What is a VVT Zone Controller? .......................................................................................................................... 1
Mounting the VVT Zone Controller ..................................................................................................................... 7
To mount the controller ........................................................................................................................ 7
Wiring the VVT Zone Controller for power ......................................................................................................... 8
To wire the controller for power ............................................................................................................ 9
To address the VVT Zone Controller ................................................................................................................... 9
Wiring the VVT Zone Controller to the MS/TP network ............................................................................... 10
Single duct only ................................................................................................................................... 22
Single duct 2-position hot water ......................................................................................................... 23
Single duct modulating hot water ...................................................................................................... 23
Single duct combination base board and ducted heat ..................................................................... 24
Single duct 2-stage electric heat ........................................................................................................ 24
Fan box 2-position hot water .............................................................................................................. 25
Fan box modulating hot water - ducted or baseboard ...................................................................... 25
Fan box combination baseboard and ducted heat ........................................................................... 26
Fan box 2-stage electric heat ............................................................................................................. 26
Wiring field-supplied actuators to the analog output ........................................................................ 27
Performing system checkout ........................................................................................................................... 35
Commissioning the VVT Zone Controller ........................................................................................................ 36
Balancing the system ........................................................................................................................................ 36
Step 1: Prepare for balancing ............................................................................................................ 37
Step 2: Balance each zone ................................................................................................................ 37
Step 3: Set the system static pressure ............................................................................................. 38
Sequence of operation .............................................................................................................................................. 40
Temperature sensors ........................................................................................................................................ 40
Zone airflow control ........................................................................................................................................... 41
Zone reheat control ........................................................................................................................................... 42
Demand control ventilation (DCV) and dehumidification using optional sensors ................................... 43
Air source mode determination....................................................................................................................... 47
Serial number ..................................................................................................................................................... 49
Replacing the VVT Zone Controller's battery ................................................................................................. 49
CE Compliance ................................................................................................................................................... 50
Unit Configuration .............................................................................................................................................. 52
Service Configuration ........................................................................................................................................ 60
Index ........................................................................................................................................................................... 71
ii VVT Zone Controller
Page 5
VVT Zone
(OPN-VVTZC)
VVT Zone
(OPN-VVTZC)
VVT Zone
(OPN-VVTZC)
VVT Zone
(OPN-VVTZC)
VVT Bypass
(OPN-VVTBP)
MANUAL ON WARMER
Occupied
INFO COOLER
F
MANUAL ON WARMER
Occupied
INFO COOLER
F
MANUAL ON WARMER
Occupied
INFO COOLER
F
MANUAL ON WARMER
Occupied
INFO COOLER
F
Introduction
What is a VVT Zone Controller?
The VVT Zone Controller (#OPN-VVTZC), a component of the i-Vu Open Control System, controls zone
®
temperature in single duct, fan powered, Variable Volume and Temperature (VVT
) applications. The VVT
Zone Controller with built-in actuator maintains zone temperature by operating the terminal fan and
regulating the flow of conditioned air into the space. Buildings with diverse loading conditions can be
supported by controlling the air source heating and cooling sources or supplemental heat. The VVT Zone
Controller provides dedicated control functions for single duct and fan box terminals with modulating heat, up
to 2 stages of ducted heat, or combination baseboard and ducted heat.
The i-Vu Open Control System uses linkage to exchange data between the zone terminals and their air source
to form a coordinated HVAC system. The system's air source controller, zone controllers, and bypass controller
are linked so that their data exchange can be managed by one zone controller configured as the VVT Master.
The following illustration shows the VVT Zone Controller in a typical i-Vu Open Control System.
VVT Zone Controller 1
Page 6
Introduction
0
134
5
2
78
9 6
0
134
5
2
78
9 6
HWV
Gnd
Analog
Output
Gnd
T55 (Opt)
RH/CO2
Gnd
SAT
Gnd
REMOTE
LED
Gnd
Rnet +
Rnet -
+12V
R n e t
BACnetPower
On
4
3
2
1
-
+
Batt
CR2032
10's
1's
Thermistor
T55 (Opt)
RH/CO2
Factory Defaults
Rnet
MSTP
Output
24V Max,
1A Max
Conductors Only
Class 2
Use Copper
26Vdc, 0.1A, 3W
14VA, 0.58A
24Vac , 50- 60 H z
This produ c t w as des ign ed
CAUTION:
to be moun t ed inside the
building envelope.Warranty
voided if mounted outside.
Interconnect the Outputs of
Diff er en t Cl ass 2 Circuits.
To ReduceThe Risk of Fire
or Electric Shock, Do Not
CAUTION:
BACnet
VVT Zone
®
AO: 0-10 Vdc
5mA Max
Local
Access
Short pins
Enable SAT
Enable SAT and REM O TE
CW CCW
Motor
Error
Run
Power
0-5Vdc
Made in USA
Inputs
TxRx
MSTP Baud
76.8k38.4k19.2k9600
Damper release bu t t on inside
TYPE: 002101
E143900
88FO
Enclosed Ener gy
Managemen t Equipment
R
Net +
Net -
Shield
Ground
24V ac
Rnet+
Sense
+12V
Rnet-
Gnd
FAN
Power for B. O.s
BUS
HEAT1
HEAT2
(OPN-VVTZC)
BT485
NOTE This document gives instructions for field-installation of a VVT Zone Controller in an i-Vu Open Control
System. However, VVT Zone Controllers are available factory-mounted to Carrier’s round and rectangular
dampers. Damper assemblies have an integrated duct temperature sensor.
2 VVT Zone Controller
Page 7
Specifications
Driver drv_vvtopen
Maximum number of control
1
programs
Power 24 Vac ±10%, 50–60 Hz
14 VA power consumption (20 VA with BACview
26 Vdc (25 V min, 30 V max)
Single Class 2 source only, 100 VA or less
BACnet port
Rnet port
For communication with the controller network using MS/TP (9600 bps, 19.2
kbps, 38.4 kbps, or 76.8 kbps)
For SPT sensors and a BACview
a daisy-chain configuration:
• 1 SPT Plus or SPT Pro
• 1–4 SPT Standards
• 1–4 SPT Standards, and 1 SPT Plus or SPT Pro
• Any of the above combinations, plus a BACview
devices total
Local Access port
For system start-up and troubleshooting using Field Assistant or BACview
(115.2 kbps)
Inputs
4 inputs for connecting the following types of sensors:
• An alternate space temperature sensor (#33ZCT55SPT)
• Supply air temperature sensor (#33ZCSENSAT)
• Duct air temperature sensor (#33ZCSENDAT)
• CO2 sensor (#33ZCSENCO2)
• Relative humidity sensor (#33ZCSENSRH-01 [indoor space] or
33ZCSENDRH-01 [duct])
•Remote occupancy sensor
Input resolution 10 bit A/D
attached)
6
in any of the following combinations, wired in
6,
but no more than 6
6
Digital outputs 3 digital outputs, relay contact rated at 1 A max. @ 24 Vac/Vdc. Configured
normally open.
Analog output 1 analog output, 0–10 Vdc (5 mA max). The controlled device must have a
minimum of 2000 Ohms resistance measured from its input to ground and
must share the same ground as the controller.
Output resolution 8 bit D/A
Integral actuator Brushless DC motor, torque 35 inch-pounds (4 Nm), runtime 205 seconds for
90 degree travel during control, or 25 seconds in high-speed test and balance
mode
Battery 10-year Lithium CR2032 battery provides a minimum of 10,000 hours of data
retention during power outages
Protection Incoming power and network connections are protected by non-replaceable
internal solid-state polyswitches that reset themselves when the condition that
causes a fault returns to normal. The power, network, input, and output
connections are also protected against voltage transient and surge events.
BT485 connector You attach a BT485 (not included) to a controller at the beginning and end of
a network segment to add bias and to terminate a network segment.
VVT Zone Controller 3
Page 8
Introduction
Status indicators LED's indicate status of communications, running, errors, power, and digital
outputs
Environmental operating
0 to 130° F (-18 to 54°C), 0 to 90% relative humidity, non-condensing
range
Storage temperature range -24 to 140°F (-30 to 60°C), 0 to 90% relative humidity, non-condensing
Physical UL94-5VA plenum rated enclosure for installation in plenum (or other space
for environmental air) in accordance with NEC Section 300.22 (c) and (d)
Overall dimensions A:
B:
C:
Mounting dimensions D:
E:
F:
G:
H:
7 in. (17.8 cm)
6-1/32 (15.4 cm)
6 in. (15.24 cm)
5-5/8 in. (14.3 cm)
4-9/16 in. (24.3 cm)
1-5/16 in. (3.3 cm.)
7/8 in. (2.2 cm)
1-5/16 in. (3.3 cm)
Panel depth 2-1/2 in. (6.4 cm) minimum
Shaft dimension Minimum shaft diameter: 3/8 in. (.95 cm.)
Maximum shaft diameter: 1/2 in. (1.27 cm)
Minimum shaft length: 1 3/4 in. (4.45 cm)
Weight 1.7 lbs (0.77 kg)
BACnet support Conforms to the Advanced Application Controller (B-AAC) Standard Device
Profile as defined in ANSI/ASHRAE Standard 135-2004 (BACnet) Annex L
Listed by UL-916 (PAZX), cUL-916 (PAZX7), FCC Part 15-Subpart B-Class A, CE
EN50082-1997
4 VVT Zone Controller
Page 9
Safety Considerations
SAFETY NOTE
Air conditioning equipment will provide safe and reliable service when operated within design
specifications. The equipment should be operated and serviced only by authorized personnel who have a
thorough knowledge of system operation, safety devices, and emergency procedures.
Good judgment should be used in applying any manufacturer's instructions to avoid injury to personnel or
damage to equipment and property.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury, death, and/or equipment damage.
Disconnect all power to the unit before performing maintenance or service. Unit may automatically start if
power is not disconnected.
Follow all local, state, and federal laws regarding disposal of equipment containing hazardous materials
such as mercury contactors.
VVT Zone Controller 5
Page 10
Installation
Installation
To install the VVT Zone Controller:
1 Mount the controller to the VVT box. (page 7)
2 Wire the controller for power. (page 8)
3 Set the controller's address. (page 9)
4 Wire the controller to the MS/TP network. (page 10)
5 Wire sensor(s) to the controller. (page 11)
6 Wire equipment to the controller's outputs. (page 21)
Field-supplied hardware
Each zone controller installation requires the following field-supplied components:
• zone terminal unit
• round or rectangular mounting bracket
• space temperature sensor
• supply air temperature sensor
• 4x2-in. electrical box
• transformer— 24 Vac, 40 VA
• two no. 10 x 1/2-in. sheet metal screws (to secure SAT sensor to duct)
• two no. 6-32 x 5/8-in. screws (to mount space temperature sensor base to electrical box)
• wiring
• bushings (required when mounting SAT sensor in a duct 6-in. or less in diameter)
Optional:
• contactors (if required for fan or electric heat)
• indoor air quality sensor
• relative humidity sensor
• 2 screws and 2 hollow wall anchors (to mount relative humidity sensor directly to wall)
• valve and actuator for hot water heat (if required)
6 VVT Zone Controller
Page 11
End view inle t
Controller
Allow 1 ft. (.3 m) clea rance
for service access
2.5 in.
(6.35
cm)
Damper ShaftVVT Box
Controller
Anti-rotation slot
O-ringBushing
Anti-rotation slot
Mounting the VVT Zone Controller
Mount the VVT Zone Controller on the zone terminal’s damper actuator shaft. For service access, allow at
least 1 foot (.3 m) of clearance between the front of the controller and adjacent surfaces.
To mount the controller
1 Turn the damper shaft to fully close the damper.
2 Remove the controller’s cover.
3 Mount the controller to the VVT box by sliding the clamp assembly onto the damper shaft.
4 Secure the controller by installing the screw provided through the anti-rotation slot's bushing and o-ring.
NOTE Center the bushing in the slot. Failure to do so may cause the actuator to stick or bind.
5 Hold down the controller’s damper release button and rotate the actuator clamp in the same direction
that closed the damper. Rotate the clamp until it stops, then rotate it back one notch.
VVT Zone Controller 7
Page 12
Installation
Damper
release
button
5/8-in. nuts
Move stop
clamp if
necessary
6 Release the button.
7 Tighten the actuator clamp to the damper shaft by tightening the two 5/16 inch nuts.
8 Hold down the damper release button and rotate the damper from fully closed to fully open. If the
damper traveled less than 90 degrees, do the following to set the actuator's fully open position:
a) Loosen the appropriate stop clamp screw. See figure below.
b) Move the stop clamp until it contacts the
edge of the actuator cam.
c) Tighten the screw.
9 Hold down the damper release button, rotate the damper to verify that it fully opens and closes, then
release the button.
Wiring the VVT Zone Controller for power
The VVT Zone Controller is powered by a Class 2 power source. Take appropriate isolation measures when
mounting it in a control panel where non-Class 2 circuits are present.
8 VVT Zone Controller
Carrier controllers can share a power supply as long as you:
• Maintain the same polarity
• Use the power supply only for Carrier Open controllers
Page 13
10's
1's
1
3
4
5
2
7
8
9
6
0
1
3
4
5
2
7
8
9
6
0
To wire the controller for power
1 Remove power from the power supply.
2 Pull the screw terminal connector from the controller's power terminals labeled Gnd and 24 Vac or Hot.
3 Connect the transformer wires to the screw terminal connector.
4 Apply power to the power supply.
5 Measure the voltage at the VVT Zone Controller’s power input terminals to verify that the voltage is within
the operating range of 21.6–26.4 Vac.
6 Connect a 4-inch (10.2 cm) wire from Gnd to the control panel.
7 Insert the screw terminal connector into the VVT Zone Controller's power terminals.
8 Verify that the Power LED is on and the Run LED is blinking.
To address the VVT Zone Controller
You must give the VVT Zone Controller an address that is unique on the network. You can address the VVT
Zone Controller before or after you wire it for power.
1 If the VVT Zone Controller has been wired for power, pull the screw terminal connector from the
controller's power terminals labeled
apply power to it.
2 Using the rotary switches, set the controller's address. Set the Tens (10's) switch to the tens digit of the
address, and set the
Ones (1's) switch to the ones digit.
EXAMPLE If the controller’s address is 25, point the arrow on the Tens (10's) switch to 2 and the arrow
on the
Ones (1's) switch to 5.
CAUTION The factory default setting is "00" and must be changed to successfully install your VVT Zone
Controller.
VVT Zone Controller 9
Gnd and 24 Vac. The controller reads the address each time you
Page 14
Installation
Wiring the VVT Zone Controller to the MS/TP network
The VVT Zone Controller communicates using BACnet on an MS/TP network segment communications at
9600 bps, 19.2 kbps, 38.4 kbps, or 76.8 kbps.
Wire the controllers on an MS/TP network segment in a daisy-chain configuration.
Install a BT485 on the first and last controller on a network segment to add bias and prevent signal
distortions due to echoing.
See the MS/TP Networking and Wiring Installation Guide for more details.
1 Pull the screw terminal connector from the controller's power terminals labeled Gnd and 24 Vac or Hot.
2 Check the communications wiring for shorts and grounds.
3 Connect the communications wiring to the BACnet port’s screw terminals labeled Net +, Net -, and
Shield.
NOTE Use the same polarity throughout the network segment.
4 Verify that the MSTP jumper is set to MSTP.
10 VVT Zone Controller
Page 15
5 Set DIP switches 1 and 2 to the appropriate baud rate. See the MSTP baud diagram on the VVT Zone
Controller. The default baud rate is 76.8 kbps.
NOTE Use the same baud rate for all controllers on the network segment.
