Carrier Ultra, Solara, Extra XT, Ultra XL Operator's Manual

OPERATOR’S MANUAL
for
Ultra/Ultra XL, Ultima and Solara
Beginning With
S/N HAR90573670
And Extra/Ultra XT
Trailer Refrigeration Units
Standard Microprocessors
62--10601 Rev G
Trailer Refrigeration
FAULT
START/STOP
FUNCTION CHANGE
UNIT
DATA
PRETRIP
CHECK
AUTOS/S
CONTINUOUS
MANUAL
DEFROST
ENTER
SETPOINT BOX TEMPERATURE
-20 34.5° F
STANDBY
FAULT
STANDBY
POWER ON
10START/RUN
OFF
STANDBY
ENGIN E
R
MANUAL
for
OPERATOR’S
TRAILER
REFRIGERATION UNITS
WITH STANDARD
MICROPROCESSOR
CONTENTS
Page
Safety 1....................................
Unit Identification 2..........................
Unit Operation 4............................
Starting Unit 4..............................
Pretrip Check 8.............................
Changing Setpoint 10........................
Start--Stop Operation 12......................
Continuous Run Operation 14.................
Manual Defrost 16...........................
Function Change 18.........................
Unit Data 20................................
Alarm Display and Reset 22..................
Standby Operation 24........................
Stopping Unit 26............................
Pre--Trip Inspection 28.......................
Product Loading 30..........................
Recommended Transport Temperatures 32.....
Problems 33................................
Fuses 34...................................
Unit Maintenance 35.........................
Unit Maintenance Schedule 36................
Priming Fuel System 39......................
Emergency Road Service 40..................
1
62--10601
SAFETY
Your Carrier Transicold refrigeration unit has been designed with the safety of the operator in mind. During all pre-trip inspections, daily inspections, and problem troubleshooting, you may be exposedtomovingparts; pleasestayclear of allmoving partswhen the unit isin operation and when the Start/Run-Off Switch is in the START/RUN position.
AUTO-START
YourrefrigerationunitisequippedwithAuto-Startin both Start/Stop and Continuous Run modes. The unit may start at any time, a buzzer will sound for 5 seconds before the unit is started. When performing any check of the refrigeration unit (e.g., checking the belts, checking the oil), makecertain that the Start/Run-Off Switch is in the OFF position.
ENGINE COOLANT
The engine is equipped with a pressurized cooling system. Under normal operating conditions, the coolant in theengine andradiator isunder high pressureandis veryhot. Contact withhot coolantcan cause severe burns. Do not remove the cap from a hot radiator; if the cap must be removed, do sovery slowly in order to releasethe pressure without spray.
REFRIGERANTS
The refrigerant contained in the refrigeration system of your unit can cause frostbite, severe burns, or blindness when in direct contact with the skin or eyes. For this reason, and because of legislation regarding the handling of refrigerants during system service, we recommend that, whenever your unit requires service of the refrigeration system, you contact your nearest Carrier Transicold authorized repair facility for service.
BATTERY
This unit is equipped with a lead-acid type battery. The battery normally vents small amounts of flammable hydrogen gas. Do not smoke when checking the battery. A battery explosion can cause serious physical harm and/or blindness.
2
62--10601
UNIT IDENTIFICATION
Each unit is identified by a decal attached to the frame of the unit. This decal is on the roadside vertical frame post behind the roadside side door. This decal identifies the complete model number of the unit, the serial number, the refrigerant charge and quantity, and the date the unit was placed in service.
If a problem occurs, please refer to the information on this decal, and make a note of the model andserial number before calling for assistance. This information will be needed when you contact a technician orCarrier TransicoldService Engineer sothat they may properly assist you.
3
62--10601
Unit Identification Decal
4
62--10601
UNIT OPERATION STARTING UNIT - AUTO
FAUL T STAND-BY
START/STOP
FUNCTION
CHANGE
UNIT DAT A
PRETRIP
CHECK
AUTO S/S
CONTINUOUS
MANUAL
DEFROST
ENTER
SETPOINT BOX TEMPERATURE
FAULT
STANDBY
POWER ON
10START/RUN
OFF
STANDBY
ENGINE
88888
88
88
88
888888
88
88
88
88
88
88
88
88
88
8****
FAUL T STAND-BY
START/STOP
FUNCTION
CHANGE
UNIT DAT A
PRETRIP
CHECK
AUTO S/S
CONTINUOUS
MANUAL
DEFROST
ENTER
SETPOINT BOX TEMPERATURE
FAULT
STANDBY
POWER ON
10START/RUN
OFF
STANDBY
ENGINE
----22220000....00003
33
34444....5555°°°°F
FF
F
1. Place the START/RUN - OFF switch to START/RUN position.
DISPLAY
SELF TEST
5
62--10601
The microprocessor controller will run a self test. All of the mode lights will light, all of the segments on the display will be turned on.
