Carrier WeatherExpert 48LC Installation Instructions Manual

48LC
WeatherExpertRSeries Single Package Rooftop
Gas Heat/Electric Cooling Unit with Puronr (R ---410A) Refrigerant Sizes: 14, 17, 20, 24, 26
Installation Instructions
NOTE: Read the entire instruction manual before starting the installation.
TABLE OF CONTENTS
SAFETY CONSIDERATIONS 2....................
Rated Indoor Airflow (cfm) 4.....................
INSTALLATION 15..............................
Jobsite Survey 15...............................
Step 1 -- Plan for Unit Location 15.................
Roof Mount 15..............................
Step 2 -- Plan for Sequence of Unit Installation 15.....
Curb--Mounted Installation 15..................
Pad--Mounted Installation 15...................
Frame--Mounted Installation 15.................
Step 3 -- Inspect Unit 15..........................
Step 4 -- Provide Unit Support 16..................
Roof Curb Mount 16.........................
Slab Mount (Horizontal Units Only) 16..........
Alternate Unit Support
(In Lieu of Curb or Slab Mount) 16.............
Step 5 -- Field Fabricate Ductwork 20...............
Step 6 -- Rig and Place Unit 20....................
Positioning on Curb 21.......................
Step 7 -- Horizontal Duct Connection 21............
Step 8 -- Install Outside Air Hood — Factory Option 21..
Step 9 -- Install Flue Hood and Combustion Air Hood 22.
Step 10 -- Install Gas Piping 23....................
Gas Supply Line 23..........................
Factory--Option Thru--Base Connections 24.......
Step 11 -- Install External Condensate Trap and Line 25..
Step 12 -- Make Electrical Connections 25...........
Field Power Supply 25........................
Units Without Factory--Installed
Non--Fused Disconnect or HACR 32.............
Units With Factory--Installed
Non--Fused Disconnect or HACR 32.............
All Units 33................................
Convenience Outlets 33.......................
HACR 34..................................
Factory--Option Thru--Base Connections 35......
Units Without Thru --Base Connections 35........
Field Control Wiring 35.......................
Thermostat 35...............................
Unit Without Thru--Base Conversion Kit 35.......
Heat Anticipator Settings 36...................
Transformer Connection
for 208--v Power Supply 36.....................
RTU Open Controller (Factory--Installed Option) 36...
SystemVut Controller (Factory--Installed Option) 36..
Humidi--MiZer
Humidi--MiZer System -- Space RH Controller 37..
Integrated Staging Control (ISC) Board 38...........
ISC Board — Sequence of Operation 38...........
General 38.................................
Ventilation 38...............................
Cooling 39.................................
Humidi--MiZer System (Optional) 39............
Economizer (Optional) 39.....................
Low Ambient Cooling Operation
Down to 40_F(4_C) 40.......................
Heating 40.................................
EconoMi$er
Unit Installation 41..........................
Enthalpy Sensor Relocation 41.................
W7220 Economizer Controller 41................
User Interface 41............................
Keypad 41.................................
Menu Structure 42.............................
Connections and Applications 46.................
W7220 Economizer Module Wiring 46..........
Economizer Controlled Configurations 47..........
Enthalpy Changeover Control 47...............
Enthalpy Settings 47.........................
Demand Controlled Ventilation 49..............
Economizer Occupancy Control 50..............
R
System Control Connections 37....
R
X (Factory--Installed Option) 41.......
Hardware 51.................................
Actuators 51................................
Supply Air Temperature Sensor 51..............
Outside Air Temperature Sensor 51.............
Enthalpy Control Sensor Configuration 51........
Operating Sequences 52........................
Staged Air Volume (3--Speed) Fan Motor 52......
W7220 Economizer Control 52.................
Base Unit Controls 52........................
R
Cooling, Unit With EconoMi$er Without CO
Heating With EconoMi$er X 54.................
Demand Controlled Ventilation 55..............
Setup and Configuration 55.....................
Initial Menu Display 55.......................
Time--out and Screensaver 55..................
Checkout 55.................................
Status 56...................................
Calibration of Sensors 56......................
Resetting All Defaults 56......................
Troubleshooting 56............................
Power Up Delay 56..........................
Power Loss (Outage or Brownout) 56............
Alarms 56..................................
Clearing Alarms 56..........................
Control Set Point and Configuration Log 59........
Staged Air Volume (SAVt)
with Variable Frequency Drive 62..................
Multi--Speed VFD Display Kit
(Field--Installed Accessory) 63....................
Connecting the Keypad to the VFD 63.............
Program the VFD for 3 Discrete
Indoor Fan Speeds 64..........................
Smoke Detectors 80...........................
Return Air Sensor Tube Installation 80...........
Smoke Detector Test Magnet 80................
Additional Application Data 80.................
Step 13 -- Install Accessories 80...................
Step 14 -- Check Belt Tension 81...................
UNIT START--UP CHECKLIST 83..................
Sensor 52.......................
2
X
product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloths for brazing operations and have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and appropriate national electrical codes (in USA, ANSI/NFPA 70, National Electrical Code (NEC); in Canada, CSA C22.1) for special requirements.