6 Insert the power screw terminal connector into the VVT Zone Controller's power terminals.
7 Verify communication with the network by viewing a module status report.
Wiring sensors to inputs
You can wire the following sensors to the VVT Zone Controller's inputs:
• Space temperature sensor (page 12)
• Alternate space temperature sensor (page 14)
• Supply Air Temperature sensor (page 15)
• Duct Air Temperature sensor (page 16)
• CO
sensor
2
• Relative Humidity sensor (page 19)
• Remote occupancy contact sensor (page 20)
NOTE This document gives instructions for wiring the sensors to the VVT Zone Controller. For mounting and
wiring the sensors, see the Carrier Sensors Installation Guide.
Disconnect electrical power to the VVT Zone Controller before wiring it. Failure to follow this warning could
cause electrical shock, personal injury, or damage to the controller.
• Do not run sensor or relay wires in the same conduit or raceway with Class 1 AC or DC service wiring.
• Do not abrade, cut, or nick the outer jacket of the cable.
• Do not pull or draw cable with a force that may harm the physical or electrical properties.
• Avoid splices in any control wiring.
VVT Zone Controller 11
Page 16
Installation
Sensor
Part #
Features
SPT Standard
SPT Plus
•
SPT Pro
•
Wiring an SPT sensor
The VVT Zone Controller is connected to a wall-mounted space temperature sensor to monitor room
temperature.
An i-Vu Open Control System offers the following SPT sensors:
SPS
• Local access port
• No operator control
SPPL
Slide potentiometer to adjust setpoint
• MANUAL ON button to override schedule
• LED to show occupied status
• Local access port
SPP
LCD display
• MANUAL ON button to override schedule
• WARMER and COOLER buttons to adjust setpoint
• INFO button to cycle through zone and outside air temperatures,
setpoints, and local override time
•Local access port
You wire SPT sensors to the VVT Zone Controller's Rnet port. An Rnet can consist of any of the following
combinations of devices wired in a daisy-chain configuration:
• 1 SPT Plus or SPT Pro
• 1–4 SPT Standards
• 1–4 SPT Standards, and 1 SPT Plus or SPT Pro
6
•Any of the above combinations, plus up to 2 BACview
's but no more than 6 devices total
NOTES
•If you have 2 BACview
6
's, the second BACview6 must have a separate power supply with the same
ground as the controller.
•If the Rnet has multiple SPT Standard sensors, you must give each a unique address on the Rnet. See
the Carrier Sensors Installation Guide.
•If the Rnet has multiple BACviews, you must give each a unique address on the Rnet. See the BACview
Installation and User Guide.
Rnet wiring specifications
NOTE Use the specified type of wire and cable for maximum signal integrity.
1 Partially cut, then bend and pull off the outer jacket of the Rnet cable(s). Do not nick the inner insulation.
Strip about .25 inch (.6 cm) of the inner insulation from each wire.
2 Wire each terminal on the sensor to the same terminal on the controller. See diagram below.
NOTE Carrier recommends that you use the following Rnet wiring scheme:
Red
Black
White
Green
3 Verify that the Rnet jumper is set to Rnet.
+12V
Rnet-
Rnet+
Gnd
VVT Zone Controller 13
Page 18
Installation
Wiring a T55 space temperature sensor
Part #33ZCT55SPT
This wall-mounted sensor monitors space temperature and can be used instead of an SPT sensor.
Wiring specifications
Cable from sensor to controller: If <100 ft (30.5 meters) 22 AWG, unshielded
If >100 ft (30.5 meters) 22 AWG, shielded
Maximum length: 500 feet (152 meters)
To wire the T55 sensor to the controller
1 Strip the outer jacket from the cable for at least 3 inches (7.62 cm). Strip .25 inch (.6 cm) of insulation
from each wire. Cut the shield and drain wire from the cable.
2 Wire the sensor to the controller, attaching the red wire to the T55 (Opt) terminal and the black wire to
the
Gnd terminal. See diagram below.
3 Verify that the T55 (Opt) jumper is in the Thermistor position.
14 VVT Zone Controller
Page 19
Wiring a Supply Air Temperature sensor
Part #33ZCSENSAT
The VVT Zone Controller requires a temperature sensor installed in the supply air stream. The Supply Air
Temperature (SAT) sensor is used when the zone controller is equipped with ducted heating.
Wiring specifications
Cable from sensor to controller: If <100 ft (30.5 meters) 22 AWG, unshielded
Maximum length: 500 feet (152 meters)
To wire the SAT sensor to the controller
If >100 ft (30.5 meters) 22 AWG, shielded
1 Wire the sensor to the controller. See diagram below.
2 Verify that the Enable SAT jumper is on.
3 Verify that the Enable SAT and REMOTE jumper is in the left position.
VVT Zone Controller 15
Page 20
Installation
Wiring a Duct Air Temperature sensor
Part #33ZCSENDAT
The Duct Air Temperature Sensor (DAT) monitors the supply air temperature and is required for cooling and
heating air source applications on non-Carrier dampers and for stand-alone operation without ducted reheat.
Wiring specifications
Cable from sensor to controller: If <100 ft (30.5 meters) 22 AWG, unshielded
If >100 ft (30.5 meters) 22 AWG, shielded
Maximum length: 500 feet (152 meters)
To wire the DAT sensor to the controller
1 Wire the sensor to the controller. See diagram below.
NOTE Sensor wiring does not have polarity. The wires can be connected to either terminal.
2 Using electrical tape, insulate any exposed wire to prevent shorting.
3 Connect shield to earth ground (if using shielded wire to extend cable length).
4 Verify that the Enable SAT jumper is on.
5 Verify that the Enable SAT and REMOTE jumper is in the left position.
16 VVT Zone Controller
Page 21
Wiring a CO2 sensor
Part #33ZCSPTCO2LCD-01 (Display model)
Part #33ZCSPTCO2-01 (No display)
Part #33ZCT55CO2 (No display)
A CO
sensor monitors carbon dioxide levels. As CO2 levels increase, the VVT Zone Controller adjusts the
2
outside air dampers to increase ventilation and improve indoor air quality. These sensors also monitor
temperature using a 10K thermister.
A CO
sensor can be wall-mounted or mounted in a return air duct. (Duct installation requires an Aspirator
2
Box Accessory - Part #33ZCASPCO2.)
The sensor has a range of 0–2000 ppm and a linear 4-20 mA output. This is converted to 1-5 Vdc by a 250
Ohm, 1/4 watt, 2% tolerance resistor connected across the zone controller's CO2 input terminals.
NOTE Do not use a relative humidity sensor and CO2 sensor on the same zone controller.
Wiring specifications
Cable from sensor to controller: If <100 ft (30.5 meters) 22 AWG, unshielded
Maximum length: 500 feet (152 meters)
To wire the CO2 sensor to the controller
#33ZCSPTCO2
1 Wire the sensor to the controller. See appropriate diagram below.
2 Verify that the RH/CO2 jumper is set to 0-5Vdc on the VVT Zone Controller.
3 Verify the J7 jumper on the sensor is set to 0-5Vdc.
If >100 ft (30.5 meters) 22 AWG, shielded
VVT Zone Controller 17
Page 22
Installation
Wiring diagram for #33ZCSPTCO2:
#33ZCT55CO2
1 Wire the sensor to the controller. See appropriate diagram below.
2 Install a field supplied 250 Ohm 1/4 watt 2% tolerance resistor across the controller's RH/CO2 and Gnd
terminals.
3 Verify that the RH/CO2 jumper is set to 0-5Vdc on the VVT Zone Controller.
18 VVT Zone Controller
Page 23
Wiring diagram for #33ZCT55CO2:
Wiring a Relative Humidity sensor
Part #OPNSENSRH-01
The Relative Humidity (RH) sensor is used for zone humidity control (dehumidification) if the rooftop unit has
a dehumidification device. If not, the sensor only monitors humidity.
NOTE Do not use a relative humidity sensor and CO2 sensor on the same zone controller.
Wiring specifications
Cable from sensor to controller: If <100 ft (30.5 meters) 22 AWG, unshielded
Maximum length: 500 feet (152 meters)
If >100 ft (30.5 meters) 22 AWG, shielded
VVT Zone Controller 19
Page 24
Installation
To wire the RH sensor to the controller
1 Strip the outer jacket from the cable for at least 4 inches (10.2 cm). Strip .25 inch (.6 cm) of insulation
from each wire.
2 Wire the sensor to the controller. See diagram below.
3 Using electrical tape, insulate any exposed resistor lead to prevent shorting.
4 Verify that the RH/CO2 jumper is set to 0-5Vdc.
5 Set SW3 on the sensor as shown below.
Wiring a remote occupancy sensor
You can wire a normally open or normally closed dry-contact occupancy sensor to the VVT Zone Controller's
REMOTE input as shown below. The controller supplies the 24 Vac needed for the input.
20 VVT Zone Controller
Page 25
Wiring specifications
Cable from sensor to controller: If <100 ft (30.5 meters) 22 AWG, unshielded
Maximum length: 500 feet (152 meters)
Wiring equipment to outputs
Use the following wiring diagrams to wire zone terminal equipment to the VVT Zone Controller's outputs.
Single duct (page 22)
Single duct 2-position hot water (page 23)
Single duct modulating hot water (page 23)
Single duct combination baseboard and ducted heat (page 24)
Single duct 2-stage electric heat (page 24)
Fan box 2-position hot water (page 25)
Fan box modulating hot water (page 25)
Fan box combination base board and ducted heat (page 26)
Fan box 2-stage electric heat (page 26)
If >100 ft (30.5 meters) 22 AWG, shielded
Disconnect electrical power to the VVT Zone Controller before wiring it. Failure to follow this warning could
cause electrical shock, personal injury, or damage to the controller.
Wiring specifications
To size output wiring, consider the following:
•Total loop distance from the power supply to the controller, and then to the controlled device
NOTE Include the total distance of actual wire. For 2-conductor wires, this is twice the cable length.
• Acceptable voltage drop in the wire from the controller to the controlled device
• Resistance (Ohms) of the chosen wire gauge
• Maximum current (Amps) the controlled device requires to operate
VVT Zone Controller 21
Page 26
Installation
Gnd
HWV
CO2
LED
REMOTE
RH
SAT
SPT
T55 (OPT)
– – –
Wiring diagram legend
=
Ground
=
Hot water valve
=
CO
sensor
2
=
Not used
=
Remote occupancy sensor
=
Relative humidity sensor
=
Supply air temperature sensor
=
Space temperature sensor
=
Alternate space temperature sensor
Field-supplied wiring
Single duct only
22 VVT Zone Controller
Page 27
Single duct 2-position hot water
Single duct modulating hot water
VVT Zone Controller 23
Page 28
Installation
Single duct combination base board and ducted heat
Single duct 2-stage electric heat
24 VVT Zone Controller
Page 29
Fan box 2-position hot water
Fan box modulating hot water - ducted or baseboard
VVT Zone Controller 25
Page 30
Installation
Fan box combination baseboard and ducted heat
Fan box 2-stage electric heat
26 VVT Zone Controller
Page 31
Wiring field-supplied actuators to the analog output
You can wire a high-torque actuator or parallel actuators to the controller's 0–10 Vdc analog output.
High-torque actuators
You can wire one of the following Belimo actuators to the VVT Zone Controller's analog output instead of using
the controller's built-in, 35 in.-lb actuator.
NMX24-MFT P-10028 90 in.-lb actuator with 0–10 Vdc control and 0–10 Vdc feedback
AMX24-MFT P-10028 180 in.-lb actuator with 0–10 Vdc control and 0–10 Vdc feedback
1 Install the actuator according to the manufacturer's instructions.
2 Wire the actuator to the controller using the diagram below.
NOTE For proper operation and to prevent damage to the devices, use the same polarity for the actuator's
power and the VVT Zone Controller's power.
VVT Zone Controller 27
Page 32
Installation
Linked actuators
You can wire up to 4 of the following Belimo actuators to the VVT Zone Controller's analog output. Use like
actuators so that travel times and other parameters coincide.
LMX24-MFT P-10028 45 in.-lb actuator with 0–10 Vdc control
NMX24-MFT P-10028 90 in.-lb actuator with 0–10 Vdc control
AMX24-MFT P-10028 180 in.-lb actuator with 0–10 Vdc control
1 Install the actuators according to the manufacturer's instructions.
2 Wire the actuators to the controller using the diagram below.
3 Set the direction rotation switch on each actuator to CW.
IMPORTANT! If slaving 45° actuators, you must go to Properties > I/O Points > Hot Water Valve Max and
change scaling to
200 for the slave actuator to correctly track the primary actuator.
NOTE Maintain polarity if using the same power supply for more than one actuator.
28 VVT Zone Controller
Page 33
This interface...
Provides a...
i-Vu Open
Field Assistant
Virtual BACview
BACview6 Handheld
BACview6
Start-up
To start up the VVT Zone Controller, you need one of the following user interfaces. These items let you access
the controller information, read sensor values, and test the controller.
Permanent interface software
software -
1
runs on a laptop connected to controller's Local Access port
software -
1, 2
runs on a laptop connected to controller's Local Access port
keypad/display unit -
connects to controller's Local Access port
1, 2
keypad/display unit
connected to controller's Rnet port
1
Requires a USB Link (USB-L).
2
See the BACview Installation and User Guide for instructions on connecting and using the above items.
2
Configuring the VVT Zone Controller's properties
To start up the VVT Zone Controller, you need to configure the properties described in the following sections.
These properties affect the unit operation and/or control. Review and understand the meaning and purpose
of each property before changing it.
• Unit Configuration properties30 (page )
• Setpoint Configuration properties30 (page )
• Service Configuration properties33 (page )
• Linkage properties34 (page )
See Appendix A (page 51) for a complete list of the controller's points/properties.
NOTE Engineering units shown in this document in the defaults and ranges are strictly for reference. You
must enter an integer only.
Temporary interface
Temporary interface
Temporary interface
Permanent interface
VVT Zone Controller 29
Page 34
Start-up
Navigation:
Properties > Equipment > Configuration > Unit Configuration
HOME
CONFIG
UNIT
Point Name/Description
Default/Range
Heat Enable
Parallel Fan Heat On Delay
Term Type
Parallel
Term Type
Single Duct
DCV Max Vent Damper Pos
Heating Lockout Temperature
Navigation:
Properties > Equipment > Configuration > Setpoint Configuration
HOME
CONFIG
SETPOINT
Point Name/Description
Default/Range
Heating Capacity
Heating Design Temp
Cooling Capacity
Cooling Design Temp
m must run constantly to maintain comfort. This information is available in
Unit Configuration properties
i-Vu / Field Assistant:
BACview:
>
>
– The delay in reheat coming on after the zone has a
heating demand. If the
to heat the space prior to bringing mechanical reheat. If the
is
, this allows the fan time to use plenum air
is
we recommend that you set this value to 1 minute.
override the damper to. When active, the damper modulates to the temperature
control position or the IAQ override position, whichever is greater.
temperature exceeds this value. Supplemental reheat is enabled when the outside air
temperature falls below a fixed hysteresis of 2°F. This function is active only if there is
a valid network outside air temperature.
Setpoint properties
D: – Enables the reheat function.
Enable
R:
Disable/Enable
D:
15 minutes
R:
,
0 to 30 minutes
70%
D: – The maximum damper position that the IAQ function can
R:
0 to 100%
70°F
D: – Supplemental reheat is disabled if outside air
R:
-60 to 150°F
i-Vu / Field Assistant:
BACview:
>
>
temperature changes when the heating system runs at full capacity to maintain
designed occupied heating setpoint.
heating system must run constantly to maintain comfort. This information is available
in ASHRAE publications and most design references.
temperature changes when cooling system runs at full capacity to maintain designed
occupied cooling setpoint.
cooling syste
ASHRAE publications and most design references.
