Phase
22
Page 23
COPPER
WIRE ONLY
ELECTRIC
DISCONNECT
SWITCH
ALUMINUM
WIRE
WARNING
FIRE HAZARD Failure to follow this warning could result in personal inju-
ry, death, or property damage. Do not connect aluminum wire between disconnect switch
and unit. Use only copper wire.
Fig. 34 — Disconnect Switch and Unit
UNITS WITH FACTORY-INSTALLED NON-FUSED DIS­CONNECT OR HACR
The factory-installed optional non-fused disconnect (NFD) or HACR switch is located in a weatherproof enclosure located under the main control box. The manual switch handle and shaft is shipped in the disconnect or HACR enclosure. Assem­ble the shaft and handle to the switch at this point.

TO FIELD-INSTALL THE NFD SHAFT AND HANDLE:

1. Remove the control box access panel. The NFD enclosure is located below the control box (see Fig. 35)
2. Remove (3) cap head screws that secure the NFD enclo­sure front cover – (2) on the face of the cover and (1) on the left side cover. See Fig. 36.
3. Remove the front cover of the NFD enclosure.
4. Make sure the NFD shipped from the factory is at OFF position (the arrow on the black handle knob is at OFF).
5. Insert the shaft with the cross pin on the top of the shaft in the horizontal position.
6. Measure from the tip of the shaft to the top surface of the black pointer; the measurement should be 3.75-in. to
3.88-in. (95 mm to 99 mm).
7. Tighten the locking screw to secure the shaft to the NFD.
8. Turn the handle to the OFF position with red arrow point­ing at OFF.
9. Install the handle on to the painted cover horizontally with the red arrow pointing to the left.
10. Secure the handle to the painted cover with (2) screws and lock washers supplied.
11. Engaging the shaft into the handle socket, re-install (3) cap head screws on the front cover.
Re-install the unit front panel.
Fig. 35 — Location of Non-Fused Disconnect
Enclosure
Fig. 36 — Handle and Shaft Assembly for NFD

TO FIELD-INSTALL THE HACR SHAFT AND HANDLE:

1. Remove the control box access panel. The HACR enclo­sure is located below the control box (see Fig. 37).
2. Remove (3) cap head screws that secure the HACR enclo­sure – (2) on the face of the cover and (1) on the left side cover. See Fig. 38.
3. Remove the front cover of the HACR enclosure.
4. Make sure the HACR shipped from the factory is at OFF position (the white arrow pointing at OFF).
5. Insert the shaft all the way with the cross pin on the top of the shaft in the horizontal position.
6. Tighten the locking screw to secure the shaft to the HACR.
7. Turn the handle to the OFF position with red arrow point­ing at OFF.
8. Install the handle on to the painted cover horizontally with the red arrow pointing to the left.
9. Secure the handle to the painted cover with (2) screws and lock washers supplied.
10. Engaging the shaft into the handle socket, re-install (3) cap head screws on the front cover.
Re-install the unit front panel.
23
Page 24
Fig. 37 — Location of HACR Enclosure
Convenience
Outlet GFCI
Pwd-CO
Fuse
Switch
Pwd-CO
Tr ansformer
Control Box
Access Panel
ALL UNITS All field wiring must comply with NEC and all local codes.
Size wire based on MCA (Minimum Circuit Amps) on the unit informative plate. See Fig. 29 and the unit label diagram for power wiring connections to the unit power terminal blocks and equipment ground. Maximum wire size is #2ga AWG per pole on contactors. #2ga AWG per pole on optional disconnect or HACR. See Fig. 29 and unit label diagram for field power wiring connections.
Provide a ground-fault and short-circuit over-current protection device (fuse or breaker) per NEC Article 440 (or local codes). Refer to unit informative data plate for MOCP (Maximum Over-Current Protection) device size.
NOTE: Units ordered with factory installed HACR do not need an additional ground-fault and short-circuit over-current protective device unless required by local codes.
All field wiring must comply with the NEC and local requirements.
All units except 208/230-v units are factory-wired for the volt­age shown on the nameplate. If the 208/230-v unit is to be con­nected to a 208-v power supply, the control transformer must be rewired by moving the black wire with the spade connector from the 230-v connection and moving it to the 200-v
1
/4-in. male terminal on the primary side of the trans-
1
/4-in. female
former. Refer to unit label diagram for additional information. NOTE: Check all factory and field electrical connections for
tightness.

CONVENIENCE OUTLETS

Fig. 38 — Handle and Shaft Assembly for HACR

UNITS WITHOUT FACTORY-INSTALLED NON-FUSED DISCONNECT OR HACR

When installing units, provide a disconnect switch per NEC (National Electrical Code) of adequate size. Disconnect sizing data is provided on the unit informative plate. Locate discon­nect sizing data on unit cabinet or within sight of the unit per national or local codes. Do not cover unit informative plate if mounting the disconnect on the unit cabinet.
WARNING
ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal inju-
ry or death. Units with convenience outlet circuits may use multiple
disconnects. Check convenience outlet for power status be­fore opening unit for service. Locate its disconnect switch, if appropriate, and open it. Lock-out and tag-out this switch, if necessary.
Two types of convenience outlets are offered: non-powered and unit-powered. Both types provide a 125-v GFCI (ground­fault circuit-interrupter) duplex receptacle rated at 15-A behind a hinged waterproof access cover, located on the end panel of the unit. See Fig. 39.
Fig. 39 — Convenience Outlet Location
24
Page 25
Installing Weatherproof Cover:
TOP
TOP
TOP
WET LOCATIONS
WET LOCAT IONS
COVER - WHILE-IN-USE
WEATHERPROOF
BASEPLATE FOR
GFCI RECEPTACLE
GASKET
GFCI RECEPTACLE
NOT INCLUDED
A weatherproof while-in-use cover for the factory-installed convenience outlets is now required by UL standards. This cover cannot be factory-mounted due to its depth; it must be in­stalled at unit installation. For shipment, the convenience outlet is covered with a blank cover plate.
The weatherproof cover kit is shipped in the unit’s control box. The kit includes the hinged cover, a backing plate, and gasket.
DISCONNECT ALL POWER TO UNIT AND CONVE­NIENCE OUTLET. LOCK-OUT AND TAG-OUT ALL POWER.
Remove the blank cover plate at the convenience outlet; dis­card the blank cover.
Loosen the two screws at the GFCI duplex outlet, until approx­imately
1
/2-in. (13 mm) under screw heads are exposed. Press the gasket over the screw heads. Slip the backing plate over the screw heads at the keyhole slots and align with the gasket; tighten the two screws until snug (do not over-tighten).
Mount the weatherproof cover to the backing plate as shown in Fig. 40. Remove two slot fillers in the bottom of the cover to permit service tool cords to exit the cover. Check for full clos­ing and latching.
UNIT
VOLTAGE
208, 230 240
460 480
575 600
CONNECT
AS
PRIMARY
CONNECTIONS
L1: RED +YEL L2: BLU + GRA
L1: RED Splice BLU + YEL L2: GRA
L1: RED L2: GRA
TRANSFORMER
TERMINALS
H1 + H3 H2 + H4
H1
H2 + H3
H4 H1
H2
Fig. 41 — Powered Convenience Outlet Wiring
Using unit-mounted convenience outlets:
Units with unit-mounted convenience outlet circuits will often require that two disconnects be opened to de-energize all pow­er to the unit. Treat all units as electrically energized until the convenience outlet power is also checked and de-energization is confirmed. Observe National Electrical Code Article 210, Branch Circuits, for use of convenience outlets.
Fuse on power type:
The factory fuse is a Bussman
1
“Fusetron” T-15, non-renew-
able screw-in (Edison base) type plug fuse.
Non-powered type:
This type requires the field installation of a general-purpose 125-v 15-A circuit powered from a source elsewhere in the building. Observe national and local codes when selecting wire size, fuse, or breaker requirements and disconnect switch size and location. Route 125-v power supply conductors into the bottom of the utility box containing the duplex receptacle.
Unit-powered type:
A unit-mounted transformer is factory-installed to stepdown the main power supply voltage to the unit to 115-v at the du­plex receptacle. This option also includes a manual switch with fuse, located in a utility box and mounted on a bracket behind the convenience outlet; access is through the unit’s control box access panel. See Fig. 36.
The primary leads to the convenience outlet transformer are not factory-connected. Selection of primary power source is a customer option. If local codes permit, the transformer primary leads can be connected at the line-side terminals on the unit­mounted non-fused disconnect or HACR breaker switch; this will provide service power to the unit when the unit disconnect switch or HACR switch is open. Other connection methods will result in the convenience outlet circuit being de-energized when the unit disconnect or HACR switch is open. See Fig. 41.
Fig. 40 — Weatherproof Cover Installation
Fig. 42 — Convenience Outlet Utilization Notice Label
Duty Cycle:
The unit-powered convenience outlet has a duty cycle limita­tion. The transformer is intended to provide power on an inter­mittent basis for service tools, lamps, etc; it is not intended to provide 15 amps loading for continuous duty loads (such as electric heaters for overnight use). Observe a 50% limit on cir­cuit loading above 8 amps.
Convenience outlet usage rating:
Continuous usage: 8 amps maximum Test the GFCI receptacle by pressing the TEST button on the
face of the receptacle to trip and open the receptacle. Check for proper grounding wires and power line phasing if the GFCI
1. Bussman and Fusetron are trademarks of Cooper Technologies Company.
25
Page 26
receptacle does not trip as required. Press the RESET button to clear the tripped condition.
HACR The amp rating of the HACR factory-installed option is based
on the size, voltage, indoor motor, and other electrical options of the unit as shipped from the factory. If field-installed acces­sories are added or changed in the field (i.e. electric heat, pow­er exhaust, ERV), the HACR may no longer be of the proper amp rating and therefore will need to be removed from the unit. See unit nameplate and label on factory-installed HACR for the amp rating of the HACR that was shipped with the unit from the factory. See unit nameplates for the proper fuse, HACR, or maximum over-current protection device required on the unit with field-installed accessories. See Fig. 43.
and the current within 10%. Use the following formula to de­termine the percent of voltage imbalance. Operation on im­proper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Carrier warranty.
% Voltage Imbalance:
= 100 x
Example: Supply voltage is 230-3-60
Average Voltage =
Determine maximum deviation from average voltage. (AB) 227-224 = 3 v (BC) 231-227 = 4 v (AC) 227-226 = 1 v Maximum deviation is 4 v. Determine percent of voltage imbalance.
max voltage deviation from average voltage
average voltage
ABC
MOTOR
AB = 224 v BC = 231 v AC = 226 v
(224 + 231 + 226)
33
681
=
= 227
Fig. 43 — HACR Caution Label
FACTORY-OPTION THRU-BASE CONNECTIONS (ELEC­TRICAL CONNECTIONS)
This service connection kit consists of a er fitting (brass), a
3
/4-in. electrical bulkhead connector, all factory-installed in the embossed (raised) section of the unit basepan in the condenser section. The
1
/2-in. electrical bulkhead connector and a
3
/4-in. bulkhead connector enables the low-voltage
control wires to pass through the basepan. The
1
/2-in. NPT gas adapt-
1
/2-in. electrical bulkhead connector allows the high-voltage power wires to pass through the basepan. See Fig. 21.
Check tightness of connector lock nuts before connecting elec­trical conduits.
Field-supplied and field-installed liquid-tight conduit connec­tors and conduit may be attached to the connectors on the base­pan. Pull correctly-rated high voltage and low voltage through appropriate conduits. Connect the power conduit to the internal disconnect (if unit is so equipped) or to the external disconnect (through unit side panel). A hole must be field-cut in the main control box bottom on the left side so the 24-v control connec­tions can be made. Connect the control power conduit to the unit control box at this hole.