The display willthen show the setpoint temperature onthe left and the box temperature of the trailer on the right. The last character (after the degree symbol) shows the temperature units as F (Fahrenheit) or C (Celsius).
If the unit is in Auto Start/Stop mode or Continuous Run/Auto Operation mode, the glow plugs will energize, the buzzer will sound, and the diesel engine will start.
If the unit is set for Continuous Run/Manual Operation mode, the unit must be started manually.
WARNING
Under no circumstances should ether or any other starting aids be used to start engine.
The microprocessor controller monitors box temperature, battery voltage, and engine coolant temperature. Once the setpoint is reached the controller will shut off the diesel engine to conserve fuel. The controller willnot shutoff theengine ifthebatteryvoltage is not sufficient to restart it.
The controller will restart the engine if any of the following criteria have been met:
SBox temperature has changed by ¦ 11°F(¦ 6.1°C)for setpoints in the perishable range and +1 1° F(+6.1°C) for setpoints in the frozen range DURING minimum off time.
SBox temperature has moved away from setpoint by ¦3.6°F (2.0°C) AFTER minimum off time for setpoints in the perishable range or +3.6°F(2.0°C) for setpoints in the frozen range.
SThe battery voltage drops below 11 Vdc (12.2 Vdc for units with EEPROM Rev 3.25 and higher -- Refer to Page 21 for unit data).
SThe engine coolant temperature drops below 34°F(1°C).
6
62--10601
STARTING UNIT - MANUAL (CONTINUOUS RUN ONLY)
FAUL T STAND-BY
FUNCTION CHANGE
UNIT
DAT A
PRETRIP CHECK
AUTO S/S
CONTINUOUS
MANUAL
DEFROST
ENTER
SETPOINT BOX TEMPERATURE
FAULT
STANDBY
POWER ON
10START/RUN
OFF
STANDBY
ENGINE
M
MM
MAAAANNNNO
OO
OPPPP
Side of Control Box
4. Hold GLOW/CRANK switch in the GLOW position for
5 to 15 seconds (see chart on next page). Then hold the GLOW/CRANK switch in the CRANK position for up to 10 seconds to start the diesel engine.
1. Place START/RUN - OFF switch to the START/RUN position. If START/STOP is displayed, press AUTO S/S-CONTINUOUS toggle key to place unit in Continuous Run Mode .
2. Press FUNCTION CHANGE key until AUTO OP or MAN OP is displayed. If MAN OP appears, unit is in manual start mode.
3. If AUTO OP appears, first press ENTER key, then UP or DOWN arrow key until MAN OP is displayed. Press ENTER key to lock in manual mode.
5. With MAN OP selected, press AUTO S/S-CONTINUOUS key to toggle between Auto Start-Stop and Manual Start/Continuous Run modes.
7
62--10601
Glow Time
Engine Coolant Temperature Glow Time in Seconds Engine Coolant Temperature
TV/Short
(Default)
DI/
Long
Less than 32_F(0_C) 15 55 33_Fto50_F(1_Cto10_C) 10 40 51_Fto77_F(11_Cto25_C) 5 25 Greater than 78_F(26_C) 0 10
NOTE: When the unit is inContinuous Run mode and set for Manual Operation, the unit must be started manually
WARNING
Under no circumstances should ether or any other starting aids be used to start engine.
8
62--10601
PRETRIP CHECK 1.
FAUL T ST AND-BY
COOL
FUNCTION
CHANGE
UNIT DAT A
PRETRIP
CHECK
AUTO S/S
CONTINUOUS
MANUAL
DEFROST
ENTER
SETPOINT BOX TEMPERATURE
FAULT
STANDBY
POWER ON
10START/RUN
OFF
STANDBY
ENGINE
PPPPP
PP
PPPPPPPPP
2. Press PRETRIP CHECK key to start PRETRIP. “PPPP” will appear on the display.
1. Start and run unit until box temperature is 40_F(
4.4°C)or
lower.
9
62--10601
The PRETRIP mode is for checking unit operation and evaluating operation of all modes. The unit will cycle thru all modes of operation at30 secondintervals. WhenPretripis complete,Pretrip mode is terminated and the unit returns to normal operation.
The final PRETRIP mode is Defrost. When Defrost ends, PRETRIP will be complete.
This is not a self-diagnosing pretrip test. Nospecific pretrip alarms will be generated. Pretrip must be monitored by the user to verify that the unit operates through all cycles.
See Page 28 for more information on Pretrip.
10
62--10601
CHANGING SETPOINT
FAUL T STAND-BY
FUNCTION
CHANGE
UNIT DAT A
PRETRIP CHECK
AUTO S/S
CONTINUOUS
MANUAL
DEFROST
ENTER
SETPOINT BOX TEMPERATURE
FAULT
STANDBY
POWER ON
10START/RUN
OFF
STANDBY
ENGINE
----22220000....00003
33
34444....5555°°°°F
FF
F
Press ENTER key when desired setpoint is
displayed to lock in new setpoint.
