Carrier VVT Bypass II Installation And Startup Manual

VVVVTT BByyppaassss IIII CCoonnttrroolllleerr
IInnssttaallllaattiioonn aanndd SSttaarrtt--uupp GGuuiiddee
CARRIER CORPORATION ©2019 A member of the United Technologies Corporation family · Stock symbol UTX · Catalog No. 11-808-601-01 · 1/25/2019
www.hvacpartners.com
Document revision history
Verify that you have the most current version of this document from
office.
Important changes are listed in
CARRIER CORPORATION ©2019. All rights reserved throughout the world. i-Vu is a registered trademark of Carrier Corporation. All other trademarks are the property of their respective owners.
at the end of this document.
or your local Carrier
Introduction .................................................................................................................................................................. 1
Installing the VVT Bypass II ......................................................................................................................................... 6
Start-up ....................................................................................................................................................................... 22
Sequence of operation .............................................................................................................................................. 26
To adjust the driver properties.................................................................................................................................. 29
Troubleshooting ......................................................................................................................................................... 35
Compliance ................................................................................................................................................................ 39
Contents
What is a VVT Bypass II? ...................................................................................................................................... 1
Specifications ........................................................................................................................................................ 3
Safety Considerations .......................................................................................................................................... 5
Field-supplied hardware ...................................................................................................................................... 6
Mounting the VVT Bypass II ................................................................................................................................. 7
To mount the controller and actuator .................................................................................................. 7
Wiring the VVT Bypass II for power ................................................................................................................. 12
To wire the controller for power .......................................................................................................... 13
Addressing the VVT Bypass II ........................................................................................................................... 14
Wiring for communications .............................................................................................................................. 14
Wiring specifications for BACnet MS/TP and ARC156 ...................................................................... 14
To wire the controller to the BACnet network .................................................................................... 15
Wiring inputs and outputs ................................................................................................................................ 16
Wiring a Duct Air Temperature sensor to an input ............................................................................ 16
Wiring field-supplied actuators to the analog output ........................................................................ 17
Wiring and mounting the Equipment Touch to the Rnet port ........................................................... 20
Wiring the TruVu™ ET Display to the Rnet port ................................................................................. 21
Configuring the VVT Bypass II's properties .................................................................................................... 22
Performing system checkout ........................................................................................................................... 23
Bypass damper .................................................................................................................................... 23
Variable frequency drive (VFD) ........................................................................................................... 24
Duct static pressure control ............................................................................................................................. 26
LAT monitoring and limiting ............................................................................................................................. 26
Equipment fan off detection ............................................................................................................................ 27
Supply Air Temperature Alarm ........................................................................................................................ 27
Airside linkage .................................................................................................................................................... 27
Air source mode determination....................................................................................................................... 28
Driver ................................................................................................................................................................... 29
Device .................................................................................................................................................................. 30
Notification Classes ........................................................................................................................................... 31
Calendars ............................................................................................................................................................ 32
Common Alarms ................................................................................................................................................ 32
Specific Events ................................................................................................................................................... 33
Switches, Jumpers, Options ............................................................................................................................. 33
Flow Calibration Archive ................................................................................................................................... 33
Act Net Network Details ................................................................................................................................... 34
LED's .................................................................................................................................................................... 35
To get the serial number .................................................................................................................................. 36
To restore factory defaults ............................................................................................................................... 36
To replace the battery ....................................................................................................................................... 37
To clean the airflow sensor orifice .................................................................................................................. 37
FCC Compliance ................................................................................................................................................. 39
CE Compliance ................................................................................................................................................... 39
BACnet Compliance........................................................................................................................................... 39
Contents
Appendix A: VVT Bypass II Points/Properties ......................................................................................................... 40
Appendix B: BACnet points list ................................................................................................................................ 45
Document revision history ........................................................................................................................................ 46
Status................................................................................................................................................................... 40
Unit Configuration .............................................................................................................................................. 40
Maintenance ....................................................................................................................................................... 42
Alarms ................................................................................................................................................................. 43
Linkage ................................................................................................................................................................ 43
I/O Points ............................................................................................................................................................ 44

What is a VVT Bypass II?

