Carrier Viento 200, Viento 300, Viento 350 Operation & Service Manual

Page 1
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- # 1/54
INSTALLATION
Page 2
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- # 2/54
Introduction...................................................................................................................................................................................4
Preparation before installation....................................................................................................................................................5
Vehicle partition..........................................................................................................................................................................................................6
Box preparation............................................................................................................................................................................7
Drilling.........................................................................................................................................................................................................................7
Roof top and cut mounting............................................................................................................................................................................................................8
Nosemount..................................................................................................................................................................................................................................11
Evaporator ..................................................................................................................................................................................................................................12
Harness and hoses hole.............................................................................................................................................................................................................14
Drain water hose hole.................................................................................................................................................................................................................15
Mushrooms...............................................................................................................................................................................................................16
Preparation .................................................................................................................................................................................................................................16
Set up..........................................................................................................................................................................................................................................18
Unit installation...........................................................................................................................................................................19
Evaporator installation...............................................................................................................................................................22
Hoses...........................................................................................................................................................................................23
Mounting recommendations......................................................................................................................................................................................24
Preparation...............................................................................................................................................................................................................25
Unit connection...........................................................................................................................................................................27
Refrigeration hoses...................................................................................................................................................................................................29
Evaporator connection...............................................................................................................................................................33
Refrigeration hoses...................................................................................................................................................................................................33
RAT sensor...............................................................................................................................................................................................................35
Drain pan..................................................................................................................................................................................................................36
INSTALLATION Table of content
Page 3
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- # 3/54
Driver cab preparation ...............................................................................................................................................................37
Cab command harness fitting ...................................................................................................................................................38
Compressor connection ............................................................................................................................................................40
Injection thermostat ..................................................................................................................................................................................................42
Commissioning...........................................................................................................................................................................47
Leak checking...........................................................................................................................................................................................................47
Unit vacuum..............................................................................................................................................................................................................48
Refrigerant charge....................................................................................................................................................................................................49
Settings.....................................................................................................................................................................................................................51
CPR adjustment..........................................................................................................................................................................................................................51
TXV setting .................................................................................................................................................................................................................................53
INSTALLATION Table of content
Page 4
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- # 4/54
This document gives the correct rules to follow in order to correctly install the VIENTO 200 / 300 / 350 units.
SAFETY FIRST
MANDATORY BEFORE ANY ELECTRICAL OPERATION:
DISCONNECT THE VEHICLE BATTERY:
- First remove the battery ground (-)
- then remove the positive battery (+)
PERSONAL PROTECTIVE EQUIPMENT
Always use adequate personal protective equipment before doing anything on this refrigerant unit.
BODYBUILDER RECOMMENDATIONS
Drain hose from the evaporator to the outside must have an angle to insure water to be drained out. A descent of 10 cm minimum must be applied between evaporator drain water hoses and the hoses
inside the body (picture page 36).
Installation Introduction
Page 5
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- # 5/54
1. Unpack the box contents in your warehouse.
KEEP THE DOCUMENT DELIVERED WITH THE UNIT !
2. Unpack the box.
3. Check if the box content corresponds to the bill of material on the packaging.
Condenser Evaporator Mounting kit Cab command
In the event of any abnormality (missing, damaged part or part number etc), fill in the form "Advance Warning, DOA, Claim"
Installation Preparation before installation
Page 6
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- # 6/54
Take care not to obstruct the air intakes on the
evaporator section and the ventilation ducts.
For any mobile partition installation, contact our
Technical Department or refer to the following chart:
MODELS Evaporator X Y
MXS 600
Viento 200
MXS 850 MXS 850
Viento 300
MXL 850
500 mm
MXS 1100
Viento 350
MXL 1100
1000 mm
150 mm
Installation Preparation before installation Vehicle partition
Page 7
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- # 7/54
RECOMMENDATIONS
Before box preparation and unit installation commences, protect the vehicle roof and the refrigeration
box floor (cover, cardboard…).
There are 3 possibilities to fit the unit:
Roof top Nosemount Roof cut mounting
Installation Box preparation Drilling
Page 8
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- # 8/54
1. Present the drilling template – not supplied - (refer to the bodybuilder drawing)
2. Mark out the 4 fixing holes and the electrical harness and hoses hole
3. Drill the fixing holes.
drill 10 mm
4. For roof top mounting: drill a hole 80 mm to pass hoses and harnesses.
Installation Box preparation Drilling Roof top and cut mounting
Page 9
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- # 9/54
5. Install the 4 silent blocks:
put silicone to waterproof on the bottom. put silicone to waterproof on the 4 screws before to install
the host unit.