New setpoint will flash and then return to original
setpoint if ENTER key is not pressed.
Press UP arrow key to increase displayed
setpoint.
Press DOWN arrow key to decrease
displayed setpoint.
11
62--10601
Setpoints of -22°Fto+89°F (-30°Cto+32°C) may be entered via the keypad. The controller always retains thelast entered setpoint in memory. If no setpoint is in memory (i.e. on initial startup), the controller will lock out the run relay and flash “SP” on the left hand display until a valid setpoint is entered. The setpoint may be changed up or down in 1° increments by pressing and releasing either the UP ARROW or DOWN ARROW key.
Youcan notchangesetpoint when unit isin Pretripor whenviewing Unit Data or Functional Parameters.
Pressing the ENTER key will cause the new displayed setpoint value tobecome active. If thedisplay is flashing and the newvalue is not entered, after 5 seconds of no keyboard activity, the display will flash for 5 seconds and then revert back to the last setpoint. All other keys are active at this time and may be pushed while the display is flashing.
12
62--10601
START-STOP OPERATION
FAUL T ST AND-BY
START/STOP
FUNCTION CHANGE
UNIT DAT A
PRETRIP
CHECK
AUTO S/S
CONTINUOUS
MANUAL
DEFROST
ENTER
SETPOINT BOX TEMPERATURE
FAULT
STANDBY
POWER ON
10START/RUN
OFF
STANDBY
ENGINE
----22220000....00003
33
34444....5555°°°°F
FF
F
1. Press the AUTO S/S-CONTINUOUS toggle key until START-STOP is displayed. Unit is now in Automatic Start/Stop mode.
START/STOP
Automatic start/stop is provided to permit starting/restartingof the diesel-driven compressor as required. This gives the microprocessor automatic control of starting and stopping the diesel engine. The main function of automatic start-stop is to turn off the refrigeration system near the setpoint to provide a fuel efficient temperature control system and then restart the engine when needed. Start-Stop operation is normally used for frozen loads.Refer toR
ECOMMENDED TRANSPORTTEMPERATURES (SeePage
32).
13
62--10601
The unit will remain in low speed after engine start-up - 5 minutes for XT products, 10 minutes for all others. If the unit fails to start, shuts down on a safety, or fails to run for the minimum run time, three consecutive times, the fault light is on.
Low speed Start--up for low coolant temperatures is available on Configuration7 for allunits except thosewithEEPROM REV3.23 and 3.24 -- Refer to Page 21 for unit data.
The microprocessor controller monitors box temperature, battery voltage, and engine coolant temperature.
Whenever the unit starts in Start--Stop, it will run until:
SIt has run for the predetermined minimum run time. SThe engine coolant temperature is above 122°F(50°C) SThe box temperature is at setpoint.
Thecontrollerwillnot shut offtheengineif thebatteryvoltage isnot sufficient to restart it. Battery voltage above approximately 13.4 volts is required for shutdown. This varies depending on ambient. Look at battery voltage in data list to find out whether shutdown voltage has been reached. If there is a “+” in front of the number , the voltage is enough to shutdown and restart. If only the number appears, the voltage is still too low for shutdown.
The controller will restart the engine if any of the following criteria have been met:
SBox temperature has changed by ¦ 11°F(¦ 6.1°C)for setpoints in the perishable range and +1 1° F(+6.1°C) for setpoints in the frozen range DURING minimum off time.
SBox temperature has moved away from setpoint by ¦3.6°F (2.0°C) AFTER minimum off time for setpoints in the perishable range or +0.5°F(0.3°C) for setpoints in the frozen range.
SThe battery voltage drops below 11 Vdc (12.2 Vdc for units with EEPROM Rev 3.25 and higher -- Refer to Page 21 for unit data).
SThe engine coolant temperature drops below 34°F(1°C).
14
62--10601
CONTINUOUS RUN OPERATION
FAUL T STAND-BY
FUNCTION CHANGE
UNIT DAT A
PRETRIP
CHECK
AUTO S/S
CONTINUOUS
MANUAL
DEFROST
ENTER
SETPOINT BOX TEMPERATURE
FAULT
STANDBY
POWER ON
10START/RUN
OFF
STANDBY
ENGINE
----22220000....00003
33
34444....5555°°°°F
FF
F
START/STOP Must Not Be Displayed
1. Check if START-STOP is displayed. If it
is, press the AUTO S/S-CONTINUOUS toggle key to place unit in Continuous Run mode.
15
62--10601
In the Continuous Run mode, the diesel engine will run continuously providing constant air flowandtemperature controlto the product. Continuous Run operation is normally used for perishableloads. RefertoR
ECOMMENDED TRANSPORTTEMPERATURES
(See Page 32). Start-Stop and Continuous operation may be tied to the setpoint
ranges for frozen and perishable loads and the START-STOP/CONTINUOUS key may be locked out.