5°F/hr
D: – Used for Optimal Start, this is the rate at which the zone
R:
0 to 120°F/hr
0°F
D: – The geographically-based outdoor air temperature at which the
R:
-100 to 150°F
5°F/hr
D: – Used for Optimal Start, this is the rate at which the zone
R:
0 to 140°F/hr
D: – The geographically-based outdoor air temperature at which the
100°F
R:
-100 to 150°F
30 VVT Zone Controller
Page 35
Point Name/Description
Default/Range
Hysteresis
Time
Temp
Occupied heating setpoint: 70°
75.5°
70.5°
Occupied cooling setpoint: 76°
.5° hysteresis
.5° hysteresis
Learning Adaptive Optimal Start
learned
heating capacity
learned cooling capacity
Learning Adaptive
Optimal Start
Optimal Start
Learning Adaptive Optimal Start
Effective Set Points
Setpoints
Effective Setpoints
Heating –
Heating
Cooling –
Cooling
– The desired difference between the temperature at which the zone color
changes as the zone temperature departs from the acceptable range between the
heating and cooling setpoints (green) into the Cooling 1 (yellow) or Heating 1 (light
blue) and the temperature at which the zone color changes back to the acceptable
range between the heating and cooling setpoints.
For example, the following graph shows the zone color that results as the zone
temperature departs from and returns to the acceptable range in a zone with the
following settings:
•Color Change Hysteresis = .5° (applies as the temperature returns to the
acceptable range)
• Occupied cooling setpoint = 76°
• Occupied heating setpoint = 70°
D:
R:
0.5°F
0.2 to 1.0°F
achieve the occupied setpoint by the time scheduled occupancy begins. This learning adaptive algorithm uses the
algorithm calculates a learned cooling and heating capacity during the previous unoccupied time. Set the
adjustments are based on the color that is achieved when occupancy begins. Adjustment amounts are defined in the
thermographic color fields located directly above the
The Effective Setpoints graph shows the current occupied or unoccupied setpoints. If occupied, these values are the current
programmed setpoints plus the offset of any setpoint adjustment that may be in affect. If unoccupied, the values are the
programmed unoccupied setpoints.
– This function gradually adjusts the unoccupied setpoints over a specified period of time to
and
recovery period from 1 to 4 hours in
values to calculate the effective setpoints prior to the occupied start time. The
. When the
graph under
(Occupied or Unoccupied, depending on mode) The current programmed
setpoint adjusted by any offset that may be in effect.
(Occupied or Unoccupied, depending on mode) The current programmed
setpoint adjusted by any offset that may be in effect.
R:
R:
routine runs,
.
0 to 120°F
0 to 120°F
VVT Zone Controller 31
Page 36
Start-up
Learned cooling capacity
Learned heating capacity
Min Setpoint Separation
Optimal Start
NOTE
Properties
Equipment
Maintenance
Occupancy
BAS On/Off
Unoccupied
Occupied
Optimal Start Type
None*
Temp Compensated*
Learning Adaptive Start – Unit gradually changes to occupied setpoints by adjusting the
*
None
Temp Compensated
Heat Start K factor (min/deg)
Optimal Start Type
Temp Compensated
Cool Start K factor (min/deg)
Optimal Start Type
Temp Compensated
Standby Offset
Occupied RH Control Setpoint
Optional Sensor Type
RH Sensor
RH
Control
Enable
Cool
Vent
Cooling
Vent
DCV Start Ctrl Setpoint
Optional Sensor Type
IAQ Sensor
DCV Control
Enable
DCV Max Ctrl Setpoint
DCV Max Vent Damper Pos
– The cooling capacity learned by Learning Adaptive Optimal
Start that is required to bring the space temperature down to the occupied cooling
setpoint prior to the occupied time.
– The heating capacity learned by Learning Adaptive Optimal
Start that is required to bring the space temperature up to the occupied heating
setpoint prior to the occupied time.
heating and cooling setpoints.
– The earliest time, prior to occupancy, at which the Optimal Start
function may begin to adjust the effective setpoints to achieve the occupied setpoints
by the time scheduled occupancy begins. Enter 0 to disable Optimal Start.
Optimal Start is automatically disabled when
>
>
is set to either
>
or
>
.
– The method used to change from unoccupied to occupied
setpoint.
Options:
– Unit will not change to occupied setpoint until the scheduled time or the unit
goes into an occupied mode. Setpoints do not ramp, but change immediately from
unoccupied to occupied values.
– Unit changes to occupied setpoints at a variable time prior to
the occupied time, which is calculated by the current error between space temperature
and the appropriate heating or cooling setpoint. At that time, the setpoints do not ramp,
but change immediately from unoccupied to occupied values.
D: – Minimum separation that must be maintained between the
4°F
R:
2 to 10°F
D:
1 hr
R:
0 to 4 hr
D:
Temperature
Compensated
None
R:
Temperature
Compensated
Learning Adaptive
unoccupied setpoints over a specified period of time to achieve the occupied setpoint
by the time scheduled occupancy begins.
Optimal Start transition factors to 0.
the time in minutes per degree that the equipment starts before the occupied period
when the space temperature is below the occupied heating setpoint (including any
setpoint offset).
time in minutes per degree that the equipment starts before the occupied period when
the space temperature is above the occupied cooling setpoint (including any setpoint
offset).
space occupancy sensor indicates that the space is unoccupied. If 0, the unoccupied
setpoints are used.
source mode must be
before the dehumidification function can be active.
is set to
control function. This value should be set to approximately 75 ppm above the outdoor
air CO2 level.
to control the damper to its
When selecting
is set to
or
– If
– If
– If
, you MUST set all Learning Adaptive
is
is
is set to
and
, this is the relative humidity setpoint during occupancy. The air
or
– If
and the terminal mode must be
is set to
or
and
, this is the value that the CO2 sensor must exceed to begin the DCV
– The value that the CO2 level must exceed for the IAQ function
.
15.00
D: , this is
R:
0 to 99
15.00
D: , this is the
R:
0 to 99
0°F
D: – The value by which the occupied setpoints are expanded when the
R:
0 to 15°F
D:
65%rh
R:
0 to 100%rh
D:
500ppm
R:
0 to 5000ppm
D:
1050ppm
R:
0 to 5000ppm
32 VVT Zone Controller
Page 37
Parallel Fan ON Value
Terminal Type
Parallel Fan
Occupied Min Airflow
Navigation:
Properties > Equipment > Configuration > Service Configuration
HOME
CONFIG
SERVICE
Point Name/Description
Default/Range
Terminal Type
Damper Size (in.)
Damper Area (sq.in.)
External Actuator Enable
Heat Type
None
Modulating
Two Position
Staged EH
Combination
Ducted Heat
Heat Type
Combination
Yes
Number of Heat Stages
Heat Type
Staged EH
Valve Type
– If
is
and the zone does not require
heating, when the zone’s airflow control setpoint decreases below this value, the
parallel fan turns on to increase airflow, ventilation, and prevent cold air dumping into
the zone. If the airflow control setpoint rises above this value by more than 1 cfm, the
parallel fan turns off. We recommend this value be set to approximately 10% above the
setpoint. Set to 0 to disable this function.
Service Configuration properties
i-Vu / Field Assistant:
BACview:
>
demand. If the zone damper is round, enter its diameter. If rectangular, enter 0.
demand. If the damper is rectangular, enter its area (width x height). If the damper is
round, enter 0.
external high-torque or slave actuator. Enabling this setting disables the output for
Modulating Hot Water or Combination reheat functions.
– The type of supplemental reheat that the zone controller will control. The
heat may be used with system heat, depending on the space temperature demand.
Options:
– no heat
– ducted or baseboard modulating hot water
– two position hot water
– ducted or baseboard electric heat
– combination baseboard modulating hot water and ducted staged
electric heat
– Determines whether the zone is using ducted heat or baseboard. If
is
, set this field to
for ducted heat.
>
D:
0 cfm
R:
0 to 99999 cfm
D: – The type of zone terminal that the controller is installed on.
Single Duct
R:
Single Duct
Parallel
Series Fan
D: – Used by the VVT Master to calculate the weighted average
6.00 in.
R:
0 to 100.00 in
0 sq.in.
D: – Used by the VVT Master to calculate the weighted average
R:
0 to 9999 sq.in.
D: – Enable if the controller's analog output is used for an
Disable
R:
Enable/Disable
D:
None
R:
None
Modulating
Two Position
Staged EH
Combination
D:
Yes
R:
Yes/No
– The number heat stages when the
Fan powered terminals are limited to no more than 2 stages.
power applied to the valve.
VVT Zone Controller 33
is
D: .
Two stages
R:
One stage
Two stages
Three stages
D: – Two Position hot water only - The hot water valve's position with no
NC
R:
NC/NO (normally
closed/normally open)
Page 38
Start-up
Point Name/Description
Default/Range
Optional Ctrl Type
RH/CO2
RH Control –
IAQ Control
PD (Pressure Dependent) Control:
Direction Clockwise
Damper Actuator
Built-in actuator
Cooling Min Damper Position
Cooling Max Damper Position
Reheat Min Damper Position
Cooling Min Damper Position
Heating Min Damper Position
Heating Max Damper Position
Vent Position
– The type of sensor used on the controller's
setting determines the control function that is used to override the damper operation.
Options:
zone dehumidification
– Indoor Air Quality control
the damper's position when it rotates clockwise.
controls to when the air source mode is Cooling, Vent, or Free Cooling and the
– If
is set to
space requirements for cooling are at a minimum. We recommend that you set this
no lower than 10%.
controls to when the air source mode is Cooling, Vent, or Free Cooling and the
space requirements for cooling are at a maximum.
desired damper position at which the reheat will provide optimum performance.
This value is compared to the
– For Single Duct units with ducted reheat. Set to the
value, and the greater
of the two values determines the damper position.
controls to when the air source mode is Heat and the space requirements are at a
minimum.
controls to when the air source mode is Heat and the space requirements are at a
maximum.
air source mode is Vent and the terminal mode is not in the Heat or Cool mode. If
Linkage is not active, the zone determines vent mode by verifying that its SAT
sensor is between 65°F and 80°F.
input. This
D:
R:
D: , set this field to
R:
D: – The minimum damper position the terminal
R:
D: – The maximum damper position the terminal
R:
D:
R:
D: – The minimum damper position the terminal
R:
D: – The maximum damper position the terminal
R:
D: – The ventilation damper position the terminal controls to when the
R:
None
None
RH Control
IAQ Control
Closed
Open/Closed
20%
0 to 100%
100%
0 to 100%
45%
0 to 100%
20%
0 to 100%
20%
0 to 100%
50%
0 to 100%
Linkage properties
The i-Vu Open Control System uses linkage to exchange data between the zone terminals and their air source
to form a coordinated HVAC system. The system's air source controller, zone controllers, and bypass controller
are linked so that their data exchange can be managed by one zone controller configured as the VVT Master.
The system can have a maximum of 31 zone controllers (VVT Master and slave controllers).
The linked controllers must be sequentially addressed. The VVT Master must have the highest address, the
bypass controller the next lower address, and then the slave zone controllers.
To set up linkage, you must define the properties below only for the VVT Master controller. If you are
configuring a slave controller, do not change any
After you define the properties, the VVT Master immediately begins to send zone data to the air source and
receive information from the air source.
34 VVT Zone Controller
Linkage settings as the defaults are for a slave.
Page 39
i-Vu / Field Assistant:
Navigation:
Properties > Equipment > Linkage
HOME
CONFIG
LINKAGE
Point Name/Description
Default/Range
Linkage Collector
Number of Providers
Linkage Provider
Network Number
Address
Network Number
Address
Linkage Zone Type
VAV Master
VVT Master
Linkage Callers
The minimum number of zones required to make the air source go
BACview:
>
>
– Set the
in the linked system, including the bypass and VVT Master.
– Enter the MS/TP
and MAC
of the
linked air source controller.
– Select whether the controller is a Master or a slave.
Select
if the controller is the Master or a sub-master in a VAV
application.
Select
only if the controller is the Master in a VVT application. VVT
applications do not support sub-masters.
into heating or cooling mode. 1 is typical for systems with 8 zones or less. For larger
systems, increase the number by 1 for each 6 zones. For example, 3 linkage callers
for a 20 zone system.
D: to the total number of controllers
R: 1 1 to 32
0
D:
0 to 65535
R:
0
D:
0 to 127
R:
Slave
D:
R:
Slave
VVT Master
VAV Master
D: –
R: 1 1 to 64
Performing system checkout
1 Verify that all power and communication connections are correct and tight.
2 Verify that all zone terminals, ductwork, and zone controllers are properly installed and set according to
3 Verify that all air duct connections are tight.
4 Verify that zone terminal fans and system controls operate properly. Verify that actuator screws are
5 At the zone terminals, check electrical system and connections of any optional electric reheat coil. If hot
6 Verify that all zone terminal dampers are fully open.
7 If using an air source with field-installed controls, make sure controls and sensors have been installed
8 Verify that the air source motor starter and, if applicable, the Hand/Off/Auto (HOA) switch are installed
9 Verify that the area around the air source is clear of construction dirt and debris.
10 Verify that final filters are installed in the air handler(s). Dust and debris can adversely affect system
11 Verify that the space sensor and all optional sensors are reading correctly.
VVT Zone Controller 35
installation instructions and job requirements.
properly tightened.
water reheat is used, check piping and valves against job drawings.
and wired per manufacturer installation instructions.
and wired.
operation.
Page 40
Start-up
Before starting the air source fan, make sure the zone terminal dampers are not closed. Starting the fan
with dampers closed will damage the system ductwork.
Commissioning the VVT Zone Controller
Using Field Assistant or i-Vu:
1 Calibrate the damper travel.
a) Go to
b) Click
c) Click
2 For Parallel or Series Fan terminals – in the Locks section, select the Fan's Lock value to checkbox, then
select
3 For modulating hot water reheat – Go to Properties > I/O Points tab, then lock Hot Water Valve to 100%.
If the controller is configured for Single Duct, make sure the air source fan is on. If ducted heat, verify the
heat works by verifying that the SAT rises. For baseboard heat, physically check the heating element for
proper temperature rise. Release the
4 Release the fan.
5 If the controller is part of a linked system, verify Linkage > Airside Linkage Status shows Active.
CAUTION Pressing the actuator release button and moving the damper or disconnecting the actuator ribbon
connector while the bypass controller is powered will cause the damper position to be out of calibration. To
recalibrate the damper position, you must perform steps 1a–1c above or power cycle the controller.
Properties > Configuration > Service Configuration > Pressure Dependent Control > Details
tab > Test and Balance. Click Calibrated Damper Close
Calibrated Damper Open
Automatic Control
and verify it travels to the full open.
to return the damper to normal operation.
and verify it goes to the closed position.
On in the droplist. Click Apply. Verify the fan's operation.
Hot Water Valve.
Balancing the system
Most VVT system airflow designs are based on cooling requirements which require a greater CFM flow than
heating requirements. Using this balancing procedure, you will adjust the cooling airflow first. If the heating
and cooling maximum airflow requirements are the same, you will not need to balance the heating airflow.
There are two methods of balancing the system. Using the Test & Balance program or using i-Vu/Field
Assistant. Test & Balance can perform all of the steps outlined here, including shutting down the Linked air
source and performing global commands to all zones in the system. Items 1 through 5 in Step 1 should be
done prior to using Test & Balance. Please refer to Test & Balance's Help files for details on the required
steps to complete the balancing procedure.
Complete the following steps when using i-Vu or Field Assistant to perform the system balancing.
NOTE We recommend that the heating minimum airflow settings for all the zones in the system be set to
maintain the air source’s design minimum heat CFM airflow across its heat exchanger to prevent damage to
the equipment.
36 VVT Zone Controller
Page 41
Step 1: Prepare for balancing
1 Log in to i-Vu with an Administrator or Installer security level, or use Field Assistant.
2 Make sure the air source and its controller have been properly started and can run as a stand-alone unit.
3 Make sure the zone and bypass controllers have been addressed, commissioned, and started.
4 Verify that a manual damper is installed upstream of the zone damper. This damper will be used to
adjust the maximum design airflow to the space when the zone damper is at 100% open. We strongly
recommend that you do not use the damper Cool or Heat Max damper configuration setting for this
purpose. Exception: If the design maximum airflow for one mode is less the other, the maximum damper
position configuration may be used to adjust the designed airflow of that mode.