It is important to recognize safety information. This is the safety--alert symbol
unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in seve re personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
!
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect gas piping from unit when leak testing at pressure greater than 0.5 psig (3450 Pa). Pressures greater than 0.5 psig (3450 Pa) will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pressure greater than 0.5 psig (3450 Pa), it must be replaced before use. When pressure testing field--supplied gas piping at pressures of 0.5 psig (3450 Pa) or less, a unit connected to such piping must be isolated by closing the manual gas valve.
FIRE HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
Inlet pressure tab set screw must be tightened and NPT pipe plug must be installed to prevent gas leaks.
!
. When you see this symbol on the
WARNING
WARNING
1
/8in.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this
518
GAS VALVE
INLET PRESSURE
TAP SET SCREW
2
!
WARNING
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
Manifold pressure tap set screw must be tightened and
1
/8in. NPT pipe plug must be installed to prevent gas
leak.
MANIFOLD PRESSURE
TAP SET SCREW
MANIFOLD
GAS VALVE
!
WARNING
CARBON--MONOXIDE POISONING HAZARD
Failure to follow instructions could result in severe personal injury or death due to carbon--monoxide poisoning, if combustion products infiltrate into the building.
Check that all openings in the outside wall around the vent (and air intake) pipe(s) are sealed to prevent infiltration of c om bustion products into the building.
Check that furnace vent (and air intake) terminal(s) are not obstructed in any way during all seasons.
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal injury, death and/or equipment damage.
Puronr (R--410A) refrige rant systems operate at higher pressures than standard R--22 systems. Do not use R--22 service equipment or components on Puron refrigerant equipment.
!
WARNING
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could cause personal injury or death.
Relieve pre ssure and recover all refrigerant before system repair or final unit disposal.
Ware safety glasses and gloves when handling refrigerants. Keep torches and other ignition sources away from refrigerants and oils.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing air conditioning equipment.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury or death.
Before performing service or maintenance operations on unit, always turn off main power switch to unit and install lock(s) and lockout tag(s). Unit ma y have more than one power switch.
3
518
Rated Indoor Airflow (cfm)
The table to the right lists the rated indoor airflow used for the AHRI efficiency rating for the units covered in this document.
Model Number Full Load Airflow (cfm)
48LC**14 4375
48LC**17 4875
48LC**20 5690
48LC**24 6500
48LC**26 7500
Position:
Example:
1234567891011 12 13 14 15 16
48LCD0 24A1A5 -0A0A0
Unit Heat Type
48 - Gas Heat Packaged Rooftop
Model Series - WeatherExpert
®
LC - Ultra High Efficiency
Heat Options
D = Low Gas Heat E = Medium Gas Heat F = High Gas Heat S = Low Heat w/ Stainless Steel Exchanger R = Medium Heat w/ Stainless Steel Exchanger T = High Heat w/ Stainless Steel Exchanger
Refrig. Systems Options
0 = Three stage cooling capacity control with TXV A = Three stage cooling capacity control with TXV and Humidi-MiZer
®
system
Cooling Tons
14 - 12.5 ton 17 - 15 ton 20 - 17.5 ton 24 - 20 ton 26 - 23 ton
Sens or Options
A = None B = RA Smoke Detector C = SA Smoke Detector D = RA + SA Smoke Detector E = CO
2
F = RA Smoke Detector and CO G = SA Smoke Detector and CO H = RA + SA Smoke Detector and CO
2
2
2
Indoor Fan Motor Options
1 = Standard Static / Vertical Supply, Return Air Flow 2 = Medium Static / Vertical Supply, Return Air Flow 3 = High Static / Vertical Supply, Return Air Flow 4 = Ultra High Static / Vertical Supply, Return Air Flow 5 = Standard Static / Horizontal Supply, Return Air Flow 6 = Medium Static / Horizontal Supply, Return Air Flow 7 = High Static / Horizontal Supply, Return Air Flow 8 = Ultra High Static / Horizontal Supply, Return Air Flow
17
18
Packaging
0 = Standard 1 = LTL
Electrical Options
A = None B = HACR Circuit Breaker C = Non-Fused Disconnect
Service Options
0 = None 1 = Unpowered Convenience Outlet 2 = Powered Convenience Outlet 3 = Hinged Panels 4 = Hinged Panels and Unpowered Convenience Outlet 5 = Hinged Panels and Powered Convenience Outlet