The unit will remain in low speed - 5 minutes for XT products, 10 minutes for all others, after engine start-up when the Continuous Run setpoint is below 10°F (-12°C).
16
62--10601
MANUAL DEFROST
FAUL T ST AND-BY
DEFROST
FUNCTION
CHANGE
UNIT
DAT A
PRETRIP
CHECK
AUTO S/S
CONTINUOUS
MANUAL DEFROST
ENTER
SETPOINT BOX TEMPERATURE
FAULT
STANDBY
POWER ON
10START/RUN
OFF
STANDBY
ENGINE
----22220000....00003
33
34444....5555°°°°F
FF
F
DEFROST Indicator
2. Press the MANUAL DEFROST key to
initiate Manual Defrost.
1. Check that box temperature is 40_F(
4.4°C)orlower.
NOTE: Defrost cannot be started when the Evaporator Coil temperature is above 40°F(4.4°C).
17
62--10601
The defrost mode may be initiated in three different ways if the evaporator coil is below 40°F(4.4°C):
1. Defrost is initiated automatically at preset intervals by the defrost timer in the microprocessor.
2. Defrost is initiated by the defrost air switch.
3. The defrost mode may be manually initiated by pressing the Manual Defrost Key.
The defrost mode terminates when the evaporator temperature is higher than 55°F (12.8°C). Should the defrost cycle not complete within 45 minutes, the defrost cycle is terminated.
After the 45 minute termination, the controller will wait 1.5 hours before attempting another defrost cycle. Pressing the manual defrost key will override this mode and start a defrost cycle.
If a shutdown alarm occurs, defrost will be terminated.
18
62--10601
FUNCTION CHANGE (PARAMETERS)
FAUL T STAND-BY
DEFROST
FUNCTION
CHANGE
UNIT
DAT A
PRETRIP CHECK
AUTO S/S
CONTINUOUS
MANUAL
DEFROST
ENTER
SETPOINT BOX TEMPERATURE
FAULT
STANDBY
POWER ON
10START/RUN
OFF
STANDBY
ENGINE
2. Press ENTER key.
3. Press either UP or DOWN ARROW key
until desired Function setting is displayed.
4. Press the ENTER key to lock in new setting.
1. Press FUNCTION CHANGE key until
Function to be changed is displayed.
DDDDEEEEFFFFRRRR1
11
12222....0000HHHH
NOTE: Function changes will change operation
of unit.
NOTE:If configurationCNF11is“ON” functional parameters are locked. The ability to change any functional parameters is disabled.
19
62--10601
FUNCTION CHANGE (PARAMETERS)
The following table has columns for Code and English displays. English is the default setting. Change Functional Parameter to Code to see Code display format.
Function Codes
CODE ENGLISH DATA
FN0 DEFR Defrost Time Interval FN1 ON HIGH AIR High Air Flow FN1 OFF NORM AIR Normal Air Flow FN2 OFF T Minimum Off-time FN3 ON T Minimum On-time
FN4 A
REM
PROBE
Controlling Probe ­Return Air
FN4 B
SUP
PROBE
Dual Controlling Probe ­Return and Supply Air
FN5
Degrees
ForC
Temperature Unit
Displayed in _Cor_F
FN6 ON
TIME
STRT
Maximum Off-Time 30 Min
FN6 OFF
TEMP
STRT
Temperature and Minimum Off-Time Based Restarting For AutoStart/
Stop FN7 MOP STD Unloader Control FN10 ON AUTO OP Auto Start Operation FN10 OFF MAN OP Manual Start Operation FN11 TRANGE Out-of-Range Tolerance Code vs English = Code or English display format Manual Glow Override = Normal or Add 30sec Alarm Reset = Alarm Reset or No Alarms
20
62--10601
UNIT DATA
FAUL T ST AND-BY
COOL
FUNCTION
CHANGE
UNIT DAT A
PRETRIP CHECK
AUTO S/S
CONTINUOUS
MANUAL
DEFROST
ENTER
SETPOINT BOX TEMPERATURE
FAULT
STANDBY
POWER ON
10START/RUN
OFF
STANDBY
ENGINE
ssssuuuucccctttt2
22
25555PPPP
2. To scroll through the list faster, use the UPorDOWN ARROW keys.
4. Press the ENTER key to display data for 30 seconds.
1.Press UNIT DATA key to scroll thru data list one item at a time.
3. Data will display for 5 seconds
21
62--10601
UNIT DATA
The following table has columns for Code and English displays. English is the default setting. Change Functional Parameter to Code to see Code display format.