5 Verify that zone controllers supplying multiple registers have manual dampers on each register branch
duct for balancing the design airflow through each register.
6 Disable the air source heating and cooling outputs using one of the following methods:
○ Physically disconnect the air source controller’s output wiring to the unit, then enable the fan.
○ In the i-Vu or Field Assistant tree, select the RTU Open or WSHP Open controller. Go to Properties >
Configuration > Service Configuration > Service Test and enable Service Test and Fan Test. Make
sure all other outputs are disabled.
Step 2: Balance each zone
1 In the i-Vu or Field Assistant tree, select the zone controller that is physically closest to the air source. Go
Properties > Equipment > Configuration > Service Configuration > Pressure Dependent Control >
to
Details tab.
2 Do one of the following:
○ Single Duct or Parallel Fan zone terminals – Click Cool Max to override the zone damper to its
maximum open position. Check the zone for design cooling maximum airflow using certified
measuring devices. Make adjustments using the manual volume damper located upstream of the
zone damper.
○ Series Fan zone terminals – Click Damper Full Close to override the zone damper to its fully closed
position. Wait 30 seconds after the damper is closed, select the
select
On in the droplist. Click Apply. You must follow this procedure to prevent the fan from turning
backwards. When the fan starts, click
Cool Max to open the zone damper to its maximum position.
Fan's Lock value to checkbox, then
Check the zone for design cooling maximum airflow using certified measuring devices. See the zone
terminal manufacturer's instructions to adjust the fan speed to meet design airflow requirements.
After you set the fan speed, verify that the zone terminal plenum air intakes do not have a positive
airflow. If so, adjust the manual volume damper located upstream of the zone damper so that the
airflow is not positive or negative.
Note the zone’s name in the tree. You will need it when setting the system static pressure setpoint.
3 Check all branch duct terminal registers for design flow. If necessary, adjust the manual volume dampers
in the branch ducts.
4 On the zone’s Pressure Dependent Control > Details tab, click Cool Min to set the zone damper to its
cooling minimum position. Type the desired damper position next to
Cool Min to adjust the airflow to the
design value. If you do not have a design value, set the value to no less the 10% for minimum ventilation.
5 Parallel Fan Zone Terminals only - To adjust Parallel Fan airflow, make sure Cool Min is active, select the
Fan's Lock value to checkbox, then select On in the droplist. Click Apply. See the zone terminal
manufacturer's instructions on adjusting the fan speed to meet design airflow requirements. When
finished, clear the
Fan's Lock value to checkbox.
6 Click Vent to set the zone damper to its ventilation position. Type the desired damper position next to
Vent to adjust the airflow to the design value. If you do not have a design value, leave the value at 50%
for minimum ventilation.
VVT Zone Controller 37
Page 42
Start-up
7 Series Fan Zone Terminals only - If the zone maximum heating airflow design requirements are the same
as cooling, the
Heating Max Damper Position should be 100%, same as the Cooling Max Damper
Position. If the heating requirement is less than the cooling requirement, type the appropriate value in
Heating Max Damper Position per the design requirements.
8 If the terminal has ducted reheat, click Reheat Min to force the zone to its reheat damper position. Type
the desired damper position next to
Reheat Min to adjust the airflow to its design reheat position.
9 If the zone maximum heating airflow design requirements are the same as cooling, skip this step. If they
are less than cooling, click
Heat Max to force the zone to its maximum heating position. Check the zone
for design heating maximum airflow using certified measuring devices. Type the damper position next to
Heat Max.
10 To set the heating minimum airflow, click Heat Min, then type the damper position. We recommend that
the sum of this setting for all zones in the system be equal to the minimum heat CFM requirements of
the air source.
11 Repeat steps 1 through 10 for each zone until all zones have been balanced.
Step 3: Set the system static pressure
For the air source to deliver the required airflow, you must set the bypass controller's static pressure setpoint
high enough to provide the demand but low enough to maintain reasonable noise levels. The bypass
controller maintains static pressure by controlling a damper or a supply fan VFD. You need the following data
to set the static pressure:
• The air source’s design maximum airflow in CFM (manufacturer’s data)
• The system’s design external static pressure (inches or water). This is the amount of static pressure that
the air source is designed to deliver at its maximum design airflow in CFM (supplied by the mechanical
design engineer).
•The maximum cooling or heating (whichever is greater) CFM requirements for all zones connected to the
air source
NOTE The air source fan must have been tested and certified that it can deliver the above requirements.
The sum of the maximum CFM requirements of all zones will generally exceed the air source's maximum CFM
rating by 10 to 20%. This is by design and based on a factor known as diversity. It works on the basis that
under normal design heating and cooling conditions, not every zone will be 100% open. Knowing this, you will
need to force open only zones whose sum CFM is equal to the unit design CFM. With the bypass damper fully
closed (0%) or supply fan VFD at 100%, the bypass controller's static pressure should be the controlling
setpoint.
To set the static pressure:
1 Starting with zone furthest from the air source and working towards it, add up the maximum design CFM
airflow of the zones until the sum equals the air source’s design CFM (+/-5%). Note each zone that you
included.
2 For each zone noted in step 1, go to Properties > Equipment > Configuration > Service Configuration >
Pressure Dependent Control > Details tab. Click Cool Max or Heat Max (whichever has the highest
design max airflow) to force the damper to its maximum open position.
3 In the tree, select the Bypass controller, then go to Properties > Equipment > Status. Note the Static
Pressure value, then go to Unit Configuration > Bypass Control > Details tab.
○If Damper Position is 0% or VFD Output is 100%, enter the static pressure in the Duct Static
Pressure Setpoint field.
○If the Damper Position is not 0% or VFD Output is not 100%, enter the static pressure +.1” in the
Duct Static Pressure Setpoint field. Wait 1–2 minutes, then verify that the Damper Position is 0% or
VFD Output is 100%. If not, repeat the process, adding .05” to the previous Duct Static Pressure
Setpoint until the Damper Position is 0% or VFD Output is 100%.
38 VVT Zone Controller
Page 43
4 For each zone in the system that was balanced, go to its Pressure Dependent Control > Details tab, then
click
Automatic Control to return the zone to normal control.
5 In the tree, select the air source controller, then do one of the following.
a) For an RTU Open or WSHP Open controller, go to
Configuration > Service Test and disable Service Test and Fan Test
Properties > Equipment > Configuration > Service
.
b) For any equipment whose wiring was disconnected to insure that only the fan only was running,
reconnect it the wires for normal operation.
CAUTION You must complete steps 4 and 5 to prevent loss of temperature control to the space and to
maintain normal operation of the system.
VVT Zone Controller 39
Page 44
Sequence of operation
Sensors
Notes
Space temperature sensors:
System
Space Temperature
Duct temperature sensors:
If the zone does not have ducted reheat, install a DAT sensor on the
Sequence of operation
The VVT Zone Controller supports 3 types of pressure-dependent terminal configurations:
• Single duct
• Series fan-powered
• Parallel fan-powered
The controller can operate as part of a linked VVT system or as a stand-alone controller.
Temperature sensors
The VVT Zone Controller supports the following temperature sensors:
• SPT Standard, Plus, or Pro
• T55
You can average up to 5 SPT communicating sensors.
Push the sensor's override button from 2 to 10 seconds to initiate a
timed override.
If a network space temperature value is used, that value must be
written to the BACnet space temperature point (system_spt) at 1 to
5 minute intervals or on a COV of 0.1°F.
To reference another zone as your space temperature input, read
the BACnet point zone_temp by using the network point
.
•Duct Air Temperature (DAT)
10K Type II.
inlet of the damper.
•Supply Air Temperature (SAT)
If the zone has ducted reheat, install an SAT sensor downstream of
the reheat source. The SAT is used in controlling the reheat.
The DAT/SAT determines the air source mode if Linkage
communication fails or if the controller is stand-alone. See Air Source Mode Determination47 (page ) for details.
See the Carrier Sensors Installation Guide for details on these sensors.
40 VVT Zone Controller
Page 45
Zone airflow control
The VVT Zone Controller provides pressure-dependent zone temperature control by modulating its built-in
damper actuator to control the flow of primary air into the zone. The controller uses PID control to calculate
the damper position based on the difference between the zone’s temperature and setpoints.
The air source mode determines if the primary air can meet the zone’s need. If the zone controller is in a
linked system, the air source mode is determined by the air source. If the zone controller is stand-alone or if
linkage communication fails, the mode is determined by the controller's SAT. See Air source mode determination (page 47). If the air source mode is the same as the zone’s local mode, the damper is
positioned between the mode’s configurable minimum and maximum damper position. If not, the damper is
positioned at the mode's minimum damper position to insure sufficient minimum airflow at the air source.
When the air source mode is Vent and the zone’s temperature demand is satisfied, the damper moves to its
Vent Position to increase airflow and ventilation to the space.
Single duct with reheat – The Reheat Min Damper Position allows an increase of primary airflow across the
terminal’s ducted heating coil when the terminal is operating its local heat while the air source mode is Cool.
This provides the ability to lower the cooling minimum airflow limits while providing the necessary airflow
when the terminal is heating to ensure design load conditions and electric heater minimum airflow.
Parallel fan terminals – The controller's Parallel Fan On Value determines when the fan turns on to increase
airflow at the zone’s diffusers and prevent cold air from dumping into the zone when the system mode is Cool.
This is achieved by increasing the volume and temperature of the air exiting the diffusers. Should the zone’s
damper close below the
primary air to increase total airflow and ventilation to the zone. The fan turns off when the damper position
opens to 1% above the setpoint.
The fan also starts in Heat mode if the zone is configured for ducted heat as described in Zone reheat control
(page 42).
Series fan terminals – The fan energizes when the air source fan is on if the zone controller is part of a linked
system or in the unoccupied heat mode and the equipment fan is off. If the zone controller is stand-alone, the
fan runs continuously. There is a fan start delay on transition to occupied, based on the
Delay. Before the fan starts, the damper closes. The damper position must be less than 5% for 10 seconds
before the fan starts to prevent the fan from starting backwards.
See Appendix B: VVT terminal modes (page 69).
Damper Actuator(s) – The VVT Zone Controller's built-in 35 in/lb actuator has a 205 second full travel time
for 90° operation. For field retrofit applications, the actuator can be adjusted for a damper stroke between
30° and 90°, and it can be configured to move clockwise (default) or counterclockwise.
If the built-in actuator's torque is insufficient for large damper applications, the VVT Zone Controller's analog
output can drive an external, 0-10 volt, high-torque actuator. Or, the controller can drive one or more
additional slave actuators. A slave actuator must be mounted and configured to fully close the damper when
the output signal is 0 volts. See Wiring field-supplied actuators to the analog output. (page 27)
Parallel Fan On Value, the parallel fan is energized to mix ceiling plenum air with the
Power Fail Start
VVT Zone Controller 41
Page 46
Sequence of operation
Zone reheat control
The VVT Zone Controller can be configured for one of the following Heat Types to meet the zone's heating
requirements:
• Modulating Hot Water/Steam
• Two Position Hot Water/Steam
• Staged Electric Heat (2 stages for Series/Parallel Fan, 3 stages for Single Duct.)
• Combination Modulating Baseboard/Staged Electric Heat (2 stages for Series/Parallel Fan, 3 stages for
Single Duct.)
All of the above except Combination Modulating Baseboard/Staged Electric Heat can be ducted or nonducted (baseboard). For ducted heat and Combination Modulating Baseboard/Staged Electric Heat, an SAT
sensor (33ZCSENSAT) must be installed in the duct downstream of the heat source. The controller has a
configurable
when the terminal’s ducted heat is operating.
If the network provides the OAT, heating can be disabled if the OAT rises above the configured Heating
Lockout Temperature.
Modulating Hot Water / Steam Heating Heat – The controller modulates a normally closed or normally open
hot water or steam valve connected to the discharge air heating coil. The valve opens and closes as needed
to meet heating requirements. For ducted heat, the terminal’s heat supplements heat from the primary air
source if it is in heating mode and is controlled so that the SAT does not exceed the
(105°F default). For baseboard heating (non-ducted heat), the valve modulates to keep the zone’s
temperature at the heating setpoint.
Two-Position Hot Water / Steam Heating Heat – The controller operates a normally closed or normally open
hot water or steam valve connected to the discharge air heating coil. The valve opens and closes as needed
to meet heating requirements. For ducted heat, the terminal’s heat supplements heat from the primary air
source if it is in the heating mode and is controlled so that the SAT does not exceed the
SAT (105°F default). For non-ducted (baseboard) heating, the valve is controlled to keep the zone’s
temperature at the heating setpoint.
Electric Auxiliary Heat – The controller operates 1 or 2 stages of electric heat. For ducted heat, the terminal’s
heat supplements heat from the primary air source if it is in the heating mode and is controlled so that the
SAT does not exceed the
the stages are controlled as needed to keep the zone’s temperature at the heating setpoint.
Combination Modulating Baseboard / Electric Heat – The controller can modulate a normally closed or
normally open hot water or steam valve connected to a perimeter baseboard radiation system and control up
to 2 stages of ducted electric heat. The valve modulates as needed to meet heating requirements. If the valve
cannot meet the load, electric heat is used. The terminal’s electric heater supplements heat from the primary
air source if it is in heating mode and is controlled so that the SAT does not exceed the
SAT (105°F default).
Parallel Fan Heat On Delay – For Parallel Fan terminals only, the controller has a configurable Parallel Fan
Heat On Delay to save energy. During the delay (15 minute default), only the fan operates to recycle heat
from the ceiling plenum. If the heating requirement is not met by the end of the delay, reheat is enabled.
Fan Heat Off Delay – For fan-powered terminals, the controller has a configurable Fan Off Delay. After the
heating coil de-energizes, the fan continues to run for the length of the delay to deliver to the zone any heat
stored in the coil. The default delay of 2 minutes is optimal for ducted hot water coils. For ducted electric heat
coils, the nominal delay is approximately 1 minute. For baseboard and non-ducted heat, the delay should be
set at 0.
This feature applies to parallel fan terminals in both occupied and unoccupied mode and series fan terminals
in the unoccupied mode if the air source fan is off.
Maximum Heating SAT for supply air temperature control. The zone controller monitors the (SAT)
Maximum Heating SAT
Maximum Heating
Maximum Heating SAT (105°F default). For non-ducted (baseboard) electric heat,
Maximum Heating
42 VVT Zone Controller
Page 47
Demand control ventilation (DCV) and dehumidification using optional
sensors
The VVT Zone Controller’s RH/CO2 input supports an optional CO2 sensor or Relative Humidity (RH) sensor.
The sensor can have a 5-volt maximum output. The range is configurable as either 0–5 or 1–5 volts (1–5 volt
supports 4–20 mA sensors with a 250 ohm resistor). The controller's low and high sensor input configuration
allows for a wide range of sensors.
The controller can also support both DCV and dehumidification functions, by using a system RH or CO2 sensor
input connected to another controller.
NOTE If the connected sensor and/or system sensor value are used by the air source through Linkage, set
the appropriate control type to
or
Maximum RH Override Airflow to 0.
Demand Control Ventilation (DCV) – Requires CO2 sensor
The zone controller monitors the CO2 sensor and can override the temperature control to respond to
increasing CO2 levels when the zone is occupied. If the sensor’s value exceeds the
and the air source is in cooling or ventilation mode, the controller increases airflow to the zone at a base rate
defined by ASHRAE, and then proportionally increases ventilation if the CO2 level continues to increase. If the
sensor's value exceeds the
Damper Position.
When the zone is unoccupied, the Cooling Min Damper Position and Heating Min Damper Position provide
base ventilation.
If the controller is configured for reheat, the heating setpoint is temporarily increased to a value halfway
between the heating and cooling setpoints. If the zone temperature drops below the heating setpoint, the DCV
override is temporarily suspended and the damper returns to normal control until the zone temperature is
satisfied.