UNITS WITHOUT THRU-BASE CONNECTIONS

1. Install power wiring conduit through side panel openings.
Install conduit between disconnect and control box.
2. Install power lines to terminal connections as shown in
Fig. 29.
Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate. On 3-phase units, voltages between phases must be balanced within 2%
% Voltage Imbalance =100x
This amount of phase imbalance is satisfactory as it is below the maxi­mum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
NOTE: Check all factory and field electrical connections for tightness.
4
227
= 1.78%
FIELD CONTROL WIRING The 48LC unit requires an external-temperature control device.
This device can be a thermostat (field-supplied) or, the RTU Open Controller for Building Management Systems using non­CCN protocols (RTU Open is available as a factory-installed option only), or a space temperature sensor (SPT) with factory installed SystemVu™ controller.
THERMOSTAT Install a Carrier-approved accessory thermostat according to
installation instructions included with the accessory. For com­plete economizer function and two-stage compressor opera­tion, select a two-stage cooling thermostat. Locate the thermo­stat accessory on a solid wall in the conditioned space to sense average temperature in accordance with the thermostat installa­tion instructions.
If the thermostat contains a logic circuit requiring 24-v power, use a thermostat cable or equivalent single leads of different colors with minimum of seven leads. If the thermostat does not require a 24-v source (no “C” connection required), use a ther­mostat cable or equivalent with minimum of six leads. Check the thermostat installation instructions for additional features which might require additional conductors in the cable.
For wire runs up to 50 ft. (15 m), use no. 18 AWG (American Wire Gage) insulated wire [35°C (95°F) minimum]. For 50 to 75 ft. (15 to 23 m), use no. 16 AWG insulated wire [35°C (95°F) minimum]. For over 75 ft. (23 m), use no. 14 AWG in­sulated wire [35°C (95°F) minimum]. All wire sizes larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat. See Fig. 44.
26
Page 27

UNIT WITHOUT THRU-BASE CONNECTION KIT

X
C
G
W2
C
W2
G
W1
O/B/Y2
Y2
R
W1
R
Y1
Y1
T H E R M O
S
T A T
(Note 1) (Note 2)
Note 1: Typical multi-function marking. Follow manufacturer’s conguration
Instructions to select Y2.
Note 2: Y2 to Y2 connection required for 2 stage cooling operation and when
integrated economizer function is desired.
Field Wiring
Central
Terminal
Board
Typical
Thermostat
Connections
RACEWAY
HOLE IN END PANEL (HIDDEN)
Pass the thermostat control wires through the hole provided in the corner post; then feed the wires through the raceway built into the corner post to the control box. Pull the wires over to the terminal strip on the upper-left corner of the Controls Con­nection Board. See Fig. 45.
Fig. 44 — Low-Voltage Connections
NOTE: If thru-the-bottom connections accessory is used, refer to the accessory installation instructions for information on routing power and control wiring.
HEAT ANTICIPATOR SETTINGS Set heat anticipator settings at 0.14 amp for the first stage and
0.14 amp for second-stage heating, when available.

Humidi-MiZer® Control Connections

NOTE: It is recommended the Auto-Changeover function of an installed thermostat be enabled when used in conjunction with the Humidi-MiZer Adaptive Dehumidification system.
HUMIDI-MIZER – SPACE RH CONTROLLER The Humidi-MiZer dehumidification system requires a field-
supplied and field-installed space-relative humidity control de­vice. This device may be a separate humidistat control (contact closes on rise in space RH above control setpoint) or a combi­nation thermostat-humidistat control device such as Carrier’s
®
Edge
Pro Thermidistat with isolated contact set for dehumidi­fication control. The humidistat is normally used in applica­tions where a temperature control is already provided (units with SystemVu™ controls).
To connect the Carrier humidistat (HL38MG029):
1. Route the humidistat 2-conductor cable (field-supplied)
through the hole provided in the unit corner post.
2. Feed wires through the raceway built into the corner post
(see Fig. 45) to the 24-v barrier located on the left side of the control box. The raceway provides the UL-required clearance between high-voltage and low-voltage wiring.
3. Use wire nuts to connect humidistat cable to the leads in
the low-voltage wiring (as shown in Fig. 48), connecting PKN to PNK and PNK/BLK to PNK/BLK.
To connect the Thermidistat device (33CS2PPRH-03):
1. Route the Thermidistat multi-conductor thermostat cable
(field-supplied) through the hole provided in the unit cor­ner post.
2. Feed wires through the raceway built into the corner post
(see Fig. 45) to the 24-v barrier located on the left side of the control box. The raceway provides the UL-required clearance between high-voltage and low-voltage wiring.
3. The Thermidistat has dry contacts at terminals D1 and D2
for dehumidification operation (see Fig. 52). The dry con­tacts must be wired between CTB terminal R and the PNK/ BLK lead to the LTLO switch with field-supplied wire nuts. Refer to the installation instructions included with the Car­rier Edge Thermidistat device for more information.
Fig. 45 — Field Control Raceway
27
Page 28
%RELATIVEHUMIDITY
®
Fig. 46 — Accessory Field-Installed Humidistat
Fig. 47 — Edge
®
Pro Thermidistat
®
Fig. 48 — Typical Humidi-MiZer
Adaptive Dehumidification System Humidistat Wiring
Table 7 — Control Modes with Humidi-MiZer System
Output and Valve States versus Circuit Mode
DEMAND AND MODE OUTPUTS 48LC 04-06 VALVES
Space
Humidity
No power Off Off Off Off (Open) Off (Open) Off (Closed) Low No Off Off Off Off Off (Open) On (Closed) Off (Closed) Low Yes Cool On Off Off Off (Open) On (Closed) Off (Closed)
High Yes Reheat 1 On On Off On (Closed) Off (Open) Off (Closed) High No Reheat 2 On On On On (Closed) Off (Open) On (Open)
Circuit
Cooling
Demand
Circuit Mode
Circuit
Compressor
Cooling
Reheat
Control
28
Reheat 2
Valve
CLV RLV RDV
Page 29
REHEAT MODES Dehumidification (reheat) is a cooling mode function. Refer to
Cooling Operation for cooling mode control. With Humidi­MiZer units, there are three additional HVAC Mode (HVAC) expanded texts available for the user: Reheat1, Reheat2, and Reheat1/Reheat2. Selection of the reheat mode for each refrig­erant circuit is determined by the dehumidification demand and the cooling demand. Table 7 shows the corresponding circuit mode and output status for the different demand combinations. Units with multiple circuits can operate with a combination of Reheat1 and Reheat2 circuits, as determined by the amount of space cooling demand.
NOTE: Compressor staging control for Humidi-MiZer units re­quires that circuit A always operates when circuit B is on. This ap­plies to normal operation, service test, and for control alarm re­sponses. This operation difference is required due to the fact that the Motormaster outdoor fan control senses circuit A only. Opera­tion of the revised refrigerant circuit for each mode is described below.
Normal Cooling
For 48LC04-6 units, refrigerant flows from the outdoor con­denser through the normally open Cooling Liquid Valve (CLV)
to the expansion device. Reheat Liquid Valve (RLV) and Re­heat Discharge Valve (RDV) are closed. (See Fig. 49.)
Reheat 1 (Subcooling Mode)
This mode increases latent cooling and decreases sensible cooling compared to normal cooling.
For 48LC04-6 units, refrigerant flows from the outdoor con­denser, through the normally open Reheat Liquid Valve (RLV), and through the reheat condenser coil to the expansion device. Cooling Liquid Valve (CLV) and Reheat Discharge Valve (RDV) are closed. (See Fig. 50.)
Reheat 2 (Hot Gas ReheatMode)
This mode provides maximum latent cooling with little to no sensible capacity. This mode can operate to provide dehumidi­fication when there is no cooling demand. Similar to Reheat 1 mode, refrigerant flows from the outdoor condenser, through the normally open Reheat Liquid Valve (RLV1), or through the energized 3-way Liquid Diverter Valve (LDV), and through the reheat condenser coil to the expansion device. Reheat Dis­charge Valve (RDV) is open, which provides some compressor discharge gas to the reheat condenser to further increase the re­heat of the evaporator air stream (See Fig. 51).
RDV
VALV E
RLV
VALV E
CONDENSER COIL
OUTDOOR AIR
CLV
VALV E
COMPRESSOR
= CLOSED VALVE
= OPEN VALVE
HUMIDI-MIZER COIL
EVAPORATOR COIL
Fig. 49 — Normal Cooling Mode — Humidi-MiZer System
RDV
VALV E
CONDENSER COIL
RLV
VALV E
HUMIDI-MIZER COIL
INDOOR SUPPLY
AIR
EXPANSION
VALV E
(TXV)
INDOOR RETURN
AIR
INDOOR SUPPLY
AIR
OUTDOOR AIR
CLV
VALV E
COMPRESSOR
EVAPORATOR COIL
= CLOSED VALVE
= OPEN VALVE
INDOOR RETURN
AIR
Fig. 50 — Subcooling Mode (Reheat 1) — Humidi-MiZer System
29
EXPANSION
VALV E
(TXV)
Page 30
RDV
Rc
Rh
W1
G
Y2
C
O/W2/B
Y1
OAT RR
S
S
RTN
HUM
D1 D2 V+ Vg
X
*
C
G
W2
W1
Y2
Y1
R
Edge Programable Thermostat
Unit CTB
THERMOSTAT
*Connection not required.
Humidi-MiZer FIOP
VALV E
INDOOR SUPPLY
AIR
CONDENSER COIL
RLV
VALV E
OUTDOOR AIR
CLV
VALV E
COMPRESSOR
= CLOSED VALVE
= OPEN VALVE
HUMIDI-MIZER COIL
EXPANSION
VALV E
(TXV)
EVAPORATOR COIL
INDOOR RETURN
AIR
Fig. 51 — Hot Gas Reheat Mode (Reheat 2) — Humidi-MiZer System
Fig. 52 — Typical Rooftop Unit with Humidi-MiZer Adaptive Dehumidification System with Edge

EconoMi$er® X (Factory-Installed Option)

For details on operating 48LC units equipped with the factory­installed EconoMi$er X option, refer to EconoMi$er X Facto-
ry-Installed Option Low Leak Economizer for 2 Speed SAV™ (Staged Air Volume) Systems.