NOTE

Introduction

The VVT Bypass II (#OPN-VVTBP-02), a component of the i-Vu® Control System, regulates the supply duct static pressure by controlling one of the following:
The system's bypass damper The controller's damper actuator provides 45 in/lbs (5 Nm) of torque. If the actuator's torque is insufficient, the VVT Bypass II can be used to drive an external high-torque actuator. Or, the controller can drive multiple external damper actuators.
The air source supply fan's variable frequency drive (VFD)
The VVT Bypass II controller is available in both English or Metric units. The metric version has (-M)
appended to the part number. Everything in this document applies to both versions.
The i-Vu Control System uses linkage to exchange data between the zone terminals and their air source to form a coordinated HVAC system. The system's air source controller, zone controllers, and bypass controller are linked so that their data exchange can be managed by one zone controller configured as the VVT Master.
You can disconnect the actuator from the controller and mount them separately, connecting them with just the actuator cable or using an additional extension cable, up to a maximum distance of 300 feet.
The following illustration shows the VVT Bypass II in a typical i-Vu® Control System.
VVT Bypass II Controller CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 1
Introduction
NOTE
This document gives instructions for field-installation of a VVT Bypass II in an i-Vu® Control System.
VVT Bypass II Controller CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 2
Introduction

Specifications

CAUTION
Driver drv_bpopn02
Power 24 Vac ±10%, 50–60 Hz
14 VA power consumption 26 Vdc (25 V min, 28.8 V max) Single Class 2 source only, 100 VA or less
Actuator Belimo brushless DC motor, torque 45 inch-pounds (5 Nm), runtime 154 seconds
Act Net port To connect the actuator cable and the VVT Bypass II
BACnet port
Rnet port You can connect:
Local Access port For system start-up and troubleshooting
Input 1 input for connecting the Duct air temperature sensor (#33ZCSENDAT)
For communication with the controller network using BACnet ARC156 (156 kbps) or BACnet MS/TP (9600 bps – 76.8 kbps)
One Equipment Touch, using an external 24 Vac power supply or One TruVu™ ET Display, using an external 24 Vdc power supply
Input resolution 10 bit A/D
Analog output 1 analog output, 0–10 Vdc (5 mA max).
The controlled device must have a minimum of 2000 Ohms resistance measured from its input to ground and must share the same ground as the controller.
Output resolution 8 bit D/A
Integral airflow sensor Precision differential pressure sensor 0–2 in. H2O, sensitive down to ±0.001 in.
H2O. Barbed tapered airflow connections accept 3/16 in. (4.75 mm) I.D. tubing. Allows for readings across the 0–2 in. H2O range, accurate to ±5% of full flow at 2 in. H2O.
Battery 10-year Lithium CR2032 battery retains the following data for a maximum of
10,000 hours during power outages: control programs, editable properties, schedules, and trends.
Protection Built-in surge and transient protection for power and communications in
compliance with EN61000-6-1.
Incoming power and network connections are protected by non-replaceable internal solid-state polyswitches that reset themselves when the condition that causes a fault returns to normal.
The power, network, input, and output connections are also protected against transient excess voltage/surge events lasting no more than 10 msec.
To protect against large electrical surges on serial EIA-485
networks, place a PROT485 at each place wire enters or exits the building.
BT485 connector You attach a BT485 (not included) to a controller at the beginning and end of a
network segment to add bias and to terminate a network segment.
VVT Bypass II Controller CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 3
Introduction
Status indicators LEDs indicate status of communications, running, errors, power, and digital
outputs
Environmental operating
32 to 130°F (0 to 54.4°C), 10–90% relative humidity, non-condensing
range
Storage temperature range -24 to 140°F (-30 to 60°C), 0 to 90% relative humidity, non-condensing
Physical UL94-5VA plenum rated enclosure for installation in plenum (or other space for
environmental air) in accordance with NEC Section 300.22 (c) and (d)
Controller and actuator overall dimensions
Width: Height:
8.9 in. (22.7 cm)
5.9 in. (15.0 cm)
Controller and actuator mounting dimensions
Controller overall dimensions
Controller mounting dimensions
Actuator overall dimensions Width:
Actuator mounting
7.1 in. (18.0 cm) from left side controller mounting hole centerline to actuator mounting hole centerline
Width: Height: Depth:
6.4 in. (16.3 cm)
5.7 in. (14.5 cm)
2.1 in. (5.3 cm)
5.3 in. (13.4 cm) from left side controller mounting hole centerline to right side controller mounting hole centerline
3.0 in. (7.6 cm) Height: Depth:
5.9 in. (15.0 cm)
2.5 in. (6.4 cm)
4.4 in. (11.2 cm) from shaft centerline to actuator mounting hole centerline
dimensions
Panel depth 2.5 in. (6.4 cm) minimum
Shaft dimensions Minimum shaft diameter: .25 in. (.64 cm)
Maximum shaft diameter: .63 in. (1.59 cm) Minimum shaft length: 1.75 in. (4.45 cm)
Weight 1.8 lbs (0.82 kg)
BACnet support Conforms to the BACnet Advanced Application Controller (B-AAC) Standard Device
Profile as defined in ANSI/ASHRAE Standard 135-2012 (BACnet) Annex L, Protocol Revision 9
Listed by UL-916 (PAZX), cUL-916 (PAZX7), FCC Part 15-Subpart B, Class B, CE
VVT Bypass II Controller CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 4
Introduction