Dehumidification – Requires RH sensor
The zone controller monitors the RH sensor and can provide dehumidification if the sensor's value exceeds
the
Occupied RH Control Setpoint. If the zone is occupied and does not require heating, and the air source is
operating in a cooling mode and providing primary air with a sufficiently low dew point, the controller
overrides the damper control to increase airflow to the zone. During the dehumidification mode, the heating
setpoint is temporarily increased to a value halfway between the heating and cooling setpoints to prevent
overcooling the zone. The controller uses a PID control loop to provide dehumidification. The controller has a
Maximum RH Override Airflow setting to prevent excessive airflow during dehumidification.
NOTE If both control functions are enabled, the zone will control to the greatest calculated damper position of
the three values (temperature, RH, or IAQ
Enable. If you do not need local control at the zone, set DCV Max Vent Airflow
DCV Start Ctrl Setpoint
DCV Max Ctrl Setpoint, the controller modulates the damper to its DCV Max Vent
VVT Zone Controller 43
Page 48
Sequence of operation
Occupancy
The VVT Zone Controller's operation depends on the zone's occupancy state as determined by occupancy
schedules or a remote occupancy override.
Occupancy Schedules – An occupancy schedule can be one of the following:
• A local schedule set up directly in the controller using a BACview or Field Assistant.
• A network schedule from an i-Vu internal router. The VVT Zone Controller must be networked to an i-Vu
Open Router or an i-Vu internal router.
•A System Occupancy network point. This point links the controller occupancy to another controller in the
network so that multiple zones can follow the occupancy of another VVT Zone or other controller on the
network.
To set up occupancy schedules, you first define a schedule for each day of the week and then define
schedules for the exceptions, such as holidays. The exceptions can be based on a date, a date range, or a
week and day.
NOTES
• The Occupancy Schedules
• A network schedule downloaded from i-Vu will overwrite a local schedule that was set up in a BACview or
Field Assistant.
Remote Occupancy Override – The controller monitors its Remote input that is typically connected
to the isolated, dry contact of an occupancy sensor located in the zone. The controller can override the
occupancy state based on whether or not the space is actually occupied. If the occupancy sensor contact is in
the same state as
schedule. If the contact is in the opposite state, it overrides the zone into the unoccupied mode. The input
can be configured for normally closed or normally opened contact types and is set to Open by default so that
it does not affect the controller occupancy operation if left unused.
Occ Override Normal Logic State setting, the zone follows its normal occupancy
property must be enabled (default).
Learning Adaptive Optimal Start – This function gradually adjusts the unoccupied setpoints over a
specified period of time to achieve the occupied setpoint by the time scheduled occupancy begins. This
learning adaptive algorithm uses the learned heating capacity and learned cooling capacity
values to calculate the effective setpoints prior to the occupied start time. The algorithm calculates a learned
cooling and heating capacity during the previous unoccupied time. Set the Learning Adaptive
Optimal Start
Optimal Start
Adjustment amounts are defined in the thermographic color fields located directly above the
Points
graph under Setpoints.
BAS On/Off
Schedules
recovery period from 1 to 4 hours in Optimal Start. When the Learning Adaptive
routine runs, adjustments are based on the color that is achieved when occupancy begins.
Effective Set
– This function allows third party control of the controller occupancy. Occupancy
must be set to Disable to use this function. When set to Occupied or Unoccupied,
Optimal Start is automatically disabled.
44 VVT Zone Controller
Page 49
Alarms
Space Temp Sensor Alarm – The VVT Zone Controller monitors each space temperature sensor and the
network input for space temperature. If no valid space temperature value is available, the controller
generates an alarm and disables all local heating or cooling. The controller modulates the damper to the
minimum heat, minimum cool, or ventilation position based on the air source mode. Normal operation
resumes when the controller detects a valid sensor value.
Space Temperature Alarm – The controller generates an alarm if the space temperature exceeds the alarm
setpoint. The occupied alarm setpoint is the configurable
Occupied Alarm Hysteresis (5°F default) subtracted
from and added to the configured occupied heat and cool setpoints. The configurable unoccupied high and
low alarm setpoints have a fixed 10 minute alarm delay. When a transition from unoccupied to occupied
occurs or the occupied temperature setpoints are changed, causing an alarm condition, the controller
automatically calculates an alarm delay of 10 minutes for each degree of change. The delay prevents
unnecessary alarms and gives the zone time to correct the alarm condition. The alarm returns to normal
when the space temperature goes between the current mode’s setpoints.
Supply Air Temperature Alarm – The controller generates an alarm if the SAT exceeds the configured High
SAT Alarm Limit (120°F default) or falls below the Low SAT Alarm Limit (45°F default) for more than 5
minutes. The hysteresis for return to normal is 1°F.
Space Relative Humidity Alarm – If a Space Relative Humidity (RH) sensor is installed, the controller
generates an alarm if the sensor's value exceeds the
Occ High RH Alarm Limit (100% rh default) or the Unocc
High RH Alarm Limit (100% rh default). The controller provides a 30-minute alarm delay during unoccupied
periods. During occupied periods, the controller uses the
OccHigh RH Alarm Limit. When a transition from
unoccupied to occupied occurs or the occupied high alarm limit is lowered causing an alarm condition to
occur, the controller automatically calculates an alarm delay of 5 minutes per %RH multiplied by the amount
of the change. The delay prevents unnecessary alarms and gives the zone time to correct the alarm condition.
The hysteresis for return to normal is 3% RH.
Indoor Air Quality Alarm – If a CO2 sensor is installed, the controller generates an alarm during occupied
periods if the sensor's value exceeds the Occupied High CO2 Alarm Limit. When a transition from unoccupied
to occupied occurs, or if the occupied alarm limit is changed to a value that causes an alarm condition to
occur, the controller automatically calculates an alarm delay based on the error from setpoint (15 minutes
minimum, 4 hours maximum). The delay prevents unnecessary alarms and gives the zone time to correct the
alarm condition. To disable the IAQ alarm, set
Occupied High CO2 Alarm Limit to 0. The default value is
1100ppm. The hysteresis for return to normal is 100ppm.
Filter Alarm – For series or parallel fan-powered terminals, the controller monitors the accumulated hours of
fan operation and generates an alarm when the
Filter Runtime hours exceed the configured Filter Service
Alarm Timer limit. The default value is 0 hours which disables the alarm. The alarm can be reset by setting
Reset Filter Alarm to On or resetting the configured alarm limit to 0 hours.
Airside Linkage Alarm – The slave zone controller generates an alarm if it does not receive linkage
information for 5 minutes. If the controller is the VVT Master, it generates an alarm if it does not communicate
with its air source for 5 minutes. A return-to-normal is generated after successful Linkage communication
resumes.
VVT Zone Controller 45
Page 50
Sequence of operation
Demand limiting
Demand limiting is a cost-saving strategy to reduce energy consumption. The strategy expands the setpoints
when the system reaches one of 3 levels of consumption. With the expanded setpoints, the equipment works
less, thereby saving energy.
If the VVT Zone Controller receives a demand limit signal through the network, it expands its setpoints based
on the demand level. The default amount is 1°F for demand level 1, 2°F for demand level 2, or 4°F for
demand level 3.
Linkage
The i-Vu Open Control System uses linkage to exchange data between the zone terminals and their air source
to form a coordinated HVAC system. The system's air source controller, zone controllers, and bypass controller
are linked so that their data exchange can be managed by one zone controller configured as the VVT Master.
The VVT Master gathers the following information from the slave zone controllers: occupancy status,
setpoints, zone temperature, relative humidity, CO
Master performs mathematical calculations and algorithms on the data and then sends the composite
information to the air source. The VVT Master receives information from the air source such as mode, supply
air temperature, and outside air temperature, if present, and passes that information to all linked controllers.
The VVT Master determines system operation by prioritizing heating and cooling requirements from all the
zones based on their occupancy and demand. The VVT Master scans the system continuously to determine if
any zones are occupied. Occupied zones are a higher priority than unoccupied zones. The VVT Master
evaluates all the occupied zones' heating or cooling demands and sends a request to the air source for:
•Cooling, if the number of occupied zones with cooling demands exceeds the number of occupied zones
with heating demands, and the demand is greater than or equal to the number of configured
Callers
.
•Heating, if the number of occupied zones with a heating demand exceeds or is equal to the number of
Linkage Callers
.
If no zones are occupied or no occupied zones require heating or cooling, the VVT Master performs the
evaluation described above for the unoccupied zones.
The VVT Master then gathers the following information and sends it to the air source:
•The setpoints and zone temperature from the zone with the greatest demand for the requested air
source mode (heating or cooling). (This zone is called the reference zone.)
• The system occupancy status
• Most open damper position from any zone
• RH and CO
values (if applicable)
2
The air source responds by sending the air source mode, supply air temperature, and outside air temperature.
The air source verifies the mode by comparing its supply air temperature to the space temperature received
through Linkage. See the air source documentation for operation and parameters used to verify its mode.
This verification allows the VVT system to determine if the desired air source mode is actually being provided.
For example, if the VVT Master sends a request for heating and the air source does not have heat or it’s heat
has failed, the air source's actual mode indicates that and its current mode is sent to the zones so that they
can control accordingly.
The system remains in that mode until all zones of that demand are satisfied or until a fixed 30 minute mode
reselect timer causes a forced re-evaluation of the system. If there is no demand for the opposite mode, the
reselect timer starts again and the current mode continues until all zones are satisfied or until the reselect
timer expires, repeating the process. If there is a demand for the opposite mode, the VVT Master sends the
reference zone's space temperature and setpoints to the air source and restarts the reselect timer. The air
source re-evaluates its demand based on the new information and goes to the Vent mode until the new mode
can be verified as described above. The amount of time this takes is determined by the air source’s operating
parameters.
level, damper position, and optimal start data. The VVT
2
Linkage
46 VVT Zone Controller
Page 51
The VVT Master continuously evaluates the system and updates the air source with the most current system
demand. Based on the evaluation, the reference zone can change from one zone to another. The evaluation
process continues until there is no demand from any zone or the 30 minute timer causes a re-evaluation of
the system conditions.
If no heating or cooling is required or the current air source mode is satisfied, the VVT Master calculates the
weighted average of the occupied and unoccupied heating and cooling setpoints. It also calculates a zone
temperature that is midway between the setpoints (occupied or unoccupied based on the system’s current
occupancy status). This information, plus the occupancy status, is sent to the air source so that its current
mode is disabled and the unit ceases heating or cooling operation. If the system is occupied, the air source
fan and OA damper, if applicable, operate to maintain proper ventilation.
Air source mode determination
Linked air source modes – In a linked system, the air source determines its operating mode and qualifies
that mode based on its own SAT. The following modes can be sent by the air source depending on its
configuration:
• OFF – Air source fan is off.
• WARMUP – Air source fan is on and providing first cycle of heat when changing from unoccupied to
occupied.
• HEAT – Air source fan is on and providing heat.
• FREECOOL – Air source fan is on and providing cooling using economizer only.
• COOL – Air source fan is on, and cooling is provided by economizer and mechanical cooling.
• PRESSURIZATION – Fire-Life safety override input is active. Air source fan is on providing 100 percent
outside air. Mechanical heating and cooling may be disabled.
• EVACUATION/SHUTDOWN – Fire-Life safety override input is active. Air source fan is off.
• VENT – Air source fan is on, economizer providing ventilation without heating or cooling, providing neutral
supply air temperature.
See the air source’s installation manual for specific operation.
Local air source modes – If the zone controller is stand-alone, or if linkage communication fails, the zone
controller assumes that the fan is always on and monitors its SAT sensor to determine if the primary air
source is providing heating, cooling, or recirculating air in a fan-only or ventilation mode.
•HEAT – For Series or Parallel Fan controllers when the zone terminal fan is off or for single duct
controllers: The zone’s local heat has not operated for at least 5 minutes, and the SAT is more than 5°F
warmer than the space temperature. If the terminal fan is on, the SAT must be at least 8°F more than
the space temperature.
In all cases, Heat mode is maintained until the SAT drops 2°F below the space temperature.
•VENT – The zone’s local heat has not operated for at least 5 minutes and the SAT is between 65 and
80°F.
•COOL – The zone’s local heat has not operated for at least 5 minutes, the current mode is not Heat or
Vent, and the SAT is less than 65°F.
See Appendix B: VVT terminal modes (page 69).
VVT Zone Controller 47
Page 52
Troubleshooting
If this LED is on...
Status is...
Power
Rx
Tx
DO#
CW
CCW
If Run LED shows...
And Error LED shows...
Status is...
Run
Error
Run
Troubleshooting
If you have problems mounting, wiring, or addressing the VVT Zone Controller, contact Carrier Control Systems
Support.
LED's
The LED's on the VVT Zone Controller show the status of certain functions.
The VVT Zone Controller has power
The VVT Zone Controller is receiving data from the network segment
The VVT Zone Controller is transmitting data over the network segment
The digital output is active
The Run and Error LED's indicate controller and network status.
1 flash per second
2 flashes per second
2 flashes per second 2 flashes,
2 flashes per second 3 flashes,
2 flashes per second On Two or more devices on this
2 flashes per second 1 flash per second The controller is alone on the
The actuator motor is turning clockwise
The actuator motor is turning counterclockwise
1 flash per second, alternating
with the
Off Normal
alternating with
then off
The controller files are archiving.
Archive is complete when LED
LED stops flashing.
Five minute auto-restart delay
after system error LED
The controller has just been
formatted
network have the same MS/TP
network address
network
48 VVT Zone Controller
Page 53
If Run LED shows...
And Error LED shows...
Status is...
stopped
Run
Run
2 flashes per second
On Exec halted after frequent system
errors, due to:
• Controller halted
• Program memory corrupted
• Address conflicts - duplicate
MS/TP MAC addresses
•One or more programs
5 flashes per second On Exec start-up aborted, Boot is
running
5 flashes per second Off Firmware transfer in progress,
Boot is running
7 flashes per second 7 flashes per second,
alternating with
14 flashes per second 14 flashes per second,
alternating with
LED
Ten second recovery period after
brownout LED
Brownout
On On Failure. Try the following solutions:
•Turn the VVT Zone Controller
off, then on.
•Download memory to the VVT
Zone Controller.
•Replace the VVT Zone
Controller.
Serial number
If you need the VVT Zone Controller's serial number when troubleshooting, the number is on:
• a sticker on the back of the main controller board
• a Module Status report (modstat) from your user interface
Replacing the VVT Zone Controller's battery
The VVT Zone Controller's 10-year Lithium CR2032 battery provides a minimum of 10,000 hours of data
retention during power outages.
If the VVT Zone Controller experiences a power outage and the control program stops functioning, replace the
battery.
1 Remove the VVT Zone Controller's cover.
2 Remove the battery from the controller, making note of the battery's polarity.
3 Insert the new battery, matching the battery's polarity with the polarity indicated on the controller's cover.
4 Replace the VVT Zone Controller's cover.
5 Download the VVT Zone Controller.
VVT Zone Controller 49
Page 54
Compliance
Compliance
FCC Compliance
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to
Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful
interference when the equipment is operated in a commercial environment. This equipment generates, uses,
and can radiate radio frequency energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. Operation of this equipment in a
residential area is likely to cause harmful interference in which case the user will be required to correct the
interference at his own expense.
CAUTION Changes or modifications not expressly approved by the responsible party for compliance could
void the user’s authority to operate the equipment.
CE Compliance
WARNING This is a Class A product. In a domestic environment, this product may cause radio interference in
which case the user may be required to take adequate measures.
BACnet Compliance
BACnet® is a registered trademark of ASHRAE. ASHRAE does not endorse, approve or test products for
compliance with ASHRAE standards. Compliance of listed products to requirements of ASHRAE Standard 135
is the responsibility of the BACnet manufacturers Association (BMA). BTL® is a registered trademark of the
BMA.