SystemVu™ Controller (Factory-Installed Option)

For details on operating 48LC units equipped with the factory­installed SystemVu control option, refer to 48/50LC 04-26 Sin-
gle Package Rooftop Units with SystemVu Controls Version 2.X Controls, Start-up, Operation and Troubleshooting manual.

RTU Open Control System

For details on operating 48LC**04-06 units equipped with the factory-installed RTU Open controller option, refer to the Fac-
Thermidistat Device
tory Installed Option RTU Open Multi-Protocol Controller Controls, Start-Up, Operation, Troubleshooting manual. See
Fig. 53 and 54.
30
®
Pro
Page 31
Fig. 53 — RTU Open System Control Wiring Diagram
31
Page 32
Fig. 54 — RTU Open System Control Wiring Diagram with Humidi-MiZer
32
®
System
Page 33

Smoke Detectors

RETURN AIR
SMOKE DETECTOR
(AS SHIPPED)
Smoke detectors are available as factory-installed options on 48LC models. Smoke detectors may be specified for supply-air only, for return-air without or with economizer, or in combina­tion of supply-air and return-air. All components necessary for operation are factory-provided and mounted. The unit is facto­ry-configured for immediate smoke detector shutdown opera­tion; additional wiring or modifications to unit terminal board may be necessary to complete the unit and smoke detector con­figuration to meet project requirements.
Units equipped with factory-optional return-air smoke detec­tors require a relocation of the sensor module at unit installa­tion. See Fig. 55 for the as-shipped location.
Completing Installation of Return Air Smoke Sensor:
1. Unscrew the two screws holding the return-air smoke detector assembly. See Fig. 56, Step 1. Save the screws.
2. Turn the assembly 90 degrees and then rotate end to end. Make sure that the elbow fitting is pointing down. See Fig. 56, Step 2.
3. Screw the sensor and detector plate into its operating posi­tion using screws from Step 1. See Fig. 56, Step 3.
4. Connect the flexible tube on the sampling inlet to the sam­pling tube on the basepan.
Additional Application Data
Refer to the application data document “Factory Installed Smoke Detectors for Small and Medium Rooftop Units 2 to 25 Tons” for discussions on additional control features of these smoke detectors, including multiple unit coordination.
Fig. 55 — Return-Air Smoke Detector, Shipping
Position
Step 1 Step 2 Step 3
Fig. 56 — Completing Installation of Return-Air Smoke Sensor
33
Page 34

Step 14 — Adjust Factory-Installed Options

Table 1
Table 2
BELT
CROSS
SECTION
SMALLEST
SHEAVE
DIAMETER
BELT DEFLECTION FORCE (LBS)
UNNOTCHED
BELTS
NOTCHED BELTS
USED NEW USED NEW
A, AX
3.0-3.6 3.7 5.5 4.1 6.1
3.8-4.8 4.5 6.8 5.0 7.4
5.0-7.0 5.4 8.0 5.7 8.4
B, BX
3.4-4.2 4.9 7.2
4.4-5.6 5.3 7.9 7.1 10.5
5.8-8.6 6.3 9.4 8.5 12.6
BELT CONDITION TENSION FORCE IN BELT (LBS)
New 100
Used 80
SMOKE DETECTORS Smoke detector(s) will be connected at the Central Terminal
Board (CTB), at terminals marked “Smoke Shutdown”. Re­move jumper JMP 3 when ready to energize unit.

Step 15 — Install Accessories

Available accessories include:
Curb
EconoMi$er
®
X (with control)
EconoMi$er2 (without control/for external signal)
Power Exhaust
Differential dry-bulb sensor (EconoMi$er2)
Outdoor enthalpy sensor
Differential enthalpy sensor
•CO
sensor
2
Louvered hail guard
Phase monitor control
Refer to separate installation instructions for information on in­stalling these accessories.

Step 16 — Check Belt Tension

Measure the belt span length as shown in Fig. 57. Calculate the re­quired deflection by multiplying the belt span length by example, if the belt span length is 32 inches:
1
32 x
/64 = 1/2-in. deflection.
BELT FORCE — DEFLECTION METHOD Check the belt tension with a spring-force belt force deflection
gage (available from drive belt manufacturer).
1. Place a straightedge along the belt between the two pul­leys. Measure the distance between the motor shaft and the blower shaft.
2. Set the tension gage to the desired tension (see Table 1 in Fig. 57). Place the large O-ring at that point.
3. Press the tension checker downward on the belt until the large O-ring is at the bottom of the straightedge.
4. Adjust the belt tension as needed.
Adjust belt tension by loosing the motor mounting plate front bolts and rear bolt (see Fig. 58) and slide the plate towards the fan (to reduce tension) or away from the fan (to increase tension). Ensure the blower shaft and motor shaft are parallel to each other (pulleys aligned). Tighten all bolts securely when finished.
1
/64. For
Fig. 57 — V-Belt Force Label
BELT TENSION METHOD Requires belt tension gage that measures tension in belt in units of
lbs force.
BLOWER PULLEY
V-B ELT
MOTOR PULLEY
MOTOR
MOUNTING
BOLTS (4)
MOTOR MOUNTING
PLATE
Fig. 58 — Belt Drive Motor Mounting

Pre-Start and Start-Up

This completes the mechanical installation of the unit. Refer to the unit’s Service Manual for detailed Pre-Start and Start-Up instructions. Download the latest versions from HVAC Part­ners (www.hvacpartners.com).
34
Page 35