Intake / Exhaust Options
A = None B = Temperature Standard Leak Economizer with Barometric Relief C = Temperature Standard Leak Economizer with Centrifugal Power Exhaust - Vertical Only E = Enthalpy Standard Leak Economizer with Barometric Relief F = Enthalpy Standard Leak Economizer with Centrifugal Power Exhaust - Vertical Only N = Temperature Ultra Low Leak Economizer with Barometric Relief P = Temperature Ultra Low Leak Economizer with Centrifugal Power Exhaust - Vertical Only R = Enthalpy Ultra Low Leak Economizer with Barometric Relief S = Enthalpy Ultra Low Leak Economizer with Centrifugal Power Exhaust - Vertical Only
Base Unit Controls
0 = Electro-mechanical Controls 1 = RTU Open Multi-Protocol Controller 4 = SystemVu™ Controller
Design Revision
- = Factory Design Revision
Coil Options: Fin/Tube (Condenser- Evaporator - Hail Guard)
A = Al/Cu - Al/Cu B = Precoat Al/Cu - Al/Cu C = E-coat Al/Cu - Al/Cu D = E-coat Al/Cu - E-coat Al/Cu E = Cu/Cu - Al/Cu F = Cu/Cu - Cu/Cu M = Al/Cu -Al/Cu — Louvered Hail Guard N = Precoat Al/Cu - Al/Cu — Louvered Hail Guard P = E-coat Al/Cu - Al/Cu — Louvered Hail Guard Q = E-coat Al/Cu - E-coat Al/Cu — Louvered Hail Guard R = Cu/Cu - Al/Cu — Louvered Hail Guard S = Cu/Cu - Cu/Cu — Louvered Hail Guard
Fig. 1 -- 48LC 14--26 Model Number Nomenclature (Example)
Voltage
1 = 575/3/60 5 = 208-230/3/60 6 = 460/3/60
a48--- 9335
4
Fig. 2 -- Unit Dimensional Drawing – 14 Size Unit, Sheet 1 of 3
C13057
5
Fig.2(cont)--UnitDimensionalDrawing–14SizeUnit,Sheet2of3
C13058
6
Fig.2(cont)--UnitDimensionalDrawing–14SizeUnit,Sheet3of3
C13059
7
Fig. 3 -- Unit Dimensional Drawing – 17 and 20 Size Units, Sheet 1 of 3
C13032
8
Fig. 3 (cont) -- Unit Dimensional Drawing – 17 and 20 Size Units, Sheet 2 of 3
C13033
9
Fig. 3 (cont) -- Unit Dimensional Drawing – 17 and 20 Size Units, Sheet 3 of 3
C13034
10
Fig. 4 -- Unit Dimensional Drawing – 24 and 26 Size Units, Sheet 1 of 3
C14106
11
Fig. 4 (cont) -- Unit Dimensional Drawing – 24 and 26 Size Units, Sheet 2 of 3
C14107
12
Fig. 4 (cont) -- Unit Dimensional Drawing – 24 and 26 Size Units, Sheet 3 of 3
C14108
13
C
D
B
LOCATION DIMENSION CONDITION
A 36-- -in (914 mm) • Recommended clearance for air flow and service
B 42--- in (1067 mm) • Recommended clearance for air flow and service
• No Convenience Outlet
18-- -in (457 mm)
36-- -in (914 mm)
C
42-- -in (1067 mm)
96-- -in (2438 mm)
D 42--- in (1067 mm) • Recommended clearance for service.
NOTE: Unit not designed to have overhead obstruction. Contact Application Engineering for guidance on any application planning
overhead obstruction or for vertical clearances.
•NoEconomizer
• No field--- installed disconnect on economizer hood side (Factory --- installed disconnect installed).
• Convenience Outlet installed.
• Vertical surface behind servicer is electrically non ---conductive (e.g.: wood, fiberglass).
• Convenience Outlet installed.
• Vertical surface behind servicer is electrically conductive (e.g.: metal, masonry).
• Economizer and/or Power Exhaust installed.
• Check for sources of flue products with 10 feet (3 meters) of economizer fresh air intake.
A
Fig. 5 -- Service Clearance Dimensional Drawing
C12384
48LC**
Base Unit 1853 (842.3) 2095 (952.3) 2201 (1000.7) 2347 (1067.0) 2492 (1132.6)
Economizer 246 (112) 246 (112) 246 (112) 246 (112) 246 (112)
Powered Outlet 35 (16) 35 (16) 35 (16) 35 (16) 35 (16)
Curb
14--- in/356 mm 240 (109) 240 (109) 255 (116) 255 (116) 273 (124)
24--- in/610 mm 340 (154) 340 (154) 355 (161) 355 (161) 355 (161)
14 17 20 24 26
Table 1 – Operating Weights
UNIT LB (KG)
14
INSTALLATION
Jobsite Survey
Complete the following checks before installation.
1. Consult local building codes and the NEC (National Electrical Code) ANSI/NFPA 70 for special installa­tion requirements.
2. Determine unit location (from project plans) or select unit location.
3. Check for possible overhead obstructions which may interfere with unit lifting or rigging.
Step 1 — Plan for Unit Location
Select a location for the unit and its support system (curb or other) that provides for the minimum clearances required for safety. This includes the clearance to combustible surfaces, unit performance and service access below, around and above unit as specified in unit drawings. See Fig. 5.
NOTE: Consider also the effect of adjacent units.
Be sure that the unit is installed such that snow will not block the combustion air intake or flute outlet.
Unit may be installed directly on wood floo rin g or on Class A, B, or C roof--covering material when roof curb is used.