Installation Box preparation Drilling Roof top and cut mounting
Page 10
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #10/54
6. To pass harnesses and hoses between condenser and evaporator, drill the electrical harness and hoses hole.
Roof cut mounting : on vertical face of the vehicle Roof top mounting: on the roof of the body (refer to
bodybuilder drawing)
Installation Box preparation Drilling Roof top and cut mounting
Page 11
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #11/54
1. Present the drilling template – not supplied (refer to the bodybuilder drawing)
2. Mark out fixing and electrical harness and hoses holes.
3. Drill the fixing holes
- drill 10 mm
4. Drill the electrical harness and hoses hole.
Installation Box preparation Drilling Nosemount
Page 12
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #12/54
NOTE :
- The drilling depends on the evaporator you have to install.
- Let a minimum space of 15 cm between the box wall and the rear of the evaporator.
1. Mark the fixing holes for the evaporator (refer to the bodybuilder drawing).
If needed, use the fixing material adapted to reinforcement done by the bodybuilder.
If you don't have reinforcement, you will have to use mushrooms (refer to section "Mushrooms" page 16).
Installation Box preparation Drilling Evaporator
Page 13
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #13/54
If body reinforced, install the insert using the adapted tool
(manual or pneumatic).
Installation Box preparation Drilling Evaporator
Page 14
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #14/54
2. Drill the electrical harness and hoses hole inside the box.
Installation Box preparation Drilling Harness and hoses hole
Page 15
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #15/54
1. If body is not prepared to pass harnesses, refrigerant and water drain hoses, drill the hose inside body.
RECOMMENDATIONS
A descent of MINIMUM 10 cm must be applied between the drain water hoses pipe and the hoses inside the body to help to drain water out.
Installation Box preparation Drilling Drain water hose hole
Page 16
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #16/54
1. From box inside, drill 4 holes 5 mm in the roof through and through (drill of minimum size 140mm)
2. Countersink with a drill 12,5 mm the 4 tapping drill holes realized at the previous step.
RECOMMENDATIONS Take care not to damage the 5 mm drilling of
the box external skin.
3. From box outside, countersink with a circular slitting saw 22 mm.
RECOMMENDATIONS Take care not to damage the 12,5 mm drilling
of the box internal skin.
Installation Box preparation Mushrooms Preparation
Page 17
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #17/54
4. Measure the roof thickness.
5. Adjust the mushroom length (L) to the roof thickness minus the internal skin thickness (E –E')
L: mushroom length E: roof thickness E': internal skin thickness
Mushroom in place
1. mushroom
2. silicon gasket
3. skin of external box
4. polyurethane foam
5. skin of internal box
6. evaporator upper side
7. washer
8. screw M12
Installation Box preparation Mushrooms Preparation
Page 18
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #18/54
1. Apply silicon on the internal side of the mushroom head.
2. Put mushrooms in holes previously realized in box roof.
3. With a mallet, slightly crush the silicon gasket.
4. Follow silent block installation. Take care to clean silent block surface for a better sticking/water proof ness.
Installation Box preparation Mushrooms Set up
Page 19
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #19/54
1. Remove the grill:
remove the 4 fixing screws remove the grill
Installation Unit installation
Page 20
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #20/54
2. Remove the top cover:
remove the 3 rear fixing screws push the cover and remove it.
RECOMMENDATIONS Do not try to un-tight the 2 front screws of top
cover. They are part of the caplocks system.
Installation Unit installation
Page 21
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #21/54
3. Roof top and roof cut mounting installation:
Drill the 4 fixing holes 10 mm in the bottom cover of
the unit.
4. Nosemount installation:
Use the 4 fixing holes at the rear of the frame (refer to
"Box preparation/Drilling/Nosemount – page11)
5. Using the lifting device (P/N 07-60110-00) put the unit in place on the 4 silent blocks.
6. Roof top and roof cut mounting installation:
Fix the unit with the 4 silent blocks and bolts delivered in
the packaging.
7. Nosemount installation:
Fix the unit with the 4 bolts.
Installation Unit installation
Page 22
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #22/54
1. Remove the two side panels.
2. Using the adapted tool, put the evaporator facing the fixing holes previously drilled.
3. Check the minimum distance between the rear of the evaporator and the box is correct (refer to the chart p6)
4. Tighten the screws.
Installation Evaporator installation
Page 23
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #23/54
RECOMMENDATIONS
For a good functioning of refrigeration circuit,
refrigeration hoses must be clean and dry.
Hoses must be stocked in a dry area, with
less variation in temperature as possible and sheltered from moisture.