Unit Data Codes
CODE ENGLISH DATA
CD1 SUCT Suction Pressure CD2 ENG Engine Hours CD3 WT CoolantTemperature
CD4 RAS Return Air Temperature *CD5 SAS Supply Air Temperature *CD6 REM Remote Air Temperature
CD7 ATS Ambient Air Temperature
CD8 -- -- -- Door Open/Closed
CD9 CDT Discharge Temperature
CD10 BATT Battery Voltage CD11 SBY Standby Hours CD12 MOD V Future Expansion CD13 REV Software Revision CD14 SERL Serial Number Lower CD15 SERU Serial Number Upper CD18 MHR1 Maintenance Hour Meter 1 CD19 MHR2 Maintenance Hour Meter 2 CD20 SON Switch On Hour Meter
* Codes 5 & 6 are variable. SAS is displayed when the SUP Probe Function is selected. REM is dis­played when the REM Probe Function is selected.
(See Functional Parameter List on Page 19.)
22
62--10601
ALARM DISPLAY & RESET ALARM DISPLAY
When an alarm is on, normal display of Setpoint/Box Temperature alternates with alarm display.
When fault light is on, check display for alarm message.
ALARM RESET
FAUL T ST AND-BY
COOL
FUNCTION
CHANGE
UNIT DAT A
PRETRIP CHECK
AUTO S/S
CONTINUOUS
MANUAL
DEFROST
ENTER
SETPOINT BOX TEMPERATURE
FAULT
STANDBY
POWER ON
10START/RUN
OFF
STANDBY
ENGINE
EEEENNNNGGGGO
OO
OIIIILLLL
1. Press FUNCTION CHANGE key.
3. Press ENTER to clear alarm. ALARM
CLR will be displayed. (Unit will restart if alarm condition has been corrected and unit is in Start/Stop or Auto OP).
2. Press UP/DOWN arrow key until ALARM RST is displayed.
FAULT LIGHT
ALTERNATE ALARM RESET
Place START/RUN-OFF switch to OFF position. (Unit can now be restarted after alarm condition has been corrected).
23
62--10601
The following table has columns for Code and English displays. English is the default setting. Change Functional Parameter to Code to see Code display format.
Display
CODE ENGLISH ALARM DESCRIPTION
AL0 ENG OIL Low Oil Pressure AL1 ENG HOT
High Coolant
Temperature AL2 HI PRESS High Pressure AL3 STARTFAIL Auto Start Failure AL4 LOW BATT Low Battery Voltage AL5 HI BA TT High Battery Voltage AL6 DEFR FAIL Defrost Override AL7 ALT AUX Alternator Not Charging AL8 STARTER Starter Motor AL9 RA SENSOR Return Air Sensor
AL10 SA SENSOR Supply Air Sensor AL11 WT SENSOR
Coolant Temperature Sensor
AL12 HIGH CDT
High Discharge
Temperature
AL13 CD SENSOR
Compressor Discharge Temperature Sensor
AL14 SBY MOTOR Standby Motor Overload
(NDM Only)
AL15 FUSE BAD Fuse Blown Or Dirty
Battery Cables
AL16 SYSTEM CK
Check Refrigeration
System
AL17 DISPLAY Display AL18 SERVICE 1 Maintenance Hour Meter 1 AL19 SERVICE 2 Maintenance Hour Meter 2 AL20 OUT RANGE Out-of-range
= FAULT LIGHT ON
24
62--10601
STANDBY OPERATION
FAUL T STAND-BY
COOL
FUNCTION
CHANGE
UNIT DAT A
PRETRIP CHECK
AUTO S/S
CONTINUOUS
MANUAL DEFROST
ENTER
SETPOINT BOX TEMPERATURE
----22220000....00003
33
34444....5555°°°°F
FF
F
3. Place ENGINE/STANDBY switch in STANDBY position.
2. Plug in power supply.
1. Place ST ART/RUN-OFF switch in OFF
position
For units equipped with electric standby:
4. Place START/RUN-OFF switch in ST ART/RUN position.
FAULT
STANDBY
POWER ON
10START/RUN
OFF
STANDBY
ENGINE
WARNING
Make sure the power plugs are clean and dry before connec­tor to any power receptacle.
25
62--10601
Standby Operation is for Ultra NDM units only. Checkfor propermotor rotation. Condenser air mustbe drawninto
unit. To reverse rotation, stop unit, disconnect power cord and change polarity of plug.
26
62--10601
STOPPING UNIT
FAUL T STAND-BY
FUNCTION
CHANGE
UNIT
DAT A
PRETRIP CHECK
AUTO S/S
CONTINUOUS
MANUAL
DEFROST
ENTER
SETPOINT BOX TEMPERATURE
FAULT
STANDBY
POWER ON
10START/RUN
OFF
STANDBY
ENGINE
1. To stop the unit, place the START/RUN - OFF switch to OFF position.
----22220000....00003
33
34444....5555°°°°F
FF
F
COOL
27
62--10601
The diesel engine will stop and the microprocessor controller will turn off.