Do not install unit in an indoor location. Do not locate air inlets near exhaust vents or other sources of contaminated air. For proper unit operation, adequate combustion and ventilation air must be pro vid ed in accord an ce with S ection
5.3 (Air for Combustion and Ventilation) of the National Fuel Gas Code, ANSI Z223.1 (American National Standards Institute) and NFPA (National Fire Protection Association) 54 TIA----54----84----1. In Canada, installation must be in accordance with the CAN1----B149 installation codes for gas burning appliances.
Although unit is weatherproof, avoid locations that permit water from higher level runoff and overhangs to fall onto the unit.
Locate mechanical draft system flue assembly at least 4 ft (1.2 m) from any opening through which combustion products could enter the building, and at least 4 ft (1.2 m) from any adjacent building (or per local code). Locate the flue assembly at least 10 ft (3.05 m) from an adjacent unit’s fresh air intake hood if within 3 ft (0.91 m) of same elevation (or per local code). When unit is located adjacent t o public walkways, flue assembly must be at least 7 ft (2.1 m) above grade.
Select a unit mounting system that provides adequate height to allow installation of condensate trap per requirements. Refer to Step 11 — Install External Condensate Trap and Line for required trap dimensions.
Roof Mount —
Check building codes for weight distribution requirements. Unit operating weight i s shown in Table 1.
Step 2 — Plan for Sequence of Unit Installation
The support method used for this unit will dictate different sequences for the steps of unit installation. For example, on curb--mounted units, some accessories must be installed on the unit before the unit is placed on the curb. Review the following for recommended sequences for installation steps.
Curb--mounted installation —
Install curb Install field--fabricated ductwork inside curb Install thru-- base service connection fittings (affects
curb and unit) Rig and place unit Remove top skid Install outside air hood Install smoke detector tube Install combustion air hood Install flue hood Install gas piping Install condensate line trap and piping Make electrical connections Install other accessories
Pad--mounted installation —
Prepare pad and unit supports Rig and place unit Remove duct covers and top skid Install smoke detector return air sensor tube Install field--fabricated ductwork at unit duct openings Install outside air hood Install combustion air hood Install flue hood Install gas piping Install condensate line trap and piping Make electrical connections Install other accessories
Frame--mounted installation —
Frame--mounted applications generally follow the sequence for a curb installation. Adapt as required to suit specific installation plan.
Step 3 — Inspect unit
Inspect unit for transportation damage. File any claim with transportation agency.
Confirm before i nstallation of unit that voltage, amperage and circuit protection requirements listed on unit data plate agree with power supply provided.
On units with hinged panel option, check to be sure all latches are tight and in closed position.
Locate the carton containing the outside air hood parts; see Fig. 7 and 13. Do not remove carton until unit has been rigged and located in final position.
15
Step 4 — Provide Unit Support
A
Roof Curb Mount —
Accessory roof curb details and dimensions are shown in Fig. 8, 9 and 10. Assemble and install accessory roof curb in accordance with instructions shipped with the curb.
NOTE: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket supplied with the roof curb as shown in Fig. 8, 9 and 10. Improperly applied gasket can also result in air leaks and poor unit performance.
Curb should be level. This is necessary for unit drain to function properly. Unit leveling tolerances are shown in Fig. 6. Refer to Accessory Roof Curb Installation Instructions for additional information as required.
C
A
B
Fig. 6 -- Unit Leveling Tolerances
Install insulation, cant strips, roofing fe lt, and counter flashing as shown. Ductwork must be attached to curb and
not to the unit. Thru--the--base power connection must be installed before the unit is set on the roof curb. If
field--i nstalled thru--the--roof curb gas connections are desired, remove knockout in basepan located in the gas section; see Fig. 7 for location. Gas connections and power connections to the unit must be field--installed after the unit is installed on the roof curb.
MAXIMUM ALLOWABLE
DIFFERENCE IN. (MM)
A-B
0.25” (6)
B-C
0.5” (12)
A-C
0.5” (12)
C10628
box area of access panel; see Fig. 2, 3, or 4 for basepan knockout loc ations for location. Attach the service connections to the basepan.
Hood Carton Location
(rear access panel)
Control Box
ccess Panel
Filter and
Indoor Coil
Access Panel
Indoor Blower Access Panel
Gas Heat
Access Panel
Compressor
(each side)
C11154
Fig. 7 -- Typical Access Panel and Compr es s o r Locations
Slab Mount (Horizontal Units Only) —
Provide a level concrete slab that extends a minimum of 6–in. (150 mm) beyond unit cabinet. Install a gravel apron in front of condenser c oil air inlet to prevent grass and foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if required.
Alternate Unit Support (In Lieu of Curb or Slab Mount) —
A non--combustible sleeper rail can be used in the unit curb support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 4 equally spaced 4--in. x 4--in. (102 mm x 102 mm) pads on each side. Locate pads so that they support the rail s. Make sure to avoid the fork openings.