50 VVT Zone Controller
Page 55
i-Vu / Field Assistant:
Navigation:
Properties > Equipment > Status
HOME
STATUS
Point Name/Description
Range
Terminal Mode
Term Type
Space Temperature - Prime Variable
Damper Position
Supply Air Temperature
Heating Capacity
Baseboard Heating Capacity
Outdoor Air Temperature
Fan
Term Type
Parallel Fan
Series Fan
CO2 (ppm)
Optional Sensor Type
IAQ Control
Space Relative Humidity
Optional Sensor Type
RH Control
Shutdown
Active
Appendix A: VVT Zone Controller Points/Properties
Status
NOTE Engineering units shown in this document in the defaults and ranges are strictly for reference. You
must enter an integer only.
BACview:
>
– The controller's current operating status. OFF
– The type of zone terminal that the controller is installed on. Single Duct
– The space temperature value currently used for
control.
the zone is configured for Combination Baseboard and Ducted Heat.
source, if available, or from another network source.
R: – The current supply air temperature. -56 to 245°F
R: – The current reheat capacity when the zone is configured for reheat. 0 to 100%
R: – The current modulating baseboard heat capacity when
0 to 100%
R: – The current outdoor air temperature from a linked air
-56 to 245°F
. On/Off
R:
– The current IAQ value if
is set to
– The current space relative humidity if
is set to
– When
delays and close the damper.
VVT Zone Controller 51
R: . 0 to 5000ppm
R: . 0 to 100%rh
D: , disables all control functions, at normal equipment time
Inactive
R:
Inactive/Active
Page 56
Appendix A: VVT Zone Controller Points/Properties
Navigation:
Properties > Equipment > Configuration > Unit Configuration
HOME
CONFIG
UNIT
Point Name/Description
Default/Range
Heat Enable
Parallel Fan Heat On Delay
Term Type
Parallel
Term Type
Single Duct
Fan Off Delay
e terminals only. The amount of time the terminal fan continues
Maximum Heating SAT
DCV Max Vent Damper Pos
Filter Service Alarm Timer
Filter Alarm
Pushbutton Override
Setpoint Adjust
Setpoint Adjustment Range
Heating Lockout Temperature
Power Fail Restart Delay
Occupancy Schedules
Enabled
Disabled
BAS On/Off
System Occupancy
T55 Override Duration
Pushbutton Override
Enable
Unit Configuration
i-Vu / Field Assistant:
BACview:
>
>
– The delay in reheat coming on after the zone has a
heating demand. If the
to heat the space prior to bringing mechanical reheat. If the
we recommend that you set this value to 1 minute.
to operate after a heating demand is satisfied.
heat is operating. Ducted type supplemental heat is controlled so that it will not exceed
this limit.
override the damper to. When active, the damper modulates to the temperature
control position or the IAQ override position, whichever is greater.
generating a
. Set to 0 to disable the alarm.
local space temperature sensor.
is
, this allows the fan time to use plenum air
is
,
– The amount of time a Parallel or Series fan will run before
D: – Enables the reheat function.
Enable
R:
Disable/Enable
D:
15 minutes
R:
0 to 30 minutes
120 seconds
D: – Fan-typ
R:
0 to 180 sec
105°F
D: – The maximum supply air temperature allowed while ducted
R:
80 to 140°F
70%
D: – The maximum damper position that the IAQ function can
R:
0 to 100%
D:
0 hr
R:
0 to 9999 hr
D: – Enables or disables the use of a pushbutton override from a
Enable
R:
Disable/Enable
setpoint on the local SPT sensor.
temperature exceeds this value. Supplemental reheat is enabled when the outside air
temperature falls below a fixed hysteresis of 2°F. This function is active only if there is
a valid network outside air temperature.
power is restored. This is typically used to prevent excessive demand when recovering
from a power failure. Applies to Series Fan start delay when system mode transitions
from unoccupied to occupied. A delay of no greater than 120 seconds is recommended
for Series Fan applications.
– If
, the controller stores and follows a schedule sent
over the network or programmed locally through a BACview or Field Assistant. If
, the controller occupancy is controlled from the
or
network point.
– The amount of time that the controller runs in the occupied
mode when a user presses the T55 sensor's override button for 1 to 10 seconds.
must be set to
.
D: – Enables the setpoint adjustment slider on the SPPL space sensor.
Enable
R:
Disable/Enable
D: - The maximum amount that a user can adjust the
2°F
R:
0 to 5°F
70°F
D: – Supplemental reheat is disabled if outside air
R:
-60 to 150°F
60 seconds
D: – How long the controller delays normal operation after the
R:
60 to 600 seconds
D:
Enable
R:
Disable/Enable
D:
1 hr
R:
1 to 4 hr
52 VVT Zone Controller
Page 57
Point Name/Description
Default/Range
Local Sensor Calibration
Space Temperature
Space Temp Calibration
Supply Air Temperature
Supply Air Temp Calibration
Space Relative Humidity –
Relative Humidity Calibration
Status > Space Relative Humidity
Navigation:
Properties > Equipment > Configuration > Setpoints
HOME
CONFIG
SETPOINT
Heating
Cooling
– The current space temperature. -56 to 245°F
– A calibration offset value to allow the local space
temperature sensor to be adjusted to match a calibrated standard measuring the
temperature in the same location.
temperature sensor to be adjusted to match a calibrated standard measuring the
temperature in the same location.
present.
– You can enter a calibration offset for the relative
humidity. The offset is added to or subtracted from the controller's RH input value, and
the calculated value is shown in the
.
Setpoints
R:
D:
0°F
R:
-9.9 to 10°F
R: – The current supply air temperature. -56 to 245°F
0°F
D: – A calibration offset value to allow the supply air
R:
-9.9 to 10°F
R: Displays the current value of relative humidity sensor, if
0 to 100%
D:
0%
R:
-15 to 15%rh
i-Vu / Field Assistant:
BACview:
>
>
Select a color band on the setpoint graph to see the current setpoints in the
descriptions below.
and
fields. See setpoint
VVT Zone Controller 53
Page 58
Appendix A: VVT Zone Controller Points/Properties
Occupied Setpoints
Default
Demand Level
Point Name/Description
Occupied
1 2 3
Occupied Heating
Occupied Cooling
Occupied Heating 1
Occupied Heating
Occupied Heating
Occupied Heating 2
Occupied Cooling 1
Occupied Cooling
Occupied Cooling
Occupied Cooling 2
Unoccupied Setpoints
Point Name/Description
Range
Unoccupied Heating
Unoccupied Cooling
The occupied setpoints described below are the setpoints under normal operating conditions. The Demand Level 1–3
setpoints apply if demand limiting is used.
Demand limiting is a cost-saving strategy to reduce energy consumption. The strategy expands the occupied heating and
cooling setpoints when the system reaches one of 3 levels of consumption. With the expanded setpoints, the equipment
works less, thereby saving energy. By default, Demand Level 1 expands the occupied heating and cooling setpoints by 1°F,
Demand Level 2 by 2°F, and Demand Level 3 by 4°F. If the occupied heating or cooling setpoints change, the (effective)
demand level setpoints automatically change by the same amount. See Sequence of Operation40 (page ) for more
information.
Range: 40 to 99°F
The heating setpoint the controller maintains while in occupied mode.
The cooling setpoint the controller maintains while in occupied mode.
– Light Blue
The space temperature must be less than this value for the VVT Master to
consider the zone a heating caller. The zone remains a heating caller until the
space temperature rises above the
that this value be set no lower than .5°F below the
The space temperature must be less than this value to generate a low space
temperature alarm.
– Yellow
The space temperature must be greater than this value for the VVT Master to
consider the zone a cooling caller. The zone remains a cooling caller until the
space temperature drops below the
that this value be set no lower than .5°F above the
The space temperature must be greater than this value before a high space
temperature alarm is generated.
setpoint. We recommend
setpoint.
setpoint. We recommend
setpoint.
70°F – Green
74°F – Green
69°F
67°F – Dark Blue
75°F
77°F – Orange
69°F 68°F 66°F
75°F 76°F 78°F
68°F 67°F 65°F
66°F 65°F 63°F
76°F 77°F 79°F
78°F 79°F 81°F
The heating setpoint the controller maintains while in unoccupied mode.
The cooling setpoint the controller maintains while in unoccupied mode.
54 VVT Zone Controller
D: – Gray
55°F
R:
D: – Gray
R:
40 to 90°F
90°F
55 to 99°F
Page 59
Unoccupied Heating 1
Unoccupied Heating
Unoccupied Heating
Unoccupied Heating 2
Unoccupied Cooling 1
the zone a cooling caller. The zone remains a cooling caller until the space temperature
Unoccupied Cooling
Unoccupied Cooling
Unoccupied Cooling 2
Point Name/Description
Range
Heating Capacity
Heating Design Temp
Cooling Capacity
Cooling Design Temp
tem must run constantly to maintain comfort. This information is available in
– Light Blue
The space temperature must be less than this value for the VVT Master to consider the
zone a heating caller. The zone remains a heating caller until the space temperature
rises above the
lower than .5°F below the
The space temperature must be less than this value before a low space temperature
alarm is generated.
– Yellow
The space temperature must be greater than this value for the VVT Master to consider
drops below the
lower than .5°F above the
The space temperature must be greater than this value before a high space
temperature alarm is generated.
setpoint. We recommend that this value be set no
setpoint.
setpoint. We recommend that this value be set no
setpoint.
– Used for Optimal Start, this is the rate at which the zone
temperature changes when the heating system runs at full capacity to maintain
designed occupied heating setpoint.
– The geographically-based outdoor air temperature at which the
heating system must run constantly to maintain comfort. This information is available
in ASHRAE publications and most design references.
– Used for Optimal Start, this is the rate at which the zone
temperature changes when cooling system runs at full capacity to maintain designed
occupied cooling setpoint.
– The geographically-based outdoor air temperature at which the
cooling sys
ASHRAE publications and most design references.
D:
R:
D: – Dark Blue
R:
D:
R:
D: – Orange
R:
D:
R:
D:
R:
D:
R:
D:
R:
54°F
40 to 99°F
52°F
40 to 99°F
91°F
40 to 99°F
93°F
40 to 99°F
5°F/hr
0 to 120°F/hr
0°F
-100 to 150°F
5°F/hr
0 to 140°F/hr
100°F
-100 to 150°F
VVT Zone Controller 55
Page 60
Appendix A: VVT Zone Controller Points/Properties
Point Name/Description
Range
Hysteresis
Time
Temp
Occupied heating setpoint: 70°
75.5°
70.5°
Occupied cooling setpoint: 76°
.5° hysteresis
.5° hysteresis
Learning Adaptive Optimal Start
learned
heating capacity
learned cooling capacity
Learning
Adaptive Optimal Start
Optimal Start
Learning Adaptive Optimal Start
Effective Set Points
Setpoints
Effective Setpoints
Point Name/Description
Heating –
Heating
Default/Range
– The desired difference between the temperature at which the zone color
changes as the zone temperature departs from the acceptable range between the
heating and cooling setpoints (green) into the Cooling 1 (yellow) or Heating 1 (light
blue) and the temperature at which the zone color changes back to the acceptable
range between the heating and cooling setpoints.
For example, the following graph shows the zone color that results as the zone
temperature departs from and returns to the acceptable range in a zone with the
following settings:
•Color Change Hysteresis = .5° (applies as the temperature returns to the
acceptable range)
• Occupied cooling setpoint = 76°
• Occupied heating setpoint = 70°
D:
R:
0.5°F
0.2 to 1.0°F
to achieve the occupied setpoint by the time scheduled occupancy begins. This learning adaptive algorithm uses the
The algorithm calculates a learned cooling and heating capacity during the previous unoccupied time. Set the
routine runs, adjustments are based on the color that is achieved when occupancy begins. Adjustment amounts are defined
in the thermographic color fields located directly above the
The Effective Setpoints graph shows the current occupied or unoccupied setpoints. If occupied, these values are the current
programmed setpoints plus the offset of any setpoint adjustment that may be in affect. If unoccupied, the values are the
programmed unoccupied setpoints.
setpoint adjusted by any offset that may be in effect.
– This function gradually adjusts the unoccupied setpoints over a specified period of time
and
recovery period from 1 to 4 hours in
values to calculate the effective setpoints prior to the occupied start time.
. When the
graph under
(Occupied or Unoccupied, depending on mode) The current programmed
.
R: 0 to 120°F
56 VVT Zone Controller
Page 61
Point Name/Description
Default/Range
Cooling –
Cooling
Learned cooling capacity
Learned heating capacity
Min Setpoint Separation
Optimal Start
NOTE
Properties
Equipment
Maintenance
Occupancy
BAS On/Off
Unoccupied
Occupied
Optimal Start Type
None*
Temp Compensated*
Learning Adaptive Start
*
None
Temp Compensated
Heat Start K factor (min/deg)
Optimal Start Type
Temp Compensated
Cool Start K factor (min/deg)
Optimal Start Type
Temp Compensated
Standby Offset
Occupied RH Control Setpoint
Optional Sensor Type
RH Sensor
RH Control
Enable
Cool
Vent
Cooling
Vent
DCV Start Ctrl Setpoint
Optional Sensor Type
IAQ Sensor
DCV Control
Enable
setpoint adjusted by any offset that may be in effect.
that is required to bring the space temperature down to the occupied cooling setpoint prior to
the occupied time.
that is required to bring the space temperature up to the occupied heating setpoint prior to the
occupied time.
and cooling setpoints.
begin to adjust the effective setpoints to achieve the occupied setpoints by the time scheduled
occupancy begins. Enter 0 to disable Optimal Start.
Options:
an occupied mode. Setpoints do not ramp, but change immediately from unoccupied to
occupied values.
occupied time, which is calculated by the current error between space temperature and the
appropriate heating or cooling setpoint. At that time, the setpoints do not ramp, but change
immediately from unoccupied to occupied values.
unoccupied setpoints over a specified period of time to achieve the occupied setpoint by the
time scheduled occupancy begins.
Start transition factors to 0.
minutes per degree that the equipment starts before the occupied period when the space
temperature is below the occupied heating setpoint (including any setpoint offset).
minutes per degree that the equipment starts before the occupied period when the space
temperature is above the occupied cooling setpoint (including any setpoint offset).
occupancy sensor indicates that the space is unoccupied. If 0, the unoccupied setpoints are
used.
set to
be
function can be active.
This value should be set to approximately 75 ppm above the outdoor air CO2 level.
(Occupied or Unoccupied, depending on mode) The current programmed
– The cooling capacity learned by Learning Adaptive Optimal Start
– The heating capacity learned by Learning Adaptive Optimal Start
– The earliest time, prior to occupancy, at which the Optimal Start function may
Optimal Start is automatically disabled when
>
is set to either
or
– The method used to change from unoccupied to occupied setpoint.
– Unit will not change to occupied setpoint until the scheduled time or the unit goes into
– Unit changes to occupied setpoints at a variable time prior to the
– Unit gradually changes to occupied setpoints by adjusting the
When selecting
or
– If
– If
, you MUST set all Learning Adaptive Optimal
is
is
– If
, this is the relative humidity setpoint during occupancy. The air source mode must
or
and the terminal mode must be
– If
is set to
, this is the value that the CO2 sensor must exceed to begin the DCV control function.
>
.
is set to
or
before the dehumidification
and
>
and
>
is
is set to
R:
0 to 120°F
D: – Minimum separation that must be maintained between the heating
4°F
R:
2 to 10°F
D:
1 hr
R:
0 to 4 hr
D:
Temperature
Compensated
R:
None
Temperature
Compensated
Learning Adaptive
15.00
D: , this is the time in
R:
0 to 99
D: , this is the time in
15.00
R:
0 to 99
0°F
D: – The value by which the occupied setpoints are expanded when the space
R:
0 to 15°F
D:
65%rh
R:
0 to 100%rh
500ppm
D:
R:
0 to 9999 ppm
VVT Zone Controller 57
Page 62
Appendix A: VVT Zone Controller Points/Properties
Point Name/Description
Default/Range
DCV Max Ctrl Setpoint
Optional Sensor Type
IAQ Sensor
DCV Control
Enable
DCV MAX Vent Airflow
Parallel Fan ON Value
Terminal Type
Parallel Fan
e’s airflow control setpoint decreases below this value, the parallel fan turns on to
, this is the value that the CO2 level must exceed to begin the IAQ function to control the
damper to
.