The two ends MUST ABSOLUTELY been
blocked with tight caps to avoid any internal damages or condensation until their connection into the circuit.
To fit hoses and electrical harnesses, use as much as
possible RSGU clamps.
To protect hoses and electrical harnesses, use adequate
rubber funnels to avoid cutting with metallic corners.
Installation Hoses Stocking recommendations
Page 24
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #24/54
Right installation
Wrong installation
Do not twist or curve the hose. Keep enough length to avoid length variation when the
pipes are under pressure.
Pipes length can vary between -2% to +4%. Using elbows and fittings make easier installations,
assist accessibility and increase hoses/pipes life.
Always insure that minimum radius is respected. Provide
a radius as big as possible to avoid constriction.
Minimum curve radius Module 6 80 mm Module 8 95 mm Module 10 110 mm Module 12 130 mm
Installation Unit hoses Mounting recommendations
Page 25
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #25/54
Tools requested
1. Cut the hose at the right length with appropriate tool.
2. Put POE oil on the connector on fitting.
3. Widen hose clearance with adapted tool before to insert double-clic clamp.
4. Insert double-clic clamp on the hose.
Installation Unit hoses Preparation
Page 26
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #26/54
5. Lubricate the fitting.
6. Don't forget to remove the hose cap.
7. Insert connector in the hose.
8. Crimp the double-click clamp with appropriate crimping tool.
Installation Unit hoses Preparation
Page 27
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #27/54
1. Run the electrical harnesses and ignition cable inside the vehicle body.
Installation Unit connection
Page 28
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #28/54
2. Run refrigeration hoses inside the vehicle body.
3. Run the drain water hose inside the vehicle body.
RECOMMENDATIONS
Always mark off the hot gas line (both sides
of the hose) in order to avoid the confusion with the liquid line hose.
Remove caps from the hoses JUST before
connecting in order to avoid too much moisture in the circuit.
Installation Unit connection
Page 29
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #29/54
RECOMMENDATIONS
Always check that O-ring is still in place. If O-
ring is missing, put a new one in place.
4 hoses have to be connected on the unit:
Oil return line High pressure line Liquid line Hot gas line
Installation Unit connection Refrigeration hoses
Page 30
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #30/54
4. Connect the OIL RETURN HOSE to the oil separator (lower fitting) to the compressor.
5. Connect the HIGH PRESSURE LINE to the oil separator – upper fitting – to the
Installation Unit connection Refrigeration hoses
Page 31
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #31/54
6. Remove the Hot Gas valve (HGV) solenoid to connect the HOT GAS LINE hose easily.
7. Connect the HOT GAS LINE fitting to the Hot Gas valve.
8. Re-install the Hot Gas valve solenoid.
9. Connect the LIQUID LINE HOSE to the filter drier.
RECOMMENDATIONS
45° fitting recommended if lateral outlet needed. GENERALY, use the appropriate fitting
depending on the installation.
Installation Unit connection Refrigeration hoses
Page 32
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #32/54
10. Attach regularly all hoses, harnesses with plastic tie­wraps.
Installation Unit connection Refrigeration hoses
Page 33
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #33/54
3 hoses have to be connected to the evaporator :
- Suction pressure hose: from the CRP valve outlet (16 – module 12) to the compressor.
- Liquid line hose: from the expansion valve through the heat exchanger (8 – module 6) to the host unit.
- Hot gas line: from the defrost element inlet (8 – module 6) to the host unit.
1. Run hoses and harness through the hole.
- Suction line
- Liquid line
- Hot gas line
- Fan motor wires
- RAT cable
- Injection valve if so equipped
2. Prepare hoses as described in section "Unit hoses / Preparation - p25".
Installation Evaporator connection Refrigeration hoses
Page 34
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #34/54
3. Install fitting and connect the SUCTION PRESSURE LINE hose (16 – module 12) to outlet of the CPR valve.
4. Install fitting and connect the HOT GAS LINE hose -with red label (8 – module 6) to the drain pan serpentin inlet.
5. Install fitting and connect the LIQUID LINE (∅8 – module
6) to the Thermostatic Expansion Valve inlet (through the heat exchanger).
6. Attach all hoses with plastic tie-wraps.
Installation Evaporator connection Refrigeration hoses
Page 35
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #35/54
7. With the ∅6 clamp, install the RAT sensor.
8. Connect together evaporator fan connectors.
9. Put the bottom skin in place.
Installation Evaporator connection RAT sensor
Page 36
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #36/54
10. Put the drain water pipe in place.
RECOMMENDATIONS
A descent of MINIMUM 10 cm must be applied between the drain water hoses pipe and the hoses inside the body to help to drain water out.