If electric and control wiring is to be routed through the basepan, remove knockouts in basepan located in control
16
C13054
Fig. 8 -- Roof Curb Details – 14 Size Unit
17
Fig. 9 -- Roof Curb Details – 17 and 20 Size Units
C13055
18
Fig. 10 -- Roof Curb Details – 24 and 26 Size Units
C13056
19
Step 5 — Field Fabricate Ductwork
Cabinet return-air static pressure (a negative condition) shall not exceed 0.5 in. wg (87 Pa) with economizer or without economizer.
For vertical ducted applications, secure all ducts to roof curb and building structure. Do not connect ductwork to unit.
Fabricate supply ductwork so that the cross sectional dimensions are equal to or greater than the unit supply duct opening dimensions for the first 18 in. (458 mm) of duct length from the unit basepan.
Step 6 — Rig and Place Unit
Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit. Rollers may be used to move unit across a roof. Level by using unit frame as a reference. See Table 1 (on page 14) and Fig. 11 (below) for additional information.
Lifting holes are provided in base rails as shown in Fig. 11. Refe r to riggi ng instructions on unit .
!
CAUTION
Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through unconditioned spaces must be insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes.
A minimum clearance is not required around ductwork.
!
CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in damage to roofing materials.
Membrane roofs can be cut by sharp sheet metal edges. Be careful when placing any sheet metal parts on such roof.
"914-1371"
(36"-54")
"B"
SEE DETAIL A
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
All panels must be in place when rigging. Unit is not designed for handling by fork truck when packaging is removed.
Before setting the unit onto the curb, recheck gasketing on curb.
PLACE ALL SEAL STRIP IN PLACE BEFORE PLACING UNIT ON ROOF CURB.
DUCT END
DETAIL A
"A"
UNIT
48LC**14 2135 970 127.8 3249 59.1 1501 52.3 1328
48LC**17 2377 1080 141.5 3595 65.5 1664 60.3 1532
48LC**20 2483 1129 141.5 3595 65.5 1664 60.3 1532
48LC**24 2629 1195 157.8 4007 72.8 1849 60.3 1532
48LC**26 2774 1261 157.8 4007 7208 1849 60.3 1532
NOTES:
1. Dimensions in ( ) are inches.
2. Hook rigging shackles through holes in base rail, as shown in detail “A .” Holes in b ase rails are centered around the unit center of gravity. Use wooden top to prevent rigging straps from damaging unit.
MAX WEIGHT
LB KG IN MM IN MM IN MM
"C"
C09107
DIMENSIONS
A B C
Fig. 11 -- Rigging Details
20
PositioningonCurb—
r
Position unit on roof curb so that the following clearances are maintained: curb and the base rail inside the right and left,
1
/4in. (6 mm) clearance between the roof
1
/2in. (12 mm) clearance between the roof curb and the base rail inside the front and back. This will result in the distance between the roof curb and the base rail inside on the condenser end of the unit being approximat ely equal to Details A and B in Fig. 8, 9 and 10.
Do not attempt to slide unit on curb after unit is set. Doing so will result in damage to the roof curb seal.
Although unit is weatherproof, guard against water from higher level runoff and ove rhangs.
Flue vent dischar ge must have a minimum horizontal clearance of 48 in. (1220 mm) from electric and gas meters, gas regulators, and gas relief equipment. Minimum distance between unit and other electrically live parts is 48 inches (1220 mm).
Flue gas can deteriorate building materials. Orient unit such that flue gas will not affect building materials . Locate mechanical draft system flue assembly at least 48 in. (1220 mm) from an adjacent building or combustible material.
Field--supplied(3/4--inch) flanges should be attached to horizontal duct openings (see Fig. 12) and all ductwork should be secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof or building openings with counter flashing and mastic in accordance with applicable codes.
Step 8 — Install Outside Air Hood — Factory Option
The outside air hood for factory--option economizer is shipped in knock--down form and requires field assembly. The panel for the hood top is shipped on the end of the unit (see Fig. 13). The remaining parts for the hood assembly (including side panels, filters and tracks) are shippedinacartonthatissecuredtotherearoftheblower assembly. Access the carton location through rear panel (see Fig. 14).
Hood Top
Shipping Position
After unit is in position, remove rigging skids and shipping materials.
Step 7 — Horizontal Duct Connection
Refer to Fig. 2, 3 and 4 for locations and sizes of the horizontal duct connections. Note that there are two different return air duct connection locations – one for unit without an economizer (on back side of unit) and a different one for unit equipped with an economizer (on left end, under the economizer hood). The supply air duct connection is on the back side. See Fig. 12 for top view depicting typical horizontal duct arrangements.
C09134
Fig. 13 -- Hood Top – Shipping Position
To remove the hood parts package:
1. Remove the back blower access panel.
2. Locate and cut the strap, being careful to not damage any wiring.
3. Carefully lift the hood package carton through the back blower access opening.
See Fig. 15 for identification of the various parts of the hood assembly.