– If
when the zon
increase airflow, ventilation, and prevent cold air dumping into the zone. If the airflow control
setpoint rises above this value by more than 1 cfm, the parallel fan turns off. We recommend
this value be set to approximately 10% above the
disable this function.
is
is set to
and
and the zone does not require heating,
setpoint. Set to 0 to
is set to
Alarm Configuration
i-Vu / Field Assistant:
BACview:
>
– This value is added to the effective cooling setpoints and
subtracted from the effective heating setpoints as output from the
microblock. These values establish the occupied high and low limits that the space
temperature must exceed before an occupied SPT alarm is generated. The alarm
returns to normal when the space temperature drops below the high effective setpoint
or rises above the low effective setpoint.
temperature alarm is generated when the controller transitions to the occupied mode.
The delay time equals this value multiplied by the difference between the sensor
temperature and occupied alarm setpoint plus 15 minutes.
–The value that the space temperature must drop
below to generate a
fixed hysteresis of 1° F for return to normal.
– The value that the space temperature must
exceed to generate a
fixed hysteresis of 1° F for return to normal.
in the unoccupied mode. There is a
in the unoccupied mode. There is a
>
>
5°F
D:
R:
0 to 20°F
D: – Determines the amount of delay before an occupied space
10 minutes
R:
0 to 30 minutes
45°F
D:
R:
35 to 90°F
95°F
D:
R:
45 to 100°F
D:
1050ppm
R:
0 to 9999 ppm
0 cfm
D:
R:
0 to 99999 cfm
generate a
normal.
generate a
normal.
58 VVT Zone Controller
– The value that the supply air temperature must drop below to
. There is a fixed hysteresis of 1° F for return to
– The value that the supply air temperature must exceed to
. There is a fixed hysteresis of 1° F for return to
D:
R:
D:
R:
45°F
15 to 90°F
120°F
90 to 175°F
Page 63
Point Name/Description
Default/Range
Space Humidity Alarm
Occ High RH Alarm Limit
Space Humidity Alarm
RH Control
Enable
Alarm Delay (min/%RH)
Unocc High RH Alarm Limit
Space Humidity Alarm
RH Control
Enable
IAQ/Ventilation Alarm
Occupied High CO2 Alarm Limit
Indoor Air Quality Alarm
DCV Control
Enable
Alarm Delay (min/ppm)
Alarms Displayed on SPT Sensor
Space Temperature Alarm
Supply Air Temp Alarm
Supply Air Temp Alarm
Dirty Filter Alarm
Space High Humidity Alarm
Space Humidity Alarm
Space High CO2 Alarm
Indoor
Air Quality Alarm
– The value that the relative humidity sensor must exceed to
generate a
in the occupied mode if
is set to
There is a fixed hysteresis of 5%rh for return to normal.
alarm is generated when the controller transitions to the occupied mode. The delay
time equals this value multiplied by the difference between the sensor RH value and
the occupied RH setpoint plus 15 minutes.
– The value that the relative humidity sensor must exceed
to generate a
in the unoccupied mode if
is set to
. There is a fixed hysteresis of 5%rh for return to normal.
– The value that the CO
generate an
in the occupied mode if
. There is a fixed hysteresis of 100ppm for return to normal.
– The fractional portion of an hour determining the amount of
delay before an indoor air quality alarm is generated when the controller transitions to
the occupied mode. The delay time equals this value multiplied by the difference
between the sensor CO
value and the setpoint plus 15 minutes.
2
– If set to display, shows the alarm indicator on the SPT Pro
sensor if the space temperature alarm is active.
– Shows the alarm indicator on the SPT Pro sensor if the
is active.
sensor must exceed to
2
is set to
100%rh
D:
.
R:
45 to 100%rh
5 minutes
D: – Determines the amount of delay before an occupied RH
R:
0 to 30 minutes
D:
100%rh
R:
45 to 100%rh
D:
1100ppm
R:
0 to 9999 ppm
D:
.25 hr (15 minutes)
R:
0 to 1.0 hr (60 minutes)
D:
Ignore
R:
Ignore/Display
D:
Ignore
R:
Ignore/Display
Pro Plus' sensor if a dirty filter alarm is active.
Pro and SPT Pro Plus' sensor if the
VVT Zone Controller 59
– If set to display, shows the alarm indicator on the SPT Pro and SPT
– If set to display, shows the alarm indicator on the SPT
is active.
– Shows the alarm indicator on the SPT Pro sensor if the
is in alarm.
D:
Display
R:
Ignore/Display
D:
Ignore
R:
Ignore/Display
D:
Ignore
R:
Ignore/Display
Page 64
Appendix A: VVT Zone Controller Points/Properties
Navigation:
Properties > Equipment > Configuration > Service Configuration
HOME
CONFIG > SERVICE
Point Name/Description
Default/Range
Terminal Type
Damper Size (in.)
Damper Area (sq.in.)
External Actuator Enable
Heat Type
None
Modulating
Two Position
Staged EH
Combination
Ducted Heat
Heat
Type
Combination
Yes
Number of Heat Stages
Heat Type
Staged EH
Valve Type
Optional Sensor Type
RH/CO2
RH Sensor –
IAQ Sensor
RH Control
DCV Control
Service Configuration
i-Vu / Field Assistant:
BACview:
>
– The type of zone terminal that the controller is installed on. D:
– Used by the VVT Master to calculate the weighted average demand. If
the zone damper is round, enter its diameter. If rectangular, enter 0.
– Used by the VVT Master to calculate the weighted average
demand. If the damper is rectangular, enter its area (width x height). If the damper is
round, enter 0.
– Enable if the controller's analog output is used for an external
high-torque or slave actuator. Enabling this setting disables the output for Modulating Hot
Water or Combination reheat functions.
– The type of supplemental reheat that the zone controller will control. The heat
may be used with system heat, depending on the space temperature demand.
Options:
– no heat
– ducted or baseboard modulating hot water
– two position hot water
– ducted or baseboard electric heat
– combination baseboard modulating hot water and ducted staged electric
heat
– Determines whether the zone is using ducted heat or baseboard. If
is
, set this field to
for ducted heat.
Single Duct
R:
Single Duct
Parallel
Series Fan
D:
6.00 in.
R:
0 to 100.00 in
D:
0 sq.in.
R:
0 to 9999 sq.in.
D:
Disable
R:
Disable/Enable
D:
None
R:
None
Modulating
Two Position
Staged EH
Combination
D:
Yes
R:
No/Yes
– The number heat stages when the
powered terminals are limited to no more than 2 stages.
– Two Position hot water only - The hot water valve's position with no power
applied to the valve.
– The type of sensor used on the controller's
setting determines the optional control functionality.
Options:
Relative humidity for zone dehumidification
– Indoor air quality to DCV control
– Demand control ventilation control. D:
60 VVT Zone Controller
is
input. This
. Fan
D:
Two stages
R:
One stage
Two stages
Three stages
D:
NC
R:
NC/NO (normally
closed/normally open)
D:
None
R:
None
RH Sensor
IAQ Sensor
D: – Zone dehumidification control.
Disable
R:
Disable/Enable
Disable
R:
Disable/Enable
Page 65
Point Name/Description
Default/Range
Min Setpoint Separation
Occ Override Normal Logic State
Remote
Occupancy
RH Sensor Min Input Volts
RH Sensor Max Input Volts
RH Sensor Value @ Min Volts
RH Sensor Value @ Max Volts
CO2 Sensor Min Input Volts
CO2 Sensor Max Input Volts
CO2 Sensor Value @ Min Volts
CO2 Sensor Value @ Max Volts
PD (Pressure Dependent) Control :
Damper Motor Travel Time
Direction Clockwise
Damper Actuator
Built-in actuator
Target Damper Position
Lock value to
Lock value to
Auxheat
Reheat Min Damper Position
Lock value to
Lock value to
Fan
Lock value to
On
Off
Lock value to
Cooling Min Damper Position
– Minimum separation that must be maintained between the
heating and cooling setpoints.
– The normal state of the controller's
input. If the input's contact is the same state as the configured state, the
controller follows its controlling schedule. If the contact is in the opposite state of the
configured state, the controller is forced into the unoccupied mode.
– The lowest voltage that should be read from the relative
humidity (RH) sensor.
– The highest voltage that should be read from the RH sensor. D:
– The % relative humidity that correlates to the RH sensor's
low voltage reading.
– The % relative humidity that correlates to the RH sensor's
high voltage reading.
2
2
sensor.
sensor.
voltage reading.
voltage reading.
– The lowest voltage that should be read from the CO
– The highest voltage that should be read from the CO
– The ppm value that correlates to the CO
– The ppm value that correlates to the CO
sensor's low
2
sensor's high
2
D:
4°F
R:
2 to 10°F
D:
Open
R:
Open/Closed
D:
0.00 V
R:
0 to 5.00 V
5.00 V
R:
0 to 5.00 V
D:
0%
R:
0 to 99%
D:
100%
R:
0 to 100%
1.00 V
D:
R:
0 to 5.00 V
D:
5.00 V
R:
0 to 5.00 V
0ppm
D:
R:
0 to 9999 ppm
2000 ppm
D:
R:
0 to 9999 ppm
This field is fixed at 205 seconds.
the damper's position when it rotates clockwise.
troubleshooting purposes, select
moves to that position until
control for reheat troubleshooting purposes, select
- The current configured
value. The damper moves to that position until
– The current value of the fan output relay. To override normal control for
troubleshooting purposes, select
stays in that state until the
to when the air source mode is Cooling, Vent, or Free Cooling and the space
requirements for cooling are at a minimum. We recommend that you set this no lower
than 10%.
VVT Zone Controller 61
– The actuator's travel time from full closed to full open.
– If
- The current damper position. To override normal control for
– The minimum damper position the terminal controls
is set to
, set this field to
and then enter a value. The damper
checkbox is cleared.
. To override normal
and then enter a
checkbox is cleared.
and then enter
or
checkbox is cleared.
. The relay
D: 205 seconds
D:
Closed
R:
Open/Closed
R: 0 to 100%
R: 0 to 100%
R: On/Off
D:
20%
R:
0 to 100%
Page 66
Appendix A: VVT Zone Controller Points/Properties
Point Name/Description
Default/Range
Cooling Max Damper Position
Reheat Min Damper Position
Cooling Min Damper Position
Heating Min Damper Position
Heating Max Damper Position
Vent Position
Test and Balance
Automatic Control
Calibrated Damper Close
Calibrated Damper Open
Cool Max
Cool Min
Automatic Control
This must be activated when you finish using
any of the other Test and Balance commands.
Damper Full Close
Heat Max
Heat Min
Reheat Min
Vent
System Space Temperature
System Space RH
System Space AQ
System Cool Demand Level
System Heat Demand Level
System Outdoor Air Temperature
to when the air source mode is Cooling, Vent, or Free Cooling and the space
requirements for cooling are at a maximum.
desired damper position at which the reheat will provide optimum performance. This
value is compared to the
two values determines the damper position.
to when the air source mode is Heat and the space requirements are at a minimum.
to when the air source mode is Heat and the space requirements are at a maximum.
source mode is Vent and the terminal mode is not in the Heat or Cool mode. If
– The ventilation damper position the terminal controls to when the air
Linkage is not active, the zone determines vent mode by verifying that its SAT sensor
is between 65°F and 80°F.
replacing the zone controller, or troubleshooting. If
– Use the following command buttons when commissioning a zone, balancing the system36 (page ),
resume normal control.
set.
– Forces the damper to its cool maximum position regardless of its current local mode.
– Forces the damper to its cool minimum position regardless of its current local mode.
– Returns the damper to its normal control routines.
– Overrides the damper to its full closed position.
– Forces the damper to its heat maximum position regardless of its current local mode.
– Forces the damper to its heat minimum position regardless of its current local mode.
– Forces the damper to its reheat position regardless of its current local position.
– Forces the damper to its ventilation position regardless of its current local mode.
– The maximum damper position the terminal controls
– For Single Duct units with ducted reheat. Set to the
value, and the greater of the
– The minimum damper position the terminal controls
– The maximum damper position the terminal controls
is not selected within 4 hours, the controller will
– Forces the damper closed so the 0% damper position can be set.
– Forces the damper to its maximum open position so that the 100% damper position can be
D:
R:
D:
R:
D:
R:
D:
R:
D:
R:
100%
0 to 100%
45%
0 to 100%
20%
0 to 100%
20%
0 to 100%
50%
0 to 100%
received over the network from another source. -999 indicates no value has been
received and it will not be used.
– The relative humidity received over the network. -999 indicates no
value has been received and it will not be used.
value has been received and it will not be used.
demand limiting function to expand the cooling setpoint.
demand limiting function to expand the heating setpoint.
– The indoor air quality received over the network. -999 indicates no
62 VVT Zone Controller
– The current value of the controlling space temperature
R: -50 to 150°F
R: 2 to 100%
R: 300 to 9999 ppm
– This value received over the network and used by the
– This value received over the network and used by the
– The OAT received over the network. R: -50 to 150°F
R: 0 to 3
R: 0 to 3
Page 67
Point Name/Description
Default/Range
System Occupancy
System Occupancy
Navigation:
i-Vu / Field Assistant:
Properties > Equipment > Maintenance
HOME
MAINT
Point Name/Description
Default/Range
Unit
Occupancy Status
Temp Compensated Start
Learning Adaptive Start
Space Temp Source –
Sensor Failure
SPT Sensor
T55/56
Network
Airside Linkage
Locked Value
Setpoint Adjustment
Effective Heat Setpoint
Effective Cool Setpoint
Relative Humidity Source –
IAQ Source –
– The status of the
Maintenance
BACview:
– The controller's occupancy status as determined by a network
schedule, a local schedule, or a timed override.
Indicates the current status of the system:
The source of the controlling space temperature value.
Options:
– No valid space temperature or sensor status = failed.
– An SPT sensor is connected to the controller’s Rnet port.
– A T55, T56, or T59 sensor is connected to the controller’s J20 terminals.
– A network temperature sensor is bound to the controller’s space
temperature AV.
– The space temperature from a linked terminal.
–The controller’s space temperature input has been manually locked at
a value.
>
D: network point.
Unoccupied
R:
Unoccupied/Occupied
R: Unoccupied/Occupied
R: Inactive/Active
R: Sensor Failure
SPT Sensor
T55/T56
Network
Airside Linkage
Locked Value
space sensor.
The source of the indoor air quality. R:
VVT Zone Controller 63
– The amount that a user has adjusted the setpoints at an SPT
R: -20 to 20°F
– The current heating setpoint. R: -56 to 245°F
– The current cooling setpoint.
The source of the relative humidity. R:
R: -56 to 245°F
N/A
Local
Network
Linkage
Locked Value
N/A
Local
Network
Linkage
Locked Value
Page 68
Appendix A: VVT Zone Controller Points/Properties
Point Name/Description
Default/Range
Outdoor Air Temperature Source
Heat Delay –
Remaining Heat Delay –
Heat Delay
Active
Cooling Demand Level
Heating Demand Level
Calculated DCV Damper Position –
Calculated Dehumidify Dmpr Position –
Reset Filter Alarm
Filter Alarm
Filter
Service Alarm Timer
Off
Occupancy Contact State
Remote
Occupancy
BAS On/Off
Inactive
Occupied
Unoccupied
NOTE
BAS On/Off
Unoccupied
Occupied
Optimal Start
Schedules
Pushbutton Override
Active
Override Time Remaining
Occupancy Contact Status
Remote
Global Occupancy –
System Occupancy
– The source of the outside air temperature.
The status of the terminal heat delay. R: Inactive/Active
If
– The system cool demand level being received over the
network.
– The system heat demand level being received over the
network.
calculated minimum damper position that will be maintained to satisfy the mode.
the calculated minimum damper position that will be maintained to satisfy the mode.