11. Connect the drain water hoses between drain water pipes and evaporator water tubes.
12. Fix tie-wrap sockets to maintain drain tubes in the right position.
13. Insulate the two holes with silicone.
14. Instal the two evaporator sides.
Installation Evaporator connection Drain pan
Page 37
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #37/54
RECOMMENDATIONS Before drilling the floor, check the location of
fuel tank, harness and/or tubes.
1. Drill a hole in the cab floor (behind driver or passenger seat – depends on battery location).
RECOMMENDATIONS Protect the hole (ex: armoured hose) to avoid
harness damage.
2. Run water drain hose through the floor.
3. Run battery cable through the floor.
4. Run the cab command and ignition cable to the dashboard.
5. Install a capping (not supplied) to cover the hoses and harness.
6. Insulate the water drain hose.
Installation Driver cab preparation
Page 38
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #38/54
NOTE: For cab command harness fitting, refer to the vehicle mounting kit instructions.
1. Route the cab command harness to the vehicle dashboard.
RECOMMENDATIONS
Protect or move the harness away from
metallic corners of the chassis.
Avoid connecting the harness to/or in contact
with heating source.
Avoid connecting the harness to parts that
may cause vibrations.
Installation Cab command harness fitting
Page 39
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #39/54
2. Fit the cab command (in specified location).
RECOMMENDATIONS
Take care not to pierce any harness or hoses
within the dashboard.
If the cab command is built into the
dashboard, fit it as far as possible from the heating ducts.
Maximum temperature of exposure: 70°C
(158°F)
The cab command MUST NOT be located
behind the screen (T° too high and obstruction of windscreen).
Installation Cab command harness fitting
Page 40
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #40/54
MANDATORY BEFORE ANY ELECTRICAL OPERATION.
DISCONNECT THE VEHICLE BATTERY: Remove the battery ground (-), the positive battery (+) and lock-out.
1. Move along hoses and battery harness to the compressor and vehicle battery.
2. Attach regularly the harness with plastic tie-wraps and base tie-wraps onto the chassis.
3. Insulate the hole with silicon.
RECOMMENDATIONS
Protect or move the harness away from
metallic corners of the chassis.
Avoid connecting the harness to/or in contact
with heating source.
Avoid connecting the harness to parts that
may cause vibrations.
Do not secure the unit harness to the vehicle
harness or piping
Avoid drilling the vehicle frame.
Installation Compressor connection
Page 41
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #41/54
4. Connect the HIGH PRESSURE HOSE.
5. Connect the SUCTION PRESSURE HOSE.
6. Connect the OIL RETURN HOSE if available (under the compressor).
Installation Compressor connection
Page 42
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #42/54
7. Install injection thermostat on the compressor High pressure line fitting with the clamp.
RECOMMENDATIONS
Take care to place correctly the thermostat in order to have a good contact with the fitting.
8. Fit injection thermostat wires and compressor clutch wires in a retractable sleeve.
9. Insert terminals in the injection thermostat.
Installation Compressor connection Injection thermostat
Page 43
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #43/54
10. Protect the wires with sleeve.
11. Maintain all cables with plastic tie-wraps.
Installation Compressor connection Injection thermostat
Page 44
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #44/54
1. Route the ignition cable to the vehicle fuse box.
2. Connect the white wire onto the fuse holder supplied in the mounting kit (1A).
3. Refer to the corresponding mounting kit instruction to connect the +12Vdc ignition live.
4. Cut the battery harness to the required length.
5. Strip the + battery (35mm
2
red) and the fuse holder for the
+ microprocessor positive.
6. Using a crimping tool, install the (125A) fuse supplied with the mounting kit.
NOTE : Soft-solder is recommended.
Installation Battery & ignition key harness fitting
Page 45
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #45/54
7. Heat the retractable sleeve to insulate the connector.
8. Strip the battery ground (-) (35mm
2
black) – crimp the
terminal with the adapted crimping tool.
NOTE : Soft-solder is recommended.