28
62--10601
PRE-TRIP INSPECTION
The pre-trip inspection should be performed before picking up any load.Thisinspectionisessentialtoanticipateandhelpminimizethe possibility of “over-the-road” problems. These checks take only a few minutes.
1. Place the unit’s main switch in the STOP (0) position.
2. Fuel - drain any water and impurities from the sump of the
refrigerationunitfuel tankbyopeningthedrain-cock locatedon the bottom of the tank (if so equipped). Close the valve when only pure fuel emerges. Check the fuel level in the tank, ensuring that the fuel supply is adequate for unit operation. Refuelif necessary.Disposeof fuelproperly.Don’t drainwaste fuel onto ground.
3. Belts -Check thebelt tensionby depressingthe beltwith your thumb, near the center of the longest free run of each belt. Under moderate pressure each belt should deflect approximately 1/4 inchto 1/2 inch(5 mm to 15mm). If thebelts deflectmorethanthis theyshouldbe tightened(loosebeltsmay slip, generating heat andreducing belt life). If the belts are too tight they should be loosened; tight belts can reduce bearing life.
4. Battery - on unit equipped with serviceable batteries, the level of the electrolyte in each of the cells should bechecked. If the level is low ,distilled watershould beadded tothe correctlevel. Most units,however,areequipped withlowor no-maintenance batteries; these should be inspected to ensure that the connections are clean and tight, and the battery hold-down should be checked for tightness.
5. Engine Oil - the engine oil should be checked last since it is
necessary for oil to drain out of the block andinto the oil panto obtain a correct reading. Unscrew and remove the dipstick. Wipe the dipstick clean and insert it into the oil fill tube without threading it alltheway back intothe tube. Remove thedipstick again and check oil level. DO NOT add oil if the level is in the “safe” range. If needed, add oil as indicated by markings on dipstick until level is in the “safe” range. (See page 35).
29
62--10601
6. Over-all Unit - visually inspect the entire unit for leaks, loose bolts, frayed, loose, or broken wires, etc. The radiator/condenser coils of theunit shouldbe freeof dirt,bugs, cardboard, orany otherdebristhat mayobstruct airflow across the coils. The evaporator (located inside the trailer) should be free of debrisalso,especially stretch-wrap, whichis oftenused during transport to prevent cargo shifting.
7. Start a Pretrip Check (See Page 8). The unit will cycle thru all modesofoperationat30secondintervals, andreturntonormal operation when complete. Monitor Pretrip and watch/listen for unusual operation or noises.
30
62--10601
PRODUCT LOADING
BEFORE LOADING:
D Pre-cool the trailer. This will remove much of the heat from the
inside of the trailer,and givethe product better protection when it is loaded.
D If possible, placethe unit in a defrost cycle immediately before
loading. This will remove moisture accumulated on the evaporator coil.
DURING LOADING:
D Turn the unit off! D Check product temperature during loading. D Ensure that the air return and supply opening remain
unobstructed.
D Leave approximately 4 to 5 inches (10 to 12 cm) between the
load and the front wall for air return to the unit.
D Leave at least 10to 12 inches (25 to 30 cm) between the top of
theload and theceilingto ensure thatthereisnothingtoprevent airflow to the rear of the body
D Load product on pallets to provide free air return to unit and
improve product protection.
Proper air circulation in the trailer, air that can move around and through theload, isa critical elementin maintainingproduct quality during transport. If aircannot circulate completely aroundthe load, hot spots or top-freeze can occur.
The use of pallets is highly recommended. Pallets, when loaded so air can flow freely through the pallets to return to the evaporator, help protect the product from heat passing through the floor of the trailer. When usingpallets, it isimportant to refrain from stacking extra boxes on the floor at the rear of the trailer, this will cut off the airflow.
31
62--10601
Product stacking is another important factor in protecting the product. Products that generate heat - fruits and vegetables, for example-should bestackedsotheaircanflowthrough theproduct to remove the heat; this is called “air stacking” the product. Products that do not create heat - meats and frozen products ­should be stacked tightly in the center of the trailer. All products shouldbekept away fromtheside-wallsof the body,toallowairflow between the body and the load; this preventsheat filteringthrough the walls from affecting the product.
It is importantto checkthetemperatureof theproduct being loaded to ensure that it is at the correct temperature for transport. The refrigeration unit is designed to maintain the temperature of the product at the temperature at which it was loaded; it was not designed to cool warm product.
32
62--10601
RECOMMENDED TRANSPORT TEMPERATURES
Below are some general recommendations on product transport temperaturesandoperating modesfor the unit.These areincluded for reference only and should not be considered preemptive of the setpoint required by the shipper or receiver.
More detailed information can be obtained from your Carrier Transicold dealer.