Hood
Package
Horizontal Supply Air
Supply
Location Back Back Left end
H e i g h t --- I n . ( m m ) 157/8(402) 493/8(1253) 183/8(467)
W i d t h --- i n . ( m m ) 293/4(756) 233/8(593) 615/8(1564)
Return Air Duct
Return without
Economizer
Fig. 12 -- Horizontal Duct Opening Dimensions
without
Economizer
Return Air Duct
with Economize
Return with
Economizer
C10626
C09133
Fig. 14 -- Hood Package – Shipping Location
21
To assemble the outside air hood:
A
1. Remove hood top panel from shipping position on unit end.
2. Install four angles to the upper end panel using the screws provided.
3. Apply seal strip to mating flanges on the side plates of the hood (see Fig. 15).
pply Seal Strips to the back of these flanges
2
Seal Strips
5
Apply Seal Strip to the front of this flange
6
Apply Seal Strips to the back of these surfaces
7
4
Item # Description Qty 1 Angles 4 2 Side Plates 2 3 Hood 1 4 Outdoor Air Screens 4 5 Side Filter Supports 2 6 Side Drip Angles 2 7 Top Diverters 2
4
1
3
7
4
Apply Seal Strip to the back of this flange
Apply Seal Strip to the front of this flange
4
C09079
Fig. 15 -- Hood Part Identification and Seal Strip
Application Areas
Step 9 — Install Flue Hood and Combustion Air Hood
The flue hood is shipped screwed to the fan deck inside the burner compartment. Remove the burner access panel and then rem ove the flue hood from i ts shipping location. Using the screws provided, install flue hood in the location shown in Fig. 17.
The combustion air hood is attache d to the back of the burner access panel. Remove the two screws securing the hood to the back of the burner access panel. Using the two
2
5
6
screws, re--attach the hood to the front of the burner access panel as shown in Fig. 17.
4. Secure side plates to panel using the screws provided.
5. Apply seal strip to mating flange of the hood (see Fig. 15).
Combustion
Air Hood
Flue Hood
C10744
Fig. 17 -- Flue Hood and Combustion Air Hood Details
6. Secure top flange using screws provided in kit.
7. Install outdoor air screens by sliding them into the channel formed by the four angles install ed in step 2. Make sure that the screens extend across the entire length of the hood.
8. Install side filter supports using the screws provided.
9. Install side drip angles using the screws provided.
10. Run a continuous length of seal strip across the hood covering the engagement holes in the lower hood.
11. Install top diverter using the screws provided.
12. On units with barometric relief, remove screws at bot­tom of relief damper. Do not discard damper door.
C09090
Fig. 16 -- Hood Assembly – Completed
22
Step 10 — Install Gas Piping
Installation of the gas piping must be in accordance with local building codes and with applicable national codes. In U.S.A., refer to NFPA 54/ANSI Z223.1 National Fuel Gas Code (NFGC). In Canada, installation must be accordance with the CAN/CSA B149.1 a nd CAN/CSA B149.2 installation codes for gas burning appliances.
This unit is factory equipped for use with Natural Gas fuel at elevations up to 2000 ft (610 m) above sea level. Unit may be field converted for operation at elevations above 2000 ft (610 m) and/or for use with liquefied petroleum fuel. See accessory kit installation instructions regarding these accessories.
NOTE: Furnace gas input rate on rating plate is for installation up to 2000 ft (610 m) above sea level. In U.S.A. the input rating for altitudes above 2000 ft (610 m) must be derated by 4% for each 1000 ft (305 m) above sea level.
For natural gas applications, gas pressure at unit gas connection must not be less than 5 in. wg (1246 Pa) or greater than 13 in. wg (3240 Pa) while the unit is operating. For liquified petroleum applications, the gas pressure must not be less than 11 in. wg (2740 Pa) or greater than 13 in. wg (3240 Pa) at the unit connection.
T able 2 – Typical
Item Qty Description
1 1 90 Deg Street Elbow
2 1 5 Inch Long Nipple
3 1 Ground--- Joint Union
4 1 3 Inch Long Nipple
5 1 90 Deg Elbow
6 1 12 Inch Long Nipple
7 1 90 Deg Elbow
8 1 3 Inch Long Nipple
9 1 TEE
10 1 4 Inch Long Nipple (Sediment Trap)
11 1 Cap
12 1 31/2Inch Long Nipple
13 1 NIBCO* Ball Valve (GB30)
14 1 8 Inch Long Nipple
15 1 90 D eg Elbow
3
/4--in. NPT Field Supplied Piping Parts
Pipe gas supply into 90 degree elbow item 15 (see Table 2) through the hole in the unit basepan.
For typical3/4inch NPT field supplied fittings required for NON Thru--Base gas supply starting from the unit gas valve, omit items 14 and 15 from Table 2 and pipe gas supply into TEE. See Fig. 19.
4
6
5
3
2
1
Gas Supply Line —
The gas supply pipe enters the unit adjacent to the burner access panel on the front side of the unit, through the grommeted hole. The gas connection to the unit is made
3
to the
Table 2 lists typical
/4in. FPT gas inlet port on the unit ga s valve.
3
/4inch NPT (National Pipe Thread) field supplied pipe fittings required for Thru--Base gas supply, starting from the unit gas valve (see Fig. 18).