APPENDIX A — VFD OPERATION WITH REMOTE KEYPAD

All 48LC size 04-06 units are equipped with a VFD (Variable Frequency Drive) to automatically adjust the indoor-fan motor speed in sequence with the unit’s ventilation, cooling and heat­ing operation. The VFD keypad is included as standard on electromechanical and RTU Open models. See Fig. B for loca­tion of the VFD and the VFD keypad in these units.
NOTE: SystemVu models do not include the VFD keypad as VFD control operation is accessed through the SystemVu controls.
The VFD keypad is shown in Fig. A. The function of SOFT KEYS 1 and 2 change depending on what is displayed on the screen. The function of SOFT KEY 1 matches the word in the lower left-hand box on the display screen. The function of SOFT KEY 2 matches the word in the lower right-hand box on the display screen. If the box is empty, then the SOFT KEY does not have a function on that specific screen. The UP and DOWN keys are used to navigate through the menus. The OFF key is used to turn off the VFD. The AUTO key is used to change control of the drive to automatic control. The HAND key is used to change control of the drive to local (hand held) control. The HELP button is used to access the help screens.
For the VFD to operate on the units covered by this document, the drive must be set in AUTO mode. The word “AUTO” will appear in the upper left hand corner of the VFD display. Press the AUTO button to set the drive in AUTO mode.
Fig. A — VFD Keypad
Use the RJ-45 (CAT5) cable (bundled with the Control Harness
- see Fig. B) to provide easier access for using the VFD Re­mote Keypad. The cable’s length is long enough to route it through to the unit’s control box, if desired.
To Connect the VFD Keypad using the RJ-45 Cable
1. Remove the Keypad from the front of the VFD.
2. Remove the RJ-45 adapter from the back of the Remote Keypad and insert the adapter into the RJ-45 port on the front of the VFD.
3. Separate the RJ-45 (CAT5) cable from the Control Harness.
4. Use the CAT5 cable to connect the Remote Keypad to the VFD.
START UP WITH ASSISTANT Initial start-up has been performed at the factory. Use of the
start up assistant will override factory VFD configurations. DO NOT USE THE START-UP ASSISTANT ON THESE LC UNITS!
35
Page 36
RJ-45 (CAT5) Cable (Bundled with Control Harness)
ABB VFD w/ Remote Keypad
Fig. B — Location of VFD in 48LC 04-06 Units
Start Up by Changing Parameters Individually
Initial start-up is performed at the factory. To start up the VFD by changing individual parameters, perform the following pro­cedure:
1. Select MENU (SOFT KEY 2). The Main menu will be displayed.
2. Use the UP or DOWN keys to highlight PARAMETERS on the display screen and press ENTER (SOFT KEY 2).
3. Use the UP or DOWN keys to highlight the desired parameter group and press SEL (SOFT KEY 2).
4. Use the UP or DOWN keys to highlight the desired parameter and press EDIT (SOFT KEY 2).
5. Use the UP or DOWN keys to change the value of the parameter.
6. Press SAVE (SOFT KEY 2) to store the modified value. Press CANCEL (SOFT KEY 1) to keep the previous value. Any modifications that are not saved will not be changed.
7. Choose another parameter or press EXIT (SOFT KEY 1) to return to the listing of parameter groups. Continue until all the parameters have been configured and then press EXIT (SOFT KEY 1) to return to the main menu.
NOTE: The current parameter value appears above the highlight parameter. To view the default parameter value, press the UP and DOWN keys simultaneously. To restore the default factory set­tings, select the application macro “HVAC Default.”
VFD Modes
The VFD has several different modes for configuring, operat­ing, and diagnosing the VFD. The modes are:
Standard Display mode—shows drive status information and operates the drive
Parameters mode—edits parameter values individually
Start-up Assistant mode—guides the start up and configu­ration. DO NOT USE THE START-UP ASSISTANT ON THESE LC UNITS!
Changed Parameters mode—shows all changed parameters
Drive Parameter Backup mode—stores or uploads the parameters
Clock Set mode—sets the time and date for the drive
I/O Settings mode—checks and edits the I/O settings
STANDARD DISPLAY MODE Use the standard display mode to read information on the drive
status and operate the drive. To reach the standard display mode, press EXIT until the LCD display shows status informa­tion as described below. (See Fig. C.)
The top line of the LCD display shows the basic status infor­mation of the drive. The HAND icon indicates that the drive control is local from the control panel. The AUTO icon indi­cates that the drive is in remote control mode, such as the basic I/O or field bus.
36
Page 37
The arrow icon indicates the drive and motor rotation status. A
60.0Hz
100.0 %SP
1.9 A
10.0 Vdc
rotating arrow (clockwise or counterclockwise) indicates that the drive is running and at set point and the shaft direction is forward or reverse. A rotating blinking arrow indicates that the drive is running but not at setpoint. A stationary arrow indi­cates that the drive is stopped. For the units covered in this manual, the correct display rotation is clockwise.
The upper-right corner shows the frequency setpoint that the drive will maintain.
Using parameter group 34, the middle of the LCD display can be configured to display 3 parameter values. The default dis­play shows parameters 0103 (OUTPUT FREQ) in percent speed, 0104 (CURRENT) in amperes, and 0120 (Al1) in volt­age DC.
The bottom corners of the LCD display show the functions cur­rently assigned to the two soft keys. The lower middle screen displays the current time (if configured to show the time).
The first time the drive is powered up, it is in the OFF mode. To switch to local hand-held control and control the drive using the control panel, press and hold the HAND button. Pressing the HAND button switches the drive to hand control while keeping the drive running. Press the AUTO button to switch to remote input control. To start the drive press the HAND or AUTO buttons, to stop the drive press the OFF button.
Fig. C — Standard Display Example
To adjust the speed in HAND mode, press the UP or DOWN buttons (the reference changes immediately). The reference can be modified in the local control (HAND) mode, and can be parameterized (using Group 11 reference select) to also allow modification in the remote control mode.
PARAMETERS MODE The Parameters mode is used to change the parameters on the
drive. To change parameters, perform the following procedure. See Tables A through C for a listing of the VFD parameters per motor and VFD drive models:
1. Select MENU (SOFT KEY 2). The main menu will be displayed.
2. Use the UP or DOWN keys to highlight PARAMETERS on the display screen and press ENTER (SOFT KEY 2).
3. Use the UP or DOWN keys to highlight the desired parameter group and press SEL (SOFT KEY 2).
4. Use the UP or DOWN keys to highlight the desired parameter and press EDIT (SOFT KEY 2).
5. Use the UP or DOWN keys to change the value of the parameter.
6. Press SAVE (SOFT KEY 2) to store the modified value. Press CANCEL (SOFT KEY 1) to keep the previous value. Any modifications that are not saved will not be changed.
7. Choose another parameter or press EXIT (SOFT KEY 1) to return to the listing of parameter groups. Continue until all the parameters have been configured and then press EXIT (SOFT KEY 1) to return to the main menu.
NOTE: The current parameter value appears above the highlight parameter. To view the default parameter value, press the UP and DOWN keys simultaneously. To restore the default factory set­tings, select the Carrier application macro.
CHANGED PARAMETERS MODE The Changed Parameters mode is used to view and edit recent-
ly changed parameters on the drive. To view the changed pa­rameters, perform the following procedure:
1. Select MENU (SOFT KEY 2). The main menu will be displayed.
2. Use the UP or DOWN keys to highlight CHANGED PAR on the display screen and press ENTER (SOFT KEY 2). A list of the recently changed parameters will be displayed.
3. Use the UP or DOWN keys to highlight the desired parameter group and press EDIT (SOFT KEY 2) to change the parameter if desired.
4. Press EXIT (SOFT KEY 1) to exit the Changed Parame­ters mode.
DRIVE PARAMETER BACKUP MODE The drive parameter back-up mode is used to export the param-
eters from one drive to another. The parameters can be upload­ed from a VFD to the removable control panel. The control panel can then be transferred to another drive and the parame­ters are downloaded into memory.
Depending on the motor and application, there are two options available. The first option is to download all parameters. This copies both application and motor parameters to the drive from the control panel. This is recommended when using the same application for drives of the same size. This can also be used to create a backup of the parameters group for the drive.
The second option downloads only the application parameters to the drive. This is recommended when using the same appli­cation for drives of different sizes.
Upload All Parameters
To upload and store parameters in the control panel from the VFD, perform the following procedure:
1. Select MENU (SOFT KEY 2). The main menu will be displayed.
2. Use the UP or DOWN keys to highlight PAR BACKUP on the display screen and press ENTER (SOFT KEY 2).
3. Use the UP or DOWN keys to highlight UPLOAD TO PANEL and press SEL (SOFT KEY 2).
4. The text “Copying Parameters” will be displayed with a progress indicator. To stop the process, select ABORT (SOFT KEY 1).