– Set this to On to reset an active
. After the alarm returns to normal, this automatically changes to
.
- The physical state of the
is
, this is the remaining delay time. R: 0 to 60 minutes
If the controller is in IAQ Override mode, this is the
If the controller is in Dehumidify mode, this is
and restart the
input. R: Open/Closed
R: N/A
R:
R:
R: 0 to 100%
R: 0 to 100%
D:
R:
Local
Network
Linkage
Locked Value
0 to 3
0 to 3
Off
On/Off
– Determines the occupancy state of the controller and can be set over
the network by another device or third party BAS.
Options:
•
•
•
– Occupancy is determined by a configured schedule.
– The controller is always in the occupied mode.
– The controller is always in the unoccupied mode.
If
is set to either
is automatically disabled.
– The controller's occupancy status based on the schedule. R: Occupied/Unoccupied
–
indicates if a user pushed the sensor's override button to
override the occupancy state.
– The amount of time remaining in an override period. R: 0 to 480 minutes
– The physical state of the controller's
The current state of the
or
, the
routine
input. R: Inactive
network input. D:
D:
Inactive
R:
Inactive
Occupied
Unoccupied
R: Off/Active
Active Unoccupied/Stdby
Unoccupied
R:
Unoccupied/Occupied
64 VVT Zone Controller
Page 69
Navigation:
Properties > Equipment > Alarms
HOME
ALARM
Point Name/Description
Range
Space Temperature
Alarming Temperature
Space Temperature
Alarm
Alarm Limit Exceeded
Space
Temperature
Alarm
Space Temp Sensor –
Indoor Air Quality
Occupied High CO2
Alarm Limit
Supply Air Temperature
Filter
Space Relative Humidity
Network OAT -
Airside Linkage Status
Alarm
Alarm
Navigation:
Properties > Equipment > Linkage
HOME
CONFIG > LINKAGE
Point Name/Description
Default/Range
Airside Linkage
Linkage Collector/Linkage Provider
Summary
Details
Linkage Collector
Number of Providers
Alarms
i-Vu / Field Assistant:
BACview:
>
– Indicates if the space temperature exceeds the high or low alarm limit. R: Normal/Alarm
– Indicates the space temperature value that caused the space
temperature alarm. This value is only displayed when the
is in
.
alarm (above)
– Indicates the value of the space temperature alarm limit that
caused the space temperature alarm condition. Value is only displayed when the
alarm (above) is in
.
Indicates if the space temperature sensor fails. R: Normal/Alarm
– Indicates if the occupied CO
level exceeds the
2
.
– Indicates if the supply air temperature exceeds the high
temperature alarm limit or drops below the low temperature alarm limit.
– Indicates if the filter's runtime hours exceeds the runtime alarm limit. R: Clean/Dirty
– Indicates if the relative humidity exceeds the high RH alarm limit. R: Normal/Alarm
Indicates if the controller is not receiving a valid OAT value over the network. R: Normal/Alarm
R: -56 to 245°F
R: -56 to 245°F
R:
R: Normal/Alarm
Normal/Alarm
– If the controller is the VVT Master,
indicates that it lost
Linkage communications with the air source. If the controller is a slave,
it lost Linkage communications with the VVT master.
Linkage
i-Vu / Field Assistant:
BACview:
>
Click
and
tabs. See the microblock popup's Help files for more detailed
explanations.
– Set the
the linked system, including the bypass and VVT Master.
to access the microblock popup's
to the total number of controllers in
indicates that
D:
R: 1 1 to 32
R: Normal/Alarm
VVT Zone Controller 65
Page 70
Appendix A: VVT Zone Controller Points/Properties
Point Name/Description
Default/Range
Linkage Provider
Network Number
Address
Network Number
Address
Airside Linkage Status
Active
Not
Active
Linkage Zone Type
VAV Master
VVT Master
Active Heating Caller
Active Cooling Caller
Linkage Callers
System Mode Reselect Timer (minutes)
Inhibit Heating Call from this zone
Inhibit Cooling Call from this zone
Yes
Linkage RH Type
Linkage IAQ Type
Air Source Mode
Airside Linkage Status
Active
Airside Linkage Status
Not Active
Air Source Supply Air Temp
Airside Linkage
Status
Active
Airside Linkage Status
Not Active
– Enter the MS/TP
air source controller.
– If
, the controller is part of a linked system. If
, the controller is a stand-alone device.
– Select whether the controller is a Master or a slave.
Select
Select
if the controller is the Master or a sub-master in a VAV application.
only if the controller is the Master in a VVT application. VVT
applications do not support sub-masters.
– Determines if the zone will be counted as a heat caller for
system heating when the zone has a local demand for heat.
– Determines if the zone will be counted as a cool caller for
system cooling when the zone has a local demand for cooling.
– The minimum number of zones required to make the air source go
into heating or cooling mode. 1 is typical for systems with 8 zones or less. For larger
systems, increase the number by 1 for each 6 zones. For example, 3 linkage callers
for a 20 zone system.
and MAC
of the linked
0
D:
1 to 65535
R:
0
D:
1 to 99
R:
R: Not Active/Active
D:
Slave
R:
Slave
VVT Master
VAV Master
D:
Yes
R:
No/Yes
D:
Yes
R:
No/Yes
D:
R: 1 1 to 32
long the system continues to operate in the current mode before it reassesses all
zones while the current demand is still active.
heating caller.
cooling caller.
– Determines if the VVT or VAV Master sends to the air source the
average or maximum values of all linked zone controllers that have a relative
humidity (RH) sensor.
– Determines if the Master controller sends to the air source the
average or maximum values of all linked zone controllers that have a CO
DCV and IAQ control.
– If
linked air source. If
source as determined by the zone controller’s SAT sensor.
is
. If
66 VVT Zone Controller
– Applies only to a VVT master. Defines how
- If Yes, the VVT Master ignores this controller as a
- If
, the VVT Master ignores this controller as a
is
is
– Shows the air source’s SAT when
is
, this is the current mode of the
, this is the mode of the air
, a “?” is displayed.
sensor for
2
D:
30
R:
10 to 120
D:
No
R:
No/Yes
D:
No
R:
No/Yes
D:
Avg
R:
Avg/Max
D:
Max
R:
Avg/Max
D:
OFF
WARMUP
R:
HEAT
COOL
FREECOOL
PRESSURE
EVAC
VENT
R: ? or -56 to 245°F
Page 71
Point Name/Description
Default/Range
Air Source Outdoor Air Temp
Airside Linkage
Status
Active
Airside Linkage Status
Not Active
Navigation:
i-Vu / Field Assistant:
Properties > I/O Points
N/A
Point Name/Description
Default/Range
SPT Temp Sensor/Zone Temp
SPT Temp Sensor
Properties
Details
Zone Temp
Sensor Type:
Min Present Value
Max Present Value
Setpoint Adjustment:
Max Adjust
Reset setpoint adjust to zero when unoccupied -
Each Pulse
Max Accum
Cancel override
– Shows the air source’s OAT when
is
. If
is
, a “?” is displayed.
I/O Points
BACview:
WARNING! Do not change the Value, Offset/Polarity, Exp:Num, I/O Type, Sensor/Actuator
Type, Min/Max, or Resolution I/O configuration parameter for the points listed below. Changing these
parameters could cause improper control and/or equipment damage. Use extreme caution if locking a
point as this may also cause improper control and/or equipment damage.
•
- (For the SPT Standard, SPT Plus, and SPT Pro sensors only).
Sensor configurations on the microblock's
For more information, consult the Carrier Sensors Installation Guide.
•
- do not adjust these settings.
>
R: ? or -56 to 245°F
R: -56 to 245°F
tab are listed below.
- Minimum present value the sensor transmits before indicating
an alarm.
an alarm.
- Maximum present value the sensor transmits before indicating
– The amount that a user may adjust the setpoint at the sensors.
when the controller transitions to unoccupied.
a user pushes the sensor's override button.
when a user pushes the sensor's override button.
an override.
– The amount of time that is added to the total override time each time
– The maximum amount of override time that can be accumulated
– How long a user must push the sensor's override button to cancel
Resets the setpoint bias to zero
D:
45
D: 96
D:
5°F
R:
0 to 15°F
D: Off
D:
30:00 mm:ss
R:
0:00 to 1440:00 mm:ss
D:
240:00 mm:ss
R:
0:00 to 2000:00 mm:ss
D:
3 seconds
R:
0 to 60 seconds
VVT Zone Controller 67
Page 72
Appendix A: VVT Zone Controller Points/Properties
Point Name/Description
Default/Range
Sensor Array:
Sensor calculation method -
BACnet configuration:
Network Visible -
Object Name -
CO2 Sensor
RH/CO2
RH Sensor
RH/CO2
Zone Temp
T55
SAT Sensor
Occupancy Contact State
Remote Occupancy
Override
Sensor Invalid
Off
Hot Water Valve
HWV/ACT
Heating Stage 1
HEAT1
Heating Stage 2
HEAT2
Fan S/S or EH 3
FAN/HEAT3
variable to be passed to the controller.
point, and for this point to generate alarms.
.
and the SPT sensor.
When using multiple SPT sensors, select the process
Must be enabled for other BACnet objects to read or write to this
Do notD: change. zone_temp
– The current voltage of the controller's
– The value of the controller's
– The current value of the controller's SAT input. R: -56 to 140°F
- The hardware state of the contact used for
– This internal input monitors the communication between the controller
indicates communication is normal.
- The current value of the controller's
D:
Avg
R:
Avg, Min, Max
D:
Enabled
input. R: 0 to 5 Vdc
input. 0 to 5 Vdc
space temperature sensor input. R: -56 to 245°F
output. R: 0 to 100%
R: – The current voltage of the controller's
R: Open/Closed
R: Off/On
- The current hardware state of the controller's
- The current hardware state of the controller's
- The current hardware state of the controller’s
function of this output depends on the terminal type.
output. R: Off/On
output. R: Off/On
output. The
R: Off/On
68 VVT Zone Controller
Page 73
Air Source
Mode
Temperature
Control
Requirements
Terminal Type
Aux
Heat
Terminal
Mode
Damper Control (Damper
Setpoint used)
Heat
Control
Fan
Control
Modulate Damper Position
Heating
Single Duct,
No
Cooling
Minimum Damper Position
Disable
Disable
Minimum Damper Position
Cooling
Single Duct
N/A
Cooling
Modulate Damper Position
Disable
N/A
Modulate Damper Position
Parallel Fan
N/A
Cooling
Modulate Damper Position
Disable
Disable
Appendix B: VVT terminal modes
Off None All N/A Off Hold Damper @65% (None) Disable Disable
Vent None Single Duct N/A Vent Vent Damper Position (Vent) Disable N/A
Cool or Freecool None Single Duct N/A Vent
Cooling All N/A Off Hold Damper @65% (None) Disable Disable
Heating Single Duct N/A Off Hold Damper @65% (None) Disable N/A
Series or
Parallel Fan
Series Fan Yes Heating Hold Damper @65% (None) Enable Enable
Parallel Fan Yes Heating Close Damper (None) Enable Enable
Series Fan N/A Vent Vent Damper Position (Vent) Disable Enable
Parallel Fan N/A Vent Vent Damper Position (Vent) Disable Disable
Cooling Single Duct N/A Cooling
Series Fan N/A Cooling
Parallel Fan N/A Cooling
Parallel Fan
Series Fan No Heating
Single Duct Yes Reheat Minimum Damper Position Enable N/A
Series or
Parallel Fan
Series Fan N/A Vent
Parallel Fan N/A Vent
No Off Hold Damper @65% (None) Disable Disable
Yes Heating
Modulate Damper Position
(Cool)
Modulate Damper Position
(Cool)
(Cool)
(Cool)
Minimum Damper Position
(Cool)
Minimum Damper Position
(Cool)
Minimum Damper Position
(Cool)
Minimum Damper Position
(Cool)
(Cool)
(Cool)
Disable N/A
Disable Enable
Disable Disable
Disable Enable
Enable Enable
Disable N/A
Disable Enable
Disable Disable
Heating
VVT Zone Controller 69
Series Fan N/A Cooling
Single Duct,
Parallel Fan
Series Fan No Heating
Single Duct Yes Reheat Minimum Damper Position Enable N/A
Series or
Parallel Fan
No Heating
Yes Heating
(Cool)
(Cool)
Minimum Damper Position
(Cool)
Minimum Damper Position
(Cool)
Minimum Damper Position
(Cool)
Enable Enable
Disable Disable
Disable Enable
Enable Enable
Page 74
Appendix B: VVT terminal modes
Air Source
Mode
Temperature
Control
Requirements
Terminal Type
Aux
Heat
Terminal
Mode
Damper Control (Damper
Setpoint used)
Heat
Control
Fan
Control
Single Duct,
Minimum Damper Position
Series Fan
N/A
Heating
Minimum Damper Position
Disable
Enable
Maximum Damper Position
Cooling
Single Duct,
N/A
Pressurize
Maximum Damper Position
Disable
Disable
Series Fan
N/A
Pressurize
Maximum Damper Position
Disable
Enable
Heat, Warmup None
Pressurization
(Linked air
source only)
Evacuation/
Shutdown
(Linked)
Parallel Fan
Cooling
Heating Single Duct No Heating
None
Heating
All All N/A Evacuate Close Damper Disable Disable
Single Duct,
Parallel Fan
Series Fan N/A Heating
Single Duct Yes Heating
Series or
Parallel Fan
Series or
Parallel Fan
Single Duct,
Parallel Fan
Series Fan N/A Pressurize
Parallel Fan
Single Duct,
Parallel Fan
Series Fan No Pressurize
Single Duct,
Parallel Fan
Series Fan Yes Pressurize
N/A Heating
N/A Heating
No Heating
Yes Heating
N/A Pressurize
No Pressurize
Yes Pressurize
(Heat)
(Heat)
Minimum Damper Position
(Heat)
Minimum Damper Position
(Heat)
Modulate Damper Position
(Heat)
Modulate Damper Position
(Heat)
Modulate Damper Position
(Heat)
Modulate Damper Position
(Heat)
Maximum Damper Position
(Cool)
(Cool)
(Cool)
(Cool)
Maximum Damper Position
(Cool)
Maximum Damper Position
(Cool)
Maximum Damper Position
(Cool)
Maximum Damper Position
(Cool)
Disable Disable
Disable Disable
Disable Enable
Disable N/A
Enable N/A
Disable Enable
Enable Enable
Disable Disable
Disable Enable
Disable Disable
Disable Enable
Disable Disable
Disable Enable
70 VVT Zone Controller
Page 75
Index
Index
A
Actuator • 1, 3, 27, 41
Addressing the controller • 9
Air source • 41, 46
Air source modes • 41, 46, 47
Airside linkage • 65
Alarm configuration • 58
Alarms • 45, 65
Automatic Control • 60
Schedules • 44
Sequence of operation • 40
Serial number • 49
Series fan terminals • 41
Service Configuration • 29, 33, 60
Setpoint Configuration • 29, 30, 53
Single duct with reheat • 41
space temperature sensors • 45
SPT sensors • 3, 12, 40
Start-up • 29
Status • 51
Supply Air Temperature Alarm • 58
Supply Air Temperature sensor • 3, 40
System checkout • 35
T
T55 / T56 • 14, 40
temperature sensors • 40
Duct Air Temperature sensor • 1, 3, 16, 40
SPT sensors • 3, 12, 40
Supply Air Temperature sensor • 3, 40
Terminal modes • 69
Test and Balance • 36, 60
Troubleshooting • 48
U
Unit Configuration • 29, 30, 52
V
Vent • 60
Virtual BACview • 29
VVT Master • 1, 46
Page 78
Index
VVT system • 1
VVT terminal modes • 69
W
wall-mounted sensors
CO2 sensor • 3, 43, 45
Weight • 3
Wiring
Actuator • 27
Fan box 2-position hot water wiring diagram •