4
6
7
8
9
10
11
12
5
13
14
3
2
1
15
7
8
9
12
13
10
11
C101006
Fig. 19 -- Gas Supply Line Piping
Table 3 – Natural Gas Supply Line Pressure Ranges
UNIT MODEL UNIT SIZE MIN MAX
48LC** 14, 17, 20, 24, 26
5.0 in. wg (1246 Pa)
13.0 in. wg (3240 Pa)
Table 4 – Liquid Propane Supply Line Pressure Ranges
UNIT MODEL UNIT SIZE MIN MAX
48LC** 14, 17, 20, 24, 26
11.0 in. wg (2740 Pa)
13.0 in. wg (3240 Pa)
Fig. 18 -- Gas Supply Line Piping with Thru--Base
C10999
Manifold pressure is factory--adjusted for natural gas (NG) fuel use. Adjust as required to obtain best flame characteristics.
Table 5 – Natural Gas Manifold Pressure Ranges
UNIT MODEL UNIT SIZE HIGH FIRE LOW FIRE
48LC** 14, 17, 20, 24, 26
* NIBCO is a registered trademark of NIBCO Inc.
23
3.0 in. wg (747 Pa)
2.0 in. Wg (498 Pa)
Manifold pressure for liquid propane (LP) fuel must be
R
adjusted to specified range. Follow instructions in the accessory kit to make initial readjustment.
Table 6 – Liquid Propane Manifold Pressure Ranges
UNIT MODEL UNIT SIZE HIGH FIRE LOW FIRE
48LC** 14, 17, 20, 24, 26
48LCS* 14 only
!
CAUTION
11.0 in. wg (2740 Pa)
9.8 in. wg (2441 Pa)
7.3 in. Wg (1818 Pa)
6.5 in. Wg (1619 Pa)
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in damage to equipment.
When connecting the gas li ne to the unit gas valve, the installer MUST use a backup wrench to prevent damage to the valve.
Install a gas supply line that runs to the unit heating section. Refer to the NFPA 54/NFGC or equivalent code for gas pipe sizing data. Do not use a pipe smaller than the size specified. Siz e the gas supply line to allow for a maximum pressure drop of 0.5--in. wg (124 Pa) between gas regulator source and unit gas valve connection when unit is operating at high--fire flow rate.
The gas supply line can approach the unit in two ways: horizontally from outside the unit (across the roof), or through unit basepan. Observe clearance to gas line components per Fig. 20.
X
9” MINIMUM CLEARANCE
BASE UNIT
BASE RAIL
FOR PANEL REMOVAL
MANUAL GAS SHUTOFF VALVE
48” MINIMUM
ROOF CURB
NFGC – National Fuel Gas Code
Field supplied.
*
NOTE: Follow all local codes.
STEEL PIPE
NOMINAL DIAMETER
(in.)
1
/
2
3
/
or 1
4
1
1
/
or larger
4
LEGEND
GAS REGULATOR
*
DRIP LEG
PER NFGC
FABRICATED
SPACINGOFSUPPORTS
X DIMENSION
(ft)
6 8
10
*
*
FIELD-
SUPPORT
FROM GAS METE
*
C11121
Fig. 20 -- Gas Piping Guide
Factory--Option Thru--Base Connections —
Electrical Connections: Knockouts are located in the
control box area. Remove the appropriate size knockout for high voltage connection. Use the field supplied connector depe nding on wiring or conduit being utilized.
7
Remove the
/8--in. (22mm) knockout and appropriate
connector for low voltage wiring. If non--unit powered
7
convenience outlet is being utilized, remove the
/8-- i n . (22mm) knockout and utilize appropriate connector for 115 volt line. See “Step 12 — Make Electrical Connections” for details.
Gas Connections: Remove the knockout in the base pan
3
and route
/4--in. gas line up through the opening. Install an elbow and route gas line through opening in panel after first removing plastic bushing. Install a gas shut off followed by a drip leg and ground--joint union. Route gas line into gas section through the grommet (Part #: KA56SL112) at the gas inlet and into the gas valve. See Fig. 18 and Table 2. If a regulator is installed, it must be located 4 feet (1.22 meters) from the flue outlet.
Some municipal codes require that the manual shutoff valve be located upstream of the sediment trap. See Fig. 19 for typical piping arrangements for gas piping that has been routed through the sidewall of the base pan.
When installing the gas supply line, observe local codes pertaining to gas pipe installations. Refer to the NFPA 54/ANSI Z 223. 1 NFGC latest edition (in Canada, CAN/CSA B149.1). In the absence of local building codes, adhere to the following pertinent recommendations:
1. Avoid low spots in long runs of pipe. Grade all pipe
1
/4--in. in every 15 ft (7 mm in every 5 m) to prevent traps. Grade all horizontal runs downward to risers. Use risers to connect to heating section and to meter.
2. Protect all segments of piping system against physical and thermal damage. Support all piping with appro­priate straps, hangers, etc. Use a minimum of one hanger every 6 ft (1.8 m). For pipe sizes larger than
1
/2--in., follow recommendations of national codes.