5. When the upload is complete, the text “Parameter upload successful” will be displayed.
6. The display will then return to the PAR BACKUP menu. Select EXIT (SOFT KEY 1) to return to the main menu.
7. The control panel can now be disconnected from the drive.
Download All Parameters
To download all parameters from the control panel to the VFD, perform the following procedure:
1. Install the control panel with the correct parameters onto the VFD.
2. Select MENU (SOFT KEY 2). The main menu will be displayed.
3. Use the UP or DOWN keys to highlight PAR BACKUP on the display screen and press ENTER (SOFT KEY 2).
4. Use the UP or DOWN keys to highlight DOWNLOAD TO DRIVE ALL and press SEL (SOFT KEY 2).
5. The text “Restoring Parameters” will be displayed with a progress indicator. To stop the process, select ABORT (SOFT KEY 1).
6. When the download is complete, the text “Parameter download successful” will be displayed.
7. The display will then return to the PAR BACKUP menu. Select EXIT (SOFT KEY 1) to return to the main menu.
37
Page 38
8. The control panel can now be disconnected from the drive.
Download Application Parameters
To download application parameters only to the control panel from the VFD, perform the following procedure:
1. Install the control panel with the correct parameters onto the VFD.
2. Select MENU (SOFT KEY 2). The main menu will be displayed.
3. Use the UP or DOWN keys to highlight PAR BACKUP on the display screen and press ENTER (SOFT KEY 2).
4. Use the UP or DOWN keys to highlight DOWNLOAD APPLICATION and press SEL (SOFT KEY 2).
5. The text “Downloading Parameters (partial)” will be dis­played with a progress indicator. To stop the process, select ABORT (SOFT KEY 1).
6. When the download is complete, the text “Parameter download successful” will be displayed.
7. The display will then return to the PAR BACKUP menu. Select EXIT (SOFT KEY 1) to return to the main menu.
8. The control panel can now be disconnected from the drive.
CLOCK SET MODE The clock set mode is used for setting the date and time for the
internal clock of the VFD. In order to use the timer functions of the VFD control, the internal clock must be set. The date is used to determine weekdays and is visible in the fault logs.
To set the clock, perform the following procedure:
1. Select MENU (SOFT KEY 2). The main menu will be displayed.
2. Use the UP or DOWN keys to highlight CLOCK SET on the display screen and press ENTER (SOFT KEY 2). The clock set parameter list will be displayed.
3. Use the UP or DOWN keys to highlight CLOCK VISI­BILITY and press SEL (SOFT KEY 2). This parameter is used to display or hide the clock on the screen. Use the UP or DOWN keys to change the parameter setting. Press OK (SOFT KEY 2) to save the configuration and return to the Clock Set menu.
4. Use the UP or DOWN keys to highlight SET TIME and press SEL (SOFT KEY 2). Use the UP or DOWN keys to
Table A — 48LC 04 VFD Parameters
change the hours and minutes. Press OK (SOFT KEY 2) to save the configuration and return to the Clock Set menu.
5. Use the UP or DOWN keys to highlight TIME FORMAT and press SEL (SOFT KEY 2). Use the UP or DOWN keys to change the parameter setting. Press OK (SOFT KEY 2) to save the configuration and return to the Clock Set menu.
6. Use the UP or DOWN keys to highlight SET DATE and press SEL (SOFT KEY 2). Use the UP or DOWN keys to change the day, month, and year. Press OK (SOFT KEY 2) to save the configuration and return to the Clock Set menu.
7. Use the UP or DOWN keys to highlight DATE FORMAT and press SEL (SOFT KEY 2). Use the UP or DOWN keys to change the parameter setting. Press OK (SOFT KEY 2) to save the configuration and return to the Clock Set menu.
8. Press EXIT (SOFT KEY 1) twice to return to the main menu.
I/O SETTINGS MODE The I/O Settings mode is used for viewing and editing the I/O
settings. To configure the I/O settings, perform the following procedure:
1. Select MENU (SOFT KEY 2). The main menu will be displayed.
2. Use the UP or DOWN keys to highlight I/O SETTINGS on the display screen and press ENTER (SOFT KEY 2). The I/O Settings parameter list will be displayed.
3. Use the UP or DOWN keys to highlight the desired I/O setting and press SEL (SOFT KEY 2).
4. Use the UP or DOWN keys to select the parameter to view. Press OK (SOFT KEY 2).
5. Use the UP or DOWN keys to change the parameter set­ting. Press SAVE (SOFT KEY 2) to save the configura­tion. Press CANCEL (SOFT KEY 1) to keep the previous value. Any modifications that are not saved will not be changed.
6. Press EXIT (SOFT KEY 1) twice to return to the main menu.
PARAMETER
GROUP
START-UP
DATA
START/STOP/
DIR
REFERENCE
SELECT
UNIT SIZE 48LC 04
Motor Description 1.7 HP 575v 1.7 HP 208-230v 1.7 HP 460v 2.4 HP 575v 2.4 HP 208-230v
Drive/Motor Voltage 575v 208-230v 460v 575v 208-230v
PARAMETER
NUMBER
9902 Application Macro
9905
9906
9907
9908
9909 Motor Nominal Power 1.7 1.7 1.7 2.4 2.4 1001 EXT1 Commands (1) DI1 (1) DI1 (1) DI1 (1) DI1 (1) DI1 1003 Direction (1) Forward (1) Forward (1) Forward (1) Forward (1) Forward 1103 REF1 Select (1) AI1 (1) AI1 (1) AI1 (1) AI1 (1) AI1 1104 REF1 Minimum 0 Hz 0 Hz 0 Hz 0 Hz 0 Hz 1105 REF1 Maximum 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz
Motor Part Number HD56FR579 HD56FR233 HD56FR463 HD56FE577 HD56FE653
VFD Part Number HK30WA048 HK30WA045 HK30WA046 HK30WA048 HK30WA001
ABB Part Number
Motor Nominal
Voltage
Motor Nominal
Current
Motor Nominal
Frequency
Motor Nominal
Speed
ACH550-
CARUH
-03A9-6
(1) HVAC
DEFAULT
575 230 460 575 230
3.1 5.8 2.9 3.4 7.9
60 60 60 60 60
1725 1725 1725 1725 1725
ACH550-
CARUH
-07A5-2
(1) HVAC
DEFAULT
ACH550-
CARUH
-04A-4
(1) HVAC
DEFAULT
ACH550-
CARUH
-03A9-6
(1) HVAC
DEFAULT
38
ACH550-
CARUH
-012A-2
(1) HVAC
DEFAULT
Page 39
Table A — 48LC 04 VFD Parameters (cont)
UNIT SIZE 48LC 04
Motor Description 1.7 HP 575v 1.7 HP 208-230v 1.7 HP 460v 2.4 HP 575v 2.4 HP 208-230v
Drive/Motor Voltage 575v 208-230v 460v 575v 208-230v
PARAMETER
GROUP
CONSTANT
SPEEDS
ANALOG
INPUTS
RELAY
OUTPUTS
SYSTEM
CONTROL
OVERRIDE 1701 Override Sel (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL
LIMITS
START/STOP
ACCEL/
DECEL
MOTOR
FAULT
FUNCTIONS
AUTOMATIC
RESET
EFB
PROTOCOL
OPTIONS 9802 COMM PROT SEL 6 (LEN) 6 (LEN) 6 (LEN) 6 (LEN) 6 (LEN)
PARAMETER
NUMBER
1201
1202 Constant Speed 1 52.4 52.4 52.4 52.4 52.4 1203 Constant Speed 2 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 1204 Constant Speed 3 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 1301 Minimum AI-1 20.00% 20.00% 20.00% 20.00% 20.00% 1302 Maximum AI-1 100.00% 100.00% 100.00% 100.00% 100.00% 1401 Relay Output 1 (1) Ready (1) Ready (1) Ready (1) Ready (1) Ready 1402 Relay Output 2 (2) Run (2) Run (2) Run (2) Run (2) Run 1403 Relay Output 3 (16) FLT/ALARM (16) FLT/ALARM (16) FLT/ALARM (16) FLT/ALARM (16) FLT/ALARM 1604 Fault Reset Sel (0) Keypad (0) Keypad (0) Keypad (0) Keypad (0) Keypad 1608 Start Enable 1 (4) DI4 (4) DI4 (4) DI4 (4) DI4 (4) DI4
2003 Maximum Current 3.6 6.7 3.3 3.9 9.1 2007 Minimum Frequency 0.0 Hz 0.0 Hz 0.0 Hz 0.0 Hz 0.0 Hz 2008 Maximum Frequency 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 2101 Start Function (1) AUTO (1) AUTO (1) AUTO (1) AUTO (1) AUTO 2102 Stop Function (1) Coast (1) Coast (1) Coast (1) Coast (1) Coast 2109 EM STOP Sel (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL 2201 Acc/Dec 1/2 Sel (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL 2202 Accelerate Time 30.0 s 30.0 s 30.0 s 30.0 s 30.0 s 2203 Decelerate Time 10.0 s 10.0 s 10.0 s 10.0 s 10.0 s 2606 Switching Frequency 4 kHz 4 kHz 4 kHz 4 kHz 4 kHz
2607
3005 Motor Therm Prot (1) Fault (1) Fault (1) Fault (1) Fault (1) Fault 3006 Motor Thermal Time 1050 s 1050 s 1050 s 1050 s 1050 s 3007 Motor Load Curve 100% 100% 100% 100% 100% 3008 Zero Speed Load %00705 %00705 %00705 %00705 %00705
3009
3104 AR Overcurrent (0) DISABLE (0) DISABLE (0) DISABLE (0) DISABLE (0) DISABLE 3105 AR Overvoltage (1) ENABLE (1) ENABLE (1) ENABLE (1) ENABLE (1) ENABLE 3106 AR Undervoltage (1) ENABLE (1) ENABLE (1) ENABLE (1) ENABLE (1) ENABLE 5301 EFB PROTOCOL ID 0601 (hex) 0601 (hex) 0601 (hex) 0601 (hex) 0601 (hex) 5302 EFB STATION ID 41 41 41 41 41 5303 EFB BAUD RATE 38400 38400 38400 38400 38400 5304 EFB PARITY 8 NONE 1 8 NONE 1 8 NONE 1 8 NONE 1 8 NONE 1 5305 EFB CTRL PROFILE DCU PROFILE DCU PROFILE DCU PROFILE DCU PROFILE DCU PROFILE
Motor Part Number HD56FR579 HD56FR233 HD56FR463 HD56FE577 HD56FE653
VFD Part Number HK30WA048 HK30WA045 HK30WA046 HK30WA048 HK30WA001
ABB Part Number
Constant Speed
Select
Switching Frequency
Control
Break Point
Frequency
ACH550-
CARUH
-03A9-6
(8) DI2,3 (8) DI2,3 (8) DI2,3 (8) DI2,3 (8) DI2,3
(1) ON (1) ON (1) ON (1) ON (1) ON
35 Hz 35 Hz 35 Hz 35 Hz 35 Hz
ACH550-
CARUH
-07A5-2
ACH550-
CARUH
-04A-4
ACH550-
CARUH
-03A9-6
ACH550-
CARUH
-012A-2
39
Page 40
Table B — 48LC 04-06 VFD Parameters
UNIT SIZE 48LC 04 48LC 05 48LC 06
Motor
Description Drive/motor
Voltage
PARAMETER
GROUP
START-UP
DATA
START/STOP/
DIR
REFERENCE
SELECT
CONSTANT
SPEEDS
ANALOG
INPUTS
RELAY
OUTPUTS
SYSTEM
CONTROL
OVERRIDE 1701 Override Sel (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL
LIMITS
START/STOP
ACCEL/DECEL
MOTOR
PARAMETER
NUMBER
9902
9905
9906
9907
9908
9909
1001 EXT1 Commands (1) DI1 (1) DI1 (1) DI1 (1) DI1 (1) DI1 1003 Direction (1) Forward (1) Forward (1) Forward (1) Forward (1) Forward 1103 REF1 Select (1) AI1 (1) AI1 (1) AI1 (1) AI1 (1) AI1 1104 REF1 Minimum 0 Hz 0 Hz 0 Hz 0 Hz 0 Hz 1105 REF1 Maximum 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz
1201
1202
1203
1204