Safety Considerations

CAUTION
WARNING Electrical Shock Hazard
WARNING
Air conditioning equipment will provide safe and reliable service when operated within design specifications. The equipment should be operated and serviced only by authorized personnel who have a thorough knowledge of system operation, safety devices, and emergency procedures.
Good judgment should be used in applying any manufacturer's instructions to avoid injury to personnel or damage to equipment and property.
Failure to follow this warning could cause personal injury, death, and/or equipment damage.
Disconnect all power to the unit before performing maintenance or service. Unit may automatically start if power is not disconnected.
materials such as mercury contactors.
Follow all local, state, and federal laws regarding disposal of equipment containing hazardous
VVT Bypass II Controller CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 5
Installing the VVT Bypass II

Field-supplied hardware

Installing the VVT Bypass II

To install the VVT Bypass II:
1 Mount the controller (page 7).
2 Wire the controller for power (page 12).
3 Set the controller's address (page 14).
4 Wire the controller to the BACnet MS/TP or BACnet ARC156 network (page 14).
5 Wire the inputs and outputs (page 16).
Each VVT Bypass II installation requires the following field-supplied components:
damper
damper actuator (if high-torque actuator or slaved dampers are required)
duct air temperature sensor
transformer— 24 Vac, 40VA
wiring
VVT Bypass II Controller CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 6
Installing the VVT Bypass II

Mounting the VVT Bypass II

To mount the controller and actuator

Mount the VVT Bypass II on the bypass duct damper actuator shaft. For service access, allow at least 1 foot (.3 m) of clearance between the front of the controller and adjacent surfaces.
To disconnect and mount the controller and actuator separately
VVT Bypass II Controller CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 7
Installing the VVT Bypass II
Act Net
Disconnect the actuator from the controller by inserting a screw driver in the slot on the back of the VVT Bypass II and pressing the tab. The actuator cable or an attached extension cable must connect to the controller's port.
1 Turn the damper shaft to fully close the damper.
2 Mount the controller to the VVT terminal by sliding the clamp assembly onto the damper shaft.
VVT Bypass II Controller CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 8
Installing the VVT Bypass II
NOTE
O-ring Bushing
Anti-rotation slot
NOTES
For service access, allow at least 1 foot (.3 m) of clearance between the front of the controller and
adjacent surfaces.
3 Secure the controller and the actuator by installing the screws, anti-rotation slot's bushings, and o-rings that
are supplied with the VVT Bypass II.
Center the bushing in the slot. Failure to do so may cause the actuator to stick or bind.
The VVT Bypass II must be secured, but loose enough to allow movement. of the damper shaft.
VVT Bypass II Controller CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 9
Installing the VVT Bypass II
CAUTIONS
must
You
use the screws, anti-rotation slot's bushings, and o-rings that are shipped with the VVT Bypass
II.
Overtightening the screws so that the controller and actuator cannot move may damage the unit.
4 Hold down the controller’s damper release button and rotate the actuator clamp in the same direction that
closed the damper. Rotate the clamp until it stops, then rotate it back one notch.
5 Release the button.
6 Tighten the actuator clamp to the damper shaft by tightening the two M5 nuts.
VVT Bypass II Controller CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 10
Installing the VVT Bypass II
High
NOTE
7 Hold down the actuator damper release button and rotate the damper from fully closed to fully open. If the
damper traveled less than 90 degrees, do the following to set the actuator's fully open position:
a) Loosen the appropriate stop clamp screw. See figure below.
b) Move the stop clamp until it contacts the
edge of the actuator cam.
c) Tighten the screw.
8 Hold down the actuator damper release button, rotate the damper to verify that it fully opens and closes, then
release the button.
9
10 Connect the tube provided to the controller's
connector. Using 1/4" poly tubing, connect the other end to a duct static pressure probe (for example, Dwyer Instruments part #A-491, or the equivalent, for a 6” length probe) located in the supply air duct downstream of the bypass damper, but before the first branching of ductwork.
Tubing should be at least 2 ft. (.61 meters) long for stable airflow measurement. The combined high
and low tubing length should not exceed 16.4 ft. (5 meters) in order to ensure accurate measurements.
VVT Bypass II Controller CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 11
Installing the VVT Bypass II
Low

Wiring the VVT Bypass II for power

WARNING
CAUTIONS
11 Connect the controller's
return.
connector to open space for plenum return or to a room space if using ducted
The VVT Bypass II is powered by a Class 2 power source. Take appropriate isolation measures when mounting it in a control panel where non-Class 2 circuits are present.
Carrier controllers can share a power supply as long as you:
Maintain the same polarity.
Use the power supply only for Carrier controllers.
Do not apply line voltage (mains voltage) to the controller's ports and terminals.
VVT Bypass II Controller CARRIER CORPORATION ©2019 Installation and Start-up Guide All rights reserved 12
Loading...
+ 36 hidden pages