3. Apply joint compound (pipe dope) sparingly and only to male threads of joint when making pi pe connections. Use only pipe dope that is resistant to action of liquefied petroleum gases as specified by local and/or national codes. If using PTFE (Teflon*) tape, ensure the material is Double Density type and is labeled for use on gas lines. Apply tape per manufacturer’s instructions.
4. Pressure--test all gas piping in accordance with local and national plumbing and gas codes before connect­ing piping to unit.
NOTE: Pressure test the gas supply system after the gas supply piping is connected to the gas valve. The supply piping must be disconnected from the gas valve during the testing of the piping systems when test pressure is in excess of 0.5 psig (3450 Pa). Pressure test the gas supply piping system at pressures equal to or less than 0.5 psig (3450 Pa). The unit heating section must be isolated from the gas piping system by closing the external ma in manual shutoff valve and slightly opening the ground--joint union.
Check for gas leaks at the field--installed and factory--installed gas lines after all piping connections have been completed. Use soap--and--water solution (or method specified by local codes and/or regulations).
* Teflon is a registered trademark of DuPont.
24
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
S Connect gas pipe to unit using a backup wrench to
avoid damaging gas controls.
S Never purge a gas line into a combustion chamber. S Never test for gas leaks with an open flame. Use a
commercially available soap solution made specifically for the detection of leaks to check all connections.
S Use proper length of pipe to avoid stress on gas
control manifold.
The piping for the condensate drain and external trap can be completed after the unit is in place. Hand tighten fittings to the drain pan fitting. Provide adequate support for the drain line. Failure to do so can result in damage to the drain pan. See Fig. 23.
MINIMUM PITCH 1” (25mm) PER 10’ (3m) OF LINE
TO ROOF DRAIN
BASE RAIL
OPEN VENT
3˝ (76mm)
MIN
SEE NOTE
NOTE: If orifice hole appears damaged or it is suspected to have been redrilled, check orifice hole with a numbered drill bit of correct size. Never redrill an orif ice. A bur r--free and squarely aligned orifice hole is essential for proper flame characteristics.
BURNER
ORIFICE
A93059
Fig. 21 -- Orifice Hole
Step 11 — Install External Condensate Tr ap and Line
The unit has one3/4-in. condensate drain connection on the end of the condensate pan (see Fig. 22). See Fig. 2, 3 and 4, item “E”, in the view labeled “BACK (HORIZONTAL DISCH A RG E) ” (located on sh eet 2 of 3 of each figure) for the location of the condensate drain connection.
ROOF
DRAIN PLUG
NOTE: Trap should be deep enough to offset maximum unit static difference. A 4” (102mm) trap is recommended.
CURB
C11291
Fig. 23 -- Condensate Drain Piping Details
All units must have an external trap for condensate drainage. Install a trap at least 4-in. (102 mm) dee p and protect against freeze-up. If drain line is installed downstream from the external trap, pitch the line away from the unit at 1-in. per 10 ft (25 mm in 3 m) of run. Do not use a pipe size smaller than the unit connection
3
/4-in.).
(
Step 12 — Make Electrical Connections
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Do not use gas piping as an electrical ground. Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code); ANSI/NFPA 70, latest edition (in Canada, Canadian Electrical Code CSA [Canadian Standards Association] C22.1), and local electrical codes.
CONDENSATE DRAIN CONNECTION
Fig. 22 -- Condensate Drain Pan Connection
C10729
NOTE: Field--supplied wiring shall conform with the limitations of minimum 63_F(33_C) rise.
Field Power Supply —
If equipped with optional Powered Convenience Outlet: The power source leads to the convenience outlet’s transformer primary are not factory connected. Installer must connect these leads according to required operation of the convenience out let. If an always--energized convenience outlet operation is desire d, connect the source leads to the line side of the uni t--mounted
25
disconnect. (Check with local codes to ensure this method is acceptable in your area.) If a de--energize via unit disconnect switch operation of the convenienc e outlet is desired, connect the source leads to the load side of the unit disconnect. On a unit without a unit--mounted disconnect or HACR, connect the source leads to the terminal block with unit field power leads. See Fig. 24.
BLK
YEL
BLU
LOAD
SIDE
LINE SIDE
SEE
DETAIL
A
L1
L2
L3
A
DETAIL
CONTROL BOX
C11181
Fig. 24 -- Location of TB1
Field power wires are connected to the unit at line--side pressure lugs on the terminal block (see wiring diagram
label for control box component arrangement) or at factory--installed option non--fused disconnect switch or HACR breaker. Use copper conductors only.
NOTE: Make field power connections directly to line connection pressure lugs only.
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in intermittent operation or unsatisfactory performance.
Do not connect aluminum wire between disconnect switch and air conditioning unit. Use only copper wire.(SeeFig.25.)
ELECTRIC
DISCONNECT
SWITCH
COPPER
WIRE ONLY
ALUMINUM
WIRE
A93033
Fig. 25 -- Disconnect Switch and Unit
26
Loading...
+ 58 hidden pages