AQUAZONE TM 50RHC,RVC,RHR,RVR
RDS,RHS,RVS,HQL,VQL,KQL,RTG,RWS
Complete C
Deluxe D
Solid-State Heat Pump Controls
Control Operation and Troubleshooting
Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS ............................ 1
GENERAL ............................................ 12
INSTALLATION ....................................... 2-9
Wiring Requirements ................................... 2
Wiring Connections .................................... 2
Jumper Settings ........................................ 2
Complete C Control ..................................... 8
• WATERCOIL FREEZE PROTECTION (FP1) LIMIT
SETTING
• AIR COIL FREEZE PROTECTION (FP2) LIMIT SETTING
• ALARM RELAYSETTING
DeluxeO Control ....................................... 8
• WATERCOIL FREEZE PROTECTION (FP1) LIMIT
SETTING
• AIR COIL FREEZE PROTECTION (FP2) LIMIT SETTING
• ALARM RELAYSETTING
• LOW PRESSURESETTING
CONFIGURATION .................................... 9,10
Complete C Control DIP Switches ...................... 9
• PERFORMANCE MONITOR (PM)
• STAGE 2
• DDC OUTPUT AT EH2
• FACTORY SETTING
DeluxeD Control DIP Switches ......................... 9
• D]PSWITCH BANK 1 (S l)
• DIP SWITCH BANK2 ($2)
DeluxeD Control Accessory RelayConfigurations .... 10
CYCLE WITH FAN
CYCLE WITH COMPRESSOR
DIGITAL NIGHT SET BACK (NSB)
WATER VALVE (Slow Opening)
OUTSIDE AIR DAMPER (OAD)
HUMIDITY CONTROL
CONTROL OPERATION ............................. 11-16
Complete C Control Indicators......................... lI
Complete C and Deluxe D Controls .................... 11
TEST MODE
RETRYMODE
POWER UP MODE
STANDBYMODE
COOLING MODE
HEATINGSTAGE 1MODE
HEATINGSTAGE2 MODE
LOCKOUT MODE
LOCKOUT WITH EMERGENCY HEAT
EMERGENCY HEAT MODE
HIGH-PRESSURE SWITCH (HP)
LOW-PRESSURE SWITCH(LP)
WATERCOIL FREEZE PROTECTION (FP1)
AIR COIL FREEZE PROTECTION (FP2)
CONDENSATEOVERFLOW (CO)
OVER/UNDER VOLTAGESHUTDOWN
PERFORMANCE MONITOR (PM)
ANTI-SHORT CYCLEPROTECTION
RANDOM START
SWAPPEDFP1/FP2 THERMISTORS
SENSORS
Page
Deluxe D Control ...................................... 13
• LED INDICATORS
EXTENDED COMPRESSOR OPERATION MONITOR
STANDBY/FAN ONLY MODE
HEATING STAGE 1MODE
HEATING STAGE 2 MODE
HEATING STAGE 3 MODE
EMERGENCY HEAT MODE
COOLING STAGE 1
COOLING STAGE 2
NIGHT LOW LIMIT (NLL) STAGED HEATING
Thermostat Inputs .................................... 14
• COMPLETE C CONTROL
• DELUXE D CONTROL
• COMMUNICATION PORTS
• MECHANICAL NIGHT SET BACK
TROLIBLESHOOTING ............................... 16-20
Field Inputs ........................................... 16
Sensor Inputs ......................................... 16
Sensor Outputs ....................................... 17
Test Mode ............................................. 17
l MPORTANT: Read the entire instruction manual before /starting inst_dlation.
]
SAFETY CONSIDERATIONS
Read and follow mmmfacturer instructions cguefully. Fol-
low all local electrical codes during installation. All wiring
must conform to local and national electrical codes, hnproper
wiring or installation may dalnage sensol:
Undel,stand the signal words DANGER, WARNING and
CAUTION. These words gueused with the safety alert symbol.
DANGER identifies the most serious hazards which will result
in severe pel,sonal injuU or death. WARNING signifies a haz-
_udwhich could result in personal injuU or death. CAUTION
is used to identify unsafe practices which would result in minor
personal injuU or property damage.
GENERAL
Aquazone Complete C and Deluxe D electronic heat pump
controls are durable, microprocesso>based controllers used to
improve the safety mid operation of Aquazone water source
heat pumps. The microprocessor board is specifically designed
to protect against building electrical system noise contamina-
tion mid radio fiequency interference.
The Complete C control base model is a low cost, easy to
use control that provides all the necessaU features for water
source heat pump safety mid operation. The Complete C
control features a light-emitting diode (LED) to indicate high
pressure, low pressure, low voltage, high voltage, air/water
freeze protection, condensate overflow and control status. The
Complete C control is compatible with most heat pump
thermostats, but is not compatible with Heat/Cool thermostats.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 111 Catalog No. 535-00058 Printed in U.S.A. Form 50H,K,R-2T Pg 1 6-05 Replaces: 50H,K,R-1T