1301 Minimum AI-1 20.00% 20.00% 20.00% 20.00% 20.00% 1302 Maximum AI-1 100.00% 100.00% 100.00% 100.00% 100.00% 1401 Relay Output 1 (1) Ready (1) Ready (1) Ready (1) Ready (1) Ready 1402 Relay Output 2 (2) Run (2) Run (2) Run (2) Run (2) Run 1403 Relay Output 3 (16) FLT/ALARM (16) FLT/ALARM (16) FLT/ALARM (16) FLT/ALARM (16) FLT/ALARM 1604 Fault Reset Sel (0) Keypad (0) Keypad (0) Keypad (0) Keypad (0) Keypad 1608 Start Enable 1 (4) DI4 (4) DI4 (4) DI4 (4) DI4 (4) DI4
2003
2007
2008
2101 Start Function (1) AUTO (1) AUTO (1) AUTO (1) AUTO (1) AUTO 2102 Stop Function (1) Coast (1) Coast (1) Coast (1) Coast (1) Coast 2109 EM STOP Sel (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL 2201 Acc/Dec 1/2 Sel (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL 2202 Accelerate Time 30.0 s 30.0 s 30.0 s 30.0 s 30.0 s 2203 Decelerate Time 10.0 s 10.0 s 10.0 s 10.0 s 10.0 s
2606
2607
Motor Part
Number
VFD Part
Number
ABB Part
Number
Application
Macro
Motor
Nominal Voltage
Motor
Nominal Current
Motor
Nominal
Frequency
Motor
Nominal Speed
Motor
Nominal Power
Constant Speed
Select
Constant Speed
1
Constant Speed
2
Constant Speed
3
Maximum
Current
Minimum
Frequency
Maximum
Frequency
Switching
Frequency
Switching
Frequency
Control
2.4 HP 460v 1.7 HP 575v 1.7 HP 208-230v 1.7 HP 460v 2.4 HP 575v
460v 575v 208-230v 460v 575v
HD56FE653 HD56FR579 HD56FR233 HD56FR463 HD56FE577
HK30WA008 HK30WA048 HK30WA045 HK30WA046 HK30WA048
ACH550-
CARUH
-06A9-4
(1) HVAC
DEFAULT
460 575 230 460 575
4.0 3.1 5.8 2.9 3.4
60 60 60 60 60
1725 1725 1725 1725 1725
2.4 1.7 1.7 1.7 2.4
(8) DI2,3 (8) DI2,3 (8) DI2,3 (8) DI2,3 (8) DI2,3
52.4 42.6 42.6 42.6 42.6
60 Hz 60 Hz 60 Hz 60 Hz 60 Hz
60 Hz 60 Hz 60 Hz 60 Hz 60 Hz
4.6 3.6 6.7 3.3 3.9
0.0 Hz 0.0 Hz 0.0 Hz 0.0 Hz 0.0 Hz
60 Hz 60 Hz 60 Hz 60 Hz 60 Hz
4 kHz4 kHz4 kHz4 kHz4 kHz
(1) ON (1) ON (1) ON (1) ON (1) ON
ACH550-
CARUH
-03A9-6
(1) HVAC
DEFAULT
ACH550-
CARUH
-07A5-2
(1) HVAC
DEFAULT
ACH550-
CARUH
-04A1-4
(1) HVAC
DEFAULT
ACH550-
CARUH
-03A9-6
(1) HVAC
DEFAULT
40
Page 41
PARAMETER
GROUP
FAULT
FUNCTIONS
AUTOMATIC
RESET
EFB PROTOCOL
OPTIONS 9802
Table B — 48LC 04-06 VFD Parameters (cont)
UNIT SIZE 48LC 04 48LC 05 48LC 06
Motor
Description Drive/motor
Voltage
PARAMETER
NUMBER
3005 Motor Therm Prot (1) Fault (1) Fault (1) Fault (1) Fault (1) Fault
3006
3007
3008 Zero Speed Load %00705 %00705 %00705 %00705 %00705
3009
3104 AR Overcurrent (0) DISABLE (0) DISABLE (0) DISABLE (0) DISABLE (0) DISABLE 3105 AR Overvoltage (1) ENABLE (1) ENABLE (1) ENABLE (1) ENABLE (1) ENABLE 3106 AR Undervoltage (1) ENABLE (1) ENABLE (1) ENABLE (1) ENABLE (1) ENABLE
5301
5302 EFB STATION ID 41 41 41 41 41
5303
5304 EFB PARITY 8 NONE 1 8 NONE 1 8 NONE 1 8 NONE 1 8 NONE 1
5305
Motor Part
Number
VFD Part
Number
ABB Part
Number
Motor Thermal
Time
Motor Load
Curve
Break Point
Frequency
EFB PROTOCOL
ID
EFB BAUD
RATE
EFB CTRL
PROFILE
COMM PROT
SEL
2.4 HP 460v 1.7 HP 575v 1.7 HP 208-230v 1.7 HP 460v 2.4 HP 575v
460v 575v 208-230v 460v 575v
HD56FE653 HD56FR579 HD56FR233 HD56FR463 HD56FE577
HK30WA008 HK30WA048 HK30WA045 HK30WA046 HK30WA048
ACH550-
CARUH
-06A9-4
1050 s 1050 s 1050 s 1050 s 1050 s
100% 100% 100% 100% 100%
35 Hz 35 Hz 35 Hz 35 Hz 35 Hz
0601 (hex) 0601 (hex) 0601 (hex) 0601 (hex) 0601 (hex)
38400 38400 38400 38400 38400
DCU PROFILE DCU PROFILE DCU PROFILE DCU PROFILE DCU PROFILE
6 (LEN) 6 (LEN) 6 (LEN) 6 (LEN) 6 (LEN)
ACH550-
CARUH
-03A9-6
ACH550-
CARUH
-07A5-2
ACH550-
CARUH
-04A1-4
ACH550-
CARUH
-03A9-6
PARAMETER
GROUP
START-UP
DATA
START/STOP/
DIR
REFERENCE
SELECT
CONSTANT
SPEEDS
ANALOG
INPUTS
RELAY
OUTPUTS
Table C — 48LC 05-06 VFD Parameters
UNIT SIZE 48LC 06 48LC 05/06
Motor Description
Drive/Motor Voltage 208-230v 460v 208-230v 460v 575v
PARAMETER
NUMBER
9902 Application Macro
9905 Motor Nominal Voltage 230 460 230 460 575 9906 Motor Nominal Current 7.9 4.0 9.2 4.6 4.2
9907
9908 Motor Nominal Speed 1725 1725 1725 1725 1725 9909 Motor Nominal Power 2.4 2.4 2.4 2.4 2.4 1001 EXT1 Commands (1) DI1 (1) DI1 (1) DI1 (1) DI1 (1) DI1 1003 Direction (1) Forward (1) Forward (1) Forward (1) Forward (1) Forward 1103 REF1 Select (1) AI1 (1) AI1 (1) AI1 (1) AI1 (1) AI1 1104 REF1 Minimum 0 Hz 0 Hz 0 Hz 0 Hz 0 Hz 1105 REF1 Maximum 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 1201 Constant Speed Select (8) DI2,3 (8) DI2,3 (8) DI2,3 (8) DI2,3 (8) DI2,3 1202 Constant Speed 1 42.6 42.6 41.2 41.2 41.2 1203 Constant Speed 2 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 1204 Constant Speed 3 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 1301 Minimum AI-1 20.00% 20.00% 20.00% 20.00% 20.00% 1302 Maximum AI-1 100.00% 100.00% 100.00% 100.00% 100.00% 1401 Relay Output 1 (1) Ready (1) Ready (1) Ready (1) Ready (1) Ready 1402 Relay Output 2 (2) Run (2) Run (2) Run (2) Run (2) Run
1403 Relay Output 3
Motor Part Number HD56FE653 HD56FE653 HD58FE654 HD58FE654 HD58FE577
VFD Part Number HK30WA001 HK30WA008 HK30WA001 HK30WA008 HK30WA021
ABB Part Number
Motor Nominal
Frequency
2.4 HP 208­230v
ACH550-
CARUH
-012A-2
(1) HVAC
DEFAULT
60 60 60 60 60
(16) FLT/
ALARM
2.4 HP 460v
ACH550-
CARUH
-06A9-4
(1) HVAC
DEFAULT
(16) FLT/
ALARM
2.9 HP 208­230v
ACH550-
CARUH
-012A-2
(1) HVAC
DEFAULT
(16) FLT/
ALARM
2.9 HP 460v 3.7 HP 575v
ACH550-
CARUH
-06A9-4
(1) HVAC
DEFAULT
(16) FLT/
ALARM
ACH550-
CARUH
-06A1-6
(1) HVAC
DEFAULT
(16) FLT/
ALARM
41
Page 42
Table C — 48LC 05-06 VFD Parameters (cont)
UNIT SIZE 48LC 06 48LC 05/06
Motor Description
Drive/Motor Voltage 208-230v 460v 208-230v 460v 575v
PARAMETER
GROUP
SYSTEM
CONTROL
OVERRIDE 1701 Override Sel (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL
LIMITS
START/STOP
ACCEL/DECEL
MOTOR
FAULT
FUNCTIONS
AUTOMATIC
RESET
EFB
PROTOCOL
OPTIONS 9802 COMM PROT SEL 6 (LEN) 6 (LEN) 6 (LEN) 6 (LEN) 6 (LEN)
PARAMETER
NUMBER
1604 Fault Reset Sel (0) Keypad (0) Keypad (0) Keypad (0) Keypad (0) Keypad 1608 Start Enable 1 (4) DI4 (4) DI4 (4) DI4 (4) DI4 (4) DI4
2003 Maximum Current 9.1 4.6 10.6 5.3 4.8 2007 Minimum Frequency 0.0 Hz 0.0 Hz 0.0 Hz 0.0 Hz 0.0 Hz 2008 Maximum Frequency 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 2101 Start Function (1) AUTO (1) AUTO (1) AUTO (1) AUTO (1) AUTO 2102 Stop Function (1) Coast (1) Coast (1) Coast (1) Coast (1) Coast 2109 EM STOP Sel (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL 2201 Acc/Dec 1/2 Sel (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL 2202 Accelerate Time 30.0 s 30.0 s 30.0 s 30.0 s 30.0 s 2203 Decelerate Time 10.0 s 10.0 s 10.0 s 10.0 s 10.0 s 2606 Switching Frequency 4 kHz 4 kHz 4 kHz 4 kHz 4 kHz
2607
3005 Motor Therm Prot (1) Fault (1) Fault (1) Fault (1) Fault (1) Fault 3006 Motor Thermal Time 1050 s 1050 s 1050 s 1050 s 1050 s 3007 Motor Load Curve 100% 100% 100% 100% 100% 3008 Zero Speed Load %00705 %00705 %00705 %00705 %00705 3009 Break Point Frequency 35 Hz 35 Hz 35 Hz 35 Hz 35 Hz 3104 AR Overcurrent (0) DISABLE (0) DISABLE (0) DISABLE (0) DISABLE (0) DISABLE 3105 AR Overvoltage (1) ENABLE (1) ENABLE (1) ENABLE (1) ENABLE (1) ENABLE 3106 AR Undervoltage (1) ENABLE (1) ENABLE (1) ENABLE (1) ENABLE (1) ENABLE 5301 EFB PROTOCOL ID 0601 (hex) 0601 (hex) 0601 (hex) 0601 (hex) 0601 (hex) 5302 EFB STATION ID 41 41 41 41 41 5303 EFB BAUD RATE 38400 38400 38400 38400 38400 5304 EFB PARITY 8 NONE 1 8 NONE 1 8 NONE 1 8 NONE 1 8 NONE 1 5305 EFB CTRL PROFILE DCU PROFILE DCU PROFILE DCU PROFILE DCU PROFILE DCU PROFILE
Motor Part Number HD56FE653 HD56FE653 HD58FE654 HD58FE654 HD58FE577
VFD Part Number HK30WA001 HK30WA008 HK30WA001 HK30WA008 HK30WA021
ABB Part Number
Switching Frequency
Control
VFD DIAGNOSTICS The drive detects error situations and reports them using:
1. Green and red LEDs on the body of the drive (located under the keypad)
2. Status LED on the control panel
3. Control panel display
4. The Fault Word and Alarm Word parameter bits (parame­ters 0305 to 0309)
The form of the display depends on the severity of the error. The user can specify the severity for many errors by directing the drive to ignore the error situation, report the situation as an alarm, or report the situation as a fault.
Faults (Red LED Lit)
The VFD signals that it has detected a severe error, or fault, by:
1. Enabling the red LED on the drive (LED is either steady or flashing)
2. Setting an appropriate bit in a Fault Word parameter (0305 to 0307)
3. Overriding the control panel display with the display of a fault code
4. Stopping the motor (if it was on)
5. Sets an appropriate bit in Fault Word parameter 0305-0307
The fault code on the control panel display is temporary. Press­ing the MENU, ENTER, UP button or DOWN buttons re­moves the fault message. The message reappears after a few
2.4 HP 208­230v
ACH550-
CARUH
-012A-2
(1) ON (1) ON (1) ON (1) ON (1) ON
2.4 HP 460v
ACH550-
CARUH
-06A9-4
seconds if the control panel is not touched and the fault is still active.
Alarms (Green LED Flashing)
For less severe errors, called alarms, the diagnostic display is advisory. For these situations, the drive is simply reporting that it detects something unusual.
In these situations, the drive:
1. Flashes the green LED on the drive (does not apply to alarms that arise from control panel operation errors)
2. Sets an appropriate bit in an Alarm Word parameter (0308 or 0309)
3. Overrides the control panel display with the display of an alarm code and/or name
Alarm messages disappear from the control panel display after a few seconds. The message returns periodically as long as the alarm condition exists.
Correcting Faults
The recommended corrective action for faults is shown in Table D. The VFD can also be reset to remove the fault. If an external source for a start command is selected and is active, the VFD may start immediately after fault reset.