Setpoint Range
Prod
uct
°
°°
°F °°°°C
O
peratingMode
1
Bananas 56 to 58 13 to 14 Continuous Fresh fruits and
vegetables
33 to 38 0.5to3 Continuous
Fresh meats and seafood
28 to 32 -2 to 0
Auto-Start/Stop or
Continuous
Dairy Products 33 to 38 0.5to3
Auto-Start/Stop or
Continuous
Ice 15 to 20 -10to-7 Auto-Start/Stop
2
Frozen fruits and vegetables
-10to0 -23to-18 Auto-Start/Stop
2
Frozen meats and seafood
-10to0 -23to-18 Auto-Start/Stop
2
Ice Cream -20to-15 -29to-26 Auto-Start/Stop
2
1
During delivery cycles that include frequent stops and door openings,itisrecommended thattheunitalways beoperated inthe continuous runmode tohelp insure productquality. Ifit is possible, the unit should be turned off during the time the trailer doors are open to help conserve the product temperature.
2
Variations may be necessary for very high or very low ambient
temperatures.
2.
33
62--10601
PROBLEMS
Everything possible has been done to ensure that your unit is the most reliable, trouble-free equipment available today. If, however you run into problems the following section may be of assistance.
If you do not find the trouble that you have experienced listed, please call your Carrier Transicold dealer for assistance.
General Problems
Unit won’t c rank. Check battery condition.
Check battery connections. Check allfuses
Unit won’t start. Check fuel level.
Check allfuses Check fuel system forloss of prime (See Page 39)
Unit won’t run. Check fuel level.
Check engine oil level. Check allfuses
Unit stops operating. Check belts.
Check engine oil level. Check coolantlevel. Check fuellevel. Check all fuses.
Unit not cooling properly. Defrost unit.
Check evaporator for airflow restriction. Check condenser for airflow restriction. Check body for damage or air leaks.
34
62--10601
FUSES
The fuses that protect the circuits of the Microprocessor control system are located in the control box on the roadside of the unit. They may be accessed by loosening the screws that hold the control box cover closed. The cover can be removed and hung below the control box by its tethers as shown below .
F1
Fuse Purpose Amps
F1 glow plug & starter solenoid 80A F2 fuel heater (optional) 20A F4 speed control solenoid & front unloader 15A
F5
auto restart, out of range lights
and SV3 (if equipped)
7.5A
F6 fault light and DataLink (if equipped) 5A F9 Microprocessor 5A
F11 fuel solenoid, clutch & defrost light 10A
F12
SV1, SV2, SV4, heat & cool lights &
rear unloader
10A
35
62--10601
UNIT MAINTENANCE 3.
Engine oil - the oils recommended for use inyour refrigeration unit must comply with the American Petroleum Institute’s (API) CI or higher rating or Mobil Delvac 1synthetic oil. The use ofany oilthat does not meet this rating may affect the warranty on the engine in the unit. The use of oil of the proper weight (viscosity) is also essential. The following chart indicates the SAE Weight Rating of the oil to be used in various climates:
°F
-20 -10 0 10 20 30 40 50 60 70 80 90 100
30W, 10W-30, or 15W-40
10W-30, or 15W-40
0W-20, or 5W-30
°C
-28 -23 -17 12 -7 -1 -4 10 16 21 27 32 38
30W, 10W-30, or 15W-40
10W-30, or 15W-40
0W-20, or 5W-30
T o check the engine oil level: Run the unit to bring the engine up to operating temperature, shut the unit off, and unscrew the cap/dipstick. Wipe the dipstick clean and insert it into the oil fill tube without
threading it all the way back into the tube. Remove the dipstick again and check oil level. DO NOT add oil if the level is in the “safe” range. If needed, add oil as indicated by markings on dipstick until level is in the “safe” range.
QTS
1 2 SAFE
Cap Dipstick
36
62--10601
UNIT MAINTENANCE SCHEDULE
For the most reliable operation and for maximum life, your unit requires regular maintenance. This includes oil and filter changes, fuel and air filter replacement, coolant replacement. Maintenance should be performed on the following schedule:
SERVICE
Every 1500 Hours (TV engine)
Every 2000 Hours (DI engine)
Yearly (ALL engines)
D Drain the engine oil and replace oil filter.*
D Check engine cooling system. D Check air cleaner. D Check all bolts, screws and unit mounting
bolts for tightness. Tighten as required.
D Check all belts. D Replace fuelfilter. D Clean fuelpump filter. D Check battery terminals and fluid level. D Check compressor oil level. D Check alternatorbrushes. D Check engine thermostat. D Check defrost:
- Check defrost air switch calibration
- Check timersetting and function
- Check refrigerant control valves
- Defrost ends automatically
- Water drains from evaporator
D Clean radiator/condenser. D Check engine speed under load D Pre-Trip Inspection.
Every 3000 Hours D Check alternator.
D Clean and adjust fuel injectors. D Clean crankcase breather. D Pre-Trip Inspection.