9. Install the 80 amps fuse holder as closed as possible from the 12 Vdc battery.
10. Put grease on the fuse holder connections.
Installation Battery & ignition key harness fitting
Page 46
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #46/54
11. Install the 80 amps fuse in the fuse holder.
12. Install protection cap on the fuse.
13. Connect unit ground (-) to the vehicle chassis.
14. Re-connect the ground (-) of the vehicle battery.
Installation Battery harness fitting
Page 47
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #47/54
REQUIREMENT
1 vacuum pump 1 manifold gauges (4 connections) 1 vacuumeter
To check gas leak
1. Install manifold gauges on the compressor side.
2. Connect the vacuum pump to the manifold gauges.
3. Start the vacuum pump and vacuum for 15 mn: to remove the air in the circuit.
4. After 15mn, stop the vacuum pump.
5. Connect the nitrogen to the manifold gauges.
6. Put 15 bar (219 psi) in the circuit.
7. Use bubbles water on all refrigeration fittings
8. No bubbles formation means that the circuit is tight.
Installation Commissioning Leak checking
Page 48
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #48/54
To vacuum the circuit
1. Remove the nitrogen.
2. Start the vacuum pump.
3. Apply "Triple evacuation" process (refer to refrigeration training module)
4. Stop the vacuum pump.
5. Check if vacuum is complete with vacuumeter. (refer to refrigeration training module)
Installation Commissioning Unit vacuum
Page 49
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #49/54
REQUIREMENT
1 manifold gauges (4 connections) 1 refrigerant cylinder 1 scale - minimum precision requested: 5%
After vacuum, charge the circuit
1. Install the manifold gauges on "Free Schrader" fitting located inside the condenser on the high pressure line.
2. Place refrigerant cylinder on scale and connect charging line from cylinder to manifold.
3. Purge charging line at inlet manifold.
4. Note the weight of refrigerant cylinder. Be sure that the unit is stopped during this operation.
5. Open liquid valve on refrigerant cylinder and allow the liquid refrigerant to flow into the unit until the correct weight of refrigerant has been added as indicated by weight scale.
Installation Commissioning Refrigerant charge
Page 50
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #50/54
6. When refrigerant cylinder weight (scale) indicates that the correct charge has been added, close the manifold valves.
Refrigerant charge Viento 200 0.85 Kg ± 5% Viento 300 1 Kg ± 5% Viento 350 1,1 Kg ± 5%
NOTE
It is possible that all liquid may not be pulled into the circuit.
Complete the charge in vapour through the
compressor.
Installation Commissioning Refrigerant charge
Page 51
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #51/54
The Compressor Regulation valve is a device designed to regulate the flow of refrigerant returning to the compressor from the evaporator, this ensures correct capacity for the unit.
The Compressor Regulation valve also reduces the load on the compressor during start-up & whilst in operation which is why it is important it is correctly set-up on commissioning.
Adjustment has to be done:
Road operation Heat or defrost mode
Compressor speed at 2400 rpm
Installation Commissioning Settings CPR adjustment
Page 52
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #52/54
1. Connect manifold to CPR fitting.
2. Start the unit in Heating or Defrost mode.
3. Check compressor speed: 2400 rpm.
4. Remove CPR cap.
5. Adjust CPR to get gauge pressure value with hexagonal socket head wrenches (n°8) :
To raise the suction pressure : turn the setting screw
clockwise
To lower the suction pressure: turn the setting screw
counterclockwise.
CPR adjustment R134a R404A Viento 200 3 bar 2.7 bar
Viento 300 2.2 bar
LA
1,85 bar
HA
1.25 bar
Viento 350 2.8 bar
LA
3.4 bar
HA
1,8 bar
6. When the setting has been adjusted, tighten the jam nut securely against the setting screw to prevent any movement of the setting screw due to vibrations in the unit.
7. Replace the cap.
Installation Commissioning Settings CPR adjustment
jam nut
settting screw
cap
Page 53
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #53/54
The Thermo Expansion valve is a precision device designed to meter the flow of refrigerant into an evaporator in exact proportion to the rate of evaporation of the refrigerant in the evaporator.
The Thermo Expansion valve can control the refrigerant gas leaving the evaporator at a pre-determined superheat.
The superheat is the temperature difference between T1 (Temperature measured at remote bulb location) and P2 (Evaporation temperature of the last liquid drop).
T1 : Temperature at remote bulb location P2 : Evaporator outlet pressure S : Superheat
Installation Commissioning Settings TXV setting
Page 54
Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #54/54
1. Connect manifold to evaporator outlet fitting.
2. Install a sensor on the expansion valve bulb location.
3. Run the unit on COOLING mode.
4. Correct superheat:
Turn anti-clockwise to increase flow & decrease
superheat
Turn clockwise to decrease flow and increase
superheat.
TXV adjustment
Viento 200 Viento 300 Viento 350
8°C at box temperature 0°C (14.4°F at box T° : 32°F)
4°C at box temperature -20°C (7.2°F at box T° : -4°F)
Installation Commissioning Settings TXV setting
Loading...