To reset a fault indicated by a flashing red LED, turn off the power for 5 minutes. To reset a fault indicated by a red LED (not flash­ing), press RESET from the control panel or turn off the power for 5 minutes. Depending on the value of parameter 1604 (FAULT RESET SELECT), digital input or serial communication could
2.9 HP 208­230v
ACH550-
CARUH
-012A-2
2.9 HP 460v 3.7 HP 575v
ACH550-
CARUH
-06A9-4
ACH550-
CARUH
-06A1-6
42
Page 43
also be used to reset the drive. When the fault has been corrected, the motor can be started.
History
For reference, the last three fault codes are stored into parame­ters 0401, 0412, 0413. For the most recent fault (identified by parameter 0401), the drive stores additional data (in parameters 0402 through 0411) to aid in troubleshooting a problem. For example, a parameter 0404 stores the motor speed at the time of the fault. To clear the fault history (all of Group 04, Fault History parameters), follow these steps:
1. In the control panel, Parameters mode, select parameter
0401.
2. Press EDIT.
3. Press the UP and DOWN buttons simultaneously.
4. Press SAVE.
Correcting Alarms
To correct alarms, first determine if the Alarm requires any corrective action (action is not always required). Use Table E
If diagnostics troubleshooting has determined that the drive is defective during the warranty period, contact ABB Automation Inc., at 1-800-435-7365, option 4, option 3. A qualified techni­cian will review the problem with the caller and make a deter­mination regarding how to proceed. This may involve dis­patching a designated service station (DSS) representative from an authorized station, dispatching a replacement unit, or advising return for repair.
Control Panel Cleaning
Use a soft damp cloth to clean the control panel. Avoid harsh cleaners which could scratch the display window.
Battery Replacement
A battery is only used in assistant control panels that have the clock function available and enabled. The battery keeps the clock operating in memory during power interruptions. The ex­pected life for the battery is greater than ten years. To remove the battery, use a coin to rotate the battery holder on the back of the control panel. Replace the battery with type CR2032.
to find and address the root cause of the problem.
Table D — FAULT CODES
FAULT CODE FAULT NAME IN PANEL DESCRIPTION AND RECOMMENDED CORRECTIVE ACTION
1 OVERCURRENT
2 DC OVERVOLT
3 DEV OVERTEMP
4 SHORT CIRC Fault current. Check for short-circuit in the motor cable(s) or motor or supply disturbances. 5 OVERLOAD Inverter overload condition. The drive output current exceeds the ratings.
6 DC OVERVOLT
7 AI1 LOSS
8 AI2 LOSS
9 MOT OVERTEMP
10 PANEL LOSS
11 ID RUN FAIL The motor ID run was not completed successfully. Check motor connections.
12 MOTOR STALL
13 RESERVED Not used. 14 EXT FAULT 1 Digital input defined to report first external fault is active. See parameter 3003 EXTERNAL FAULT 1.
15 EXT FAULT 2
16 EARTH FAULT
17 UNDERLOAD
18 THERM FAIL
19 OPEX LINK
20 21 CURR MEAS Internal fault. Current measurement is out of range. Contact Carrier. 22 SUPPLY PHASE Ripple voltage in the DC link is too high. Check for missing main phase or blown fuse. 23 RESERVED Not used.
24 OVERSPEED
25 RESERVED Not used. 26 DRIVE ID Internal fault. Configuration block drive ID is not valid.
OPEX PWR Internal fault. Low voltage condition detected on the OINT board. Contact Carrier.
Output current is excessive. Check for excessive motor load, insufficient acceleration time (parameters 2202 ACCELER TIME 1, default 30 seconds), or faulty motor, motor cables or connections.
Intermediate circuit DC voltage is excessive. Check for static or transient over voltages in the input power supply, insufficient deceleration time (parameters 2203 DECELER TIME 1, default 30 seconds), or undersized brake chopper (if present).
Drive heat sink is overheated. Temperature is at or above 115°C (239°F). Check for fan failure, obstructions in the airflow, dirt or dust coating on the heat sink, excessive ambient temperature, or excessive motor load.
Intermediate circuit DC voltage is not sufficient. Check for missing phase in the input power supply, blown fuse, or under voltage on main circuit.
Analog input 1 loss. Analog input value is less than AI1 FLT LIMIT (3021). Check source and connection for analog input and parameter settings for AI1 FLT LIMIT (3021) and 3001 AI<MIN FUNCTION.
Analog input 2 loss. Analog input value is less than AI2 FLT LIMIT (3022). Check source and connection for analog input and parameter settings for AI2 FLT LIMIT (3022) and 3001 AI<MIN FUNCTION.
Motor is too hot, as estimated by the drive. Check for overloaded motor. Adjust the parameters used for the estimate (3005 through 3009). Check the temperature sensors and Group 35 parameters.
Panel communication is lost and either drive is in local control mode (the control panel displays LOC), or drive is in remote control mode (REM) and is parameterized to accept start/stop, direction or reference from the control panel. To correct check the communication lines and connections. Check parameter 3002 PANEL COMM ERROR, parameters in Group 10: Command Inputs and Group 11:Reference Select (if drive operation is REM).
Motor or process stall. Motor is operating in the stall region. Check for excessive load or insufficient motor power. Check parameters 3010 through 3012.
Digital input defined to report second external fault is active. See parameter 3004 EXTERNAL FAULT
2. The load on the input power system is out of balance. Check for faults in the motor or motor cable.
Verify that motor cable does not exceed maximum specified length. Motor load is lower than expected. Check for disconnected load. Check parameters 3013
UNDERLOAD FUNCTION through 3015 UNDERLOAD CURVE. Internal fault. The thermistor measuring the internal temperature of the drive is open or shorted.
Contact Carrier. Internal fault. A communication-related problem has been detected between the OMIO and OINT
boards. Contact Carrier.
Motor speed is greater than 120% of the larger (in magnitude) of 2001 MINIMUM SPEED or 2002 MAXIMUM SPEED parameters. Check parameter settings for 2001 and 2002. Check adequacy of motor braking torque. Check applicability of torque control. Check brake chopper and resistor.
43
Page 44
Table D — FAULT CODES (cont)
FAULT CODE FAULT NAME IN PANEL DESCRIPTION AND RECOMMENDED CORRECTIVE ACTION
27 CONFIG FILE Internal configuration file has an error. Contact Carrier.
28 SERIAL 1 ERR
29 EFB CON FILE Error in reading the configuration file for the field bus adapter. 30 FORCE TRIP Fault trip forced by the field bus. See the field bus reference literature. 31 EFB 1 Fault code reserved for the EFB protocol application. The meaning is protocol dependent. 32 EFB 2 Fault code reserved for the EFB protocol application. The meaning is protocol dependent. 33 EFB 3 Fault code reserved for the EFB protocol application. The meaning is protocol dependent.
34 MOTOR PHASE
35 OUTP WIRING
101-105 SYSTEM ERROR Error internal to the drive. Contact Carrier and report the error number. 201-206 SYSTEM ERROR Error internal to the drive. Contact Carrier and report the error number.
1000 PAR HZRPM
1001 PAR PFA REFNG
1002 PAR PFA IOCNF
1003 PAR AI SCALE
1004 PAR AO SCALE
1005 PAR PCU 2
1006 PAR EXT RO
1007 PAR FBUS
1008 PAR PFA MODE
1009 PAR PCU 1
1010 OVERRIDE/PFA CONFLICT
Field bus communication has timed out. Check fault setup (3018 COMM FAULT FUNC and 3019 COMM FAULT TIME). Check communication settings (Group 51 or 53 as appropriate). Check for poor connections and/or noise on line.
Fault in the motor circuit. One of the motor phases is lost. Check for motor fault, motor cable fault, thermal relay fault, or internal fault.
Error in power wiring suspected. Check that input power is wired to drive output. Check for ground faults.
Parameter values are inconsistent. Check for any of the following: 2001 MINIMUM SPEED > 2002 MAXIMUM SPEED 2007 MINIMUM FREQ > 2008 MAXIMUM FREQ 2001 MINIMUM SPEED / 9908 MOTOR NOM SPEED is outside of the range: -128/+128 2002 MAXIMUM SPEED / 9908 MOTOR NOM SPEED is outside of the range: -128/+128 2007 MINIMUM FREQ / 9907 MOTOR NOM FREQ is outside of the range: -128/+128 2008 MAXIMUM FREQ / 9907 MOTOR NOM FREQ is outside of the range: -128/+128
Parameter values are inconsistent. Check that 2007 MINIMUM FREQ is negative, when 8123 PFA ENABLE is active.
Parameter values are inconsistent. The number of programmed PFA relays does not match with Interlock configuration, when 8123 PFA ENABLE is active. Check consistency of RELAY OUTPUT parameters 1401 through 1403, and 1410 through 1412. Check 8117 NR OF AUX MOTORS, 8118 AUTOCHANGE INTERV, and 8120 INTERLOCKS.
Parameter values are inconsistent. Check that parameter 1301 AI 1 MIN > 1302 AI 1 MAX and that parameter 1304 AI 2 MIN > 1305 AI 2 MAX.
Parameter values are inconsistent. Check that parameter 1504 AO 1 MIN > 1505 AO 1 MAX and that parameter 1510 AO 2 MIN > 1511 AO 2 MAX.
Parameter values for power control are inconsistent: Improper motor nominal kVA or motor nominal power. Check the following parameters:
1.1 < (9906 MOTOR NOM CURR * 9905 MOTOR NOM VOLT * 1.73 / PN) < 2.6 Where: PN = 1000 * 9909 MOTOR NOM POWER (if units are kW) or PN = 746 * 9909 MOTOR NOM POWER (if units are HP, e.g., in US)
Parameter values are inconsistent. Check the extension relay module for connection and 1410 through 1412 RELAY OUTPUTS 4 through 6 have non-zero values.
Parameter values are inconsistent. Check that a parameter is set for field bus control (e.g., 1001 EXT1 COMMANDS = 10 (COMM)), but 9802 COMM PROT SEL = 0.
Parameter values are inconsistent. The 9904 MOTOR CTRL MODE must = 3 (SCALAR SPEED) when 8123 PFA ENABLE activated.