Every 6000 hours D Change anti-freeze.**
D Check and adjust rocker arms. D Pre-Trip Inspection.
37
62--10601
*Engine Service Information
Oil & Filter Change
Interval
Eng. Type
Std. Oil
Filter
ESI Oil
Filter
API
Class
CG or
Higher
Mobil Delvac1
30-00450-00
2000hrs/
1yr
4000 hrs/ 2 yrs***
DI
30-00463-00
3000
hrs/
2yrs.
4000 hrs/ 2yrs
30-00450-00
1500
hrs/1 yr
3000 hrs/ 2 yrs***
T
V
30-00463-00
3000 hrs/
2yrs
4000 hrs/ 2yrs.
Cooling System Service Interval
Standard Coolant
6000 hrs/2 yrs
Extended Life Cool-
ant
12000 hrs/5 yrs
Eng. Oil Type: API Class CI or higher or Mobil Delvac 1 Engine OIl Viscosity: SAE 15W40 or 10W-30 Engine Oil Capacity: 15 quarts Engine Coolant Mixture: 50/50 Engine Coolant Capacity: 8 quarts
These maintenance schedules are based on the use of approved oilsandregular Pre-Tripinspectionsof theunit. Failuretofollowthe recommended maintenance schedule may affect the life and reliability of the refrigeration unit.
**12,000 hours with Texaco (Havoline) extended life coolant. ***New oil filter required at 1 year interval.
38
62--10601
In addition to theabove service requirements pleaseadhere to the following:
S Non-synthetic engine oil should be changed at least once
per year and synthetic engine oil should be changed at least once every 2 years, even if the engine has not run the necessary number of hours.
S Standard coolant (anti-freeze) should be replaced every
two years. Extended life coolant should be replaced every five years.
A more detailed description of service requirements and procedures canbe foundin theServiceandOperations Manual for yourunit.Thismanualmay beobtained fromanyCarrierTransicold dealer.
39
62--10601
PRIMING FUEL SYSTEM
The mechanical fuel lift pump is mounted onthe enginenext to the injectionpump.Thispumphasamanualplunger forprimingthefuel system when the fuel tank has been run dry.
To prime the fuel system, use the following steps:
1. Turn the bleed valve (Red) counter-clockwise until fully opened.
2. Turn the top of the manual fuel pump plunger counter-clockwise to unlock it. S-L-O-W-L-Y (up/down once per second) pump the manual plunger until positive pressure (resistance) is felt. This may take up to 200 strokes. This will indicate fuel flow.
3. Continue to pump S-L-O-W-L-Y (up/down once per second) approximately 100 morestrokestofill thefilterandbleedtheair out of the lines.
4. Start engine.It may be necessary tocontinue topumpuntil the engine starts.
5. Depress and turn the top of the manual plunger clockwise to lock in place.
6. When engine is running smoothly, turn bleed valve clockwise
until fully closed.
Manual Fuel Pump Plunger
Red Fuel Bleed Valve
40
62--10601
EMERGENCY ROAD SERVICE
At Carrier Transicold we’re working hard to give you complete service when and where you need it. That means a worldwide network of dealers that offer 24-hour emergency service. These service centers are manned by factory trained service personnel and backed by extensive parts inventories that will assure you of prompt repair.
Should you experience a unit problem with your refrigeration unit during transit, follow your company’s emergency procedure or contact the nearest Carrier Transicold service center. Consult the Shortstop Service Centers directory to locate the service center nearest you. This directory may be obtained from your Carrier Transicold dealer.
SSSS If you are u n able t o reach a service center,
call our 24-hour Action Line: (800)448-1661
When calling, please have the following information ready for fastest service:
S Y our name, the name of your company, and your location. S A telephone number where you can be called back. S Refrigeration unit model number and serial number. S Box temperature, setpoint and product.
Brief description ofthe problemyou are having,andwhat youhave already done to correct the problem.
Wewill doeverything wecan toget your problem takencare ofand get you back on the road.
2005 Carrier Corporation D Printed in U. S. A. 0505
Carrier Transicold Division, Carrier Corporation Truck/Trailer Products Group P.O. Box 4805 Syracuse, N.Y. 13221 U.S A
www .carrier.transicold.com
North America
Carrier Transicold 700 Olympic Drive Athens, GA 30601 USA Tel: 1--706--546--6469 Fax: 1--706--546--5207
Central America and Mexico
Ejercito Nacional No. 418 Piso 9, Torre Yumal Col. Chapultepec Morales 11570 Mexico, D.F. Tel: (5255) 9126.0300 Fax: (5255) 9126.0373
A member of the United T echnologies Corporation family. Stock symbol UTX
CALIFORNIA
Proposition 65 Warning
Diesel engine exhaust and some of its constituents are known to the State of California to cause cancer, birth defects, and other reproductive harm.
Loading...