Parameter values for power control are inconsistent or improper motor nominal frequency or speed. Check for both of the following: 1 < (60 * 9907 MOTOR NOM FREQ / 9908 MOTOR NOM SPEED < 16
0.8 < 9908 MOTOR NOM SPEED / (120 * 9907 MOTOR NOM FREQ / Motor poles) < 0.992 Override mode is enabled and PFA is activated at the same time. This cannot be done because PFA
interlocks cannot be observed in the override mode.
44
Page 45
Table E — ALARM CODES
ALARM CODE ALARM NAME IN PANEL DESCRIPTION AND RECOMMENDED CORRECTIVE ACTION
2001 - Reserved 2002 - Reserved 2003 - Reserved
2004 DIR LOCK
2005 I/O COMM
2006 AI1 LOSS
2007 AI2 LOSS
2008 PANEL LOSS
2009 - Reserved
2010 MOT OVERTEMP
2011 UNDERLOAD
2012 MOTOR STALL Motor is operating in the stall region. This alarm warns that a Motor Stall fault trip may be near.
2013* AUTORESET
2014 AUTOCHANGE
2015 PFA INTERLOCK
2016 - Reserved
2017* OFF BUTTON This alarm indicates that the OFF button has been pressed.
2018 PID SLEEP
2019 ID RUN The VFD is performing an ID run. 2020 OVERRIDE Override mode is activated.
2021 START ENABLE 1 MISSING
2022 START ENABLE 2 MISSING
2023 EMERGENCY STOP Emergency stop is activated.
The change in direction being attempted is not allowed. Do not attempt to change the direction of motor rotation, or change parameter 1003 DIRECTION to allow direction change (if reverse operation is safe).
Field bus communication has timed out. Check fault setup (3018 COMM FAULT FUNC and 3019 COMM FAULT TIME). Check communication settings (Group 51 or 53 as appropriate). Check for poor connections and/or noise on line.
Analog input 1 is lost, or value is less than the minimum setting. Check input source and connections. Check the parameter that sets the minimum (3021) and the parameter that sets the Alarm/Fault operation (3001).
Analog input 2 is lost, or value is less than the minimum setting. Check input source and connections. Check parameter that sets the minimum (3022) and the parameter that sets the Alarm/Fault operation (3001).
Panel communication is lost and either the VFD is in local control mode (the control panel displays HAND), or the VFD is in remote control mode (AUTO) and is parameterized to accept start/stop, direction or reference from the control panel. To correct, check the communication lines and connections, Parameter 3002 PANEL LOSS, and parameters in groups 10 COMMAND INPUTS and 11 REFERENCE SELECT (if drive operation is REM).
Motor is hot, based on either the VFD estimate or on temperature feedback. This alarm warns that a Motor Overload fault trip may be near. Check for overloaded motor. Adjust the parameters used for the estimate (3005 through 3009). Check the temperature sensors and Group 35 parameters.
Motor load is lower than expected. This alarm warns that a Motor Underload fault trip may be near. Check that the motor and drive ratings match (motor is NOT undersized for the drive). Check the settings on parameters 3013 to 3015.
This alarm warns that the drive is about to perform an automatic fault reset, which may start the motor. To control automatic reset, use parameter group 31 (AUTOMATIC RESET).
This alarm warns that the PFA autochange function is active. To control PFA, use parameter group 81 (PFA) and the Pump Alternation macro.
This alarm warns that the PFA interlocks are active, which means that the drive cannot start any motor (when Autochange is used), or a speed regulated motor (when Autochange is not used).
This alarm warns that the PID sleep function is active, which means that the motor could accelerate when the PID sleep function ends. To control PID sleep, use parameters 4022 through 4026 or 4122 through 4126.
This alarm warns that the Start Enable 1 signal is missing. To control Start Enable 1 function, use parameter 1608. To correct, check the digital input configuration and the communication settings.
This alarm warns that the Start Enable 2 signal is missing. To control Start Enable 2 function, use parameter 1609. To correct, check the digital input configuration and the communication settings.
45
Page 46
© Carrier Corporation 2019
Catalog No. 04-53480187-01 Printed in U.S.A. Form 48LC-4-6-04SI Pg 46 6-19 Replaces: 48LC-4-6-03SI
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Page 47
START-UP CHECKLIST FOR 48LC SINGLE PACKAGE ROOFTOP COOLING ONLY
(REMOVE AND STORE IN JOB FILE)
NOTE: To avoid injury to personnel and damage to equipment or property when completing the procedures listed in this start-up checklist, use good judgment, follow safe practices, and adhere to the safety considerations/information as outlined in preced­ing sections of this Installation Instruction document.
I. PRELIMINARY INFORMATION
MODEL NO ____________________________________________
JOB NAME_____________________________________________
SERIAL NO ____________________________________________
ADDRESS _____________________________________________
START-UP DATE________________________________________
TECHNICIAN NAME _____________________________________
ADDITIONAL ACCESSORIES
_____________________________________________________________________________________________________
II. PRE-START-UP
Verify that all packaging materials have been removed from unit (Y/N) _____ Verify installation of outdoor air hood (Y/N) _____ Verify installation of flue exhaust and inlet hood (Y/N) _____ Verify that condensate connection is installed per instructions (Y/N) _____ Verify that all electrical connections and terminals are tight (Y/N) _____ Verify gas pressure to unit gas valve is within specified range (Y/N) _____ Check gas piping for leaks (Y/N) _____ Check that indoor-air filters are clean and in place (Y/N) _____ Check that outdoor-air inlet screens are in place (Y/N) _____ Verify that unit is level (Y/N) _____ Check fan wheels and propeller for location in housing/orifice and verify setscrew is tight (Y/N) _____ Verify that fan sheaves are aligned and belts are properly tensioned (Y/N) _____ Verify that scroll compressors are rotating in the correct direction (Y/N) _____ Verify installation of thermostat (Y/N) _____
Verify that crankcase heaters have been energized for at least 24 hours (Y/N) _____
III. START-UP
ELECTRICAL
Supply Voltage L1-L2_____________ L2-L3_____________ L3-L1_____________ Compressor Amps 1 L1 _____________ L2 _____________ L3 _____________ Compressor Amps 2 L1 _____________ L2 _____________ L3 _____________ Supply Fan Amps L1 _____________ L2 _____________ L3 _____________
TEMPERATURES
Outdoor-Air Temperature _____________ °F DB (Dry Bulb) Return-Air Temperature _____________ °F DB _____________ °F Wb (Wet Bulb) Cooling Supply Air Temperature _____________ °F Gas Heat Air Temperature _____________ °F
Catalog No. 04-53480187-01 Printed in U.S.A. Form 48LC-4-6-04SI Pg CL-1 6-19 Replaces: 48LC-4-6-03SI
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Page 48
PRESSURES
Gas Inlet Pressure _____________ IN. WG Gas Manifold Pressure STAGE 1 _____________ IN. WG
STAGE 2 _____________ IN. WG
Refrigerant Suction CIRCUIT A _____________ PSIG
CIRCUIT B _____________ PSIG
Refrigerant Discharge CIRCUIT A _____________ PSIG
CIRCUIT B _____________ PSIG
Verify Refrigerant Charge using Charging Charts (Y/N) _____
GENERAL
Economizer minimum vent and changeover settings to job requirements (if equipped) (Y/N) _____ Verify smoke detector unit shutdown by utilizing magnet test (Y/N) _____
IV. HUMIDI-MIZER® START-UP
NOTE: Units equipped with either SystemVu™ or RTU Open controls have Service Test menus or modes that can assist with the Humidi-MiZer System Start-Up function and provide the means to make the observations listed for this start-up.
STEPS
1. Check CTB for jumper 5, 6, 7 (Jumper 5, 6, 7 must be cut and open) (Y/N) _____
2. Open humidistat contacts (Y/N) _____
3. Start unit In cooling (Close Y1) (Y/N) _____
OBSERVE AND RECORD
A. Suction pressure _______________ PSIG B. Discharge pressure _______________ PSIG C. Entering air temperature _______________ ° F D. Liquid line temperature at outlet or reheat coil _______________ ° F E. Confirm correct rotation for compressor (Y/N) _____ F. Check for correct ramp-up of outdoor fan motor as condenser coil warms (Y/N) _____
4. Check unit charge per charging chart (Y/N) _____ (Jumper 32L Motormaster
5. Switch unit to high-latent mode (sub-cooler) by closing humidistat with Y1 closed (Y/N) _____
®
temperature sensor during this check. Remove jumper when complete.)
OBSERVE
A. Reduction in suction pressure (5 to 7 psi expected) (Y/N) _____ B. Discharge pressure unchanged (Y/N) _____ C. Liquid temperature drops to 50°F to 55°F range (Y/N) _____ D. LSV solenoid energized (valve closes) (Y/N) _____
6. Switch unit to dehumid (reheat) by opening Y1 (Y/N) _____
OBSERVE
A. Suction pressure increases to normal cooling level B. Discharge pressure decreases (35 to 50 psi) (Limited by Motormaster control) C. Liquid temperature returns to normal cooling level D. LSV solenoid energized (valve closes) E. DSV solenoid energized, valve opens
7. With unit in dehumid mode close W1 compressor and outdoor fan stop; LSV and DSV solenoids de-energized
(Y/N) _____
8. Open W1 restore unit to dehumid mode (Y/N) _____
9. Open humidistat input compressor and outdoor fan stop; LSV and DSV solenoids de-energized (Y/N) _____
10. Restore set-points for thermostat and humidistat (Y/N) _____
REPEAT PROCESS FOR 2 COMPRESSOR SYSTEMS.
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
© Carrier Corporation 2019
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53480187-01 Printed in U.S.A. Form 48LC-4-6-04SI Pg CL-2 6-19 Replaces: 48LC-4-6-03SI
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
Loading...